1 Rosemex Products 96 VENTILATION CLIMATAIR CENTRAL STATION AIR HANDLING

2 1 INDEX INTRODUCTION... 1 PHYSICAL FEATURES PHYSICAL DATA PERFORMANCE AIR DISCHARGE- MOTOR POSITIONS DIMENSIONS FAN SECTION -A TO TO 15-O ELIMINATOR SECTION AND HUMIDIFIERS... DAMPER SECTIONS PLENUMS FILTER SECTIONS... MIXING BOXES BAG FILTER SECTIONS - TYPE I... BAG FILTER SECTIONS - TYPE II... 3 MULTIZONE OR DUAL DUCT HEAD... AIR WASHERS ACCESS DOORS... VARIMARK II... 9 ARRANGEMENTS SPECIFICATIONS... GENERAL Under the trade name CLIMATAIR, ROSEMEX offers a complete range of central station air handling units to meet the requirements of all air conditioning, heating and ventilating applications. With draw-thru or blow-thru blower sections, CLIMATAIR units will cool, humidify or dehumidify, filter and heat the air volume required to meet system design specifications. These central station air handlers are designed to operate at low, medium or high pressures using Class I, II or III fans. Mechanical components, such as shafts and bearings, are sized by computer to meet blower class requirements. ROSEMEX coils, with chilled water, refrigerant, hot water or steam, provide complete year-round comfort. LAMILINE integral face-and-bypass coil preheats using either hot water or steam. Three types of air washers are available: spray chamber, sprayed coil and wet pad evaporative cooler. A full line of components complements central station air handlers: humidifiers, eliminators, flat and angle bank filter sections with -inch filters, side access high efficiency filter sections with bag filters, standard or high-performance mixing boxes, shutoff, internal or external face-and-bypass damper sections, plenums with or without access doors, and VARIMARK II volume control for VAV (variable air volume) systems. All CLIMATAIR units and components are subjected to a rigid quality inspection program thus ensuring best performance and long, trouble- free life. INTRODUCTION TYPES OF CLIMATAIR S MVT: for heating and ventilating. A draw-thru type unit. Casing of these units is not insulated, and there is no condensate pan. CSAH: for heating, cooling and ventilating. A draw-thru type unit. Blower section is completely insulated and rests on an insulated condensate pan. The cooling coils are also provided with a condensate pan. MZ: for heating, cooling and ventilating. A blow-thru type unit for dual duct or multizone applications, with a possibility of 3 zones in the largest unit. The cold deck on these units is entirely insulated and the cooling coils rest on an insulated condensate pan. OPERATING PRESSURE LEVELS PRESSURE - LP Ps: from 0,0 to 0, kpa (from 0.0 to 3,0 WG) Air flow: from 0,5 to,50 m 3 /s (from 1,000 to 61,000 S) Horizontal models: all units Vertical models: from -A TO incl. PRESSURE - MP Ps: from 0,35 to 1,0 kpa (from 1.5 to 5.5 WG) Air flow: from 1, to,50 m 3 /s (from,00 to 61,000 S) Horizontal models: all units except -A Vertical models: from to incl. PRESSURE - HP Ps: from 1, to,50 kpa (from 5.0 to 10.0 WG) Air flow: from, to,50 m 3 /s (from 5,500 to 61,000 S) Horizontal models:,,, and to 15-O Vertical models: none

3 PHYSICAL FEATURES FAN SECTION Designed for maximum rigidity and fan efficiency, this section supplies the required air volume at the necessary static pressure. Four types of wheel are available in the CLIMATAIR: a) FC: forwardly curved blades, used in the following units: low pressure: from -A to incl. medium pressure: from to incl. high pressure: none b) Bl: backwardly inclined flat blades, used in the following units: low pressure: from to 15-O incl. medium pressure: from to 15-O incl. (except ) high pressure: none c) AS: single thickness airfoil blades, used in the following units: low pressure: from to incl. (except ) medium pressure: from to incl. (except ) high pressure:,,, and 9-l d) AD: double thickness airfoil blades, used in the following units: low pressure: ; to 15-O incl. medium pressure: from to 15-O incl. high pressure: from to 15-O incl. NOTE: All blower wheels are dynamically balanced in their scroll before shipping. SHAFTS: All shaft sizes are selected to ensure maximum fan operating speeds well below first critical shaft speed. Hollow steel shafts are used on all twowheel FC units,,, and. Solid, ground and polished steel shafts are used on all other units. A bituminous coating is used for protection against corrosion. CONDENSATE PAN: All welded sandwich type construction made from heavy galvanized steel having a 13 mm (1/ ) rigid insulating board covered by a sealed galvanized steel sheet. MOTOR LOCATION: On units -A to, motor is outside the fan section and mounted on a hinge-type base. On units to 15-O, motor is inside the fan section and mounted on an adjustable slide base. Both installations provide for perfect belt tension adjustment. BEARINGS: In order to insure long, trouble-free performance, bearings used in the CLIMATAIR air handlers are either single or double row. All bearings are sized for an average minimum life of 00,000 hours. Self-aligning single-row ball bearings have a sphered outer ring fitted into the housing. Self-aligning double-row ball bearings have a common sphered raceway in the outer ring. Both designs allow minor angular displacements of the shaft relative to the housing. Whenever a bearing is installed inside the fan casing, an extended lubrication line is supplied as standard equipment for ease of maintenance. All bearing housings are fitted with a grease nipple which feeds a lubrication groove machined in the bore of the housing, therefore making it possible to relubricate as part of a maintenance program. On low pressure units from -A to, bearing housings are flange type, bolted to the fan section side walls which are reinforced by steel channels. Construction is the same as above on medium pressure units from -A to, except for units and, where opposite side bearing is a pillow block inside the fan section. On high pressure units from to, opposite side bearing is also a pillow block inside the fan section, while drive side bearing is a flange bearing. On units to 15-O for all pressures, two pillow block bearings are used, both mounted inside the fan casing on a rigid steel structure. VARIMARK II Rosemex s centrifugal fan volume controler may be adapted for use on the CLIMATAIR air handlers. The Varimark II is particularly suitable for variable air volume (VAV) systems where required minimum volume is fairly low. Because of its unique characteristics, this revolutionary control system will ensure a stable operation down to only 0% of maximum required air flow. The Varimark II may be used on all CLI- MATAIR single-wheel AS, AD or BI models. On models having a mm ( ) diameter or larger wheel, the Varimark II-S option eliminates the need of additional backdraft dampers when sequencing the operation of parallel fans. NOTE: CLIMATAIR units utilizing FC wheels for VAV applications may be supplied with a scroll volume damper upon request. This damper can be manually or motor operated.

4 3 PHYSICAL FEATURES COILS In fin-to-air heat transfer, efficiency is mainly influenced by the very thin air film which adheres to the fin surface and acts as an insulator. ROSEMEX engineers have designed a fin with deep corrugations which create the turbulence required to continuously move and replace this air film, increasing the air volume that comes in contact with the fin, thus its efficiency. Heat exchanger tubes are staggered so that more air comes in contact with the tubes. The new fin design, plus the staggering of the tubes, have produced a highly efficient heat exchanger. ROSEMEX offers a complete range of coils with a wide variety of fin spacing and circuit arrangements for optimum coil selection, while taking into consideration performance plus initial and operating costs. Various options are available with the CLIMATAIR series: FOR HEATING: type WH: hot water coil type S: steam coil type NFS: non-freeze steam coil FOR COOLING: type WC: chilled water coil type RC: refrigerant coil FOR PREHEATING: type LLW: LAMILINE hot water face and bypass coil type LLS: LAMILINE steam face and bypass coil Fins are aluminum or copper. Tubes are 16mm (5/8 ) O.D., either copper, red brass or cupronickel. Turbulators are available upon request. Perfect mechanical bond between tube and fins is achieved through a tube expansion process that eliminates tube springback. Return bends are silver soldered to the tubes and the steel headers are brazed to the tubes. These headers are mm ( ) or 6 mm ( 1/ ) in diameter, male threaded and provided with plugs for drain and vent; they are coated with zinc chromate red oxide for corrosion protection. Coil frames are galvanized steel; on large coils, intermediate tube sheets are added for more rigidity. Cooling coils are built with a special frame to fit the condensate pan for proper water elimination. When the unit requires two cooling coils one above the other, each coil has a different frame. All coils are tested at 1380 kpa (00 PSIG) air pressure under water. INTEGRAL FACE AN BY-PASS PREHEATING COIL ROSEMEX builds a unique heat exchanger with dampers, the LAMI- LINE. The arrangement of alternate narrow coil and by-pass sections permits diverting the air stream and provides effective mixing without stratification. This unit has been mainly designed for preheating the fresh air supply to a controlled leaving temperature with a minimum risk of freezing the coil. LAMILINE heating coils incorporate the same fin and tube construction features as standard coils. Damper blades are extruded aluminum specially designed for LAMILINE units. The heavy cross-section of these blades provides for a perfect fit and maximum rigidity. All steam coils (LAMILINE, S and NFS) may be used for steam pressures up to 15 P.S.O. Higher pressures available upon request.

5 PHYSICAL FEATURES PLENUMS Generally used in four main applications: - as a support leg for the coils - to gain access to the inside of the system - to support blower section in vertical models ( ) - as a spacer for air entry in certain blower arrangements. Access plenums are available in 356 mm (1 ), 7 mm (18 ) and mm ( ) lengths. A hinged sandwich-type access door can be supplied on access and (vertical model) plenums. DAMPER SECTIONS Three types of damper sections are available, all with opposed blade operation. - internal face and by-pass - external face and by-pass - shutoff The internal by-pass damper is used with a small face area coil, and the external by-pass damper is used with a large face area coil. In both cases, damper blades modulate the air volume through the coil and by-pass for temperature control. The shutoff damper controls the amount of air through the coil or shuts it off completely. The damper blades used in these sections are not designed for airtight shutoff, but rather for modulations; therefore, a 5 to 10% leakage rate is to be expected. On applications where a 1 to 3% maximum leakage rate is required, ROSEMEX offers a low-leak blade as an option. A specially designed gasket is fastened to the blades, thus ensuring a tight, permanent closure. All damper blade center shafts rotate in nylon bushings. HUMIDIFIERS STEAM GRID TYPE: Consists of a copper tube with steam jets, wrapped with a liner held in place by copper fasteners. Humidity is absorbed by the air from steam coming out of the saturated liner. Installed in the blower section. NOTE: Weights of condensate given in the tables are for total steam delivery. HOODED WATER SPRAY (TARGET) TYPE: Non-clogging brass nozzles spray atomized water on galvanized steel targets. The air absorbs humidity as it flows through an aluminized wire and fiberglass hood covering the steel targets. At air velocities below,5 m/s (500 FPM), the humidifier may be installed in the blower section. From,5 m/s (500 FPM) up, the humidifier must be installed in a separate section with eliminators to prevent water droplets from being carried into the airstream. Eliminator blades, streamlined in design, are extruded from a thermosetting, rot-resisting plastic having a low water-absorbing coefficient. This makes possible a high degree of efficiency combined with a minimum resistance to the air flow. The galvanized steel drain pan with threaded connection is easily removable for cleaning. It is recommended that the spray water temperature be F higher than the dew point of air to get an acceptable efficiency. The use of unheated water is not at all recommended. NOTE: Weights of water given in tables are for water flow through nozzles.

6 5 PHYSICAL FEATURES FILTER SECTIONS ROSEMEX offers five different types: - low capacity flat filter section - medium capacity angle bank filter section - high capacity angle bank filter section - high efficiency standard capacity bag filter section MULTIZONE OR DUAL DUCT HEAD Multizone or Dual Duct head is available in 18 sizes (from to 15-O). The Multizone head includes fully gasketed zone dampers. When dampers are supplied, ROSEMEX can install the necessary linkages and mechanisms to meet on-the-job requirements, while Dual Duct head has no dampers. Factoryinstalled perforated plates are used to balance hot and cold deck pressures. - high efficiency high capacity bag filter section Standard dimension mm ( ) thick filters are used in above first three; they may be throwaway, replaceable core or permanent filters. When using bag filters, it is advisable to pre-filter the air with mm ( ) flat filters. Slots to this effect are standard in all bag filter sections. All five models come with a hinged access door for easy servicing. MIXING BOXES Three types of mixing boxes are available for use with the CLIMATAIR series: - standard mixing box - combination mixing box with filters - Anti-Strata mixing box STANDARD MIXING BOX Using interconnected parallel blade dampers, this section will modulate and thoroughly mix any proportion of recirculated and fresh air. COMBINATION MIXING BOX WITH FILTERS Ideal arrangement where space is at a premium. The filtering surface is the same as that of the medium angle bank filter section. Flat mm ( ) thick standard-sized filters are used. A large hinged access door is supplied on this section. On low and medium pressure units to, Multizone sections are bolted to the blower. On all other sizes, including all high pressure units, a flexible connection is used. ANTI-STRATA MIXING BOX For applications where the quality of the air mixture must be excellent, ROSE- MEX has designed the Anti-Strata. A combination of dampers and partitions, incorporated inside the casing, allow alternate narrow streams of warm and cold air to meet and thoroughly mix. A diffuser plate, mounted at the outlet, further reduces the temperature gradient so that the risk of coil freeze-up is really at a minimum. This section is also supplied with a large hinged access door.

7 6 PHYSICAL FEATURES AIR WASHERS As its name implies, this unit removes dust and dirt from the air. It is also used to cool, heat, humidify and dehumidify the air. ROSEMEX manufactures three types of air washers: SPRAY CHAMBER This unit consists of a 7 mm (18 ) high water tank, fabricated from 5 mm (3/16 ) thick, all-welded steel plates, coated inside and out with a red oxide primer to prevent corrosion. A heavy asphalt type coating is applied inside the tank and a coat of black enamel covers the red oxide outside the tank. Over this tank is mounted a galvanized steel casing, inside which spray trees are erected, supporting evenly distributed non-clogging brass nozzles. Through intimate contact between the atomized water and the air stream, the air is either cooled, heated or humidified according to requirements. A bank of highly efficient galvanized eliminator blades is mounted at the outlet to prevent carry-over. Available lengths are 119 mm ( ) model D, mm ( ) model 6D, and 86 mm ( ) model 8DU. Inside surfaces vary from 1,1 m (1 sq. ft) to 8,1 m ( sq. ft.). WET PAD EVAPORATIVE COOLER SPRAYED COIL With the integrated copper-finned cooling coils, this unit cools and de-humidifies the air. It can also be used for humidification during winter or evaporative cooling during mid-seasons without operating the cooling coils. Spray nozzles are mounted on horizontal headers; casing is galvanized steel, and the water tank is the same construction as in the spray chamber, but only 5 mm (1 ) deep. Coils incorporate the same features as standard coils, but copper fins are used. Where water is alkaline, 6 FPI is recommended to prevent clogging between fins. The Mark Kool is an evaporative cooler utilizing impregnated cellulose paper or glass fiber evaporative pads to achieve high cooling efficiencies. Intimate contact between air and water is obtained as the air stream flows through the wet cross-fluted pads. These pads are made of either cellulose paper impregnated with insoluble anti-rot salts and rigidifying saturants, or of large glass fibers bound together by inorganic noncrystalline fillers. Their design generates the necessary turbulence for efficient contact between water and air. With the addition of chilled water or refrigerant coils, this unit will also cool and dehumidify. The entire casing is made of galvanized steel. Tank construction is the same as that used in others types of air washers; it is 5 mm (1 ) deep for the recirculating type, and only 10 mm ( ) deep if the water is not recirculated.

8 7 APPLICATION AIR FRICTION LOSS IMPERIAL S (in. H O) COIL VELOCITY (FPM) THROWAWAY FLAT DISP. CORE CAPACITY FILTER / PERMANENT THROWAWAY STANDARD ANGLE DISP.CORE EFFICIENCY CAPACITY FILTER / FILTER PERMANENT THROWAWAY ANGLE DISP. CORE CAPACITY FILTER / PERMANENT MIXING BOXES STANDARD ANTI-STRATA DAMPER ELIMINATOR PLENUM MULTIZONE MZ FILTER VELOCITY (FPM) THROWAWAY PRE DISP. CORE FILTER / OR PERMANENT EFFICIENCY HP-15 FILTER CAPACITY FINAL HP- FILTER HP SI S (Pa) COIL VELOCITY (m/s) THROWAWAY FLAT DISP. CORE CAPACITY FILTER / PERMANENT THROWAWAY STANDARD ANGLE DISP.CORE EFFICIENCY CAPACITY FILTER / FILTER PERMANENT THROWAWAY ANGLE DISP. CORE CAPACITY FILTER / PERMANENT MIXING BOXES STANDARD ANTI-STRATA DAMPER ELIMINATOR PLENUM MULTIZONE MZ FILTER VELOCITY (m/s) THROWAWAY PRE DISP. CORE FILTER / OR PERMANENT EFFICIENCY HP-15 FILTER CAPACITY FINAL HP- FILTER HP

9 8 IMPERIAL S PHYSICAL DATA FILTER SECTIONS COILS FAN SECTION (LB) O.D.P. MOTOR 1800 RPM NOM. EFFICIENCY STANDARD EFFICIENCY PRESSURE VARIMARK II PRESSURE VARIMARK II PRESSURE VARIMARK II LESS MOTOR HEATING AND COOLING HEATING LAMILINE CAPACITY FLAT FILTER BOX CAPACITY ANGLE FILTER BOX AND MIXING BOX CAPACITY ANGLE FILTER BOX CAPACITY FILTER BOX CAPACITY FILTER BOX DAMPERS PLENUMS FC BI, AS-AD FC BI, AS-AD AS-AD FULL FACE SMALL FACE MZ LLW-H LLS-H LLS-V FILTERS FILTERS FILTERS PRE FILTERS BAG FILTERS C/W FILTERS PRE FILTERS BAG FILTERS QTY-DIA. SQ. FT. QTY-DIA. SQ. FT. QTY-DIA. SQ. FT. QTY-DIA. SQ. FT. QTY-DIA. SQ. FT. PRESSURE PRESSURE PRESSURE HP MAXIMUM FRAME SHAFT DIAMETER STANDARD POSITION SQ. FT. CONN. QTY SQ. FT. CONN. QTY SQ. FT. CONN. QTY SQ. FT. CONN. QTY SQ. FT. CONN. QTY SQ. FT. THROWAWAY PERMANENT SQ. FT. THROWAWAY PERMANENT THROWAWAY PERMANENT SQ. FT. THROWAWAY PERMANENT AT 500 FPM SQ./FT. ADAPTORS 1 ADAPTOR AT 500 FPM SQ. FT. ADAPTORS C/W FILTERS 1 ADAPTOR ANTI-STRATA MIXING BOX SHUTOFF INTERNAL EXTERNAL ELIMINATOR ELIMINATOR / HUMIDIFIER ACCESS SPACER CSAH MVT MULTIZONE MZ -A T OUT 1-18 x x x x x x x x T OUT 1- x x x x x x x x 0-0 x x 5-0 x x C T OUT 1- x x x x x x x x 5-0 x x x x x - x T OUT 1- x x x x x x 0-16 x x x x x - x T OUT 1- x x x x x x x x x T OUT 1- x x x x x x x x x x x x x - x x T OUT 1- x x x x x x 0-0 x x x x x x x - x T OUT 1- x x x x x x 0-16 x x x x x x x 3- x T OUT 1- x x x x x x 0-0 x x x x 0-0 x x - x x T OUT 1- x x x x x x x 0-0 x 0-0 x x x x x 6- x FC: Forward curved blades BI: Backwardly inclined blades AS-AD: Airfoil blades

10 9 PHYSICAL DATA IMPERIAL S FILTER SECTIONS COILS FAN SECTION (LBS) O.D.P. MOTOR 1800 RPM NOM. EFFICIENCY STANDARD EFFICIENCY PRESSURE VARIMARK II PRESSURE VARIMARK II PRESSURE VARIMARK II LESS MOTOR HEATING AND COOLING HEATING LAMILINE CAPACITY FLAT FILTER BOX CAPACITY ANGLE FILTER BOX AND MIXING BOX CAPACITY ANGLE FILTER BOX CAPACITY FILTER BOX CAPACITY FILTER BOX DAMPERS PLENUMS QTY-DIA. FC SQ. FT. QTY-DIA. BI, AS-AD SQ. FT. QTY-DIA. FC SQ. FT. QTY-DIA. BI, AS-AD SQ. FT. QTY-DIA. AS-AD SQ. FT. PRESSURE PRESSURE PRESSURE HP MAXIMUM FRAME SHAFT DIAMETER STANDARD POSITION FULL FACE SQ. FT. CONN. QTY SMALL FACE SQ. FT. CONN. QTY MZ SQ. FT. CONN. QTY LLW-H LLS-H LLS-V FILTERS FILTERS FILTERS PREFILTERS BAGFILTERS C/W FILTERS PRE FILTERS BAG FILTERS SQ. FT. CONN. QTY SQ. FT. CONN. QTY SQ. FT. THROWAWAY PERMANENT SQ. FT. THROWAWAY PERMANENT THROWAWAY PERMANENT SQ. FT. THROWAWAY PERMANENT AT 500 FPM SQ. FT. ADAPTORS 1 ADAPTOR AT 500 FPM SQ. FT. ADAPTORS C/W FILTERS 1 ADAPTOR ANTI-STRATA MIXING BOX SHUTOFF INTERNAL EXTERNAL ELIMINATOR ELIMINATOR / HUMIDIFIER ACCESS SPACER CSAH MVT MULTIZONE MZ T OUT 1- x x x x x x 0-0 x 0-16 x 5-0 x x x x 0-0 x x - x x T.15 0 OUT 1- x x x x x x x x x x x x x T INS 1- x x x x x x x x x x x x x x 8- x IDENTIFICATION: MODEL MVT FAN BI PRESSURE LP T INS 1-7 x 8 1- x x x x x x x x 0-0 x x x 8- x T.3 7 INS 1- x 1- x x 1- x x x x x 0-0 x x 5-0 x x x x x x 9- x x 1- x L T.8 95 INS 1- x x x x x x x x x x x x x T.8 95 INS - x x x x x x x x x x x x x 15- x N T INS - x x x x x x 5 1- x x x 0-16 x x x x x x x x O T INS 1- x 1 1- x x 1 1- x x x 1 1- x x x x x x x x x 0-0 x x

11 10 SI S PHYSICAL DATA -A T OUT 1-7x x x x x x x x T 3.9 OUT 1-609x x x x x x635 1-x x x x C T 3.9 OUT 1-76x x x x x x635 1-x x635 -x x 3-x x x -x T 3.9 OUT 1-76x x x x x x -06x x 3-06x x x -x T.1 98 OUT 1-609x x x x x x x x x T OUT 1-x x x x x x 1-x 1-06x635 1-x x 3-x x x -x x T OUT 1-9x x x x x x -06x x 3-x x635 3-x x x -x T OUT 1-76x x x x x x -06x x 6-06x x 6-x x x 3-x T OUT 1-9x x x x x x -x x 6-x x 8-x x -x x T OUT -609x.0 1-x x x x x x -x -x x 10-x x x 6-x m 3 /s QTY-DIA. m QTY-DIA. m QTY-DIA. m QTY-DIA. m QTY-DIA. m FC BI, AS-AD FC BI, AS-AD AS-AD PRESSURE VARIMARK II PRESSURE VARIMARK II PRESSURE VARIMARK II LESS MOTOR PRESSURE PRESSURE PRESSURE HP MAXIMUM FRAME SHAFT DIAMETER STANDARD POSITION m CONN. QTY m CONN. QTY m CONN. QTY m CONN. QTY m m CONN. QTY m THROWAWAY PERMANENT m THROWAWAY PERMANENT THROWAWAY PERMANENT m THROWAWAY PERMANENT m 3 /s AT.5 m/s m 3 /s AT.5 m/s ANTI-STRATA MIXING BOX SHUTOFF INTERNAL EXTERNAL ELIMINATOR ELIMINATOR / HUMIDIFIER ACCESS SPACER CSAH MVT MULTIZONE MZ m ADAPTORS 1 ADAPTOR m ADAPTORS 1 ADAPTOR DAMPERS PLENUMS (kg) EFFICIENCY STANDARD EFFICIENCY COILS FAN SECTION O.D.P. MOTOR 1800 RPM NOM. FILTER SECTIONS FILTERS FILTERS FILTERS FULL FACE SMALL FACE MZ LLW-H LLS-H LLS-V HEATING AND COOLING HEATING LAMILINE CAPACITY FLAT FILTER BOX CAPACITY ANGLE FILTER BOX AND MIXING BOX CAPACITY ANGLE FILTER BOX CAPACITY FILTER BOX CAPACITY FILTER BOX PRE FILTERS BAG FILTERS C/W FILTERS PRE FILTERS BAG FILTERS C/W FILTERS FC: Forward curved blades BI: Backwardly inclined blades AS-AD: Airfoil blades

12 11 PHYSICAL DATA SI S IDENTIFICATION: MODEL MVT FAN BI PRESSURE LP T OUT 1-x x x x x x -x -06x635 -x x -x x -x x -x x T OUT 1-10x x x x x x 5-x x 6-x x x x T 53.9 INS x x x x x x x635 6-x x 1-x x635 1-x x x 8-x T 53.9 INS x1 1-76x x x x x x 3-x x -x x x -x T INS. 1-76x86 1-x x x x x x x -x 6-06x635 -x x 10-x x 1-x x 9-x x 1-x L T INS. 1-76x5 1-X x X X x x x 10-x x x x x T INS. 1-X x x X x x x 15-06x x 1-x x 16-x x x 15-x N T INS. -10x x x x0 1-x x x x 15-x -06x635 3-x x 6-x x 8-x x x O T INS. 1-76x 1-x x 1-76x x.31 1-x x x x 6-x635 9-x 9-x x 18-x x -x x m 3 /s QTY-DIA. m QTY-DIA. m QTY-DIA. m QTY-DIA. m QTY-DIA. m FC BI, AS-AD FC BI, AS-AD AS-AD PRESSURE VARIMARK II PRESSURE VARIMARK II PRESSURE VARIMARK II LESS MOTOR PRESSURE PRESSURE PRESSURE HP MAXIMUM FRAME SHAFT DIAMETER STANDARD POSITION m CONN. QTY m CONN. QTY m CONN. QTY m CONN. QTY m CONN. QTY m THROWAWAY PERMANENT m THROWAWAY PERMANENT THROWAWAY PERMANENT m THROWAWAY PERMANENT m 3 /s AT.5 m/s m 3 /s AT.5 m/s ANTI-STRATA MIXING BOX SHUTOFF INTERNAL EXTERNAL ELIMINATOR ELIMINATOR / HUMIDIFIER ACCESS SPACER CSAH MVT MULTIZONE MZ m ADAPTORS 1 ADAPTOR m ADAPTORS 1 ADAPTOR DAMPERS PLENUMS (kg) EFFICIENCY STANDARD EFFICIENCY COILS FAN SECTION O.D.P. MOTOR 1800 RPM NOM. FILTER SECTIONS FILTERS FILTERS FILTERS FULL FACE SMALL FACE MZ LLW-H LLS-H LLS-V HEATING AND COOLING HEATING LAMILINE CAPACITY FLAT FILTER BOX CAPACITY ANGLE FILTER BOX AND MIXING BOX CAPACITY ANGLE FILTER BOX CAPACITY FILTER BOX CAPACITY FILTER BOX PREFILTERS BAGFILTERS C/W FILTERS PRE FILTERS BAG FILTERS C/W FILTERS

13 1 -A IMPERIAL DATA PERFORMANCE PRESSURE 9 F BER OUTLET AREA: 0.8 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP A - FULL FACE B - SMALL FACE C- MZ

14 13 PERFORMANCE IMPERIAL DATA PRESSURE 1 F BER OUTLET AREA: 1.6 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 1 BI BER OUTLET AREA: 1. SQ. FT AS BER OUTLET AREA: 1. SQ. FT PRESSURE 10 F BER OUTLET AREA: 1.03 SQ. FT COIL VELOCITY 1.50 S.P. 1. S.P..00 S.P..5 S.P..50 S.P.. S.P S.P S.P..00 S.P. 1 BI BER OUTLET AREA: 1. SQ. FT COIL VELOCITY 3.00 S.P. 3.5 S.P S.P. 3. S.P..00 S.P..5 S.P..50 S.P S.P S.P. 1 AS BER OUTLET AREA: 1. SQ. FT A - FULL FACE B - SMALL FACE C- MZ

15 1 -C IMPERIAL DATA PERFORMANCE PRESSURE 15 F BER OUTLET AREA:.05 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 15 BI BER OUTLET AREA:. SQ. FT AS BER OUTLET AREA:. SQ. FT PRESSURE 1 F BER OUTLET AREA: 1.6 SQ./FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 13 BI BER OUTLET AREA: 1. SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 13 AS BER OUTLET AREA: 1. SQ. FT A - FULL FACE B - SMALL FACE C- MZ

16 15 PERFORMANCE IMPERIAL DATA PRESSURE 15 F BER OUTLET AREA:.05 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 15 BI BER OUTLET AREA:. SQ. FT AS BER OUTLET AREA:. SQ. FT PRESSURE 1 F BER OUTLET AREA: 1.6 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 15 BI BER OUTLET AREA:. SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 15 AS BER OUTLET AREA:. SQ. FT A - FULL FACE B - SMALL FACE C- MZ

17 16 IMPERIAL DATA PERFORMANCE PRESSURE 1 F BERS OUTLET AREA:.9 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 1 BI BERS OUTLET AREA: 3.1 SQ. FT AS BERS OUTLET AREA: 3.1 SQ. FT PRESSURE 10F BERS OUTLET AREA:.03 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP A - FULL FACE B - SMALL FACE C- MZ

18 17 PERFORMANCE IMPERIAL DATA PRESSURE 18 F BER OUTLET AREA:. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA: 3.50 SQ. FT AS BER OUTLET AREA: 3.50 SQ. FT PRESSURE 15 F BER OUTLET AREA:.05 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 16 BI BER OUTLET AREA:.86 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 16 AS BER OUTLET AREA:.86 SQ. FT PRESSURE 15 AS BER OUTLET AREA:. SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

19 18 IMPERIAL DATA PERFORMANCE PRESSURE 0 F BER OUTLET AREA:.5 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA:.19 SQ. FT AS BER OUTLET AREA:.19 SQ. FT PRESSURE 18 F BER OUTLET AREA:. SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 18 BI BER OUTLET AREA: 3.50 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 18 AS BER OUTLET AREA: 3.50 SQ. FT PRESSURE 16 AS BER OUTLET AREA:.86 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

20 19 PERFORMANCE IMPERIAL DATA PRESSURE 15F BERS OUTLET AREA:.10 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 15 BI BERS OUTLET AREA:.7 SQ. FT AS BERS OUTLET AREA:.7 SQ. FT PRESSURE 1F BERS OUTLET AREA:.9 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 13 BI BERS OUTLET AREA: 3.86 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 13 AS BERS OUTLET AREA: 3.86 SQ. FT A - FULL FACE B - SMALL FACE C- MZ

21 0 IMPERIAL DATA PERFORMANCE PRESSURE F BER OUTLET AREA: 5.16 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA: 5.18 SQ. FT AS BER OUTLET AREA: 5.18 SQ. FT PRESSURE 0 F BER OUTLET AREA:.5 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 0 BI BER OUTLET AREA:.19 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 0 AS BER OUTLET AREA:.19 SQ. FT PRESSURE 18 AS BER OUTLET AREA: 3.50 SQ./FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

22 1 PERFORMANCE IMPERIAL DATA PRESSURE 5 F BER OUTLET AREA: 6.78 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA: 6.7 SQ. FT AD BER OUTLET AREA: 6.7 SQ. FT PRESSURE 0 F BER OUTLET AREA:.5 SQ. FT COIL VELOCITY 1.50 S.P. 1. S.P..00 S.P..5 S.P..50 S.P.. S.P S.P S.P..00 S.P. BI BER OUTLET AREA: 5.18 SQ. FT COIL VELOCITY 3.00 S.P. 3.5 S.P S.P. 3. S.P..00 S.P..5 S.P..50 S.P S.P S.P. AS BER OUTLET AREA: 5.18 SQ. FT PRESSURE 0 AS BER OUTLET AREA:.19 SQ. FT COIL VELOCITY 5.00 S.P S.P S.P S.P S.P S.P S.P S.P S.P A - FULL FACE B - SMALL FACE C- MZ

23 IMPERIAL DATA PERFORMANCE PRESSURE 18 F BERS OUTLET AREA: 5.7 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 18 BI BERS OUTLET AREA: 7.0 SQ. FT AS BERS OUTLET AREA: 7.0 SQ. FT PRESSURE 15 F BERS OUTLET AREA:.10 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 16 BI BERS OUTLET AREA: 5.7 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 16 AS BERS OUTLET AREA: 5.7 SQ. FT A - FULL FACE B - SMALL FACE C- MZ

24 3 PERFORMANCE IMPERIAL DATA PRESSURE 0 F BERS OUTLET AREA: 8.50 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 0 BI BERS OUTLET AREA: 8.38 SQ. FT AS BERS OUTLET AREA: 8.38 SQ. FT PRESSURE 18 F BERS OUTLET AREA: 5.7 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 18 BI BERS OUTLET AREA: 7.0 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 18 AS BERS OUTLET AREA: 7.0 SQ. FT A - FULL FACE B - SMALL FACE C- MZ

25 IMPERIAL DATA PERFORMANCE PRESSURE 7 F BER OUTLET AREA: 8. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA: 7.60 SQ. FT AD BER OUTLET AREA: 7.60 SQ. FT PRESSURE 5 F BER OUTLET AREA: 6.78 SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP BI BER OUTLET AREA: 6.7 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP AD BER OUTLET AREA: 6.7 SQ. FT PRESSURE AS BER OUTLET AREA: 5.18 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

26 5 PERFORMANCE IMPERIAL DATA PRESSURE F BER OUTLET AREA: 9.38 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP BI BER OUTLET AREA: 9.3 SQ. FT AD BER OUTLET AREA: 9.3 SQ. FT PRESSURE 7 F BER OUTLET AREA: 8. SQ. FT COIL VELOCITY 1.50 SP 1. SP.00 SP.5 SP.50 SP. SP 3.00 SP 3.50 SP.00 SP 7 BI BER OUTLET AREA: 7.60 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 7 AD BER OUTLET AREA: 7.60 SQ. FT PRESSURE AD BER OUTLET AREA: 6.7 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

27 6 IMPERIAL DATA PERFORMANCE A - FULL FACE B - SMALL FACE C- MZ PRESSURE BI BER OUTLET AREA: 11. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP AD BER OUTLET AREA: 11. SQ. FT PRESSURE BI BER OUTLET AREA: 9.3 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP AD BER OUTLET AREA: 9.3 SQ. FT PRESSURE 7 AD BER OUTLET AREA: 7.60 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP

28 1-L 7 PERFORMANCE IMPERIAL DATA PRESSURE BI BER OUTLET AREA: 13. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP AD BER OUTLET AREA: 13.9 SQ. FT PRESSURE BI BER OUTLET AREA: 11. SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP AD BER OUTLET AREA: 11. SQ. FT PRESSURE AD BER OUTLET AREA: 9.3 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP A - FULL FACE B - SMALL FACE C- MZ

29 8 IMPERIAL DATA PERFORMANCE A - FULL FACE B - SMALL FACE C- MZ PRESSURE 0 BI BER OUTLET AREA: 16. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 0 AD BER OUTLET AREA: 16. SQ. FT PRESSURE BI BER OUTLET AREA: 13.9 SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP AD BER OUTLET AREA: 13.9 SQ. FT PRESSURE AD BER OUTLET AREA: 11. SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP

30 1-N 9 PERFORMANCE IMPERIAL DATA PRESSURE BI BER OUTLET AREA: 0. SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP AD BER OUTLET AREA: 0. SQ. FT A - FULL FACE B - SMALL FACE C- MZ PRESSURE 0 BI BER OUTLET AREA: 16. SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP 0 AD BER OUTLET AREA: 16. SQ. FT PRESSURE AD BER OUTLET AREA: 13.9 SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP

31 15-O IMPERIAL DATA PERFORMANCE A - FULL FACE B - SMALL FACE C- MZ PRESSURE 9 BI BER OUTLET AREA: 6.9 SQ. FT COIL VELOCITY 0.50 SP 0. SP 1.00 SP 1.5 SP 1.50 SP 1. SP.00 SP.50 SP 3.00 SP 9 AD BER OUTLET AREA: 6.9 SQ. FT PRESSURE BI BER OUTLET AREA: 0. SQ. FT COIL VELOCITY 3.00 SP 3.5 SP 3.50 SP 3. SP.00 SP.5 SP.50 SP 5.00 SP 5.50 SP AD BER OUTLET AREA: 0. SQ. FT PRESSURE 0 AD BER OUTLET AREA: 16. SQ. FT COIL VELOCITY 5.00 SP 5.50 SP 6.00 SP 6.50 SP 7.00 SP 7.50 SP 8.00 SP 9.00 SP SP

32 31 AIR DISCHARGE - MOTOR POSITIONS CW MOTOR POSITIONS CCW AIR INTAKE AIR AIR AIR DISCHARGE INTAKE DISCHARGE TH DB T* B L R* L NA NA NA NA NA T* B R L* R TH DB MVT T NA T B* NA B* MVT BH UB T R L* R B NA NA NA NA NA T L R* L B BH UB TH B** NA B** L NA NA R TH B** NA B** BH BH R NA NA L CSAH CSAH B** NA B** UB R L* NA NA NA NA L R* UB MZ BH R NA NA NA L T NA NA NA T BH MZ NOTES 1) All information is given facing drive side. ) Maximum motor sizes when installed in position ➀ on -blower models are: : 10 HP : 10 HP : 5 HP : HP 3) Motor mounted inside blower section (position ➄) only on units to 15-O. * Plenum spacer required at air intake. Dimensions as per unit selected. ** plenum required at air intake. Dimensions as per unit selected. Blower identification: MVT-CW-TH-B-

33 3 CSAH -A TO FAN SECTION NOTE: DEPTHS OF HEATING COIL SEC- TIONS ARE AS FOLS: 1- ROWS: 17 mm (5 ) 3- ROWS: 03 mm (8 ) COOLING COILS ARE ALWAYS 356 mm (1 ) DEEP 5 1/ x 7 1/ (10 mm x 1 mm) ACCESS DOOR IS OPTIONAL * BI, high pressure models, not available. Dimensions refers to CSAH and MVT. -A -C PRESSURE A B 7 C D 18 E F G H F * * * * G * * * * H * * * * J K FC BI, AS-AD IMPERIAL S (in.)

34 FAN SECTION MVT -A TO NOTE: DEPTHS OF HEATING COIL SEC- TIONS ARE AS FOLS: 1- ROWS: 17 mm (5 ) 3- ROWS: 03 mm (8 ) COOLING COILS ARE ALWAYS 356 mm (1 ) DEEP 5 1/ x 7 1/ (10 mm x 1 mm) ACCESS DOOR IS OPTIONAL * BI, high pressure models, not available. Dimensions refers to CSAH and MVT. -A -C PRESSURE A B C D E F G H F G H J K FC BI, AS-AD SI S (mm)

35 3 FAN SECTION MVT AND CSAH TO 15-O NOTE: DEPTHS OF HEATING COIL SECTIONS ARE AS FOLS: 1- ROWS: 17mm (5 ) 3- ROWS: 03mm (8 ) COOLING COILS ARE ALWAYS 356 mm (1 ) DEEP. * BH arr. not available on low pressure 15-O unit.

36 35 MVT AND CSAH TO 15-O FAN SECTION SI S (mm) * BH arr. not available on low pressure 15-O unit. IMPERIAL S (in.) 1-L 1-N 15-O PRESSURE A B C D E F G H J K L H J K L FC BI, AS - AD 1-L 1-N 15-O PRESSURE A B C D E F G H J K L H J K L FC BI, AS - AD

37 ELIMINATOR SECTION AND HUMIDIFIERS ➁ ➀ ELIMINATOR (USED OVER,5 m/s (500 FPM)) ➁ WATER SPRAY HUMIDIFIER SECTION (USED OVER,5 m/s (500 FPM)) ➀ SI S (mm) -A -C 1-L 1-N 15-0 A B C D IMPERIAL S (in.) A B C D -A -C 1-L 1-N

38 37 DAMPER SECTIONS ➀ ➁ ➀ SHUTOFF ➁ INTERNAL ➂ EXTERNAL ➂ SI S (mm) IMPERIAL S (in.) -A A 5 B C 7 D E 1 F 7 G 0 H 6 -A A 1 B 7 C 18 D E 7 1/ F 8 1/ G 13 H 5 1/ / 3 1/ / -C C 7 1/ 0 1/ / / 0 1/ / / 3 1/ / / / / 0 1/ / / / / / / / / 1-L L / / 1-N N / /

39 38 PLENUMS -A -C 1-L 1-N 15-0 A B C D E F G H A -C 1-L 1-N 15-0 A B C D E F G H SI S (mm) IMPERIAL S (in.) ➀ ACCESS ➁ SPACER ➂ SUPPORT ➃ MVT ➄ CSAH ➀ ➄ ➃ ➂ ➁

40 FILTER SECTIONS -A -C 1-L 1-N 15-0 A B C D E F A -C 1-L 1-N 15-0 A B C D E F SI S (mm) IMPERIAL S (in.) ➀ ➁ ➂ ➂ ➁ ➀

41 0 MIXING BOXES - STANDARD -A -C 1-L 1-N 15-0 A B C D E F G H A -C 1-L 1-N 15-0 A B C D E F 11 1/ G H 5 1/ 37 1/ 37 1/ 9 1/ 67 1/ 9 1/ 55 1/ 73 1/ 67 1/ 67 1/ 91 1/ 103 1/ SI S (mm) IMPERIAL S (in.) INLET POSITIONS TOP-REAR -A TO 15-O TOP-BOTTOM -A TO REAR-BOTTOM -A TO MVT -A to CSAH -A to MVT and CSAH to 15-O

42 1 MIXING BOXES - ANTI-STRATA MVT -A to INLET POSITIONS REAR-REAR -A TO 15-O TOP-REAR -A TO 15-O TOP-BOTTOM -A TO CSAH -A to MVT and CSAH to 15-O REAR-BOTTOM -A TO SI S (mm) IMPERIAL S (in.) -A A 5 B C 889 D 7 E F 03 G 711 H 6 -A A 1 B 7 C 35 D 18 E F 8 G 8 H 5 1/ / -C C / / / / / / / / 67 1/ / / 103 1/ L L N N

43 BAG FILTER SECTIONS - TYPE I -A -C 1-L 1-N 15-O A B C D E F 76 G H 711 J A B C D E F G H J CAPACITY CAPACITY SI (mm) ARRANGEMENT MVT -A to CSAH -A to MVT and CSAH to 15-O

44 3 BAG FILTER SECTIONS - TYPE II MVT -A to ARRANGEMENT CSAH -A to MVT and CSAH to 15-O IMPERIAL S (in.) -A -C 1-L 1-N 15-O A 7 1/ 7 1/ 1/ 7 1/ 1/ 1/ 1/ 5 1/ 1/ 63 3/ 3/ 3/ B C 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ / 7 3/ 7 3/ CAPACITY D E F G H J 5 1/ 9 1/ 9 1/ 9 1/ 73 1/ 9 1/ 55 1/ 73 1/ 67 1/ 73 1/ 97 1/ 103 1/ A 1/ 1/ 1/ 1/ 1/ 63 3/ 1/ 1/ 63 3/ 3/ 3/ 88 B C 1/ 1/ 1/ 1/ 1/ 60 3/ 1/ 1/ 60 3/ 7 3/ 7 3/ D CAPACITY E F G H J 9 1/ 9 1/ 61 1/ 73 1/ 73 1/ 73 1/ 97 1/ 11 1/

45 MULTIZONE OR DUAL DUCT HEAD -A -C 1-L 1-N 15-O A B C D E F G H J A B C D E F G H J 37 1/ 37 1/ 9 1/ 67 1/ 9 1/ 55 1/ 73 1/ 67 1/ 67 1/ 91 1/ 103 1/ 79 1/ 85 1/ 91 1/ 103 1/ 115 1/ 17 1/ 10 1/ SI S (MM) IMPERIAL S (IN.) VERTICAL OUTLET ARRANGEMENT ARRANGEMENTS to to 15-O QTY

46 AIR WASHERS SPRAYED COIL ACCESS PLENUM SI S (mm) -A -C 1-L 1-N 15-0 A B C D C IMPERIAL S A B C D -A -C 1-L 1-N / 6 1/ 6 1/ 0 1/ 5 1/ 55 1/ 6 1/ 55 1/ 6 1/ 5 1/ 58 1/ 70 1/ 76 1/ 8 1/ 88 1/ 97 1/ 103 1/ 106 1/

47 6 AIR WASHERS SPRAY CHAMBER MODEL D MODEL 6D MODEL 8DU SI S (mm) -A -C 1-L 1-N 15-0 A B C D IMPERIAL S A B C D -A -C 1-L 1-N / 9 1/ 9 1/ 3 1/ 55 1/ 61 1/ 9 1/ 61 1/ 70 1/ 55 1/ 6 1/ 73 1/ 79 1/ 85 1/ 91 1/ 103 1/ 109 1/ 109 1/

48 7 AIR WASHERS MARK KOOL NON RECIRCULATING TYPE RECIRCULATING TYPE WITH COILS SI S (mm) -A -C 1-L 1-N 15-0 A B C D IMPERIAL S (in.) -A -C 1-L 1-N 15-0 A PG B C D / 5 1/ 37 1/ 3 1/ 31 1/ 3 1/ 5 1/ 37 1/ 6 1/ 55 1/ 61 1/ 67 1/ 73 1/ 85 1/ 91 1/ 91 1/

49 ACCESS DOORS Access doors are supplied on all blower sections, and are available on all access plenums. 10 mm x 1 mm (5 1/ x 7 1/) doors are single thickness, gasketed sheet steel fastened at the corners. All larger sizes are hinged, insulated sandwich-type doors. SI S (mm) -A -C 1-L 1-N A -C 1-L 1-N 15-0 FC 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 x 119 x 119 IMPERIAL S (in.) FC 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 7 x 7 x FAN SECTION PLENUMS PRESSURE PRESSURE PRESSURE WIDTH BI, AS- AD 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x x 6 x 119 x 119 x 119 x 119 x 15 x 15 x 15 FAN SECTION PLENUMS PRESSURE PRESSURE PRESSURE WIDTH BI, AS-AD 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 1 x 5 1/ 7 x 7 x 7 x 7 x 7 x 60 7 x 60 7 x 60 FC 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 x 119 x 119 FC 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 7 x 7 x BI, AS-AD 10 x 1 10 x 1 10 x 1 10 x 1 10 x 1 10 x x x 6 10 x x 6 x 119 x 119 x 119 x 119 x 15 x 15 x 15 BI, AS-AD 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 5 1/ x 7 1/ 1 x 5 1/ 1 x 5 1/ 5 1/ x 7 1/ 1 x 5 1/ 7 x 7 x 7 x 7 x 7 x 60 7 x 60 7 x 60 AS-AD 10 x x x 6 x 119 x 119 x 119 x 119 x 15 x 15 x 15 AS-AD 5 1/ x 7 1/ 1 x 5 1/ 1 x 5 1/ 7 x 7 x 7 x 7 x 7 x 60 7 x 60 7 x x x x 6 79 x 6 79 x x 6 79 x 6 79 x 6 79 x 6 79 x 6 79 x 6 79 x x x x 5 1/ 11 x 5 1/ 11 x x 5 1/ 11 x 5 1/ 11 x 5 1/ 11 x 5 1/ 11 x 5 1/ 11 x 5 1/ 11 x 5 1/ 7 79 x x x x 6 79 x x x x x x x x x x x x x x x x x 16 1 x 5 1/ 1 x 5 1/ 11 x 16 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 1 x 1 x 1 x 1 x 60 1 x 60 1 x x x x x 6 79 x x x x x x x x x x x x x x x x x 16 1 x 5 1/ 1 x 5 1/ 11 x 16 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 5 1/ 1 x 1 x 1 x 1 x 1 x 60 1 x 60 1 x 60

50 9 VARIMARK II The Varimark II control for VAV systems is easily adapted for use with the CLIMATAIR series. May be employed on all single-wheel BI, AS or AD models. Listed below are the clearances required by the Varimark II mechanism on the CLIMATAIR units with the motor outside the blower section. See tables below and fig. A. On large CLIMATAIR units with the motor inside the blower section, the Varimark II mechanism is also inside the section. See fig. B. DIMENSION X SI S (mm) -C BI PRESSURE MED AS-AD PRESSURE MED Fig. A IMPERIAL S (in.) -C BI PRESSURE MED. 16 1/ 16 1/ 16 1/ 16 1/ 16 1/ 16 1/ 17 1/ 17 1/ 18 1/ 17 1/ 18 1/ 18 1/ 19 1/ 18 1/ 16 1/ 16 1/ 16 1/ 17 1/ 18 1/ 18 1/ 19 1/ AS-AD PRESSURE MED. 16 1/ 16 1/ 16 1/ 17 1/ 17 1/ 18 1/ 18 1/ 16 1/ 17 1/ 17 1/ 18 1/ Fig. B

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

A Division of Nailor International Inc. ECONOMY AIR HANDLERS A Division of Nailor International Inc. MODEL : ECONOMY AIR HANDLERS Thermal Model Standard Specification MODEL 800-4000 CFM AIR HANDLERS Description Model air handlers are designed for efficient and economical

More information

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES

More information

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499] BC--1.0 03-01-1 Belt Drive Blower Coil Unit, Basic Unit Discharge ARGT. 1 4. See page 1 for filter rack details. 5. Base rail is optional on he base unit. See page 13. Base rails must be used with mixing

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-5 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR AIR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for difficult

More information

McQuay. Central Station Air Handlers Low Pressure. LHD, LYF, LSL, LML, LWL Vintage C. LML, LSB Vintage E. Last Manufactured: 1999

McQuay. Central Station Air Handlers Low Pressure. LHD, LYF, LSL, LML, LWL Vintage C. LML, LSB Vintage E. Last Manufactured: 1999 Replacement Parts List No. 055222600 Revision F 11/2011 McQuay Central Station Air Handlers Low Pressure LHD, LYF, LSL, LML, LWL 103-228 Vintage C LML, LSB 106-111 Vintage E Last Manufactured: 1999 To

More information

ARROW UNITED INDUSTRIES

ARROW UNITED INDUSTRIES IP-3R ARROW UNITED INDUSTRIES Building Tomorrow s Ventilation Today Heavy Duty Dampers Industrial, Power Plant & Commercial Applications ARROW UNITED INDUSTRIES has specialized in the design and manufacturing

More information

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM an ELTA GROUP company ELTAFANTECH 700 up to 42,000 CFM INNOVATIVE Design & Performance INTRODUCTION There are 24 standard sizes of optimally engineered s to handle air volumes from 700 CFM to 42,000CFM.

More information

BAC, BAF, BAH Central Station Air Handlers

BAC, BAF, BAH Central Station Air Handlers PRODUCT DATA & INSTALLATION Bulletin B80-BA-PDI-5 Part # 1097717 PRODUCT SUPPORT web: b-rp.ca/bah email: ahu@b-rp.ca call: 1-844-893-3222 x527 scan: BAC, BAF, BAH Central Station Air Handlers Indoor and

More information

AIR HANDLING UNIT. MODEL: PM0809 to PM CFM to CFM

AIR HANDLING UNIT. MODEL: PM0809 to PM CFM to CFM AIR HANDLING UNIT MODEL: PM0809 to PM2738 700CFM to 41000 CFM POWER METAL TECHNOLOGIES (M) SDN BHD Lot 37830, Jalan Bukit Naga, Kampung Bukit Naga, Section 32, 40460 Shah Alam, Selangor Darul Ehsan. Tel:

More information

50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS

50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS R FORM NO: MS0305F Products That Perform...By People Who Care AIR - COOLED SPLIT SYSTEM AIR CONDITIONERS WITH SCROLL COMPRESSORS 50 Hz COOLING CAPACITY- 60 MBH TO 1360 MBH ACCS SERIES HEB-D, EB-D SERIES

More information

ENGINEERED PRODUCTS. Project: Unit Tag: MS-80-D-3 Page 1 of 5

ENGINEERED PRODUCTS. Project: Unit Tag: MS-80-D-3 Page 1 of 5 ENGINEERED PRODUCTS Model - Unit Type (UT) - MS, Separated Combustion Indoor Unit Capacity (CA) - (50-80) (500-800 mbtu) Furnace Type (FT) - A, B Standard Temperature Rise (30-80)F Indoor Arrangement (IA)

More information

ARROW INDUSTRIAL PRODUCTS

ARROW INDUSTRIAL PRODUCTS IP-2R ARROW INDUSTRIAL PRODUCTS For Applications in Industrial, Power Plant & Commercial Projects ARROW UNITED INDUSTRIES ARROW UNITED INDUSTRIES has specialized in the manufacturing of air control products

More information

Nomenclature. Contents. Air Handling Unit SR AH 250 LP HS

Nomenclature. Contents. Air Handling Unit SR AH 250 LP HS SARAN Mf g. Group 1 Contents Features...... 2-4 Selection Procedures... 5-7 Capacity Ratings (Chilled Water, D.X Coil, Hot Water, Steam Ratings)... 8-15 Correction Factor Tables... 16-18 Dimensions (Horizontal

More information

Climas y Proyectos Leyco, S.A. de C.V.

Climas y Proyectos Leyco, S.A. de C.V. GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA

More information

Product Data. 39T Central Station Air-Handling Units. Features/Benefits. Nominal 3,500 to 46,000 Cfm

Product Data. 39T Central Station Air-Handling Units. Features/Benefits. Nominal 3,500 to 46,000 Cfm Product Data 39T Central Station Air-Handling Units Nominal 3,500 to 46,000 Cfm Features/Benefits Flanged and gasketed modular components units are available as a single assembly up to 40 ft long, or shipped

More information

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage D. LML, LSB, MMM, MSB Vintage E

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage D. LML, LSB, MMM, MSB Vintage E Replacement Parts List No. 046902100 Revision D 01/2015 McQuay Central Station Air Handler LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL 137-172 Vintage D LML, LSB, MMM, MSB 137-172 Vintage E Last Manufactured:

More information

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 model vp - belt drive utility set Application VENT-PAK fan wheels are the versatile, quiet, energy efficiency backward inclined

More information

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement SECTION MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement SECTION MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 73 13 MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions.

More information

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage C. Last Manufactured: 1984

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage C. Last Manufactured: 1984 Replacement Parts List No. 055222700 Revision D 0/205 McQuay Central Station Air Handler LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL 37-72 Vintage C Last Manufactured: 984 To find your Daikin Applied parts

More information

SPECIFICATIONS AND DESIGN ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE. EDITION 11

SPECIFICATIONS AND DESIGN ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE. EDITION 11 AIR HANDLING UNIT (DOUBLE SKIN) MODEL: DS-CW/DX-AHU-H (Chilled Water or Direct Expansion) CAPACITY: 3.3 to 125 Nominal Tons 39,000 to 1,500,000 BtuH 11.4 to 439.5 KW 1,300 to 50,000 CFM Benefits Horizontal

More information

TYPICAL SPECIFICATION: Critical Process Roof Top Unit 7/14/15

TYPICAL SPECIFICATION: Critical Process Roof Top Unit 7/14/15 UNIT CONSTRUCTION: Casing: A. 2.5 NTM (No Thru Metal Casing) 1. Base frame fabrication utilizes a single frame construction for supporting the casing and internal component. 2. The casing walls and roof

More information

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING PUB. NO. 732-3 DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING The most widely used dampers in commercial HVAC applications Control Dampers - Extruded Aluminum

More information

ELITE SERIES R-410A Ready - Multi-Position

ELITE SERIES R-410A Ready - Multi-Position PRODUCT SPECIFICATIONS AIR HANDLERS CBXM ELITE SERIES R-0A Ready - Multi-Position Bulletin No. 0 October 07 Supersedes June 0 Nominal Capacity -. to Tons Optional Electric Heat -. to 0 kw MODEL NUMBER

More information

Cyclone Custom Centrifugal Fans

Cyclone Custom Centrifugal Fans Cyclone Custom Centrifugal Fans A L P H A I R Custom Engineered Centrifugal Fans ALPHAIR s line of custom engineered centrifugal fans is ideally suited for applications that involve moving air at higher

More information

FILTERED AIR SUPPLY FANS. Direct Drive & Belt Driven Models FSR / FSWD / FSWB / FF. Model FSWB Wall Mounted. Model FSR Roof Mounted

FILTERED AIR SUPPLY FANS. Direct Drive & Belt Driven Models FSR / FSWD / FSWB / FF. Model FSWB Wall Mounted. Model FSR Roof Mounted The Industrial Choice. Model FSWB Wall Mounted Model FSR Roof Mounted FILTERED AIR SUPPLY FANS Direct Drive & Belt Driven Models FSR / FSWD / FSWB / FF CATALOG 664 June 2013 Filtered Air Supply Fans Roof

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS TABLE OF CONTENTS H & V Features and Benefits...4 Coil and Filter Data, Static Pressure Data...7 Electric Resistance Heat Section...8 Coil Information

More information

TUBULAR CENTRIFUGAL INLINE FANS

TUBULAR CENTRIFUGAL INLINE FANS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS TUBULAR CENTRIFUGAL INLINE FANS MODEL TSL CATALOG 1001 APRIL 2014 CENTRIFUGAL INLINE FANS Model TSL The TSL is an inline centrifugal

More information

BAC / BHC Product Specifications

BAC / BHC Product Specifications COMMERCIAL AIR HANDLERS (3 PHASE) 6 to 20 TON / Product Specifications REFRIGERATION CIRCUIT Standard factory-installed thermostatic expansion valves (TXVs) on units; units include TXVs and check valves

More information

MODULAR AIR HANDLING UNITS GAH SERIES

MODULAR AIR HANDLING UNITS GAH SERIES MODULAR AIR HANDLING UNITS GAH SERIES 15 Models with Air Flows from 2,250 Cu.m/hr upto 77,800 Cu.m/hr Suitable for both Standard and District Cooling Applications GAH-TC-10-13 CONTENTS Design 2 Various

More information

SINGLE PACKAGE HEAT PUMPS

SINGLE PACKAGE HEAT PUMPS SINGLE PACKAGE HEAT PUMPS HPP024 THRU 060 2 THRU 5 NOMINAL TONS 13 SEER FACTORY MOUNTED TXV DESCRIPTION These packaged heat pumps are designed for outdoor installation. Only utility and duct connections

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 39M Central Station Air-Handling Units Sizes 03-30 Installation, Start-Up and Service Instructions CONTENTS Page INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: 036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections

More information

The highest energy recovery available.

The highest energy recovery available. The highest energy recovery available. RG S e r i e s Dual Core Energy Recovery Temperature Efficiency Tempeff North America products employ Dual Core regenerative technology that offers up to 95% temperature

More information

Automatic Roof Door Vents

Automatic Roof Door Vents DATA SHEET Automatic Roof Door Vents Features n UL Listed for use as an automatic smoke vent n FM Approved as an automatic door vent for use in high expansion foam systems n Available in multiple sizes

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 0) File no. E000 and for grease removal (UL/C-UL US ) File no. MH. Accurex, LLC certifies model XRUB, XRUD, XSEB, XSED, and

More information

VAHU Vertical Air Handling Unit

VAHU Vertical Air Handling Unit 500 to 5,400 CFM @ up to 6.00" TSP 2" double wall construction, perforated or solid lined 18 gauge G90 galvanized steel cabinet 4 standard cabinet sizes available Internally isolated direct drive plug

More information

SARAVEL MINI AIR-HANDLING UNIT

SARAVEL MINI AIR-HANDLING UNIT CAT-MAHU-2003(1) SARAVEL MINI AIR-HANDLING UNIT 800 TO 5500 CFM ( 1400 TO 9300 m³/hr ) 1 TABLE OF CONTENTS Introduction... 3 Specifications 4 Examples.... 5 Coil Circuiting & Physical Data..... 7 Rating

More information

Typical Applications. Horizontal Installation

Typical Applications. Horizontal Installation ENGINEERING DATA COILS COIL UNITS CB19 AND CBH19 SERIES UP-FLOW, DOWN-FLOW AND HORIZONTAL COIL UNITS *12,600 to 65,500 Btuh (3.7 to 19.2 kw) Cooling Capacity 11,500 to 60,000 Btuh (3.4 to 17.6 kw) Heat

More information

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil

More information

Centrifugal Filtered Supply Roof Blowers

Centrifugal Filtered Supply Roof Blowers CFS Centrifugal Filtered Supply Roof Blowers Page Introduction...................................... 2 Specifications and Dimension Data................... 3 Typical Installation................................

More information

Recold JW Series. Lenntech. Tel Fax ENGINEERING DATA AND SPECIFICATIONS

Recold JW Series. Lenntech. Tel Fax ENGINEERING DATA AND SPECIFICATIONS Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 ENGINEERING DATA AND SPECIFICATIONS Recold JW Series FLUI D COOLER Recold JW Series Fluid Cooler Contents 2 Construction...

More information

MAH. Modular Air Handling Unit

MAH. Modular Air Handling Unit MA Modular Air andling Unit 500 to 11,000 CFM @ up to 6.00 TSP 2 and 4 double wall construction, perforated or solid lined 18 gauge G0 galvanized steel cabinet 26 standard cabinet sizes available Internally

More information

BAC / BHC SERIES 6 to 20 Ton Air Handlers

BAC / BHC SERIES 6 to 20 Ton Air Handlers / SERIES 6 to 20 Ton Air Handlers COMMERCIAL SPLIT SYSTEM AIR HANDLER FEATURES CONSTRUCTION Die-formed galvanizedsteel casingsprovide durabilityand structuralintegrity. HIGH STATIC DESIGN High static design

More information

Defining Innovation. backward curved FANs

Defining Innovation. backward curved FANs Defining Innovation. high efficiency industrial backward curved FANs TYPE HIB BULLETIN 00-B May 20 HIB High-Efficiency Industrial Backward-Curved Fans Model HIB fans from Twin City Fan & Blower employ

More information

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change without Notice.

More information

SHELDONS ENGINEERING Inc. Sheldons Engineering Product Index

SHELDONS ENGINEERING Inc. Sheldons Engineering Product Index SHELDONS ENGINEERING Inc. Sheldons Engineering Product Index AIR HANDLING-RADIAL BLADE CENTRIFUGAL FAN XB GENERAL The centrifugal fan shall be designed and manufactured by Sheldons Engineering to ensure

More information

OEM and Industrial Air Handling Specialist Snider Road, Mason, OH Telephone:

OEM and Industrial Air Handling Specialist Snider Road, Mason, OH Telephone: HDBI BLOWERS OEM and Industrial Air Handling Specialist BACKWARD INCLINED CLASS II CLASS III CLASS IV 797 Snider Road, Mason, OH 45040-915 Telephone: 51-57-000 Visit us at www.cincinnatifan.com for more

More information

SINGLE PACKAGE AIR CONDITIONING WATER COOLED

SINGLE PACKAGE AIR CONDITIONING WATER COOLED MODELS: CU060-300 5-25 TONS VERTICAL SINGLE PACKAGE AIR CONDITIONING WATER COOLED MODELS: CH060-5-10 TONS HORIZONTAL FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TABLE OF CONTENTS

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Direct and Belt Driven Models VUDK and VUBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Product Data. 42D Ducted Fan Coil Air Conditioners cfm

Product Data. 42D Ducted Fan Coil Air Conditioners cfm Product Data 42D Ducted Fan Coil Air Conditioners 600-2000 cfm Carrier s 42D series ducted fan coil units offer design and equipment location flexibility Choice of 5 models, each available in 8 sizes For

More information

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ) 550.39-TG1YI (994) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H5CE090 & H3CE120 7.5 AND 10 NOMINAL TONS (World 50HZ) HCE090 SUNLINE 2000 DESCRIPTION These Sunline 2000 units are completely assembled, piped

More information

KLIMA Active Chilled Beams

KLIMA Active Chilled Beams KLIMA 2 600 Active Chilled Beams 0 Index Subject Page Index 1 Introduction 2 General description 3-4 Product features 5-6 Dimensions 7 Performance data 8-11 Selection example 12 Guide specifications 13

More information

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT SIZES FROM 600 TO 4,000 All Technical Specifications are Subject to Change without Notice.

More information

McQuay MDM Air Handling Unit CMDM

McQuay MDM Air Handling Unit CMDM McQuay MDM Air Handling Unit CMDM - 2004 Contents Page Nomenclature System... 1 Features... 2 Performance Tables... 4 Outlines and Dimensions... 15 Section Weights... 23 Installation... 25 Operation...

More information

General TAHVIEH HAMOON Airfoil Centrifugal Fans Utilize the latest design techniques to product a quiet highly efficient air mover.

General TAHVIEH HAMOON Airfoil Centrifugal Fans Utilize the latest design techniques to product a quiet highly efficient air mover. General TAHVIEH HAMOON Airfoil Centrifugal Fans Utilize the latest design techniques to product a quiet highly efficient air mover. Aerodynamically designed blades and air passages allow more air to be

More information

Product Data. Features/Benefits. 39NX Central Station Air-Handling Units. Nominal 2,000 to 55,000 Cfm

Product Data. Features/Benefits. 39NX Central Station Air-Handling Units. Nominal 2,000 to 55,000 Cfm Product Data 39NX Central Station Air-Handling Units Nominal 2,000 to 55,000 Cfm Features/Benefits Sloped, double-wall coil condensate drain pan complies with ASHRAE Standard 62 Double-wall casings solid,

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

Nomenclature. Nomenclature Distributing coil types

Nomenclature. Nomenclature Distributing coil types STEAM COILS Contents and Nomenclature Distributing coil types Nomenclature... 1 Distributing Coil Types JA and GA... 1 DA and LA... 1 RA and TA... 2 Non-Distributing Coil Types SA and HA, SB and HB...

More information

AIR-AIR ENERGY CONSERVATION MODULE

AIR-AIR ENERGY CONSERVATION MODULE AIR-AIR ENERGY CONSERVATION MODULE BC-ECW SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY TABLE OF CONTENTS BC-ECW - Description...3 Components and fabrication details...3-4 Frost prevention & selection

More information

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz Precision Cooling For Business-Critical Continuity Liebert CW System Design Manual - 26-181kW, 50 & 60Hz TABLE OF CONTENTS LIEBERT CW MODEL NUMBER NOMENCLATURE....................................1 1.0

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A) Product Data OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A) 5 to 20 Nominal Tons The 50XCR single-package remote aircooled units offer: Compact, durable,

More information

42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 300 to 1400 cfm Electric heater option

42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 300 to 1400 cfm Electric heater option 42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 0 to 10 cfm Electric heater option 42DC/ 42DCD Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 0 to 00 cfm Electric heater

More information

Modular Variable Speed Air Handlers

Modular Variable Speed Air Handlers Modular Variable Speed Air Handlers Convertible Variable Speed Communicating Air Handlers - 1 1/2-5 Ton 4TEE3C01A1000A 4TEE3C02A1000A 4TEE3C03A1000A 4TEE3C04A1000A 4TEE3C05A1000A 4TEE3C06A1000A 4TEE3C07A1000A

More information

BAC / BHC SERIES 6 to 20 Ton Air Handlers

BAC / BHC SERIES 6 to 20 Ton Air Handlers / SERIES 6 to 20 Ton Air Handlers COMMERCIAL SPLIT SYSTEM AIR HANDLER FEATURES CONSTRUCTION Die-formed galvanizedsteel casingsprovide durabilityand structuralintegrity. HIGH STATIC DESIGN High static design

More information

Generator and Motor Coolers

Generator and Motor Coolers Generator and Motor Coolers Enerfin Generator and Motor Coolers (RAM) are manufactured and designed to ASME codes and TEMA standards as required. Our coolers with removable covers can be manufactured using

More information

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Direct and Belt Driven Models VWDK and VWBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company centrifugal wall

More information

Fire Dampers Catalogue

Fire Dampers Catalogue Fire s Catalogue DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) CRFD - Type A, B, CR & CO Rectangular, Round & Flat Oval UL 555 Classified 2013 For Use in Static & Dynamic Systems 3 Hour Rating Made in

More information

Centrifugal Utility Fans - SFD/SFB

Centrifugal Utility Fans - SFD/SFB C H F D B G E A Centrifugal Utility Fans - SFD/SFB SFB STANDARD CONSTRUCTION FEATURES HOUSING: Heavy gauge steel housing with Lock-seam construction Unit support angles with prepunched mounting holes Adjustable

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

SQAF AIRFOIL BLOWERS CLASS IP CLASS II CLASS IIP CLASS III. OEM and Industrial Air Handling Specialist

SQAF AIRFOIL BLOWERS CLASS IP CLASS II CLASS IIP CLASS III. OEM and Industrial Air Handling Specialist OEM and Industrial Air Handling Specialist SQAF AIRFOIL BLOWERS CLASS IP CLASS II CLASS IIP CLASS III 69 Snider Road, Mason, OH 4040-913 Telephone: 13-3-0600 Visit us at www.cincinnatifan.com for more

More information

A. Manufacturer: Provide products complying with these specifications and produced by the following:

A. Manufacturer: Provide products complying with these specifications and produced by the following: SECTION 23 76 13 - PACKAGED AIR HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23

More information

NH 3. Evaporator. Ammonia Applications Tons MANP

NH 3. Evaporator. Ammonia Applications Tons MANP NH 3 Evaporator Ammonia Applications 12-108 Tons > > Used for medium TO large Industrial Ammonia applications Manufactured with Stainless steel tubes. The Global Leader In Heat Exchange Technology With

More information

Daikin McQuay. Large Capacity Fan Coil Belt Drive. HCBB, HHBB Design 1. Replacement Parts List No Revision E 03/2018

Daikin McQuay. Large Capacity Fan Coil Belt Drive. HCBB, HHBB Design 1. Replacement Parts List No Revision E 03/2018 Replacement s List No. 700024000 Revision E 03/2018 Daikin McQuay Large Capacity Fan Coil Belt Drive HCBB, HHBB 08-30 Design 1 To find your Daikin Applied parts distributor, call 1-800-377-2787 or visit

More information

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS 550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece

More information

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat Producing Quality Heating & Cooling Equipment For Over 50 Years CEA SERIES CEILING EPOSED HORIZONTAL FAN COIL UNITS The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

More information

BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS

BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS MAGIC AIRE BVX SERIES FAN COILS ARE ETLC LISTED IN ACCORDANCE WITH UL 1995 AND ARE ASSEMBLED TO ORDER FOR COMPETITIVE DELIVERY. UNITED ELECTRIC COMPANY,

More information

forward curved inline duct blowers

forward curved inline duct blowers Defining Innovation. forward curved inline duct blowers TYPE DBS (Single) DBT (Twin) BULLETIN 4220 January 2011 Duct Blowers General Information Twin City Fan s belt driven DBS (single) and DBT (twin)

More information

Product Data. 40RUA 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz

Product Data. 40RUA 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz Product Data 07 --- 12 C09035 Carrier s versatile packaged air-handling units satisfy design requirements with: S Multi-position design

More information

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MADE IN USA SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change without

More information

Air Handling Unit Fan Selection Guide

Air Handling Unit Fan Selection Guide KEES Air Handling Unit Fan Selection Guide This document applies to models: DFG Direct Fired Gas Heater IFG Indirect Fired Gas Heater MUA Tempered Air NTS Non-Tempered Supply Table of Contents: Page 2-4

More information

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating. Issued 2005/06/01 Section 15831 Commercial Fans Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01355 Waste Management and Disposal..2 Section 15053 Motors, Drives and Guards..3 Section 15072

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Centrifugal Exhaust Fans Series C. Roof Upblast and Sidewall

Centrifugal Exhaust Fans Series C. Roof Upblast and Sidewall Centrifugal Exhaust s Series C Roof Upblast and Sidewall April 28 Series C - Spun Aluminum Roof Upblast and Sidewall Centrifugal Exhaust s When you buy a Greenheck Series C model, you receive a fan with

More information

VXI Closed circuit cooling towers

VXI Closed circuit cooling towers Closed circuit cooling towers Key benefits Reliable Quiet Compact characteristics Counter flow, centrifugal fan, forced draft Capacity range up to 2615 kw Maximum entering fluid temperature 82 C Typical

More information

Series 8500 Centrifugal Swingout Fans Design 8510 Centrifugal Airfoil Design 8520 Centrifugal BI

Series 8500 Centrifugal Swingout Fans Design 8510 Centrifugal Airfoil Design 8520 Centrifugal BI Bulletin 8510-4 May 2000 Series 8500 Centrifugal Swingout Fans Design 8510 Centrifugal Airfoil Design 8520 Centrifugal BI Description Index Series 8500 Centrifugal Swingout Fans The Series 8500 Centrifugal

More information

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL MODEL FEATURES Exhaust air up to 60,116 CFM in static pressure applications up to 1 w.g. Straight-through air flow design results in maximum exhaust efficiency Motor and drives are located outside

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

LINEAR DIFFUSERS AND BAR GRILLES

LINEAR DIFFUSERS AND BAR GRILLES LINEAR DIFFUSERS AND AR GRILLES LINEAR DIFFUSERS AND AR GRILLES LINEAR SLOT DIFFUSER PLENUMS FOR TECHZONE TYPE CEILINGS Model Series 5300TZ Plenums are designed to fit the 5000TZ Series Slot Diffusers.

More information

SQBI BLOWERS BACKWARD INCLINED CLASS II CLASS IIP CLASS III. OEM and Industrial Air Handling Specialist

SQBI BLOWERS BACKWARD INCLINED CLASS II CLASS IIP CLASS III. OEM and Industrial Air Handling Specialist OEM and Industrial Air Handling Specialist SQBI BLOWERS BACKWARD INCLINED CLASS II CLASS IIP CLASS III 7697 Snider Road, Mason, OH 4040-913 Telephone: 13-73-0600 Visit us at www.cincinnatifan.com for more

More information

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT MADE IN USA SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change

More information

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED ROOF VENTILATORS Models BSHD / BSHB CATALOG 632 November 12 Hooded Roof Ventilators Models BSHD BSHB Aerovent Low Profile Hooded Roof Ventilators

More information

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor Guide Specifications General CR-A series ducted concealed chilled water fan coil units have an air flow range from 45 to 3060 cubic meters per hour with a capacity range from kw up to 9 kw. The CR-A series

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

CS3 Series 50/60Hz. Modular Central Station Air Handling Units Air Volume: 1000 to cfm (1700 to m 3/hr)

CS3 Series 50/60Hz. Modular Central Station Air Handling Units Air Volume: 1000 to cfm (1700 to m 3/hr) CS3 Series 50/60z Modular Central Station Air andling Units Air Volume: 1000 to 56000 cfm (1700 to 90 m 3/hr) Products that perform...by people who care DUNAM-BUS CS3 Series Introduction For more than

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information