ECO Pump successfully prevents slow release of oil from Substation Secondary Containment System
|
|
- Dinah Singleton
- 6 years ago
- Views:
Transcription
1 Substation Secondary Containment System In January, 2013 a C.I.Agent Storm Water Solutions ECO Pump was installed at a Cleveland area substation for a major utility as part of the secondary containment system. This was a new site with new transformers and containment area. The ECO Pump was located in a sump where the containment site drains. The ECO Pump is a robust submersible pump and zero voltage pump switch designed with a C.I.Agent oil solidifying filter. This design allows for all pump discharges to first be filtered through a one micron pre-filter, and if hydrocarbons overwhelm the pre-filter, a main filter filled with C.I.Agent polymers will solidify not allowing any hydrocarbons to leave the site. In late May, the utility informed C.I. Agent Solutions that the pump was running continuously. On June 4, 2013 a ECO Pump set in utility vault C.I.Agent Solutions representative visited the site to witness the ECO Pump performance. Upon arrival to the site, it was observed that the new transformer had been leaking and there was oil on the top of the pad, on three sides of the pad, and on the stone around the pad. The representative confirmed this with a Hydrocarbon Detection Strip. Oil leaking from transformer and indicated by Hydrocarbon Detection Strip
2 There was no visible oil in the sump. The representative monitored the water coming out of the ECO Pump and tested it with Hydrocarbon Detection Strips. No visible sheen was detected nor did the strip indicate the presence of hydrocarbons. The ECO Pump, probably through vibration, had moved slightly and trapped the float switch inside the ECO Pump, causing the pump to run continuously. The ECO Pump was put back in position and was functioning normally again. No oil presence downstream A couple of weeks later C.I.Agent Solutions was contacted as the ECO Pump was not pumping. On June 28, 2013 the C.I.Agent Solutions representative brought a new ECO Pump to the site. This model had a sealed bottom. The addition of a bottom to the ECO Pump makes it impossible for the bottom of the pump to move and lodge against the float switch as the pump bottom is bolted to the filter bottom. This is a permanent addition to all new ECO Pumps. Oil sheen visible in the manhole The representative opened the lid of the manhole to find three feet of water above the original ECO Pump. The water had oil sheen on the surface. He unplugged the pump and checked the outlet for current. It was hot. He lowered the new ECO Pump into the sump and anchored it to keep it from moving. He plugged in the new ECO Pump and it pumped for more than an hour, nonstop, until the water in the sump was about six inches down from the top of the pump. The oil sheen was getting heavier as time passed. The water that was being pumped and discharged out of the ECO Pump was monitored and checked with Hydrocarbon Detection Strips. There was no indication of oil. The pump stopped pumping even though water was still higher than the normal float setting. The ECO Pump top contains a sealed plug that can be removed to view the internal components inside the filter as well as to test the float switch and thus pump. The plug was removed from the top of the ECO Pump. It was observed that water flow through the filter was nearly stopped. When the float was manually lifted the pump would turn on and was functioning properly. 2 P a g e
3 The new ECO Pump was unplugged and removed from the sump. The old ECO Pump was also removed. The pre-filter on the outside of both ECO Pumps was saturated with oil. The ECO Pumps, both original and replacement, had been blinded by the oil and kept the contaminated water in the sump and containment unit. This utility and many others had used oil sensing switches for this application in the past. After many years of failures, this utility decided to change to the ECO Pump technology. Through laboratory testing of this situation, if the utility had continued using the oil sensing switch, it would have released the oil. The representative returned the two ECO Pumps to the factory for further evaluation. Upon evaluation: Box 1 (the first ECO Pump with no bottom) The perforated cylinder and pump looked to be in good shape. The pump was powered and activated with the float switch. The pump performed to specifications. Box 2 (the second ECO Pump with a bottom) The perforated cylinder, switch and pump looked to be in good shape. The pump performed to specifications. Analysis Pre-Filter: The pre-filtration fabrics were analyzed for total oil content on ECO Pump #1 with a bottom and ECO Pump #2 without a bottom. (Note: ECO Pump#1 is actually the second pump used and ECO Pump #2 was the original pump) The total square inches of each pre-filter were 820 sq. in. A 36 square inch vertical strip was taken from each prefilter and the oil extracted with DCM per EPA method 3550 for solids. The DCM extract was dried with sodium sulfate. The DCM evaporated off at 120C and the weight of residue weighed. The residue was light oil with a slight petroleum odor. (see photo). The specific gravity of the oil was This constant was used to convert weight to volume. Hydrocarbons from pre-filters 3 P a g e
4 Oil in Pre-Filters Results Pre-filter pump#1 Pre-filter pump#2 Wt. oil in 36sq/in test strip grams Total oil in 820 sq./in prefilter grams Total Vol. oil in Prefilter 680 ml or 3/4 quart 326ml or 1/3 quart Physical Inspection of the Filters: The filters from ECO Pump #1 with a sealed bottom and ECO Pump #2 without a bottom were inspected for evidence of oil solidification/encapsulation. The ECO Pump filter resides inside the pre-filter, and contains 6 layers of C.I. Agent Agent-Q. Each layer contains quilted packets of C.I.Agent, a proprietary oil solidifier polymer which is designed to allow water to freely pass through, while retaining and encapsulating oils. When the polymers become fully saturated with oil, the solidification process causes swelling and agglomeration of the free polymer into flakes and sheets which seal off all flow of both oil and water. Oil saturation Filter #: 1 ECO Pump with Bottom Filter #2: ECO Pump without Bottom The examination of the solidifier in the Agent Q packets as shown in the above photos reveals that the fine polymer powder has agglomerated into flakes indicating oil saturation. Unfortunately it is not possible to solvent extract out the oil from the polymer filter to determine the extent of oil saturation, as the polymer will encapsulate the solvent, and dissolve into the solvent during the extraction process. The filter acts like a chemical valve and is operating successfully if the following conditions are met: The pump influent through the filter is restricted preventing pumping Field inspection through the pump top removable plug will validate water restriction Evidence of pre-filters saturated with oil Examination of polymer for agglomeration into flakes showing that the chemical valve had been successfully activated preventing a release of oil 4 P a g e
5 It was concluded through these studies and the field testing that both ECO Pump filters performed their expected function. Oil, both emulsified and non-emulsified, was stopped in the sump and prevented from leaving the site. C.I.Agent Storm Water Solutions brings together diverse talents and experience to continually seek out innovative ideas and partnerships to offer solutions to a variety of industries and government entities. If your facilities, operations or jurisdiction are looking for ways to keep pollutants out of the environment or certain systems, bring your challenge to C.I.Agent Storm Water Solutions. Water Monitoring Systems Water Filtering Systems Water Inlet Protection Water Diversion Systems C.I.Agent Storm Water Solutions, LLC 5142 Bolsa Ave, Suite 105 Huntington Beach, CA USA P a g e
C.I.Agent HFF Oil Stop Valve
Manufacturer's Recommended Installation and Maintenance for C.I.Agent HFF Oil Stop Valve Manufactured by: C.I.Agent Solutions, LLC 11760 Commonwealth Drive Louisville, KY 40299 866-242-4368 502-267-0101
More informationInstallation and Operation Instruction Manual INSMAN-201. Industrial Multi Media Single Tank
Installation and Operation Instruction Manual INSMAN-201 Industrial Multi Media Single Tank Phone: 951.656.6716 Toll-Free: 800.854.4788 www.yardneyfilters.com 1 Yardney Water Management Systems, Inc. 6666
More informationInstallation Notes for Ford Excursion 7.3L
The following document is used in conjunction with the puradyn Bypass Oil Filtration System Installation Manual (PFT 8) that is included in the unit box, and as such, should be considered a supplemental
More informationCRITICAL FUEL FILTRATION SYSTEM For Fuel Storage Up To 10,000 Gallons (38,000 liters)
CRITICAL FUEL FILTRATION SYSTEM For Fuel Storage Up To 10,000 Gallons (38,000 liters) Overview Model CF4.0-PLC The Model 4.0-PLC is a fuel polishing system that automatically removes water and debris to
More informationINSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS
INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS CONTENTS Introduction Safety Operating Principle System Installation Initial Startup System Operations Troubleshooting Maintenance
More informationUSES FOR RECYCLED OIL
USES FOR RECYCLED OIL What happens to your recycled used oil? Used oil, or 'sump oil' as it is sometimes called, should not be thrown away. Although it gets dirty, used oil can be cleaned of contaminants
More informationEfficiency powered to infinity. Nederman Filtac oil mist filters for continuous operation
Efficiency powered to infinity Nederman Filtac oil mist filters for continuous operation Clean air around the clock Do you need a rock-solid solution for high-efficiency air filtration in your metalworking
More informationTo ensure proper installation, digital pictures with contact information to before startup.
Check List for Optimal Filter Performance? There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing or
More informationFUELTEC MODEL CF4.0. CRITICAL FUEL FILTRATION SYSTEM For Fuel Storage Up To 10,000 Gallons (38,000 liters)
FUELTEC MODEL CF4.0 CRITICAL FUEL FILTRATION SYSTEM For Fuel Storage Up To 10,000 Gallons (38,000 liters) Today s diesel engines require aircraft quality fuel. Not to many years ago diesel engines were
More informationInstallation Notes for Asplundh Chipper Model- 1003ASP- (EPS) Kubota 3.3 L KIT DOC
Note: Even though a banjo fitting has been provided, some engines have been known to have different size drain plugs, requiring a different size banjo fitting. If the banjo fitting provided does not match
More informationPurifiner Water Leak Test Report
Purifiner Water Leak Test Report 1 Summary This document and the content herein contains the procedure, log, protocol, report and analysis for the Purifiner leak test performed at Wågene Purifiner Technology
More informationLA CONNER MARINA MANDATORY BEST MANAGEMENT PRACTICES
LA CONNER MARINA MANDATORY BEST MANAGEMENT PRACTICES The following mandatory BMPs will be implemented at the La Conner Marina, per the Boatyard General Permit (effective June 1, 2011), issued by the Department
More informationDMS-9203, Asphaltic Concrete Patching Material (Containerized)
Overview Effective Date: July 1999 July 2004 This specification shall govern for containerized asphaltic concrete mixture intended primarily for cool to cold, wet weather repair of small pavement areas.
More informationTom Parece, Reggie Donoghue and Mike Domenica P. R. Ammann
To: From: Subject: Tom Parece, Reggie Donoghue and Mike Domenica P. R. Ammann TM #7 A STEP Effluent Has a Big Cost Advantage over a Gravity for Downtown Orleans Date: January 12, 2017 Summary In its preliminary
More informationG E N E S I S R O C v AUTOMATIC REPLENISHMENT MODULE
G E N E S I S R O C v AUTOMATIC REPLENISHMENT MODULE INSTALLATION AND USE Congratulations on your purchase of the GENESIS ROCv Automatic Replenishment Module! Please take a few moments to read and follow
More informationTekleen LPF USERS AUTOMATIC FILTERS, INC. MANUAL
AUTOMATIC FILTERS, INC. 2672 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 310 839 2828 800 336 1942 FAX 310 839 6878 www.tekleen.com info@tekleen.com Tekleen LPF USERS MANUAL Table of Contents SECTION I INTRODUCTION
More informationINVESTIGATION REPORT PREPARED FOR: UNIVERSITY OF NORTHERN IOWA CEDAR FALLS, IA
INVESTIGATION REPORT PREPARED FOR: UNIVERSITY OF NORTHERN IOWA CEDAR FALLS, IA Prepared By: HBK Engineering, LLC. 921 West Van Buren Street, Suite 100 Chicago, IL HBK PROJECT # 18 0788 October 2, 2018
More informationBiodiesel. As fossil fuels become increasingly expensive to extract and produce, bio-diesel is
Aaron Paternoster CHEM 380 10D Prof. Laurie Grove January 30, 2015 Biodiesel Introduction As fossil fuels become increasingly expensive to extract and produce, bio-diesel is proving to be an economically
More informationSection 4 DMS-9203, Asphaltic Concrete Patching Material (Containerized)
Section 4 DMS-9203, Asphaltic Concrete Patching Overview Effective Date: August 2004 - December 2005. This Specification governs for rapid curing containerized asphaltic concrete mixture intended primarily
More informationSetting the Standard in Oil Filtration Keep It Clean! & Keep It Green!
Setting the Standard in Oil Filtration Keep It Clean! & Keep It Green! Oil Characteristics Oil does not wear out It oxidizes during the combustion process It becomes contaminated due to high temperatures,
More informationLorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA
Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary
More informationDeploying Smart Wires at the Georgia Power Company (GPC)
Deploying Smart Wires at the Georgia Power Company (GPC) January, 2015 Contents Executive Summary... 3 Introduction... 4 Architecture of the GPC Installations... 5 Performance Summary: Long-term Test...
More informationAir Filtration CLEARPOINT. energy saving compressed air filtration. Truth in Compressed Air.
Air Filtration CLEARPOINT energy saving compressed air filtration Truth in Compressed Air. At a Glance CLEARPOINT Filters uring compressed air generation and distribution, contaminants are introduced to
More informationCore2Clean Systems. SPRAY MOP FOG S Y S T E M Technical Information
THE SPRAY MOP FOG S Y S T E M Technical Information Copyright June 2003, U.S. and Foreign Patents Pending, September 2002, Tel: (610) 983-4949 Fax: (610) 983-9494 http://www.sterile.com C2C-2002-A1 06/2003
More informationHampton Roads Planning District Commission
Hampton Roads Planning District Commission OBJECTIVE To help Grease Haulers comply with the Regional Consent Order and ensure proper maintenance of grease control devices. BACKGROUND In 2007, Special Orders
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-48 06 15 (May 2014) ---------------------------------- Preparing Activity: USACE Superseding UFGS-48 13 19.00 10 (January 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationCore2Clean Systems THE. SPRAY MOP FOG S Y S T E M Technical Information
THE SPRAY MOP FOG S Y S T E M Technical Information Plus Copyright June 2003, U.S. and Foreign Patents Pending, September 2008, Tel: (610) 644-8335 Fax: (610) 644-8336 http://www.sterile.com C2C-2002-A4
More informationAPCO ASU COMBINATION AIR VALVE
BULLETIN 300.00-1 JANUARY 2016 APCO ASU COMBINATION AIR VALVE - Design - Operation - Performance www.dezurik.com Innovative Air Valve Technology The APCO ASU Combination Air Valve introduces an innovative
More information1BGrease Traps and. Frequently Asked Questions About Grease:
0B 1BGrease Traps and Interceptors 112 W Washington Ave. Fergus Falls MN 56537 Building Department (218)332-5434 Frequently Asked Questions About Grease: Is grease a problem? What is a grease trap and
More information2011 Version D. Bambi Bucket RAINDRAIN OPERATIONS MANUAL. Emergency Response
2011 Version D RAINDRAIN OPERATIONS MANUAL Emergency Response Bambi Bucket RAINDRAIN OPERATIONS MANUAL - Version D Issue Date: June 2011 PLEASE READ BEFORE USING. SEI INDUSTRIES LTD. 7400 Wilson Avenue
More informationCompliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012
Compliance Strategies and Benefits Brian Derge Tanknology Inc. December 6, 2012 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations What we have learned over 15 years of testing Sump
More informationLABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL
LABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL Content 1. Introduction...2 2. Important safety instruction...3 3. System component...4 4. Engineering design overview...5 5. Installation...6
More informationB2. Fueling Operations
B2. Fueling Operations Commercial / Industrial / Institutional & Municipal Pollution Prevention Goal: Prevent or reduce the risk of discharge of pollutants to stormwater from vehicle and equipment fueling
More informationREPORT SYNTHETIC AND MINERAL CRUDE OILS COMPATIBILITY STUDY
REPORT SYNTHETIC AND MINERAL CRUDE OILS COMPATIBILITY STUDY Moscow - 2013 TABLE OF CONTENTS Page Introduction... 3 1. Selecting and adapting the existing methods of compatibility study for mixed synthetic
More informationPBM VALVES HANDLE PAINTS, COATINGS, RESINS AND ADHESIVES
PBM VALVES HANDLE PAINTS, COATINGS, RESINS AND ADHESIVES PBM Valves Can Handle It Extra gooey resin? Super-duper adhesive? Really expensive paint? Anything similar? A valve engineering and manufacturing
More informationOVERVIEW OPERATION. 2 Stormceptor EF Technical Manual
EF Technical Manual OVERVIEW Stormceptor EF is a continuation and evolution of the most globally recognized oil-grit separator (OGS) stormwater treatment technology - Stormceptor. Also known as a hydrodynamic
More informationArizona Tank Closure, Assessment and Response
Arizona Tank Closure, Assessment and Response By: Phillip A. Schneider, P.E. August 1, 2013 Agenda > Closure > Assessment > Response Exceptions to the UST State and Federal Regulations > USTs storing heating
More informationOWS OPERATIONS & MAINTENANCE
SUPPLEMENTAL INSTRUCTIONS 1. INTRODUCTION 1.1. Containment Solutions manufactures Oil/Water Separator (OWS) tanks with internal coalescing plates. These units are available in single or double-wall model
More informationMILITARY SPECIFICATION CORROSION PREVENTIVE COMPOUNDS, WATER DISPLACING, ULTRA-THIN FILM PAGE 1
NOT MEASUREMENT SENSITIVE 26 November 1997 SUPERSEDING AMENDMENT 2 31 July 1996 MILITARY SPECIFICATION CORROSION PREVENTIVE COMPOUNDS, WATER DISPLACING, ULTRA-THIN FILM This amendment forms a part of,
More informationEffects of Lubrication on Connector Processing
Effects of Lubrication on Connector Processing Abstract: A class of lubricants described as electrical conductive lubricants are frequently encountered in the electronics industry and especially in conjunction
More informationSwitching To Ethanol?
Switching To Ethanol? Guidelines for Conversion of Retail Service Station Tanks from Gasoline to Ethanol - Blended Gasoline Central Illinois Manufacturing Co. 201 N. Champaign St. Bement, IL 61813 Ph 217.678.2511
More informationSCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 LABORATORY SERVICES, PETROTRIN Southern Main Road Pointe-A-Pierre, Trinidad, Trinidad & Tobago Peter Bhim Phone: 868 658 4200 CHEMICAL Valid To: November 30,
More informationBiodiesel Fuel Quality
2012 Collective Biofuels Conference Temecula, California Biodiesel Fuel Quality August 17-19, 2012 Presented by Gorge Analytical, LLC Significant effort and technical consideration has gone in to developing
More informationMitsubishi SF6 Gas Circuit Breaker Type 100 SFMT-40E. Breaker Failure Report
Mitsubishi F6 Gas Circuit Breaker ype 100 FM-40E Breaker Failure Report Prepared by: Jeffery M. Wright Manager ransmission Field ervices Vermont Electric Power Company, Inc. April 6, 2004 13:08 VELCO experienced
More informationDMS-9202, Asphaltic Concrete Patching Material (Stockpile Storage)
Overview Effective Date: July 1999 July 2004 This specification shall govern for an asphaltic concrete mixture intended primarily as a cool to cold weather stockpile patching mix for maintenance. It shall
More informationSanta Fe Calvada Mine. Final Closure of a Heap Leach Facility Case Study in Design and Construction of E-cells
Santa Fe Calvada Mine Final Closure of a Heap Leach Facility Case Study in Design and Construction of E-cells Site Location Location with Surrounding Topography Overall Site Layout Google Earth View History
More informationHigh Efficiency Bypass Oil Filtration Systems for your Engine and Hydraulic Oil. Kevin Kroger (PuraDYN Filter Yechnologies MDEC 2007.
High Efficiency Bypass Oil Filtration Systems for your Engine and Hydraulic Oil Kevin Kroger (PuraDYN Filter Yechnologies MDEC 2007 The Journey to CBM Reactive Planned/ Scheduled Condition Based Maintenance
More informationStormwater Treatment System
The Up-Flo Filter Stormwater Treatment System Table of Contents 3 Up-Flo Filter - Overview - General Product Description - Typical Configurations - Maintenance Services 4 Operation - Introduction - Pollutant
More informationUltipleat SRT Filters
Lenntech info@lenntech.com www.lenntech.com Tel. +31-15-261.09.00 Fax. +31-15-261.62.89 Ultipleat SRT Filters Stress Resistant Technology The Ultimate in Filter Design Ultipleat SRT Filters Pall s Ultipleat
More informationOur COmpany... Our products ExCEllEnCE in CuSTOmEr SErviCE...
Our Company... Air Flow Technology, Inc. started in business in the mid-1980 s by calling directly on body shops and end users. Since then we have grown into a full line manufacturer of quality synthetic
More informationArticle: The Formation & Testing of Sludge in Bunker Fuels By Dr Sunil Kumar Laboratory Manager VPS Fujairah 15th January 2018
Article: The Formation & Testing of Sludge in Bunker Fuels By Dr Sunil Kumar Laboratory Manager VPS Fujairah 15th January 2018 Introduction Sludge formation in bunker fuel is the source of major operational
More informationAsphalt Emulsion VOC Testing
Asphalt Emulsion VOC Testing Presentation To PPRA Meeting Florida - 2016 Arlis Kadrmas Presentation Outline Background Why VOC testing of emulsified asphalt? Recovery Procedures used for residue VOC testing
More informationOur heritage enables us to take a small company approach to the day to day activities of each and every customer.
Our Company... Air Flow Technology, Inc. started in business in the mid-1980 s... by calling directly on body shops and end users. We are now a full line manufacturer of quality synthetic HVAC, industrial
More informationSludge Thickening. Wastewater Treatment Review. Gravity Thickening
Wastewater Treatment Review 10 Sludge Thickening nw ate rc oll e ge 20 Gravity Thickening ca Principle of Operation 1. Uses gravitational forces to separate water from sludge 2. Solids settle to bottom
More informationExcerpt from Chapter 3 of the City Code that address Fats, Oils and Grease (FOG) control program that was adopted by the City Council on May 9, 2016.
Excerpt from Chapter 3 of the City Code that address Fats, Oils and Grease (FOG) control program that was adopted by the City Council on May 9, 2016. Subd. 11. Grease Interceptors. A. Grease interceptors
More informationMATERIAL SPECIFICATION FOR EMULSIFIED ASPHALT
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 1103 FEBRUARY 1996 MATERIAL SPECIFICATION FOR EMULSIFIED ASPHALT 1103.01 SCOPE 1103.02 REFERENCES 1103.03 Not Used 1103.04 Not Used 1103.05 MATERIALS
More informationClass 5 to 7 Truck and Bus Hydraulic Brake System
Class 5 to 7 Truck and Bus Hydraulic Brake System Diagnostic Guide 2nd Edition www.bosch.us Important Service tes The information in this publication was current at the time of printing. The information
More informationPRODUCT LISTING. Water Media
Mi-Glow Fluorescent Material Wet Method Water Media MI-GLOW 834 - Mi-Glow 800 fluorescent yellow-green particles premixed with powdered Wetting Agent 34 for use in water media. It is designed to be used
More informationTHIS BULLETIN MODIFIES THE A4A BULLETIN , DATED DECEMBER 11, 2017
Bulletin 2018.1 Update on ATA103 Requirements June 5, 2018 THIS BULLETIN MODIFIES THE A4A BULLETIN 2017.2, DATED DECEMBER 11, 2017 Based on feedback from the industry, A4A is modifying the deadlines for
More informationLEAKING UNDERGROUND STORAGE TANKS
LEAKING UNDERGROUND 9-12 STORAGE TANKS SUBJECTS: TIME: Science (Physical Science, Environmental Science), Social Studies (Economics), Math 2 class periods MATERIALS: 2 sheets of graph of bookkeeping paper
More information(Please type or use black ink)
(Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of
More informationFUELTEC CF8.0 PLC AUTOMATIC FUEL POLISHING SYSTEM 480 GPH
FUELTEC CF8.0 PLC AUTOMATIC FUEL POLISHING SYSTEM 480 GPH The Model 8.0-PLC is a fuel polishing system that automatically removes water and debris to prevent bacterial growth and unexpected engine shut
More informationOKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS
OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008
More informationSeries Base mounted pump. Installation and operating instructions
Series 4030 Installation and File No: 40.80 Date: june 25, 2015 Supersedes: 40.80 Date: october 10, 2009 contents General 4 Inspection 4 Installation - Series 4030 base mounted Pump 4 1.0 Location 4 2.0
More informationWaste Lubricating Oil Purification and Recovery
Waste Lubricating Oil Purification and Recovery It may be surprising to note that, under normal circumstances, lubricating oil cannot be easily destroyed; it only gets dirty and is easily contaminated
More informationTHE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS
THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS Presented by: Joyce A. Rizzo President JD2 Environmental, Inc. 800 East Washington Street West Chester, PA 19380 www.jd2env.com
More information6.4L Diesel Water In Fuel GSB
General Service Bulletin (GSB): This GSB targets the diagnosis, inspection and repair of the 6.4L diesel fuel system. Some 6.4L diesel vehicles may experience drivability concerns due to fuel system failures.
More informationSteam Turbine Seal Rub
Steam Turbine Seal Rub Date : November 19, 2014 Steam Turbine Seal Rub Vibration data helps to identify a steam turbine seal rub. Sotirios Christofi Deputy Manager, Head of Mechanical Maintenance, Thessaloniki
More informationNewton s First Law. Evaluation copy. Vernier data-collection interface
Newton s First Law Experiment 3 INTRODUCTION Everyone knows that force and motion are related. A stationary object will not begin to move unless some agent applies a force to it. But just how does the
More informationPhase-Two Water Detector
Phase-Two Water Detector Frequently Asked Questions Sections: Background on Phase Separation Fuel Compatibility Equipment Compatibility Phase-Two Operability Background on Phase Separation 1. What is phase
More informationCOMPETITIVE INITIATIVE AVIATION FUEL RECLAMATION SYSTEM TECHNICAL SPECIFICATION
1.0 SCOPE COMPETITIVE INITIATIVE AVIATION FUEL RECLAMATION SYSTEM TECHNICAL SPECIFICATION A system brand name or equal to Filterdyne Filtration Systems, Inc. Fuel Reclaim System Model F-111 Special, as
More informationWASH SYSTEM. Instructions for Use
WASH SYSTEM Instructions for Use COMPONENTS LIST THESE SYSTEMS MUST BE CORRECTLY INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF REGULATORY WATER AUTHORITY PRIOR TO USE Pre-Filter / Release Valve Outlet Water
More informationCF50.0 CRITICAL FUEL SYSTEMS For Fuel Storage Up To 250,000 Gallons (946,000 liters)
CF50.0 CRITICAL FUEL SYSTEMS For Fuel Storage Up To 250,000 Gallons (946,000 liters) Overview: THE CF50.0-PLC-UL Fuel polishing system was initially designed in 2015 for a very large data center group.
More informationONSITE WASTEWATER TREATMENT SYSTEM Property Transfer Certification Instructions and Inspection Report
ONSITE WASTEWATER TREATMENT SYSTEM Property Transfer Certification Instructions and Inspection Report These instructions are for homeowners and inspectors completing the onsite wastewater treatment system
More informationFlorida Community Services Corporation of Walton County d/b/a Regional Utilities (Regional) FOG Control Policy
Florida Community Services Corporation of Walton County d/b/a Regional Utilities (Regional) FOG Control Policy 1. Introduction Fats, Oils, & Grease (FOG) are one of the primary causes of stoppages, backups,
More informationThis publication is copyrighted and intended for the sole use of General Industries - 07/07/2016
AQUASWEEP JUNE 2009 INSTALLATION INSTRUCTIONS FOR AQUASWEEP UNDERGROUND OIL WATER SEPARATORS PREFACE i. Install the AquaSweep Oil Water Separator using personnel who have knowledge and experience in procedures
More informationHow to Make Biodiesel
How to Make Biodiesel Overview Biodiesel can me made by anyone in a simple process that is often compared to brewing beer. For this reason it is possible for nearly anyone to take control of their own
More information5. What are other common issues with on farm fuel storage?
5. What are other common issues with on farm fuel storage? Storing fuel on the farm poses some interesting challenges to producers in order to maintain the quality and quantity of the product. Changes
More informationVILLAGE OF ORLAND PARK
14700 Ravinia Avenue Orland Park, IL 60462 www.orland-park.il.us Monday, 6:00 PM Village Hall Public Works Committee Chairman Michael F. Carroll Trustees James V. Dodge and Carole Griffin Ruzich Village
More informationMarine Fuel Filtration. Marine Turbine Series. Stage One: Separation. Stage Two: Coalescing. Stage Three: Filtration. And more
filter assemblies are designed to be installed on the vacuum side of the fuel transfer pump for best efficiency and protect precision engine components from dirt, rust, algae, asphaltines, varnishes, and
More informationHow to Design a Genset Fuel System With Gen Evo (Franklin) ATG
ESS.HT.612 How to Design a Genset Fuel System With Gen Evo (Franklin) ATG GENERAL The GenEvo fuel system is a comprehensive fuel manager for reliable generator fuel supply. The Franklin Fuelling EVO 550
More informationTechnical Procedure for the Examination of Arson Evidence
Technical Procedure for the Examination of Arson Evidence 1.0 Purpose This technical procedure shall be followed for the examination of arson (fire debris) evidence. 2.0 Scope This procedure applies to
More informationFEDERAL SPECIFICATION ETHER, PETROLEUM; TECHNICAL GRADE. 1.1 Scope. This specification covers technical grade petroleum ether to be used as a solvent.
METRIC 4 May 2015 SUPERSEDING O-E-751C 10 January 2003 FEDERAL SPECIFICATION ETHER, PETROLEUM; TECHNICAL GRADE The General Services Administration has authorized the use of this federal specification by
More informationTRANSFORMER SERVICE. ABB Ability inspection for transformers TXplore Oil-filled transformer internal inspection service
TRANSFORMER SERVICE ABB Ability inspection for transformers TXplore Oil-filled transformer internal inspection service 2 ABB ABILIT Y INSPECTION FOR TR ANSFORMERS TXPLORE Use ABB's inspection service to
More informationPENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation, these instructions must be read carefully and understood. PRODUCT WARRANTY Emerson warrants its Penberthy products as designed and manufactured to be free of defects in the material
More informationMarine Fuel Filtration Marine 800 Series
Racor recyclers offer large diesel engine operators both ease of maintenance and continuous engine operation. Continuous operations include filter changeouts and the draining of accumulated water from
More informationToday s Fuels and Compatibility With Storage Systems
Today s Fuels and Compatibility With Storage Systems NISTM Alexandria, VA June 9, 2015 LO R R I G R A I N AW I D I R E C TO R O F T E C H N I C A L S E R V I C E S S T I / S P FA LG R A I N AW I @ S T
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationStatic Discharge Ignition of Combustible Atmospheres
26 Autumn 2012 Discharges of static electricity from hoses are known to cause the ignition of combustible atmospheres during the transfer of material to or from vacuum tankers and road tankers. There are
More informationRAINWATER HARVESTING INSTALLATION GUIDE RH High Capacity Vortex Rainwater Fine Filter for Above or Below Grade Application
RAINWATER HARVESTING INSTALLATION GUIDE RH9521-12 High Capacity Vortex Rainwater Fine Filter for Above or Below Grade Application RH9521-12 Vortex Filter Operation and Maintenance Overview The RH9521-12
More informationSUBMERSIBLE DIRTY WATER PUMP
FOR USE WITH A 110V SUPPLY ONLY SUBMERSIBLE DIRTY WATER PUMP MODEL NO: DWP210A PART NO: 7230102 OPERATION & MAINTENANCE INSTRUCTIONS LS0115 INTRODUCTION Thank you for purchasing this CLARKE Submersible
More informationRESOLUTION MEPC.205(62) Adopted on 15 July GUIDELINES AND SPECIFICATIONS FOR ADD-ON EQUIPMENT FOR UPGRADING RESOLUTION
MEPC.60(33)-COMPLIANT OIL FILTERING EQUIPMENT MEPC.60(33)-COMPLIANT OIL FILTERING EQUIPMENT MEPC 62/24/Add.1 Annex 24, page 1 ANNEX 24 RESOLUTION MEPC.205(62) 2011 GUIDELINES AND SPECIFICATIONS FOR ADD-ON
More informationProfessional Séries. Professional Séries. Model T03828 SUBMERSIBLE SUMP DUPLEX SYSTEM SUBMERSIBLE SUMP DUPLEX SYSTEM. 1/3HP 2400 GPH Head of 20 (6 m)
Model T0828 Primary pump 1/HP 200 GPH Head of 20 (6 m) SUBMERSIBLE SUMP DUPLEX SYSTEM Professional Séries Discharge: 1 1/2 ABS DWV pipe Electric cable: 9 piggyback type Oil cooled Cast iron construction
More informationAPPLICATION BRIEF. Model 4730/4731 NTO New Technology Oven. June 2000
APPLICATION BRIEF Model 4730/4731 NTO New Technology Oven June 2000 Introduction The quality of asphalt concrete pavement is typically characterized by two very important factors the asphalt binder content
More informationABCD BFDC BEDA AB CDEFCC
ABCD BFDC BEDA AB CDEFCC ABCD BFDC BEDA AB CDEFCC AFC Oil/ Water Separator Specifications and Operation & Maintenance Schedule 1) Model of AFC Oil/ Water Separator: a)
More informationEnvironmental Questionnaire
Environmental naire Instructions: The following questions should be asked of (1) the current Owner of the Property, (2) any Major Occupant of the Property or, if the Property does not have any major Occupants,
More informationVWR Zero Air Generator
Technical Information Installation, Operation, and Maintenance Manual VWR 89237-564 Zero Air Generator Figure 1 - VWR Zero Air Generator These instructions must be thoroughly read and understood before
More informationFiltered Pet Waterer. Owner s Manual MODEL NO SW 2000 MW 2000 LW. Model and serial number may be found at the rear of the waterer base.
Owner s Manual Filtered Pet Waterer MODEL NO. 2000 SW 2000 MW 2000 LW Model and serial number may be found at the rear of the waterer base. Please record both model and serial number in a safe place for
More informationExperimental investigation on constant-speed diesel engine fueled with. biofuel mixtures under the effect of fuel injection
Experimental investigation on constant-speed diesel engine fueled with biofuel mixtures under the effect of fuel injection 1 I. Vinoth kanna *, 2 K. Subramani, 3 A. Devaraj 1 2 3 Department of Mechanical
More informationOxidation Technologies for Stationary Rich and Lean Burn Engines
Oxidation Technologies for Stationary Rich and Lean Burn Engines Advances in Emission Control and Monitoring Technology for Industrial Sources Exton, PA July 9-10, 2008 1 Oxidation Catalyst Technology
More information