Session Four Applying functional safety to machine interlock guards

Size: px
Start display at page:

Download "Session Four Applying functional safety to machine interlock guards"

Transcription

1 Session Four Applying functional safety to machine interlock guards Craig Imrie Technology Specialist: Safety, NHP Electrical Engineering Products Abstract With the recent Australian adoption of functional safety standards IEC Ed 1 and ISO :2006, a greater emphasis has been placed on systematic failures and common cause failures for machine safety control systems. This has been a major issue when designing interlock guards and trying to achieve PL or SIL requirements. With the new revision of the AS series, ISO 14119:2013 has been adopted as AS Due to this new standard, information is now at hand to provide guidance on designing interlock guards to achieve the requirements of PL and SIL. This paper explains the new design considerations of this standard. Introduction In recent times the primary reference for machine safety in Australia has been the AS series. AS is a collection of standards that cover fundamental aspects of machine safety such as: Risk Assessment Ergonomics Design of safety control systems Design of Guards Etc AS adopts European standards that cover these various topics, for example: AS is equivalent to ISO for General principles for design Risk Assessment and Risk Reduction AS is equivalent to ISO for Interlocking devices associated with guards AS is equivalent to ISO for Safety-related parts of control systems General principles for design Etc AS is designed in this way so it can be updated and revised in a simple manner. When an international standard is revised the relevant part of AS can be updated to reflect this without altering the other parts of the edition. The preface of AS reflects this idea by stating:..when new editions of relevant ISO, IEC or EN Standards became available, they could be adopted and published within the framework of AS 4024 with minimum delay, so ensuring continued international alignment. Safety Control Systems Conference

2 Due to this desire to keep AS aligned with international standards, the series was revised in late Most of the parts that make up the 2014 series have been updated to adopt the current international standard. The parts concerned with Safety-related parts of control systems were of major interest. The 2006 version of AS included two parts: 1. AS : Design of safety related parts of control systems General principles for design 2. AS : Design of safety related parts of control systems Validation Both of these parts were based on design and validation according to Safety Categories. This design concept is widely used in Australia and has been part of the standard since However since 2012, Safety Categories have been superseded in international standards by ISO :2006, this standard uses the design concept of Performance Level (PL). Due to this change in international standards the 2014 version of AS now has three parts concerned with Safety-related parts of control systems: 1. AS : Design of safety related parts of control systems General principles for design (Safety Categories) 2. AS : Design of safety related parts of control systems Validation (Safety Categories) 3. AS :2014 : Safety-related parts of control systems General principles for design (Performance Levels) The relationship between PL and Safety Categories is very strong because PL is based on the architecture of Safety Categories. However there are some additional design considerations with PL, as can be seen in Figure 1. Figure 1 - Inner mechanics of a PL As can be seen in Figure 1, PL inherits the well-tried architectures of Safety Categories, it also adds the following new design aspects: Safety Control Systems Conference

3 Mean Time To Dangerous Failure (MTTF d ) This metric considers the reliability of the components used in the safety-related parts of the control system. Reliability data will usually be sourced from the manufacturer Diagnostic Coverage (DC) This metric evaluates the level of diagnostics the safety control system has in respect to dangerous failures Common Cause Failure (CCF) This aspect provides a method for the designer to avoid common cause failures in their safety system. A common cause failure would be multiple channels of a safety system failing due to the same event The relationship between Categories and PL can be seen graphically in Figure 2. It is demonstrated how the Category architecture in combination with the DC and MTTF d combine to create a PL. A certain Category can achieve multiple PL depending on the other aspects of design. Figure 2 - Relation between CAT and PL It can be seen that the PL design method includes new considerations that weren t applicable with Safety Categories. To aid users in transitioning to PL there has been significant changes made to the new interlock guard standard, AS :2014. This standard assists designers in transitioning to PL and provides guidance to design more reliable interlocking systems in the following ways: New classifications of interlock devices to better represent the current technologies available Safety Control Systems Conference

4 Information of how to design interlocking systems to achieve diversity as part of the CCF method Information on how to evaluate the DC of series wired interlock guard functions Method for designing interlock guards to reduce the probability of users defeating the interlocking safety system New interlock classifications Since the 2006 version of AS there has been significant advances in the technology of interlock devices, there has also been a transition in the types of devices used in industry. In recent years there has been development of interlock devices that provide higher levels of tamper resistance and diagnostic capabilities. The 2014 version of AS has new classifications that better represent these interlock technologies. These classifications are then used in the standard to demonstrate aspects such as how to avoid defeat of the interlock systems, determine CCF tolerance and quantify the DC of the interlock system. The new classifications are separated depending on the following criteria: Actuation principle This determines if the switch is a mechanical or non-contact device. Coding The device is either coded or uncoded. The higher the degree of coding the more tamper resistant the device is. Coding is classified into 3 sub classes: o Low level coding 1 to 9 variations in coding o Medium level coding 10 to 1000 variations in coding o High level coding Over 1000 variations in coding Table 1 shows the classifications for interlock devices. Actuation Principle Actuator Example Type Coding Level Uncoded Limit switch, Hinge switch 1 None Mechanical Coded Tongue interlock Trapped key interlock 2 Low level Medium to High level Uncoded Magnetic, inductive 3 None Non-contact Coded Coded magnetic Coded RFID 4 Low level Medium to High level Table 1 - Classifications of interlock devices Safety Control Systems Conference

5 Design interlock system to avoid Common Cause Failure (CCF) Designing the interlock system to avoid CCF is a major design consideration for achieving PL according to AS ; it is also integral to achieving SIL according to AS The method to avoid CCF is explained in Annex F of AS In this method the designer is presented with different measures that can be used in their system design, each measure is worth a certain score. As the designer achieves the requirements of each measure the cumulative score increases, once the designer achieves a score of 65 they have achieved the CCF avoidance requirements. Table 2 shows a summary of the measures and their associated score. Measure against CCF Score Separation/Segregation 15 Diversity 20 Design/Application/Experience 20 Assessment/Analysis 5 Competence/Training 5 Environment 35 Table 2 - Summary of CCF measure and associated scores, AS As can be seen in Table 2, Diversity is a significant measure when the designer is attempting to reach a score of 65. The general requirements in AS are vague on different approaches to achieve diversity; this led to confusion of how diversity could be achieved for common safety functions such as interlock systems. AS now includes some guidance on how to achieve diversity in common interlock arrangements. Diversity with Type 1 interlocking devices One technique to achieve diversity when using Type 1 (Uncoded, mechanical device) interlocking devices is explained in clause of AS Here the combination of direct and non-direct mechanical action is used. In Figure 2, an example of direct and non-direct mechanical action is demonstrated. In this example a sliding guard is shown in its closed state; the guard will slide to the left to open. Safety Control Systems Conference

6 Figure 3 Diversity with Type 1 devices In this example limit switches are used because they are Type 1 interlocking devices. Switch S1 is direct mechanical action mounted because the guard will directly actuate the switch when it is opened, by rolling on top the device. Switch S2 is non-direct mechanical action mounted because the guard will roll off the switch when opened. Due to the opposite actuating principles, diversity has been created with this combination of Type 1 interlocking devices. This is not a new concept and has been part of the standards for many years, however AS now defines that the above arrangement will achieve the complete 20 points for Diversity as part of the CCF method in AS This is clarity that was required as designers come to grips with the new requirements of AS Power medium diversity Some machines have two or more energy sources required for hazardous movement, for example hydraulic and electrical energy. In this case diversity can be achieved by having two independent interlocking devices, each of which interrupts the supply from a different energy source. AS states that 20 points of Diversity can be claimed for the CCF method according to AS Quantify the DC of series connected interlock functions (*Coming soon) In order to achieve a PL or calculate a SIL, the DC of the system must be determined. In industry it is common to observe multiple interlock guards wired in series, this can reduce the amount of safety inputs needed in the safety relay system or safety PLC. The method to determine DC is explained in Annex E of AS , however there is no guidance given on how to evaluate series connected interlock guards. The DC achieved by series wired interlock guards can be complex to evaluate. The potential of masked faults in the system can be influenced by the following application characteristics: How many guards are wired in series? How many are guards are used frequently? How many individual devices are used on each guard? What wiring configuration is used? What type of evaluation is used to detect faults? Safety Control Systems Conference

7 What type of cable is used? As you can imagine this has caused significant confusion on how to determine the DC achieved by series connected interlock guards. Clause 8.6 of AS will shortly provide a solution for this problem. The clause references a technical report, ISO/TR 24119, which will provide a simple method to evaluate the maximum DC achieved by series connected interlock guards. This technical report is currently in draft stage, but hopefully will be released later this year and provide much needed clarity of this issue. Design to minimise defeat possibilities The previous sections of this paper explain various ways that AS :2014 can assist with transitioning to design methods such as PL or SIL. However the most significant improvement with this new standard is the defined process to avoid defeat of interlock guards. Many of the aspects and measures are not new, but this standard now provides a structured process to follow. This should result in improved compatibility between machine function and interlock guards. Figure 3 shows the flow diagram that designers can use to ensure motivation to defeat is minimised and resistance to defeat is present where needed. Safety Control Systems Conference

8 Start Implement basic measures Is there a motivation to defeat? yes no Is it possible to eliminate or minimise motivation to defeat? yes no Use additional measures to minimise defeat possibility Implement design measures or add alternative modes End Figure 4 Flow diagram to minimize chance of defeat As seen in Figure 3, the first step is to implement basic measures, an example of these basic measures includes: Correct fastening of switches o Loosening of position switches, actuators and cams must require a tool o Type 1 position switches may require permanent fixing, such as pins or dowels o Self-loosening should be avoided Switch should be mounted appropriately o Access should be provided for maintenance o Switch should be mounted to protect against foreseeable damage o Switch should not be used as a mechanical stop o Type 1 or 2 switches should be direct mechanical action mounted, with direct opening action contact elements Safety Control Systems Conference

9 Once the above basic measures are ticked off, the designer can use the method explained in Annex H of AS to determine if a motivation to defeat the interlock system exists. This is a new method introduced with this version of the standard and provides guidance that has never been available before. Table 3 is an example of how the method in Annex H of AS is documented. The process includes 4 steps: 1. All modes of operation of the machine are identified, eg Mode 1 = Automatic and Mode 2 = Maintenance (Listed as headings in Col 2 and 3) 2. All tasks should be listed as the rows of the table. An x is to be used to indicate what mode of operation the task needs to be performed in. (Listed in Col 1) 3. The next column (Col 4) indicates whether it s possible to perform the task in that mode without defeating the interlock guard a. If the answer is no then improvement of the machine design or implementing new modes of operation is mandatory 4. The following columns (Col 5 and above) identify if other benefits of defeating the interlock exist when completing that task a. These benefits will need to be addressed as per the flow diagram depicted in Figure 3 Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 etc Task Automatic Maintenance Task possible Faster to Better Reduced. Mode Mode without defeating complete task visibility travel Start-up x Yes Machine operation x Yes Material feeding x No etc Benefit of defeat: 0 = None, + = Minor, ++ = Substantial Table 3 - Example of documenting motivation to defeat process In Table 3, there are 2 modes of operation and 3 tasks. For machine start-up, the task needs to be performed in Automatic mode and it is possible to complete the task without defeating the interlock guard. The following columns also indicate that no other benefits are achieved by performing this task with the interlock defeated. For material feeding it can be seen that this task needs to be performed in Automatic Mode, however the task is not possible in this mode without defeating the interlock guard. The material feeding task requires the ability to jog the machine with the interlock guard open, but the automatic mode won t allow operation with the interlock guard open. This result will require a new mode of operation to be added to allow the material feeding task to be performed in a safe way. For machine operation it can be seen that this task needs to be performed in Automatic mode and it is possible to complete the task without defeating the interlock guard. The following columns indicate that there is a substantial benefit of improved visibility when defeating the interlock guard. The designer Safety Control Systems Conference

10 should consider what design measures could address this benefit, eg: Using a guard that provides the required visibility. If there are no design measures available then the designer would need to implement additional measures to minimise defeat possibility. Additional measures to minimise defeat possibility are used to address residual motivation to defeat once all possible design measures and alternative modes of operation have been exhausted. The measures are reliant on the level of coding incorporated by the interlock devices. The lower the level of coding; the more measures are required to avoid defeat, examples of measures used are: Mounting out of reach Mounting the interlock device in a position that is out of the reach limits of the operator Physical Obstruction/Shielding Mounting the interlock device behind physical obstructions, so the operator can t easily access the device Mounting the interlock device in a hidden position Status monitoring or cyclic testing - These two techniques are systems that ensure the interlock device s function is tested, thus the test will detect if the device has been defeated Non-detachable fixings These fixings prevent the switch, actuator or both being removed from their intended position in order to defeat the safety function Additional device Utilising two independent devices for the interlock function, thus if one device is defeated the safety function will still operate Table 4 indicates what measures are implemented for the different classifications of interlock devices. Safety Control Systems Conference

11 Measures Type 1 or 3, except hinge switch Mount device out of reach Shield device Mount device in hidden position Status monitoring/ cyclic testing Non-detachable fixing for switch and actuator Non-detachable fixing for switch Non-detachable fixing for actuator X Hinge Switch Type 2 or 4 with low or medium coding level Additional device R R M X Type 2 or 4 with high coding level Trapped key system with medium or high level coding M M M M X = measure should be considered, M = measure is mandatory, R = measure is recommended Table 4 - Additional measures to minimise defeat possibility M Conclusion In conclusion the new version of AS provides assistance for designers to achieve the requirements of AS :2014. The standard provides guidance on how to design interlock systems to avoid CCF and will provide a method to evaluate the DC of interlock functions that are series connected. The other significant improvement of this standard is the process to minimise the probability of defeat. This method ensures that interlock guards will be designed with the operation of the machine in mind. This will reduce the motivation for operators to defeat the interlocking systems. The process also provides a method to select the appropriate interlocking devices to address any residual motivation to defeat the interlock system. References AS :2014 AS :2014 Safety Control Systems Conference

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE NHP SAFETY REFERENCE GUIDE WHITEPAPERS Interlock classifications Since the 2006 version of AS 4024.1602 there has been significant advances in the technology of interlock devices, there has also been a

More information

Achieving Required Safety Levels Using a Pneumatic Safety Exhaust Valve

Achieving Required Safety Levels Using a Pneumatic Safety Exhaust Valve EMBARGO DATE OCTOBER 16, 2017 Parker Hannifin Corporation Pneumatic Division 8676 E. M89 P.O. Box 901 Richland, Michigan 49083 USA www.parker.com/pneumatics Achieving Required Safety Levels Using a Pneumatic

More information

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE 4 NHP SAFETY REFERENCE GUIDE CONTENTS SAFETY TECHNOLOGY Risk Reduction Options Permanent Fixed Guard 4-02 Interlocked Guard: 4-03 Limit Switches 4-08 Presence Sensing Technology 4-09 Safety Laser Scanners

More information

P33T Series Redundant Safety Exhaust Valve ENGINEERING YOUR SUCCESS.

P33T Series Redundant Safety Exhaust Valve ENGINEERING YOUR SUCCESS. aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding P33T Series Redundant Safety Exhaust Valve Catalogue PDE675TCUK October

More information

P33T Series Redundant Safety Exhaust Valve ENGINEERING YOUR SUCCESS. Bulletin 0700-B13.

P33T Series Redundant Safety Exhaust Valve ENGINEERING YOUR SUCCESS. Bulletin 0700-B13. aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding P33T Series Redundant Safety Exhaust Valve Bulletin 0700-B3 ENGINEERING

More information

More than just a solenoid interlock AZM300

More than just a solenoid interlock AZM300 More than just a solenoid interlock AZM300 Safe solutions for your industry AZM300 The one for all Symmetrical mounting for right- and left-hinged doors Only one version for hinged and sliding doors Compact

More information

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS Door Monitoring Trojan 5 Interlock Switch, Guardmaster Safety Relay, PowerFlex 525 Drive with Safe Torque-off Table of Contents: Introduction 6-122

More information

MKey9-series Safety Interlock Switch with Guard Locking

MKey9-series Safety Interlock Switch with Guard Locking Original instructions MKey9-series Safety Interlock Switch with Guard Locking ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document

More information

UNI EN ISO EN

UNI EN ISO EN Airplus Safeline eneral Upon implementation of the AIRPLUS T series, air-treatment units, PNEUMAX develops a supply and discharge valve, with an electropneumatic control and spring-return, fitted with

More information

F3S-TGR-KHL1/-KHL3/-KHL3R

F3S-TGR-KHL1/-KHL3/-KHL3R Safety guard-lock door switches with full stainless steel body F3S-TGR-KHL1/-KHL3/-KHL3R The F3S-TGR-KHL3 safety-door switch keeps medium to large guard doors closed until hazards have been removed. It

More information

Modern Industrial Pneumatics. Design and Troubleshooting Industrial Pneumatics PN111 PN121

Modern Industrial Pneumatics. Design and Troubleshooting Industrial Pneumatics PN111 PN121 Modern Industrial Pneumatics Design and Troubleshooting Industrial Pneumatics PN111 PN121 Drives: Cylinders for different drive purposes Valves: Various valve types (pneumatically/electrically controlled,

More information

AZM300 More than just a solenoid interlock

AZM300 More than just a solenoid interlock AZM300 More than just a solenoid interlock AZM300 The one for all Symmetrical mounting for right- and left-hinged doors Only one version for hinged and sliding doors Compact design Can be used as end stop

More information

AS/NZS ISO :2013

AS/NZS ISO :2013 ISO 7176-28:2012, IDT Australian/New Zealand Standard Wheelchairs Part 28: Requirements and test methods for stair-climbing devices AS/NZS ISO 7176.28:2013 This Joint Australian/New Zealand Standard was

More information

Application of safety principles for a guidance system in public transport

Application of safety principles for a guidance system in public transport Application of safety principles for a guidance system in public transport H. Schäbe TÜV Rheinland InterTraffic, Cologne, Germany H. Vis & R. Bouwman Advanced Public Transport systems, Helmond, The Netherlands

More information

ZB0050 / ZB0051 ZB0070 / ZB0071

ZB0050 / ZB0051 ZB0070 / ZB0071 Operating instructions Safety Rope Emergency Stop Switches UK ZB0050 / ZB0051 ZB0070 / ZB0071 7390877 / 02 08/2013 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4 2.2

More information

CETOP POSITION PAPER PP 07

CETOP POSITION PAPER PP 07 CETOP POSITION PAPER PP 07 MACHINERY DIRECTIVE 2006/42/EC Valid since 26 th May 2010 CETOP General Secretariat Lyoner Straße 18 D-60528 Frankfurt am Main Phone: +49 69 6603 1201 Fax: +49 69 6603 2201 E-mail:

More information

Selecting & Integrating Safety Exhaust Valves White Paper

Selecting & Integrating Safety Exhaust Valves White Paper Selecting & Integrating Exhaust Valves White Paper Selecting and Integrating Exhaust Valves Linda Caron Global Product Manager, Factory Automation Parker Hannifin Corporation Today, exhaust valves are

More information

Modern Safety Systems and Advanced Fluid Power Solutions

Modern Safety Systems and Advanced Fluid Power Solutions Modern Safety Systems and Advanced Fluid Power Solutions Chris Brogli Global VP of Safety Business Development TUV FS Expert ID#213/13 Phone: 1-859-595-9630 Email: chris.brogli@rosscontrols.com Today we

More information

Investigation into UK socket-outlets incorporating USB charging points

Investigation into UK socket-outlets incorporating USB charging points Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of

More information

Certification Memorandum. Approved Model List Changes

Certification Memorandum. Approved Model List Changes Certification Memorandum Approved Model List Changes EASA CM No.: CM 21.A-E Issue 01 issued 15 August 2018 Regulatory requirement(s): 21.A.57, 21.A.61, 21.A.62, 21.A.91, 21.A.93, 21.A.97, 21.A.114, 21.A.117,

More information

Transponder-coded. with guard locking

Transponder-coded. with guard locking Transponder-coded safety switch CTP with guard locking The safety switch CTP The safety switch CTP combines the proven principle of operation of electromechanical safety switches with guard locking with

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT Date of publication: 1 November 2016Not yet published Issued by: Mark Wogan, Manager Energy Safety WorkSafe New ZealandNot yet issued Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

More information

An important type of protective

An important type of protective Courtesy of CM/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) 426-5480 www.cmafh.com Interlocking Principles and Devices n important type of protective device is a safety

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 4029.2:2000 AS/NZS 4029.2 Australian/New Zealand Standard Stationary batteries Lead-acid Part 2: Valve-regulated type (IEC 60896-2:1995, MOD) AS/NZS 4029.2:2000 This Joint Australian/New Zealand

More information

Sense7-series Non-contact coded safety switch

Sense7-series Non-contact coded safety switch Original instructions Sense7-series Non-contact coded safety switch ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please

More information

Transponder-coded. with guard locking

Transponder-coded. with guard locking Transponder-coded safety switch CTP with guard locking The safety switch CTP The new safety switch CTP combines the proven principle of operation of electromechanical safety switches with guard locking

More information

Technical support to the correlation of CO 2 emissions measured under NEDC and WLTP Ref: CLIMA.C.2/FRA/2012/0006

Technical support to the correlation of CO 2 emissions measured under NEDC and WLTP Ref: CLIMA.C.2/FRA/2012/0006 Technical support to the correlation of CO 2 emissions measured under NEDC and WLTP Ref: CLIMA.C.2/FRA/2012/0006 Further details regarding the target translation 18 th December 2013 John Norris Project

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

Operating instructions Safety sensor BNS About this document. Content. 6 Disassembly and disposal 6.1 Disassembly Disposal...

Operating instructions Safety sensor BNS About this document. Content. 6 Disassembly and disposal 6.1 Disassembly Disposal... Safety sensor BNS Disassembly and disposal. Disassembly..... Disposal... EU Declaration of conformity Operating instructions.............pages to Original x.000 / 0.0 / v.a. - 09009- / J / 0-0-0 / AE-Nr.

More information

CEN/TC 198. EN :2005/FprA1:2010. Date: CEN/TC 198. Secretariat: DIN

CEN/TC 198. EN :2005/FprA1:2010. Date: CEN/TC 198. Secretariat: DIN CEN/TC 198 Date: 2010-05 EN 1010-5:2005/FprA1:2010 CEN/TC 198 Secretariat: DIN Safety of machinery Safety requirements for the design and construction of printing and paper converting machines Part 5:

More information

Mechanical Trainstop Systems

Mechanical Trainstop Systems Mechanical Trainstop Systems Synopsis This document defines the functional requirements for mechanical trainstop systems and the requirements relating to their use on both track and trains. Signatures

More information

E.V.READY Specification for Installer Training Content

E.V.READY Specification for Installer Training Content E.V.READY Specification for Installer Training Content Document: TISN E.V.Ready 1.4D Ed 1.0 of 13/09/2016 Page: 2/2 Contents 1. Change tracking... 3 2. Background and purpose... 4 3. Training course structure...

More information

Australian Standard. Electricity metering equipment (AC) Particular requirements

Australian Standard. Electricity metering equipment (AC) Particular requirements AS 62053.21 2005 Reconfirmed 2016 AS 62053.21 2005 Australian Standard Electricity metering equipment (AC) Particular requirements Part 21: Static meters for active energy (classes 1 and 2) (IEC 62053-21,

More information

VOLUNTARY CODE OF PRACTICE FOR ELECTROMAGNETIC COMPATIBILITY (EMC) OF MOTOR VEHICLES (13 October 2014)

VOLUNTARY CODE OF PRACTICE FOR ELECTROMAGNETIC COMPATIBILITY (EMC) OF MOTOR VEHICLES (13 October 2014) FEDERAL CHAMBER OF AUTOMOTIVE INDUSTRIES VOLUNTARY CODE OF PRACTICE FOR ELECTROMAGNETIC COMPATIBILITY (EMC) OF MOTOR VEHICLES (13 October 2014) This code is prepared under the direction of the FCAl Board,

More information

Hinge Wing Safety Interlock Switches

Hinge Wing Safety Interlock Switches Hinge Wing Safety Interlock Switches SI-HG80 Series Safety Interlock Switches Encapsulated in a Load-Bearing Hinge Inline QD Fitting Right-Angle QD Fitting Features Safety switch is integrated and encapsulated

More information

Rapid Response. Lineside Signal Spacing. Railway Group Standard GK/RT0034 Issue Three Date September 1998

Rapid Response. Lineside Signal Spacing. Railway Group Standard GK/RT0034 Issue Three Date September 1998 Rapid Response Railway Group Standard Lineside Signal Spacing Synopsis This Standard specifies the minimum distance that must be provided between the first signal displaying a cautionary aspect and the

More information

Status of the Informal Working Group on ACSF

Status of the Informal Working Group on ACSF Submitted by the IWG on ACSF Informal document GRRF-86-20-Rev.1 86 th GRRF session, 12-16 February 2018, Agenda item 9(b) Status of the Informal Working Group on ACSF Summary ACSF IWG Meeting 16th Session

More information

Safety Sensor CSS 180 Product Information

Safety Sensor CSS 180 Product Information Safety Sensor CSS 180 Product Information Safety Sensor CSS 180 CSS180CSS 180 PDF-M / EN 60947-5-3 EN 954-1 Control Category 4 IEC 61508, suitable for use in SIL 3 applications BG Type-Certification in

More information

EEVC Report to EC DG Enterprise Regarding the Revision of the Frontal and Side Impact Directives January 2000

EEVC Report to EC DG Enterprise Regarding the Revision of the Frontal and Side Impact Directives January 2000 EEVC Report to EC DG Enterprise Regarding the Revision of the Frontal and Side Impact Directives January 2000 EEVC Report to EC DG Enterprise Regarding the Revision of the Frontal and Side Impact Directives

More information

High Speed Passenger Rail Interoperability in North America

High Speed Passenger Rail Interoperability in North America High Speed Passenger Rail Interoperability in North America APTA Rail Conference - Boston Thomas Peacock Larry D. Kelterborn June15, 2011 Discussion Topics The New Transportation Vision Meaning of Interoperability

More information

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual Electronic Motor Brake Type G Instructions and Setup Manual Table of Contents Table of Contents Electronic Motor Brake Type G... 1 1. INTRODUCTION... 2 2. DESCRIPTION AND APPLICATIONS... 2 3. SAFETY NOTES...

More information

Technical Article. ISO26262: ams deploys unique technology to meet every new safety requirement. Roland Einspieler

Technical Article. ISO26262: ams deploys unique technology to meet every new safety requirement. Roland Einspieler Technical ISO26262: ams deploys unique technology to meet every new safety requirement Roland Einspieler ISO26262: ams deploys unique technology to meet every new safety requirement Roland Einspieler As

More information

NOT PROTECTIVELY MARKED. Vehicle fleet

NOT PROTECTIVELY MARKED. Vehicle fleet Vehicle fleet Contents Policy statement... 2 Principles... 2 Responsibilities... 3 All police officers and police staff drivers... 3 First line manager or supervisor... 3 District and departmental heads...

More information

Compatibility of STPA with GM System Safety Engineering Process. Padma Sundaram Dave Hartfelder

Compatibility of STPA with GM System Safety Engineering Process. Padma Sundaram Dave Hartfelder Compatibility of STPA with GM System Safety Engineering Process Padma Sundaram Dave Hartfelder Table of Contents Introduction GM System Safety Engineering Process Overview Experience with STPA Evaluation

More information

SAFETY AND RELIABILITY ANALYSIS OF ELECTRIC POWER STEERING SYSTEM USED IN AUTOMOBILES

SAFETY AND RELIABILITY ANALYSIS OF ELECTRIC POWER STEERING SYSTEM USED IN AUTOMOBILES SAFETY AND RELIABILITY ANALYSIS OF ELECTRIC POWER STEERING SYSTEM USED IN AUTOMOBILES A.Vanaja 1, H.Gargama 2, B. Sarvesh 3 1 M.Tech, Reliability Engg. Student, JNTUACEA Anantapuramu, Andhra Pradesh (India)

More information

Certification Directorate. General Aviation and RPAS Department. Report

Certification Directorate. General Aviation and RPAS Department. Report Certification Directorate Report EU/US BASA Safety Emphasis Items (SEI) List for CS 23 Page 1 of 6 Report EU/US BASA Safety Emphasis Items (SEI) List for CS23 Document ref. Status Date Contact name and

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PNEUMATIC CIRCUTS. This work covers part of outcome 3 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PNEUMATIC CIRCUTS. This work covers part of outcome 3 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PNEUMATIC CIRCUTS This work covers part of outcome 3 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome

More information

Variable Valve Timing

Variable Valve Timing Service. Self-study programme 246 Variable Valve Timing with fluted variator Design and Function The demands on combustion engines continue to grow. On one hand, customers want more power and torque, while

More information

Notice of Proposed Amendment Regular update of CS-25

Notice of Proposed Amendment Regular update of CS-25 European Aviation Safety Agency Rulemaking Directorate tice of Proposed Amendment 2014-06 Regular update of CS-25 RMT.0606 27.03.2014 EXECUTIVE SUMMARY This tice of Proposed Amendment (NPA) makes use of

More information

Solenoid interlock AZM 200 The non-contact interlock.

Solenoid interlock AZM 200 The non-contact interlock. Solenoid interlock AZM 200 The non-contact interlock. Solenoid interlock AZM 200 The non-contact Solenoid interlocks demand accurate alignment of actuator and device. This requirement is met on new machinery.

More information

National Unit Specification: General Information

National Unit Specification: General Information National Unit Specification: General Information NUMBER 2210278 COURSE SUMMARY This unit is designed to develop a knowledge of steering system components fitted to a vehicle, how they operate, the areas

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX B4 1667206 [ ](2014) XXX DRAFT 30.04.2014 COMMISSION REGULATION (EU) No /.. of XXX supplementing Regulation (EC) No 661/2009 of the European Parliament and of the Council

More information

Christian Theis 52 nd GRB, 6-8 September 2010, ASEP outline. Summary & Conclusion

Christian Theis 52 nd GRB, 6-8 September 2010, ASEP outline. Summary & Conclusion ASEP outline Summary & Conclusion Background Information 2005: GRB adopted new test procedure (ISO 362) Technical principle: - technology neutral vehicle operating conditions to estimate the actual 90th

More information

Explanatory Note to Decision 2017/017/R

Explanatory Note to Decision 2017/017/R Maintaining aerodrome rules AMC/GM for Aerodromes Amendment 2 RELATED NPA/CRD 2016-10 RMT.0591 EXECUTIVE SUMMARY The objective of this Decision is to maintain a high level of safety for aerodrome and flight

More information

ELECTRICAL TECHNOLOGY 3 March 2008

ELECTRICAL TECHNOLOGY 3 March 2008 I. Course Description ELECTRICAL TECHNOLOGY 3 March 2008 The purpose for this course is to instruct potential electricians in the skills necessary for entry into the job market. During this course, the

More information

English version of. Executive Order on vehicles' technical compatibility with the rail network (Bekendtgørelse nr af 30. november 2012) Preface

English version of. Executive Order on vehicles' technical compatibility with the rail network (Bekendtgørelse nr af 30. november 2012) Preface English version of Executive Order on vehicles' technical compatibility with the rail network (Bekendtgørelse nr. 1127 af 30. november 2012) Preface Please note that the English version is for informational

More information

Tina 4A Connection block

Tina 4A Connection block Original instructions Tina 4A Connection block Instructions valid for versions of the product from ver. H ABB Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read

More information

PROTECT SRB s Safety relay modules with intrinsically safe monitoring circuits Ex i L-protection for ATEX zones 1, 2, 21 and 22.

PROTECT SRB s Safety relay modules with intrinsically safe monitoring circuits Ex i L-protection for ATEX zones 1, 2, 21 and 22. PROTECT SRB s Safety relay modules with intrinsically safe monitoring circuits Ex i L-protection for ATEX zones 1, 2, 21 and 22 News 08 PROTECT SRB s Safety relay modules with intrinsically safe monitoring

More information

AS/NZS :2013. Wheelchairs AS/NZS :2013. Australian/New Zealand Standard

AS/NZS :2013. Wheelchairs AS/NZS :2013. Australian/New Zealand Standard AS/NZS 3695.2:2013 Australian/New Zealand Standard Wheelchairs Part 2: Requirements and test methods for electrically powered wheelchairs (including mobility scooters) Superseding AS 3695 1992 AS/NZS 3695.2:2013

More information

POLLUTION PREVENTION AND RESPONSE. Application of more than one engine operational profile ("multi-map") under the NOx Technical Code 2008

POLLUTION PREVENTION AND RESPONSE. Application of more than one engine operational profile (multi-map) under the NOx Technical Code 2008 E MARINE ENVIRONMENT PROTECTION COMMITTEE 71st session Agenda item 9 MEPC 71/INF.21 27 April 2017 ENGLISH ONLY POLLUTION PREVENTION AND RESPONSE Application of more than one engine operational profile

More information

Presented to the IAPMO Standards Review Committee on December 9, 2013

Presented to the IAPMO Standards Review Committee on December 9, 2013 Summary of Substantive Changes between the 2010 edition including Updates No. 1 and No. 2 dated September 2010 and August 2011 and the 2013 edition of CSA C22.2 No. 14 Industrial control equipment Presented

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3112:2011 AS/NZS 3112:2011 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets AS/NZS 3112:2011 This Joint Australian/New Zealand Standard was prepared by Joint

More information

Revised proposal to amend UN Global Technical Regulation No. 3 (Motorcycle brake systems) I. Statement of technical rationale and justification

Revised proposal to amend UN Global Technical Regulation No. 3 (Motorcycle brake systems) I. Statement of technical rationale and justification Submitted by the expert from Italy Informal document GRRF-86-10 86 th GRRF, 12-16 February 2018 Agenda item 5 Revised proposal to amend UN Global Technical Regulation No. 3 (Motorcycle brake systems) Based

More information

Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Parts

Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Parts Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Study Dates: March 1999 March 2002 Prepared By Certified Automotive Association 1518 K Street NW, Suite 306 Washington, DC 20005

More information

Notification of a Proposal to issue a Certification Memorandum. Approved Model List Changes

Notification of a Proposal to issue a Certification Memorandum. Approved Model List Changes Notification of a Proposal to issue a Certification Memorandum Approved Model List Changes EASA Proposed CM No.: Proposed CM 21.A-E Issue 01 issued 02 October 2017 Regulatory requirement(s): 21.A.57, 21.A.61,

More information

Transport of explosives from blasting explosives to low order explosives

Transport of explosives from blasting explosives to low order explosives Transport of explosives from blasting explosives to low order explosives Henry Zuidersma Principal Dangerous Goods Officer 1 April 2016 Need to transport explosives correctly Need suitable equipment to

More information

Safety Control HR1S-AC. Safety Relay HR1S-AC

Safety Control HR1S-AC. Safety Relay HR1S-AC HRS-AC Safety Relay HRS-AC Key features: NC or 2NC safety input type, such as E-Stops or Interlock Switches EN ISO 3849- PLe, Safety Cat 3 compliant, and EN 6206 SIL 3 Fault diagnosis function with dual

More information

4 Redundant Control System

4 Redundant Control System 4 Redundant Control System Introducing the all NEW RCS Configurator Safety Instrumented Systems Process Reliability Process Valve Diagnostics COMPLETE FUNCTIONAL SAFETY WITH ENHANCED RELIABILITY The Redundant

More information

New Machinery Directive

New Machinery Directive New Machinery Directive Machinery Directive 2006/42/EC Member States to adopt and Publish 29 th June 2008 Directive applies in full 29 th December 2009 This Directive now looks at the lifecycle of the

More information

Compatibility Between Electric Trains and Electrification Systems

Compatibility Between Electric Trains and Electrification Systems Compatibility Between Electric Trains and Electrification Systems Synopsis Process for managing change that affects the compatibility between electric trains and electrification systems Submitted by Signatures

More information

The Automotive Industry

The Automotive Industry WLTP AUTOMOTIVE INDUSTRY GUIDE WLTP GUIDANCE FOR The Automotive Industry NEDC WLTP Executive Summary The purpose of this guide is to provide an overview of WLTP and its transition into UK policy and consumer

More information

Specifications. Safety Ratings. Standards. Safety Classification. Certifications. Power Supply

Specifications. Safety Ratings. Standards. Safety Classification. Certifications. Power Supply Safety Guard Locking Atlas 5 General 1-2-Opto-electronics 3-Interlock Logic Description The Atlas 5 is a positive-mode, tongue-operated guard-locking interlock switch that locks a machine guard closed

More information

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011-

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011- Proceedings of ASME PVP2011 2011 ASME Pressure Vessel and Piping Conference Proceedings of the ASME 2011 Pressure Vessels July 17-21, & Piping 2011, Division Baltimore, Conference Maryland PVP2011 July

More information

SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES

SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES ROA MANUAL SCHEDULE OF AMENDMENTS SECTION 8 AMENDMENT NUMBER PAGES AMENDED AMENDMENT SUMMARY DATE ISSUED Portions of this Section of the ROA

More information

Testing Directive. Changes to vehicle testing: STEERING AND SUSPENSION. Introduction

Testing Directive. Changes to vehicle testing: STEERING AND SUSPENSION. Introduction Testing Directive Changes to vehicle testing: STEERING AND SUSPENSION Introduction This is the second in a series of Technical Pen Pictures that looks at the changes VOSA will be implementing as a result

More information

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material

More information

AS/NZS :2011. Gate valves for waterworks purposes AS/NZS :2011. Part 1: Metal seated. Australian/New Zealand Standard

AS/NZS :2011. Gate valves for waterworks purposes AS/NZS :2011. Part 1: Metal seated. Australian/New Zealand Standard AS/NZS 2638.1:2011 Incorporating Amendment No. 1 Australian/New Zealand Standard Gate valves for waterworks purposes Part 1: Metal seated AS/NZS 2638.1:2011 AS/NZS 2638.1:2011 This joint Australian/New

More information

Safety Integrated for entry level personnel SINAMICS. SINAMICS G converters Safety Integrated for entry level personnel. Hazards in plants and

Safety Integrated for entry level personnel SINAMICS. SINAMICS G converters Safety Integrated for entry level personnel. Hazards in plants and Hazards in plants and machines 1 Drives with "Safety Integrated" in the application 2 SINAMICS SINAMICS G converters Safety Integrated for entry level personnel An overview of the "Safety Integrated" functions

More information

Hinge Wing Safety Interlock Switches

Hinge Wing Safety Interlock Switches SI-HG80 Series Safety Interlock Switches encapsulated in a load-bearing hinge Safety switch is integrated and encapsulated into a load-bearing hinge, providing a high degree of protection from intentional

More information

Key elements of the AS3000 Wiring standards and some of the recent changes.

Key elements of the AS3000 Wiring standards and some of the recent changes. Key elements of the AS3000 Wiring standards and some of the recent changes. Dean of Engineering Steve Mackay Worked for 30 years in Industrial Automation 30 years experience in mining, oil and gas, electrical

More information

MCS. Important Information on MCS 012 Issue 2.1 for MCS Solar Photovoltaic and Solar Thermal Contractors. Last Updated: 25 th September 2017

MCS. Important Information on MCS 012 Issue 2.1 for MCS Solar Photovoltaic and Solar Thermal Contractors. Last Updated: 25 th September 2017 MCS Important Information on MCS 012 Issue 2.1 for MCS Solar Photovoltaic and Solar Thermal Contractors Last Updated: 25 th September 2017 1. Publication of MCS 012 Issue 2.1 on 5 th April 2016 Please

More information

SG-B1 SERIES / SG-A1 SERIES

SG-B1 SERIES / SG-A1 SERIES 643 Door with Solenoid Interlock / Door Ultra-slim SG-B1 SERIES / SG-A1 SERIES Related Information General terms and conditions... F-7 General precautions... P.1501 PHOTO PHOTO Conforming to Machine &

More information

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( ) Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 (2382-18) March 2018 Version 1.0 FAQs 1 18 th Edition IET Wiring Regulations 2018 FAQs When will the 18 th Edition of BS 7671

More information

Industrial Maintenance. Basic Controls. Courseware Sample F0

Industrial Maintenance. Basic Controls. Courseware Sample F0 Industrial Maintenance Basic Controls Courseware Sample 39163-F0 Order no.: 39163-10 First Edition Revision level: 04/2015 By the staff of Festo Didactic Festo Didactic Ltée/Ltd, Quebec, Canada 2007 Internet:

More information

A REPORT ON THE STATISTICAL CHARACTERISTICS of the Highlands Ability Battery CD

A REPORT ON THE STATISTICAL CHARACTERISTICS of the Highlands Ability Battery CD A REPORT ON THE STATISTICAL CHARACTERISTICS of the Highlands Ability Battery CD Prepared by F. Jay Breyer Jonathan Katz Michael Duran November 21, 2002 TABLE OF CONTENTS Introduction... 1 Data Determination

More information

IDEM MPC Non-Contact Coded Magnetic Safety Switches MPC Series Plastic Housing

IDEM MPC Non-Contact Coded Magnetic Safety Switches MPC Series Plastic Housing IDEM MPC Non-Contact Coded Magnetic MPC Series Plastic Housing MPC-114105 Coded magnetic actuation Compact yet robust fitting suitable for all small guard applications Hygenic screw cap covers ensure suitability

More information

AS/NZS 3112:2004 AS/NZS

AS/NZS 3112:2004 AS/NZS AS/NZS 3112:2011 Incorporating Amendment No. 1, 2, and 3 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets Superseding AS/NZS 3112:2004 AS/NZS 3112:2011 AS/NZS 3112:2011

More information

CMP266 Removal of Demand TNUoS charging as a barrier to future elective Half Hourly settlement

CMP266 Removal of Demand TNUoS charging as a barrier to future elective Half Hourly settlement CMP266 Removal of Demand TNUoS charging as a barrier to future elective Half Hourly settlement Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures

More information

BACS APPROVED BUREAU SCHEME SUPPORT GUIDELINES

BACS APPROVED BUREAU SCHEME SUPPORT GUIDELINES BACS APPROVED BUREAU SCHEME SUPPORT GUIDELINES VERSION 8.2 May 2017 CONTENTS 1 DOCUMENT INFORMATION 4 1.1 VERSION HISTORY 4 1.2 DOCUMENT REVIEWERS 4 1.3 COPYRIGHT STATEMENT 4 2 CONFIDENTIALITY 4 3 INTRODUCTION

More information

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas AS 62040.1.1 2003 IEC 62040-1-1:2002 IEC 62040-1-1:2002/Corr.1:2002 Reconfirmed 2013 AS 62040.1.1 Australian Standard Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS

More information

This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists.

This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists. /2.0 PURPOSE This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists. The HMS system is a means of preventing hoist operation or movement to

More information

ISO :2015/DAM 1

ISO :2015/DAM 1 DRAFT AMENDMENT ISO 19973-2:2015/DAM 1 ISO/TC 131 Voting begins on: 2018-01-15 Secretariat: ANSI Voting terminates on: 2018-04-09 Pneumatic fluid power Assessment of component reliability by testing Part

More information

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches An Investment in Plant Floor Safety 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches Notes 2 802C Cable Pull Safety Switches Safety and Application Safety

More information

Model 277EC ENGINE IDLE LIMITER

Model 277EC ENGINE IDLE LIMITER Model 277EC ENGINE IDLE LIMITER Manufactured by FLIGHT SYSTEMS www.flightsystems.com INSTALLATION INSTRUCTIONS Please read these instructions entirely before starting the installation. CONFIGURATION: Unless

More information

IMILV08 Diagnose and rectify light vehicle chassis system faults

IMILV08 Diagnose and rectify light vehicle chassis system faults Overview This NOS is about diagnosing and rectifying faults occurring within vehicle steering, suspension and braking systems. IMILV08 1 Performance criteria You must be able to: P1 wear suitable personal

More information

Copyright 2003 Advanced Power Technologies, Inc.

Copyright 2003 Advanced Power Technologies, Inc. Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design

More information

Universal Gate Box with Safety Interlocking TYPE: UGB-KLT FEATURES & APPLICATION:

Universal Gate Box with Safety Interlocking TYPE: UGB-KLT FEATURES & APPLICATION: SECTION 6 Universal Gate Box with Safety Interlocking TYPE: UGB-KLT FEATURES & APPLICATION: 70 Application: IDEM Universal Gate Boxes (UGB-KLT) provide high level RFID coded interlocking and machine control

More information

Unit level 4 Credit value 15. Introduction. Learning Outcomes

Unit level 4 Credit value 15. Introduction. Learning Outcomes Unit 6: Unit code Mechatronics T/615/1480 Unit level 4 Credit value 15 Introduction Auto-focus cameras, car cruise control and automated airport baggage handling systems are examples of mechatronic systems.

More information

Vehicle Systems and Technology

Vehicle Systems and Technology Unit 75: Vehicle Systems and Technology Unit code: D/601/1374 QCF level: 5 Credit value: 15 Aim This unit will develop learners understanding of the operating principles associated with advanced vehicle

More information

KEWTECH. KT56 digital multi function tester. Instruction manual

KEWTECH. KT56 digital multi function tester. Instruction manual KEWTECH KT56 digital multi function tester Instruction manual Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating

More information