1 We manage heat Model APS 3B Snow and Ice Melting Control 120 VAC Part Number VAC Part Number Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana (574) or (800) FAX (574) or (888)
2 DISCLAIMER makes no representations or warranties, either expressed or implied, with respect to the contents of this publication or the products that it describes, and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose. Environmental Technology, Inc. reserves the right to revise this publication and to make changes and improvements to the products described in this publication without the obligation of to notify any person or organization of such revisions, changes or improvements. Copyright 1995, 2004 All rights reserved. No part of this manual may be reproduced or translated in any form or by any means, electronic or mechanical including photocopying and recording, for any purpose without the express written consent of The ETI logo, We Manage Heat, Snow Switch, APS, SC and RCU are reg is tered trademarks of En vi ron men tal Technology, Inc. Printed in USA PN17702 rev 4/2005
3 Installation Install in accordance with the requirements of all applicable electrical and building codes and regulations. Enclosure The APS-3B nonmetallic enclosure is suitable for installation in environments corresponding to NEMA 1, 2, 3R, 12 and 13 applications. The APS 3B was designed to operate satisfactorily over an ambient temperature range of 40 to 136 F. ( 40 to 58 C.). Using the integral external mounting flanges, the APS 3B is intended to be installed on fixed, vertical, flat surfaces as it was shipped; no disassembly or component removal is required. The choice of anchors and companion mounting hardware should be appropriate for both the mounting surface and the environment. The mounting flanges accommodate a range of fastener diameters up to ¼ (6.35 mm). Conduit The APS-3B nonmetallic enclosure is furnished with three ¾ (21 mm) conduit entries to be utilized in the following manner: Bottom, right: Line voltage (120 VAC or VAC) supply branch circuit conductors. Bottom, left: Snow/ice melting system load branch circuit conductors or pilot duty Top, right: conductors controlling remote contactor(s). Low voltage (Class 2) wiring; principally intended for connection of the selected snow/ice sensor. Also to be used for the Class 2 wiring associated with both the optional RCU 1 Remote Control Unit. Prior to finalizing the arrangement and selection of raceways, familiarize yourself with the specific requirements of both the grounding and wiring sections of these instructions. Should the use of a single line voltage conduit entry best serve the planned installation, a nonmetallic knockout enclosure has been furnished, permitting the unused opening to be permanently abandoned. If the APS 3B is to be installed in a hostile environment, ensure that all conduit terminations are watertight. rounding Effective grounding is key to the safe, proper operation of the APS-3B. Based on the planned installation, you may elect one (or both) of the following means to accomplish this. Provide a continuous copper equipment grounding conductor routed with the branch circuit conductors. Caution: If the branch circuit conductors are contained within continuous rigid metallic raceway(s), connect a copper bonding jumper to each line voltage race way terminating at the nonmetallic enclosure using a grounding type bushing or conduit hub or locknut having approved grounding provisions. The equipment grounding conductor(s) and/or the bonding jumper(s) are, each, to be properly sized for the rating of the branch circuit overcurrent protective device employed and shall be terminated in the mechanical lug designated ". 1.
4 Wiring - Line Voltage Line voltage (120 VAC or VAC) supply and load branch circuit conductors must be copper and must have sufficient ampacity to limit the maximum insulation temperature to 60 C. To assist in your selection of a minimum wire size appropriate for the snow/ice melting system load, see Table 1. (Caution: For circuits of extraordinary installed length, it may be necessary to utilize larger conductors to minimize voltage drop.) Line voltage conductors, #10 AW and smaller, must be served with appropriate one-hole lugs to be landed under the #8 binder head terminal screws of both the Supply and Load barriered terminal blocks. Numerous wiring arrangements for the APS 3B are compiled in Appendix A to guide your installation. Wiring - Class 2 Low Voltage The Class 2 low voltage terminal block, shown in Figure 1 below, contains three sets of terminals for, from top to bottom: Remote Control, Sensor, and Comm Link. Figure 1. Class 2 low voltage terminal block. Each of these Class 2 circuits may have an equivalent installed length of 2,000 feet (609.5 mm) utilizing multiconductor #18 AW jacketed cable. For distances exceeding this length, contact Environmental Technology Customer Service for assistance. Proper automatic operation of the APS 3B requires the connection of at least one snow/ice sensor, color matching the sensor lead wires to the respective terminals as shown (blk-blk, wht-wht, red-red). Systems employing multiple sensors should be connected in parallel in whatever fashion may conveniently accommodate the planned installation; it is unnecessary to wire radially to each sensor. For guidance in physically installing a specific snow/ice sensor, consult the Installation Instructions for the selected model. If the system incorporated an (optional) RCU 1 Remote Control Unit, it is un-necessary to discriminate between the two required conductors when terminating. See the Installation Instructions for the unit regarding specific installation requirements. Upon completing all line and low voltage and grounding terminations, and prior to energizing the APS 3B, reinstall the deadfront metal compartment cover. 2.
5 Checkout Thoroughly check the system before placing it in service. Our experience shows that installation errors cause the majority of problems. Frequently encountered problems include wiring errors. Simple electrical tests and visual inspections identify these problems. Once the APS 3B installation has been properly completed, it may be energized. (Note: If the snow/ice melting system is comprised of one or more SC 40 Satellite Contactors, energization will entail the closing of multiple branch circuit overcurrent protective devices.) The green Supply LED will be illuminated on each successive unit as its respective supply circuit is energized; the RCU 1 Remote Control Unit LED display, if a part of the system, operates in tandem with the APS 3B. Should any individual momentary contact Heater Cycle push button be held depressed, all LEDs will flash, continuously, at one second intervals until the offending push button is released. Once weather tracking has begun, should any installed sensor detect snow/ice, the amber Snow LED on the APS 3B will be illuminated. Subsequently, the APS 3B will initiate operation of the snow/ice melting system, this being signaled by its amber Heater LED and the companion display on the RCU 1 Remote Control Unit (if a part of the system). Similarly, the amber Heater LED on all installed SC 40 Satellite Contactors having an energized power supply will be illuminated as each initiates its respective snow/ice melting system load. The APS 3B Hold-On Time adjustment, having a range of 0 to 10 hours, may be employed for the following purposes: To maintain snow/ice melting function for a selected time duration, beginning when all installed sensors concur that snowfall has ceased. This, for example, ensures complete clearing and drying of such sensitive locations as ramps for the physically challenged, or permits effective clearing of zones regularly experiencing excessive drifting, slush deposition or similar anomaly. An initial setting of 3 hours is suggested; for enhanced effectiveness and/or economy, this setting may be altered based upon operational experience. To manually energize the snow/ice melting system for a selected time duration by depressing the APS 3B Heater Cycle push button for (at least) 3 seconds and releasing. This mode is most useful as an annual, pre-season, operational test of the snow/ice melting system or as a diagnostic aid in troubleshooting. If the outdoor temperature is sufficiently cold, the system will be continuously energized for the selected time duration. This mode may be duplicated utilizing the Heater Cycle push button on the remote control accessory, if present in the system. If you experience installation problems or have any question regarding proper installation procedures, Environmental Technology Customer Service is available for assistance during normal business hours, 8: 00 am to 4: 00 pm, EST. Phone (800) Fax (574)
6
7 Appendix A APS 3B Wiring Diagrams I. Pilot Duty A. Mechanically-Held Contactor(s) VAC Coil(s) Figure A VAC Coil(s) Figure A 2 B. Electrically-Held Contactor(s) VAC Coil(s) Figure A VAC Coil(s) Figure A 4 II. Switching Duty A. 120 VAC One 30A (or smaller) Branch Circuit Figure A 5 B VAC One 30 A. (or smaller) Branch Circuit Figure A 6
8 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) C2 UNLATCH LATCH N LATCH UNLATCH C1 120 VAC 50/60 Hz Figure A-1: Pilot Duty - Operating mechanically-held contactors with 120V coils.
9 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) C2 UNLATCH LATCH CONNECTION LATCH UNLATCH C VAC 50/60 Hz Figure A-2: Pilot Duty - Operating mechanically-held contactors with 208V or 240V coils.
10 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) C2 N C1 120 VAC 50/60 Hz Figure A-3: Pilot Duty - Operating electrically-held contactors with 120V coils.
11 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) C2 CONNECTION C VAC 50/60 Hz C1 CONNECTION VAC 50/60 Hz Figure A-4: Pilot Duty - Operating electrically-held contactors with 208V or 240V coils.
12 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) HEATER 2 N HEATER VAC 50/60 Hz Figure A-5: 120V Switching Duty - Operating one 30 A (or smaller) branch circuit. Combined heater load may not exceed 24A
13 APS-3B Snow/Ice Melting Controller SW HEATER HEATER CYCLE HOLD-ON TIME (HRS) South Bend, Indiana USA (800) HEATER 1 CONNECTION VAC 50/60 Hz HEATER 2 CONNECTION HEATER VAC 50/60 Hz Figure A-6: 208V or 240V Switching Duty - Operating one 30 A (or smaller) branch circuit. Combined heater load may not exceed 24A
Snow Switch Models HSC 4 (P/N 24220) & HSC 5 (P/N 24221)
Description The Snow Switch Model HSC 4 and HSC 5 Pavement-Mounted Deicing Controllers reliably operate snow and ice melting heaters based upon pavement conditions. This ensures that deicing heaters operate
More informationMODEL SIT -6E PAVEMENT-MOUNTED SNOW AND ICE SENSOR
MODEL SIT -6E PAVEMENT-MOUNTED SNOW AND ICE SENSOR DESCRIPTION The Snow Switch Model SIT 6E Pavement-Mounted Snow and Ice Sensor reliably detects snow and ice conditions on pavement surfaces when used
More informationModel LA 4400 Time Delay OFF Controller
ISIMET LA Series Model LA 4400 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller with integral 24-hr. programmable time clock operates
More informationPavement-Mounted Deicing Controller SNOW SWITCH MODEL HSC 24. Installation and Operation Manual
Pavement-Mounted Deicing Controller SNOW SWITCH MODEL HSC 24 MANUAL We Manage Heat Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574)
More informationModel LA 4100 Time Delay OFF Controller
ISIMET LA Series Model LA 4100 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller operates as a single output controller where the application
More informationMODEL HSC-24 AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL
MODEL HSC-24 AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL DESCRIPTION The Snow Switch Model HSC-24, 24-volt Pavement-Mounted Snow and Ice Sensor reliably detects snow and ice conditions on pavement
More informationGC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY
GC-1 Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY GENERAL INFORMATION The GC-1 heating cable controller has been designed and manufactured for
More informationSAFETY INFORMATION AND WARNINGS
This manual refers to the control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and have different
More informationModel LA 4300 Time Delay OFF Controller
ISIMET LA Series Model LA 4300 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller operates as a single output controller where the application
More informationPatient Care Facility
ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for
More informationDrug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions
ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control
More informationCAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877
CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems
More informationDisconnect Combiner Box Installation Manual
Disconnect Combiner Box Installation Manual SolarBOS, Inc. 310 Stealth Court Livermore CA 94551-9552 925-456-7744 ph. 925-456-7710 fax www.solarbos.com Copyright 2008 SolarBOS, Inc. All rights reserved.
More informationPatient Care Facility
ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for
More informationPatient Care Facility Multiple Room Configuration Style 3 W/ Ver 4.41 pcb & Pulse Relay pcb(s)
ISIMET DLA Controller Patient Care Facility Multiple Room Configuration Style 3 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Application: The DLA
More informationDrug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions
ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control
More informationSAFETY INFORMATION AND WARNINGS
SAFETY INFORMATION AND WARNINGS Abnormal Odor or Smoke In the event of smoke or a burning or abnormal odor, immediately interrupt power to the unit by unplugging the unit or by turning off the circuit
More informationINSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH
INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by
More informationContactor Combiner Box Installation Manual
Contactor Combiner Box Installation Manual SolarBOS, Inc. 310 Stealth Court Livermore CA 94551-9552 925-456-7744 ph. 925-456-7710 fax www.solarbos.com Copyright 2008 SolarBOS, Inc. All rights reserved.
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationTransfer Switch TS-50. Owner s Manual
Transfer Switch TS-50 Owner s Manual Table of Contents Introduction 2 Installation 2 Operational Testing 7 Troubleshooting 7 Hi-Pot Testing 8 Generator Note 9 Medical Appliances 10 Caution 10 Disclaimer
More informationSAVE THESE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be
More informationITS-50R TRANSFER SWITCH OWNER S MANUAL
ITS-50R OWNER S MANUAL IOTA Engineering Transfer Switches provide automatic power switching between two or three separate 120/240 volt AC input sources, including powercords, onboard generators, onboard
More informationmodel ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION
MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.
More informationCombiner Box Installation Manual
Combiner Box Installation Manual SolarBOS, Inc. 310 Stealth Court Livermore CA 94551 925-456-7744 ph. 925-456-7755 fax www.solarbos.com Copyright 2008 SolarBOS, Inc. All rights reserved. All rights reserved.
More informationElectric Vehicle Charging Station
EVoReel Electric Vehicle Charging Station INSTALLATION GUIDE AND USER MANUAL Model: Dual Output Pedestal Mount 30A EVoReel EVSE Model Numbers: With Basic EVSE: EV072-400-002A; With Intelligent ievse: EV072-410-002A;
More informationCIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT
GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT INSTALLATION AND WIRING INSTRUCTIONS MANUAL 8030 MANUAL PART NUMBER JANUARY 2011. 4304 MATTOX RD. KANSAS CITY, MO 64150 TABLE OF CONTENTS
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before
More informationTOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)
TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29499-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the user
More informationModel C230 Pump Controller
MANUAL Model C230 Earthsafe Systems, Inc. 7553 S. Madison Willowbrook, IL 60527 T: (630) 794-5100 F: (630) 794-5106 info@earthsafe.com www.earthsafe.com March 1, 2010 The information contained herein is
More informationManual Transfer Switch
Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal
More informationSpectron Industrial Series
1300650 1300654 1300666 1300754 1300823 1300886 Table B Constant Value per Voltage System Wire Size (Maximum Voltage Drop 5%) System 6 Volt 12 Volt 24 Volt Wire Size #12 #10 #8 #6 #12 #10 #8 #6 #10 #12
More informationSelf-Testing Industrial Series
Series: AS-I (Maint.-Free) Self-Testing Industrial Series Emergency Lighting Equipment Instructions for INSTALLATION OPERATION SERVICE SPECIFICATIONS 1300650 1300654 1300666 1300754 1300823 1300886 Hubbell
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationPATENT PENDING. Phone: (877) Operation and Service Manual
PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product
More informationTOPAZ 24 DIMMER RACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)
TOPAZ 24 DIMMER RACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29132-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the
More informationInstallation Instructions
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment
More informationINSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR NEW YORK 18 WATT SERIES
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR NEW YORK 18 WATT SERIES IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:
More informationInstallation, Operating and Maintenance Manual
DOCUMENT # BASTD1007 Installation, Operating and Maintenance Manual 1. Technical Note - Hopper Hammer Initial Settings Pages 7 and 8 of the Hopper Hammer Models PASTD583-2 & PASTD978 Installation, Operating
More informationTRANSMISSION SYSTEMS
TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric
More informationINSTALLATION GUIDE AND USER MANUAL
Electric Vehicle Charging Station INSTALLATION GUIDE AND USER MANUAL Model: 30A EVoCharge EVSE Model Number: EV072-300-001A Product Safety Certification: UL and cul Listed Description: SAE J1772 AC Level
More information8460SRC Replacement Chassis for Scully ST-6 and Biclops Monitors
8460SRC Replacement Chassis for Manual Part Number: OPTI-THERM is a registered trademark of CIVACON, A Dover Company QUICK-START is a registered trademark of CIVACON, A Dover Company Biclops is a registered
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More informationInstallation Instructions Central Battery Units
Phone: 605.542.4444 concealite.com! Installation Instructions s Please Save These Instructions Important Safeguards Read and Follow All Safety Instructions When using electrical equipment, basic safety
More informationINSTALLATION GUIDE AND USER MANUAL
Electric Vehicle Charging Station INSTALLATION GUIDE AND USER MANUAL SAE J1772 AC Level 2 EVSE Model: 30A EVoCharge EVSE Wall Mount P/N: EV072-300-001A Version 2.0 IMPORTANT Read this manual thoroughly
More informationACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-8 Features: ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS Filtered/Regulated 24 Volts DC Up to Full 2 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit
More informationMANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450
MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION
More informationR & D SPECIALTIES ROTROL I USER'S MANUAL
R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL
More informationSIGNAL WORDS QUALIFIED PERSON
SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or
More informationInstallation Instructions: HYPERION R-Lite SYSTEM
Installation Instructions: HYPERION R-Lite SYSTEM READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS WILL VOID YOUR WARRANTY! INSTALLATION TIPS Read
More informationIMPORTANT SAFEGUARDS
INSTRUCTION MANUAL NON-INTERRUPTIBLE AC INVERTER SYSTEM MODEL EAC FTM 350 FOR EMERGENCY LIGHTING POWER IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed,
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More informationMP461SC Flex Probes* Installation Instructions
PNEUMERCATOR Liquid Level Control Systems MP461SC Flex Probes* Installation Instructions Model MP461SC Magnetostrictive Flex Probes For use with the following consoles: TMS2000 TMS3000 NOTE: MP461SC PROBES
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS
ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners YD360/480/600, YJ-30/-40/-50 and J30/40/50 YD Models 642546-UAI-A-080 GENERAL Standard operation
More informationUNIVERSAL SOLAR SYSTEM (USS) USER MANUAL. For Millennium Low Power Gas Detectors or other continuous loads less than 0.
UNIVERSAL SOLAR SYSTEM (USS) USER MANUAL For Millennium Low Power Gas Detectors or other continuous loads less than 0.8 Watts (12 V dc) Part Number: MAN-0048-00 Rev 3 May 2006 IMPORTANT INFORMATION This
More informationSunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual
Combiner Box Installation & Operations Manual SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual TABLE OF CONTENTS Notices and Safety Precautions Pages 1-2 Combiner
More informationQuik-Spec Coordination Panelboard
Read and retain for future reference Quik-Spec Coordination Panelboard Instruction Leaflet 3A1071 RevD Section TABLE OF CONTENTS Page Danger and warnings for installation of the equipment.............3-4
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSure-Lites. Installation Instructions for the Sure-Lites UX Self Powered Exit Sign with Self Diagnostics. IB505037EN Important Safeguards
049-289 Sure-Lites Installation Instructions for the Sure-Lites UX Self Powered Exit Sign with Self Diagnostics. WARNING Risk of Fire/Electric Shock If not qualified, consult an electrician. WARNING Risk
More informationR. STAHL Schaltgeräte GmbH Geschäftsbereich Leuchten Nordstraße Weimar, Germany
, INC. ECOLUX 6600 Series 6600/5 Explosion Protected Fluorescent Light Fixtures for Hazardous and Corrosive Applications Please read this entire document before beginning any work. 1. Safety Instructions
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationINTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES
INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES 3. Definitions ( cont'd) Parallel System: A generating facility that is electrically interconnected
More informationR. STAHL Schaltgeräte GmbH Geschäftsbereich Leuchten Nordstraße Weimar, Germany
ECOLUX 6608 Series 6608/5 Explosion Protected Fluorescent Emergency Light Fixtures for Hazardous and Corrosive Applications Please read this entire document before beginning any work. 1. Safety Instructions
More informationManual No: Revision: F. Mag Probe Assembly Manual
Manual No: 576013-730 Revision: F Mag Probe Assembly Manual Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationNEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry
NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry See NEW information on Class 82 size 1 in an extra wide enclosure and size 2 standard enclosures. usa.siemens.com/controls
More informationUpdated: October 2012
T: (630) 794-5100 EMERGENCY POWER FUEL SYSTEMS Earthsafe Systems, Inc. 7320 S. Madison Willowbrook, IL 60527 F: (630) 794-5106 info@earthsafe.com www.earthsafe.com Updated: October 2012 The information
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationDispenser Pan Sensors & Containment Sump Sensors
Manual No: 576013-306 Revision: E Dispenser Pan Sensors & Containment Sump Sensors Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not
More informationIntelliTouch Expansion Center Kit
pool/spa control system IntelliTouch Expansion Center Kit Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS 2005 Pentair Water Pool and Spa, Inc.
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationDrop Feeder Control. Part Number Introduction. Setting the Control. Time Clock operation. Manual Operation
Drop Feeder Control Part Number 28999 Introduction The 28999 Drop Feeder Control is designed to be used with a Chore-Time Drop Feeding System and Chore- Time Flex-Auger System. The control will automatically
More informationRental Industry Safety Tester Safe Check 5s
Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product
More informationTransfer Switch GPTS 30
Transfer Switch GPTS 30 Owner s Manual Table of Contents Introduction 2 Installation 3 Operational Testing 7 Troubleshooting 8 Hi-Pot Testing 9 Generator Note 10 Medical Appliances 10 Caution 10 Warranty
More informationPowerLogic High Density Metering System 4-Meter Enclosure Installation Guide
PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment
More informationME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position
LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationNEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry
NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry See NEW preliminary information on Class 82 size 1 in an extra wide enclosure and size 2 standard enclosures. www.usa.siemens.com/controls
More informationSprayer Control. Manual for SprayLink Cable Installations. Tank. Jet Agitator. Agitator Valve. Diaphragm Pump. Pressure Transducer.
Sprayer Control Plumbing & Installation Manual for SprayLink Cable Installations Tank Jet Tank Shut-Off Diaphragm Pump Electric Ball s Transducer Strainer Relief Regulating Copyrights 2012 TeeJet Technologies.
More informationTIMER INTERFACE USER MANUAL
TIMER INTERFACE USER MANUAL Premium Efficiency Two-Speed Motor with Integrated Timer Formerly A. O. Smith Electrical Products Company A Regal Beloit Company COPYRIGHT Copyright 2011, Regal Beloit EPC,
More informationTO AVOID DOING IRREPARABLE DAMAGE TO DRIVE CIRCUITRY NEVER APPLY AC POWER DIRECTLY TO LED LIGHTBOXES!
INSTALLATION MANUAL TO AVOID DOING IRREPARABLE DAMAGE TO DRIVE CIRCUITRY NEVER APPLY AC POWER DIRECTLY TO LED LIGHTBOXES! 4949 South 110 th Street Greenfield, WI 53228 Phone: (800) 610-6053 Fax: (414)
More informationSchaltgeräte GmbH GmbH Geschäftsbereich Leuchten
,, INC. INC. GmbH 9001 Knight Road Houston, TX 77054 Tel: 800-782-4357 FAX: 713-792-9301 E-mail: sales@rstahl.com Website: www.rstahl.com & SHEET EXLUX 6000 Series 6000/5 6000/8 Explosion Protected Fluorescent
More informationINSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:
INSTRUCTION MANUAL IMPORTANT SAFEGUARDS SERIES D LIGHTING EQUIPMENT When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationManufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN
Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180 ST Series Service Tester Phase Identifier Operating Instructions ST500PGN REV. ED. 101229 CONTENTS Limitation of Warranty and Liability
More informationIndianapolis Power & Light Company
Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationRain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
More informationHS593 Feed Line Control Unit 230V Single Phase
HS593 Feed Line Control Unit 230V Single Phase General Installation Notes: Make sure that power is disconnected from system prior to servicing. Installation of this equipment and related OEM equipment
More informationCombiner Manual #OMBINER #OMBINER < 2* )NSTALLATION 7(&+12/ i 62/$5
Combiner Manual i ii Combiner Manual Combiner Manual Copyright 2004 SMA America, Inc. All rights reserved. All rights reserved. No part of this document may be reproduced, stored in a retrieval system,
More informationWARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES
FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other
More informationSecoVac * Ground & Test Device
GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6
More informationNOVALYNX CORPORATION MODEL 200-WS-02F WIND SPEED & DIRECTION SENSOR INSTRUCTION MANUAL
NOVALYNX CORPORATION MODEL 200-WS-02F WIND SPEED & DIRECTION SENSOR INSTRUCTION MANUAL REVISION DATE: MAY 2005 Receiving and Unpacking Carefully unpack all components and compare to the packing list. Notify
More informationPD404-AN V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V. Serial Number
0-10V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V 4 circuit Analog 1-10V 4 x 4 A. Dimmer pack Serial Number Dimmers Indicators Digital Lighting Systems,Inc Info@digitallighting.com
More informationInstallation Instructions: ACCENT SYSTEM
Installation Instructions: ACCENT SYSTEM READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS WILL VOID YOUR WARRANTY! INSTALLATION TIPS Read this entire
More informationACSI MODEL POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-9 ACSI MODEL 1400-6100 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Used exclusively with the ACSI Series 6100 Communicating Bath Door (Common Bath) System Two separate and identical rows of
More informationE.S.P. Embedded Sensing Probes for Motor Brushes
E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com
More information