1 Solenoid valves EVR 2 40 NC/ NO REFRIGERATION AND AIR CONDITIONING Technical leaflet

2 2 DKRCCPDBB0A H275 Danfoss A/S,

3 Contents Page Introduction Features Approvals Technical data Ordering Liquid capacity Q o kw, R22/ R4a/R404A/R Liquid capacity Q o kw, R407C Suction vapour capacity Q o kw, R Suction vapour capacity Q o kw, R4a/R404A/R Suction vapour capacity Q o kw, R407C Hot gas capacity Q h kw, R Hot gas capacity Q h kw, R4a Hot gas capacity Q h kw, R404A/R Hot gas capacity Q h kw, R407C Hot gas capacity G h kg/s, R22/R4a Hot gas capacity G h kg/s, R404A/R507/R407C Design/ Function Material specification Dimensions and weight, EVR (NC) 2 5 and -> 5 (NO) with fl are connection Dimensions and weight, EVR (NC) 2 22 and -> 22 (NO) with solder connection Dimensions and weight, EVR (NC) 25, 2 og 40 with solder connection Danfoss A/S, DKRCCPDBB0A H275

4 Introduction EVR is a direct or servo operated solenoid valve for liquid, suction, and hot gas lines with fluorinated refrigerants. EVR valves are supplied complete or as separate components, i.e. valve body, coil and flanges, if required, can be ordered separately. Features Approvals Technical data Complete range of solenoid valves for refrigeration, freezing and air conditioning plant Supplied both normally closed (NC) and normally open (NO) with de-energized coil Wide choice of coils for a.c. and d.c. Suitable for all fluorinated refrigerants Designed for media temperatures up to 05 C DnV, Det norske Veritas, Norge Pressure Equipment Directive (PED) 97/2/EC The Low Voltage Directive (LVD) 7/2/EC with amendments EN Refrigerants CFC, HCFC, HFC Temperature of medium C with 0 W or 2 W coil. Max. 0 C during defrosting. MOPD up to 25 bar with 2 W coil Flare connections up to 5/8 in. Solder connections up to 2 /8 in. Extended ends for soldering make installation easy It is not necessary to dismantle the valve when soldering in. EVR are also available with flange connections Polski Rejestr Statków, Polen MRS, Maritime Register of Shipping, Russia Versions with UL approval can be supplied to order. Ambient temperature and enclosure for coil See "Coils for solenoid valves", RD.J.E DKRCCPDBB0A H275 Danfoss A/S,

5 Technical data (continued) Opening differential pressure with standard coil Δp bar Max. (= MOPD) liquid 2 ) Temperature of medium Max. working pressure PB k v value ) Min. 0 W a. c. 2 W a. c. 20 W d. c. C bar m /h EVR EVR NO EVR EVR 0 NO EVR EVR 5 NO (a.c.) (d.c.) NO EVR EVR 22 NO ) ) ) ) The k v value is the water flow in m /h at a pressure drop across valve of bar, ρ = 000 kg/m. 2 ) MOPD for media in gas form is approx. bar greater. ) Min. diff. pressure 0.07 bar is needed to stay open. Rated capacity kw Liquid Suction vapour Hot gas R22 R4a R404A/R507 R407C R22 R4a R404A/R 507 R407C R22 R4a R404A/R507 R407C EVR EVR EVR EVR EVR Rated liquid and suction vapour capacity is based on evaporating temperature t e = -0 C, liquid temperature ahead of valve t l = C, pressure drop in valve Δp = 5 bar. Rated hot gas capacity is based on condensing temperature t c = +40 C, pressure drop across valve Δp = bar, hot gas temperature t h = +65 C, and subcooling of refrigerant Δt sub = 4 K. Danfoss A/S, DKRCCPDBB0A H275 5

6 Ordering Complete valves Normally closed (NC) with a.c. coil ) Code no. Connection Valve body + 0 W a. c. coil with m cable Flare 2 ) Solder ODF in. mm in./mm in. mm EVR / F809 02F F2052 / F807 02F F2092 EVR 0 / F809 02F222 02F22 EVR 5 5 / F802 02F292 02F292 Code no. Connection Valve body + 0 W a. c. coil with terminal box Flare 2 ) Solder ODF in. mm in./mm in. mm EVR / F80 02F204 02F205 / F F208 02F209 EVR 0 / F F22 02F2 EVR 5 5 / F80 02F29 02F29 7 / F224 02F224 ) Please specify code no., voltage and frequency. Voltage and frequency can also be given in the form of an appendix number, see table "Appendix numbers". 2 ) Supplied without flare nuts. Separate flare nuts: / 4 in. or 6 mm, code no. 0L0 / 8 in. or 0 mm, code no. 0L5 / 2 in. or 2 mm, code no. 0L0 5 / 8 in. or 6 mm, code no. 0L67 ) Can only be used with DIN plug Appendix numbers Voltage V Frequency Hz /60 50/60 Energy consumpt. W Appendix no DKRCCPDBB0A H275 Danfoss A/S,

7 Ordering (conmtinued) Components Flare and solder connections Separate valve bodies, normally closed (NC) Required coil type Connection Flare ) in. mm in./mm in. mm EVR 2 a.c. / F F20 02F202 EVR EVR 0 EVR 5 a.c./d.c. / F807 02F206 02F207 / F86 02F204 02F208 / F F22 02F2 / F F209 02F26 / F F27 02F28 5 / F F24 02F24 5 / F80 02F228 02F228 Code no. Valve body without coil Solder ODF With manual With manual operation 5 / F800 2 ) 02F227 7 / F225 02F225 7 / F240 02F240 a.c. 7 / F254 / F244 02F245 7 / F264 02F264 d.c. 7 / F274 EVR 22 a.c. / F267 02F267 a.c./d.c. Without manual operation / 8 02F F F F2206 / F F2208 / H05 042H06 5 / 8 042H0 042H H07 042H08 5 / 8 042H09 042H H 042H4 2 / H 042H2 Separate valve bodies, normally open (NO) ) Code no. Required Connection Valve body without coil ) coil type Flare ) Solder ODF in. mm in. mm in. mm / F F F290 02F295 EVR 0 / F809 02F809 02F29 02F296 5 / F F F299 02F299 EVR 5 a.c./d.c. 7 / F270 02F270 7 / F260 02F260 / F269 02F279 EVR 22 a.c. / F268 02F268 ) Valve bodies are supplied without flare nuts. Separate flare nuts: / 4 in. or 6 mm, code no. 0L0 / 8 in. or 0 mm, code no. 0L5 / 2 in. or 2 mm, code no. 0L0 5 / 8 in. or 6 mm, code no. 0L67 2 ) With manual operation. ) The normal range of coils can be used for the NO valves, with the exception of the double frequency versions of 0 V, 50/60 Hz and 220 V, 50/60 Hz. Coils See "Coils for solenoid valves", RD.J.E2.02. Danfoss A/S, DKRCCPDBB0A H275 7

8 Ordering (continued) Components Flare and solder connections Separate valve bodies, normally closed (NC) EVR 5 Require coil type Connection Code no. Valve body + gaskets +bolts; without coil and flanges Without manual operation Without manual operation a.c./d.c. 02F24 02F224 a.c. Flanges 02F25 02F24 d.c. 02F27 02F26 Coils See "Coils for solenoid valves", RD.J.E2.02. Flange sets Valve type EVR 5 Connection Code no. Solder Weid in. mm in. mm in. / 2 027N5 5 / L7 027L6 / 4 027N20 7 / L2 027L22 / 4 027N220 7 / L22 027L N225 / L L228 Example EVR 5 without manual operation, code no. 02F224 + /2 in. weld flange set, code no. 027N5 + coil with termfnal box, 220 V, 50 Hz, code no. 08F670 (See "Coils for solenoid valves", RD.J.E2.02.). Accessories Description Mounting bracket for EVR 2,, 6 and 0 Strainer FA for direct mounting Code no. 02F097 See "FA" 8 DKRCCPDBB0A H275 Danfoss A/S,

9 Capacity Liquid capacity Q e kw Liquid capacity Q e kw at pressure drop across valve Δp bar EVR EVR EVR EVR EVR R22 Liquid capacity Q e kw Capacities are based on liquid temperature t l = C ahead of valve, evaporating temperature t e = 0 C, superheat 0 K. Correction factors When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid temperature t l ahead of valve/evaporator. When the corrected capacity is known, the selection can be made from the table. R4a Liquid capacity Q e kw at pressure drop across valve Δp bar EVR EVR EVR EVR EVR Liquid capacity Q e kw R404A/R507 Liquid capacity Q e kw at pressure drop across valve Δp bar EVR EVR EVR EVR EVR Correction factors for liquid temperature t l t l C R R4a R404A/R Danfoss A/S, DKRCCPDBB0A H275 9

10 Capacity (continued) Liquid capacity Q e kw R407C Liquid capacity Q e kw at pressure drop across valve Δp bar EVR EVR EVR EVR EVR Capacities are based on liquid temperature t l = C ahead of valve, evaporating temperature t e = 0 C, and superheat 0 K. Correction factors When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid temperature t l ahead of valve/evaporator. When the corrected capacity is known, the selection can be made from the table. Correction factors based on liquid temperature t l t l C R407C Capacities are based on liquid temperature t l = C ahead of evaporator. The table values refer to the evaporator capacity and are given as a function of evaporating temperature t e and pressure drop Δp across valve. Capacities are based on dry, saturated vapour ahead of valve. During operation with superheated vapour ahead of valve, the capacities are reduced by 4% for each 0 K superheat. Suction vapour capacity Q e EVR 0 EVR 5 EVR 22 Pressure drop Δp bar Suction vapour capacity Q e kw at evaporating temperature t e C R Correction factors When sizing valves, the evaporator capacity must be divided by a correction factor depending on liquid temperature t l ahead of expansion valve. When the corrected capacity is known, the selection can be made from the table. Correction factors for liquid temperature t l t l C R DKRCCPDBB0A H275 Danfoss A/S,

11 Capacity (continued) Capacities are based on liquid temperature t l = C ahead of evaporator. The table values refer to the evaporator capacity and are given as a function of evaporating temperature t e and pressure drop Δp across valve. Capacities are based on dry, saturated vapour ahead of valve. During operation with superheated vapour ahead of valve, the capacities are reduced by 4% for each 0 K superheat. Suction vapour capacity Q e EVR 0 EVR 5 EVR 22 Suction vapour capacity Q e kw EVR 0 EVR 5 EVR 22 Pressure drop across valve Δp bar Pressure drop across valve Δp bar R404A/R507 Suction vapour capacity Q e kw at evaporating temperature t e C R4a Suction vapour capacity Q e kw at evaporating temperature t e C Correction factors When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid temperature t l ahead of valve/evaporator. When the corrected capacity is known, the selection can be made from the table. Correction factors based on liquid temperature t l t l C R4a R404A/R Danfoss A/S, DKRCCPDBB0A H275

12 Capacity (continued) Pressure drop across valve Δp bar R407C Suction vapour capacity Q e kw at evaporating temperature t e C EVR EVR Capacities are based on liquid temperature t l = C ahead of evaporator. The table values refer to the evaporator capacity and are given as a function of evaporating temperature t e and pressure drop Δp across valve. Capacities are based on dry, saturated vapour ahead of valve. During operation with superheated vapour ahead of valve, the capacities are reduced by 4% for each 0 K superheat. EVR Correction factors When sizing valves, the evaporator capacity must be multiplied by a correction factor depending on liquid temperature t l ahead of expansion valve. When the corrected capacity is known, the selection can be made from the table. Correction factors based on liquid temperature t l t l C R407C Hot gas defrosting With hot gas defrosting it is not normally possible to select a valve from condensing temperature t c and evaporating temperature t e. This is because the pressure in the evaporator as a rule quickly rises to a value near that of the condensing pressure. It remains at this value until the defrosting is finished. In most cases therefore, the valve will be selected from condensing temperature t c and pressure drop Δp across the valve, as shown in the example for heat recovery. Heat recovery The following is given: Refrigerant = R22 Evaporating temperature t e = 0 C Condensing temperature t c = + 40 C Hot gas temperature ahead of valve t h = + 85 C Heat recovery condenser yield Q h = 8 kw The capacity table for 22 with t c = + 40 C gives the the capacity for an EVR 0 as 8.9 kw, when pressure drop Δp is bar. The correction factor for t e = 0 C is given in the table as The correction for hot gas temperature t h = + 85 C has been calculated as 4% which corresponds to a factor of.04. Q h must be corrected with factors found: With Δp = bar is Q h = 8.9 x 0.94 x.04 = 8.7 kw. With Δp = bar, Q h becomes only 6. x 0.94 x.04 = 6.2 kw. An would also be able to give the required capacity, but with Δp at approx. bar. The is therefore too small. The EVR is so large that it is doubtful whether the necessary Δp of apprx. bar could be obtained. An EVR 5 would therefore be too large. Result: An EVR 0 is the correct valve for the given conditions. 2 DKRCCPDBB0A H275 Danfoss A/S,

13 Capacity (continued) An increase in hot gas temperature t h of 0 K, based on t h = t c C, reduces valve capacity approx. 2% and vice versa. A change in evaporating temperature t e changes valve capacity; see correction factor table below. Hot gas capacity Q h kw EVR 2 EVR EVR 0 EVR 5 EVR 22 Pressure drop across valve Δp bar Hot gas capacity Q h kw Evaporating temp. t e =-0 C. Hot gas temp. t h =t c C. Subcooling Δt sub =4 K Condensing temperature t c C R Correction factors When sizing valves, the table value must be multiplied by a correction factor depending on evaporating temperature t e. Correction factors for evaporating temperatur t e t e C R Danfoss A/S, DKRCCPDBB0A H275

14 Capacity (continued) An increase in hot gas temperature t h of 0 K, based on t h = t c C, reduces valve capacity approx. 2% and vice versa. A change in evaporating temperature t e changes valve capacity; see correction factor table below. Hot gas capacity Q h kw EVR 2 EVR EVR 0 EVR 5 EVR 22 Pressure drop across valve Δp bar Hot gas capacity Q h kw R4a Evaporating temp. t e =-0 C. Hot gas temp. t h =t c C. Subcooling Δt sub =4 Kv Condensing temperature t c C Correction factors When sizing valves, the table value must be multiplied by a correction factor depending on evaporating temperature t e. Correction factors for evaporating temperatur t e t e C R4A DKRCCPDBB0A H275 Danfoss A/S,

15 Capacity (continued) An increase in hot gas temperature t h of 0 K, based on t h = t c C, reduces valve capacity approx. 2% and vice versa. A change in evaporating temperature t e changes valve capacity; see correction factor table below. Hot gas capacity Q h kw EVR 2 EVR EVR 0 EVR 5 EVR 22 Pressure drop across valve Δp bar Hot gas capacity Q h kw R404A/R507 Evaporating temp. t e =-0 C. Hot gas temp. t h =t c C. Subcooling Δt sub =4 K Condensing temperature t c C Correction factors When sizing valves, the table value must be multiplied by a correction factor depending on evaporating temperature t e. Correction factors for evaporating temperatur t e t e C R440A/R Danfoss A/S, DKRCCPDBB0A H275 5

16 Capacity (continued) An increase in hot gas temperature t h of 0 K, based on t h = t c C, reduces valve capacity approx. 2% and vice versa. A change in evaporating temperature t e changes valve capacity; see correction factor table below. Hot gas capacity Q h kw EVR 2 EVR EVR 0 EVR 5 EVR 22 Pressure drop across valve Δp bar Hot gas capacity Q h kw R407C Evaporating temp. t e =-0 C. Hot gas temp. t h =t c C. Subcooling Δt sub =4 K Condensing temperature t c C Correction factors When sizing valves, the table value must be multiplied by a correction factor depending on evaporating temperature t e Correction factors for evaporating temperatur t e t e C R407C DKRCCPDBB0A H275 Danfoss A/S,

17 Capacity (continued) An increase in hot gas temperature t h of 0 K reduces valve capacity approx. 2% and vice versa. Hot gas capacity G h kg/s EVR 2 EVR EVR 0 EVR 5 EVR 22 EVR 2 EVR EVR 0 EVR 5 EVR 22 Hot gas temperature th C +90 Hot gas temperature th C +60 Condensing temperature tc C Condensing temperature tc C Hot gas capacity G h kg/s at pressure drop across valve Δp bar R Hot gas capacity G h kg/s at pressure drop across valve Δp bar R4a Danfoss A/S, DKRCCPDBB0A H275 7

18 Capacity (continued) Hot gas capacity G h kg/s EVR 2 EVR EVR 0 EVR 5 EVR 22 Hot gas temperature th C +60 Condensing temperature tc C Hot gas capacity G h kg/s at pressure drop across valve Δp bar R404A/R R407C Hot gas temperature th C Condensing temperature tc C Hot gas capacity G h kg/s at pressure drop across valve Δp bar EVR EVR EVR EVR EVR An increase in hot gas temperature t h of 0 K reduces valve capacity approx. 2% and vice versa DKRCCPDBB0A H275 Danfoss A/S,

19 Design / Function EVR 2 (NC) EVR 0 (NC) EVR 0 (NO) (NC) and 40 (NC) 4. Coil 6. Armature 8. Valve plate / Pilot valve plate 20. Earth terminal 24. Connection for flexible steel hose 28. Gasket 29. Pilot orifice 0. O-ring. Piston ring 6. DIN plug 7. DIN socket (to DIN 4650) 40. Protective cap/terminal box 4. Valve cover 44. O-ring 45. Valve cover gasket 49. Valve body 50. Gasket 5. Threaded plug 5. Manual operation spindle 7. Equalization hole 74. Main channel 75. Pilot channel 76. Compression spring 80. Diaphragm/Servo piston 8. Valve seat 84. Main valve plate 90. Mounting hole EVR solenoid valves are designed on two different principles:. Direct operation 2. Servo operation. Direct operation EVR 2 and are direct operated. The valves open direct for full flow when the armature (6) moves up into the magnetic field of the coil. This means that the valves operate with a min. differential pressure of 0 bar. The teflon valve plate (8) is fitted direct on the armature (6). Inlet pressure acts from above on the armature and the valve plate. Thus, inlet pressure, spring force and the weight of the armature act to close the valve when the coil is currentless. 2. Servo operation 22 are servo operated with a "floating" diaphragm (80). The pilot orifice (29) of stainless steel is placed in the centre of the diaphragm. The teflon pilot valve plate (8) is fitted direct to the armature (6). When the coil is currentless, the main orifice and pilot orifice are closed. The pilot orifice and main orifice are held closed by the weight of the armature, the armature spring force and the differential pressure between inlet and outlet sides. When current is applied to the coil the armature is drawn up into the magnetic field and opens the pilot orifice. This relieves the pressure above the diaphragm, i.e. the space above the diaphragm becomes connected to the outlet side of the valve. The differential pressure between inlet and outlet sides then presses the diaphragm away from the main orifice and opens it for full flow. Therefore a certain minimum differential pressure is necessary to open the valve and keep it open. For 22 valves this differential pressure is 0.05 bar. When current is switched off, the pilot orifice closes. Via the equalization holes (7) in the diaphragm, the pressure above the diaphragm then rises to the same value as the inlet pressure and the diaphragm closes the main orifice., 2 and 40 are servo operated piston valves. The valves are closed with currentless coil. The servo piston (80) with main valve plate (84) closes against the valve seat (8) by means of the differential pressure between inlet and outlet side of the valve, the force of the compression spring (76) and possibly the piston weight. When current to the coil is switched on, the pilot orifice (29) opens. This relieves the pressure on the piston spring side of the valve. The differential pressure will then open the valve. The minimum differential pressure needed for full opening of the valves is bar. EVR (NO) has the opposite function to EVR (NC), i.e. it is open with de-energised coil. EVR (NO) is available with servo operation only. Danfoss A/S, DKRCCPDBB0A H275 9

20 Material specifications EVR 2 to 25 Solenoid valves Standard No. Description Material Analysis Mat.no. W.no. DIN EN Valve body EVR 2 to 25 Brass CuZn40Pb2 CW67N EVR 2 to Stainless steel X5 CrNi Cover to 22 Brass CuZn40Pb2 CW67N Cast iron EN-GJS LT EN-JS Armature tube EVR 2 to 25 Stainless steel X2 CrNi Armature tube nut Stainless steel X8 CrNiS Gasket EVR 2 to 25 Rubber Cr 6 Gasket Al. gasket Al Solder tube Copper SF-Cu CW024A Screws EVR 2 to 25 Stainless steel A Spindle for man. operat. Stainless steel X8 CrNiS Gasket Rubber Cr to 40 Solenoid valves Standard No. Description Material Analysis Mat.no. W.no. DIN EN Valve body /40 Cast Iron EN-GJS LT EN-JS Cover /40 Brass CuZn40Pb2 CW67N Armature tube /40 Stainless steel X2 CrNi Armature tube nut /40 Stainless steel X8 CrNiS Gasket /40 Rubber Cr 6 Gasket /40 Al. gasket Al Solder tube /40 Copper SF.Cu CW024A Screws /40 Stainless steel A Spindle for. man. operation /40 Stainless steel X8 CrNiS DKRCCPDBB0A H275 Danfoss A/S,

21 Dimensions and weights EVR (NC) 2 5 and 5 (NO), flare connection Weight of coil 0 W: approx. 0. kg 2 and 20 W: approx. 0.5 kg With cable connection coil With DIN plugs coil With terminal box coil Connection NV L 5 max. Weight H Flare H 2 H H 4 L L 2 L L 4 B B max. with 0 W 2/20 W coil in. mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg EVR 2 / EVR / / / / EVR 0 / / EVR 5 5 / Danfoss A/S, DKRCCPDBB0A H275 2

22 Dimensions and weights (continued) EVR (NC) 2 22 and 22 (NO), solder connection Weight of coil 0 W: approx. 0. kg 2 and 20 W: approx. 0.5 kg With cable connection coil With DIN plugs coil With terminal box coil Connection L 5 max. Weight H Solder H 2 H H 4 L L 2 L L 4 B B max. with coil 0 W 2/20 W in. mm mm mm mm mm mm mm mm mm mm mm mm mm kg EVR 2 / EVR / / / / EVR 0 / / EVR 5 5 / / / / EVR 22 / DKRCCPDBB0A H275 Danfoss A/S,

23 Dimensions and weights (continued) EVR (NC) 25, 2 og 40, solder connection and 40 terminal box and 40 with terminal box coil Weight of coil 0 W: approx. 0. kg 2 and 20 W: approx. 0.5 kg Coil with cable Coil with DIN plugs Connection Solder H H 2 H H 4 L L 2 cable connection Coil with L Coil with DIN connection L 4 Coil with terminal box L 5 max. 0 W 2/20 W in. mm mm mm mm mm mm mm mm mm mm mm mm mm kg / / / / / / B B max. Weight with coil EVR (NC) 5 and 20, flange connection Coil with cable Coil with DIN plugs Weight of coil 0 W: approx. 0. kg 2 and 20 W: approx. 0.5 kg With terminal box coil Weight of flange set For EVR 5: 0.6 kg For : 0.9 kg H H 2 H H 4 L L L 2 connection Coil with cable L Coil with DIN connection L 4 Coil with terminal box L 5 max. B B max. 0 W 2/20 W mm mm mm mm mm mm mm mm mm mm mm mm mm kg EVR Weight with coil excl. flanges Danfoss A/S, DKRCCPDBB0A H275 2

24 24 DKRCCPDBB0A H275 Danfoss A/S,

Solenoid valve Types EVR 2 EVR 40 NC/NO

Solenoid valve Types EVR 2 EVR 40 NC/NO MAKING MODERN LIVING POSSIBLE Data sheet Solenoid valve s EVR 2 EVR 40 NC/NO EVR is a direct or servo operated solenoid valve for liquid, suction, and hot gas lines with fluorinated refrigerants. EVR valves

More information

Solenoid valves. Solenoid valves, type PKVD Solenoid valves, type EVR NC / NO

Solenoid valves. Solenoid valves, type PKVD Solenoid valves, type EVR NC / NO Solenoid valves Contents Page Solenoid valves, type PKVD 12-20 Introduction... 5 Features... 5 Technical data... 5 Ordering... 5 Capacity... 6 Sizing... 7 Valve selection... 7 Design/Function... 8 Dimensions

More information

Solenoid valves type EVR 2 40 NC / NO

Solenoid valves type EVR 2 40 NC / NO Solenoid valves type EVR 2 40 NC / NO Introduction EVR is a direct or servo operated solenoid valve for liquid, suction, and hot gas lines with fluorinated refrigerants. Features Complete range of solenoid

More information

Solenoid valve for R410A and R744 Types EVR 2 - EVR 6 and EVRH 10 - EVRH 40

Solenoid valve for R410A and R744 Types EVR 2 - EVR 6 and EVRH 10 - EVRH 40 Data sheet Solenoid valve for R410A and R744 s EVR 2 - EVR 6 and EVRH 10 - EVRH 40 EVRH high pressure range is a direct or servo operated solenoid valve specially designed to meet the requirements for

More information

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet Solenoid valves, type 40 and EVRAT 10 20 REFRIGERATION AND AIR CONDITIONING Technical leaflet Technical leaflet Solenoid valves type to 40 and EVRAT 10 to 20 Contents Page Introduction... 3 Approvals...

More information

Solenoid valves EVRA and EVRAT

Solenoid valves EVRA and EVRAT Data sheet Solenoid valves EVRA and EVRAT EVRA is a direct or servo operated solenoid valve for liquid, suction and hot gas lines with ammonia or fluorinated refrigerants. EVRA valves are supplied complete

More information

Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20

Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20 Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20 Contents Page Approval...569 Technical data...569 Ordering...570 Rated capacity...573 Capacity...573 Design / Function...577 Material specification............................................................................

More information

MAKING MODERN LIVING POSSIBLE. Solenoid valves Type EVU for fluorinated refrigerants REFRIGERATION AND AIR CONDITIONING.

MAKING MODERN LIVING POSSIBLE. Solenoid valves Type EVU for fluorinated refrigerants REFRIGERATION AND AIR CONDITIONING. MAKING MODERN LIVING POSSIBLE Solenoid valves EVU for fluorinated refrigerants REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction... 3 Features... 3 Approvals... 3 Technical

More information

Solenoid valves Type EVU

Solenoid valves Type EVU Data sheet Solenoid valves EVU EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and servo operated versions, they can be applied in liquid, suction, and hot

More information

Solenoid valves Type EVU for fluorinated refrigerants

Solenoid valves Type EVU for fluorinated refrigerants Data sheet Solenoid valves EVU for fluorinated refrigerants EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and pilot operated versions, they can be applied

More information

Solenoid valves type EVSA 25 50

Solenoid valves type EVSA 25 50 Solenoid valves type EVSA 25 50 Introduction EVSA is an assisted lift, servo operated solenoid valve. EVSA 25, 35 and 50 are for use in suction lines - EVSA 25 in liquid and return lines too - in refrigerating

More information

Pressure and temperature regulators, type PM, and pilot valves

Pressure and temperature regulators, type PM, and pilot valves Pressure and temperature regulators, type PM, and pilot valves Introduction Main valves, type PM 1 and PM 3 Pilot valves for mounting directly into main valves, type PM Main valves, type PM 1 and PM 3

More information

Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory)

Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory) MAKING MODERN LIVING POSSIBLE Data sheet Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory) A CPCE hot gas bypass regulator is used to adapt compressor capacity to actual evaporator

More information

Electrically Operated Expansion Valve Types AKV 10, AKV 15 and AKV 20

Electrically Operated Expansion Valve Types AKV 10, AKV 15 and AKV 20 MAKING MODERN LIVING POSSIBLE Data sheet Electrically Operated Expansion Valve Types AKV 10, AKV 15 and AKV 20 AKV are electrically operated expansion valves designed for refrigerating plants. The AKV

More information

Capacity regulators (hot gas bypass) PMC and CVC

Capacity regulators (hot gas bypass) PMC and CVC MAKING MODERN LIVING POSSIBLE Technical brochure Capacity regulators (hot gas bypass) PMC and CVC The PMC and CVC is used for capacity regulation in refrigeration, freezing and air conditioning plant for

More information

Electric Expansion Valve Type AKVO 10

Electric Expansion Valve Type AKVO 10 Data sheet Electric Expansion Valve Type AKVO 10 AKVO 10 is an electrically operated expansion valve designed for refrigeration plant. AKVO 10 has an internal filter. The AKVO 10 range covers a capacity

More information

Modulating liquid level regulators, direct-controlled SV 1 and SV 3

Modulating liquid level regulators, direct-controlled SV 1 and SV 3 MAKING MODERN LIVING POSSIBLE Technical brochure Modulating liquid level regulators, direct-controlled SV 1 and SV 3 The SV 1 and 3 can be used separately as a modulating liquid level regulator in refrigerating,

More information

Electric expansion valves Types AKVA 10, 15 & 20

Electric expansion valves Types AKVA 10, 15 & 20 Data sheet Electric expansion valves Types AKVA 10, 15 & 20 AKVA are electric expansion valves designed for ammonia refrigerating plant. The AKVA valves are normally controlled by a controller from Danfoss

More information

Thermostatic expansion valves PHT

Thermostatic expansion valves PHT MAKING MODERN LIVING POSSIBLE Technical brochure Thermostatic expansion valves PHT www.danfoss.com Contents Page Introduction........................................................................................

More information

Electronically operated expansion valve for CO 2 Type AKVH

Electronically operated expansion valve for CO 2 Type AKVH MAKING MODERN LIVING POSSIBLE Technical brochure Electronically operated expansion valve for CO 2 Type AKVH AKVH are electrically operated expansion valves designed for refrigerating plants using R744

More information

Pressure operated water valve Type WVFX and WVS

Pressure operated water valve Type WVFX and WVS Data sheet Pressure operated water valve WVFX and WVS Pressure operated water valves types WVFX and WVS are used for regulating the flow of water in refrigeration plants with water-cooled condensers. The

More information

Crankcase pressure regulator Type KVL

Crankcase pressure regulator Type KVL MAKING MODERN LIVING POSSIBLE Data sheet Crankcase pressure regulator KVL Crankcase pressure regulator type KVL is fitted in the suction line ahead of the compressor. KVL protects the compressor motor

More information

Electric expansion valve Type AKV 10P, AKV 10PS

Electric expansion valve Type AKV 10P, AKV 10PS Data sheet Electric expansion valve Type AKV 10P, AKV 10PS AKV 10P and AKV10PS are electric operated expansion valves designed for refrigerating plants. The AKV 10P and AKV 10PS valves are normally controlled

More information

Crankcase pressure regulator Type KVL

Crankcase pressure regulator Type KVL Data sheet Crankcase pressure regulator KVL Crankcase pressure regulator type KVL is fitted in the suction line ahead of the compressor. KVL protects the compressor motor against overload during start-up

More information

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1 HANDBOOK Ed. 2017 VS-ED 01/2017 - ENG 1 2 VS-ED 01/2017 - ENG TABLE OF CONTENTS CHAPTER 1 CHAPTER 2 CHAPTER 3 CHAPTER 4 CHAPTER 5 CHAPTER 6 CHAPTER 7 CHAPTER 8 CHAPTER 9 CHAPTER 10 CHAPTER 11 CHAPTER 12

More information

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1 HANDBOOK Ed. 2017 VS-ED 01/2017 - ENG 1 CHAPTER 3 NORMALLY-CLOSED PULSE FOR REFRIGERATION PLANTS THAT USE HFC OR HFO REFRIGERANTS APPLICATION The solenoid valves illustrated in this chapter are designed

More information

Electronic suction modulating valves type KVS

Electronic suction modulating valves type KVS MAKING MODERN LIVING POSSIBLE Technical brochure Electronic suction modulating valves type KVS KVS is a series of electronic suction modulating valves for AC transport and refrigeration applications. Accurate

More information

Crankcase Pressure Regulating Valves

Crankcase Pressure Regulating Valves Crankcase Regulating Valves Crankcase Regulating Valves are designed to prevent overloading of the compressor motor by limiting the crankcase pressure to a predetermined maximum value during and after

More information

Electric expansion valve for R744 (CO 2 ) Type AKVH

Electric expansion valve for R744 (CO 2 ) Type AKVH Electric expansion valve for R744 (CO 2 ) Type AKVH AKVH are electrically operated expansion valves designed for refrigerating plants using R744 refrigerant. The AKVH valves are normally controlled by

More information

Liquid level control. Thermostatic liquid level regulators, type TEVA. High pressure float valve, type HFI

Liquid level control. Thermostatic liquid level regulators, type TEVA. High pressure float valve, type HFI Liquid level control Contents Page Thermostatic liquid level regulators, type TEVA Introduction... 7 Materials... 7 Technical data... 7 Ordering... 8 Identification... 8 Capacity... 9 Design/Function...

More information

Solenoid valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

Solenoid valves REFRIGERATION AND AIR CONDITIONING. Fitters notes REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Installation...3 EVRA 32 & 40 precautions...4 When pressure testing...4 The coil...5 The clip-on coil...6 The correct product...8 Fault location...9

More information

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

SOLENOID VALVES FOR REFRIGERATING SYSTEMS SOLENOID VALVES 17 SOLENOID VALVES FOR REFRIGERATING SYSTEMS APPLICATIONS The solenoid valves, shown in this chapter, are classified Pressure accessories in the sense of the Pressure Equipment Directive

More information

Solenoid Valves Type EVR

Solenoid Valves Type EVR Solenoid Valves Type EVR 16 EVR 2 and 3. Service kit (a.c.) Pos. 16 Armature assembly 1 28 Rubber gasket 1 Compress spring 1 032F0181 1 28 EVR 2 and 3. Seal kit O-ring, Armature tube 1 28 Rubber gasket

More information

Servo-operated 2/2-way solenoid valves Type EV220A

Servo-operated 2/2-way solenoid valves Type EV220A Data sheet Servo-operated 2/2-way solenoid valves Type is a compact servo-operated 2/2-way solenoid valve program, especially designed for use in machines and equipment with limited space. Features and

More information

Electric expansion valve Type ETS ETS 400

Electric expansion valve Type ETS ETS 400 MAKING MODERN LIVING POSSIBLE Data sheet Electric expansion valve Type ETS 12.5 - ETS 400 ETS is a series of electric expansion valves for precise liquid injection in evaporators for air conditioning and

More information

Electric expansion valve Type ETS ETS 400

Electric expansion valve Type ETS ETS 400 Data sheet Electric expansion valve Type ETS 12.5 - ETS 400 ETS is a series of electric expansion valves for precise liquid injection in evaporators for air conditioning and refrigeration applications.

More information

Pilot valves Types CVP, CVPP, CVC, CVE, EVM and CVH

Pilot valves Types CVP, CVPP, CVC, CVE, EVM and CVH Data sheet Pilot valves Types CVP, CVPP, CVC, CVE, EVM and CVH Pilot valves for direct mounting in main valves Pilot valves are intended for mechanical control of a main valve and are ready for direct

More information

Crankcase pressure regulator Type KVL

Crankcase pressure regulator Type KVL Data sheet Crankcase KVL KVL crankcase are used to protect the compressor motor against overload experienced during startup after long off periods or just after defrost periods. They are installed in the

More information

Expansion valves - 2 of 2

Expansion valves - 2 of 2 Expansion valves - 2 of 2 Contents Page Thermostatic expansion valves, type T 2 and TE 2 Introduction... 3 Features... 3 Technical data... 3 Superheat... 3 Ordering: Components with flare flare connection...

More information

Pilot operated main valves for regulating pressure and temperature, type PM

Pilot operated main valves for regulating pressure and temperature, type PM MAKING MODERN LIVING POSSIBLE Technical brochure Pilot operated main valves for regulating pressure and temperature, type PM PM valves are pilot operated main valves for regulating pressure and temperature

More information

Technical brochure Electrically operated expansion valves, type ETS 6

Technical brochure Electrically operated expansion valves, type ETS 6 MAKING MODERN LIVING POSSIBLE Technical brochure Electrically operated expansion valves, type ETS 6 With many years of experience the current range of Electronic Expansion Valves offers high reliability

More information

FA + solenoid valve Type ICF 15/20 EVRAT

FA + solenoid valve Type ICF 15/20 EVRAT Data sheet FA + solenoid valve Type ICF 15/20 EVRAT Based on advanced technology the ICF EVRAT retrofit valve incorporates three functions in one housing, which can replace the widely used direct coupled

More information

Pilot valves for servo opereated main valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pilot valves for servo opereated main valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet Pilot valves for servo opereated main valves REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction........................................................................................3

More information

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1 HANDBOOK Ed. 2017 1 CHAPTER 5 NORMALLY-CLOSED FOR REFRIGERATION PLANTS THAT USE HC REFRIGERANTS APPLICATION The solenoid valves illustrated in this chapter have been developed by Castel for all those refrigeration

More information

Stainless steel - the strong solution

Stainless steel - the strong solution MAKING MODERN LIVING POSSIBLE Stainless steel - the strong solution TU and TC thermostatic expansion valves REFRIGERATION & AIR CONDITIONING DIVISION TU / TC: superior by design and function The function

More information

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1 HANDBOOK Ed. 2017 RP-ED 01/2017 - ENG 1 CHAPTER 2 CRANKCASE PRESSURE REGULATORS For refrigeration plants that use HCFC or HFC refrigerants shutter continues to open, until the stroke limit is reached and

More information

Technical leaflet Thermostatic expansion valves with fixed orifice

Technical leaflet Thermostatic expansion valves with fixed orifice MAKING MODERN LIVING POSSIBLE Technical leaflet Thermostatic expansion valves with fixed orifice Type TDE / TDEB www.danfoss.com Contents Page Introduction........................................................................................3

More information

Pilot-operated servo valve Type ICS

Pilot-operated servo valve Type ICS Data sheet Pilot-operated servo valve Type ICS The valve comprises three main components: valve body, function module and top cover. ICS pilot-operated servo valves are pilot operated valves for regulating

More information

Assisted lift operated 2/2-way solenoid valves Type EV251B

Assisted lift operated 2/2-way solenoid valves Type EV251B Data sheet Assisted lift operated 2/2-way solenoid valves Type EV251B EV251B with assisted lift is especially suitable for applications such as closed systems with low and fluctuating pressure conditions

More information

Electric expansion valves Type ETS 6

Electric expansion valves Type ETS 6 MAKING MODERN LIVING POSSIBLE Data sheet Electric expansion valves Type ETS 6 The range of Electric expansion valves are based on many years of experience. ETS 6 secure reliability and provide a precise

More information

Electrically operated expansion valves, type ETS

Electrically operated expansion valves, type ETS MAKING MODERN LIVING POSSIBLE Technical brochure Introduction ETS is a series of electrically operated expansion valves for precise liquid injection in evaporators for air conditioning and refrigeration

More information

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

SOLENOID VALVES FOR REFRIGERATING SYSTEMS SOLENOID VALVES 17 SOLENOID VALVES FO EFIGEATING SYSTEMS APPLICATIONS The solenoid valves, shown in this chapter, are classified Pressure accessories in the sense of the Pressure Equipment Directive 97/23/EC,

More information

Pressure Control Type KPU

Pressure Control Type KPU MAKING MODERN LIVING POSSIBLE Data sheet Pressure Control Type KPU KPU controls are designed for use in refrigeration and air-conditioning systems to protect the systems from excessively low suction or

More information

Servo piston operated 2/2-way solenoid valves for steam Type EV245B

Servo piston operated 2/2-way solenoid valves for steam Type EV245B Data sheet Servo piston operated 2/2-way solenoid valves for steam EV245B EV245B is a servo piston operated 2/2-way solenoid valve for use in steam applications. The servo piston operated design with PTFE

More information

Data sheet. 2-way solenoid valves with Clip-on coils for neutral liquids and gases. January 2003 DKACV.PD.200.K B1472

Data sheet. 2-way solenoid valves with Clip-on coils for neutral liquids and gases. January 2003 DKACV.PD.200.K B1472 Data sheet 2-way solenoid valves with Clip-on coils for neutral liquids and gases January 200 DKACV.PD.200.K.22 520B472 2 DKACV.PD.200.K.22 Danfoss A/S 0-200 Contents 2-way solenoid valves with Clip-on

More information

Installation EVRA 32 & 40 precautions When pressure testing The coil The correct product... 18

Installation EVRA 32 & 40 precautions When pressure testing The coil The correct product... 18 Contents Page Installation....................................................................................... 15 EVRA 32 & 40 precautions.....................................................................

More information

Refrigeration K-211. Replacement Parts. Chillers, Condensers. Compressors, Motors. Electrical. Components. Heating. Indoor Air Quality.

Refrigeration K-211. Replacement Parts. Chillers, Condensers. Compressors, Motors. Electrical. Components. Heating. Indoor Air Quality. EMERSON CLIMATE TECHNOLOGIES-Oil Controls High Efficiency Centrifugal Oil Separator The High Efficiency Centrifugal Oil Separator is used in ultra-low temperature systems with long refrigerant lines or

More information

Automatic controls catalogue E.N. 4

Automatic controls catalogue E.N. 4 TV series Technical parameter Max. body temperature: 80 Max. bulb sensing temperature: 60 About R134a,R22,R407C,R404A/R507 system: Max. working pressure: 3 MPa Max. testing pressure: 3.3 MPa About R410A

More information

Injection valve, type TXI 2 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Injection valve, type TXI 2 REFRIGERATION AND AIR CONDITIONING. Technical leaflet Injection valve, type TXI 2 REFRIGERATION AND AIR CONDITIONING Technical leaflet Introduction Danfoss has developed a injection valve type TXI 2 for desuperheating in 2-stage refrigeration systems operating

More information

AIR CONDITIONING COMMERCIAL REFRIGERATION HEAT PUMP STANDARD PRODUCT

AIR CONDITIONING COMMERCIAL REFRIGERATION HEAT PUMP STANDARD PRODUCT AIR CONDITIONING COMMERCIAL REFRIGERATION HEAT PUMP STANDARD PRODUCT SANHUA Strive for perfection, Pursuit of excellence Sanhua is a leading HVAC&R manufacturer of controls and components with a global

More information

Thermostatic expansion valves Type TGE 10, TGE 20 and TGE 40

Thermostatic expansion valves Type TGE 10, TGE 20 and TGE 40 MAKING MODERN LIVING POSSIBLE Data sheet Thermostatic expansion valves Type TGE 10, TGE 20 and TGE 40 TGE is a dedicated designed series of thermostatic expansion valves for all standard refrigerants including

More information

Pilot valves for servo operated main valves

Pilot valves for servo operated main valves MAKING MODERN LIVING POSSIBLE Technical brochure Pilot valves for servo operated main valves www.danfoss.com/ir Contents Page Introduction........................................................................................3

More information

Indirect servo-operated 2/2-way solenoid valves Type EV220W 10 - EV220W 50, NBR and EPDM versions

Indirect servo-operated 2/2-way solenoid valves Type EV220W 10 - EV220W 50, NBR and EPDM versions Data sheet Indirect servo-operated 2/2-way solenoid valves Type EV220W 10 - EV220W 50, NBR and EPDM versions EV220W is a range of compact indirect servo- operated 2/2 way solenoid valves with connections

More information

Servo-operated 2/2-way solenoid valves for steam Type EV225B

Servo-operated 2/2-way solenoid valves for steam Type EV225B Data sheet Servo-operated 2/2-way solenoid valves for steam EV225B EV225B is a servo-operated 2/2-way solenoid valve for use in steam applications. The design is based on a PTFE diaphragm concept, ensuring

More information

Solenoid valves for water supply and steam inlet Types EV220T, EV220W, EV220B, EV225B, and AV210

Solenoid valves for water supply and steam inlet Types EV220T, EV220W, EV220B, EV225B, and AV210 Data sheet Solenoid valves for water supply and steam inlet Types EV220T, EV220W, EV220B, EV225B, and AV210 Valve range for water supply and steam inlet for water fluid controls: aundry Dishwashing Main

More information

MAKING MODERN LIVING POSSIBLE. Solenoid valves, 2/2-way assisted lift operated type EV251B Technical brochure

MAKING MODERN LIVING POSSIBLE. Solenoid valves, 2/2-way assisted lift operated type EV251B Technical brochure MAKING MODERN LIVING POSSIBLE Solenoid valves, 2/2-way assisted lift operated type EV251B 10-22 Technical brochure Technical brochure Solenoid valves 2/2 way assisted lift operated, type EV251B 10-22 Contents

More information

Pressure Controls type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure Controls type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet Pressure Controls type KPU REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction... 3 Features... 3 Approvals... 3 Materials in contact with medium... 3 Technical data... 4 Ordering...

More information

EX4 / EX5 / EX6 / EX7 / EX8 Electrical Control Valves

EX4 / EX5 / EX6 / EX7 / EX8 Electrical Control Valves ALCO Controls EX4 / EX5 / EX6 / EX7 / EX8 are stepper motor driven valves for precise control of refrigerant mass flow in air conditioning, refrigeration, heat pumps, close control, and industrial process

More information

Refrigeration Solenoid Valves & 3-Way Heat Reclaim Valves

Refrigeration Solenoid Valves & 3-Way Heat Reclaim Valves aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Refrigeration Solenoid s & 3-Way Heat Reclaim s Catalog D-1, May 2010

More information

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40 MAKING MODERN LIVING POSSIBLE Technical brochure Thermostatic expansion valves TGE 0, TGE 20 and TGE 40 TGE is a dedicated designed series of thermostatic expansion valves for all standard refrigerants.

More information

Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves. Technical leaflet MAKING MODERN LIVING POSSIBLE

Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves. Technical leaflet MAKING MODERN LIVING POSSIBLE MAKING MODERN LIVING POSSIBLE Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction...3 Features...3

More information

Type EV224B. Servo-operated 2/2-way solenoid valves for high pressure air. Data sheet

Type EV224B. Servo-operated 2/2-way solenoid valves for high pressure air. Data sheet Data sheet Servo-operated 2/2-way solenoid valves for high air Type EV224B EV224B for compressed air, is a high indirect servo-operated 2/2-way solenoid valve with working up to 40 bar, medium temperature

More information

Data sheet. Solenoid valves 2/2-way direct-operated Type EV210B. February 2002 DKACV.PD.200.A B1504

Data sheet. Solenoid valves 2/2-way direct-operated Type EV210B. February 2002 DKACV.PD.200.A B1504 Data sheet Solenoid valves 2/2-way direct-operated Type EV210B February 2002 DKACV.PD.200.A5.02 520B1504 closed Type EV210B NC for neutral liquids and gases DN 1.5-25 B - G1 Features Technical data 1 )

More information

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40 MAKING MODERN LIVING POSSIBLE Technical brochure Thermostatic expansion valves TGE 0, TGE 20 and TGE 40 TGE is a dedicated designed series of thermostatic expansion valves for all standard refrigerants.

More information

Coils for solenoid valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Coils for solenoid valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet REFRIGERATION AND AIR CONDITIONING Technical leaflet 2 RD3JE402 Danfoss A/S, 01-2005 Introduction The coils are specially designed to operate in the aggressive environment of high humidity and temperature

More information

Thermostatic Expansion Valve

Thermostatic Expansion Valve STANDARD Thermostatic Expansion Valve RFGD series thermostatic expansion valves are used to adjust mass flow of refrigerant into the evaporator while controlling the refrigerant s superheat at the outlet

More information

Pilot-operated servo valve Type ICS

Pilot-operated servo valve Type ICS Data sheet Pilot-operated servo valve ICS ICS pilot-operated servo valves belong to the ICV (Industrial Control Valve) family. The valve comprises three main components: valve body, function module and

More information

The precise step to take

The precise step to take New perspectives with Danfoss Saginomiya Electronic Expansion Valves The precise step to take Type KV Electronic Expansion Valves Energy efficiency Precision flow control with high resolution Compact and

More information

A full line of field-tested CO 2 controls, stocked for your convenience

A full line of field-tested CO 2 controls, stocked for your convenience A full line of field-tested controls, stocked for your convenience 7000+ systems built with products www.danfoss.us/aftermarket Why choose for? has pioneered technologies for both transcritical and subcritical

More information

Servo-operated 2/2-way solenoid valves for high pressure

Servo-operated 2/2-way solenoid valves for high pressure Data sheet Servo-operated 2/2-way solenoid valves for high Type EV224B EV224B for compressed air, is a high indirect servo-operated 2/2-way solenoid valve with working up to 40 bar, medium temperature

More information

Electric operated valves Type CCM for R744 / CO2

Electric operated valves Type CCM for R744 / CO2 Data sheet Electric operated valves Type CCM for R744 / CO2 The CCM is an electrically operated valve designed specifically for operation in CO 2 systems. The valve is capable of functioning both as an

More information

Pressure Control, Differential Pressure Control, Type RT

Pressure Control, Differential Pressure Control, Type RT MAKING MODERN LIVING POSSIBLE Data sheet Control, Control, Type RT An RT control contains a operated single-pole changeover contact, the position of which depends on the in the inlet connection and the

More information

Thermostatic Expansion

Thermostatic Expansion Thermostatic Expansion Valves Thermostatic Expansion Valves TC Series Application TC thermostatic expansion valves are used to adjust the supply of refrigerant in evaporator by controlling the superheat.

More information

Pulse Width Modulation Valves. Models SPW-0 thru -7

Pulse Width Modulation Valves. Models SPW-0 thru -7 November 2017 Bulletin / Bulletin 30-30 30-30 Page 1 Pulse Width Modulation s Models SPW-0 thru -7 Page 2 Bulletin 30-30 Pulse Width Modulation s For Refrigerant Flow Control in Direct Expansion HFC, HCFC

More information

Pilot-operated servo valve Type ICS

Pilot-operated servo valve Type ICS Data sheet Pilot-operated servo valve Type ICS ICS pilot-operated servo valves belong to the ICV (Industrial Control Valve) family. The valve comprises three main components: valve body, function module

More information

Solenoid valves for drinking water Types EV220BW and EV228BW

Solenoid valves for drinking water Types EV220BW and EV228BW Data sheet Solenoid valves for drinking water Types EV220BW and EV228BW Solenoid valve range with drinking water approvals For water supply Houses and large apartments - Kitchen and bathrooms Commercial

More information

Pilot valves for servo operated main valves

Pilot valves for servo operated main valves MAKING MODERN LIVING POSSIBLE Technical brochure Pilot valves for servo operated main valves Pilot valves for direct mounting in main valves The range of pilot valves consists of: Constant-pressure pilot

More information

Pressure control valve Type KDC

Pressure control valve Type KDC Data sheet Pressure control valve Type KDC 65-00 The KDC valve is a pressure control valve. The valve controls the discharge pressure of the compressor to ensure fast build-up of pressure and lubrication

More information

Solenoid valves 3/2-way direct-operated Type EV310A

Solenoid valves 3/2-way direct-operated Type EV310A Solenoid valves /-way direct-operated Type EV10A Features EV10A NC and NO Very compact valves for industrial application, such as control. For water, oil, compressed air and similar neutral media. Ambient

More information

HANDBOOK EXPANSION VALVES. Ed EXPANSION VALVES VE-ED 01/ ENG 1

HANDBOOK EXPANSION VALVES. Ed EXPANSION VALVES VE-ED 01/ ENG 1 HANDBOOK Ed. 2017 VE-ED 01/2017 - ENG 1 CHAPTER 12 STEP-MOTOR CERTIFIED BY UNDERWRITERS LABORATORIES INC. FOR REFRIGERATION PLANTS THAT USE HCFC, HFC OR HFO REFRIGERANTS belonging to Group 2, as defined

More information

Pressure switch and Thermostat Type CAS

Pressure switch and Thermostat Type CAS MAKING MODERN LIVING POSSIBLE Data sheet Pressure switch and Thermostat CAS The CAS Series consists of a series of pressure controlled switches and temperature controlled switches. In this series, special

More information

Thermostatic Expansion

Thermostatic Expansion Thermostatic Expansion Valves Thermostatic Expansion Valves TCCE Series Application TCCE thermostatic expansion valve is used to regulate refrigerant flow into the evaporator, especially in applications

More information

Thermo. operated water valve Type WVTS

Thermo. operated water valve Type WVTS Data sheet Thermo. operated water valve Type WVTS Thermo. operated water valve type WVTS is suitable for controlling the temperature of a flow of water or neutral brine. WVTS opens on rising sensor temperature

More information

HANDBOOK VALVES. Ed VALVES VR-ED 02/ ENG 1

HANDBOOK VALVES. Ed VALVES VR-ED 02/ ENG 1 HANDBOOK Ed. 2017 1 2 INDEX CHAPTER 1 CHAPTER 2 CHAPTER 3 CHAPTER 4 CHAPTER 5 CHAPTER 6 CHAPTER 7 CHAPTER 8 CHAPTER 9 CHAPTER 10 CHAPTER 11 CHAPTER 12 CHAPTER 13 CHAPTER 14 Valves with screw shutter For

More information

CCMT - Electrically operated valves for transcritical and subcritical CO2

CCMT - Electrically operated valves for transcritical and subcritical CO2 MAKING MODERN LIVING POSSIBLE Technical brochure - Electrically operated valves for transcritical and subcritical CO2 The is an electrically operated valve designed specifically for operation in CO 2 systems.

More information

PRODUCT DATA HDF SERIES Solenoid Valve

PRODUCT DATA HDF SERIES Solenoid Valve HDF series solenoid valves are piston type pilot operated solenoid valves, and are designed for use in all air conditioning and refrigeration systems. The HDF valves can tolerate discharge line temperatures

More information

(S)PORT - (S)PORT-II Evaporator Pressure Regulators

(S)PORT - (S)PORT-II Evaporator Pressure Regulators (S)PORT - (S)PORT-II Evaporator Pressure Regulators Features Highest capacity commercial regulator in the industry Sweat-in-place without disassembly Interchangeable capacity cartridges Low Pressure Drop

More information

Solenoid valves, 2/2-way servo-operated type EV220B 6-22

Solenoid valves, 2/2-way servo-operated type EV220B 6-22 MAKING MODERN LIVING POSSIBLE Data sheet Solenoid valves, 2/2-way servo-operated type EV220B 6-22 EV220B 6-22 is a direct servo-operated 2/2-way solenoid valve program with connections from 1/4 to 1. This

More information

Multi Ejector Solution TM for R744 (CO 2 ) Product type - CTM 1 and CTM 2 Liquid Ejector

Multi Ejector Solution TM for R744 (CO 2 ) Product type - CTM 1 and CTM 2 Liquid Ejector Data sheet Multi Ejector Solution TM for R744 (CO 2 ) Product type - CTM 1 and CTM 2 Liquid Ejector Multi Ejector Solution TM, consists of a CTM 1 and CTM 2 liquid valves and an AK-PC 782A controller.

More information

quality products for refrigeration and air conditioning products suitable for CFC, HCFC and HFC 2006 release PRODUCT HANDBOOK

quality products for refrigeration and air conditioning products suitable for CFC, HCFC and HFC 2006 release  PRODUCT HANDBOOK quality products for refrigeration and air conditioning products suitable for CFC, HCFC and HFC 2006 release www.castel.it PRODUCT HANDBOOK Pessano - February 2006 17 Thermostatic expansion valves Solenoid

More information