PF 3100 ION PILOT CARD PRO.FIRE

Size: px
Start display at page:

Download "PF 3100 ION PILOT CARD PRO.FIRE"

Transcription

1 PF 3100 ION PILOT CARD PRO.FIRE 1

2

3 TABLE OF CONTENTS PF3100 ION PILOT CARD INFORMATION GUIDE INTRODUCTION Functional Description System Requirements HARDWARE Card Specifications Card Diagram Terminal Specifications Terminal Descriptions Enclosure Specifications Enclosure Diagram Enclosure Ports CONTROLS AND DIAGNOSTICS Ports LEDs and Buttons Important Safety Information APPENDIX A: NETWORK TERMINOLOGY All content is subject to copyright and may not be reproduced in any form without the express written consent of the author Profire Energy. All rights reserved. All the information described in this document is as is, without warranty of any kind and is published in good faith and for general information purposes only. Profire does not make any guarantees about the completeness, reliability and accuracy of this information. Profire may make changes in this manual or in the product(s) described in this manual at any time. Contact your Profire Sales representative for questions, comments or further assistance PRO.FIRE DOC A 3

4 INTRODUCTION 1.1 Functional Description The PF3100 Ion Pilot card is used to generate a spark to ignite a pilot burner and to detect the flame of both a pilot and main burner. This card is powered through the PFRN network via a Controller class or Network class card (typically a BMS Controller card or a Network Switch Card). 1.2 System Requirements Specific system requirements will vary according to which Controller class card is connected to the Ion Pilot card. For additional information, refer to the Hardware Guide corresponding to the Controller type card (e.g., BMS Controller card) specific to your application. IGNITION COIL WIRING The Ion Pilot card is usually sold in a Class I, Div 1 / Zone 1 explosion proof enclosure (EPX) which also includes an ignition coil. This allows the ignition and flame monitoring to be located close to the associated burner which reduces the need for long ignition wires. Internal Ignition Coil Ignition Wire 10 Ignition Rod Ion + Coil + Coil - Red White Black WIRE REQUIREMENTS WIRE LOCATION CONNECTION DESCRIPTION WIRE TYPE AND MIN GAUGE MAX LENGTH 5 Board to Main Flame Detect Rod 10 Coil to Pilot Ignition Rod 7 mm ignition wire 7 Board to Burner 14 AWG 6 Board to Pilot Flame Detect (Dual Rod Pilot only) 7 mm ignition wire Each wire should be limited to 25 ft maximum 7 mm ignition wire 4

5 SINGLE VS DUAL ROD PILOT WIRING Use the single rod pilot configuration when using a single rod for flame detection and pilot ignition. Use the dual rod configuration when using two separate rods for pilot ignition and flame detection. Single Rod Pilot Coil { + EGND Ion Ignition Coil 10 Straight Silicone Boot Ferrule Pilot Ignition and Flame Detect Rod Main Ion + 5 Straight Silicone Boot Ferrule Main Flame Detect Rod Dual Rod Pilot Coil { + EGND Ion Ignition Coil 10 Straight Silicone Boot Ferrule Pilot Ignition Rod Straight Silicone Boot Ferrule Pilot Flame Detect Rod Main Ion + 5 Straight Silicone Boot Ferrule Main Flame Detect Rod 5

6 HARDWARE 2.1 Card Specifications TYPE Model Number PFRN Class PFRN Power PFRN Ports Voltage Input Inputs Outputs SPECIFICATIONS PF IO Power Consumer 1 PFRN IO Network Port Powered via PFRN Power: EGND LEL In, Main Ion, Pilot Ion Pilot Valve, Coil 2.2 Card Diagram 6

7 2.3 Terminal Specifications This table provides connection details and a brief description of each terminal. TERMINAL EXPECTED CONNECTIONS INPUT/OUTPUT SAFETY RATED Main Ion + Connect to main flame rod. Flame Ionization Input Yes Ion + Coil + Coil - For a Dual Rod configuration, connect to the pilot flame rod. For a Single Rod configuration, connect to the Ion+ Terminal of the coil (red wire). Connect to the primary winding of the ignition coil. (white wire) Connect to the primary winding of the ignition coil. (black wire) Flame Ionization Input Coil Drive Output LEL In + Connect to an external LEL 12/24 VDC Power Output Yes LEL In - sensor (4-20 ma or Dry). Digital / 4-20 ma Input Yes Valve + Valve - Connect to Pilot Valve terminal 1. Connect to Pilot Valve terminal 2. Do not connect to ground. Powered Output EGND Earth Ground Ground N/A Yes Yes Yes Yes Yes 2.4 Terminal Descriptions MAIN ION, PILOT ION Connect each of these inputs to a Kanthal flame rod placed directly in the pilot/main flame. The pilot and main nozzles must be grounded for the flame detection to function properly. These inputs are protected from high voltage and can be connected in series with the high voltage terminals of an external ignition coil, allowing a single flame-rod to be used for both pilot ignition and pilot flame detection. A 65 VAC signal is applied to the flame rod. The source impedance is very high so there is no danger of sparking during detection. COIL The primary of the ignition coil should be connected to these terminals. A 12 V pulsed DC signal is applied by the card to the coil. This output is protected by a 250 ma thermal fuse. LEL IN This input can be connected to an optional LEL sensor to detect explosive gas concentrations in the burner housing. The input can be configured in software to be disabled, to require an LEL switch, or to require an LEL 4-20 ma transmitter. The system will not start if the contact is open or the 4-20 ma LEL input is above the trip point. 7

8 VALVE Solenoid valves must be connected between the + and - terminals. The negative terminal is not directly connected to ground. This output is driven by 12 V and will only work with 12 V valves. EGND This terminal must be connected to the same ground as the pilot and main burner assemblies. Modules come pre-wired with a connection to the enclosure ground lug. 2.5 Enclosure Specifications The Ion Pilot card is mounted in the EPX enclosure. SPECIFICATIONS Dimensions EPX ENCLOSURE Top Width 11.7 cm (4.61 in) Base Width 16.8 cm (6.63 in) Height 21.7 cm (8.53 in) Depth 13.3 cm (5.25 in) Hazloc Rating Class I, Div 1, GRP BCD, Type 4X; Class I, Zone 1, AEx d IIB + H2 T6 Gb; Ex db IIB+H2 T6 Gb, IECEx Mounting Enclosure Construction Channel Bar or Direct Mount Aluminum Operating Temperature -40 C to 60 C Storage Temperature -40 C to 60 C Standards: Complies with IEC :2011, 6th Edition and IEC :2014, 7th Edition 8

9 2.6 Enclosure Diagram Enclosure options compatible with this card include the EPX enclosure. Port 3 Port 4 (not shown) Port 2 Port 1 All ports are ¾-14 NPT and must have appropriate pipe fittings or plugs installed. A minimum of 5 threads must be engaged in each port to maintain Div 1 / Zone 1 ratings. 9

10 CONTROLS AND DIAGNOSTICS The following is a list of all of the user interface items on the Ion Pilot card. 3.1 Ports PFRN PORTS 1 PFRN IO Network Port This port is classified as an IO class port and is also the port through which the card is powered. See the Card Diagram for the port location. 3.2 LEDs and Buttons POWER LED A Power LED is located next to the PFRN port indicating whether the port is receiving power from the network. INDICATION COLOR STATE Off - Port is not powered On Blue Port is powered LINK LED A link LED is located next to the PFRN port indicating traffic on the PFRN port. INDICATION COLOR STATE Off - PFRN network is not available On Green PFRN network is ready for communication Blinking Green Indicates that network traffic is going through the link FAULT LED ERRORS* A bank of Fault LEDs corresponds to the state of a specific input or output as noted below. INPUT/OUTPUT COLOR ERROR Pilot Red Wiring error. Reporting as open, grounded, etc. Main Red Wiring error. Reporting as open, grounded, etc. Coil Red Fault in ignition. LEL Red Fault in LEL wiring / signaling. *If one of these lines is not required for the application and is left unused, a fault will be present but the system will still be functional. 10

11 3.3 Important Safety Information Before installing the PF3100 Ion Pilot card, please review the following list of warnings. Failure to observe the following may result in death, electrocution, property damage, product damage, and/or government fines. WARNING: EXPLOSION HAZARD Do not disconnect while circuit is live unless area is known to be non-hazardous or equivalent. Substitution of components may impair suitability for specified zones. Do not service unless area is known to be non-hazardous. Do not open enclosure while energized. Installation and use must conform to the provided installation instructions. System must be properly connected to earth-ground for effective operation of flame detection circuitry. Electrical devices connected to the controller must meet certain electrical standards and be within voltage limits. INSTALLATION WARNINGS Failure to properly ground the pilot assembly back to the PF3100 Ion Pilot Module s EGND terminal may result in accidental electric shock, product damage, failure to ignite the pilot, or failure to detect flame. The PF3100 Ion Pilot Module generates 20 kv - 40 kv at the high voltage output terminal of the ignition coil which can cause cardiac arrest. Do not touch or place any object near the ignition coil s high voltage terminal or connected ignition wire while the product is operating. Even without making physical contact with the terminal, it is possible to draw a spark from several inches away, especially if the pilot bracket is not properly grounded. Make sure that the enclosures are securely closed each time after opening. To properly close the enclosure, the lid must be fully threaded on and the set screw tightened. This protects the internal circuitry from moisture damage and other environmental concerns. Moisture damage is not covered by the product warranty. To properly close the enclosure, the lid must be fully threaded on and the set screw tightened. 11

12 Do not drill holes in or otherwise modify the EPX enclosure. Any such modifications will compromise suitability for Class I, Div 1/Zone 1. The flame rods are not intended to be installed and mounted in a Class I, Division 1 or Division 2 hazardous location. Routing and installation of the flame rods shall be in accordance with the Canadian Electrical Code or National Electrical Code as per local requirements. Unused 3/4 NPT conduit ports must be plugged using appropriately rated pipe plugs in order to maintain the Div 1 / Zone 1 rating of the enclosure. Refer to the Canadian Electrical Code or National Electrical Code as applicable. APPENDIX A: NETWORK TERMINOLOGY The following terms are used to explain the network operations: Interface Class Card - Any PF3100 card that provides a control or monitoring interface to a user or remote PLC. Examples include the User Interface card and the Modbus card. Controller Class Card - Any PF3100 card that provides safety control for a specific application. Examples include the BMS Controller card and Combustor Controller card. Network Class Card - Any PF3100 card that provides multiple network ports so that additional cards may be connected together on the PFRN network. Examples include the Network Switch card, Modbus card, and the BMS Controller card. IO Class Card - Any PF3100 card that provides input and output terminals for control and monitoring. Examples include the Ion Pilot card and the Thermocouple card. PFRN - Profire Reliability Network. A proprietary safety network developed by Profire which can also be used to distribute power. The PFRN has two sub-networks: the Controller Network and the IO Network. Controller Network - A sub-network of PFRN Interface class and Controller class cards talk to each other on this network. There is usually only one of these networks in an installation. IO Network - A sub-network of PFRN IO class card talk to a single Controller class card. There is one of these networks for each Controller class card in the system. 12

13 13

14 PROFIRE 14

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

REV INSTALLATION GUIDE BURNER MANAGEMENT SYSTEM

REV INSTALLATION GUIDE BURNER MANAGEMENT SYSTEM REV 2.5 2100 INSTALLATION GUIDE BURNER MANAGEMENT SYSTEM IMPORTANT SAFETY INFORMATION! THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1, DIVISION 2, GROUPS ABCD OR NON-HAZARDOUS LOCATIONS ONLY. WARNING: EXPLOSION

More information

PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER

PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER Cautions WARNING: EXPLOSION HAZARD- -DO NOT SERVICE UNLESS AREA IS KNOWN TO BE NON- HAZARDOUS -DO NOT OPEN WHEN ENERGIZED EXPLOSION HAZARD- -SUBSTITUTION

More information

TABLE OF CONTENTS 1 INTRODUCTION 4 SYSTEM BEHAVIOR 5 EXPANSION CARDS 6 TROUBLESHOOTING 2 INSTALLATION 3 USER INTERFACE & SETTINGS APPENDICES

TABLE OF CONTENTS 1 INTRODUCTION 4 SYSTEM BEHAVIOR 5 EXPANSION CARDS 6 TROUBLESHOOTING 2 INSTALLATION 3 USER INTERFACE & SETTINGS APPENDICES PF2100 USER MANUAL TABLE OF CONTENTS PF2100 MANUAL V2.32 1 INTRODUCTION 1.1 Important Safety Information 1.2 HW & FW Versioning 1.3 Approvals 1.4 Available Models 1.5 Included Components 1.6 Common Applications

More information

REV 1.7 PROFIRE 2100 MANUAL BURNER MANAGEMENT SYSTEM

REV 1.7 PROFIRE 2100 MANUAL BURNER MANAGEMENT SYSTEM REV 1.7 PROFIRE 2100 MANUAL BURNER MANAGEMENT SYSTEM WARNING THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1, DIVISION 2, GROUPS ABCD OR NON-HAZARDOUS LOCATIONS ONLY. WARNING: EXPLOSION HAZARD DO NOT DISCONNECT

More information

Figure 1 Figure 2 Double Acting Actuator Spring Return Actuator

Figure 1 Figure 2 Double Acting Actuator Spring Return Actuator ACCORD CONTROLS Aviator II Valve Controller Installation Operation Maintenance FCD ACENIOM0100-02 Mechanical Installation: Installation is best performed with the NAMUR mounting kits. These kits allow

More information

GETTING STARTED GUIDE NI AI, ±10 V, 16 Bit, 1 MS/s/ch Simultaneous

GETTING STARTED GUIDE NI AI, ±10 V, 16 Bit, 1 MS/s/ch Simultaneous GETTING STARTED GUIDE NI 9223 4 AI, ±10 V, 16 Bit, 1 MS/s/ch Simultaneous This document explains how to connect to the NI 9223. Note Before you begin, complete the software and hardware installation procedures

More information

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER 5500 COMBUSTION SAFETY CONTROL INSTALLATION MANUAL FOR 5500 COMBUSTION SAFETY CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed

More information

GETTING STARTED GUIDE NI Channel Sinking Digital Input Module

GETTING STARTED GUIDE NI Channel Sinking Digital Input Module GETTING STARTED GUIDE NI 9421 8-Channel Sinking Digital Input Module This document explains how to connect to the NI 9421. In this document, the NI 9421 with screw terminal, NI 9421 with spring terminal,

More information

GETTING STARTED GUIDE NI AI, ±10 V, 12 Bit, 500 ks/s Aggregate

GETTING STARTED GUIDE NI AI, ±10 V, 12 Bit, 500 ks/s Aggregate GETTING STARTED GUIDE NI 9201 8 AI, ±10 V, 12 Bit, 500 ks/s Aggregate This document explains how to connect to the NI 9201. In this document, the NI 9201 with screw terminal, NI 9201 with spring terminal,

More information

LTX RF LEVEL SENSOR. Instruction Manual

LTX RF LEVEL SENSOR. Instruction Manual LTX RF LEVEL SENSOR Instruction Manual FOR MODELS LTX01, LTX02, LTX05 Intempco Document No: LTX - M01 Rev. 1 Issue Date: April 2005 LTX01 RF LEVEL SENSOR USER MANUAL Software Rev : Rev. Date : June 2004

More information

GETTING STARTED GUIDE NI DI, ±5 V to 24 V, Differential/Single-Ended, 500 ns

GETTING STARTED GUIDE NI DI, ±5 V to 24 V, Differential/Single-Ended, 500 ns GETTING STARTED GUIDE NI 9411 6 DI, ±5 V to 24 V, Differential/Single-Ended, 500 ns This document explains how to connect to the NI 9411. Note Before you begin, complete the software and hardware installation

More information

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10. BATTERY MODULE Long Life Battery: 10 to 12 Years According to EUROBAT Small Mounting Footprint Easy Access to the Terminals and the Fuse Heavy Duty Fuse Holder and Spare Fuse Included 3 Year Warranty,

More information

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE 24V, 7Ah Battery Capacity (2x 12V Batteries in Series) Small Mounting Footprint 2m Power Leads Included PT1000 Sensor for Battery Module Temperature Included Includes a Center-tap Terminal

More information

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT INSTALLATION AND WIRING INSTRUCTIONS MANUAL 8030 MANUAL PART NUMBER JANUARY 2011. 4304 MATTOX RD. KANSAS CITY, MO 64150 TABLE OF CONTENTS

More information

K Series 3 Way Direct Acting Balanced Poppet Solenoid Valve

K Series 3 Way Direct Acting Balanced Poppet Solenoid Valve Ex d Ex m IP5 Series 3 Way Direct Acting Balanced Poppet Solenoid Valve DB2S-M2C \ Ex d IIC with Integral Stainless \ Steel Junction Box. \ Valve. \ Manual Override, Option M2. J77072S-M2 \ Ex m II NASS

More information

Prodigy HDLV Generation II Pump Panel

Prodigy HDLV Generation II Pump Panel Prodigy HDLV Generation II Pump Panel Customer Product Manual Issued 01/10 For parts and technical support, call the Finishing Customer Support Center at (800) 433-9319. This document is subject to change

More information

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75 Cascade CD101 Auto-Start Controller Installation and Operations Manual 00-02-0594 2018-02-15 Sections 40 & 75 In order to consistently bring you the highest quality, full featured products, we reserve

More information

GETTING STARTED GUIDE NI DO, 6 V to 30 V, Sourcing, 100 μs

GETTING STARTED GUIDE NI DO, 6 V to 30 V, Sourcing, 100 μs GETTING STARTED GUIDE NI 9472 8 DO, 6 V to 30 V, Sourcing, 100 μs This document explains how to connect to the NI 9472. In this document, the NI 9472 with screw terminal, NI 9472 with spring terminal,

More information

Technical Offer. ViscoPro Measure Viscosity and Temperature on line for continuous process improvement

Technical Offer. ViscoPro Measure Viscosity and Temperature on line for continuous process improvement Technical Offer ViscoPro 2100 2015.2 Measure Viscosity and Temperature on line for continuous process improvement Advantages: Long and stable calibration Vibration and flow rate insensitivity Low maintenance

More information

Explosion-proof Solenoids ATEX. II 2 G / II 2 D EEx dm IIC T4, T5, T6. Catalogue 8735/GB. Maximum photo

Explosion-proof Solenoids ATEX. II 2 G / II 2 D EEx dm IIC T4, T5, T6. Catalogue 8735/GB. Maximum photo Explosion-proof Solenoids II 2 G / II 2 D EEx dm IIC T4, T5, T6 Catalogue Maximum photo ATEX Explosionproof solenoids with flameproof enclosure/encapsulation "dm" According to ATEX directive 94/9/EC and

More information

Series 3730 Electropneumatic Positioner Type

Series 3730 Electropneumatic Positioner Type Series 3730 Electropneumatic Positioner Type 3730-1 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Self-calibrating, automatic adaptation to valve and

More information

APPROVALS:

APPROVALS: DOC #: DE733010102 Rev A NAMEPLATE 138.3 5.45 DISPLAY CAN BE ROTATED UP TO 180 BOTH DIRECTIONS A14005 91.9 3.62 41.1 1.62 46 1.81 119.2 4.69 146.5 5.77 CLEARANCE FOR 1/4" BOLT (4 PLCS) GAGE 1/2" NPT (FEMALE)

More information

EStrong-series Emergency Stop

EStrong-series Emergency Stop Original instructions EStrong-series Emergency Stop ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand

More information

NI 9251 with mini XLR

NI 9251 with mini XLR GETTING STARTED GUIDE NI 9251 with mini XLR 2 AI, 3 Vrms, 24 Bit, 102.4 ks/s/ch Simultaneous, AC/DC Coupling This document explains how to connect to the NI 9251 with mini XLR. Note Before you begin, complete

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS WARNING: WARNING: www.altronicinc.com DEVIATION DEVIATION FROM THESE FROM INSTRUCTIONS THESE INSTRUCTIONS MAY LEAD MAY TO LEAD IMPROPER TO IMPROPER OP- ERATION OF ENGINE THE MACHINE

More information

Rosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications

Rosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications Product Data Sheet Rosemount 3051 FIELDBUS PROTOCOL Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof

More information

Safety Instructions Proline Promass 300

Safety Instructions Proline Promass 300 XA01472D/06/EN/01.16 71327890 Products Solutions Services Safety Instructions Proline Promass 300 Class I, Zone 1, AEx/Ex de ia IIC/IIB Class I, Zone 1, AEx/Ex d ia IIC/IIB Zone 21, AEx/Ex tb IIIC Txx

More information

GETTING STARTED GUIDE NI DO, 5 V to 30 V, Sourcing, 1 μs

GETTING STARTED GUIDE NI DO, 5 V to 30 V, Sourcing, 1 μs GETTING STARTED GUIDE NI 9474 8 DO, 5 V to 30 V, Sourcing, 1 μs This document explains how to connect to the NI 9474. In this document, the NI 9474 with screw terminal and the NI 9474 with spring terminal

More information

Mid-West Instrument. Diaphragm Type Model 240. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter

Mid-West Instrument. Diaphragm Type Model 240. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter BULLETIN NO. 240/11 (SUPERSEDES BULLETIN NO. 240/06) Mid-West Instrument Diaphragm Type Model 240 Hazardous Locations Indicating / Non-Indicating Differential Pressure Switch or Transmitter Field wireable

More information

Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box

Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box 1 TECHNICAL DATA SHEET Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box XPCJ series series of explosionproof aluminum enclosures are typically used in the packaging of electrical/electronic

More information

Sensor boxes SRBE Key features and product range overview

Sensor boxes SRBE Key features and product range overview Sensor boxes SRBE Sensor boxes SRBE Key features and product range overview Function Sensor boxes SRBE are used for electrical feedback and control of the position of process valves actuated using pneumatic

More information

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries Product Data Sheet January 214 813-1-475, Rev FA Rosemount 875WA Magnetic Flowmeter System For Water and Wastewater Industries THE 875WA MAGNETIC FLOWMETER Rosemount reliability in a customized offering

More information

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures Enclosures for hazardous areas clamped enclosures Clamped NEMA 7 classifi ed enclosures Clamped : NEMA 7 classified enclosures Safer. Faster. Easy access, lower risk and less downtime. Creative thinking

More information

T 3965 EN Type 3965 Solenoid Valve Island To control pneumatic actuators

T 3965 EN Type 3965 Solenoid Valve Island To control pneumatic actuators T 365 EN Type 365 Solenoid Valve Island To control pneumatic actuators Application The Type 365 Solenoid Valve Island is a compact solution for the central control of pneumatic actuators in chemical and

More information

Proximity Transmitters, and Seismic Vibration Transmitters

Proximity Transmitters, and Seismic Vibration Transmitters TM016 Velocity/ Acceleration Vibration Transmitter Introduction The TM016 is a solid state loop powered transmitter which provides a 4-20mA output proportional to the machine case vibration level. The

More information

INTERNATIONAL METAL ENGINEERING

INTERNATIONAL METAL ENGINEERING INDICATING TEMPERATURE TRANSMITTER WITH HART 8080HT UNIVERSAL SETTINGS WITH HART PROTOCOL FOR VARIOUS INPUT SIGNALS 2 WIRE TECHNOLOGY, 4 TO 20mA ANALOG OUTPUT HIGH ACCURACY IN TOTAL AMBIENT TEMPERATURE

More information

D2LC Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments

D2LC Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments D2LC Series Circuit Breaker Panelboards for Harsh and Hazardous Environments IBUTI TR HA ON DIS KILLARK Z LO C Type 4X Gasket Stainless Steel Tri-Lead Cover Bolts Spare Sealed Wires Termination at Terminal

More information

GETTING STARTED GUIDE NI AI/1 Neutral, 400 Vrms L-N/690 Vrms L-L, 24 Bit, 50 ks/s/ch Simultaneous

GETTING STARTED GUIDE NI AI/1 Neutral, 400 Vrms L-N/690 Vrms L-L, 24 Bit, 50 ks/s/ch Simultaneous GETTING STARTED GUIDE NI 9244 3 AI/1 Neutral, 400 Vrms L-N/690 Vrms L-L, 24 Bit, 50 ks/s/ch Simultaneous This document explains how to connect to the NI 9244. Note Before you begin, complete the software

More information

Flow Computer Installation

Flow Computer Installation Flow Computer Installation WARNING: Only personnel who are experienced with field wiring should perform these procedures. All field wiring must conform to the National Electrical Code, NFPA 70, Article

More information

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Product Overview. Product Identification. Amps One CT Two CTs Three CTs AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot SPOOL VALVES operated / to / tapped body and NAMUR for integrated pilot ATEX /-/ Series - FEATURES The valves offer environmental protection against the ingress of liquids, dusts or other foreign matter

More information

Mid-West Instrument. Piston Type Model 220. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter

Mid-West Instrument. Piston Type Model 220. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter BULLETIN NO. 220/11 (SUPERSEDES BULLETIN NO. 220/06) Mid-West Instrument Piston Type Model 220 Hazardous Locations Indicating / Non-Indicating Differential Pressure Switch or Transmitter Low cost piston

More information

SECTION 2.10 IGNITION SYSTEM DESCRIPTION CEC IGNITION MODULE SYSTEM MAGNETO IGNITION SYSTEM

SECTION 2.10 IGNITION SYSTEM DESCRIPTION CEC IGNITION MODULE SYSTEM MAGNETO IGNITION SYSTEM SECTION 2.10 SYSTEM DESCRIPTION CEC SYSTEM The Custom Engine Control (CEC) Ignition Module is located on the engine's left side (see Figure 2.10-1 and Figure 2.10-2). The CEC Ignition Module system consists

More information

APPLICATION MANUAL. Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin

APPLICATION MANUAL. Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin Updated 09.11.16 APPLICATION MANUAL Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin Contents: 1. Destination. 2. Flameproof joints, process

More information

SynergEX Panelboards for Hazardous Locations

SynergEX Panelboards for Hazardous Locations SynergEX Panelboards for Hazardous Locations Installation & Maintenance Information 1. APPLICATION SynergEX panelboards provide short circuit protection for feeder or branch circuits to control lighting,

More information

APS & APIS ATEX AIRPOWER SWITCH BOXES FEATURES DESCRIPTION

APS & APIS ATEX AIRPOWER SWITCH BOXES FEATURES DESCRIPTION page 1 DESCRIPTION The switch boxes are suitable for rotary actuators and are the industry leader in versatility, quality and approvals gained. Models include APS standard range with a variety of outputs

More information

249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h

249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h No Filter 81.6 % Auto 9.1 m3/h 250.0 m3/h Auto 99.7 m3/h 100.0 m3/h Auto 91.3 m3/h 92.0 m3/h Auto 40.0 m3/h 7. MW Auto 50.7 m3/h 50.0 m3/h 7.2 % Auto.6 % 45.0 % ABB NF Contactor Relays Overview...3 Ordering

More information

HKH Series. HAZCON Controls for Harsh and Hazardous Environments

HKH Series. HAZCON Controls for Harsh and Hazardous Environments HKH Series HAZCON Controls for Harsh and Hazardous Environments Z A H LO C NON-METALLIC DIN RAIL MOUNT Component Mounting Rail Optional Customer I.D. Nameplate Optional Legend Plate Explosion Protective

More information

Models beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.

Models beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions. Models beginning with MO, MK, 7B, 6S, 6F or 5B The Mini Meter Product Description Technical Specifications Installation Instructions February 28 th, 2013 1. Product Description...2 1.1 General Description...2

More information

Versions. Version with K VS Version with K VS 2.0. Fig. 1: Type 3967 Solenoid Valve

Versions. Version with K VS Version with K VS 2.0. Fig. 1: Type 3967 Solenoid Valve Type 367 Solenoid Valve Application Solenoid valve for controlling pneumatic linear actuators with NAMUR rib according to IEC 60534 or pneumatic rotary actuators with NAMUR interface according to VDI/VDE

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

CX1 ProVector Explosion-Proof Heaters

CX1 ProVector Explosion-Proof Heaters Explosion-Proof Heaters For hazardous locations heating, rely on the for the most dependable, troublefree service available. CCI Thermal Technologies Inc. manufactures explosion-proof air heaters to satisfy

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

Three Phase Explosion Proof Switch - Non Fused - 60 Amps - Early Break Auxiliary Contacts

Three Phase Explosion Proof Switch - Non Fused - 60 Amps - Early Break Auxiliary Contacts Three Phase Explosion Proof Switch - Non Fused - 60 Amps - Early Break Auxiliary Contacts Part #: EPSW-3PH-60-EB Page: 1 The EPSW-3PH-60-EB Three Phase Explosion Proof Switch by Larson Electronics is a

More information

INTECH Micro 2300-RTD6

INTECH Micro 2300-RTD6 INTECH Micro 2300-RTD6 6 Channel RTD Input Station Overview. The Intech Micro 2300 Series is a system of modular I/O Remote Stations, that add an even lower cost option to Intech s already extensive intelligent

More information

LIMIT SWITCH Axiom - AX

LIMIT SWITCH Axiom - AX LIMIT SWITCH Axiom - AX with AS-Interface (Standard Addressing) Installation, Maintenance and Operating Instructions (AX9 ) 2 Table of Contents Table Of Contents... Page 2 Axiom Model Guide... Page 3 Dimensions

More information

Shock/Vibration Control Switches

Shock/Vibration Control Switches Shock/Vibration Control Switches Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 ` Installation Instructions 00-02-0185 2013-02-01 Section 20 Please read the following information before installing.

More information

ACE Variable Frequency Drive System

ACE Variable Frequency Drive System ACE Variable Frequency Drive System Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IF 1690 BLOWER COOLING INTAKE SHROUDS BLOWER FUSE BLOCK TEMPERATURE CONTROLLER TRANSFORMER

More information

Redundant Control System

Redundant Control System Redundant Control System Safety instrumented system applications up to SIL 3 Process reliability Process valve diagnostics COMPLETE FUNCTIONAL SAFETY WITH ENHANCED RELIABILITY The Redundant Control System

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExBGL2D LED BEACON For use in Flammable Gas and Dust Atmospheres BExBGL2D 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGIZED POTENTIAL

More information

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC 9419 E US HWY 175, Kemp, TX 75143 Phone: 1 8003696671 Fax: 903.498.3364 Email: sales@larsonelectronics.com Explosion Proof Receptacle Integral Circuit Breaker Class 2 Division 1 30 Amp 480VAC Part #: EPO3W4P30AICB

More information

Smart Valve Positioner 700 Series with HART Communication Protocol

Smart Valve Positioner 700 Series with HART Communication Protocol No. SS2-AVP702-0100 Smart Valve Positioner 700 Series with HART Communication Protocol OVERVIEW The Smart Valve Positioner 700 Series (model number: AVP7**) not only inherits the reliability of the core

More information

Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit

Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit Instruction Sheet 10 2004 Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit 541 0810 GENERAL INFORMATION This kit contains one Control Communications Module (CCM-G) with

More information

For mounting on subbase or footprint in accordance with CNOMO recommendation E 06620N Part numbers (and voltages) Voltage max. power consumption U nom

For mounting on subbase or footprint in accordance with CNOMO recommendation E 06620N Part numbers (and voltages) Voltage max. power consumption U nom Intrinsically Safe Miniature Solenoid Valves Order/Technical Support Tel: (800) 6775 / FAX: (800) 677865 / www.crouzetusa.com 5/6 5 For mounting on subbase or footprint in accordance with CNOMO recommendation

More information

Intrinsically Safe Miniature Solenoid Valves

Intrinsically Safe Miniature Solenoid Valves Intrinsically Safe Miniature Solenoid Valves 5 Order/Technical Support Tel: (800) 6775 / FAX: (800) 677865 / www.crouzetusa.com 5/6 Intrinsically safe miniature solenoid valves EEx ia T6 approval no. 9

More information

D Series Ex d Stainless Steel

D Series Ex d Stainless Steel 2 Way irect Acting Solenoid Valve IIC T4/T6 Series Stainless Steel 2 and 3 Way irect Acting Solenoid Valve IIC T4/T6 2SK-CM [ FEATURES ] Integral terminal box with coil housing. Valve do not require minimum

More information

GETTING STARTED GUIDE NI AO, ±10 V, 16 Bit, 25 ks/s/ch Simultaneous

GETTING STARTED GUIDE NI AO, ±10 V, 16 Bit, 25 ks/s/ch Simultaneous GETTING STARTED GUIDE NI 9264 16 AO, ±10 V, 16 Bit, 25 ks/s/ch Simultaneous This document explains how to connect to the NI 9264. In this document, the NI 9264 with spring terminal and the NI 9264 with

More information

Valve Position Monitors

Valve Position Monitors Valve Position Monitors EX Series for Hazardous Locations APL Series NEMA 4, 4X 1 LIMIT SWITCHES Triac APL Series Limit Switches The Triac APL Series Limit Switches feature high quality, easy to use multiple

More information

ILED Dorado. User Manual

ILED Dorado. User Manual 10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

LIMIT SWITCH Axiom - AX

LIMIT SWITCH Axiom - AX LIMIT SWITCH Axiom - AX with FOUNDATION Fieldbus Installation, Maintenance and Operating Instructions (AX93 ) 2 Table of Contents Table Of Contents... Page 2 Axiom Model Guide... Page 3 Dimensions and

More information

Level Measurement Point level measurement - RF Capacitance switches

Level Measurement Point level measurement - RF Capacitance switches Pointek CLS200 - Standard Overview Configuration Installation Pointek CLS200 (standard version) is a versatile inverse frequency shift capacitance level and material detection switch with optional rod/cable

More information

Operations Manual. Zero Speed Switch Sensor Model ZS09P

Operations Manual. Zero Speed Switch Sensor Model ZS09P Zero Speed Switch Sensor Model ZS09P The must be referred to for correct installation. Failure to comply with the shall void all warranties and liabilities. Overview The Phares Electronics Model ZS09P

More information

Fisher 546 Electro Pneumatic Transducer

Fisher 546 Electro Pneumatic Transducer 546 Transducer Product Bulletin Fisher 546 Electro Pneumatic Transducer Fisher 546 transducers receive a direct current input signal and use a torque motor, nozzle flapper, and pneumatic relay to convert

More information

BMRX Series ROTARY LEVEL CONTROL

BMRX Series ROTARY LEVEL CONTROL BMRX Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0292 Rev C TABLE OF CONTENTS GENERAL SPECIFICATIONS... 3 SAFETY SUMMARY... 4 1.0 INTRODUCTION... 5 2.0 INSTALLATION...

More information

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 - Type 2000 Pneumatic and Electropneumatic Valve Positioner Installation, Operation and Maintenance Instructions Ordering Information Use this coding system to order Model CA20 - Type of Positioner 00 P/P

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

WF-5100 Series True Sine Wave Inverters

WF-5100 Series True Sine Wave Inverters Operator s Manual WF-5100 Series True Sine Wave Inverters WF-9900 Series WF-5118 WF-5120 ( The Inverter model number is located on the label on top of the enclosure) Distributed in the U.S.A. and Canada

More information

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 4/18 Siemens FI Overview.

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 4/18 Siemens FI Overview. Pointek CLS200 Standard Overview Configuration Installation Pointek CLS200 (standard version) is a versatile inverse frequency shift capacitance level switch with optional rod/cable choices liquids, solids,

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module The following specification defines the minimum requirements for the supply of motor operated valve actuators with a field communication bus system for remote control. The complete system shall consist

More information

Certificate of Compliance

Certificate of Compliance FF0 002 Certificate of Compliance Issued to: Rotork Controls Inc. 675 Mile Crossing Blvd Rochester, NY 14624 USA Attention: Matt Cogill The products listed below are eligible to bear the CSA Mark shown

More information

GVB-8 (Boost) Manual

GVB-8 (Boost) Manual www.genasun.com GVB-8 (Boost) Manual Solar Charge Controllers with Maximum Power Point Tracking For models: GVB-8-Pb-12V: 12V Lead-Acid/AGM/Gel/Sealed/Flooded GVB-8-Pb-24V: 24V Lead-Acid/AGM/Gel/Sealed/Flooded

More information

GETTING STARTED GUIDE NI AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate

GETTING STARTED GUIDE NI AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate GETTING STARTED GUIDE NI 9205 16 AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate This document explains how to connect to the NI 9205. In this document, the NI 9205 with

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

Single Point Overfill Prevention Control Monitor Model: ST-15C Series Technical Manual

Single Point Overfill Prevention Control Monitor Model: ST-15C Series Technical Manual scully Single Point Overfill Prevention Control Monitor Model: ST-15C Series Technical Manual Duocept, Dynacheck, Dynamic Self Checking, Dynamic Faylsafe, Go Anywhere, Dynamic Self-Testing, IntelliCheck,

More information

Rosemount 3051CFA Annubar Flowmeter

Rosemount 3051CFA Annubar Flowmeter December 2013 Rosemount 3051 Rosemount 3051CFA Annubar Flowmeter The Rosemount 3051CFA Annubar Flowmeter utilizes the patented T-shaped sensor design that delivers best in class accuracy and performance.

More information

Smart Valve Positioner 700 Series with HART Communication Protocol

Smart Valve Positioner 700 Series with HART Communication Protocol No. SS2-AVP702-0100 Smart Valve Positioner 700 Series with HART Communication Protocol OVERVIEW The Smart Valve Positioner 700 Series (model number: AVP7**) not only inherits the reliability of the core

More information

Installation Instructions

Installation Instructions AQU244 & AQU128 Series Installation Instructions Installation Instructions AQU244 24vdc 5A Supervised Power Supply/Charger module AQU128 12vdc 10A Supervised Power Supply/Charger module Both Mounted in

More information

burners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive.

burners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive. LAST UPDATE 29/08/12 INSTALLATION INSTRUCTIONS v. 3 UNIT SPECIFICATIONS Main Gas Valve, Pilot Gas Valve Ionisation, Ignition and Flame Monitoring with Common Electrode or Remote Sensor Integrated Cyclic

More information

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. icenta Controls Ltd

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. icenta Controls Ltd Pointek CLS200 Standard Overview Configuration Installation Pointek CLS200 (standard version) is a versatile inverse frequency shift capacitance level switch with optional rod/cable choices liquids, solids,

More information

GVB-8 (Boost) Manual

GVB-8 (Boost) Manual GVB-8 (Boost) Manual Solar Charge Controllers with Maximum Power Point Tracking For models: GVB-8-Pb-12V: 12V Lead-Acid/AGM/Gel/Sealed/Flooded GVB-8-Pb-24V: GVB-8-Pb-36V: GVB-8-Pb-48V: GVB-8-Pb-CV: 24V

More information

The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor

The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor OPERATIONS MANUAL The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor The CSA approved alternative ignition system delivering safety, reliability and versatility. KEY FEATURES Unique

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit Instruction Sheet 10-2004 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch.

More information

Manual. EN Appendix. Lynx Ion BMS 400A / 1000A

Manual. EN Appendix. Lynx Ion BMS 400A / 1000A Manual EN Appendix Lynx Ion BMS 400A / 1000A 1. SAFETY INSTRUCTIONS 1.1 In general Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions

More information

Integrated Control modules

Integrated Control modules .60.0 Rev. 0 Page of 9 Integrated Control modules QC, QC2 and QC Features: - Basic actuator functions for: - Spring return applications, or - Double acting applications or, - Double acting Fail in Last

More information

CONTENTS 1. 1 Power Units Overview Applications Models Power Units... 3

CONTENTS 1. 1 Power Units Overview Applications Models Power Units... 3 CONTENTS 1 Power Units Contents 1 Power Units 2 1.1 Overview........................................ 2 1.2 Applications...................................... 2 2 Models 3 2.1 Power Units......................................

More information

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101428D0201 28/03/11 -.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits. NF(Z)

More information

Mid-West Instrument. Piston Type Model 220. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter. Min.

Mid-West Instrument. Piston Type Model 220. Hazardous Locations. Indicating / Non-Indicating Differential Pressure Switch or Transmitter. Min. Piston ype Model 220 Hazardous Locations BULLEIN NO. 220/11 (SUPERSEDES BULLEIN NO. 220/06) Indicating / Non-Indicating Differential Pressure Switch or ransmitter Low cost piston type differential pressure

More information