Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Size: px
Start display at page:

Download "Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions"

Transcription

1 Solar Thermal Grant Solar Pump Station Installation & Servicing Instructions Part No. DOC 96. Rev 02. October 2012

2 Important Note Important Note for Installers The Pump Station supplied with your Grant Solar Thermal system differs from that shown in the Installation Instructions supplied. This change is part of our continued product improvement process. The information in these Solar Pump Station Installation Instructions replaces that given in Sections 13 and 14 of the Grant Solar Thermal Systems Installation Instructions (DOC 73. Rev.02). Please read these Pump Station instructions in conjunction with the System Installation Instructions supplied. After commissioning, please leave both the System Installation Instructions and these Pump Station Instructions with the user for future reference. Important: All system pipe connections must use compression fittings with brass olives. Soft soldered joints must NOT be used on the solar primary circuit. Plastic pipe must NOT be used for any part of the solar primary circuit. 2Important Note GRANT ENGINEERING (UK) LIMITED Hopton House, Hopton Industrial Estate, Devizes, Wiltshire SN10 2EU Tel: Fax: This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. Grant Engineering (UK) Limited No part of this manual may be reproduced by any means without prior written consent.

3 Contents 1 Introduction Description 4 2 Technical Specifications Specification Pump Performance Dimensions Components 6 3 Installation General Fitting Procedure System Connections Expansion Vessel Safety Valve Discharge Electrical Connection 9 4 Commissioning Expansion Vessel Filling Valves Gravity Brakes Solar Fluid Filling the System Filling Procedure Releasing Trapped Air Setting the Flow Rate 13 5 Fault Finding No System Circulation Pump not Operating Loss of System Pressure 14 6 Spare Parts 15 Contents 3

4 1 Introduction 1.1 Description A two-line Solar Pump Station for the circulation of glycol mix solar fluid through Grant solar thermal systems. All components are housed within an insulated enclosure designed to be wall mounted. The pump station provides the following functions: Filling and flushing connection points Fluid flow rate regulation System pressure and temperature readings Check valves (Gravity Brakes) for anti-gravitation circulation Safety pressure relief valve and discharge connection System expansion vessel connection point Isolation valves for upper and lower system levels and pump psi bar OFF ON OFF ON Flow - from Collectors Return - to Collectors MADE IN ITALY 4Introduction Figure 1-1: Pump station with front cover removed

5 2 Technical Specifications 2.1 Specification System pipe connections: Safety valve: Safety valve discharge connection: Pressure gauge range: Thermometer gauge range: Maximum run temperatures: Maximum peak temperatures: Maximum glycol (%) in solar fluid: Circulator: Electrical supply: Insulation: Flow and Return valves: Min pressure to open check valve: Check valve activation: ¾" BSP Female 6 bar - certified TUV to SV Directive 97/23/CE ¾" BSP Female 0-10 bar C 130 C 150 C 50% WILO STAR ST 15-6 Eco. 3P connections, 1M-130mm Class F, PN10, TF110, IP44, 2 µf, 230V 50Hz, VDE, CE V 50 Hz Black PPE density 40kg/m³, plain DN20. ¾" BSP Female connection, integral check valve 2 kpa (200mm w.g./ 20mbar) Closure at 90 and opening at Pump Performance 6 5 Head (m) Water flow (m 3 /h) Figure 2-1: Standard 6m head pump - performance curves Head (m) Water flow (m 3 /h) Figure 2-2: Optional 8m head pump - performance curves Technical Specifications 5

6 2 Technical Specifications 2.3 Dimensions 312 Side view of pump station psi bar Plan view of pump station Technical Specifications Components Key No. Description 1 Flow valve (red knob) - ¾" BSP Female connection 2 Thermometer (0-160 C) on flow valve 3 Wall bracket with retaining clip and screw 4 Connection pipe - copper 18mm 5 Manual air vent with hose connection 6 Air separator with integral manual air vent 7 Filling hose connectors (x 2) to fit filling/flushing valve - 15mm dia x ¾" swivel nut 8 System connection - ¾" Female 9 System connection - ¾" Female 10 Filling return valve connection - ¾" BSP Male with safety cap and chain 11 Flow meter range 2-12 l/min 12 Filling flow valve connection - ¾" BSP Male with safety cap and chain 13 Filling/shut-off valve 14 Circulator Wilo STAR ST m head 15 Expansion vessel connection ¾" BSP Male with flat gasket connection 16 Pressure gauge (0-10bar) 17 Safety valve discharge connection 18 Safety valve (6 bar) 19 Return valve (blue knob) - ¾" BSP Female connection. ¾" BSP Male connection always open on right side 20 Thermometer (0-160 C) on return valve 21 Insulated housing

7 3 Installation 3.1 General Installation of this pump station must be carried out by a competent installer in compliance with all current local Building Regulations, codes of practice, Health & Safety legislation and any relevant bylaws and regulations in force at the time. All electrical installation work must be carried out by a qualified electrician. All wiring and bonding must comply with current IEE wiring regulations (including any amendments). Wall bracket 3.2 Fitting Procedure 1. Remove the front section of the insulated pump station housing. 2. Undo screw and remove retaining clip from wall bracket. 3. Lift out both the flow valve/air separator assembly and the return valve/pump assembly. 4. Position the back section of the insulated housing in the required location. If necessary check the cover is level using a spirit level and mark the two holes for the wall bracket. Note: The solar pump station MUST only be installed vertically, as shown in Figure Separate the wall bracket from the back section of the housing. Drill the wall with an 8mm drill and securely fix the wall bracket to the wall using the fixings supplied. 6. Fit the back section of the insulated housing onto the wall bracket, taking care to insert it completely. Refer to Figure Re-fit the flow and return assemblies, inserting the body of the flow and return valves into the corresponding fork in the wall bracket. Refer to Figure Fit the retaining clip and secure using the screw provided. 8. Connect the flow and return pipes. Refer to figure 3-3. Insulated housing back section Figure 3-1: Fit back section of housing onto wall bracket Retaining clip Installation Figure 3-2: Re-fitting flow and return assemblies to wall bracket 7

8 3 Installation 3.3 System Connections Solar collectors Note: This is a diagrammatic view showing the connections to the pump station. As such it does NOT include all valves and controls and is NOT intended as a complete system diagram. Important: All system pipe connections must use compression fittings with brass olives. Soft soldered joints must NOT be used on the solar primary circuit. Plastic pipe must NOT be used for any part of the solar primary circuit. OFF ON OFF ON psi bar Hot water cylinder MADE IN ITALY Solar expansion vessel Safety (pressure relief) valve fluid recovery container Figure 3-3: System connections to solar pump station 8Installation 3.4 Expansion Vessel The correct size of expansion vessel should be used, based on the volume of the system i.e. the number of collectors, the length and diameter of the system pipework, etc. For systems using up to 4 Grant solar collectors, with no more than 50 metres of 15mm pipework (total length of flow and return combined), an 18 litre expansion vessel is supplied as standard. For 5 collectors a 24 litre expansion vessel is used. For larger system configurations, contact the Grant Technical department for guidance on the expansion vessel required. The expansion vessel is connected to the pump station via the ¾ BSP connection on the safety valve manifold, using the 1250mm long flexible corrugated stainless steel pipe. This pipe is supplied with flanged ends, each fitted with a ¾ union nut, and two sealing washers (Grant Part No. GS222074). This flexible pipe cannot be cut and must be used as supplied. The expansion vessel is fixed to the wall using the Vessel Mounting kit (Grant Part No. GS222073). This kit includes an isolation valve union and the vessel mounting bracket. Fix the mounting bracket to the wall, using the screws and wall plugs provided, to position the vessel in the required location. IMPORTANT The expansion vessel must be located BELOW the connection on the pump station with the vessel connection pointing upwards. See Figure 3-3.

9 Assemble and fit the isolation valve union as follows, referring to Figure 3-4: Fit the small black sealing washer onto the threaded connection of the bleed valve. Screw the bleed valve into the threaded port in the side of the valve union body and tighten. Remove the thin nut from the thread on the valve union. Fit the threaded connection on the expansion vessel up through the hole in the mounting bracket and secure using the thin nut. Using the sealing washer supplied, fit the valve union to the expansion vessel connection. Tighten the union nut to secure the valve union in the required position. Connect the flexible stainless steel pipe to the safety valve manifold and expansion vessel union valve, using the sealing washers provided with the pipe. Ensure that the expansion vessel isolation valve is OPEN this is indicated when the two indicators (on the square end of the valve) are in line with the valve. Ensure that the bleed valve is fully CLOSED before filling the system. 3.5 Safety Valve Discharge A discharge pipe must be fitted to the outlet of the safety valve. It is recommended that the safety valve discharge should be connection to a suitable discharge recovery tank, such as the Grant safety valve liquid recovery container with drain valve (Grant Part No.GS550001). This discharge pipe should be 15mm copper. IMPORTANT Plastic pipe should NOT be used. 3.6 Electrical Connection The pump requires a 230V 50Hz power supply from the Solar Controller to operate. Refer to the Installation instructions provided with the Solar Controller for further information on the electrical control system wiring. IMPORTANT The electrical supply must be isolated before making the connections to the solar pump. After making the connections ensure cover is fitted to enclosure before reconnecting the electrical supply. The power supply should be connected to the solar circulating pump (in the pump station) as follows: Insert the blade of a small flat screwdriver into the retaining clip on the side of the electrical enclosure on the pump. Carefully prise open the clip and pull the cover upwards and remove from the enclosure. Slacken off the cable gland nut and feed the electrical cable through the gland. See Figure 3-5. Prepare the cable cut back the outer sheath and strip the ends of the three wires as required. Fit the wires into the terminals by pushing the black lever away from the enclosure (to open the terminal). See Figure 3-5. Release the lever to secure the wire in the terminal. Fit the three wires into the terminals as follows: Live terminal L Neutral terminal N Earth terminal Tighten the cable gland to grip the cable and re-fit the cover to the enclosure. Flexible stainless steel pipe Bleed valve Union nut Thin nut Pipe union nut Isolating valve Vessel mounting bracket Cable gland Live terminal Neutral terminal Earth terminal Terminal lever Figure 3-4: Expansion vessel connection Expansion vessel Figure 3-5: Solar pump electrical connections Installation Reconnect the electrical supply to test the operation of the pump. 9

10 4 Commissioning 4.1 Expansion Vessel Ensure that the expansion vessel charge pressure is correct for the system pressure (when cold) and that this, in turn, corresponds to the height of the system. Refer to Table 4-1. The height of the system should be measured from the expansion vessel to the top of the highest collector. NOTE: If the collectors are positioned below the level of the expansion vessel (e.g. if the collectors are mounted at ground level), then measure from the bottom of the collectors to the expansion vessel. This will be a negative height value, e.g. 5 metres. The vessel charge pressure must be checked before filling the system. Height difference Initial expansion System charge pressure (height of the collector vessel C ( bar field minus height pressure (air charge greater than vessel of expansion vessel) setting on valve) charge pressure) - 5m ~ 1.0 bar ~ 1.3 bar < 0m ~ 1.0 bar ~ 1.3 bar < 5m ~ 1.5 bar ~ 1.8 bar < 10m ~ 2.0 bar ~ 2.3 bar < 15m ~ 2.5 bar ~ 2.8 bar > 15m Contact Grant Technical Department for guidance Table 4-1: Expansion vessel pressures 4.2 Filling Valves The Filling flow and return valves, and the Filling/Shut off valve, are used for filling and flushing the solar thermal installation. Refer to Figure 4-1. To enable filling/flushing of the system, the Filling/Shut-off valve must be rotated fully 90 clockwise. Refer to Figure 4-2. This will divert the flow from the filling station, entering the system via the Filling flow valve, through the pump, up to the collectors, through the coil of the cylinder and back to the filling station via the Filling return valve. Filling/ shut-off valve Filling flow valve Figure 4-2: Closing Filling/Shut off valve to prepare to fill system Filling return valve Commissioning Figure 4-1: Filling and flushing valves 10

11 4.3 Gravity Brakes The gravity brakes (check valves) are incorporated into both the flow and return valve assemblies. These gravity breaks operate at 20 mbar and are operated by turning the valve handle on the valves as follows: Flow and Return valves OPEN markers on valve handles in VERTICAL position To prevent gravity circulation of solar fluid, gravity brakes must be in the operating position (closed), i.e. with markers in vertical position. See Figure 4-3. Gravity Brakes OPEN markers on valve handles at 45 angle To fill or completely empty the solar thermal installation, the gravity brakes must be opened, i.e. by turning the valve handles to the right to an angle of 45. See Figure 4-4. Flow and Return valves CLOSED markers on valve handles in HORIZONTAL position The flow and return valves are closed by turning the valve handles 90 to the right, i.e. until the V markers are horizontal. See Figure 4-5. Figure 4-3: Flow and return valves open Figure 4-4: Gravity breaks open 4.4 Solar Fluid In order to prevent frost and corrosion damage to solar collectors and pipework, the system must only be filled with a high quality solar fluid. The Grant solar fluid is a ready mixed 40% solution of 1,2 propylene glycol/water providing frost protection down to approx. -23 C. To prevent damage to the system the same specification solar fluid should be used when replacing or topping up the solar fluid in the system. If required, a copy of the Material Safety Data Sheet for the Grant solar fluid is available on request from Grant UK. Figure 4-5: Flow and return valves closed Commissioning 11

12 4 Commissioning Commissioning 4.5 Filling the System Grant Solar Thermal systems should be flushed and filled using a purpose designed closed circuit solar thermal filling station, incorporating a high pressure pump, such as the Grant Solar Filling Station. See Figure 4-6.! WARNING If the pump station is located in the roof space, there must be a suitable flat surface on which to stand the filling station, e.g. floor, loft boarding or similar, capable of carrying the weight of the filling station with a full tank of solar fluid. Figure 4-6: Grant Solar Filling Station 4.6 Filling Procedure IMPORTANT The collectors must be cool before filling the system. They must be covered, to stop solar radiation reaching them, until the filling and commissioning procedure is completed. Before filling the system: Check all system connections and the expansion vessel charge pressure. Refer to Table 4-1 (page 10). Phase 1 Connect the pressure hose from the filling station to the Filling Flow valve connection and open the valve. Refer to Figure 4-1 (page 10). Connect the return hose from the filling station to the Filling Return valve connection and open the valve. Refer to Figure 4-1 (page 10). Using a small spanner, rotate the Filling/Shut-off valve 90 clockwise. Refer to Figure 4-2 (page 10). This will divert the flow from the filling station through the pump, up to the collectors, through the coil of the cylinder and back to the filling station via the filling return valve. Fill the filling station tank with sufficient solar fluid for the system. Check that Flow and Return valves are set to 'half open' position (to open the gravity brakes) as shown in Figure 4-4 (page11). Switch on the filling station to fill and then flush the solar circuit for approx.15 minutes. Phase 2 Whilst the filling pump is running, close the Filling Return valve and allow the system pressure to reach around 4-5 bar. When the pressure reaches 5 bar, close the Filling Flow valve and immediately switch off the filling pump. Check that the system pipework and pump station are leak-free. After leaving the system at about 5 bar for a minimum of 15 minutes, check if the pressure gauge shows any significant drop in pressure. If it does, this points to a leak in the system that must be traced and rectified. Check the operation of pressure relief valve by slowly rotating the valve knob, lifting the valve, until fluid is discharged. This should be collected in a suitable container, e.g. a pressure relief valve fluid recovery container (as shown in Figure 3-3 on page 8). Phase 3 Re-open the Filling/Shut-off valve by turning 90 anti-clockwise. Switch on the circulating pump (by setting the solar controller to manual ) to the highest pumping speed and allow the solar fluid to circulate for at least 15 minutes. Set the solar controller to stand by (pump = OFF). Bleed the air separator using the manual air vent until the solar fluid begins to escape. Refer to section 4.7 (page 13). Set the operating pressure (as in Table 4-1) by carefully opening the Filling Return valve and releasing the fluid back into the filling station tank. Phase 4 Reset Flow and Return valves to fully open position. Refer to Figure 4-3 (page 11). Switch on the circulating pump (solar controller set to manual ). Set the flow rate on the flow rate indicator (refer to section 4.8) by selecting the appropriate pump speed and by using the Filling/Shutoff valve. Remove the filling station hoses from the filling connections and screw the caps on both valves. Release the Filling Return valve first and then the Filling Flow valve. Switch the solar controller to automatic operation and remove covers from the collectors. 12

13 4.7 Releasing Trapped Air The residual air from the heat transfer fluid is collected in the air separator and manually released via the air vent. There is no need to use an automatic air vent elsewhere on the solar primary circuit, e.g. at high level. To release any air collected in the air separator, push a plastic tube on to the manual air vent outlet and catch the fluid that is released in a suitable container. Open the manual air vent until all air has been vented, i.e. a steady stream of solar fluid is flowing from the air vent.! CAUTION Venting air from the system should only be carried out only by a competent installer. Frequent venting leads to system pressure loss and disruption to the system operation. 4.8 Setting the Flow Rate The setting of the solar fluid flow rate is made via the speed setting of the circulating pump and the Filling/Shut-off valve. For required system flow rates refer to Table 4-2. The flow indicator displays the fluid flow rate. The display range is between 1 and 13 litres per minute. See Figure 4-8. MADE IN ITALY Figure 4-7: Air separator and air vent Manual air vent Air separator! CAUTION Danger of scalding! The temperature of both the escaping air and the solar fluid can exceed 100 C.! NOTE For larger installations, please contact Grant Technical Department for assistance. Read flow rate from bottom edge of bobbin Figure 4-8: Flow rate indicator Number of solar panels Type of connection Flow and return pipe diameter Minimum volume flow rate Table 4-2: System volume flow rates 1 to Up to 5 in series 2 x 3 in parallel 2 x 4 in parallel 3 x 3 in parallel 4 x 3 in parallel 15mm 22mm 22mm 22mm 22mm 2-3 l/ min 4-5 l/ min 4-5 l/ min 6-8 l/ min 6-8 l/ min Commissioning 13

14 5 Fault Finding In the event of a problem occurring with your Grant Solar Thermal system, follow the information given below in order to identify and rectify the matter: 5.1 No System Circulation Check for the following: Pump is not operating (see 5.2 below). If pump is noisy, there may be air in the system. Pump may be air locked and needs venting. Turn off power, remove central screw on pump motor to vent. Valves are closed ensure that Flow, Return and Filling/Shut off valves are all fully open. Refer to Fig 4-3 on page Pump not Operating Check for the following: No electrical supply to pump. Controller is not calling for pump to operate (see below). Check power supply to controls (at fused spur). Check wiring to controller and pump is correct. Check for any loose connections. Controller is not calling for pump to operate. Check controller settings and correct as necessary (see Instructions supplied with the Solar Controller). Collectors may be in stagnation mode wait for system to cool down. Collector temperature may be too low (insufficient solar radiation). Cylinder temperature setting may be satisfied. Pump is stuck - Turn off power, remove central screw on pump motor and rotate motor using a screwdriver. Motor capacitor failed replace capacitor or pump motor. 5.3 Loss of System Pressure (on pressure gauge) Check for the following: Leaks on system find and rectify as necessary. Expansion vessel pre-charge lost check and re-charge vessel as necessary. Pressure relief valve discharging fluid check and rectify/replace valve. Fault Finding 14

15 6 Spare Parts psi bar OFF ON OFF ON /06 MADE IN ITALY Key No. Description Part No. 01 Flow valve assembly (Red) GSE01 02 Return valve assembly (Blue) GSE02 03 Safety valve assembly (6 bar) GSE03 04 Pressure gauge GSE04 05 Solar circulator (6 metre) GSE05 06 Solar circulator (8 metre) GSE06 07 Air separator assembly GSE07 08 Fill/flush valve and flow regulator assembly GSE08 Spare Parts 15

16 GRANT ENGINEERING (UK) LTD Hopton House, Hopton Industrial Estate, Devizes, Wiltshire. SN10 2EU Telephone: Fax: Website:

ADDENDUM to INSTALLATION INSTRUCTIONS for Grant Solar Pump Station

ADDENDUM to INSTALLATION INSTRUCTIONS for Grant Solar Pump Station ADDENDUM to INSTALLATION INSTRUCTIONS for Grant Solar Pump Station DOC.96-05/01 Rev01 - May 2015 ATTENTION INSTALLERS - UPDATED INFORMATION! There has been a recent change to the Grant Solar Thermal System

More information

Grant Vortex Mag One. Magnetic Central Heating Filter. Installation and Servicing Instructions

Grant Vortex Mag One. Magnetic Central Heating Filter. Installation and Servicing Instructions Grant Vortex Mag One Magnetic Central Heating Filter Installation and Servicing Instructions UK - DOC98 Rev 1.1 - October 2015 Contents 1 General 3 1.1 Introduction 3 1.2 How a Magnetic Filter Works 3

More information

Vertical Balanced Flue Kit All Internal Grant Boilers

Vertical Balanced Flue Kit All Internal Grant Boilers GENERAL Flue sections cannot be cut. Part No. DOC30 REV04 October 2008 SUPPLEMENTARY INSTALLATION INSTRUCTIONS Vertical Balanced Flue Kit All Internal Grant Boilers THIS SUPPLEMENT SHOULD BE READ IN CONJUNCTION

More information

Valves, controls + systems Valves and controls for solar installations Regusol-180

Valves, controls + systems Valves and controls for solar installations Regusol-180 The Oventrop Quality Management System is certified to DIN-EN-ISO 9001 Application: The Oventrop programme for solar installations allows the connection of the collector to the storage cylinder within

More information

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components 7EN www.caleffi.com Circulation units for solar thermal systems Copyright Caleffi 7HE - 79HE series INSTALLATION AND COMMISSIONING MANUAL CONTENTS Function Product range Technical specifications Characteristic

More information

OPERATION AND INSTALLATION

OPERATION AND INSTALLATION OPERATION AND INSTALLATION RESIDENTIAL SOLAR PUMP STATION» SE FLOWSTAR PUMP STATION Table of Contents 1 For your safety 1.1 About this manual 1.2 Designated use 1.3 Qualification of the installer 1.4 Hand-over

More information

CIRCO5SolarCirculationUnit

CIRCO5SolarCirculationUnit TECHNICAL INFORMATION / INSTALLATION MANUAL CIRCO5SolarCirculationUnit Wagner& Co CIRCO 5 Solar Circulation Unit the reliable pump station for efficient circulation of the heating fluid in combination

More information

Grant Vortex Mag One. Universal Magnetic Central Heating Filter. Installation and Servicing Instructions

Grant Vortex Mag One. Universal Magnetic Central Heating Filter. Installation and Servicing Instructions Grant Vortex Mag One Universal Magnetic Central Heating Filter Installation and Servicing Instructions UK DOC 0098 Rev 2.0 October 2017 Important Note for Installers These instructions are intended to

More information

ZonePlus Z322 zone valve Installation and commissioning instructions

ZonePlus Z322 zone valve Installation and commissioning instructions ZonePlus Z322 zone valve Installation and commissioning instructions The Z322 mid-position valve has been designed to control the water circulation in fully pumped systems, which employ a single pump for

More information

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS COMPONENTS FOR SOLAR THERMAL SYSTEMS 2012 2 The CALEFFI SOLAR product range has been specially developed for use in solar thermal systems, where high temperatures can normally be reached and where, depending

More information

RESOL SBS 1000 * * Connection Operation

RESOL SBS 1000 * * Connection Operation RESOL SBS 1000 Connection Operation FlowCon SBS 1000 A www.resol.de *48003820* 48003820 Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from this

More information

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications 28237 www.caleffi.com Circulation units for solar thermal systems Copyright 204 Caleffi 278-279 series INSTALLATION AND COMMISSIONING MANUAL CONTENTS Function Important Product range Technical specifications

More information

ECONOPLATE BV SERIES HOT WATER SERVICE PACKAGED HEAT EXCHANGERS WITH THERMAL STORES

ECONOPLATE BV SERIES HOT WATER SERVICE PACKAGED HEAT EXCHANGERS WITH THERMAL STORES ECONOPLATE BV SERIES HOT WATER SERVICE PACKAGED HEAT EXCHANGERS WITH THERMAL STORES TECHNICAL AND INSTALLATION DOCUMENTATION STOKVIS ENERGY SYSTEMS UNIT 34 CENTRAL PARK ESTATE 34 CENTRAL PARK ESTATE WEST

More information

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS COMPONENTS FOR SOLAR THERMAL SYSTEMS The Caleffi Solar product range has been specially developed for use in solar thermal systems, where high temperatures can normally be reached and where, depending

More information

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual SBS 2000 Filling and flushing station Manual for the specialised craftsman Connection Operation Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from

More information

Grant Grid-Connected Inverter For Grant Solar PV Systems. Installation & User Instructions

Grant Grid-Connected Inverter For Grant Solar PV Systems. Installation & User Instructions PROVISIONAL COPY Grant Grid-Connected Inverter For Grant Solar PV Systems Installation & User Instructions Doc. 92. Rev. 00 August 2010 Contents Contents 1 Introduction & General Requirements 3 1.1 Installation

More information

Installation instruction

Installation instruction 1 Safety Before installing the device, please read this manual carefully. Please note that the installation must be executed according to relevant technical rules. The installation must also be adapted

More information

VT Oil-Free Range Operators Handbook

VT Oil-Free Range Operators Handbook VT Oil-Free Range Operators Handbook Covering Models:- VT7 / VT7D VT10 / VT10D VT200 / VT200D VT300 / VT300D VT00 / VT00D BAMBI AIR COMPRESSORS LTD 12 Thimble Mill Lane Heartlands Birmingham B7 HT Tel:

More information

DCE 100 Series Dust Filter

DCE 100 Series Dust Filter Installation, Operation and Maintenance Manual DCE 100 Series Dust Filter Publication 2638B (GB) 0702 1419-8000A Donaldson Torit DCE reserve the right to alter design without notice. Freedom from patent

More information

VIESMANN. Installation instructions VITOSOL 200-T. for contractors. Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle

VIESMANN. Installation instructions VITOSOL 200-T. for contractors. Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle Installation instructions for contractors VIESMANN Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle VITOSOL 200-T 6/2010 Dispose after installation. Safety instructions Please

More information

Installation and Commissioning Instructions High Temperature Zone Module F31-1" (DN 25)

Installation and Commissioning Instructions High Temperature Zone Module F31-1 (DN 25) PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Tel.: +49-5151-9856-0, Fax: +49-5151-9856-98 Email: info@paw.eu, Web: www.paw.eu Installation and Commissioning Instructions High Temperature Zone

More information

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Compact System NRGS 11-2 NRGS Original Installation Instructions English Compact System NRGS 11-2 NRGS 16-2 EN English Original Installation Instructions 810366-05 1 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 LV (Low Voltage) Directive

More information

Installation & Technical Guide. Domestic & Commercial.

Installation & Technical Guide. Domestic & Commercial. Installation & Technical Guide Domestic & Commercial www.challisbooster.com www.challisboosterplus.com Installation and Technical Guide Domestic and Commercial Challis Water Controls Europower House, Lower

More information

CALEFFI. Solar pump stations 01166/14 NA. 278 and 279 series 01264/16 NA

CALEFFI. Solar pump stations 01166/14 NA. 278 and 279 series 01264/16 NA Solar pump stations 78 and 79 series 0/4 N CLEFFI 04/ N CCREDITED ISO 900 FM 4 ISO 900 No. 000 Function Solar pump stations are used on the primary circuit of solar thermal water heating systems to control

More information

VIESMANN. Installation instructions VITOSOL-F. for contractors

VIESMANN. Installation instructions VITOSOL-F. for contractors Installation instructions for contractors VIESMANN Vitosol-F Type SV and SH Flat-plate collector for installation on supports and wall mounting VITOSOL-F 9/2010 Dispose after installation. Safety instructions

More information

Duo water control system

Duo water control system Duo water control system Installation and maintenance guide DUOINSTRUCT Contents Important and safety information Pack contents / Tools required Duo trim plate dimensions Flow performance Typical wall

More information

Installation Instructions. Vitosol 100. Vitosol 100 Type w 2.5 Flat collector for flat roofs and freestanding installation Part No.

Installation Instructions. Vitosol 100. Vitosol 100 Type w 2.5 Flat collector for flat roofs and freestanding installation Part No. Installation Instructions Vitosol 100 Type w 2.5 Flat collector for flat roofs and freestanding installation Part No. 3001 970 Vitosol 100 8/99 Safety instructions This hazard symbol precedes all important

More information

Product and installation manual. Underfloor Heating Composite Manifold

Product and installation manual. Underfloor Heating Composite Manifold Product and installation manual Composite Manifold Contents Introduction 2 Manifold Overview 3 Manifold Design 3 Manifold Dimensions 3 Manifold Installation 4-9 Pack Requirements 4 Required Tools 4 General

More information

KS Pump Stations. Engineering Submittal Sheet. Installation Sets for Collectors

KS Pump Stations. Engineering Submittal Sheet. Installation Sets for Collectors Engineering Submittal Sheet Installation Sets for Collectors Layout legend S Supply from collector to storage R Return from storage to collector 1 Ball valve with thermometer and integrated gravity break

More information

Operating & Maintenance Manual Compact Domestic Booster Set Model BTAF Arrow Valves

Operating & Maintenance Manual Compact Domestic Booster Set Model BTAF Arrow Valves Arrow Valves Ltd Tel 01442 823123 Fax 01442 823234 Installation Instructions/ Operating & Maintenance Manual Pent-A-Boost Compact Domestic Booster Set Models BTAF 700 900 1200 230-240 V Single Phase &

More information

PRESSURE CONTROL VALVES SABS 198

PRESSURE CONTROL VALVES SABS 198 PRESSURE CONTROL VALVES SABS 198 1 CALVALVE DOUBLE BLOCK Pressure control combined pressure reducing valve and expansion relief valve, copper by copper compression ends. DZR alloy body. Replaceable cartridge

More information

M Series Condensate Recovery Unit

M Series Condensate Recovery Unit 0898050/3 IM-P089-29 ST Issue 3 M Series Condensate Recovery Unit Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Wiring diagram

More information

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009 HOT WASHER MODEL NO: KING 125 PART NO: 7320170 OPERATION & MAINTENANCE INSTRUCTIONS LS1009 INTRODUCTION Thank you for purchasing this Hot Washer. This machine is a portable, high pressure power washer,

More information

HR25 Solo. Installation and User Instructions. Through the Wall Heat Recovery Ventilators

HR25 Solo. Installation and User Instructions. Through the Wall Heat Recovery Ventilators abc GB HR25 Solo Installation and User Instructions Models:- HR25 Solo HR25 Solo L HR25 Solo H HR25 Solo LH Through the Wall Heat Recovery Ventilators PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

More information

Operating & Maintenance Manual Break Tank & Pump Set Model BTAB Arrow Valves

Operating & Maintenance Manual Break Tank & Pump Set Model BTAB Arrow Valves Arrow Valves Ltd Tel 01442 823123 Fax 01442 823234 info@arrowvalves.co.uk www.arrowvalves.co.uk Installation Instructions/ Operating & Maintenance Manual Boost-A-Break, Break Tank & Pump Sets - Models

More information

Mini Twinline Sequential Shower Valves

Mini Twinline Sequential Shower Valves Guarantee and Registration Guarantee All products are manufactured to the highest standards and 5-year guarantee covers any defect in manufacture. Any part found to be defective during the above guarantee

More information

Navigator ADS551 Low level dissolved oxygen Replacement / Upgrade procedures wet section spares

Navigator ADS551 Low level dissolved oxygen Replacement / Upgrade procedures wet section spares Instruction replacement procedure INS/ANAINST/025 EN Rev. A Navigator ADS551 Low level dissolved oxygen Replacement / Upgrade procedures wet section spares Kit references: flowcell, tundish, flowmeter,

More information

LK Manifold Shunt VS2

LK Manifold Shunt VS2 LK Manifold Shunt VS2 Design LK Manifold Shunt VS2 is a shunt unit with a two way control valve used in systems with a primary pump. The shunt unit is mountable from both the left and right of LK Manifolds.

More information

POND PUMP Model Nos:SPP3 & SPP6 0200

POND PUMP Model Nos:SPP3 & SPP6 0200 OPERATING & MAINTENANCE INSTRUCTIONS POND PUMP Model Nos:SPP3 & SPP6 0200 Thank you for purchasing this CLARKE Water Pump, which is particularly suitable for the filtration of small to medium size swimming

More information

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions 4034450/9 IM-P403-15 AB Issue 9 BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions 1. Safety information 2. Application 3. Technical data 4. Operation 5. Installation 6. Rotating

More information

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c. 24V DC-CW332 DOC531/11 Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c. To obtain the best performance from your Pressurised water

More information

Breezair TBA 550 Installation Manual

Breezair TBA 550 Installation Manual Breezair TBA 550 Installation Manual Table of Contents ITEM Safety Instructions Specifications Exploded View of the Air Cooler Components of the Air Cooler Dismantling the Air Cooler Installing the Transition

More information

Acura TMV3 Bath Filler AC50010CP and AC50020CP

Acura TMV3 Bath Filler AC50010CP and AC50020CP Acura TMV3 Bath Filler AC50010CP and AC50020CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

SUBMERSIBLE WATER PUMP

SUBMERSIBLE WATER PUMP SUBMERSIBLE WATER PUMP MODEL NO: CSV1A, CSV2A PART NO: 7230582, 7230602 OPERATION & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS 05/14 iss 4 INTRODUCTION Thank you for purchasing this CLARKE Submersible

More information

40 geothermal ground loop manifolds

40 geothermal ground loop manifolds 40 geothermal ground loop manifolds GeoCal (key features listed left) This is the first thermoplastic, fully modular manifold system designed specifically for installations using ground source heat pumps.

More information

Solar Thermal Energy Flat & Tube Panel Standard Kits Installation Overview

Solar Thermal Energy Flat & Tube Panel Standard Kits Installation Overview Solar Thermal Energy Flat & Tube Panel Standard Kits Installation Overview Viessmann As a world leader in heating technology, Viessmann has 30 years experience in renewable energy systems and there are

More information

Clos-o-Mat Lima Lifter installation & user guide

Clos-o-Mat Lima Lifter installation & user guide Clos-o-Mat Lima Lifter installation & user guide design manufacture supply install service recycle Technical data General specifications 1 Technical data 1.1 General specifications 2 Technical data Operating

More information

APRICUS PUMP STATION TECHNICAL GUIDE

APRICUS PUMP STATION TECHNICAL GUIDE APRICUS PUMP STATION TECHNICAL GUIDE A technical reference for the Apricus Pump Station for installers Version 1.1 The customer agrees to and accepts all related charges incurred as a result of a warranty

More information

Taps, Valves & Components. Section 1

Taps, Valves & Components. Section 1 Taps, Valves & Components Section 1 taps, valves & components index Index 1 SECTION PAGE sink taps 1.1-1.4 sink taps & spares 1.5 basin taps 1.6 general purpose taps & valves 1.7 flexible connectors, angle

More information

Installation, Operation & Maintenance Instructions for MF-Solar Series Solution Feeders

Installation, Operation & Maintenance Instructions for MF-Solar Series Solution Feeders INDUSTRIES LIMITED Installation, Operation & Maintenance Instructions for MF-Solar Series Solution Feeders Startup Procedure 1) Close isolation valve between feeder and system connection point 2) Fill

More information

Underfloor heating & cooling solutions by Wavin

Underfloor heating & cooling solutions by Wavin February 2010 UF428 Underfloor heating & cooling solutions by Wavin Composite Manifold Installation Guide FOR RESIDENTIAL AND LIGHT COMMERCIAL APPLICATIONS Usability, Versatility and Reliability Composite

More information

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00 INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR469100 BR25AT REV00 I CONTENT: 1 SAFETY 1.1 Safety instructions 1 1.2 Specified applications 1 1.3 Safety notes on the equipment operation 1 2 BR 25

More information

Installation, Operating, Maintenance and Safety Instructions JABSCO & Series 1 40 SIZE UTILITY Pump

Installation, Operating, Maintenance and Safety Instructions JABSCO & Series 1 40 SIZE UTILITY Pump Installation, Operating, Maintenance and Safety Instructions JABSCO 53040 & 5304-Series 40 SIZE UTILITY Pump TO OBTAIN THE BEST PERFORMANCE FROM YOUR JABSCO PUMP PLEASE READ THESE INSTRUCTIONS CAREFULLY

More information

INSTALLATION INSTRUCTIONS SERVICE KIT - MONSOON EXTRA S1.4 bar SINGLE Part No MONSOON EXTRA U1.4 bar SINGLE Part No.

INSTALLATION INSTRUCTIONS SERVICE KIT - MONSOON EXTRA S1.4 bar SINGLE Part No MONSOON EXTRA U1.4 bar SINGLE Part No. ISTALLATIO ISTRUCTIOS SERVICE KIT - MOSOO EXTRA S1.4 bar SIGLE Part o. 28454 - MOSOO EXTRA U1.4 bar SIGLE Part o. 28455 23 Capacitor (not shown) All Models - see Sections 1 & 5 25 Adhesive foam pad (not

More information

Part No: Genuine Mira Accessories

Part No: Genuine Mira Accessories Bar Valve Fixing Kit Part No: 1663.017 Genuine Mira Accessories 1 Introduction Please take time to read this guide thoroughly, having done so, keep it handy for future reference. This Fixing Kit has been

More information

(UK) Date : January 2014

(UK)   Date : January 2014 Sentinel Door Curtain - Model 270 Installation, Operation & Maintenance Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD Tel. 023 9247 7700 Fax. 023 9245 3601 (Global) www.dunham-bush.com Document

More information

The Mikrofill Electronic Filling Device. (EFD)

The Mikrofill Electronic Filling Device. (EFD) The Mikrofill Electronic Filling Device. (EFD) The Mikrofill EFD is a fully automatic sealed system filling device, and is suitable for the water management in all domestic and commercial heating and cooling

More information

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk Black Teknigas Powerseat Eco Gas Safety Shut-Off Valve Technical, and Maintenance Details WattsIndustries.co.uk Safety shut off valves for gas, air and oil EN161 approved; EC certificated Robust construction

More information

FOR HEATING & PLUMBING SYSTEMS

FOR HEATING & PLUMBING SYSTEMS Quality Plastics Ltd. Pushfit Option Compression Option MANIFOLD SYSTEM ADVANTAGES: Central Control. Eliminates variations in pressure and flow. Individual pipes to each outlet allowing separate shut-off

More information

The Powermatic User Guide Test Sieve Shaker

The Powermatic User Guide Test Sieve Shaker The Powermatic User Guide Test Sieve Shaker ISSUE 04-02 Contents Description Page 1 Setting Up: 2-8 Unpacking 2 Assembly 3-4 Levelling 4 Electrical Connections 5 Sieve Stacking 6-8 Operating Instructions

More information

Hot and Cold Plumbing Manifold Systems

Hot and Cold Plumbing Manifold Systems Hot and Cold Plumbing Manifold Systems Hot and Cold Manifold Overview By using an Emmeti manifold system in a point to point plumbing configuration you can greatly reduce the number of joints in your system,

More information

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB Distribution manifold for radiant panel systems 664 series FM 21654 003 CALEFFI 01260/18 GB replaces 01260/14 GB Function The distribution manifold for radiant panel systems is used to optimally distribute

More information

Level Electrode NRG NRG NRG NRG

Level Electrode NRG NRG NRG NRG Level Electrode NRG 16-11 NRG 17-11 NRG 19-11 NRG 111-11 EN English Original Installation Instructions 818578-05 1 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4

More information

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors Type range: UN813.3ANI UN813.4ANI UN813.3ANDCB UN813.4ANDCB UN813.5ANI Fig. 1: UN813.3ANI Fig. 2: UN813.4ANI You have selected

More information

JABSCO & Series 1½ 80 SIZE UTILITY Pump

JABSCO & Series 1½ 80 SIZE UTILITY Pump DOC271/98/01 Installation, Operating, Maintenance & Safety Instructions for JABSCO 53080 & 53081-Series 1½ 80 SIZE UTILITY Pump TO OBTAIN THE BEST PERFORMANCE FROM YOUR JABSCO PUMP PLEASE READ THESE INSTRUCTIONS

More information

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1 Model 340i / 680i / 1220i DC drive product manual HG102938 iss 8 1 Sprint Electric Limited, Arundel, UK Tel. +44 (0)1903 730000 Fax. +44 (0)1903 730893 Email. info@sprint-electric.com www.sprint-electric.com

More information

VIESMANN. Installation instructions VITOSOL 200. for heating engineers. Vitosol 200 Type SD2 Direct flow vacuum tube collector

VIESMANN. Installation instructions VITOSOL 200. for heating engineers. Vitosol 200 Type SD2 Direct flow vacuum tube collector Installation instructions for heating engineers VIESMANN Vitosol 200 Type SD2 Direct flow vacuum tube collector VITOSOL 200 5/2005 Dispose after installation. Safety instructions Please follow these safety

More information

SUBMERSIBLE WATER PUMPS

SUBMERSIBLE WATER PUMPS SUBMERSIBLE WATER PUMPS Model Nos. CS85S - CS85SA CS120S - CS120SA CS185S - CS185SA CS240S - CS240SA CS305S - CS305SA OPERATING & MAINTENANCE INSTRUCTIONS 1000 CONTENTS Warranty conditions... 3 Safety

More information

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3 EN Operating manual Motorised zone valve Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3 This manual ensures safe and efficient use of the 3PV2 or 3PV8 force-actuated three-way valve with spring-loaded return

More information

APT10-2 Automatic Pump Trap

APT10-2 Automatic Pump Trap 6120050/3 IM-P612-18 ST Issue 3 APT10-2 Automatic Pump Trap Installation and Maintenance Instructions 1. General safety information 2. Product information 3. Installation Closed loop steam systems only

More information

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

DS Series Solar System

DS Series Solar System DS Series Solar System Permit information Consol 30-58-1800 Collector Flat mount on Colorsteel Plumdeck roofing Valve vent, Open loop http:// www.consolsolar.co.nz 21 Page 1 of This system is an evacuated

More information

THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions

THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions Please retain for future reference DUAL INLINE CONCEALED VALVE SV2204 / SV4404 / SV5504 / SV6604 SV7704 / SV8804 / SV9904

More information

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies D1541 D1542 D1543 D1545 D1543-X-8 D1545-X-8 D1545-4BNC D154X Series 1A 2A 3A 5A 3A fitted with 8-way output splitter

More information

1901 Thermostatic Shower Mixer

1901 Thermostatic Shower Mixer 1901 Thermostatic Shower Mixer (Universal Valve with Adjustable Riser, Surface Mounted Valve with Rigid Riser or Recessed Valve with Fixed Head) Fitting Instructions & Contents List Before starting any

More information

Installation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP /055/100

Installation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP /055/100 Installation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP-53-030/055/100 Rev. 1 3/21/11 K.G. Type - John Wood #JWOP-53-030/055/100, Outdoor Glycol Feed System Capacity 30/55/100 Gallons

More information

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB Distribution manifold for radiant panel systems 664 series ACCREDITED CALEFFI 01260/14 GB ISO 9001 FM 21654 ISO 9001 No. 0003 Function The distribution manifold for radiant panel systems is used to optimally

More information

Your Guide to the Installation, Care and maintenance of PERFORMA. Electronic Self Closing Fittings - Mains Powered 886V (343029) 885V (343027)

Your Guide to the Installation, Care and maintenance of PERFORMA. Electronic Self Closing Fittings - Mains Powered 886V (343029) 885V (343027) Your Guide to the Installation, Care and maintenance of PERFORMA Electronic Self Closing Fittings - Mains Powered 886V (343029) 885V (343027) Pegler Limited, St Catherine s Avenue, Doncaster DN4 8DF Telephone

More information

SOLAR AEROLINE. fast simple reliable. The perfect connection technology for solar hot water

SOLAR AEROLINE. fast simple reliable. The perfect connection technology for solar hot water SOLAR The perfect connection technology for solar hot water Pipe systems for solar, heating, heat pumps and air-conditioning technology fast simple reliable Assembly options Applications: On-roof, in-roof

More information

MOBILE PRODUCT RECOVERY TANK

MOBILE PRODUCT RECOVERY TANK FUELLING COMPONENTS LIMITED > MOBILE PRODUCT RECOVERY TANK STAINLESS STEEL CONSTRUCTION FULLY MOBILE STABLE AND MANOEUVRABLE ZERO FUEL WASTE FAST PAYBACK 150 LITRE OR 400 LITRE CAPACITY WIDE RANGE OF OUTLET

More information

Axiom Industries Ltd Wentz Avenue Saskatoon, SK S7K 5J1 Ph: (306) Fax: (306)

Axiom Industries Ltd Wentz Avenue Saskatoon, SK S7K 5J1 Ph: (306) Fax: (306) INDUSTRIES LIMITED Installation, Operation & Maintenance Instructions for MF Series Solution Feeders Axiom Industries Ltd. 2615 Wentz Avenue Saskatoon, SK S7K 5J1 Ph: (306) 651-1815 Fax: (306) 242-3373

More information

Endura AZ10 Oxygen probe Sensor sub-assembly tested spares kit

Endura AZ10 Oxygen probe Sensor sub-assembly tested spares kit Information INF15/166 EN Endura AZ10 Oxygen probe Sensor sub-assembly tested spares kit Measurement made easy 1 Introduction This publication details how to replace the sensor sub-assembly on an AZ10 oxygen

More information

DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL

DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL LILLY ENGINEERING COMPANY 217 CATALPA STREET P.O. BOX 173 ITASCA, ILLINOIS 60143 630-773-2222 FAX: 630-773-3443 www.lillyengineering.com

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Section 3. Technical Information 3.1 Electrical Wiring Details 3.2 Commissioning Data 3.3 Fuel 3.4 Wiring Diagrams 3.5 Technical Information 3.6 Burner Specification Summaries 3.7

More information

Engineering Standard. Fig 707 Safety Relief Valve Installation and Maintenance Instructions

Engineering Standard. Fig 707 Safety Relief Valve Installation and Maintenance Instructions ES/707/0/003 ES/707/0/003 June 2007 Engineering Standard Fig 707 Safety Relief Valve Installation and Maintenance Instructions Sharp Street, Worsley, Manchester M28 3NA: Tel +44 (0) 161 790 7741 Fax +44

More information

The LOK Range. Models:

The LOK Range. Models: The LOK Range Packaged Plate Heat Exchangers for Domestic Hot Water Production Installation, Commissioning and Maintenance Instructions Models: LOK8-50/LOKT8-50 LOK8-100/ LOKT8-100 LOK8-150/ LOKT8-150

More information

Guidance to Installers of Viridian EV Charging Stations

Guidance to Installers of Viridian EV Charging Stations Guidance to Installers of Viridian EV Charging Stations Iss 6 - Jul 2016 Page 2 of 9 This guide is intended to instruct in the proper installation of a Viridian EV Charging Station. Please note that when

More information

HERZ 7217 V. Integral Fixed Orifice Control Valve HERZ 7217 V. Data sheet 7217 V, Issue Size in mm. STRÖMAX Fig No DN L Lm Rp H SW kv kvs

HERZ 7217 V. Integral Fixed Orifice Control Valve HERZ 7217 V. Data sheet 7217 V, Issue Size in mm. STRÖMAX Fig No DN L Lm Rp H SW kv kvs HERZ 7217 V Integral Fixed Orifice Control Valve Data sheet 7217 V, Issue 1011 Size in mm STRÖMAX Fig No DN L Lm Rp H SW kv kvs TS-V LF 1 7217 50 15 83 28,5 1/2 41 27 0,07-0,45 0,48 TS-V MF 1 7217 59 15

More information

BATH FILLER & BATH / SHOWER MIXER Installation & aftercare instructions

BATH FILLER & BATH / SHOWER MIXER Installation & aftercare instructions GENERAL NOTES This mixer should be installed in accordance with water regulations. Approved check valves should be fitted where required. For further details please contact your local water authority.

More information

original operating manual Operating manual Translation of the Item-No.: ,

original operating manual Operating manual Translation of the Item-No.: , Translation of the original operating manual Operating manual Item-No.: 015 431 551, 015 431 581 Important! Copyright The operating manual is always to be read before commissioning the equipment. No warranty

More information

THERMOSTATIC CONCENTRIC DUAL CONTROL SHOWER VALVES Installation & aftercare instructions

THERMOSTATIC CONCENTRIC DUAL CONTROL SHOWER VALVES Installation & aftercare instructions THERMOSTATIC CONCENTRIC DUAL CONTROL SHOWER VALVES Installation & aftercare instructions Please retain for future reference EXPOSED CONCENTRIC VALVE SV2201 / SV4401 / SV5501 / SV6601 SV7701 / SV8801 /

More information

Instruction Manual. Sewage lifting station compli 300

Instruction Manual. Sewage lifting station compli 300 Instruction Manual Sewage lifting station compli 300 Safety instructions Areas of application Electrical connection Installation Servicing Technical data Appendix JUNG PUMPEN GmbH Industriestr. 4-6 33803

More information

MSC Manifolds - DIN for Steam Distribution and Condensate Collection Installation and Maintenance Instructions

MSC Manifolds - DIN for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1170650/3 IM-P117-17 ST Issue 3 MSC Manifolds - DIN for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1 General safety information 2 General product information

More information

Infrared Control Valve Installation Guide

Infrared Control Valve Installation Guide Infrared Control Valve Installation Guide Supplied Parts 1. Sensor Unit 2. Solenoid Valve 3. Mounting Bracket (for cavity walls or ceiling tiles) 4. Remote Valve Plug & Gasket 5. Mounting Screws M3.5 x

More information

Infrared Control Valve Installation Guide

Infrared Control Valve Installation Guide Infrared Control Valve Installation Guide Supplied Parts 1 1. Sensor Unit 2. Solenoid Valve 3. Mounting Bracket (for cavity walls or ceiling tiles) 2 4. Remote Valve Plug & Gasket 5. Mounting Screws M3.5

More information

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h) Ball shut-off valve fitted for integrated flow rate measuring sensor series ACCREDITED CALEFFI 034/3 GB ISO 900 FM 654 ISO 900 No. 0003 Function The valve allows to shut the circuit off and is fitted for

More information

SE RV I CE MANUAL. Page 1 of 13

SE RV I CE MANUAL. Page 1 of 13 SE RV I CE MANUAL Technical Data Mechanical Repair Electrical Repairs Calibration Fault Diagnosis Tools and Test Equipment Parts List Page 1 of 13 Technical Data Continuous operation, with intermittent

More information

REX/REX F/REX K/REX K F REX DUAL/REX DUAL F

REX/REX F/REX K/REX K F REX DUAL/REX DUAL F TECHNICAL MANUAL REX/REX F/REX K/REX K F REX DUAL/REX DUAL F PRESSURISED STEEL BOILERS INDEX 1 GENERAL WARNINGS... 4 2 TECHNICAL SPECIFICATIONS... 5 2.1 REX/REX K/REX F/REX K F 7-130 BOILER... 5 2.2 REX/REX

More information

Pump Stations for Heating Circuits

Pump Stations for Heating Circuits Pump Stations for Heating Circuits circulation pumps pump stations manifolds Regulus spol. s r.o., Czech Republic Do Koutů 897/, Praha Tel.: + 7 9, Fax: + 7 97 E-mail: sales@regulus.eu Web: www.regulus.eu

More information

SRG LPG Liquid Service/Offtake Valve Type /

SRG LPG Liquid Service/Offtake Valve Type / SRG LPG Liquid Service/Offtake Valve Type 480-426 / 480-427 Inlet Connection Outlet Connection Width across flats ¾ NPT 1 ¼ NPT M26x1,814 36 mm 46 mm Product Description: The SRG type 480 liquid service

More information