SEASONAL MAINTENANCE CHECKLISTS Johnson Controls

Size: px
Start display at page:

Download "SEASONAL MAINTENANCE CHECKLISTS Johnson Controls"

Transcription

1 SPRING CHECK LIST ABSORPTION CHILLERS Check starter and control panel. Leak test. Check hand valve diaphragms and replace as required. Check operation of purge unit. Change oil in the purge pump. Lubricate purge pump motor and change belt. Clean magnetic strainer on the solution motor cooling circuits. Review manufacturer's recommendation for start-up. Check auxiliary equipment operation. Check and test all operating and safety controls. Check solution pump motor operation. Log all operating conditions after unit stabilizes. Add octyl alcohol. Trim solution concentration to maximum efficiency. A Lithium Bromide solution sample should be taken for test lab analysis. Review operation procedures. AUTOMATIC TEMPERATURE CONTROLS AIR COMPRESSOR Drain tank and check traps. Change oil and check oil pressure. Check belt and sheaves, then change as required. Change suction filter as required. Check unloader and check valve. Check high pressure safety valve. 1

2 Check motor operating conditions and lubricate. Check PE switch, starter and alternator. Record compressor run time. REFRIGERATED AIR DRYER Check refrigerant pressure. Check refrigerant temperature. Clean condenser and cover grilles. FILTER AND PRESSURE REDUCING STATION Check particle filters (change as required). Check oil filter (change as required). Check pressure reducing valve settings. Check low pressure safety valve. BOILER, CHILLER, CONVERTER PUMPS AND ZONE CONTROLS Calibrate all controllers. Calibrate all transmitter and receiver gauges. Check all PE switches. Check all control valves. Check all pilot positioners. Check all auxiliary control devices. FAN SYSTEMS AND HVAC UNIT CONTROLS Review sequence of operation. Check all dampers and lubricate. Check pilot positioners. Check all control valves. Calibrate all controllers. Calibrate all transmitters and receiver gauges. 2

3 Check all solenoid air valves, PE switches and air valves. Check all auxiliary control devices. ROOM TERMINAL UNIT CONTROLS Check all room thermostats. Check all control valves. Check operation of unit coil steam traps. Check operation of all dampers and lubricate. Check all PE switches, solenoid air valves and limit controls. Check operation of all auxiliary devices. CENTRIFUGAL CHILLERS Check main starter and control panel. Leak test. Inspect condenser tubes for fouling clean as necessary. Meg compressor motor and oil pump motor. Change oil and filters. Test oil for acidity. Check operation of purge unit. Clean purge drum and oil separator. Change oil in purge pump and oil separator. Lubricate purge pump motor and change belt. Lubricate inlet vane linkage. Check oil pump heater operation. Review manufacturer's recommendations for start-up. Check auxiliary equipment operation. Check refrigerant and oil levels. Check oil pump heater and purge oil heater. Check and test all operating and safety controls. 3

4 Log all operating conditions after unit stabilizes. Review operating procedures. Purge operation. Check sight glass and drain non-condensables from purge. An oil sample should be taken after start-up for test lab analysis. CHILLED WATER COIL COOLING Lubricate fan bearings per manufacturer's recommendation. Lubricate motor bearings per manufacturer's recommendation. Check belts and sheaves. Replace and adjust as required. Lubricate and adjust dampers and linkage. Inspect filters. Check motor operating conditions. Inspect electrical connections, contactors, relays and operating/safety controls. Check and clean strainers and humidifier. Check hand valves and steam traps. Check and clean drains and drain pans. Check heating coils. Secure unit panels and inspect roof curb flashing. COOLING TOWER Remove all debris from within and around unit then flush as required. Check and clean strainers, bleed, overflow and drain. Lubricate fan and motor bearings per manufacturer's recommendation. Change oil in gear reducer assembly per manufacturer's recommendation. Check belts, motor pulley and motor mounts. Replace and adjust as required. Inspect electrical connections, contactors, relays and operating/safety controls. Check motor operating conditions. Clean float valve assembly and check for proper operation. Check operating conditions. Adjust as required. 4

5 DIRECT EXPANSION COOLING SEASONAL MAINTENANCE CHECKLISTS Lubricate fan bearings per manufacturer's recommendation. Lubricate motor bearings per manufacturer's recommendation. Check belts and sheaves. Replace and adjust as required. Check and clean coils. Straighten fins as required. Lubricate and adjust dampers and linkages. Check and clean drain pan and drains. Inspect filters. Check motor operating conditions. Inspect electrical connections, contactors, relays and operating/safety controls. Check compressor oil level, acid test oil and meg motor. Check crankcase heater operation. Start compressor, check operating conditions and adjust as required. Secure unit panels and inspect roof curb flashing. Inspect for refrigerant leaks. Check operating conditions and adjust as required. HEAT EXCHANGER HUMIDIFIERS Visually check for leaks. Tighten connections. Verify pressure gauge and thermometer accuracy. Check and clean strainers. Check steam traps and hand valves. Check operating safety devices. Clean exterior surfaces as required. Check and clean strainers. Check steam trap and hand valves. Clean and check float assembly. Check and clean drains and drain pan. Clean heating element. 5

6 STEAM PRV SEASONAL MAINTENANCE CHECKLISTS Inspect electrical connections, relays, contactors and operating and safety controls. Clean plugged spray nozzles. Check unit operating conditions. Clean exterior surfaces as required. Verify accuracy of gauges. Check unit operation and lubricate as required. Clean as required. FANS & CENTRAL FAN SYSTEMS Check and clean fan assembly. Lubricate fan bearings per manufacturer recommendations. Lubricate motor bearings per manufacturer's recommendations. Check belts and sheaves. Replace and adjust as required. Tighten all nuts and bolts. Check motor mounts and vibration pads. Replace and adjust as required. Check motor operating conditions. Inspect electrical connections and contactors. Lubricate and adjust associated dampers and linkage. Check fan operation. Clean outside air intake screen. Check and clean drains and drain pans. Check and clean strainers, check steam traps and hand valves. Check filter advancing mechanism. Lubricate and adjust as required. Inspect filters. Check heating and cooling coils. Inspect humidifier. 6

7 Clean external surfaces as required. CONDENSERS AIR COOLED Remove all debris from within and around unit. Inspect for leaks. Check belts, pulleys and mounts. Replace and adjust as required. Lubricate fan and motor bearings per manufacturer's recommendation. Inspect electrical connections, contactors, relays and operating and safety controls. Check motor operating conditions. Check and clean fan blades as required. Check and clean coil. Straighten fins as required. Check operating conditions. Adjust as required. HOT WATER BOILERS Inspect fire side of boiler and record condition. Brush and vacuum soot and dirt from flues and combustion chamber. Inspect firebrick and refractory for defects. Patch and coat as required. Visually inspect boiler pressure vessel for possible leaks and record condition. Disassemble, inspect and clean low-water cutoff. Check hand valves and automatic feed equipment. Repack and adjust as required. Inspect, clean and lubricate the burner and combustion control equipment. Check burner sequence of operation and combustion air equipment. Check fuel piping for leaks and proper support Clean external surfaces as required. Clean boiler room. Review log. Log all operating conditions. Test low water cut-off and pressure relief valve. Check operating and safety controls. 7

8 Review boiler operation with boiler operator. PUMPS Lubricate pump bearings per manufacturer's recommendations. Lubricate motor bearings per manufacturer's recommendations. Tighten all nuts and bolts. Check motor mounts and vibration pads. Replace and adjust as required. Visually check pump alignment and coupling. Check motor operating conditions. Inspect electrical connections and contactors. Check and clean strainers, then check hand valves. Inspect mechanical seals. Replace as required or inspect pump packing. Replace and adjust as required. Verify gauges for accuracy. Clean external surfaces as required. Check suction and discharge pressures. RECIPROCATING CHILLERS Inspect for leaks. Check belts, sheaves and coupling alignment. Replace and adjust as required. Check compressor oil level, acid test oil and meg hermetic motor. Change oil and refrigerant filter-dryer as required. Check compressor crankcase heater operation. Check vibration eliminators. Replace or adjust as required. Inspect electrical connections, contactors, relays and operating/safety controls. Clean external surfaces as required. Review manufacturer's recommendation for start-up. Check auxiliary equipment operation. Energize crankcase heater per manufacturer's recommendation for crankcase warm-up. 8

9 Check and test all operating and safety controls. Start chilled water pump, condenser water pump and cooling tower. Check refrigerant charge, oil and oil pressure. Log all operating conditions, after unit stabilizes. Review operating procedures. Inspect chiller and make adjustments as required. Cycle operating controls and check unloaders. Review chiller operation. STEAM BOILERS Inspect boiler and burner, then make adjustments as required. Test low water cut-off and pressure relief valve. Check operating and safety controls. Review boiler operations with boiler operator. Log all operating conditions. Shut off burner and open electrical disconnect. Close fuel supply valves. Thoroughly blow down boiler. WATER TREATMENT COOLING TOWERS Operate all chemical bleed and feed equipment to assure proper operation. Chemically test the system water for proper bleed rate and treatment levels. Adjust the controls to obtain proper operation. Visually inspect the open portions of the system for evidence of corrosion, scale or slime and algae growth. Slug feed biocide and antiform to control slime and algae growth. Furnish a written report of the test and inspection results including recommendations. Inventory the remaining water treatment chemicals and reorder as required. 9

10 CLOSED SYSTEMS Chemical test the system water for proper treatment levels. Adjust the treatment level for proper operation. Furnish a written report of the test and inspection results including recommendations. ASSOCIATED EQUIPMENT UNIT VENTILATOR FAN COILS RADIATION Brush and vacuum grilles, coil, fan and unit interior. Lubricate fan and motor bearings per manufacturer's recommendations. Check belt and sheaves. Replace and adjust as required. Check and clean drains and drain pan. Check and clean strainers. Check steam traps and hand valves. Inspect filters. Check unit operating conditions. Lubricate and adjust dampers and linkage. Brush and vacuum grilles, coil, fan and unit interior. Lubricate fan and motor bearings per manufacturer's recommendations. Check belt and sheaves. Replace and adjust as required. Check and clean drains and drain pan. Check and clean strainers. Check steam traps and hand valves. Inspect filters. Check unit operating conditions. Lubricate and adjust dampers and linkage. Visually inspect fins/cast iron. Clean as required. Check and clean strainers. Check traps and hand valves. INDUCTION UNITS 10

11 Visually inspect coil. Clean as required. Check and clean drains and drain pans. Clean discharge grille. Check and clean strainers. Check and clean steam traps and hand valves. REHEAT COILS Visually inspect coil. Clean as required. Check and clean strainers. Check steam traps and hand valves. Inspect electrical connections, relays, contactors and operating and safety controls. BOXES DUAL DUCT AND VARIABLE AIR VOLUME Inspect box for duct work connection. Lubricate and adjust dampers and linkage. FALL PRESEASON CHECK LIST BOILERS Check safety relief valve. Check combustion controls. Check piping and connections. Check low water cutoff. Check water make-up system. Check room air intake system. Check valves. Check water level gauge glass and controls. Disassemble low water cutoff. Clean low water cutoff. Check contacts. Check mercury bulbs. Check wiring. Reassemble low water cutoff. 11

12 Clean internal surfaces (as required). Clean external surfaces (as required). Clean burner assembly. Clean make-up water components. Clean hi-water components. Clean fireside. Clean flues. Inspect refractory. Blowdown mud legs. Blowdown gauge glass. Blowdown feeder cutoff switch (steam). Prepare machine for winter conditions. Log machine condition at departure. ELECTRIC BOILERS OIL BOILERS Check magnetic contactors. Check pressure control. Check hi-limit switch. Check step controller. Check burner operation. Check burner control system. Check fuel pump. Check fuel valves (for tight seating). Check oil heater(s). Check tank heater. Check fluid system. 12

13 GAS BOILERS Check for fuel leaks. Check linkage. Check flame detection. SEASONAL MAINTENANCE CHECKLISTS Check flue gas temperature and content. Check burner operation. Check gas booster. Check gas regulator. Check linkage. Check for gas leaks. Check gas safety switch. Check gas valves (for tight seating). Check flue gas temperature and content. STEAM BOILERS Check condensate float valve. Check condensate return pumps. Check condensate tank. Check pumps. Check gas safety switches. Check pressure controls. Check draft fans/switches. HOT WATER BOILERS Check circulating pump system. Check water cutoff. Check water feeder. Check shutoff valves. 13

14 Check temperature controls. Check draft system. AUTOMATIC TEMPERATURE CONTROLS AIR COMPRESSOR Drain tank and check traps. SEASONAL MAINTENANCE CHECKLISTS Change oil and check oil pressure. Check belt and sheaves and change as required. Change suction filter as required. Check unloader and check valve. Check high pressure safety valve. Check motor operating conditions and lubricate. Check PE switch, starter and alternator. Clean and paint as required. REFRIGERATED AIR DRYER Check refrigerant pressure. Check refrigerant temperature. Clean condenser and cover grilles. Check drain trap and bypass valves. FILTER AND PRESSURE REDUCING STATION Check particle filters (change as required). Check oil filter (change as required). Check pressure reducing valve settings. Check low pressure safety valve. BOILER Calibrate all controllers. Calibrate all transmitter and receiver gauges. 14

15 Check all PE switches. Check all control valves. Check all pilot positioners. SEASONAL MAINTENANCE CHECKLISTS Check all auxiliary control devices. FAN SYSTEMS AND HVAC UNIT CONTROLS Review sequence of operation. Check all dampers and lubricate. Check pilot positioners. Check all control valves. Calibrate all controllers. Calibrate all transmitters and receiver gauges. Check all solenoid air valves, PE switches and air valves. Check all auxiliary control devices. ROOM TERMINAL UNIT CONTROLS Check all room stats. Check operation of unit coil steam traps. WATER TREATMENT OPEN STEAM BOILERS Operate all chemical bleed and feed equipment to assure proper operation. Chemically test the system water for proper bleed rate and treatment levels. Adjust controls to achieve proper operation. Furnish a written report of the test and inspection results including recommendations. Inventory the remaining water treatment chemicals supply and reorder as required. CLOSED SYSTEMS Chemically test the system water for proper treatment levels. Adjust the treatment level for proper operation. 15

16 Furnish a written report of the test and inspection results including recommendations. Inventory the remaining water treatment chemicals supply and re-order as required. FANS & CENTRAL FAN SYSTEMS Check and clean fan assembly. Lubricate fan bearings per manufacturer's recommendations. Lubricate motor bearings per manufacturer's recommendations. Check belts and sheaves. Replace and adjust as required. Tighten all nuts and bolts. Check motor mounts and vibration pads. Replace and adjust as required. Check motor operating conditions. Inspect electrical connections and contactors. Lubricate and adjust associated dampers and linkage. Check fan operation. Check and clean drains and drain pans. Check and clean strainers, check steam traps and hand valves. Check filter advancing mechanism. Lubricate and adjust as required. Inspect filters. Check heating coils. Inspect humidifier. ASSOCIATED EQUIPMENT UNIT VENTILATOR Brush and vacuum grilles, coil, fan and unit interior. Lubricate fan and motor bearing per manufacturer's recommendations Check belt and sheaves. Replace and adjust as required. Check and clean drains and drain pan. Check and clean strainers. Check steam traps and hand valves. Inspect filters. 16

17 Check unit operating conditions. SEASONAL MAINTENANCE CHECKLISTS Lubricate and adjust dampers and linkage. Clean and paint exterior surfaces as required. FAN COILS / UNIT HEATERS RADIATION Brush and vacuum coil, fan and housing as required. Lubricate fan and motor bearings per manufacturer's recommendations. Check belt and sheaves. Replace and adjust as required. Check and clean strainers. Check steam traps and hand valves. Inspect electrical connections, contactors, relays and operating/safety controls. Check unit operation. Adjust as required. Visually inspect fins/cast iron. Clean as required. Check and clean strainers. Check steam traps and hand valves. INDUCTION UNITS Visually inspect coil. Clean as required. Check and clean drains and drain pans. Clean discharge grille. Check and clean strainers. Check steam traps and hand valves. REHEAT COILS Visually inspect coil. Clean as required. Check and clean strainers. Check steam traps and hand valves. BOXES DUAL DUCT AND VARIABLE AIR VOLUME Inspect box for duct work connection. Lubricate and adjust dampers and linkage. MISC. HVAC EQUIPMENT HEAT EXCHANGER Visually check for leaks. Tighten connections. 17

18 HUMIDIFIERS STEAM PRV SEASONAL MAINTENANCE CHECKLISTS Verify pressure gauge and thermometer accuracy. Check and clean strainers. Check steam traps and hand valves. Check operating safety devices. Check and clean strainers. Check steam trap and hand valves. Clean and check float assembly. Check and clean drains and drain pan. Clean heating element. Inspect electrical connections, relays, contactors and operating and safety controls. Clean plugged spray nozzles. Check unit operating conditions. Verify accuracy of gauges. Check unit operation and lubricate as required. UNITARY EQUIPMENT HEATING STEAM, HOT WATER, ELECTRIC, GAS OR OIL BURNER Lubricate fan bearings per manufacturer's recommendation. Lubricate motor bearings per manufacturer's recommendation. Check belts and sheaves. Replace and adjust as required. Check cooling coil, clean and straighten fins as required. Lubricate and adjust dampers and linkages. Check and clean drain pan and drains. Inspect filters. Check motor operating conditions. Inspect electrical connections, contactors, relays and operating/safety controls. Check and clean strainers and check hand valves. Secure unit panels and inspect roof curb flashing. 18

19 Inspect, clean and lubricate the burner and combustion control equipment. Check burner sequence of operation and combustion air equipment. END-OF-SEASON AIR CONDITIONING CHECK LIST REFRIGERATION SYSTEMS GENERAL Pump down refrigeration system (if no longer required). Close inlet and outlet valves. Check vessel connections for leaks. Check condenser and receiver relief valves for leaks. Disconnect power supply to the control circuit. Tag "off season." Check refrigeration system and piping for possible repairs. Calibrate pressure gauges and thermometers. Check safety controls for proper setting and operation. Clean and tighten electrical connections. Lab test lithium bromide and refrigerant water samples. COMPRESSORS AND MOTORS Schedule full or partial dismantling of the compressor. Check valve wear. Check bearing wear. Check for misalignment. Drain, check and clean oil reservoir. Change oil filters, clean strainers. Take oil sample for laboratory analysis. Check oil heaters and controls. Check thrust bearing end-clearance and record. Inspect inlet damper mechanisms for cracks and wear. Clean all sight glasses. 19

20 Overhaul purge unit. SEASONAL MAINTENANCE CHECKLISTS Change oil in speed increaser gear sets. Check open drive motor couplings for wear and alignment. Clean motor windings and lubricate bearings. Cover motors subject to airborne contaminants. HEAT TRANSFER SURFACES Blow air through condenser to remove trapped water. Circulate anti-freeze solution through condenser and water piping. Remove condenser heads and clean tubes. Inspect condensers for signs of corrosion. Evaluate water treatment. COOLING TOWERS Disassemble, clean, reassemble float and ball-cock valves. Wash down interior of the cooling tower. Clean perforated head pans and spray nozzles. Drain and flush tower pans. Drain and flush pipelines. Drain and flush pumps. Lock closed automatic "fill" valves. Remove and clean strainers and screens. Inspect tower fans and drives for wear, cracking and corrosion. Cover fan and louver openings subject to airborne dirt. Check pump motor bearings and lubricate. Paint all metal parts subject to alternate wetting and drying. AIR COOLED CONDENSERS Clean, inspect and cover air cooled condensers. 20

21 Clean and check fan blades. SEASONAL MAINTENANCE CHECKLISTS Inspect and lubricate fan bearings. Loosen fan belts or remove. AIR HANDLING COILS Drain and flush coils with antifreeze solution. Clean coil face. Clean condensate traps. Clean and drain pans. Check and calibrate freezestat controls in air ducts. Install freeze alarms in ducts. FREEZING WEATHER CHECK LIST BOILER AND PIPING Drain and blow out all idle equipment. Check service water lines for possible freezing. Replace damaged insulation. Check tracing around control lines and transmitter boxes. Check all steam traps for proper function. COMPRESSOR AIR SYSTEMS Check air driers. Drain air tanks. Check aftercoolers and intercoolers. Drain, blow out, and flush with glycol all idle compressor jackets. AIR CONDITIONING AND REFRIGERATING SYSTEMS Drain, blow out, and flush all seasonal equipment, condenser lines, tubing and piping. Check all outside dampers. Cut back cooling tower fan speeds. 21

22 PRESSURE VESSEL VENTS Correct low spots in long runs. Drain loops and bends. SEASONAL MAINTENANCE CHECKLISTS Enlarge vent diameters at point of outside discharge. Protect vessel vents from ice or snow accumulation. RELIEF VALVES Protect against snow or ice accumulation. Clear relief valve body drains. Protect valve discs from freezing shut. Relocate relief valves to heated areas wherever possible. MECHANICAL EQUIPMENT Drain all idle pumps and compressors. Make sure jackets are vented. Provide proper lubrication for cold weather operation. Provide heated enclosures around operating equipment wherever possible. Install no-flow switches and alarms in cooling water lines. PERSONNEL AND PROCEDURES Institute a freeze-up procedure and educate all personnel in its use. Appoint a "weather watcher" to monitor weather reports. Instruct personnel in the proper methods of thawing out frozen equipment safely. Provide cold weather gear (gloves, heavy clothing, etc.). Recruit standby personnel to monitor instrumentation when needed. Set up priority for steam usage in order to keep critical equipment in use and provide adequate tracing steam. Copyright 1986, 2009, By Refrigeration Service Engineers Society. 22

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis. CENTRIFUGAL CHILLER Annual Inspection Refrigerant Circuit Check and record refrigerant level Inspect for leak results Calculate refrigerant lass and report to the customer. Repair minor leaks as required

More information

6. Document tasks performed during visit and report any observations to the appropriate

6. Document tasks performed during visit and report any observations to the appropriate Chiller Annual Maintenance RFP Attachment B Services Required Tasking: Vibration Analysis 1. All work shall be performed in accordance with safety policies 2. Check with appropriate customer representative

More information

BOILER PM & INSPECTION

BOILER PM & INSPECTION BOILER PM & INSPECTION Record inspection log for Gaming Commission and Safety Department. The following listed maintenance items are not intended to be a complete list. Follow any additional maintenance

More information

Electric Duct Heater X X X X X X

Electric Duct Heater X X X X X X EHIBIT B-SERVICE SCHEDULE & CHECKLIST Electric Duct Heater Comprehensives Check overall condition of unit Check for unusual noise and vibration Check Voltage Check Controls Check and insure that heater

More information

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , , Table 5.1.1.2 Summary of Sprinkler System Inspection, Testing, and Maintenance Item Frequency Reference Inspection Gauges (dry, preaction, and deluge systems) Quarterly 5.2.4.2, 5.2.4.3, 5.2.4.4 Control

More information

AIR COOLED CHILLERS WATER COOLED CHILLERS

AIR COOLED CHILLERS WATER COOLED CHILLERS AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with

More information

Secondary Coolant 301

Secondary Coolant 301 Secondary Coolant 301 Instructor Rusty Walker Hill PHOENIX Learning Center Secondary Coolant 301 Start-Up Procedures Secondary Coolant 301 Objectives Describe the initial startup procedures for a medium

More information

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8 , Chapter 8 as amended by CCR, Title 19 Page 1 of 8 Address: City: Date of Pump Test: Shaft Orientation: Horizontal Vertical Annual Fire Pump Test Results Number of pumps at this location: If multiple

More information

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY SECTION 230533 - PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pressure gages. 2. Pressure gage taps. 3. Thermometers. 4. Thermometer supports. 5. Test plugs. 6. Static pressure

More information

Heating and Gas Installations - December 2014

Heating and Gas Installations - December 2014 This is an example of good practice maintenance specifications. It is not exhaustive and should only be used to assist with facilities management or specification of a maintenance contract. Emergency Gas

More information

ENGINE COOLING SECTION GENERAL DESCRIPTION / 1 ENGINE COOLING. Figure 1 - Cooling System Flow

ENGINE COOLING SECTION GENERAL DESCRIPTION / 1 ENGINE COOLING. Figure 1 - Cooling System Flow SECTION 09-302.03 09-302.03/ 1 2006JA26 1. COOLANT INLET FROM RADIATOR 2. WATER PUMP SUCTION 3. COOLANT FILTER INLET 4. COOLANT FILTER OUTLET 5. COOLANT SUPPLY TO CYLINDER HEAD 6. COOLANT RETURN FROM CYLINDER

More information

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1 26 - COOLING SYSTEM CONTENTS Page LAND ROVER V8 DESCRIPTION AND OPERATION ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 FAULT DIAGNOSIS COOLING SYSTEM FAULTS... 1 REPAIR COOLANT - DRAIN

More information

Air-to-water heat pump for indoor installation - LIK 8TES. Spare parts list

Air-to-water heat pump for indoor installation - LIK 8TES. Spare parts list Spare parts list Brand: Dimplex Type: LIK 8TES Part number: 366030 Position Description Part number Serv. ind. 1 Compressor 4522354115 2 Evaporator 4521612802 3 Expansion valve 4521614106 4 Inspection

More information

Don Searles Check List For Dredging Equipment Surveys

Don Searles Check List For Dredging Equipment Surveys Don Searles Check List For Dredging Equipment Surveys 1. General 1.1. Take pictures of everything important. Take pictures showing the side of the dredge 1.2. Inspect logs and maintenance records. Get

More information

TC Series Cooling Systems

TC Series Cooling Systems TC Series Cooling Systems Table of Contents Table of Contents...1 List of Figures...1 Safety...2 Introduction...2 General Specifications...2 Types of Coolant...2 Routine Maintenance...2 Surge Tank Coolant

More information

SECTION METERS AND GAGES FOR PLUMBING PIPING

SECTION METERS AND GAGES FOR PLUMBING PIPING PART 1 GENERAL 1.01 SECTION INCLUDES A. Positive displacement meters. B. Flow meters. SECTION 22 0519 METERS AND GAGES FOR C. Pressure gages and pressure gage taps. D. Thermometers and thermometer wells.

More information

SCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS

SCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS SCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS 1 to 40 Nominal Tons Rev-01 TABLE OF CONTENTS Page: Description 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Product Nomenclature Air Cooled Chiller

More information

MANUAL CONTROL / SEMIAUTO TEMPERATURE CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

MANUAL CONTROL / SEMIAUTO TEMPERATURE CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM SECTION 7C MANUAL CONTROL / SEMIAUTO TEMPERATURE CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM CAUTION: Disconnect the negative battery cable before removing or installing any electrical unit

More information

Routine Compressor Maintenance

Routine Compressor Maintenance Establishing a regular, well-organized maintenance program and strictly following it is critical to maintaining the performance of a compressed air system. One person should be given the responsibility

More information

COOLING SYSTEM - V8. Cooling system component layout DESCRIPTION AND OPERATION

COOLING SYSTEM - V8. Cooling system component layout DESCRIPTION AND OPERATION Cooling system component layout 26-2-2 DESCRIPTION AND OPERATION 1 Heater matrix 2 Heater return hose 3 Heater inlet hose 4 Heater inlet pipe 5 Throttle housing 6 Connecting hose 7 Throttle housing inlet

More information

PACKAGED LIQUID CHILLER 6. HUMIDIFIER SECTIONS. C Member. Liquid Chiller. nowlc And noalc Series

PACKAGED LIQUID CHILLER 6. HUMIDIFIER SECTIONS. C Member. Liquid Chiller. nowlc And noalc Series 6. HUMIDIFIER SECTIONS Liquid Chiller nowlc And noalc Series C Member 1 Features and Benefits OMRAN cold generator reciprocating Liquid chiller are designed and built to provide reliable,efficient performance

More information

EXHIBIT A SCOPE OF SERVICES MAINTENANCE OF TRANE HVAC SYSTEMS

EXHIBIT A SCOPE OF SERVICES MAINTENANCE OF TRANE HVAC SYSTEMS EXHIBIT A SCOPE OF SERVICES MAINTENANCE OF TRANE HVAC SYSTEMS DISTRICT VII, HEADQUARTERS FACILITY AND TAMPA BAY SUNGUIDE REGIONAL TRAFFIC MANAGEMENT CENTER DISTRICT VII, HEADQUARTERS FACILITY I. PURPOSE:

More information

Public Review Draft. ASHRAE Standard

Public Review Draft. ASHRAE Standard BSR/ASHRAE/ACCA Addendum a to ANSI/ASHRAE/ACCA Standard 180-2008 Public Review Draft ASHRAE Standard Proposed Addendum a to Standard 180-2008, Standard Practice for Inspection and Maintenance of Commercial

More information

Biogas safety control equipment

Biogas safety control equipment Biogas safety control equipment As environmental concerns and energy efficiency are increasing, efficient economical and safe gas control systems become an increasingly important part of operating the

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS INSTALLATION, START-UP AND SERVICE INSTRUCTIONS P705 Refrigeration Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................. 1 HANDLING.......................................

More information

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller DISCONTINUED PRODUCT CSI 15621 - Mainframe Cooling Systems 1.1 SUMMARY Liebert CSU3000 CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller GUIDE SPECIFICATIONS 1.0 GENERAL These specifications describe

More information

Engine Compartment Inspection

Engine Compartment Inspection Engine Compartment Inspection Unit Contents Student Page Student Components Learning Activities Sheet... 7 3 Abbreviated Checklist.... 7 5 Objective Sheet... 7 7 Expanded Checklist... 7 9 * Job Sheets

More information

Component Coverage* A/C Presidential Plan. A/C Executive Plan $ $278

Component Coverage* A/C Presidential Plan. A/C Executive Plan $ $278 Honest Abe Plumbing, Heating, and Cooling is pleased to offer you our exclusive maintenance agreements. Our Executive and Presidential plans not only offer our thorough annual inspection, and priority

More information

Program IV: ProStar TM. Performance A/C International. Series. Study Guide Performance A/C Program IV: International ProStar Series TMT

Program IV: ProStar TM. Performance A/C International. Series. Study Guide Performance A/C Program IV: International ProStar Series TMT Performance A/C International A N AV I S TA R C O M PA N Y Program IV: ProStar TM Study Guide TMT-160701 Series Study Guide Performance A/C Program IV: International ProStar Series TMT-160701 2007 International

More information

FD68 BURNERS SELECTION GUIDE & ENGINEERING SPECS

FD68 BURNERS SELECTION GUIDE & ENGINEERING SPECS SELECTION GUIDE The following data can be used to fill in the information appropriate for the burner size required: FD68 C A 150 L M BD FORCED DRAFT MODEL 68 FUEL A-OIL ONLY G-GAS ONLY C-GAS/OIL TYPE OF

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL HP COMBINATION GAS/OIL BURNERS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone 316-421-0480, Fax 316-421-0948

More information

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)

More information

Lubrication & Cooling Systems

Lubrication & Cooling Systems Study Guide Chapter 14 Pages 393 432 44 Points 1. The life span of an engine depends largely upon its & systems. Lube & Cooling The American Petroleum Institute (API) rates oil service classification.

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-5 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR AIR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for difficult

More information

next dx next dx rcgroupairconditioning NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans.

next dx next dx rcgroupairconditioning NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans. NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans. Cooling Capacity: 6,4 97,4 next dx C rcgroupairconditioning R410 E C UP FLOW DOWN FLOW MIN FETURES

More information

Hydraulic Pumping System

Hydraulic Pumping System Hydraulic Pumping System Easy-Kleen Pressure Systems LTD. 41 Earnhardt Road Sussex Corner, NB E4E 6A1 1 800 315 5533 1 HD SERIES PUMPING SYSTEM WITH HYDRAULIC MOTOR: OPERATION 1. Place unit on level and

More information

Air-Cooled Screw Compressor Chiller

Air-Cooled Screw Compressor Chiller Installation, Operation and Maintenance Manual IOMM ALS Group: Chiller Part Number: 070774401 Date: February 1998 Supersedes: IM 548-3 Air-Cooled Screw Compressor Chiller ALS 070A through 425A 60 Hertz

More information

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE Technical Data SD 4011 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE A SERIES AIR ADJUSTED PILOT PRINTED IN U.S.A. SD 4011/9504 Type A or A83 (wt 6 lb) Type A53 or A 85

More information

FABER BURNER ROUTINE MAINTENANCE

FABER BURNER ROUTINE MAINTENANCE FABER BURNER ROUTINE MAINTENANCE Version 2016 The Faber burner is designed for minimal maintenance; however, the frequency and quantity of maintenance that is required depends upon many factors which vary

More information

SECTION H3 TRAYMASTER SERIES DEAERATORS

SECTION H3 TRAYMASTER SERIES DEAERATORS SECTION H3 TRAYMASTER SERIES DEAERATORS SAMPLE SPECIFICATIONS PART 1 GENERAL... H3-12 1.1 Packaged Deaerator Specification... H3-12 PART 2 PRODUCTS... H3-12 2.1 Deaerator... H3-12 2.2 Deaerator Vessel...

More information

SUBMITTAL COVER SHEET

SUBMITTAL COVER SHEET SUBMITTAL COVER SHEET PROJECT NAME LOCATION ARCHITECT ENGINEER CONTRACTOR SUBMITTED BY DATE UNIT SUMMARY Quantity Unit Designation Model No. Total Cooling Sensible Cooling Air Ent. Evaporator Air Lvg.

More information

Air-Cooled Liquid Chiller with integrated hydraulic module

Air-Cooled Liquid Chiller with integrated hydraulic module Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800

More information

of Fire Pump Assemblies

of Fire Pump Assemblies A.1.0 A.1.1 A.2.0 A.2.1 A.2.2 A.2.3 A.2.4 A.2.5 A.2.6 A.3.0 A.3.1 A.4.0 A.4.1 Report of Inspection, Testing & Maintenance System in service before conducting tasks Pertinent parties notified before conducting

More information

Generator, Unit Hydrogen, Seal Oil, Stator Coolant, Demin Water Plant Operations Training Huntly Power Station: Units 1-4 Assessment ID: 8014, 8012, 8009, 8015, 8016 NZQA Unit Standard: 17413 Assessment

More information

CATÁLOGO TÉCNICO COMERCIAL

CATÁLOGO TÉCNICO COMERCIAL CATÁLOGO TÉCNICO COMERCIAL ENFRIADORAS DE AGUA CONDENSADAS POR AIRE Series LCAEX De 350 a 1600 Kw. Compresor de tornillo R-134A Index Identification code Identification code and index... pag. 2 General

More information

TECHNICAL MANUAL OPERATOR S, UNIT, INTERMEDIATE (DS) AND INTERMEDIATE (GS) MAINTENANCE MANUAL FOR

TECHNICAL MANUAL OPERATOR S, UNIT, INTERMEDIATE (DS) AND INTERMEDIATE (GS) MAINTENANCE MANUAL FOR TM 5-2815-232-14 TECHNICAL MANUAL OPERATOR S, UNIT, INTERMEDIATE (DS) AND INTERMEDIATE (GS) MAINTENANCE MANUAL FOR ENGINE, DIESEL, CATERPILLAR, MODEL 3508 NSN 2815-01-216-0938 HEADQUARTERS, DEPARTMENT

More information

PT, PTS & PTP Series Pump/Reservoirs

PT, PTS & PTP Series Pump/Reservoirs PT, PTS & PTP Series Pump/Reservoirs Installation, Operation and Maintenance Manual Table of Contents FOREWORD... 1 INSTALLATION... 1 RECEIVING INSPECTION... 1 RIGGING, HANDLING, AND LOCATING EQUIPMENT...

More information

SECTION H4 BOILERMATE DEAERATORS

SECTION H4 BOILERMATE DEAERATORS SAMPLE SPECIFICATIONS PART 1 SECTION H4 BOILERMATE DEAERATORS GENERAL...H4-14 1.01 General...H4-14 PART 2 PRODUCTS...H4-14 2.01 Hardware...H4-14 A. Deaerator...H4-14 B. Make Up Valve and Controller...H4-15

More information

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Guide Specification SECTION HYDRONIC PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY

Guide Specification SECTION HYDRONIC PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY SECTION 23 21 16 - HYDRONIC PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pressure gages. 2. Pressure gage taps. 3. Thermometers. 4. Thermometer supports. 5. Test plugs. 6. Air

More information

Eclipse 2000 Service Parts

Eclipse 2000 Service Parts This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Climas y Proyectos Leyco, S.A. de C.V.

Climas y Proyectos Leyco, S.A. de C.V. GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA

More information

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the

More information

ANNEX A-5 GAS TURBINE JET ENGINE EXPANDER TURBINE STEAM TURBINE GENERATOR

ANNEX A-5 GAS TURBINE JET ENGINE EXPANDER TURBINE STEAM TURBINE GENERATOR ANNEX A-5 UNITS IN COMBINED CYCLE or CO-GENERATION BLOCKS INDEX TO SYSTEM/COMPONENT CAUSE CODES Inlet Air System and Compressors 5000-5039 Fuel, Ignition and Combustion Systems 5040-5079 Turbine 5080-5099

More information

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75. Chiller AQL/ to 75 Air Cooled Water Chillers Only and Heat Pump Engineering Data Manual.0 to 75.8 kw 39.9 to 77.2 kw Outstanding Strength Points R410A Refrigerant. New simpler refrigerant circuit layout.

More information

Terms. Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases

Terms. Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases Pneumatic Control Terms Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases Terms Reverse Acting (RA) The action of a controller that

More information

System Verification Checklist

System Verification Checklist Manufacturer: Model Number: Unit Identification/Installation Equipment and Piping Identification Affixed, Specification 230553 Comply with Equipment Manufacturer s Written Installation Instructions Extra

More information

FULL BORE PERFORMANCE EXHAUST MANIFOLDS F-150 ECOBOOST 3.5L

FULL BORE PERFORMANCE EXHAUST MANIFOLDS F-150 ECOBOOST 3.5L 2018-01-15 FORD F150 ECOBOOST 3.5L FULL BORE PERFORMANCE MANIFOLD SET (PART #500101X) 1 FULL BORE PERFORMANCE EXHAUST MANIFOLDS F-150 ECOBOOST 3.5L INSTALLATION INSTRUCTIONS 2011-2012 FORD F150 3.5L ECOBOOST

More information

Before you go through this booklet, we request you to go through the following general instruction before commissioning your hydraulic systems.

Before you go through this booklet, we request you to go through the following general instruction before commissioning your hydraulic systems. Hello, We are proud to be on your suppliers list. During few years we came to know that most of our customers are satisfied by Yuken Hydraulic Products but some of our customers had minor problems and

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 23 22 13 STEAM AND CONDENSATE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

ROGERS MACHINERY COMPANY, INC

ROGERS MACHINERY COMPANY, INC KOBELCO KNW SERIES Sample Specifications AIR-COOLED, OIL-FREE AIR COMPRESSOR Frame 0, 1, 2 50 500 HP ROGERS 2110_KA.doc Effective: 03-24-17 Supersedes: 04-06-15 Page 1 of 9 1. SPECIFICATIONS SCOPE 1.1

More information

9/28/2018. Refrigeration compressor operation, maintenance and safety

9/28/2018. Refrigeration compressor operation, maintenance and safety Refrigeration compressor operation, maintenance and safety Presented By: Dhananjay S. Deshpande Company name: Technex HVAC&R Engg. Works 304, Shivshakti CHS, Sector 09, Plot no 15, Khanda colony, New Panvel

More information

1997 Volvo 850 GLT. Fig. 2: Removing Drive Shaft, Engine Mount Bolt & Torque Arm (5-Cylinder) Courtesy of VOLVO CARS OF NORTH AMERICA.

1997 Volvo 850 GLT. Fig. 2: Removing Drive Shaft, Engine Mount Bolt & Torque Arm (5-Cylinder) Courtesy of VOLVO CARS OF NORTH AMERICA. Fig. 2: Removing Drive Shaft, Engine Mount Bolt & Torque Arm (5-Cylinder) 4. Remove front exhaust pipe nuts and springs. Remove front exhaust pipe bolts. Disconnect speedometer. Remove engine mounting

More information

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003 1.0 Introduction The Sturdy ventilation controller is designed to automatically control indoor air quality including: temperature, relative humidity, carbon dioxide and oxygen in the interior of the vehicle

More information

SeasonPak Packaged Air-Cooled Water Chiller

SeasonPak Packaged Air-Cooled Water Chiller Installation Manual IM 676 Group: Chiller Part Number: 594920Y Date: July 1996 Supersedes: None SeasonPak Packaged Air-Cooled Water Chiller Models ALR 032E Through 185E 1996 McQuay International Table

More information

COMPONENT IDENTIFICATION

COMPONENT IDENTIFICATION This CFMI publication is for Training Purpose Only. The information is accurate at the time of compilation; however, no update service will be furnished to maintain accuracy. For authorized maintenance

More information

Recold JW Series. Lenntech. Tel Fax ENGINEERING DATA AND SPECIFICATIONS

Recold JW Series. Lenntech. Tel Fax ENGINEERING DATA AND SPECIFICATIONS Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 ENGINEERING DATA AND SPECIFICATIONS Recold JW Series FLUI D COOLER Recold JW Series Fluid Cooler Contents 2 Construction...

More information

Engine Power Output Low

Engine Power Output Low File: 3666087-t057-tr Page 1 of 5 STEP 1 Engine under excessive load STEP 2 Fuel shutoff lever (mechanical) partially engaged STEP 3 Engine will not reach full throttle STEP 4 Poor fuel quality or wrong

More information

As diesel fuel ages it degrades in 2 ways: particulate formation, and biological growth.

As diesel fuel ages it degrades in 2 ways: particulate formation, and biological growth. ESS.WP.534.YQA Fuel Quality and Polishing Your Questions Answered (20) Fuel Quality and Polishing earth safe Fuel Systems for Critical Power 18.1 Why is filtration / polishing needed? Filtration / Polishing

More information

3. Fuel System FUEL SYSTEM FUEL INJECTION (FUEL SYSTEM) A: GENERAL. FU(STi)-7

3. Fuel System FUEL SYSTEM FUEL INJECTION (FUEL SYSTEM) A: GENERAL. FU(STi)-7 W1860BE.book Page 7 Tuesday, January 28, 2003 11:01 PM 3. Fuel System A: GENERAL The fuel pressurized by the fuel tank inside pump is delivered to each fuel injector by way of the fuel pipe and fuel filter.

More information

SYSTEM SAVER 318 AIR COMPRESSOR FOR MACK E-TECH AND ASET ENGINES MAINTENANCE MANUAL

SYSTEM SAVER 318 AIR COMPRESSOR FOR MACK E-TECH AND ASET ENGINES MAINTENANCE MANUAL SYSTEM SAVER 318 AIR COMPRESSOR FOR MACK E-TECH AND ASET ENGINES MAINTENANCE MANUAL NON-THROUGH DRIVE THROUGH DRIVE Service Notes About This Manual This manual provides service and repair procedures for

More information

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM DIESEL SPACE HEATER - SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER ASSEMBLY 3. FUEL PUMP ASSEMBLY

More information

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Please consult your local representative or the factory for warranty issues. July 2017 DRS Marlo Coil Customer

More information

VXI Closed circuit cooling towers

VXI Closed circuit cooling towers Closed circuit cooling towers Key benefits Reliable Quiet Compact characteristics Counter flow, centrifugal fan, forced draft Capacity range up to 2615 kw Maximum entering fluid temperature 82 C Typical

More information

Fan Coil Units. Technical Data ECDEN FWL-DT/DF

Fan Coil Units. Technical Data ECDEN FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF TABLE OF CONTENTS FWL-DT/DF 1 Features.............................................................

More information

John Deere. MODEL: 4230 Tractor Volume 1 of 2 JD-S-TM1056

John Deere. MODEL: 4230 Tractor Volume 1 of 2 JD-S-TM1056 John Deere MODEL: 4230 Tractor Volume 1 of 2 THIS IS A MANUAL PRODUCED BY JENSALES INC. WITHOUT THE AUTHORIZATION OF JOHN DEERE OR IT'S SUCCESSORS. JOHN DEERE AND IT'S SUCCESSORS ARE NOT RESPONSIBLE FOR

More information

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting PAGE 1 This document outlines questions to ask and components to check during TES troubleshooting. More detailed troubleshooting procedures are available in the TES Troubleshooting Guide. 1. Flow Light

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS 550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece

More information

2013 Kia Optima L4-2.0L Turbo

2013 Kia Optima L4-2.0L Turbo 1 of 13 5/29/2016 11:34 AM 2013 Kia Optima L4-2.0L Turbo Vehicle» Engine, Cooling and Exhaust» Engine» Service and Repair» Removal and Replacement Removal CAUTION: Use fender covers to avoid damaging painted

More information

Section 10 Chapter 7

Section 10 Chapter 7 Section 10 Chapter 7 24 Valve, 8.3 Liter Engine Troubleshooting Symptoms Identification Note: All coding used in the 8.3 Liter and 9 Liter engine manuals are Cummins engine codes. These engine codes have

More information

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC) CHILLER START UP PROCEDURE FORM DOC. N 061103 (DOC.N 071103 BELOW TO BE RETURN TO AERMEC) 1. Preliminary Operation WARNING: The following operation must be done without the power supply (unit with the

More information

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW MODELS: D4HH 024 THRU 180 York horizontal ductable air conditioning packages offer a complete line of

More information

Cooling System Description and Operation

Cooling System Description and Operation Page 1 of 5 2008 Holden VE Sedan VE, WM, Caprice, Statesman, Lumina, Omega, VXR8 Service Manual Engine Engine Cooling Description and Operation Document ID: 1990377 Cooling System Description and Operation

More information

BENNETT CNG DISPENSER MAINTENANCE SCHEDULE

BENNETT CNG DISPENSER MAINTENANCE SCHEDULE BENNETT CNG DISPENSER MAINTENANCE SCHEDULE Serial #: DIN #: Company Name: CAUTION: Only trained personnel may work on dispensers. CAUTION: The emergency shut off valve if installed must be closed. CAUTION:

More information

Solenoid valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

Solenoid valves REFRIGERATION AND AIR CONDITIONING. Fitters notes REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Installation...3 EVRA 32 & 40 precautions...4 When pressure testing...4 The coil...5 The clip-on coil...6 The correct product...8 Fault location...9

More information

Copeland Screw Compressors Semi-Hermetic Compact Operating Instructions

Copeland Screw Compressors Semi-Hermetic Compact Operating Instructions Copeland Screw Compressors Semi-Hermetic Compact Operating Instructions SCH2 & SCA2 High Temperature Compressors 35-240 Horsepower 1. Introduction This series of semi-hermetic compact screw compressors

More information

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw TWA 212-1102 S/K/P Incorporating R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw The complete solution to all your cooling needs TWA 212-1102 S/K/P Index

More information

February 26, ch.12.notebook. Ch. 12. Preventative Maintenance and Troubleshooting. Feb 23 5:03 PM

February 26, ch.12.notebook. Ch. 12. Preventative Maintenance and Troubleshooting. Feb 23 5:03 PM Ch. 12 Preventative Maintenance and Troubleshooting Feb 23 5:03 PM 1 Why PM? preventive maintenance certain maintenance tasks must be performed regularly to keep an engine working properly helps premature

More information

NUMBER: S.M. REF.: Listed in Table ENGINE: EPA07 Series 60 DATE: October 2012 SUBJECT: REFERENCES TO THE TURBOCHARGER PURGE ROUTINE

NUMBER: S.M. REF.: Listed in Table ENGINE: EPA07 Series 60 DATE: October 2012 SUBJECT: REFERENCES TO THE TURBOCHARGER PURGE ROUTINE NUMBER: 10 01 12 S.M. REF.: Listed in Table ENGINE: EPA07 Series 60 DATE: October 2012 SUBJECT: REFERENCES TO THE TURBOCHARGER PURGE ROUTINE ADDITIONS, REVISIONS, OR UPDATES Publication Number Platform

More information

ENGINE COOLING SYSTEM GENERAL 1. GENERAL SPECIFICATIONS ENGINE COOLING SYSTEM. undefined

ENGINE COOLING SYSTEM GENERAL 1. GENERAL SPECIFICATIONS ENGINE COOLING SYSTEM. undefined 211001 043 GENERAL 1. GENERAL SPECIFICATIONS 211001 044 211001 2. FASTENER TIGHTENING SPECIFICATIONS 211001 045 OVERVIEW AND OPERATION PROCESS 1. COMPONENT LOCATOR 1. Reserver Tank 2. Deaeration Tube 3.

More information

Service/Inspection Checklist and Report

Service/Inspection Checklist and Report Fastrac 2155 and 2170 Service/Inspection Checklist and Report Fastrac 2155 and 2170 Issued by JCB Technical Publications, JCB Service, World Parts Centre, Beamhurst, Uttoxeter, Staffordshire, ST14 5PA,

More information

HS17. HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw ( to Btuh) Cooling Capacity. MATCHED REMOTE SYSTEMS 50hz ENGINEERING DATA

HS17. HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw ( to Btuh) Cooling Capacity. MATCHED REMOTE SYSTEMS 50hz ENGINEERING DATA ENGINEERING DATA ENGINEERING DATA MATCHED REMOTE SYSTEMS 50hz HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw (60 200 to 222 500 Btuh) HS17 Bulletin #490001 November 1995 Supersedes August 1994 HS17-1353

More information

SECTION 4 - FUEL SYSTEMS AND CARBURETION

SECTION 4 - FUEL SYSTEMS AND CARBURETION SECTION - FUEL SYSTEMS AND CARBURETION FUEL SYSTEMS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -62 FUEL PUMP - - - - - - -

More information

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07. Air Cooled Water Chillers CLS 182 to 602 41 to 150 kw Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.04 R Specifications General characteristics The CLS air cooled water

More information

Cooling System. Table of Contents

Cooling System. Table of Contents Sub-Headings Safety 2 s 2 Cautions 2 Notes 2 Introduction 2 General Specifications 2 Engine 2 Coolant 2 Routine Maintenance 2 Hose Connections 4 Radiator, Charge Air and Heater Cores 4 Cooling System Leaks

More information