6. Document tasks performed during visit and report any observations to the appropriate
|
|
- Veronica Daniels
- 6 years ago
- Views:
Transcription
1 Chiller Annual Maintenance RFP Attachment B Services Required Tasking: Vibration Analysis 1. All work shall be performed in accordance with safety policies 2. Check with appropriate customer representative for operational deficiencies 3. Record equipment specific information for reference 4. Install pads and labels (if applicable) 5. Install sensors in proper location 6. Start equipment and run at normal operating conditions 7. Record readings and remove sensors 8. Submit readings for report generation and deliver to customer with recommendations 9. Document tasks performed during visit and report any observations to appropriate customer representative Oil Sample and Analysis 1. All work shall be performed in accordance with safety policies 2. Check with appropriate customer representative for operational deficiencies 3. Remove sample in approved container 4. Drop off for analysis 5. Label and complete paperwork indicating present operating conditions 6. Document tasks performed during visit and report any observations to the appropriate customer representative Additional Service Requirements 1. Calibrate refrigerant monitor annually to ensure proper operation (If applicable) 2. If motors need to be adjusted for any reason laser alignment must be used to realign motor Phase I Comprehensive Annual Inspection Centrifugal Chillers Review customer logs with customer for operational problems and trends. Remove refrigerant. Lube System Megger oil pump motor and record readings. Measure and record oil pump voltage and amperage. Inspect the starter for signs of overheating, arcing, burns, etc. Verify operation of oil cooling system.* Clean oil solenoid strainer. Tighten terminal connections on the oil pump motor. Verify operation of the oil heater.
2 Change the compressor oil and filter. ** Motor and Starter (Less than 600 Volts) Clean starter cabinet. Inspect starter and starter components for signs of discoloration, burns, moisture, etc. Inspect wires for discoloration and burns. Test accuracy of motor current (amp meter). Test tightness of terminal connections. Check dash pot oil and add as necessary. Megger motor at the starter terminals; record readings. Measure operating voltage and record. Controls and Safeties Inspect and calibrate all safety and operating controls. Inspect the control panel for cleanliness, control air leaks, etc. (clean if needed) Inspect wiring and connections for signs of overheating, burns. Verify operation of the vane control system: Check for free and smooth operation. Check mechanical linkages for wear and secureness. Test vane close switch. Report accuracy of all gages and thermometers (use masters). Verify working condition of all indicator and alarm lights. Verify operation of automatic and manual capacity control. Verify operation of start, stop, and anti recycle timers. Test the operation of all pump auxiliary contacts (chw, cw, oil, etc.).* Verify operation of oil temperature and pressure controller(s). Test chilled water low temperature cutout and recycle switch calibrate and record. Test condenser high pressure cutout calibrate and record. Test refrigerant low temperature cutout calibrate and record. Test low oil pressure cutout calibrate and record. Test oil filter high pressure cutout calibrate and record. Test bearing transmission high temperature cutout calibrate and record. Test all flow switch cutouts (cw, chw).* Test motor winding high temperature safety circuit and record. Purge Unit Evacuate unit to 200 microns, Filter and transfer refrigerant back into chiller. Add compressor oil per manufactures recommendations. Drain, clean, and inspect purge drum. Clean sight glass and report condition. Clean and inspect purge float assembly. Verify operation of refrigerant pump. Lubricate purge pump. Measure and record pump voltage and amperage. Test purge safety switch* and adjust if required.
3 Change filter dryer in purge line.* Test the secureness of mounting points; tighten all major points. Test and calibrate purge operating controls. Run purge and verify operation Transmission and Bearing Inspection Inspect transmission (through access) for signs of wear, moisture, dirt, etc. Clean sump and oil heater. Replace access cover gasket. Inspect transmission s internal piping. Inspect transmission s internal wiring (hi temp, bearing safety). Inspect motor end bearings.* Diffuser Wall Verify operation of diffuser walls by manual loading and unloading of the compressor. Check calibration of the diffuser wall controller and calibrate, as required. Check calibration of the diffuser wall feedback potentiometer and calibrate, as required. Compressor and Vessels Remove condenser water box cover and brush tubes with Goodway tube brushing machine. Reinstall cover with new gaskets. Pressurize chillers to 10 PSIG and electronically leak test. Inspect for leaks and report results. Check refrigerant charge. Replace filter/dryer in motor cooling line.* Replace venturi filter. Clean demister and oil magnetic plug. Test the secureness of mounting points; tighten all major points. Inspect volute drain filter and replace if necessary. Record refrigerant level. Review machine operation with operator. Log machine at departure. Report machine condition and repair requirements (if any). Run complete interlocking circuit where possible. Re insulate and touch up paint as needed, due to servicing. * Where applicable **Remove oil from lube system after evacuating to 29 inches of mercury vacuum with refrigerant recovery unit and maintaining 140 degree oil temp to remove all refrigerant from used oil. Remove used oil from job site.
4 Phase II Spring Start up and Operational Annual Inspection Centrifugal Chillers Review customer logs with customer for operational problems and trends. System Run and record a complete test log on the equipment. Report unusual noises, vibrations, odors, etc. Verify capacity control reaction. Verify operation of vane linkage. Verify operation of flow switch. Record refrigerant level as seen in sight glass. Test complete interlocking circuit where possible. Report any drop in level of vane shaft oiler.* Run full load test if operating conditions permit. Check for leaks (high side). Check for proper refrigerant charge. Check for air in machine and purge as needed. Adjust running oil temp with water regulating valve. Check chilled water low water temperature cutout set point. Fine tune chiller for optimum efficiency. Starter (Less than 600 Volts) Open starter cabinet; check starter contacts for signs of overheating, arcing, burns, discoloration, etc. Lube System Inspect oil pump starter enclosure for cleanliness, moisture, and signs of oil. Inspect the starter for overheating, arcing, burns, etc. Additional Tasks and/or Special Instructions: Measure and record motor amperage. Verify operation of the oil heater and oil cooler. Record oil level as seen in sight glass. Purge Unit Verify operation of purge compressor. Measure and record compressor amperage. Measure and record compressor and separator oil levels. Check all sight glass levels. Measure and record volume of water drained from unit. Verify operation of purge heaters. Diffuser Wall Verify operation of diffuser wall by manually loading and unloading the compressor. Confirm and record all operating temperatures, pressures, amperage, control panel readings, etc. Upon completion, review machine operation with operator.
5 Report machine condition and repair requirements (if any). NOTE: The preceding inspection tasks will be completed when operating conditions permit. * Where applicable Phase III Mid Season Operational Inspection Centrifugal Chillers Same as Phase II plus Vibration Analysis Phase I/II/III Comprehensive Inspection Split System with Indoor Coil Review operation with customer for problems and trends. Fan(s) and Motor(s) Verify operation of system motor, gages, etc. Inspect flexible connections and ductwork for damage and leaks. Inspect tension on drive and fan belts, and change as needed. Lubricate fan shaft bearings. Lubricate motor bearings. Lubricate dampers. Clean intake screen on motor. Inspect fan wheel for free rotation, cracks and alignment. Inspect for vibrations and unusual noises. Report condition of dampers. Test secureness of guards, doors and panels. Inspect humidifier parts. Inspect roof curb flashing. Inspect all major stop valves and report condition. Inspect all structural elements for corrosion and damage. Report condition of coils clean/dirty. Inspect motor windings for cleanliness. Starter(s) Inspect wiring for secureness and damage. Megger motor at starter and record reading. Inspect switch gear, starter and contactor points. Inspect starter for signs of wear, arcing, overheating, burns, etc. Inspect electrical connections for tightness and absence of moisture. Measure and record operating voltage. Measure and record operating amperage. Compressor(s) Inspect vibration eliminators for secureness and damage. Tighten terminal connections at heater elements. Test secureness of mounting points, and tighten all major points.
6 Controls Inspect control center; clean and tighten connection; inspect components. Test low pressure cutout and record; calibrate if needed. Test high pressure safety and record; calibrate if needed. Operational Test Compressor(s) Run and record a complete test log on machine. Verify refrigerant charge. Verify oil level. Verify superheat adjustment. Inspect for vibrations and unusual noises in bearings, motor, etc. Inspect moisture indicator for evidence of moisture. Test accuracy of all pressure gages. Record compressor oil pressure. Record compressor suction pressure. Record compressor discharge pressure. * Where applicable Phase I Comprehensive Inspection Screw Chiller Review customer logs with customer for operational problems and trends. Inspect vibration eliminators for secureness and damage. Change oil and filter element (as needed)* Annual oil sample. Test secureness of mounting points, and tighten all major points. Open Compressor (Only) Lubricate motor bearings. Clean motor air intake screens. Lubricate coupling.* Inspect motor windings and report condition. Visually inspect coupling. Motor and Starter Megger motor at starter and record reading. Tighten terminal connections at heater elements. Tighten terminal connections at starter. Measure operating voltage and record readings. Inspect starter for signs of wear, arcing, overheating, burns, etc. Measure operating amperage and record readings. Clean enclosure. Controls Inspect control center clean and tighten connections. Inspect wiring and connections for signs of wear
7 Verify operation of oil temperature control. Inspect components. Test oil low temperature switch; calibrate if needed.* Test high pressure safety; calibrate if needed,* Verify operation of start, stop, and all other timers. Operational Test Verify oil level. Verify refrigerant charge. Leak test refrigerant system. Test accuracy of all pressure gauges. Inspect for vibrations and unusual noises in bearings, motors, etc. Verify superheat adjustment Inspect moisture indicator for evidence of moisture. Record compressor suction pressure. Record compressor discharge pressure. Record compressor oil pressure. Run and record a complete test log on machine. Report machine condition and repair requirements (if any). Inspect control center; clean and tighten connections. Inspect wiring and connections for signs of wear, overheating, burns, etc. Test oil high temperature cutout; calibrate if needed.* Verify capacity control reaction. Update chiller control software. *Where applicable Phase II Operational Screw Chiller Review customer logs with customer for operational problems and trends. System Run and record a complete test log on machine. Inspect for vibrations and unusual noises in bearings, motors, etc. Inspect control center; clean and tighten connections. Inspect wiring and connections for signs of wear, overheating, burns, etc. Verify capacity control reaction. Inspect components. Verify operation of start, stop, and all other timers. Verify operation of oil temperature control. Verify oil level. Verify refrigerant charge. Verify superheat adjustment Inspect moisture indicator for evidence of moisture.
8 Additional Tasks and/or Special Instructions: Starter (Less than 600 Volts) Measure operating amperage and record readings. Clean enclosure. Inspect starter for signs of wear, arcing, overheating, burns, etc. Confirm and record all operating temperatures, pressures, amperage, control panel readings, etc. Upon completion, review machine operation with operator. Report machine condition and repair requirements (if any). NOTE: The preceding inspection tasks will be completed when operating conditions permit. *Where applicable Phase III Mid Season Operation Inspection Screw Chillers Same as Phase II plus Vibration and Oil Analysis Phase I Comprehensive Annual Inspection Reciprocating Chillers and/or Standalone Compressors Review customer logs with customer for operational problems and trends. Compressor(s) Inspect vibration eliminators for secureness and damage. Tighten terminal connections at heater elements. Test secureness of mounting points, and tighten all major points. Controls Inspect control center; clean and tighten connection; inspect components. Verify operation of bypass valve. Verify capacity control reaction. Test low pressure cutout and record; calibrate if needed. Test high pressure safety and record; calibrate if needed.* Verify operation of cooling water (valve) regulator.* Test freeze control cutout and record temperature.* Verify operation of oil temperature control. Test oil high temp cutout and record; calibrate if needed.* Starter Inspect wire insulation for signs of overheating, burns, etc. Megger motor at starter and record reading. Measure operating amperage and record readings. Clean enclosure. Tighten terminal connections at starter. Measure operating voltage and record readings.
9 Inspect starter for signs of wear, arcing, overheating, burns, etc. Operational Test Run and record a complete test log on machine. Verify refrigerant charge. Verify oil level. Verify superheat adjustment. Inspect for vibrations and unusual noises in bearings, motors, etc. Inspect moisture indicator for evidence of moisture. Test accuracy of all pressure gauges. Record compressor oil pressure. Record compressor suction pressure. Record compressor discharge pressure. Report machine condition and repair requirements. Check glycol concentration for Liebert dry coolers. Check glycol concentration for Carrier Chiller serving YFS building. Leak test refrigerant system. * Where applicable Phase II and III Operational Inspection Reciprocating Chillers and Standalone Compressors Review customer logs with customer for operational problems and trends. Controls Verify operation of bypass valve. Verify capacity control reaction. Verify operation of oil temperature control.* Verify operation of cooling water (valve) regulator.* Starter Measure operating amperage and record readings. Inspect starter for signs of wear, arcing, overheating, burns, etc. Operational Test Run and record a complete test log on machine. Verify refrigerant charge. Verify oil level. Verify superheat adjustment. Inspect for vibrations and unusual noises in bearings, motors, etc. Inspect moisture indicator for evidence of moisture. Record compressor oil pressure. Record compressor suction pressure. Record compressor discharge pressure. Report condition and repair requirements (if any).
10 NOTE: The preceding inspection tasks will be completed when operating conditions permit. * Where applicable Phase I/II/III Comprehensive Annual Inspection Computer Room Units Review operation with customer for problems and trends. Fan(s) and Motor(s) Verify operation of system motor, gages, etc. Inspect flexible connections and ductwork for damage and leaks. Inspect tension on drive and fan belts, and change as needed. Lubricate fan shaft bearings. Lubricate motor bearings. Lubricate dampers. Clean intake screen on motor. Inspect fan wheel for free rotation, cracks and alignment. Inspect for vibrations and unusual noises. Report condition of dampers. Test secureness of guards, doors and panels. Inspect humidifier parts.* Inspect roof curb flashing.* Inspect all major step valves and report condition. Inspect all structural elements for corrosion and damage. Report condition of coils clean/dirty. Inspect motor windings for cleanliness. Starter Inspect wiring for secureness and damage. Megger motor at starter and record reading. Inspect switch gear, starter and contactor points. Inspect starter for signs of wear, arcing, overheating, burns, etc. Inspect electrical connections for tightness and absence of moisture. Measure and record operating voltage. Measure and record operating amperage. Condenser Fan Motor(s) Inspect for vibrations and unusual noises in bearings, motors, etc. Wipe down motor(s) to remove loose dirt and oil buildup. Inspect fans for vibrations and tightness. Inspect wiring and connections for signs of wear, overheating, burns, etc. Lubricate motor bearings. Compressor(s) Inspect vibration eliminators for secureness and damage.
11 Tighten terminal connections at heater elements.* Test secureness of mounting points, and tighten all major points. Controls Inspect all panel lights. Inspect control center; clean and tighten connections; inspect components. Check all alarm points. Test low pressure cutout and record; calibrate if needed. Test high pressure safety and record; calibrate if needed.* Test temperature sensors. Verify operation of fan speed control.* Verify economy cycle control.* Verify operation of fan cycling controller.* Verify operation of damper cycling controller.* Operational Test Compressor(s) Run and record a complete test log on machine. Verify refrigerant charge. Leak test refrigerant system. Verify oil Ievel.* Verify superheat adjustment Inspect for vibrations and unusual noises in bearings, motor, etc. Inspect moisture indicator for evidence of moisture.* Test accuracy of all pressure gages.* Record compressor oil pressure.* Record compressor suction pressure. Record compressor discharge pressure. Electric Reheat Inspect coil for damage to element. Measure and record reheat amperage. Inspect isolators for damage or cracks. Brush coil. Remove dust and debris. Torque heating terminals. Verify operation of control. Verify staging of heating elements. Steam and Hot Water Reheat Inspect coil for leaks or damage. Brush coil. Remove dust and debris. Check and clean strainers.* Verify operation of steam trap(s).* Verify operation of controls. Humidifier* Verify operation of humidity probes. Check steam orifice and clean, if necessary.*
12 Inspect humidifier pan. Inspect infrared bulbs and clean, if needed.* Report machine condition and repair requirements. *Where applicable
CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.
CENTRIFUGAL CHILLER Annual Inspection Refrigerant Circuit Check and record refrigerant level Inspect for leak results Calculate refrigerant lass and report to the customer. Repair minor leaks as required
More informationBOILER PM & INSPECTION
BOILER PM & INSPECTION Record inspection log for Gaming Commission and Safety Department. The following listed maintenance items are not intended to be a complete list. Follow any additional maintenance
More informationSEASONAL MAINTENANCE CHECKLISTS Johnson Controls
SPRING CHECK LIST ABSORPTION CHILLERS Check starter and control panel. Leak test. Check hand valve diaphragms and replace as required. Check operation of purge unit. Change oil in the purge pump. Lubricate
More informationElectric Duct Heater X X X X X X
EHIBIT B-SERVICE SCHEDULE & CHECKLIST Electric Duct Heater Comprehensives Check overall condition of unit Check for unusual noise and vibration Check Voltage Check Controls Check and insure that heater
More informationATTACHMENT A - STATEMENT OF WORK INVITATION TO BID FOR CHILLER INSPECTION SERVICES ITB NO.: DMS-13/14-035
4050 Esplanade Way Tallahassee, Florida 32399-0950 Tel: 850.488.2786 Fax: 850. 922.6149 Rick Scott, Governor Craig J. Nichols, Agency Secretary ATTACHMENT A - STATEMENT OF WORK INVITATION TO BID FOR CHILLER
More informationAir Handling Unit Construction Checklist
Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.
More informationSecondary Coolant 301
Secondary Coolant 301 Instructor Rusty Walker Hill PHOENIX Learning Center Secondary Coolant 301 Start-Up Procedures Secondary Coolant 301 Objectives Describe the initial startup procedures for a medium
More informationInspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8
, Chapter 8 as amended by CCR, Title 19 Page 1 of 8 Address: City: Date of Pump Test: Shaft Orientation: Horizontal Vertical Annual Fire Pump Test Results Number of pumps at this location: If multiple
More informationRoutine Compressor Maintenance
Establishing a regular, well-organized maintenance program and strictly following it is critical to maintaining the performance of a compressed air system. One person should be given the responsibility
More informationPERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS
50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT
More informationLubrication & Maintenance Schedule
REMOVE DIRT AND SPILLAGE FROM AROUND THE CRUSHER. REMOVE DUST AND DIRT FROM CRUSHER FRAME SURFACES. REMOVE DUST AND DIRT FROM DRIVE MOTOR. CHECK FLUID LEVELS IN DIESEL ENGINE (IF EQUIPPED). REFER TO ENGINE
More informationAIR COOLED CHILLERS WATER COOLED CHILLERS
AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with
More informationHeating and Gas Installations - December 2014
This is an example of good practice maintenance specifications. It is not exhaustive and should only be used to assist with facilities management or specification of a maintenance contract. Emergency Gas
More informationEXHIBIT A SCOPE OF SERVICES MAINTENANCE OF TRANE HVAC SYSTEMS
EXHIBIT A SCOPE OF SERVICES MAINTENANCE OF TRANE HVAC SYSTEMS DISTRICT VII, HEADQUARTERS FACILITY AND TAMPA BAY SUNGUIDE REGIONAL TRAFFIC MANAGEMENT CENTER DISTRICT VII, HEADQUARTERS FACILITY I. PURPOSE:
More informationPUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4
PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In
More informationFABER BURNER ROUTINE MAINTENANCE
FABER BURNER ROUTINE MAINTENANCE Version 2016 The Faber burner is designed for minimal maintenance; however, the frequency and quantity of maintenance that is required depends upon many factors which vary
More informationDon Searles Check List For Dredging Equipment Surveys
Don Searles Check List For Dredging Equipment Surveys 1. General 1.1. Take pictures of everything important. Take pictures showing the side of the dredge 1.2. Inspect logs and maintenance records. Get
More informationTable Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,
Table 5.1.1.2 Summary of Sprinkler System Inspection, Testing, and Maintenance Item Frequency Reference Inspection Gauges (dry, preaction, and deluge systems) Quarterly 5.2.4.2, 5.2.4.3, 5.2.4.4 Control
More informationPACKAGED LIQUID CHILLER 6. HUMIDIFIER SECTIONS. C Member. Liquid Chiller. nowlc And noalc Series
6. HUMIDIFIER SECTIONS Liquid Chiller nowlc And noalc Series C Member 1 Features and Benefits OMRAN cold generator reciprocating Liquid chiller are designed and built to provide reliable,efficient performance
More informationHanna Daily Preventive Maintenance Schedule
Hanna Daily Preventive Maintenance Schedule Location Location # Daily operation and inspection procedures to be performed by car wash personnel. Mark status in the spaces on the right after performing
More informationQUARTERLY / ANNUAL MOBILE FIRE APPARATUS INSPECTION REPORT. Manufacturer. Serial no. Legend:
QUARTERLY / ANNUAL MOBILE FIRE APPARATUS INSPECTION REPORT Inspection date Fire department Apparatus no. Apparatus Manufacturer Model Serial no. Hourmeter _ Chassis Make _ Model VIN Odometer Legend: X
More informationPERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS
50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING
More informationSCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS
SCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS 1 to 40 Nominal Tons Rev-01 TABLE OF CONTENTS Page: Description 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Product Nomenclature Air Cooled Chiller
More informationLiebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller
DISCONTINUED PRODUCT CSI 15621 - Mainframe Cooling Systems 1.1 SUMMARY Liebert CSU3000 CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller GUIDE SPECIFICATIONS 1.0 GENERAL These specifications describe
More informationCHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)
CHILLER START UP PROCEDURE FORM DOC. N 061103 (DOC.N 071103 BELOW TO BE RETURN TO AERMEC) 1. Preliminary Operation WARNING: The following operation must be done without the power supply (unit with the
More information348002K/348012K Manifold Block Style Service Manual 12/2000
348002K/348012K Manifold Block Style Service Manual 12/2000 Service Manual 348002K/348012K Manifold Block Style Recovery/Recycling/Recharging Unit For R-12 or R-134a Only TABLE OF CONTENTS: Theory of Operation
More informationTable of Contents. 1. Model Designation And Unit Models Guide Specifications Technical Data Performance Data 10
Table of Contents Page No. 1. Model Designation And Unit Models 1 2. Features 2 3. Guide Specifications 4 4. Standard Unit Components 5 5. Technical Data 6 6. Performance Data 10 7. Electrical Data 19
More informationPlanned Preventative Maintenance Schedule. Chilled Water Systems PPM Schedule. Data Centre Solutions Expertly Engineered
Planned Preventative Maintenance Schedule Chilled Water Systems PPM Schedule Data Centre Solutions Expertly Engineered Planned and contracted maintenance services To ensure that data centre or building
More informationabc CPD7948/075 Rotors, rotor shafts and rotor casings are coated with an anti-corrosive and anti wear coating to prolong element life and efficiency.
CPD7948/075 Specification Oil-Free, Air Cooled, Rotary Screw Compressors - Dryclon Range Models D75, D90, D110, D132, D150 (50Hz) D55, D75, D90, D110, D150 (60Hz) COMPRESSOR PACKAGE An enclosed two stage
More informationDIM Heating and Air Conditioning
2014 NATEF JOB TASKS COMPLETION REQUIREMENT: P1-95% P2-70% P3-25% Student Name: DETAILED COURSE CONTENT VI. HEATING, VENTILATION, & AIR CONDITIONING A. HVAC SYSTEMS -- The student will be able to: P1 P2
More informationSupersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:
YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT
More informationEclipse 2000 Service Parts
This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior
More informationnext dx next dx rcgroupairconditioning NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans.
NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans. Cooling Capacity: 6,4 97,4 next dx C rcgroupairconditioning R410 E C UP FLOW DOWN FLOW MIN FETURES
More informationSECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION
SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the
More information30GX AIR-COOLED LIQUID CHILLER
30GX-4SB 30GX080-265 AIR-COOLED LIQUID CHILLER PERFORMANCE DATA FIELD WIRING DIAGRAM 1997 Carrier Corporation Syracuse, New York 13221 Form 30GX-4SB Supersedes 30GX-3SB Printed in U.S.A. 12-97 Catalog
More informationProdigy Eclipse 600, 800, 1000 Service Parts
Prodigy Eclipse 600, 800, 000 Service Parts This part list contains the service parts for the Eclipse 600, 800 and 000 systems. The B series references changes to panels. The models that are covered include:
More informationPlanned Maintenance Agreement Renewal Between Illingworth-Kilgust Mechanical, Inc. and River Valley School District
Milwaukee Location: Madison Location: 11217 W. Becher St. 6950 Gisholt Drive Milwaukee, WI 53227-1032 Madison, WI 53713-4828 Phone: 414.476.5790 Phone: 608.222.9196 Fax: 414.476.0916 Fax: 608.222.3339
More informationPump Acceptance Test Data
Customer Location: 500 Base Ave East Venice, Fl. 34275 941-485-5402 941-483-3321 Fax Pump Acceptance Test Data Division: Customer Number: Date: City & State Work Order: Technician: PUMP IF VERTICAL TYPE
More information30GX AIR-COOLED LIQUID CHILLER
30GX-5SB 30GX080-265 AIR-COOLED LIQUID CHILLER PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GX-5SB Supersedes 30GX-4SB Printed in U.S.A. 5-98 Catalog No.
More informationALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks.
ALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks. 1. Check log book for incomplete compliance for further operation. 2.
More informationComplete HVAC Capability
Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option
More informationUD SERIES COMPRESSORS
UD SERIES COMPRESSORS INDUSTRIAL AIR COMPRESSOR 40-400 HP UPDRAFT MODELS Electric Motor - 460/575/3/60 standard (208/230/3/60 optional on most models) Motor Starter - 460 volt, full voltage magnetic starter
More informationGenerator, Unit Hydrogen, Seal Oil, Stator Coolant, Demin Water Plant Operations Training Huntly Power Station: Units 1-4 Assessment ID: 8014, 8012, 8009, 8015, 8016 NZQA Unit Standard: 17413 Assessment
More informationCopeland Screw Compressors Semi-Hermetic Compact Operating Instructions
Copeland Screw Compressors Semi-Hermetic Compact Operating Instructions SCH2 & SCA2 High Temperature Compressors 35-240 Horsepower 1. Introduction This series of semi-hermetic compact screw compressors
More informationDUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE) INSTALLATION AND OPERATING INSTRUCTIONS
4080 SE International Way. Suite B110, Milwaukie, OR 97222 (503) 654-0867 Fax: (503) 654-4671 email: ftech@filtertechnologyltd.com www.filtertechnologyltd.com DUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE)
More informationREVELSTOKE - 1 YEAR DOWN. Applied to Equipment Instruction Number R Class-Group Generate Date: 11 March 2004
Page 1 of 7 Planned Maint. Type Turbo file - Job Group 1Y-DOWN Lead Trade Applied to Equipment Instruction Number R Class-Group Generate Date: 11 March 2004 Isolation Zone Supersedes References J:\PS\mep\Maintenance
More informationInstallation, Operation and Maintenance Manual
MODELS IG / IGX Make-Up Air Unit Part # 464104 Installation, Operation and Maintenance Manual **WARNING** Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationSECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY
SECTION 230533 - PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pressure gages. 2. Pressure gage taps. 3. Thermometers. 4. Thermometer supports. 5. Test plugs. 6. Static pressure
More informationC1448, C1848, C2148 Service Parts
C8, C88, C8 Service Parts This part list contains the service parts for the air cooled, water cooled and remote air cooled C8, C88, C8 ice machines. To avoid costly and time consuming errors, double check
More informationManufacturer reserves the right to change these specifications at any time without incurring obligation. Btuh (kw) SEER SHR EER
UNHA-T2CA-T3CA-T4CA Universal Air Handler Multi-Zone Only Rev. 1.0 [07/07] JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE: UNIT
More informationINSTALLATION, START-UP AND SERVICE INSTRUCTIONS
INSTALLATION, START-UP AND SERVICE INSTRUCTIONS P705 Refrigeration Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................. 1 HANDLING.......................................
More informationProdigy Eclipse 600, 800, 1000 Service Parts
Prodigy Eclipse 600, 00, 000 Service Parts This part list contains the service parts for the Eclipse 600, 00 and 000 systems. The B series references changes to panels. The models that are covered include:
More informationTwo temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser
The ZC 107 Zone Control System was designed to provide the perfect comfort control within the home. At the same time it was designed to make an airconditioning system work more efficiently and thereby
More informationSTART-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:
START-UP INSTRUCTION OPTIMUM 36000 To 72000 BTU S PACKAGE UNITS 3 To 6 Ton START-UP CHECKLIST Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:
More informationSRT OPERATIONS MANUAL
MAINTENANCE SECTION PAGE # VEHICLE DAILY INSPECTION.......................................1 P.M. INSPECTION #1.................................................3 P.M. INSPECTION #2.................................................6
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationRecold JW Series. Lenntech. Tel Fax ENGINEERING DATA AND SPECIFICATIONS
Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 ENGINEERING DATA AND SPECIFICATIONS Recold JW Series FLUI D COOLER Recold JW Series Fluid Cooler Contents 2 Construction...
More informationBAS Construction Checklist
BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items
More informationAIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST
AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST BELT TYPE IMPORTANT PLEASE MAKE CERTAIN THAT THE PERSON WHO IS TO USE THIS EQUIPMENT CAREFULLY READS AND UNDERSTANDS THESE INSTRUCTIONS BEFORE STARTING
More informationINSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.
INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is
More informationTechnical Service Bulletin IOX/DCX Transmitter Maintenance Schedule
Technical Service Bulletin 140610 IOX/DCX Transmitter Maintenance Schedule Service Bulletin 140610 applies to Comark IOX, DCX and Paragon transmitters. This bulletin contains important maintenance schedule
More informationBITZER Capacity Controller for CSH Compressors Temperature Sensor
only. The Temperature Controller has been obsoleted. The below data is for informational purposes only BITZER Capacity Controller for CSH Compressors Temperature Sensor The BITZER CSH Capacity Controller
More informationSBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL
SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES
More informationPROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES EB COMPACT PACKAGED CHILLERS PART 1 GENERAL
PROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES EB COMPACT PACKAGED CHILLERS PART 1 GENERAL 1.1 SUMMARY A. Packaged Chillers offer a self-contained means of producing cooling liquid primarily
More informationHUDSON TECHNOLOGIES REFRIGERANTSIDE SOLUTIONS OTHER SERVICES PRODUCTS
HUDSON TECHNOLOGIES S Chiller dehydration & decontamination (online & offline) Refrigerant moisture reduction (online & offline) Rust and particulate reduction Hermetic burnout decontamination Residue
More informationSection 5 AIR - COOLED CONDENSING UNITS MODEL PC 05Z TO PC NOMINAL COOLING CAPACITY RANGE 56.6 TO 772 MBH
AIR - COOLED CONDENSING UNITS MODEL PC 05Z TO PC 80-01 NOMINAL COOLING CAPACITY RANGE 56.6 TO 772 MBH 14 FEATURES MODEL PC 05Z TO PC 30-02 CABINET: Cabinets are constructed of heavily zinc coated galvanized
More informationCentac C3000. Basic Frame Description. Process Air Solutions ESA. Date : 05/2011 Revision : 2. The picture may not represent the version offered.
Page : 1 of 13 The picture may not represent the version offered. Basic Frame Description Page : 2 of 13 Basic Frame Description 1 Introduction The CENTAC C3000 compressor is a reliable and efficient integrally
More informationAs a safety precaution, remove keys from the ignition while working under or around the vehicle.
CAB AND CHASSIS As a safety precaution, remove keys from the ignition while working under or around the vehicle. 1. Approach Check the overall appearance of vehicle stance (not leaning). Check for signs
More informationProdigy Eclipse ECC, EH330 and EH430 C or D Service Parts
This part list contains the service parts for the Eclipse 00, 00, and 800 systems. D series models began early 0 The models that are covered include: EH0 C & D EH0 C & D ECC00 ECC00 ECC800 Contents Head
More informationLG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units
Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller
More informationINSPECTION AND MAINTENANCE CHECKLIST
INSPECTION AND MAINTENANCE CHECKLIST Lattice-Boom Crawler Cranes Models 111-21000 & MLC Series Does Not Apply to Small Crawler Models or Model 31000 This record applies to the following crane: Crane Model:
More informationPH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C
PH120 R410a Refrigerant Rooftop Packaged INDOOR COIL ENTERING AIR TEMP 0 c DB WB 21 23 25 27 29 31 PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C 30 35 40 45 Cap Cap Cap Cap 17 115.3 70.7 11.5
More informationO5DMA-NRG O5DMA-NRG. Self-Contained Multi-Deck Merchandiser 4', 6', 8' & 12' (Dairy / Deli / Beverage / Produce) SHIPPING WEIGHT GENERAL NOTES
GENERAL NOTES " - - -" indicates that the feature is not an option for this case model and/or the data is not yet available. LED lights only. Maximum of 5 rows of Standard Output LED lighted shelves. 3rd
More informationINDUSTRIAL GENERATOR SERVICE
INDUSTRIAL GENERATOR SERVICE PREVENTATIVE MAINTENANCE PROGRAM Customer: Date: Contact Person: Work Order #: Contact Number: ( ) Technician: INSPECTION COMPONENTS 1. GENERAL Check fuel tank level. Check
More information2003 Explorer Sport/Sport-Trac Workshop Manual. 7. Disconnect the vacuum harness connector. Remove the nut.
7. Disconnect the vacuum harness connector. Remove the nut. 8. Remove two nuts, one bolt, and the A/C evaporator housing (19850). Remove the nut located at the bottom of the A/C evaporator housing first.
More informationEngine Compartment Inspection
Engine Compartment Inspection Unit Contents Student Page Student Components Learning Activities Sheet... 7 3 Abbreviated Checklist.... 7 5 Objective Sheet... 7 7 Expanded Checklist... 7 9 * Job Sheets
More information50JZ 7 to 14 kw ( ) STANDARD EFFICIENCY. SINGLE-PACKAGE 50 Hz. ELECTRIC HEAT PUMP UNITS with optional ELECTRIC HEAT
50JZ (50Hz.)-C1SB 50JZ 7 to 14 kw (024-048) STANDARD EFFICIENCY SINGLE-PACKAGE 50 Hz. ELECTRIC HEAT PUMP UNITS with optional ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB
More informationCATÁLOGO TÉCNICO COMERCIAL
CATÁLOGO TÉCNICO COMERCIAL ENFRIADORAS DE AGUA CONDENSADAS POR AIRE Series LCAEX De 350 a 1600 Kw. Compresor de tornillo R-134A Index Identification code Identification code and index... pag. 2 General
More informationCopeland Screw TM Compressors
Copeland Screw TM Compressors Mechanical Guidelines for SHL & SHM Models using ESC-201 Control System Contents: Start-Up Procedure Operating Specifications Maintenance Trouble Shooting Guidelines Start-up
More informationElevator Hydraulic Machine Room Instructor s Guide
Table of Contents Overview.......4 Sensory Inspection 13 Operational Inspection and Maintenance 20 Summary..53 1 Icons Used In This Guide Agenda Topic # Topic Title Duration 1 Overview 30 Minutes 2 3 4
More informationSTART-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:
START-UP INSTRUCTION START-UP CHECKLIST SERIES 5 36000 To 72000 BTU S PACKAGE UNITS 3 To 6 Ton Date: _ Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up
More informationVission 20/20 micro-controller. Operation and service manual
Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1
More informationLG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units
Universal and Multi Split Units If there is fault on any LG universal or multi unit a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the
More informationEnclosed Electric Rotary Screw Compressor Installation Guide
Enclosed Electric Rotary Screw Compressor Installation Guide Air compressors should only be installed trained installation personnel call 800-531-9656 to find a local trained. Warning: Read all installation
More informationElectronic Refrigerator Diagnostics
Electronic Refrigerator Diagnostics IMPORTANT SAFETY NOTICE The information in this presentation is intended for use by individuals possessing adequate backgrounds of electrical, electronic, & mechanical
More informationDrawing Page Drawing Page
Contents Drawing Page Drawing Page L4 Engine...1 L4 Engine - Exploded View...2 V6 Engine...3 V6 Engine - Exploded View... 4 Oil Filter...5 VTEC (Variable Timing Electronic Control) System... 6 Fuel and
More information2003 Mustang Workshop Manual
Page 1 of 6 SECTION 412-03: Air Conditioning 2003 Mustang Workshop Manual DESCRIPTION AND OPERATION Procedure revision date: 06/14/2002 Air Conditioning Printable View (225 KB) The A/C refrigerant system
More informationCENTRIFUGAL CHILLER TECHNICAL DATA SHEET Job Name: Mt Healthy Junior Senior HS Date: 6/25/2009 Version: 06.12 Submitted By: Mary Wilking Unit Description: McQuay Model Number: WSC100MBJ72R/E4212-CE-3**/C3612-BLYY-2*****/R134-BAABM
More informationPreventive Maintenance Checklist:
Description: MO -, EMERGENCY (CATERPILLAR) (File # ) GNMO Frequency: Monthly Estimated Time (hours):. (T)ools, (S)afety Equipment, and (M)aterials Required Safety Procedures 0 Procedures Mechanics/Electricians
More informationRCD Air Cooled Condensing Unit (50/60 Hz)
Environment friendly Easy to access components More efficient air cooled condenser coils Easy to install and maintain The Saudi Factory for Air Conditioning Units RCD Air Cooled Condensing Unit (50/60
More informationSteam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions
INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-8-002-US October 2016 Steam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions These instructions should be read by the Company
More informationSECTION AIR TERMINAL UNITS
SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,
More informationSECTION H4 BOILERMATE DEAERATORS
SAMPLE SPECIFICATIONS PART 1 SECTION H4 BOILERMATE DEAERATORS GENERAL...H4-14 1.01 General...H4-14 PART 2 PRODUCTS...H4-14 2.01 Hardware...H4-14 A. Deaerator...H4-14 B. Make Up Valve and Controller...H4-15
More informationSacramento - Plant - Sacramento
Bob Hackworth Employee Number: 5306 Yeast Refrigeration Compressor #1 S/N: 6734569379 Asset: 21347 Location: Roof Building: A Check/Refill Reservoir 7 9/24/2004 10/1/2004 Replace Processor 7 9/24/2004
More informationControl Panel. Operation and Service Manual
Control Panel Operation and Service Manual 1 2 Important Note Before applying power to the control panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral
More information"SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units
"SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units Spinnaker Industries Inc. Model Series SPOAU 100% Outdoor Air Systems shall be factory assembled, wired and
More informationAPPRENTICE TECHNICIAN PROGRESS LOG
APPRENTICE TECHNICIAN PROGRESS LOG APPRENTICE INRUCTIONS: At the end of each day track your progress on the attached log by including work order number and date next to each new skill you perform. Have
More informationA. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.
PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the
More informationSeasonPak Packaged Air-Cooled Water Chiller
Installation Manual IM 676 Group: Chiller Part Number: 594920Y Date: July 1996 Supersedes: None SeasonPak Packaged Air-Cooled Water Chiller Models ALR 032E Through 185E 1996 McQuay International Table
More informationProduct Catalog. NQ Series. Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons
Product Catalog NQ Series Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons Page Intentionally Blank Contents Standard Features...1 Available Options...3 Oversized Pumps... 3 High Flow Unit
More information