V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION

Size: px
Start display at page:

Download "V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION"

Transcription

1 Master Slave 1 Slave (n + 1) Master Slave 1 Slave (n + 1) Simplified Master / Slave operation GENERAL is a CIAT electronic control system designed to control non-independent air conditioning terminal units (fan coil units, UTAs, Cassettes, etc.) for 2 pipe, 2 pipe / 2 wire and 4 pipe applications using recycled air. It is available for control on water (with 2-way or 4-way valves). The drives electrothermal 24V valve actuators. control is available as a flush-mounting version factory fitted in a sill-mounted fan coil unit or wall-mounting version to be connected by the installer. control can operate in Master / Slave configuration. One master can control up to 15 slaves (recommended limit). Two wires lead from the master to the first slave, then two wires lead on to the second slave, etc. There is no need for any wires to leave the last slave. The master communicates the following information to the slaves: setpoints, air and water temperatures, on/off and speeds, economy input status, window contact status. If a slave has its own sensor (air or water), this measurement takes priority over the information from the master. Single-zone centralised cabinet control possible (see example application). DESCRIPTION units use Proportional Integral control, controlling the valve(s), electric heater and three-speed ventilation. selects automatically or manually the ventilation speeds. The control parameters (proportional band, integration time) are pre-set but two configurations can be selected on site (slow or fast). There are two adjustable setpoint temperatures, for heating (factory setting 19 C) and cooling (factory setting 23 C). Temperature settings can be modified on a range of ±6 K. The heating and cooling stages start automatically (neutral zone 3 to 6K, factory setting 6K). The integrates all calculations. The control unit is used to adjust the setpoint within the predefined range and turn the unit on or off. Turning the unit off guarantees a frost protection temperature (setpoint 8 C). A window contact is used to confirm a change to frost protection operation. An economy contact can be used to set reduced mode. It may be used in conjunction with a programmable timer, key, etc. (setpoints reduced by 5 K). If using a clock, consult "single centralised zone control". See our user's brochure for more details. AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA A 1

2 RECYCLED AIR APPLICATION TERMINAL UNITS Valve KVS = 1.6 max. G 1/2" max. Max. water flow rate 1000 l/h CONTROL ASSEMBLY PI regulator, with factory parameter settings and wiring. Terminal with potentiometer and Comfort / Stand by switch. 24V valve with electrothermal actuator- no cocks. Terminal : - V: set in, mounted on the unit - H: wall-mounted to be wired by the installer V H MAJOR 300 Auxiliary drain pan included with fuse cut-out and valves factory-fitted MAJOR 2 COADIS 2 COADIS SLIM COADIS COMFORT UTA Compact UTA Standard Cassette MELODY Without fuse cut-out and valve kit delivered separately 2-pipe system - Cooling only >1 x 2-way valve V202F V210F E E C >1 x 4-way valve* V203F V211F E E C Heating only >1 x 2-way valve V202C V210C E E C >1 x 4-way valve* V203C V211C E E C Heating / cooling > 1 x 4-way valve with change-over fitted* V204 V212 E E C pipe system + max W electric Relays included - Cooling + electric with neutral zone > 1 x 2-way valve V205 V213 E E C > 1 x 4-way valve* V206 V214 E E C Heating / cooling+ electric > 1 x 4-way valve with change-over fitted* V207 V215 E E C Supplement for electric heater power above 2800 W and up to 4600 W E INCLUDED 4 pipe system > 2 x 2-way valves V208 E E C > 2 x 4-way valves* V201 V209 E E C Compulsory supplements for valves with KVS > 1.6 For : UTA 295/04-370/44 For : UTA 370 / 66 MAJOR et 435 MELODY x 4-way valve* KVS G 3/4" 1 x 4-way valve* KVS 4 - G 3/4" E Max. water flow : 2500 l / h 1 x 2-way valve KVS G 3/4" 1 x 2-way valve KVS 4 - G 3/4" E Max. water flow : 2500 l / h Reductions for units with "Slave" function only Remove user's terminal E Remove any change over sensor E Assistance with commissioning recommended E Flat rate travelling expenses (mainland France) + Intervention supplement for each unit E *3-way + by-pass valve 2 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA A

3 SINGLE CENTRALISED ZONE CONTROL This application example enables a zone containing up to 50 terminal units to be controlled with a control loop. Pilot loops Example.A Application A : centralised control for independent office Integrated Office 1 Office 2 Terminal (2) Terminal (2) Integrated terminal bus To other offices C/O(1) Example.B Application B : single zone centralised control for one area Economy clock Integrated Anti-freeze protection clock Electrical cabinet bus Sensor Sensor (1) Change over sensor for 2-pipe reversible heat/cold application (2) If wall terminal: sensor only on the terminal (H) If built-in terminal: sensor to the fan coil inlet (V) The terminal units (fan coils or UTA) are all independent and fitted with s. A pilot control loop, fitted in an electrical cabinet outside the offices, allows a centralised remote control. This pilot control loop feeds an extra programmed and a terminal. This control loop includes an extra-parametered regulator and a terminal connected to this regulator. This terminal allows: - the setting temperature adjustment, factory adjustment at the medium point, heating setpoint: 19 C, cooling setpoint: 25 C, modifiable on a scale of ± 6K. - the automatic or manual ventilation speeds regulation: If the auto-speed is selected on the cabinet terminal, then the unit potential terminals can choose a manual ventilation speed. If a manual speed is selected on the cabinet terminal, then the unit potential terminals are fixed on this selected speed. - the operating mode adjustment: Comfort or frost free. If the is in the frost free position, the units potential terminals are blocked on stop. A clock can be wired to this pilot to program Comfort / Economy modes. A second clock can be wired to program anti-freeze modes during office vacations for example (weekends, holidays, ) Two applications are available: A : Centralised control for independent offices. The independent terminal units are fitted with a terminal and a temperature sensor, users will be allowed to change the temperature set-point within ±2 C of the value sent by the pilot, switch on the anti-freeze mode by the on/off button, and control manually fan speeds. Master/Slave groups per office cannot be re-created in this function. B : Centralised single-zone control Each independent terminal unit has its own temperature sensor. All commands are managed by the pilot. Note: For more technical details, consult us. AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA A 3

4 and settings Control on water, RECYCLED AIR APPLICATION TERMINAL UNITS Pilot loop (to integrate in an electrical cabinet): Terminal Programmable timer module Digital display programmable clock module (plan 2 modules). Opening and closing control of one or several independent circuits according to an hourly program, memorized and indicated by the user (can be associated to any regulation fitted with an auxiliary contact: V20C, and 0 ) Changeover sensor (for 2-pipe reversible units) Pipe adapter control loop fitted on the terminal unit: valve KVS = 1.6 max. G 1/2" max. Max. water flow rate 1000 l/h CONTROL ASSEMBLY PI regulator, with factory parameter settings, wiring and testing. Terminal with potentiometer, Comfort / Stand by / 3 speeds switch (except application B) 24V valve with electrothermal actuator- no cocks. Terminal: - V: set in, mounted on the unit Application A Application B - H: wall-mounted to be wired by the installer - S: Without terminal, with air inlet sensor V H S 2-pipe system - Heating only or Cooling only or Heating / cooling >1 x 2-way valve >1 x 4-way valve* - Cooling + electric with neutral zone or heating/cooling + electric with dead zone > 1 x 2-way valve > 1 x 4-way valve* - Supplement for electric heater power above 2800 W and up to 4600 W > 2 x 2-way valve > 2 x 4-way valve* MAJOR 300 / MAJOR 2 / COADIS2 / COADIS SLIM / COADIS COMFORT Cassette MELODY UTA Compact / UTA Standard 2-pipe 4-pipe 2-pipe + 2-wire 2-pipe 4-pipe 2-pipe + 2-wire E E E MAJOR 300 MAJOR 2 / COADIS 2 COADIS SLIM COADIS COMFORT UTA Compact UTA Standard Auxiliary drain pan included with fuse cut-out and valves factory-fitted Cassette MELODY Without fuse cut-out and valve kit delivered separately E E E E C E E E E C pipe system + max W electric Extra compulsory elements for valves with KVS>1.6 For: UTA 295/04-370/44 For: UTA 370 / 66 MAJOR and 435 MELODY x 4-way valve* KVS G 3/4" 1 x 4-way valve* KVS 4 - G 3/4" - - Max. water flow: 2500 l / h 1 x 2-way valve KVS G 3/4" 1 x 2-way valve KVS 4 - G 3/4" - Max. water flow: 2500 l / h Assistance with commissioning recommended Flat rate travelling expenses (mainland France) + Intervention supplement for each unit *3-way +by-pass valve E E E E C E E E E C E AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA A pipe system E E E E C E E E E C E E E E002038

5 This document is non-contractual.as part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification. Head office Avenue Jean Falconnier - B.P Culoz - France Tel.: +33 (0) Fax: +33 (0) info@ciat.fr - CIAT Service Tel.: +33 (0) Fax: +33 (0) Compagnie Industrielle d Applications Thermiques - S.A. with a registered capital of R.C.S. Belley B

VIRTUO. Comfort ventilation boxes Self-supporting casing with lacquered

VIRTUO. Comfort ventilation boxes Self-supporting casing with lacquered Comfort ventilation Self-supporting casing with lacquered finish as standard Air intake or exhaust operation Simplified access to internal components ErP READY Air flow: 500 to 35 000 m 3 /h Use ventilation

More information

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management Ductable units NEW Eco-Design Filter Air handling unit with high available static pressure V3000 control Fresh air management The range of air handling units is designed for suspended ceiling heating and

More information

climaciat airtech Air handling units Air handling for all applications Climaciat Airtech The technological choice Performing to new standards

climaciat airtech Air handling units Air handling for all applications Climaciat Airtech The technological choice Performing to new standards Climaciat Airtech The technological choice Characteristics Casing strength Casing air leakage Filter bypass leakage Thermal transmittance Thermal bridge factor Class D2 L1-L2 F9 T2 TB2 Air flow: 1 000

More information

Residential comfort unit OperatiOn 2 models. new builds or existing properties. 5 operating modes COnfOrmity COmpOnents

Residential comfort unit OperatiOn 2 models. new builds or existing properties. 5 operating modes COnfOrmity COmpOnents Residential HEE motor Silent operation Heating capacity: 200 W to 4 kw Cooling capacity: 100 W to 3 kw Operation is CIAT's residential. This vertical cased unit, designed for heating and cooling, is available

More information

V.I.R.T.U.O. Ventilation boxes. Comfort ventilation boxes. Use. Range. Design

V.I.R.T.U.O. Ventilation boxes. Comfort ventilation boxes. Use. Range. Design Comfort ventilation Very wide flow rate range: 0.11 to 9.72 m 3 /s Standard version with lacquered finish casing Use ventilation are designed for the ventilation of tertiary or industrial buildings, for

More information

Reversible air-to-water heat pump HEAT PUMP HEATING (30/35 C 40/45 C)

Reversible air-to-water heat pump HEAT PUMP HEATING (30/35 C 40/45 C) Simple, reliable efficient heat pump! Equipped with µconnect controller HFC R410A CERTITA CERTIFIED * Cooling capacity: 5 to 16.5 kw Heating capacity: 6 to 19 kw *except 75HT OPTION HEAT PUMP HEATING (30/35

More information

This generation of shell and tubes evaporator has been designed for integration into high and medium power cooling systems.

This generation of shell and tubes evaporator has been designed for integration into high and medium power cooling systems. Use Improve heat exchanges with high-efficiency tubes Quality refrigerating components ange of optimised devices Cooling capacity : 100 to 2000 kw This generation of shell and tubes evaporator has been

More information

This generation of shell and tubes evaporator has been designed for integration into high and medium power cooling systems.

This generation of shell and tubes evaporator has been designed for integration into high and medium power cooling systems. hell and tubes Use Corrugated tubes for enhanced heat transfer efrigerant grade components ange of optimised units Cooling capacity : 100 to 2000 kw This generation of shell and tubes evaporator has been

More information

CWK Circular duct coolers for cooled water

CWK Circular duct coolers for cooled water Circular duct coolers for cooled water Circular duct coolers for cooled water duct coolers are designed for using cooled water as the cooling medium and are used for cooling the ventilation air in ventilation

More information

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser The ZC 107 Zone Control System was designed to provide the perfect comfort control within the home. At the same time it was designed to make an airconditioning system work more efficiently and thereby

More information

high-power ally design Your from 230 to 1100 kw Forward-thinking PowerCIAT heralds a break in the way packaged water

high-power ally design Your from 230 to 1100 kw Forward-thinking PowerCIAT heralds a break in the way packaged water NA 01.70 E Your high-power ally from 230 to 1100 kw PowerCIAT is the new reference in 230-1100 kw cooling systems for the residential, service, hotel and catering, district heating and industrial process

More information

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start) AQUASTAR C6 (Comfort 6000) Next Generation Auto Backwash Valve System (selectable time-pressure or remote cycle start) SIDE MOUNTED AND TOP MOUNTED VALVES WITH QUICK INSTALL ELECTRIC ACTUATORS FOR PIPE

More information

NA F FLOWAY. Instruction manual

NA F FLOWAY. Instruction manual NA 09.62 F 03-2016 FLOWAY Instruction manual EN CONTENTS 1. DELIVERY 2 2. HANDLING 2 3. DESCRIPTION OF THE UNIT/TECHNICAL SPECIFICATIONS 4 4. INSTALLATION AND CONNECTIONS 14 5. COMMISSIONING 24 6. MAINTENANCE/SERVICE

More information

CWW Circular duct heaters for hot water

CWW Circular duct heaters for hot water Circular duct heaters for hot water Circular duct heaters for hot water The with circular duct connections uses hot water as the energy carrier and is used for heating the ventilation air in a ventilation

More information

HERZ Electronic room thermostat analog and digital

HERZ Electronic room thermostat analog and digital Dimension in mm 3 F799 11-3 F799 14 HERZ Electronic room thermostat analog and digital Data sheet for F799, Issue 0317 3 F799 15 3 F799 18 Mounting plate Page 1 Technical data 3 F799 11-14 3 F799 15-18

More information

CWK Circular duct coolers for cooled water

CWK Circular duct coolers for cooled water Circular duct coolers for cooled water Circular duct coolers for cooled water The with circular duct connection uses chilled water as the energy carrier and is used for cooling the ventilation air in a

More information

Fan coil units MAJOR 2 CV/CH

Fan coil units MAJOR 2 CV/CH CH 41 D CV 1 D MAJOR 2: Design and performance HEE impeller for increased performance Motor optional MAJOR 2 is a non-independant chilled and/or hot water supplied air conditioning Comfort unit for the

More information

RVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a

RVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a 4 319 2968 0 G2383en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD230 Installation Place of installation In a dry room, e.g. in the heat exchanger room

More information

MAJOR 2 NCH. Ductable units. High pressure and high capacity ductable units RANGE NCH Y NCH NCH I COADIS COMBI. Motor optional

MAJOR 2 NCH. Ductable units. High pressure and high capacity ductable units RANGE NCH Y NCH NCH I COADIS COMBI. Motor optional Y + U I COADIS COMBI High pressure and high ductable units Motor optional is a non independent air conditioning terminal unit for heating and cooling offices and hotels. With reduced dimensions and designed

More information

PGK Rectangular duct coolers for cooled water

PGK Rectangular duct coolers for cooled water Rectangular duct coolers for cooled water Rectangular duct coolers for cooled water The with rectangular duct connection uses chilled water as the energy carrier and is used for cooling the ventilation

More information

Fault Codes. J control

Fault Codes. J control J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

42GW. Hydronic Cassette Fan Coil Units PRODUCT SELECTION DATA INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS EASY INSTALLATION

42GW. Hydronic Cassette Fan Coil Units PRODUCT SELECTION DATA INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS EASY INSTALLATION PRODUCT SELECTION DATA EASY INSTALLATION INSTALLATION, OPERATION AND CENTRAL AIR DIFFUSION MAINTENANCE INSTRUCTIONS LOW ENERGY CONSUMPTION IMPROVED COMFORT ELEGANT AIR INLET GRILLE EXTREMELY QUIET OPERATION

More information

G2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base

G2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base 74 319 726 G2515 en Installation Instructions District heating controller for 2 heating circuits and d.h.w. RVD26 Keep these instructions with the controller! Installation Place of installation In a dry

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS 50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT

More information

HYDROCIAT LW. Use. Range. Water-cooled chillers. Screw compressors CIAT shell and tubes direct expansion evaporator HPS (High Power System) equipment

HYDROCIAT LW. Use. Range. Water-cooled chillers. Screw compressors CIAT shell and tubes direct expansion evaporator HPS (High Power System) equipment Screw compressors CIAT shell and tubes direct expansion evaporator (High Power System) equipment Cooling capacity: 370 to 1 170 kw Heating capacity: 500 to 1 400 kw Heating Cooling Heat recovery Use The

More information

RVD235. G2385en. Installation without base

RVD235. G2385en. Installation without base 2382Z04 G2385en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD235 Installation without base Place of installation Compact station front or control panel

More information

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB ACCREDITED Modulating temperature regulating unit with distribution kit for primary circuit 7 series ISO 9 FM 6 / GB replaces /7 GB Function The temperature regulating unit with the distribution kit for

More information

PGV Rectangular duct heaters for hot water

PGV Rectangular duct heaters for hot water Rectangular duct heaters for hot water Rectangular duct heaters for hot water The with rectangular duct connection uses hot water as the energy carrier and is used for heating the ventilation air in a

More information

Air-to-water heat pump for indoor installation - LIK 8TES. Spare parts list

Air-to-water heat pump for indoor installation - LIK 8TES. Spare parts list Spare parts list Brand: Dimplex Type: LIK 8TES Part number: 366030 Position Description Part number Serv. ind. 1 Compressor 4522354115 2 Evaporator 4521612802 3 Expansion valve 4521614106 4 Inspection

More information

RC-DO. Room controllers with display and manual forced ventilation function

RC-DO. Room controllers with display and manual forced ventilation function revision 10 2017 RC-DO Room controllers with display and manual forced ventilation function RC-DO is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.

More information

TECHNICAL BROCHURE. TC-Lube technical description DSi sprl May 2012

TECHNICAL BROCHURE. TC-Lube technical description DSi sprl May 2012 TECHNICAL BROCHURE 1 INTRODUCTION The development of turbochargers (TC) is of particular interest due to the need for low consumption and very low emission diesel and gasoline engines. Downsizing of engines

More information

Total cooling capacity kw Total heating capacity kw Features

Total cooling capacity kw Total heating capacity kw Features Room Fan Coils Idrofan Quality Management Systems 42N Total cooling capacity 0.75-6.35 kw Total heating capacity 0.60-9.50 kw The new generation 42N_S product range combines aesthetic and attractive design

More information

All solutions. Water chillers Heat pumps NA I

All solutions. Water chillers Heat pumps NA I All solutions Water chillers Heat pumps NA 04.07 I The CIAT Group Culoz - France, CIAT's main industrial site CIAT R&I Centre test platform Established in 1934, CIAT has been constantly developing its

More information

McQuay. Console Water Source Heat Pump. European Unit WWME, WWMJ, WWMK, WWML Designs A, B (1, 2) Last Manufactured: 2004

McQuay. Console Water Source Heat Pump. European Unit WWME, WWMJ, WWMK, WWML Designs A, B (1, 2) Last Manufactured: 2004 Replacement Parts List 110502500 Revision C 02/2017 McQuay Console Water Source Heat Pump European Unit WWME, WWMJ, WWMK, WWML 007-015 Designs A, B (1, 2) Last Manufactured: 2004 To find your Daikin Applied

More information

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation. Low Energy Consumption

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation. Low Energy Consumption PRODUCT SELECTION DATA Modular Horizontal ducted unit Extremely quiet operation Low Energy Consumption Flexibility for simplified installation Improved comfort Efficient Indoor Air Quality Hydronic Ducted

More information

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL. Centrifugal fan coil units

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL. Centrifugal fan coil units Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL Centrifugal fan coil units SYSCOIL Fan coil units Compact, slim fan coil units. Available

More information

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation PRODUCT SELECTION DATA Modular Horizontal ducted unit Extremely quiet operation Low Energy Consumption Flexibility for simplified installation Improved comfort Effcient Indoor Air Quality Hydronic Ducted

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

RWBa. ROOM CONTROL EQUIPMENT Electronic control of cooling and heating. RWBa

RWBa. ROOM CONTROL EQUIPMENT Electronic control of cooling and heating. RWBa ROOM CONTROL EQUIPMENT Electronic control of cooling and heating. ROOM CONTROL EQUIPMENT RWBa For sequential control of heating and cooling, or cooling/ heating only. Electromechanical actuators provide

More information

Fan Coil Units. Technical Data ECDEN FWL-DT/DF

Fan Coil Units. Technical Data ECDEN FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF TABLE OF CONTENTS FWL-DT/DF 1 Features.............................................................

More information

PROPORTIONAL BAND ZERO ENERGY BAND DEFINITION S1 S2

PROPORTIONAL BAND ZERO ENERGY BAND DEFINITION S1 S2 Honeywell T0C INDIVIDUAL ROOM TEMPERATURE CONTROLLER INSTALLATION GUIDE Cover removal Mounting T0C 00-00 R Wiring T0C.mm (max) Remote Temperature Sensor Screen wire 0 Connect screen wire to terminal or

More information

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN

More information

Zone Valves and Parts (Honeywell)

Zone Valves and Parts (Honeywell) 28/11/14 B49 Zone Valves - Two Way Fan Coil Zone Valves and Parts (Honeywell) Two-way Fan Coil Valve, the VU53 high pressure zone valves are used to control the flow of hot or chilled water in commercial

More information

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07. Air Cooled Water Chillers CLS 182 to 602 41 to 150 kw Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.04 R Specifications General characteristics The CLS air cooled water

More information

Preassembled fixed-point control, distribution and pumping unit for radiant panel heating systems DOMORADIANT Series

Preassembled fixed-point control, distribution and pumping unit for radiant panel heating systems DOMORADIANT Series 95-0055-UK-Rev1.qxd 4-09-2007 10:31 Pagina 1 Preassembled fixed-point control, distribution and pumping unit for radiant panel heating systems DOMORADIANT Series Main features DOMORADIANT, is a preassembled

More information

RVD110 RVD G2381en. Installation. Commissioning

RVD110 RVD G2381en. Installation. Commissioning 4 319 2788 0 G2381en en Installation Instructions District heating and d.h.w. controller RVD110 RVD130 Installation Place of installation In a dry room, e.g. the heat exchanger room Mounting choices: -

More information

Engineering Data Manual. New : available with EC motor. High Static Pressure Ductable Fan Coil Unit. Models 07 to to 4650 m 3 /h

Engineering Data Manual. New : available with EC motor. High Static Pressure Ductable Fan Coil Unit. Models 07 to to 4650 m 3 /h Engineering Data Manual New : available with EC motor VH High Static Pressure Ductable Fan Coil Unit Models 07 to 27 800 to 4650 m 3 /h General Characteristics Presentation On model VH 07, coils have 4

More information

Compresseur scroll. Refrigerant R410A SYSAQUAC. Air Cooled Condensing Units Models 25 to to 136.0kW

Compresseur scroll. Refrigerant R410A SYSAQUAC. Air Cooled Condensing Units Models 25 to to 136.0kW Compresseur scroll Refrigerant R410A SYSAQUAC Air Cooled Condensing Units Models 25 to 125 32.0 to 136.0kW SYSAQUA Condensation 1 Key Points R410A refrigerant, Units are optimized for partial load operation,

More information

PRODUCT CATALOGUE CHILLED WATER CASSETTE CWC

PRODUCT CATALOGUE CHILLED WATER CASSETTE CWC PRODUCT CATALOGUE CHILLED WATER CASSETTE CWC English/09-2003 CHILLED WATER CASSETTE! INTRODUCTION TO THE RANGE The units are available in the following versions:! 2 pipes! 2 pipes - 2 wires (electrical

More information

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches MiG2 TIME SWITCHES 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches The MiG2 series of timers are programmable 365-day time-switches, incorporating: Multiple switching times per day Single and block

More information

Applied Decentralized Products Water Source Heat Pump / Rev.A HWH024D, HWH030D HWW024D, HWW030D PL

Applied Decentralized Products Water Source Heat Pump / Rev.A HWH024D, HWH030D HWW024D, HWW030D PL Applied Decentralized Products Water Source Heat Pump / Rev.A HWH, HWH HWW, HWW PL-1101-4 Nomenclature Nomenclature Field Installed Thermostats & Subbases For Mark IV/AC Control Units Code 03 must be M.

More information

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300)

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12; DN80-DN300) IOM IR-472-50-bRU Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300) Description: The BERMAD Flow Control and Pressure Reducing Valve with Hydraulic Control is a

More information

Fan-coil valves Series

Fan-coil valves Series Fan-coil valves Series 11-11 - 411 Main features Complete range in the following versions : -way - DN: 1/, /4, 1 -way - DN: 1/, /4, 1 -way with 4 ports - DN: 1/, /4 - The -way version and the -way versions

More information

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features. Page of 7 Application control unit, in conjunction with the associated hydraulic set provides a complete pressure independent balancing and control group for efficient and effective individual room or

More information

The reliable and modular solution for your transfers

The reliable and modular solution for your transfers CHANGEOVER SWITCHES 35A-3200A The reliable and modular solution for your transfers INS-IN-DO-EN-61 CHANGEOVER SWITCHES SDMO CHANGEOVER SWITCHES ARE PERFECTLY SUITED TO ALL POWER FAILURE SITUATIONS Thanks

More information

RANGE. STD Version (Standard): HEE Version (High Energy Efficiency): OPERATION LIMITS. Series LP 46ºC 12ºC 18ºC 5ºC

RANGE. STD Version (Standard): HEE Version (High Energy Efficiency): OPERATION LIMITS. Series LP 46ºC 12ºC 18ºC 5ºC Cooling capacity: Heating capacity: 17,7 to 74,3 kw 21,8 to 84,8 kw Scroll compressors R-410A refrigerant Compact and silent design Cooling solution where an outdoor installation is impossible DESCRIPTION

More information

Air-Cooled Liquid Chiller with integrated hydraulic module

Air-Cooled Liquid Chiller with integrated hydraulic module Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800

More information

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0 APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or

More information

Innovative, High Performance, Quiet Units.

Innovative, High Performance, Quiet Units. Fan Coil Units Innovative, High Performance, Quiet Units. Technical Brochure TM AQF-A.4GB Date : January 2006 Supersedes : TM AQF-A.3GB/04.04 Quality, efficiency and reliability, built into every unit...

More information

ROOM CONTROLLER STRA-04 TECHNICAL CATALOGUE AND INSTALLATION

ROOM CONTROLLER STRA-04 TECHNICAL CATALOGUE AND INSTALLATION ROOM CONTROLLER STRA-04 TECHNICAL CATALOGUE AND INSTALLATION 2 STRA-04 Room Controller - Technical catalogue and installation STRA-04 ROOM CONTROLLER FOR OPTIVENT DESCRIPTION STRA-04 is a preprogrammed

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI SERVICE INSTRUCTION Models Indoor unit Outdoor unit ASU7RLF ASU9RLF ASU2RLF ASU8RLF

More information

lindab comfort Regula Control er

lindab comfort Regula Control er lindab comfort Regula Controller Regula Controller Control equipment for waterborne cooling and heating systems. Use Regula Mono, Duo and Regula Lon control the cooling and heating of a room in sequence

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev. Installation Guide DigiTract 4 Two Stage Heat/Cool Comfort Control System Part #DT4MAN Rev. October 2013 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION...1 SYSTEM DESCRIPTION...1

More information

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits. Page 1 of 12 Application pressure independent control valve (PICV) is used in heating and cooling systems in applications with Fan Coil Units, Air Handling Units or other terminal unit applications. provides

More information

Fan Coil Units. Technical Data. Flexi type unit ECDEN FWD-AT/AF

Fan Coil Units. Technical Data. Flexi type unit ECDEN FWD-AT/AF Fan Coil Units Technical Data Flexi type unit ECDEN11-400 Fan Coil Units Technical Data Flexi type unit ECDEN11-400 Table of Contents 3 I Flexi type unit FWD-AT... 3 FWD-AF... 33 1 2 Fan coil Indoor unit

More information

Product Catalogue ARMONIA Providing indoor climate comfort

Product Catalogue ARMONIA Providing indoor climate comfort Product Catalogue ARMONIA Providing indoor climate comfort ARMONIA 1,3-11 kw Water cassette Main applications Light commercial buildings Offi ces Shops General description Why this choice? Silent operation

More information

Electronically Controlled Hydrostatic Transmissions

Electronically Controlled Hydrostatic Transmissions ally led Hydrostatic Transmissions Product Focus For Mobile s Electro-hydraulic Hydrostatic Transmission Systems If you need a hydrostatic transmission to propel your vehicle, let Eaton do the driving.

More information

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths en Installation Instructions District heating and d.h.w. controller 74 39 68 G25 RVD2 RVD4 Keep these instructions with the controller! Installation Place of installation In a dry room, e.g. the heat exchanger

More information

CWP-CO / CWP-RC / CWP-HP 02 to 35

CWP-CO / CWP-RC / CWP-HP 02 to 35 Water Cooled Water Chillers Cooling Only, Condenserless and Heat Pump Versions - / - / - 02 to 35 8 to 136 9 to 164 Technical Brochure TM -N.4GB Date : March 2006 Supersedes : TM -N.3GB/05.04 Technical

More information

Polygyr -Compact Exhaust Air Temperature Controller

Polygyr -Compact Exhaust Air Temperature Controller Document No. CM1N3405E-P25 Polygyr -Compact Exhaust Air Temperature Controller Features Two outputs for heating and cooling Continuous control signal Application P control Electronic 24 Vac The RCM61.21

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev. Installation Guide DigiTract Two Stage Heat/Cool Comfort Control System Part #DTMAN Rev. February 008 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION... SYSTEM DESCRIPTION... COMPONENT

More information

Time delay relays. The following is a timing diagram of this relay contact's operation:

Time delay relays. The following is a timing diagram of this relay contact's operation: Time delay relays Some relays are constructed with a kind of "shock absorber" mechanism attached to the armature which prevents immediate, full motion when the coil is either energized or de-energized.

More information

ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use.

ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use. ECL COMFORT VI.7C.B4.0 C60 Table of Contents Daily use ECL Comfort User s Guide Section Choose favourite display Select controller mode 3 Adjust room temperature 4 Set personal day plan 5 Advantages of

More information

Ducted medium static pressure monosplit DC Inverter

Ducted medium static pressure monosplit DC Inverter +VAV (Variable Air Volume) Ducted medium static pressure monosplit Unique solutions 20 19 22 For 18-24-30-36 23 24 18 A ++ RC08W 2016 Ducted medium static pressure monosplit FUNCTIONS > Ducted line available

More information

6. Document tasks performed during visit and report any observations to the appropriate

6. Document tasks performed during visit and report any observations to the appropriate Chiller Annual Maintenance RFP Attachment B Services Required Tasking: Vibration Analysis 1. All work shall be performed in accordance with safety policies 2. Check with appropriate customer representative

More information

BUILDING AUTOMATION CONTROL TECHNOLOGY SENSOR TECHNOLOGY PRODUCT CATALOGUE Intelligent solutions for intelligent people.

BUILDING AUTOMATION CONTROL TECHNOLOGY SENSOR TECHNOLOGY PRODUCT CATALOGUE Intelligent solutions for intelligent people. BULDNG AUTOMATON CONTROL TECHNOLOGY SENSOR TECHNOLOGY PRODUCT CATALOGUE 2015 ntelligent solutions for intelligent people. ALRE-T Regeltechnik GmbH Your reliable partner. Soon, Alre T-Regeltechnik GmbH

More information

SLIMZONE CLASSIC /

SLIMZONE CLASSIC / SLIMZONE CLASSIC 2701-001 / 2701-006 ZONE CONTROL SYSTEM INSTALLATION AND OPERATION MANUAL TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 IMPORTANT NOTE...1 1.2 FEATURES...1 1.3 SAFETY INSTRUCTIONS...1 2. APPLICATION

More information

TECHNICAL HANDBOOK. for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL

TECHNICAL HANDBOOK. for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL TECHNICAL HANDBOOK for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL DESCRIPTION * Compatible with IMPACT E, IMAGE E and IMAGE 600² E systems * Configurable as either group control or multisplit * Single

More information

AHN 064 to 304 EHN/CHN 064 to 304

AHN 064 to 304 EHN/CHN 064 to 304 u Horizontal Packaged and Split Air Conditioners AHN 64 to 34 EHN/CHN 64 to 34 6. to 29.2 kw 6.4 to 29.4 kw Engineering Data Manual EDM AECHN-A.1GB Date : June 28 Supersedes : None Technical Description

More information

Appendix A: Inputs, Outputs, and Parameters

Appendix A: Inputs, Outputs, and Parameters Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Appendix A: Inputs, Outputs, and Parameters Introduction This appendix describes the inputs, outputs, and parameters used with the Metasys Zoning

More information

ZONE CONTROLE / 2-WAY

ZONE CONTROLE / 2-WAY ZONE CONTROLE / 2-WAY PRESSURE INDEPENDENT BALANCING AND CONTROL VALVE ON/OFF High-performing and compact, these pressure-independent temperature control valves for variable flow heating and cooling systems,

More information

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI

More information

HYDROCIAT LW R134a. Water cooled chillers USE RANGE

HYDROCIAT LW R134a. Water cooled chillers USE RANGE Screw compressors CIAT direct expansion shell and tubes evaporator equipment (High Power System) Cooling or heating Heat recovery ENVIRONMENTALLY HFC R134a PROTECTION DE FRIENDLY L'ENVIRONNEMENT Cooling

More information

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw Air-to-Water Reverse Cycle Heat Pumps SLH 1202 to 3804 With Screw Compressors 261 to 775 kw 287 to 853 kw Technical Brochure TM SLH-A.2GB Date : November 2004 Supersedes : TM SLH-A.1GB/05.04 Design Features

More information

DTR CG OPTIMA ver.3.0 ( )

DTR CG OPTIMA ver.3.0 ( ) Compact controlling units of supply as well as supply and exhaust air-handling units VS 10 75 CG OPTIMA VS 40 150 CG OPTIMA SUP VS 40 150 CG OPTIMA SUP EXH Operating and maintenance manual DTR CG OPTIMA

More information

Split-Sky Air FDYP-B7 Concealed Ceiling Unit

Split-Sky Air FDYP-B7 Concealed Ceiling Unit TECHNICAL DATA Split-Sky Air FDYP-B7 Concealed Ceiling Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the

More information

Models: 12 and 18. Models: 24 to 60

Models: 12 and 18. Models: 24 to 60 SPLIT CASSETTE TYPE MUCSR-H8 Series SCOP 4.0 Models: 12 and 18 RG57B2/BGE Included (CL 94 982) Models: 24 to 60 Design 360 Thanks to the 360 panel design, the air is more evenly distributed. Drainage pump

More information

Electronic Refrigerator Diagnostics

Electronic Refrigerator Diagnostics Electronic Refrigerator Diagnostics IMPORTANT SAFETY NOTICE The information in this presentation is intended for use by individuals possessing adequate backgrounds of electrical, electronic, & mechanical

More information

Water terminals from 91 to 1548 m 3 /h. from 0,5 to 9,6 kw. SysCoil Comfort. Floor and ceiling fan coil units. from 0,6 to 13,6 kw

Water terminals from 91 to 1548 m 3 /h. from 0,5 to 9,6 kw. SysCoil Comfort. Floor and ceiling fan coil units. from 0,6 to 13,6 kw Water terminals from 91 to 1548 m 3 /h SysCoil Comfort Floor and ceiling fan coil units from 0,5 to 9,6 kw from 0,6 to 13,6 kw SysCoil Comfort Innovation for an optimum comfort ErP 2018 TERTIAIRY H 3 /h

More information

Temperature Controller (Heat Pumps)

Temperature Controller (Heat Pumps) 3 345 Temperature Controller (Heat Pumps) For comfort control in HVAC systems RWD31 RWD41 Stand-alone electronic temperature controller Four 2-position (On/Off) outputs Easy adjustment of parameters via

More information

RVD125/109 RVD145/109

RVD125/109 RVD145/109 G2511 en Installation Instructions District heating and d.h.w. controller RVD125/109 RVD145/109 Installation without base Place of installation Compact station front or control panel front Permissible

More information

Digital Room Thermostats with Touch Screen LCD

Digital Room Thermostats with Touch Screen LCD TC40 Touch Series Digital Room Thermostats with Touch Screen LCD Revision Date February 22, 2013 Features Wall-mount Display Control to match any decor Extra large easy-to-read Liquid Crystal Display (LCD),

More information

The GSCP1 is a very powerful controller for its size, and it is. All switching gear and controls are locally mounted at the

The GSCP1 is a very powerful controller for its size, and it is. All switching gear and controls are locally mounted at the Paralleling The Clarke Way 30 Paralleling The Clarke Way Our systems utilize a compact modular design to reduce wiring requirements The GSCP1 is a very powerful controller for its size, and it is expandable.

More information

Ultrasonic Cleaning Generator PCB type with ON/OFF Feature

Ultrasonic Cleaning Generator PCB type with ON/OFF Feature Ultrasonic Cleaning Generator PCB type with ON/OFF Feature Technical Specifications Bosan Industrial Technology Ltd. Flat 7, 5/F., Kai Fuk Industrial centre, 1 Wang Tung Street, Kowloon Bay, Kowloon, Hong

More information

SYSCOIL 2. Range of fan coil units. Chillers & Heat Pumps Water terminals Roof tops Close control Water source heat pumps Direct expansion

SYSCOIL 2. Range of fan coil units. Chillers & Heat Pumps Water terminals Roof tops Close control Water source heat pumps Direct expansion Chillers & Heat Pumps Water terminals Roof tops Close control Water source heat pumps Direct expansion SYSCOIL 2 Range of fan coil units from 0.5 to 9.1 kw from 0.8 to 12.6 kw SYSCOIL 2 Innovation for

More information

Touch Sensor 2 plus Installation Instructions

Touch Sensor 2 plus Installation Instructions 2-channel 3-channel (1+2) 6-channel (2+4) Order no.: 2052 xx Order no.: 2053 xx Order no.: 2056 xx Contents 1. Function 2. Display window 3. Configuration 4. Locking of functions 5. Room temperature controller

More information

COMMERCIAL CONCENTRATED ENERGY ELECTRIC BOILER 22.5 KW TO 180 KW

COMMERCIAL CONCENTRATED ENERGY ELECTRIC BOILER 22.5 KW TO 180 KW ELECTRIC BOILER 22.5 KW TO 80 KW COMMERCIAL CONCENTRATED ENERGY The VOLTMAX line of electric boilers was developed to efficiently supply hydronic heating systems in commercial, institutional and industrial

More information

AL-KO HYDRAULIC STATIONS HYDRO-OPT S and AL-KO HYDRO-OPT M SMART ENERGY SAVING.

AL-KO HYDRAULIC STATIONS HYDRO-OPT S and AL-KO HYDRO-OPT M SMART ENERGY SAVING. AL-KO HYDRAULIC STATIONS HYDRO-OPT S and AL-KO HYDRO-OPT M SMART ENERGY SAVING. SIMPLE INGENIOUS QUALITY MAKES SAVING ENERGY A PIECE OF CAKE Whether for structural reasons or due to the quality of exhaust

More information

Electronic Control Valves

Electronic Control Valves 131 Series (Full Internal Port) 631 Series (Reduced Internal Port) MODEL Electronic Control Valves Model 131-01/631-01 Simple Proven Design Quality Solenoid Pilot Controls Ideal For SCADA Systems Multi-Function

More information