Service and Meter Requirements

Size: px
Start display at page:

Download "Service and Meter Requirements"

Transcription

1 Service and Meter Requirements 2017 dition An xelon ompany

2 Summary of hanges in This dition Number hange Note 2 revised to prohibit installation of power supply on corner poles and primary cable riser poles. eleted requirement for PV conduit; conduit must meet applicable building code. larified requirements for termination enclosure (note 6). eleted junction box requirements and clarified note 8 (formerly note 9) requirements. New standard for SAA-connected bulk power metering.

3 INX SRVI AN MTR RQUIRMNTS SRVI, GNRALLY General requirements Phase arrangement SRVI, OVRHA Single-phase, 400 A and below Row house service Three-phase, 200 A and below Three-phase, over 200 A ox-type service head Recessed service head Service to meter pole Service to trailer park pole Service extension on ompany pole ATV/communications supplies Street light syst s and traffic sig ls SRVI, UNRGROUN able pole onnection to overhead SS ATV/communications supplies Street light syst s and traffic sig ls SRVI, TMPORARY Outdoor, to pole Underground LIGHTING ustomer-owned outdoor light MTRING, GNRALLY General requirements High-rise AMI requirements MTRING, 1-PHAS, SLF-ONTAIN Overhead, to 200 A Overhead, 320 A Overhead, 200 A, multi-position Underground, to 200 A Underground, 320 A Underground, 200 A, multi-position MTRING, 3-PHAS, SLF ONTAIN Overhead, to 200 A Overhead, 200 A, multi-position Underground, to 200 A Underground, 200 A, multi-position Multi-position, 200 A, ovhd./undg MTRING, TRANSFORMR RAT (480 V and below) urrent transformer compartment Meter, 1-phase Meter, 3-phase (Above 480 V) SAA metering

4 This page intentionally left blank

5 PRFA This book is issued by ommonwealth dison ompany (herein called the ompany ) as a reference and guide to its regulations, specifications, and practices for the connection and supply of electric service. It is intended for the use of customers, architects, engineers, contractors, electricians, and other persons engaged in the planning or construction of buildings, or the installing or replacing of equipment that is to be connected to and served from the ompany s electric distribution system. The term ustomer as used herein includes a contractor, agent, or other representative acting for the ustomer, or the owner of the premises. ach requirement for specific equipment, facilities, or work to be done in connection with providing electric service to the ustomer shall be the ustomer s responsibility unless otherwise stated. The information and specifications contained herein supplement the ompany s rate schedule on file with the Illinois ommerce ommission, which set forth the general conditions under which electric service will be supplied. In the event a condition arises that is not specifically covered herein, consult the ompany to determine the applicable requirements. In case of a conflict between this book and the filed rate schedule, the rate schedule governs. A copy of the ompany s rate schedule currently in effect, along with proposed revisions thereto, is posted on the ompany s Web site at The specifications contained in this book come into effect on the dates shown in each, and are permitted to be used for any construction begun on or after that date. All prior specifications that conflict with the specifications in this book cease to be effective on January 1, 2017, and work done to those specifications (including all specifications contained in the Information and Requirements for the Supply of lectric Service, or Silver ook ) on or after that date will not be accepted for connection of new or revised service. Information and Advice The ompany has representatives who will meet with the ustomer and discuss any problem that may arise concerning the installation or use of electric service. Information and advice on the most efficient and reliable plan of service is also available upon request. It is recommended that the ustomer consult with the ompany well in advance of installing or modifying service. A minimum of two weeks advance notice is requested for connecting overhead service drops; at least twelve weeks may be needed for larger or more complex installations. ompliance to odes The ompany s filed Terms and onditions require that all electrical facilities, wiring, and equipment furnished by the ustomer be and remain in compliance with the National lectrical ode. Other local codes may apply, in which case the ustomer s facilities must comply with the most stringent applicable rules. It is the ustomer s responsibility to obtain any necessary permits for installation of wiring or equipment on the premises, along with any required inspections of the installation. The ompany is usually prohibited by municipal authorities from connecting service to any installation that has not passed inspection. ontracts for the electrical installation should include the requirement that all electrical wiring and apparatus conform with the requirements of applicable governmental codes, as well as the standards of the National Fire Protection Association.

6 Inspections performed by the ompany are intended to assess compliance with the ompany s rules and standards, and are not evidence of compliance with National lectrical ode or other governing codes or regulations. Organization The specifications in this book are presented as numbered standards. ach standard applies to a different type of installation, and they are not interchangeable. All of the items shown on a given standard are necessary to an acceptable installation. ach standard is numbered in both upper corners with a -number (such as 7800 ), which may also be used in communications or agreements with the ompany to specify the facilities required for a particular installation. elow the -number is a revision date, showing the date the standard was last revised. Revisions Revisions are identified by revision arrows ( ). An arrow pointing to the -number indicates an extensive revision, and the entire standard should be reviewed. A listing of standards revised and their specific revisions are provided in a Memorandum in the front of this book. Notes The notes contained in the standards are arranged in five groups: Application notes specify how or why a standard is used. They are intended to clarify usage. Reliability notes indicate items that, if improperly installed or misapplied, could lower the quality of service. Reliability notes, where referenced on the drawings, are marked with a diamond to highlight them. Supplementary Material notes contain information on variations to the standard and require an addition or omission of material where applicable. Information notes supply information such as deviations in spacing or location of equipment and references to other standards for methods of installing supplied material. Operations notes denote recommended construction procedures. Notes in parentheses are referenced on drawings. ach note is numbered for identification. ircled notes are referenced where they apply on the drawings or in the material table. Uncircled notes apply to the standard generally. Service Ordering To order new service installation, or to change or remove service facilities, call omd s New usiness hotline at (866) NW-L ( ). Please have the street address, contact information, and details about the proposed work available when you call. To request changes to an existing service, such as to start or stop service at an existing address, or to move an account to a new address, call omd s ustomer Service enter at (800) ISON-1 ( ) for residential accounts, or (877) 4-omd-1 ( ) for business accounts. You can also submit service requests through omd s Web site at

7 ONTATING TH OMPANY IN AN MRGNY To report an emergency involving power lines First: all your local emergency services, if appropriate: Then: all omd: or local number: (800) ISON-1 ( ) mergency assistance is available 24 hours a day. Tell the operator your exact address and contact information, and if anyone has been hurt or trapped. Keep everyone far away from downed wires or damaged equipment until help arrives, no matter how safe it looks. Service Installation or hanges New usiness Hotline:... (866) NW-L Start, Stop, or Move Service Residential:... (800) ISON-1 usiness:... (877) 4-OM-1 Underground Facility Location all efore You ig Outside hicago: JULI or...(800) Inside hicago: IGGR...(312) Other Requests Including requests for line voltages, rubber-up, landscaping repairs, etc. Residential:... (800) ISON-1 usiness:... (877) 4-OM-1 T/TTY:... (800) Online Service Requests: Mail omd ustomer are enter P.O. ox hicago, IL

8 o you have suggestions for this book? In the interest of improving future editions, you are invited to submit suggestions for new installation standards or changes to existing standards. Write: Service and Meter ook istribution Standards ept. omd 2 Lincoln entre, 5 th Floor Oakbrook Terrace, IL Give the -number to which your suggestion applies, along with any supporting details, sketches, diagrams, or examples. Suggestions will not normally be answered individually, but if deemed appropriate, will be incorporated into subsequent editions of this book. Please do not send payments or inquiries about customer accounts to this address, as they cannot be processed there.

9 NW STANAR APPROV FOR PULI ISTRIUTION 7800 PAG 1 OF 3 PAG 1 OF 3 GNRAL SRVI RQUIRMNTS 480V AN LOW SYSTMS NOTS: APPLIATION THIS STANAR SHALL US TO SPIFY GNRAL RQUIRMNTS FOR SONARY SRVI ONNTIONS. GNRAL IN ORR THAT A USTOMR RQUIRING LTRI SRVI MAY PURHAS APPROPRIAT SRVI NTRAN QUIPMNT, AN WIR TH USTOMR S SRVI NTRAN QUIPMNT PROPRLY, TH INTRRUPTING APAITY RQUIR TO INTRRUPT TH MAXIMUM SUPPLY APAITY PLANN Y TH OMPANY FOR TH LOATION SHOUL TAKN INTO AOUNT. THIS INFORMATION WILL FURNISH Y TH OMPANY UPON RQUST. IF TH USTOMR RQUIRS THR-PHAS, THR-WIR SRVI, TH SRVI QUIPMNT AN ITS WIRING WILL VARY PNING ON WHTHR OR NOT (A) TH SUPPLY IS TO UNGROUN (480V ONLY), OR () ON OF TH PHASS IS TO GROUN. IF A GROUN ONUTOR IS TO INLU IN TH SONARY SRVI ONNTION IN AORAN WITH TH RQUIRMNTS OF TH NATIONAL LTRI O, TH ONNTION WILL ONSIR A THR-PHAS, FOUR-WIR SRVI. TH TOTAL RAT APAITY OF ALL ISONNTING MANS SUPPLI THROUGH A SINGL OR PARALLL SRVI ONNTION OF 480 VOLTS OR LSS SHALL NOT X 4,000 AMPRS. TH SRVI POINT, AS INIAT ON TH SPIFIATIONS FOR SRVI ONNTIONS, IS TH POINT OF MARATION TWN TH OMPANY S SYSTM AN TH USTOMR S PRMIS WIRING. IN GNRAL, FAILITIS LINWAR OF THIS POINT AR MAINTAIN Y TH OMPANY, AN FAILITIS LOAWAR OF THIS POINT (XPT MTRING QUIPMNT SUPPLI AN MAINTAIN Y TH OMPANY) AR MAINTAIN Y TH USTOMR. VOLTAG TOLRAN TH OMPANY SIGNS AN OPRATS ITS SYSTM SO THAT, UNR NORMAL ONITIONS, TH MAXIMUM MOMNTARY VOLTAG IP XPRIN Y ANY USTOMR WILL NOT X 9 VOLTS ON A 120 VOLT ASIS AT A FRQUNY OF 5 PR AY OR LSS. TH TOLRAN FOR MOR FRQUNT ISTURANS IS LOWR. ONTAT TH OMPANY FOR MOR INFORMATION. TH USTOMR SHALL PROVI INFORMATION AOUT ITS MOTOR LOAS, AN OTHR LARG TRANSINT LOAS, SO THAT TH OMPANY AN INTIFY AN PRVNT INTRFRN WITH SRVI TO OTHR USTOMRS. VOLTAG IPS XING 60% MAY OASIONALLY OUR AS A RSULT OF ANORMAL OPRATIONS. USTOMRS WITH SNSITIV QUIPMNT SHOUL TAK MASURS TO PRVNT THS IPS FROM INTRRUPTING OR INTRFRING WITH THIR OPRATIONS. 0 Notice:

10 PAG 2 OF 3 PAG 2 OF 3 OVRHA SRVI IN ORR THAT WORK ON Y TH OMPANY AN TH USTOMR PROPRLY OORINAT AN THAT PROPR LARANS MAINTAIN, TH USTOMR SHALL ONSULT TH OMPANY AOUT TH LOATION OF TH OMPANY POL TO WHIH TH SRVI ROP WILL FASTN AN TH HIGHT AT WHIH TH SRVI ATTAHMNT MUST PLA ON TH UILING TO NSUR PROPR LARANS. IF TH SRVI HA IS LOAT WITHIN FOUR FT OF A OMPANY POL, NO SRVI ATTAHMNT IS RQUIR AN TH OMPANY WILL ATTAH TH SRVI ROP WIRS IRTLY TO TH SRVI NTRAN WIRS. WHR FINISHING IS ONTMPLAT ON TH INSI OF TH WALL ON WHIH TH SRVI ATTAHMNT IS MOUNT, TH WASHRS OR PLATS, AN TH NUTS OR OLT HAS WHIH SUR TH ATTAHMNT, SHOUL OUNTRSUNK INTO TH WALL OR STUING AN ANY PROTRUING OLT NS UT OFF FLUSH WITH TH NUTS. IF OUNTRSINKING IS IMPRATIAL, TH MTAL PARTS ON TH INSI OF TH WALL SHOUL INSULAT. TH SRVI ATTAHMNT SHOUL LOAT AN INSTALL IN SUH A WAY AS TO APAL OF WITHSTANING A TNSION OF 1,000 POUNS WITHOUT AMAG TO TH STRUTUR. OVR-LNGTH SRVIS MAY IMPOS GRATR LOAS ON TH ATTAHMNT; ONSULT TH OMPANY FOR FURTHR INFORMATION. ALLOWAL LNGTH OF SRVI ROP: SRVI NTRAN APAITY SINGL-PHAS, 200A OR LSS SINGL-PHAS, OVR 200A TO 400A SINGL-PHAS, OVR 400A THR-PHAS, 200A OR LSS THR-PHAS, OVR 400A ALLOWAL LNGTH 150 FT RSINTIAL 135 FT NON-RSINTIAL 110FT ONSULT OMPANY 100FT ONSULT OMPANY 0 Notice:

11 PAG 3 OF 3 PAG 3 OF 3 UNRGROUN SRVI RSINTIAL: IF TH OMPANY INSTALLS AN UNRGROUN SONARY SRVI ONNTION, AN TH LNGTH OF TH SRVI ONNTION IS 100 FT OR LSS, TH SIZ OF AL FOR A SINGL-FAMILY RSIN WILL AS ON TH USTOMR S SRVI NTRAN APAITY. TH FOLLOWING TAL LISTS STANAR ALS AN TH APPROPRIAT MTR ONNTION VI. SRVI NTRAN APAITY STANAR AL SIZ MTR ONNTION VI 100A OR 200A 2-#2/0 (AL) & 1-#1 (AL) 200A 400A (80%) kcmil. (AL) & 1-#4/0 (AL) 320A IF TH SRVI ONNTION LNGTH IS GRATR THAN 100 FT, TH OMPANY WILL TRMIN IF SONARY SRVI IS PRATIAL. IF SO, VOLTAG ROP ONSIRATIONS MAY RQUIR TH US OF A LARGR SIZ OF AL THAN THAT SHOWN IN TH TAL FOR TH SRVI NTRAN APAITY. IN SUH AS, TH OMPANY WILL INFORM TH USTOMR OF TH AL SIZ PROVI. TH USTOMR WILL PROVI A MTR ONNTION VI WITH TRMINALS OF A SIZ AQUAT TO AOMMOAT TH AL. IN TH AS OF AN APARTMNT UILING WITH LSS THAN 4 UNITS, TH OMPANY WILL INFORM TH USTOMR OF TH AL SIZ NSSARY AN TH TYP OF MTR ONNTION VI TO PROVI FOR TRMINATION OF TH SRVI ONNTION. TH MTR ONNTION VI AN AL MUST FURNISH AN INSTALL IN AORAN WITH TH RQUIRMNTS OF TH OMPANY S STANAR SPIFIATIONS AN PRVAILING LOAL O (OR NATIONAL LTRI O, IF THR IS NO PRVAILING LOAL O). IF AN UNRGROUN SONARY SRVI ONNTION IS NOT M TO PRATIAL, A RSINTIAL SRVI STATION WILL RQUIR. NON-RSINTIAL: IF TH OMPANY INSTALLS AN UNRGROUN SRVI ONNTION, TH SIZ OF AL FURNISH AS STANAR FAILITIS WILL NORMALLY AS ON TH USTOMR S XPT MAN. TH OMPANY WILL INFORM TH USTOMR OF TH AL SIZ PROVI AN TH TYP OF MTR ONNTION VI TO PROVI FOR TRMINATION OF TH SRVI ONNTION. WHR TH OMPANY INSTALLS UT FOR AN UNRGROUN SRVI ONNTION, TH OMPANY NORMALLY WILL SIZ TH UT INSTALLATION FOR TH USTOMR S SRVI NTRAN APAITY. IF TH USTOMR INSTALLS AN UNRGROUN SRVI ONNTION, ONTAINING MOR THAN ON ST OF ALS, TO TH OMPANY S OVRHA ISTRIUTION SYSTM, TH OMPANY MAY RQUIR THAT TH ALS TRMINAT AT A SRVI PSTAL, AN WILL FURNISH TH PSTAL AN TH ISTRIUTION FAILITIS FROM IT TO TH POL. UNR NO IRUMSTAN WILL TH OMPANY ONNT MOR THAN FOUR STS OF SRVI ALS TO A SINGL POL OR PSTAL. AN LTRI SRVI STATION WILL RQUIR IN SUH ASS. 0 Notice:

12 This page intentionally left blank

13 NW STANAR APPROV FOR PULI ISTRIUTION 7802 PAG 1 OF 1 PAG 1 OF 1 SRVI PHAS ARRANGMNT APPLIATION: THIS STANAR SHALL US TO SPIFY TH STANAR ARRANGMNT AN PHASING OF SRVI ONNTIONS. NOTS: INFORMATION: 1. STANAR PHAS SIGNATIONS AT omd AR AS FOLLOWS: a. ON 120/240V SRVI, TH PHASS AR SIGNAT X,Y,Z. X IS NORMALLY TH LAING PHAS OF TH LIGHTING SRVI. Y IS NORMALLY TH LAGGING PHAS OF TH LIGHTING SRVI. Z IS ALWAYS TH HIGH PHAS (208V TO NUTRAL) OF A THR-PHAS SRVI. b. ON SINGL PHAS 120/208V SRVI, TH PHASS AR SIGNAT A,. c. ON ALL OTHR SRVIS, TH PHASS AR SIGNAT A,,. 2. STANAR PHAS ROTATION IS A-- OR X-Y-Z. IN SOM ARAS OF TH omd TRRITORY, TH STANAR PHAS ROTATION IS RVRS (--A OR Z-Y-X). TH USTOMR SHOUL ONFIRM TH PHAS ROTATION OF TH OMPANY SOUR, WHN ORRING SRVI. 3. TH USTOMR SHALL URALY AN LGILY MARK ALL SRVI NTRAN ONUTORS TO INIAT PHASING. TH ROMMN OLOR O FOR INIATING PHASING IS SHOWN IN TH FOLLOWING TAL. SRVI VOLTAG A OR X OR Y OR Z NUTRAL 208Y/120V LAK R LU WHIT 120/240V LAK R ORANG WHIT 480Y/277V OR 480V (3 WIR) ROWN PURPL YLLOW GRAY ANY VOLTAG (ALTRNAT MTHO) 1 AN 2 ANS 3 ANS 4 ANS 4. WHR A IFFRNT PHAS MARKING SYSTM IS IN US, TH USTOMR SHALL NOTIFY omd's INSTALLR FOR SRVI IS ONNT. 0 Notice:

14 This page intentionally left blank

15 NW STANAR APPROV FOR PULI ISTRIUTION 7815 PAG 1 OF 1 PAG 1 OF 1 SRVI ROP-OWN POL NOTS: APPLIATION: THIS STANAR SRIS TH RQUIRMNTS WHN AN OVRHA SUPPLY IS RQUIR, UT TH omd POL IS SO LOS TO TH UILING THAT A SRVI ROP XTN FROM A ROSSARM OR SONARY RAKT IS IMPRATIAL. INFORMATION: 1 USTOMR FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT (S FIGUR 1): A - SRVI HA. ALL NW SRVI HAS SHALL LOAT AS SHOWN IN FIGUR 1, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - SRVI RUN - SRVI RUN WIRS (ALLOW SUFFIINT WIR TO MAK ONNTION TO omd SRVI ROP WIRS). USTOMR TO NOTIFY omd OF SIZ OF SRVI RUN WIRS. - INSULAT LVIS AN OLT OR SRW ON 8 INH NTRS FOR AH SRVI ROP WIR. (NOT RQUIR IF SRVI HA IS WITHIN 4 FT OF TH POL.) 2 omd FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT: - SRVI ROP F - ONNTORS FOR ONNTING USTOMR WIRS TO SRVI ROP. 3 TH UILING ATTAHMNT (ITM "") OR TH SRVI ONNTORS (ITM "F") MUST LOAT TO PROVI A MINIMUM HORIZONTAL LARAN OF 3 FT TO TH SURFA OF TH POL. OMMUNIATION OMPANY QUIPMNT 40" MIN. 3'-0' MIN. 9'-6" MAX. 18" MIN. A F 8" 8" 16'-0" MAX. TO GROUN 3'-0" MIN. SRVI POINT 8" FIGUR-1 0 Notice:

16 This page intentionally left blank

17 NW STANAR APPROV FOR PULI ISTRIUTION 7820 PAG 1 OF 7 PAG 1 OF 7 SINGL PHAS SRVI ATTAHMNT NOTS: UP TO 400 AMPS APPLIATION: THIS STANAR SRIS TH RQUIRMNTS FOR TH ATTAHMNT OF SINGL PHAS SRVIS OF UP TO 400 AMPS TO A: MASONRY WALL (FIGUR-1), RIK VNR WALL (FIGUR-2), FRAM OR STUO WALL (FIGUR-3), PORH POST (FIGUR-4), WOO RISR (FIGUR-5), STL ONUIT RISR (FIGUR-6) OR ROOF PLAT INSTALLATION (FIGUR-7). INFORMATION: 1 USTOMR OWNS AN INSTALLS TH QUIPMNT AS SPIFI IN TH APPROPRIAT FIGUR: A - ROOF PLAT. TO AT LAST #10 GAUG SHT STL, AN OLTS TO AT LAST 1/4". ROOF PLATS OF TYP A OR TYP AR APTAL. TYP A-INSTALL FOUR ARRIAG OLTS THROUGH RAFTRS WITH WASHRS AN NUTS ON TH UNRSI OF TH RAFTRS. WHN PLATS AR INSTALL ON RAFTR SPAING OTHR THAN 16", INSTALL A 2x6 OAR UNR TWO RAFTRS. AS AN ALTRNATIV FOR ARRIAG OLTS WHR TH ROOF PLAT IS SO LOAT THAT TH FASTNING OF NUTS TO SUH OLTS IS IMPRATIAL, TH US OF FOUR 3-1/2" X 1/4" LAG SRWS WILL PRMITT. TH LAG SRWS SHALL SRW, NOT HAMMR, INTO RILL HOLS 3/16" IAMTR AN 2" P. TYP -INSTALL TWO ARRIAG OLTS ON AH SI OF RAFTR WITH NUTS AN SMALL PLAT ON UNRSI OF RAFTR. - SRVI HA. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25' AOV TH GROUN AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - SRVI RUN. - SRVI RUN WIRS. USTOMR SHOUL ALLOW A MINIMUM OF 18" YON TH SRVI HA TO MAK ONNTIONS TO SRVI ROP WIRS. - SRVI ATTAHMNT - FORKOLT WITH NUTS AN WASHRS OR YPLAT. F - MTAL FLASHING SAL WITH MASTI IS RQUIR WHR SRVI RUN XTNS THROUGH ROOF. G - 2X4 LOKING SOLILY INSTALL TWN RAFTRS IS RQUIR WHR RISR XTNS THROUGH ROOF. H - 5/8" GALVANIZ MOUNTING OLTS (WITH NUTS) INSTALL IN NTR LIN OF STUING. OMIT MIL OLT FOR A 4X4 RISR INSTALLATION. J - 4X4 OR 6X6 RISR OF PRSRVATIV TRAT YLLOW PIN, OR QUALLY STRONG AN URAL WOO. K - 2-1/4" GALVANIZ SQUAR WASHR. L - GALVANIZ IRON 1/8" X 1" X 12" PORH RA WITH FOUR 5/16" HOLS, ON TO INSTALL ON AH SI. US 1/4" X 2-1/2" GALVANIZ LAG SRWS. 0 Notice:

18 PAG 2 OF 7 PAG 2 OF 7 INFORMATION (ONTINU): M - RIGI STL ONUIT - 2-1/2" FOR 100 AMPR OR SMALLR, OR 3" FOR LARGR SRVI NTRAN QUIPMNT, OR MTALLI RAWAY OF QUIVALNT STRNGTH MAY US. N - P - MOUNTING LAMP WITH 1/2" OLTS, NUTS, AN WASHRS. FOR FRAM, STUO, OR RIK VNR, INSTALL OLTS IN NTR LIN OF STUING OR, IN TH AS OF TWO OLT STRAP ATTAHMNT, STRALING A STU WITH AN ANHOR PLAT RIGING STU. MTR ONNTION VI AAPTR. 2 omd FURNISHS AN INSTALLS TH FOLLOWING QUIPMNT: Q - R - ONNTORS FOR ONNTING USTOMR'S WIRS TO SRVI ROP. SRVI ROP A-N. 12" TO 18" R 4" TO 12" Q FIGUR-1 INSTALLATION ON MASONRY WALL 0 Notice:

19 " TO 18" 7820 PAG 3 OF 7 PAG 3 OF 7 R 4" TO 12" Q FIGUR-2 INSTALLATION ON RIK VNR WALL 12" TO 18" R 4" TO 12" Q FIGUR-3 INSTALLATION ON FRAM OR STUO WALL 0 Notice:

20 PAG 4 OF 7 PAG 4 OF 7 4" TO 12" L R Q L R 4" TO 12" Q FIGUR-4 INSTALLATION ON A PORH POST (HORIZONTAL OR VRTIAL) 0 Notice:

21 PAG 5 OF 7 PAG 5 OF 7 R S TAIL-A 6" PITH ROOF F Q 4'-0" MAX. - 4" X 4" RISR 10'-0" MAX. - 6" X 6" RISR G FLAT ROOF 2'-6" MAX. K H,K J SAM AS HIGHT AOV TOP OLT, UT NOT LSS THAN 4'-0" 4" TO 12" 6" J TAIL-A RIK ONSTRUTION J H,K J H,K FRAM ONSTRUTION RIK VNR ONSTRUTION FIGUR-5 SRVI ATTAHMNT WITH WOO RISR 0 Notice:

22 PAG 6 OF 7 PAG 6 OF 7 R 4" TO 12" M / I Q 18" MIN. N M F 2'-6" MAX. 4'-2" MAX. INSTALLATION ON RIK WALL G N 2'-8" MINIMUM M N N P INSTALLATION ON FRAM OR STUO WALL INSTALLATION ON RIK VNR WALL FIGUR-6 SRVI ATTAHMNT WITH STL ONUIT RISR 0 Notice:

23 PAG 7 OF 7 PAG 7 OF 7 11/16" HOL Approx. A 4-1 X 5/16" SLOTS 2" 1" 6" 5 7/8" 1" 4" 16" TYP A ROOF PLAT 4-3/8" SQUAR HOLS 11/16" HOL 4" Approx. 2" 7/8" A 3 1/4" 3 1/4" 5" 2 1/2" 3/4" 2 1/2" 3/4" 4" 4" TYP ROOF PLAT R 2'-6" A 18" 2'-6" F 6" 6" XTN AVS Q FLUSH AVS FIGUR-7 ROOF PLAT INSTALLATION 0 Notice:

24 This page intentionally left blank

25 NW STANAR APPROV FOR PULI ISTRIUTION 7825 PAG 1 OF 1 PAG 1 OF 1 SRVI ATTAHMNT - ROW HOUS 120/240 VOLT NOTS: APPLIATION: THIS STANAR SRIS TH RQUIRMNTS FOR INSTALLATION OF SRVI ATTAHMNTS ON ROW HOUS TYP RSINS. INFORMATION: 1 USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH 2 omd FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING FOLLOWING QUIPMNT IN AORAN WITH omd QUIPMNT: SPIFIATIONS: A- SRVI HA. ALL NW SRVI HAS SHALL F- SRVI ROP (S NOT 3) LOAT NO MOR THAT 25' AOV TH GROUN AN MUST POSITION SO THAT TH SRVI WIR G- SRVI ROP A N INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. H- ONNTORS FOR ONNTING USTOMR'S WIRS TO SRVI ROP. - SRVI RUN (S NOT 3) - SRVI RUN WIRS. USTOMR SHOUL ALLOW A 3 GNRALLY omd WILL INSTALL A SRVI ROP TO AH MINIMUM OF 18" YON TH SRVI HA TO SI OF TH PARTY WALL. HOWVR, WHN AJANT ROW MAK ONNTIONS TO SRVI ROP WIRS. HOUSS AR NOT INIVIUALLY OWN, A OMMON SRVI (S NOT 3) RUN TO A MULTIPL-MTR SOKT MAY US IF RQUST Y USTOMR. FOR SRVI RUN WIRS, ALLOW A MINIMUM - MTR ONNTION VI (S NOT 3) OF 18" YON TH SRVI HA TO MAK ONNTIONS TO TH SRVI ROP WIRS. - SRVI ATTAHMNT Y OTHR STANAR. A H G F PARTY WALLS 0 Notice:

26 This page intentionally left blank

27 NW STANAR APPROV FOR PULI ISTRIUTION 7830 PAG 1 OF 7 PAG 1 OF 7 THR PHAS SRVI ATTAHMNT NOTS: APPLIATION: UP TO 200 AMPS THIS STANAR SRIS TH RQUIRMNTS FOR TH ATTAHMNT OF THR PHAS SRVIS OF UP TO 200 AMPS TO A: MASONRY WALL (FIGUR-1), RIK VNR WALL (FIGUR-2), FRAM OR STUO WALL (FIGUR-3), PORH POST (FIGUR-4), WOO RISR (FIGUR-5), STL ONUIT RISR (FIGUR-6) OR ROOF PLAT (FIGUR-7). INFORMATION: 1 USTOMR FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT: A - ROOF PLAT. TO AT LAST #10 GAUG SHT STL, AN OLTS TO AT LAST 1/4". ROOF PLATS OF TYP A OR TYP AR APTAL. TYP A-INSTALL FOUR ARRIAG OLTS THROUGH RAFTRS WITH WASHRS AN NUTS ON TH UNRSI OF TH RAFTRS. WHN PLATS AR INSTALL ON RAFTR SPAING OTHR THAN 16", INSTALL A 2x6 TIMR UNR TWO RAFTRS. AS AN ALTRNATIV FOR ARRIAG OLTS WHR TH ROOF PLAT IS SO LOAT THAT TH FASTNING OF NUTS TO SUH OLTS IS IMPRATIAL, TH US OF FOUR 3-1/2" X 1/4" LAG SRWS WILL PRMITT. TH LAG SRWS SHALL SRW, NOT HAMMR, INTO RILL HOLS 3/16" IAMTR AN 2" P. TYP -INSTALL TWO ARRIAG OLTS ON AH SI OF RAFTR WITH NUTS AN SMALL PLAT ON UNRSI OF RAFTR. - SRVI HA. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25' AOV TH GROUN AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - SRVI RUN. - SRVI RUN WIRS. USTOMR SHOUL ALLOW A MINIMUM OF 18" YON TH SRVI HA TO MAK ONNTIONS TO SRVI ROP WIRS. - SRVI ATTAHMNT - FORKOLT WITH NUTS AN WASHRS OR YPLAT. F - MTAL FLASHING SAL WITH MASTI IS RQUIR WHR SRVI RUN XTNS THROUGH ROOF. G - 2X4 LOKING SOLILY INSTALL TWN RAFTRS IS RQUIR WHR RISR XTNS THROUGH ROOF. H - 5/8" GALVANIZ MOUNTING OLTS (WITH NUTS) INSTALL IN NTR LIN OF STUS. OMIT MIL OLT FOR A 4X4 RISR INSTALLATION. J - 4X4 OR 6X6 RISR OF PRSRVATIV TRAT YLLOW PIN, OR QUIVALNT. K - 2-1/4" GALVANIZ SQUAR WASHR. L - GALVANIZ IRON 1/8" X 1" X 12" PORH RA WITH FOUR 5/16" HOLS, ON TO INSTALL ON AH SI. US 1/4" X 2-1/2" GALVANIZ LAG SRWS. M - RIGI STL ONUIT - 2-1/2" FOR 100 AMPR OR SMALLR, OR 3" FOR LARGR SRVI NTRAN QUIPMNT, OR MTALLI RAWAY OF QUIVALNT STRNGTH MAY US. 0 Notice:

28 PAG 2 OF 7 PAG 2 OF 7 INFORMATION (ONTINU): N - P - MOUNTING LAMP WITH 1/2" OLTS, NUTS, AN WASHRS. FOR FRAM, STUO, OR RIK VNR, INSTALL OLTS IN NTR LIN OF STUING OR, IN TH AS OF TWO OLT STRAP ATTAHMNT, STRALING A STU WITH AN ANHOR PLAT RIGING STU. MTR ONNTION VI AAPTR. 2 omd FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT: Q - ONNTORS FOR ONNTING USTOMR'S WIRS TO SRVI ROP. R - SRVI ROP A-N. 12" TO 18" R 4" TO 12" Q FIGUR-1 MASONRY WALLS 0 Notice:

29 PAG 3 OF 7 PAG 3 OF 7 12" TO 18" R 4" TO 12" Q FIGUR-2 RIK VNR WALL INSTALLATION 12" TO 18" 4" TO 12" R Q FIGUR-3 FRAM OR STUO WALL INSTALLATION 0 Notice:

30 PAG 4 OF 7 PAG 4 OF 7 4" TO 12" L R Q L R 4" TO 12" Q FIGUR-4 SRVI ATTAHMNT ON PORH POST 0 Notice:

31 PAG 5 OF 7 PAG 5 OF 7 R S TAIL-A 6" PITH ROOF F Q 4'-0" MAX. - 4" X 4" RISR 10'-0" MAX. - 6" X 6" RISR G FLAT ROOF 2'-6" MAX. J SAM AS HIGHT AOV TOP OLT, UT NOT LSS THAN 4'-0" 4" TO 12" H,K 6" J TAIL-A RIK ONSTRUTION J H,K J H,K FRAM ONSTRUTION RIK VNR ONSTRUTION FIGUR-5 SRVI ATTAHMNT USING WOO RISR 0 Notice:

32 PAG 6 OF 7 PAG 6 OF 7 R f 4" TO 12" M / I Q 18" MIN. N M F 2'-6" MAX. 4'-2" MAX. INSTALLATION ON RIK WALL G N 2'-8" MINIMUM M N N P INSTALLATION ON FRAM OR STUO WALL INSTALLATION ON RIK VNR WALL FIGUR-6 SRVI ATTAHMNT WITH STL ONUIT RISR 0 Notice:

33 PAG 7 OF 7 PAG 7 OF 7 A 11/16" HOL Approx. 4-1 X 5/16" SLOTS 2" 6" 1" 5 7/8" 1" 4" 16" TYP A ROOF PLAT 4-3/8" SQUAR HOLS 11/16" HOL Approx. 2" 7/8" A 3 1/4" 3 1/4" 5" 2 1/2" 3/4" 2 1/2" 3/4" 4" 4" TYP ROOF PLAT R 2'-6" A 18" 2'-6" F 6" 6" XTN AVS Q FLUSH AVS FIGUR-7 ROOF PLAT INSTALLATION 0 Notice:

34 This page intentionally left blank

35 NW STANAR APPROV FOR PULI ISTRIUTION 7840 PAG 1 OF 1 PAG 1 OF 1 SRVI ATTAHMNT INSTALLATION NOTS: APPLIATION: 400 AMPS TO 1200 AMPS, 1-PH OR 3-PH THIS STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A SRVI NTRAN WITH APAITY OF 400 AMPRS UP TO 1200 AMPRS. SRVIS OVR 1200 AMPRS WILL NORMALLY RQUIR AN SS OR RSS. INFORMATION: 1 USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - SRVI HA. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25' AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - SRVI RUN. - SRVI RUN WIRS (ALLOW SUFFIINT WIR YON TH SRVI HA TO MAK ONNTIONS TO SRVI ROP WIRS) - GALVANIZ STL PLAT (1/4" X 6" X 16") - TWO FORK OLTS OR TWO 5/8" GALVANIZ OLTS WITH 5/8" NUTS, LOKWASHRS AN LVIS OR QUIVALNT. 2 omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: F - SRVI ROP A-NS G - ONNTORS FOR ONNTING USTOMR'S WIRS TO SRVI ROP. A 2'-0" TO 2'-6" G 8" 4" TO 12" 3" 2-11/16" HOLS 7,----1 I 4" 8" 16" 4" F j-~ 6" 0 Notice:

36 This page intentionally left blank

37 PAG 1 OF 2 NOTS: APPLIATION NW STANAR APPROV FOR PULI ISTRIUTION OX TYP SRVI HA ASSMLY THIS STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A OX TYP SRVI HA ASSMLY. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: PAG 1 OF 2 SRVI HA AN 1" LTRI SLAT OR QUIVALNT PANL WITH HOLS RILL TO AOMMOAT TH ONUTORS. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. OX SHALL MA OF AT LAST #10 GAUG SHT STL, GALVANIZ AFTR FORMING. IF ONSTRUT OF ANOTHR MTAL, IT MUST HAV OMPARAL STRNGTH AN WATHR RSISTAN. KNOKOUTS MAY INSTALL AS RQUIR IN AK, SIS, OR OTTOM. HOLS IN PANL (1" SLAT OR QUIVALNT) SHALL QUALLY SPA AN SHALL ALLOW AT LAST 1 1/2" OF MATRIAL TWN HOLS. TO PRVNT TH NTRAN OF WATR INTO TH SRVI RUN, TH PANL SHALL INSTALL AT SUH AN ANGL THAT TH LOWR INSI G OF TH HOL WILL NOT LOWR THAN TH TOP OUTSI G WHN INSTALL OR, IF TH PANL ANNOT INSTALL AT SUH ANGL, A UT SALING OMPOUN SHALL US. 4" TOP RMOVAL A WL F 9 16 " HOL I 3 8 " X 1 2 " STRAP IRON I FRONT RMOVAL RIVTS RILL AN TAP FOR SHT MTAL SRWS 1" LTRI SLAT OR QUIVALNT 2" 2" NUMR OF ONUITS IMNSION IN INHS A F Notice:

38 PAG 2 OF 2 PAG 2 OF 2 2. FIGURS 1 THROUGH 5 SHOW TH VARIOUS ARRANGMNTS OF WIRS IN TH SRVI HA. TH PHAS ARRANGMNT SHALL PRMIT ONNTION TO omd's SRVI ROP WITHOUT ROSSING WIRS OUTSI TH SRVI HA. (THR-WIR SRVI IS SHOWN; FOUR-WIR SRVI TO ARRANG SIMILARLY, S NOT 4.) 3. FOR SINGL-PHAS, THR-WIR, 120/240 VOLT SRVI, TH NUTRAL SHALL LOAT IN TH NTR POSITION. 4. FOR A THR-PHAS, FOUR-WIR SRVI OR THR-PHAS, THR-WIR SRVI WITH A FOURTH GROUN ONUTOR, TH PANL SHALL XTN ON POSITION AN TH NUTRAL OR GROUN ONUTOR SHALL LOAT AT ITHR N OF TH PANL. 5. TH LOATION OF SRVI HA SHALL APPROV Y omd FOR INSTALLATION. 6. AH ONUIT SHALL ONTAIN ON ONUTOR FOR AH PHAS OF TH SRVI ROP, AN A NUTRAL ONUTOR, IF SUH ONUTOR IS PRSNT IN TH SRVI ROP. IF A GROUN ONUTOR IS PRSNT, TH USTOMR SHALL INIAT SUH ONUTOR, WHIH MAY INSTALL WITH TH PHAS WIRS IN ANY ON OF TH ONUITS, OR IN A SPARAT ONUIT FIGUR 1 3 ALS 1 ONUIT FIGUR 2 6 ALS 2 ONUITS 0 0 3" FIGUR 3 9 ALS 3 ONUITS FIGUR 4 12 ALS 4 ONUITS 0 0 FIGUR 5 18 ALS 6 ONUITS 0 Notice:

39 NW STANAR APPROV FOR PULI ISTRIUTION 7852 PAG 1 OF 2 PAG 1 OF 2 RSS SRVI HA US IN UT SRVI NTRAN NOTS: APPLIATION THIS STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A RSS SRVI HA. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - A 1 INH LTRI SLAT OR QUIVALNT PANL WITH HOLS RILL TO AOMMOAT TH ONUTORS. a. FOR IMNSIONS AN SPAING OF HOLS FOR APPROPRIAT PANL, S TAILS 1 TO 4. b. FOR 1-PHAS, 3-WIR, 120/240 VOLT SRVI, TH NUTRAL SHALL LOAT IN TH NTR POSITION. c. FOR A 3-PHAS, 4-WIR SRVI OR 3-PHAS, 3-WIR SRVI WITH A FOURTH ONUTOR WHIH IS GROUN, TH PANL SHALL XTN ON POSITION. TH NUTRAL OR GROUN ONUTOR SHALL LOAT AT ITHR N OF TH PANL. d. FOR INSTALLATION, S TAIL 5. e. TO PRVNT TH NTRAN OF WATR, UT SALING OMPOUN SHALL US IF TH LOWR INSI G OF TH HOLS IS LOWR THAN TH TOP OUTSI G WHN TH PANL IS IN PLA. - RIP AP SHALL NOT XTN MOR THAN 8 INHS FROM UILING WALL UNLSS SPIFI PRMISSION IS OTAIN FROM omd. - LUGS FOR TH ONNTION OF TH SRVI ONNTION TO TH INSI US OR, IN TH AS OF A GROUN ONUTOR, TO TH INSI AL IF US Y TH USTOMR IN PLA OF US. USTOMR TO PROVI TH NSSARY NUTS AN OLTS AN ONNT LUGS TO US OR AL. TH LUGS WILL FURNISH AN ATTAH TO TH ALS Y TH USTOMR OR omd, WHIHVR FURNISHS TH AL (S ITM 4). LUGS FURNISH Y omd RQUIR TWO 9/16" HOLS ON 1 3 4" NTRS FOR TWO 1 2" OLTS. I I - TH LOATION OF A RSS SRVI HA SHALL APPROV Y omd FOR INSTALLATION. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. 2. omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: - SRVI ONNTION. PORTION WITHIN UILING TO USTOMR'S US SHALL NOT X THR FT. 0 Notice:

40 PAG 2 OF 2 PAG 2 OF 2 11" " " 13" " " 0 3" 6" 6" 3" 18" 3" 6" 6" 3" 18" TAIL 1 TAIL 2 3 ALS 6 ALS 15" " 0 3'-0" MAX " -.I 3" 6" 6" 3" 18" SRVI POINT A, TAIL 3 9 ALS 10 FT MIN. 25 FT MAX. TO GRA " 0 13" " 7" " " 7" TO USTOMR'S SWITHOAR LG. WALL 29" TAIL 5 TAIL 4 12 ALS 0 Notice:

41 NW STANAR APPROV FOR PULI ISTRIUTION 7860 PAG 1 OF 2 PAG 1 OF 2 USTOMR SRVI POL - RURAL APPLIATIONS OUTOOR MTR ONNTION VI 3-WIR, 120/240V SUPPLY ONLY NOTS: APPLIATION THIS STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A USTOMR SRVI POL, AN A 3-WIR, 120/240V, OUTOOR MTR ONNTION VI FOR RURAL APPLIATIONS. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - TRAT POL. (MINIMUM RQUIRMNTS - LASS #7; LNGTH, 25 FT). - SRVI NTRAN AL WITH LAMPS SPA AT A MAXIMUM OF THR FT, OR ONUTORS IN ONUIT. ALLOW SUFFIINT WIR TO MAK ONNTION TO SRVI ROP WIR. WHN ONUIT IS US, INSTALL MTAL ONUIT TO 10 FT AOV GROUN LVL AN NONMTALLI RIGI ONUIT WHR US AOV 10 FT. - SRVI HAS. INSTALL AOV TH RLAT FORK OLTS AS SHOWN IN TAIL-1. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - GROUN RO, ONUTOR AN ASSOIAT ONUIT AN LAMPS FOR GROUNING MTALLI OMPONNTS. - WATHR-TIGHT AL ONNTORS OR ONUIT ONNTORS. F - FORK OLTS. G - APPROV MTR ONNTION VI. 2. omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: H - SRVI ROP A-N. J - ONNTORS FOR ONNTING USTOMR'S WIR TO SRVI ROP. USTOMR TO NOTIFY omd OF AL SIZ. 0 Notice:

42 PAG 2 OF 2 PAG 2 OF 2 S TAIL-1 F SUPPLY SRVI ROP (PROVI Y omd) H J SRVI POINT F MTR SUPPLY (PROVI Y USTOMR) 60 TOP VIW GROUP ALS (OR ONUITS) ON 60 STOR OF POL 10" 4" TO 12" 6" 4" TO 12" TAIL-1 G 60" MAXIMUM 30" MINIMUM A INSTALLATION OF USTOMR SRVI POL AN OUTOOR MTR ONNTION VI 3-WIR, 120/240V ONLY RURAL INSTALLATIONS 0 Notice:

43 NW STANAR APPROV FOR PULI ISTRIUTION 7870 PAG 1 OF 2 PAG 1 OF 2 USTOMR SRVI POL - TRAILR PARK MTR INSTALLATION 3-WIR, 120/240V SUPPLY ONLY NOTS: APPLIATION THIS STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A USTOMR SRVI POL, AN A 3-WIR, 120/240V, OUTOOR MTR ONNTION VI FOR TRAILR PARK APPLIATIONS. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - TRAT POL. (MINIMUM RQUIRMNTS - LASS #7; LNGTH, 25 FT). - SRVI NTRAN AL WITH LAMPS SPA AT A MAXIMUM OF THR FT, OR ONUTORS IN ONUIT. ALLOW SUFFIINT WIR TO MAK ONNTION TO SRVI ROP WIR. WHN ONUIT IS US, INSTALL MTAL ONUIT TO 10 FT AOV GROUN LVL AN NONMTALLI RIGI ONUIT WHR US AOV 10 FT. - SRVI HA. INSTALL AOV FORK OLT AS SHOWN IN TAIL-1. SRVI HA SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - WATHR-TIGHT AL ONNTORS OR ONUIT ONNTORS. - TWO-POSITION APPROV MTR ONNTION VI WITH HA STAMP. PROVISION FOR FOUR TRAILRS MAY MA Y UPLIATING TH INSTALLATION ON TH OPPOSIT SI OF TH POL. XTNSION OF LIN ONUTORS TWN TH TWO LOWR MTR ONNTION VIS SHALL WATHR-TIGHT. USTOMR TO PROVI APPROPRIAT ISONNTING MANS. F - GROUN RO, ONUTOR AN ASSOIAT ONUIT AN LAMPS FOR GROUNING MTALLI OMPONNTS. G - FORK OLT. 2. omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT ONLY IF SRVI ROP TRMINATS AT TH POL. H - SRVI ROP A-N. J - ONNTORS FOR ONNTING USTOMR'S WIR TO SRVI ROP. USTOMR TO NOTIFY omd OF WIR SIZ. 0 Notice:

44 PAG 2 OF 2 PAG 2 OF 2 G S TAIL-1 SUPPLY SRVI ROP H J SRVI POINT 4" TO 12" 6" TAIL-1 A 60" MAXIMUM 30" MINIMUM F INSTALLATION OF USTOMR SRVI POL AN OUTOOR MTR ONNTION VI 3-WIR, 120/240V ONLY TRAILR PARK 0 Notice:

45 NW STANAR APPROV FOR PULI ISTRIUTION 7885 PAG 1 OF 2 PAG 1 OF 2 USTOMR SRVI POL - OVH TMP SRVI NOTS: APPLIATION THIS OUTOOR MTR ONNTION VI STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A USTOMR SRVI POL AN AN OUTOOR MTR ONNTION VI FOR OVRHA TMPORARY SRVI APPLIATIONS. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - TRAT POL (MINIMUM RQUIRMNTS - LASS #7, LNGTH, 25 FT); OR A RA, 6" X 6" TIMR OF AN APPROPRIAT LNGTH. RA 6" X 6" TIMR IS NOT APPROV FOR LOATIONS AT WHIH POPL ONGRGAT, SUH AS PINI OR ARNIVAL GROUNS. - SRVI HA. INSTALL AOV FORK OLT AS SHOWN IN TAIL-1. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. - SRVI NTRAN AL WITH LAMPS SPA AT A MAXIMUM OF THR FT, OR ONUTORS IN ONUIT. ALLOW SUFFIINT WIR TO MAK ONNTION TO SRVI ROP WIR. WHN ONUIT IS US, INSTALL MTALLI RIGI ONUIT TO 10 FT AOV GROUN LVL AN NONMTALLI RIGI ONUIT (WHR US) AOV 10 FT. - WATHR-TIGHT AL ONNTORS OR ONUIT ONNTORS. - APPROV MTR ONNTION VI. F - LOKAL, WATHR-TIGHT NLOSUR FOR ISONNTING MANS. G - GROUN RO, ONUTOR AN ASSOIAT ONUIT AN LAMPS FOR GROUNING MTALLI OMPONNTS. H - WHN A 6" X 6" TIMR IS US, INSTALL 2" X 4" RAS AN STAKS FASTN Y 5/8" MAHIN OLTS WITH TWO WASHRS AN TWO NUTS PR RA. J - FORK OLT. 2. omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: K - SRVI ROP A-N. L - ONNTORS FOR ONNTING USTOMR'S WIR TO SRVI ROP. USTOMR TO NOTIFY omd OF AL SIZ. 3. ALL WORK PRFORM AN QUIPMNT PROVI Y omd WILL AT TH USTOMR'S XPNS. 4. USTOMR SHALL NOT MOV OR TAMPR WITH TMPORARY SRVI FAILITIS AS LONG AS SRVI IS NRGIZ. 5. USTOMR IS RSPONSIL TO LOK TH SRVI ISONNT QUIPMNT TO PROTT PRSONS FROM ONTAT WITH NRGIZ PARTS. 6. USTOMR SHALL NOTIFY omd PROMPTLY WHN SRVI IS NO LONGR RQUIR. 0 Notice:

46 PAG 2 OF 2 7 PAG 2 OF 2 6'-6" 5'-3" 8'-0" < SRVI ROP TAK-OFF IN THIS IRTION ONLY K J S TAIL-1 L SRVI POINT A 4" TO 12" T TAIL-1 6" MIN. H 15" 15" H 5'-6" MAX. 3'-0" MIN. G F 6'-0" APPROX. H 6" MIN. 9" MAX. 3'-0" MIN. FOR TIMR L_J t ~ I I 2'-0" MIN. I I ~ lj-~- INSTALLATION OF USTOMR SRVI POL AN OUTOOR MTR ONNTION VI TMPORARY SRVI 0 Notice:

47 NW STANAR APPROV FOR PULI ISTRIUTION 7890 PAG 1 OF 2 PAG 1 OF 2 USTOMR UNRGROUN TMP SRVI NOTS: APPLIATION THIS OUTOOR MTR ONNTION VI STANAR SRIS TH RQUIRMNTS FOR TH INSTALLATION OF A USTOMR SRVI SUPPORT, AN AN OUTOOR MTR ONNTION VI FOR TMPORARY UNRGROUN SRVI APPLIATIONS. INFORMATION 1. USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: A - SRVI SUPPORT. TRAT TIMR - 4" X 4" X 8' (MINIMUM) TO ST A MINIMUM 3 FT IN TH GROUN ON PRIVAT PROPRTY. - APPROV MTR ONNTION VI. - LOKAL, WATHR-TIGHT NLOSUR FOR ISONNTING MANS. - GROUN RO, ONUTOR AN ASSOIAT ONUIT AN LAMPS PR LOAL O. - ONUIT, SRVI ONUTORS, INSULAT USHINGS, AN ONUIT LAMPS PR LOAL O. F - SRVI AL SIZ TO ONFORM TO LOAL O RQUIRMNTS. USTOMR WILL IRT URY AL AS SHOWN, UT NOT LOSR THAN 3 FT FROM omd's TRANSFORMR PA OR PSTAL. ANY USTOMR TRNHING IN ASMNT SHALL ON AS IRT Y omd. FOR IGGING, ALL JULI OR IGGR AT LAST 48 HOURS IN AVAN FOR AL LOATING. SAL AL NS FROM MOISTUR. MARK AL N LOATION WITH AN ASILY INTIFIAL STAK. USTOMR TO PROVI AN AITIONAL 10 FT OF AL FOR omd TO MAK ONNTIONS INSI TH TRANSFORMR OR PSTAL. 2. omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: G - omd SRVI PSTAL OR TRANSFORMR LOAT IN ASMNT. omd WILL PROVI ONNTORS FOR USTOMR'S ALS AN ONNT ALS WITHIN omd's NLOSUR. 3. ALL WORK PRFORM AN QUIPMNT PROVI Y omd WILL AT TH USTOMR'S XPNS. 4. USTOMR SHALL NOT MOV OR TAMPR WITH TMPORARY SRVI FAILITIS AS LONG AS SRVI IS NRGIZ. 5. SRVI TRNH MUST AKFILL WITH LAN MATRIAL. 6. USTOMR IS RSPONSIL TO LOK TH SRVI ISONNT QUIPMNT TO PROTT PRSONS FROM ONTAT WITH NRGIZ PARTS. 7. USTOMR SHALL NOTIFY omd PROMPTLY WHN SRVI IS NO LONGR RQUIR. 0 Notice:

48 PAG 2 OF PAG 2 OF 2 A G 30" MINIMUM AOV GRA STAK FOR LOATION OF AL MINIMUM 3' 18" 24" LOOP XSS 3' L ASMNT ASMNT F MINIMUM 6' INSTALLATION OF USTOMR UNRGROUN SRVI AN OUTOOR MTR ONNTION VI - TMPORARY SRVI 0 Notice:

49 NW STANAR APPROV FOR PULI ISTRIUTION 7951 PAG 1 OF 1 PAG 1 OF 1 USTOMR AL POL TO OVH SV ROP NOTS: A APPLIATION THIS STANAR SRIS TH RQUIRMNTS FOR INSTALLATION OF A USTOMR'S AL POL WITH AN UNRGROUN SONARY SRVI ONNTION TO A omd OVRHA SONARY SRVI ONNTION (SRVI ROP). INFORMATION 1 USTOMR FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT IN AORAN WITH omd SPIFIATIONS: SRVI ROP N M L 6" 8" MAX. A- TRAT POL. (MINIMUM RQUIRMNTS - LASS #7; LNGTH, 25 FT). USTOMR SHALL ONSULT ANSI 05.1 MINIMUM STTING PTH FOR LASS AN LNGTH OF POL INSTALL. RFR TO ITM "L" FOR MAXIMUM HIGHT RSTRITION. SRVI POINT P H - GALVANIZ RIGI MTAL ONUIT (N AN ON 10-FOOT STION). TH USTOMR SHALL SPIFY TH QUARANT OF TH POL IN WHIH TH ONUIT SHALL INSTALL. - ONUIT USHING (IF URI PORTION OF AL IS NOT IN UT). - GALVANIZ ONUIT STRAPS AN/OR LAG SRWS AS RQUIR. - GROUN RO, ONUTOR AN LAMPS FOR GROUNING MTALLI ONUIT ON POL. G 5'-0" MAX. F- OUTOOR AAPTR OUPLING FOR MTALLI TO NONMTALLI ONUIT. G- NONMTALLI RIGI ONUIT. F 6" H- AL SUPPORT FOR AL LARGR THAN #4/0. 6" J- AL, AN ONUIT (IF INSTALL). AL TO XTN FIV FT YON ONUIT RISR ON POL. USTOMR TO NOTIFY omd OF AL SIZ. K- SALING OMPOUN. IF UT OR ONUIT NTRS UILING, SPA TWN TH AL AN ONUIT SHALL SAL. 10'-0" APPROX. L- SRVI HA. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25' AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. M- FORK OLT. GROUNLIN 2 omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: N- SRVI ROP A-N. K 2'-0" MIN. P- ONNTORS FOR ONNTING USTOMR'S AL SRVI ROP (SRVI POINT). J 0 Notice:

50 This page intentionally left blank

51 NW STANAR APPROV FOR PULI ISTRIUTION 7952 PAG 1 OF 3 PAG 1 OF 3 UST UNG S TO OVH SS NOTS: APPLIATION: THIS STANAR SRIS TH RQUIRMNTS TO ONNT A USTOMR UNRGROUN SONARY SRVI TO AN OVRHA LTRI SRVI STATION (SS). TH SRVI POINT FOR THIS INSTALLATION IS TH SONARY TRMINALS OF TH TRANSFORMR. INFORMATION: 1 USTOMR FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT ON TH omd POL, IN AORAN WITH omd STANARS. A - GALVANIZ RIGI MTAL ONUIT (N AN ON 10-FOOT STION). omd TO SPIFY TH QUARANT OF TH POL IN WHIH TH ONUIT SHALL INSTALL. - PROVISIONS FOR ONNTION OF GROUN WIR TO AH ONUIT Y ON OF TH FOLLOWING MTHOS 1. AWL A 2-FOOT LNGTH OF #2 AR TINN OPPR ONUTOR (19-STRAN) TO TH ONUIT PRIOR TO INSTALLING AL: OR 2. PROVI GROUN LAMP ONNTORS (URNY TYP "GAR" OR omd-approv QUIVALNT) TO AOMMOAT #2 AR TINN OPPR ONUTOR (19-STRAN). - GALVANIZ ONUIT STRAPS AN LAG SRWS OR, IF MULTIPL STS OF 5 ONUITS, MULTIPL ONUIT SUPPORT RAKTS INSTALL WITH I 8 " X 14" MAHIN OLTS, 2 1 I 4" SQUAR FLAT WASHRS AN NUTS, AN MULTIPL SUPPORT RAKTS OR ONUIT STRAP KITS (ALUMA-FORM RAKT, PROUT #6-SO-24 OR QUIVALNT). RFR TO OUTOOR AAPTR OUPLING FOR MTALLI TO NONMTALLI ONUIT. ONUIT USHING TO INSTALL IF U-GUAR IS US AOV FIRST 10-FOOT STION. - ONUIT USHING (IF URI PORTION OF AL IS NOT IN ONUIT). F - AL TO XTN AT LAST 5 FT YON RISR ON POL WITH SUFFIINT SLAK TO ONNT TO omd's FAILITIS (S ITM "M"). USTOMR TO INFORM omd OF AL SIZ. G - NONMTALLI RIGI ONUIT OR U-GUAR. omd TO SPIFY TH POINT AOV TH GROUN AT WHIH TH NONMTALLI RIGI ONUIT OR U-GUAR SHALL TRMINAT. H - ONUIT STRAPS, KITS, OR MULTIPL-RISR RAKTS (FOR SIZ AN TYP S ITM "") OR LAG SRWS. J - NONMTALLI ONUIT OUPLING. K - AL SUPPORT FOR AL LARGR THAN #4/0 AWG. L - SALING OMPOUN. IF ONUIT NTRS UILING, SPA TWN TH AL AN ONUIT SHALL SAL. M - AL TRMINALS (2-HOL NMA SPA LUGS) IF RQUIR Y omd. N - SRVI HA. ALL NW SRVI HAS SHALL LOAT NO MOR THAN 25 FT AOV TH GROUN, AN MUST POSITION SO THAT TH SRVI WIR INSTALLATION HAS SAF ASS FROM AN XTNSION LAR. 0 Notice:

52 PAG 2 OF 3 PAG 2 OF 3 INFORMATION (ONTINU): 2 omd FURNISHS, INSTALLS, AN MAINTAINS TH FOLLOWING QUIPMNT: N P P - POL (LTRI SRVI STATION SUPPORT). K,L Q - GROUN RO FOR GROUNING TRANSFORMR. M R - GROUNING ONUTOR AN ONNTION TO GROUN LAS ON MTALLI ONUIT OR ONNTION TO GROUN LAMP ONNTOR. H G 5'-0" MAX 6" 6" A R 10'-0" APPROX I GROUN 2'-0" MIN R F SINGL ONUIT RISR Q 0 Notice:

53 PAG 3 OF 3 PAG 3 OF " H I ln/ ~ r~ TOP VIW / J M N K,L P MAX. 10'-0" - H R G MAX. 10'-0" A 10" P S TAIL-1 R TAIL-1 A 10'-0" APPROX 9'-0" R Q F MULTIPL ONUIT RISRS 0 Notice:

54 This page intentionally left blank

55 NW STANAR APPROV FOR PULI ISTRIUTION 7960 PAG 1 OF 3 PAG 1 OF 3 UST OWN LIGHTING ON OM IST POL NOTS: APPLIATION: THIS STANAR SRIS RQUIRMNTS FOR INSTALLATION OF A USTOMR OWN LIGHTING UNIT ON A omd ISTRIUTION SYSTM POL. INFORMATION: 1 A USTOMR-OWN LIGHTING UNIT SRV UNR omd's USK-TO-AWN LIGHTING LIVRY LASS MAY INSTALL Y A USTOMR QUALIFYING FOR SUH SRVI ON A omd ISTRIUTION SYSTM POL, PROVI SUH INSTALLATION IS ONSIR PRATIAL Y omd AN TH USTOMR PAYS TH OST OF ANY POL OR SYSTM RVISION THAT IS NSSARY TO AOMMOAT TH LIGHTING UNIT. SUH INSTALLATION SHALL NOT PRMITT (a) ON A POL ON WHIH A TRANSFORMR, APAITORS, A STRT OR ALLY LIGHT, A AL RISR, OR OTHR MAJOR QUIPMNT IS INSTALL, OR (b) IF TH WIGHT OF TH LIGHTING UNIT OR TH LNGTH OF TH MOUNTING RAKT IS XSSIV. ALSO, TH INSTALLATION MAY NOT PRATIAL ON AN XISTING POL AUS TH AVAILAL SPA TWN omd's AN OMMUNIATION OMPANIS' FAILITIS IS NOT AQUAT TO PROVI PROPR LARANS. IN THIS AS, HOWVR, IF TH USTOMR RQUSTS, AN IF TH USTOMR ARRANGS WITH TH OMMUNIATION OMPANIS FOR TH RVISION OF THIR FAILITIS, omd WILL RVIS ITS FAILITIS TO PROVI SUH LARANS AT TH USTOMR'S XPNS. 2 TH USTOMR SHALL FURNISH, INSTALL AN MAINTAIN A LIGHTING UNIT, ON PR POL, WHIH OPRATS AT 120 VOLTS, WITH TH NSSARY ONTROL, WIRS AN APPURTNANS. TH LIGHTING UNIT INSTALLATION SHALL NOT X 560 FOOT-POUNS, WHIH IS TRMIN Y MULTIPLYING TH LNGTH OF TH RAKT Y TH WIGHT OF TH LUMINAIR. 3 TH HIGHT OF TH LOWST PART OF TH LIGHTING INSTALLATION SHALL ONFORM TO ALL APPLIAL OS. 4 TH LIGHTING UNIT SHALL INSTALL AN MAINTAIN Y QUALIFI PRSONNL UNR TH SUPRVISION OF A SUPRVISING LTRIIAN OR LTRIAL ONTRATOR. 5 IF A POL UPON WHIH A LIGHTING UNIT IS INSTALL RQUIRS RPLAMNT, omd WILL, XPT IN MRGNIS, NOTIFY TH USTOMR 48 HOURS FOR SUH WORK IS SHUL TO GIN, AN TH USTOMR WILL OORINAT TH USTOMR'S WORK TO RMOV AN RLOAT SUH LIGHTING UNIT WITH omd. IN TH VNT THAT SUH AVAN NOTI ANNOT MA OR TH USTOMR ANNOT MT omd's SHUL, omd WILL LAV TH LIGHTING UNIT IN PLA, TMPORARILY ONNT TH FIXTUR WIRS TO TH omd SUPPLY ON TH NW POL, UT AWAY TH OL POL AOV AN LOW TH FIXTUR SUPPORT AN LASH TH PORTION OF TH OL POL SUPPORTING TH FIXTUR TO TH NW POL. TH USTOMR SHALL WITHIN A RASONAL LNGTH OF TIM, TRANSFR TH LIGHTING UNIT TO TH NW POL AN RMOV TH LASH PORTION OF TH OL POL. IF TH OMMUNIATION OMPANIS' FAILITIS AR TO TRANSFRR TO TH NW POL, TH USTOMR SHALL TRANSFR TH USTOMR'S FAILITIS PRIOR TO TH AY ON WHIH TH OMMUNIATION OMPANY HAS SHUL ITS WORK. 0 Notice:

56 PAG 2 OF 3 PAG 2 OF 3 INFORMATION (ONTINU): 6 INSTALLATION RQUIRMNTS: TH LIGHTING UNIT SHALL INSTALL IN TH POL SPA SIGNAT Y omd. TH LUMINAIR SHALL LOAT SO THAT TH MOUNTING RAKT IS PRPNIULAR TO omd's OVRHA ISTRIUTION LIN, OR IF NSSARY, NO MOR THAN 45 GRS FROM SUH PRPNIULAR. FIGUR-1 ILLUSTRATS AN INTIFIS TH LARANS THAT AR RQUIR TWN TH LIGHTING UNIT AN TH XISTING OR PROPOS LTRIAL AN OMMUNIATION FAILITIS ON A POL: LARAN SHALL 12 INHS MINIMUM FOR A ISTAN OF FIV FT FROM TH FA OF TH POL. LARAN SHALL 8 INHS MINIMUM TWN TH LUMINAIR AN TH FA OF TH POL FOR A ISTAN OF TWO FT XTNING OWNWAR FROM TH SPA SRI AOV. LARAN OF RIP LOOPS SHALL A MINIMUM OF 12 INHS FROM OMMUNIATION ALS, OR A MINIMUM OF 24 INHS IF TH OMMUNIATION ALS AR INSTALL ON A ROSSARM. omd WILL SPIFY FOR AH POL TH ISTAN FROM TH GROUNLIN TO TH OTTOM OF TH omd SPA AN TH TOP OF TH OMMUNIATION SPA. 7 USTOMR FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT (S FIGUR-1 AN TAIL "A") A F - G - H - J - LUMINAIR AN LAMP (NOT SHOWN). MOUNTING RAKT FOR LAMP. HARWAR RQUIR TO MOUNT RAKT WITH LAMP TO POL, INLUING APPROPRIAT FASTNRS. SUPPLY SHALL TWO INSULAT #8 AWG WIRS (OPPR OR ALUMINUM), USING WHIT FOR NUTRAL AN LAK FOR PHAS. WIRS SHALL LONG NOUGH FOR ONNTION TO omd's ONUTORS (ITM "L") AN LFT OIL AT TH AS OF MOUNTING RAKT (ITM ""). USTOMR SHALL ONNT LIN AN LOA WIRS TO SPARAT ONTROL VI (ITM "H"), IF ANY. FUS. A FUS ONNTOR (SUH AS USSMANN, H, IAL-UHANAN SLK, FUSTK LASTIMOL 65U) WITH LASS FUS IS APPROV AS A ISONNTING MANS FOR TH PHAS WIR OF TH SUPPLY (ITM ""). TH FUS VI SHALL INSTALL ON TH LIN SI OF TH ONTROL VI (ITM "H"), AOV TH RIP LOOP AT A MINIMUM ISTAN OF 12 INHS FROM TH MOUNTING RAKT (ITM "") AN TH ONTROL VI (ITM "H"). ISONNTAL GROUN ONNTOR FOR GROUN WIR (ITM "G"), TO MOUNT GROUNING. GROUN WIR, AN INSULAT #6 AWG (OPPR OR ALUMINUM), GRN IN OLOR. WIR SHALL ONNT TO ISONNTAL GROUN ONNTOR (ITM "F"), AN AQUAT IN LNGTH FOR ONNTION TO ITM "L". WIR SHALL LFT OIL AT AS OF MOUNTING RAKT (ITM ""). ONTROL VI. PHOTOLTRI LL MAY PART OF LUMINAIR OR SPARATLY MOUNT ON POL (S TAIL-A). IF ONTROL VI IS SPARAT, USTOMR SHALL ONNT LIN AN LOA WIRS AS SRI IN ITM "". INTIFIATION TAP. R RTRORFLTIV, WATHR-RSISTANT TAP WRAPP AROUN MOUNTING RAKT (ITM "") AJANT TO TH LUMINAIR. WRAPPING SHALL 6 INHS WI, AN MUST VISIL FROM TH GROUN. 0 Notice:

57 PAG 3 OF 3 PAG 3 OF 3 INFORMATION (ONTINU): 8 omd FURNISHS, INSTALLS AN MAINTAINS, SUJT TO TH PROVISIONS OF TH GNRAL TRMS AN ONITIONS APPLIAL TO TH USK-TO-AWN LIGHTING AN GNRAL LIGHTING LIVRY LASSS: K - ISTRIUTION SYSTM POL. L VOLT IRUIT. M - PLASTI MOLING AN FASTNRS. N - ONNTORS FOR ONNTION OF SUPPLY WIRS (ITM "") AN GROUN WIR (ITM "G") TO omd's SUPPLY. 5'-0" L OTTOM OF omd SPA N 12" MIN. M J 24" F omd TO SPIFY G F K G 8" MIN. MIN. 12" TO OMM. AL MIN. 24' TO OMM. ARM fl TOP OF OMMUNIATION OMPANY SPA H K omd TO SPIFY FIGUR -1 TAIL - A 0 Notice:

58 This page intentionally left blank

59 NW STANAR APPROV FOR PULI ISTRIUTION 7973 PAG 1 OF 2 PAG 1 OF 2 TRAFFI SIGNAL/STRT LT SV ONN/OVH NOTS: APPLIATION TRANSMITTR ONNTIONS OVRHA TO UNRGROUN SRVI THIS STANAR SRIS RQUIRMNTS FOR USTOMR OVRHA ONNTION OF TRAFFI SIGNALS, STRT LIGHTING, AN TA TRANSMITTRS TO A omd UNRGROUN SRVI. INFORMATION 1 USTOMR FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT: A- AL. - ONUIT USHING, IF URI PORTION OF AL IS NOT IN UT. - GROUN RO, ONUTOR, AN ASSOIAT ONUIT AN LAMPS FOR GROUNING MTALLI OMPONNTS. - GALVANIZ RIGI MTAL ONUIT WITH N. - GALVANIZ ONUIT STRAPS. F- JUNTION OX. A WATHR-TIGHT, LOKAL, GALVANIZ OX FOR ONTROL VI AN ISONNTING MANS OR AN APPROV ONULT OR QUIVALNT FOR ISONNTING MANS IF ONTROL VI OR ISONNTING MANS IS INSTALL ON omd POL. JUNTION OX SHOUL INSTALL FAING TH AJANT PROPRTY LIN. S STION A-A FOR ALTRNAT INSTALLATION POSITIONS. G- GROUN STU FOR NUTRAL ONNTION, US WHN OVRURRNT VI IS INSTALL. H- SRVI ALS. omd TO SPIFY LNGTH OF ALS. USTOMR TO ONNT ALS IN JUNTION OX AN OIL XSS AL AT JUNTION OX. omd TO INSTALL ALS AOV JUNTION OX AN ONNT TO OVRHA LIN. J- WATHR-TIGHT ONNTOR AN ONUIT ATTAH TO POL TO AOMMOAT U-GUAR. TH ONUIT SHALL SAL WITH A SALANT APPROPRIAT FOR US NAR LTRIAL QUIPMNT. K- OVRURRNT VI OR ISONNTING MANS. 2 omd FURNISHS, INSTALLS AN MAINTAINS TH FOLLOWING QUIPMNT: L- U-GUAR TO NLOS SRVI ALS AOV JUNTION OX, ITM "F". 0 Notice:

Service and Meter Requirements Edition

Service and Meter Requirements Edition Service and Meter Requirements 2018 dition Summary of hanges in This dition Number hange 9110 Standard title revised from MTRING - GNRAL INFORMATION to MTRING - GNRAL RQUIRMNTS. This will match the index

More information

Backwater Valves Series swing-check Backwater Valve shown installed in a manhole terminal.

Backwater Valves Series swing-check Backwater Valve shown installed in a manhole terminal. ackwater Valves 259 67800 Series swing-check ackwater Valve shown installed in a manhole terminal. 260 ackwater Valves JOSAM 67100A OAT AST IRON AKWATR, PLASTI ALL-LOAT, LASTOMR SAT, RONZ AG AN OTTOM OUTLT

More information

8. INSTALLATION/WIRE CONNECT GUIDE

8. INSTALLATION/WIRE CONNECT GUIDE 8. INSTALLATION/WIRE CONNECT GUIDE Bfor Starting 1. This st is xclusivly for us in cars with a ngativ groun, 12 V powr supply. 2. Ra ths instructions carfully. 3. B sur to isconnct th attry - trminal for

More information

Konsole Typ Traglast/Paar kg

Konsole Typ Traglast/Paar kg Carrying consols for asy an fficint i chang on th prss Konsol Typ 1835- Konsol Typ 1835- Colour: RAL 1004, goln yllow Carrying consol, hanging Th carrying consols ar hung in th hooks on th i changing si

More information

R404A/R507 R407C. Danfoss Compressors V 50 Hz & 60 Hz REFRIGERATION & AIR CONDITIONING DIVISION. Quick reference

R404A/R507 R407C. Danfoss Compressors V 50 Hz & 60 Hz REFRIGERATION & AIR CONDITIONING DIVISION. Quick reference aking morn living possil R07 anfoss omprssors 0-0 V 50 Hz & 60 Hz RFRIGRATIO & AIR OITIOIG IVISIO Quik rfrn Rfrigrant Appliation Frquny BP T F FR ø6 0.6 ø9 ø6 ø6 ø6 65 5 5 8595-830-3 66 66 57 56 BP 50

More information

Pre-Load Bolt Assemblies BS EN HRC Assemblies BAPP

Pre-Load Bolt Assemblies BS EN HRC Assemblies BAPP Pr-Loa Bolt Assmblis Pr-Loa Bolt Assmblis k BS EN 14399-10 HRC Hxagon Bolt Dimnsions b(rf.) c a s w k kw r s pb c max. min. max. max. min. max. min. min. nom. max. min. min. min. max. min. M12 1.75 30

More information

4 POL 4 POL 8 POL 8 POL. CONNECTOR SPECIFICATION / Steckverbindungs-Eigenschaften L =[mm] see table TABLE 1

4 POL 4 POL 8 POL 8 POL. CONNECTOR SPECIFICATION / Steckverbindungs-Eigenschaften L =[mm] see table TABLE 1 POL 0.0 L =[mm] see table. POL 0/0/0 00 URGR 0/0/0 RUNS NO: RWN: HK': PPR: RV M x.. M x. POL POL ONNTOR SPIFITION / Steckverbindungs-igenschaften 0V / VOLTG RTING/etriebsspannung 0V / FORMT: tb-prod- RVISION:

More information

SPIRAL STAIR INSTALLATION GUIDE. Salter -Wood Tread Covers -Continuous Sleeve -Aluminum Handrail -Primed or Powdercoated

SPIRAL STAIR INSTALLATION GUIDE. Salter -Wood Tread Covers -Continuous Sleeve -Aluminum Handrail -Primed or Powdercoated 29 SPIRAL STAIR INSTALLATION GUI Salter -Wood Tread Covers -Continuous Sleeve -Aluminum Handrail -Primed or Powdercoated PARTS 1 2 3 BASPLAT BOTTOM BALUSTR MAIN BALUSTR 4 5 6 CNTR BALUSTR CNTR COLUMN TRA

More information

Overload Relays D-LINE Bimetallic

Overload Relays D-LINE Bimetallic Ovrloa Rlays D-LINE Bimtalli LR2D23kk LA7D901 LA7D03 Bi-mtalli ovrloa rlays LR*D ovrloa rlays ar sin for irt to D-lin ontators. To mount ths ovrloas sparatly s Pa -33 for sparat mount kits. D-lin ovrloa

More information

Danfoss Compressors for light commercial applications V 50 Hz. R404A/R507 R134a R290. Quick reference

Danfoss Compressors for light commercial applications V 50 Hz. R404A/R507 R134a R290. Quick reference Making MORN living possil R404A/R507 R134a R290 anfoss omprssors for light ommrial appliations 220-240 V 50 Hz RFRIGRATION & AIR ONITIONING IVISION Quik rfrn 1 Phas 3 Phas Rfrigrant R134a R404A R290 R404A

More information

ISOMETRIC VIEW SCALE: 1/2

ISOMETRIC VIEW SCALE: 1/2 NOTS:.. THIS RWING SRIS TH UL xx SRIS LTRONI UL PUMP. UNLSS OTHRWIS SPII, LL VIWS R MOLS -c, -c OR -c. TURS INLU: - THR PHS RUSHLSS MOTOR WITH NOYMIUM MGNTS - INTGRT LTRONIS WITH SP ONTROL - WT MOTOR SIGN,

More information

Transport anchor system. Lifting Socket. Flat Lifting Socket. Short Anchor

Transport anchor system. Lifting Socket. Flat Lifting Socket. Short Anchor Transport anchor systm W provi a complt Transport anchor systm, from various Transport Anchors, lifting vics to plastic accssoris as wll as Tchnical support. Casting in th anchors into th concrt with avanc

More information

February 9, Bid Opening Date: February 13, 2018 February 20, 2018

February 9, Bid Opening Date: February 13, 2018 February 20, 2018 ebruary 9, 0 OR O OUNTY OMMISSIONRS ORNG OUNTY, LORI Y--T / NUM # STRN RGIONL WTR SUPPLY ILITY IMPROVMNTS PHS III id Opening ate: ebruary, 0 ebruary 0, 0 This addendum is hereby incorporated into the bid

More information

AUSTRALIAN SPORTS COMMISSION AIS - HPC HPC SSSM BUILDING PACKAGE 1 WORKS

AUSTRALIAN SPORTS COMMISSION AIS - HPC HPC SSSM BUILDING PACKAGE 1 WORKS AIS - P P SSSM UILING PAKAG WORKS 23-5844 RAWING INX - WORKS & 2 PROJT No. ST TITL 6. WORKSOP AR - WORKS & 2 23-5844 9-A OVR & RAWING INX 23-5844 9-A SIT PLAN & STIONS 23-5844 9-A SIT TAIL PLANS 23-5844

More information

Automatic Plunger Greasing System For Triplex and Quintuplex Pumps

Automatic Plunger Greasing System For Triplex and Quintuplex Pumps utomatic Plunger reasing System or Triplex and Quintuplex Pumps Revision 0 November 12, 2007 TL O ONTNTS 1 escription, Installation, and Operation of System 2 Recommended rease 3 Maintenance and Technical

More information

BKF Off-line filter / cooler unit

BKF Off-line filter / cooler unit BKF Off-lin filtr / coolr unit Compact dsign Filling function optional (BKF 18/3) Easy installation Low- nois pump DIN filtr lmnts Efficint plat hat xchangr DE 38 1/14 Pag 1/6 Bühlr Tchnologis GmbH D -

More information

A FORMAT: Met-lega-master-tb-prod-A3 REVISION: C DATE: 2017/02/06

A FORMAT: Met-lega-master-tb-prod-A3 REVISION: C DATE: 2017/02/06 RL WITH OMPON UL SHT(S) (QTY. VRIL) LL PRT NO. QTY. O TP PRTS ORINTTION RFR TO SHT RO LL NO. OF RLS WITH M G (QTY. VRIL) RL WITH OMPON NTR UL SHT(S) (QTY. VRIL) 0.0 MOSS TP RO LL NO. OF RLS WITH M G (QTY.

More information

Control of codling moth with reduced risk insecticides in pears 2002

Control of codling moth with reduced risk insecticides in pears 2002 Chmial Control/Nw Prouts Control of oling moth with ru risk instiis in pars 2002 R. A. Van Stnwyk, S. K. Zolbro an R. M. Nomoto Dpt. of E.S.P.M., Univrsity of California, Brkly, CA Kywors: Agri-Mk, abamtin,

More information

GIGABIT MAGNETIC JACK 1x1 LED

GIGABIT MAGNETIC JACK 1x1 LED GIGIT MGNTI JK x L MOLX -XXXX WW YY Z FRONT VIW NON L VRSION P/N -00 NOTS: - SHIL MTRIL: STINLSS STL (GROUN PINS R SOLR IPP) - PLSTI MTRIL: PT, LK, UL V-0 - RJ TRMINLS MTRIL: OPPR LLOY ONTT PLTING: 0.

More information

SPIRAL STAIR INSTALLATION GUIDE

SPIRAL STAIR INSTALLATION GUIDE SPIRAL STAIR INSTALLATION UI cono Stair -Vinyl Handrail -alvanized Illustrations are general and may not match your specific stair design. PARTS 1 4 BASPLAT MAIN BALUSTR CNTR BALUSTR 5 6 7 CNTR COLUMN

More information

((36220*8' 4,/e/ON A %1'.2, PICTURE WINDOW - LARGE MISSILE IMPACT. .,e' ANDRE VV > 4, PICTURE WINDOW IMPACT E 2 MAX. UNIT SIZE IMPACT RATI NG

((36220*8' 4,/e/ON A %1'.2, PICTURE WINDOW - LARGE MISSILE IMPACT. .,e' ANDRE VV > 4, PICTURE WINDOW IMPACT E 2 MAX. UNIT SIZE IMPACT RATI NG PICTUR WINOW - LARG MISSIL GNRAL NOTS: TH PROUCT SHOWN HRIN IS SIGN AN MANUFACTUR TO MPLY WITH TH FLORIA UILING (FC), CURRNT ITION INCING TH HIGH VLOCITY HURRINCAN ON (HVH) AN IS RAT FOR WIN ON 4 MISSIL

More information

DRAWING APPROVAL SHEET

DRAWING APPROVAL SHEET O S.J. RWING PPROVL SHT RWING NUMR: MMRO--0-M-0 RWING TITL:Passenger Seats Layout ISSU T OMPIL Y HK Y STRSS Y V/PPROV 0/0/0 Gytis Leonavicius rawford Murray rawford Murray rawford Murray The drawing referenced

More information

hat channel purlins B SCREW PATTERNS: DOUBLE SCREW PATTERN ON UPPER AND LOWER ROOF PURLINS (FOR ROOF PANELS).

hat channel purlins B SCREW PATTERNS: DOUBLE SCREW PATTERN ON UPPER AND LOWER ROOF PURLINS (FOR ROOF PANELS). 6.2.524.524.524.524.524.524.524.524.524.524.524.524.524.524.524 3.2 +3.920 +3.094 note: dimensions including sheet metal transparent polymer panels, glass fiber enforced roof metal panel +3.920 +3.094

More information

Tractor - Setup Instructions

Tractor - Setup Instructions Trtor - Stup Instrutions WARNING AVOID SERIOUS INJURY OR DEATH: R n follow th trtor oprtor mnul for running ngin. Not: Follow th prours tht pply to your mol. Trtor Mols Mowr Mols 69595 4 69098 69596 69099

More information

MX MXA ALUMINIUM MOBILE ENCLOSURE APPLICATON EXAMPLE. DESKTOP AUDIO PREAMPLIFIER with USB WIRELESS MICROPHONE SYSTEM MODEL RAILROAD CONTROLLER

MX MXA ALUMINIUM MOBILE ENCLOSURE APPLICATON EXAMPLE. DESKTOP AUDIO PREAMPLIFIER with USB WIRELESS MICROPHONE SYSTEM MODEL RAILROAD CONTROLLER MX MX Th MX mobil nlosur is dsignd with a bautiful and lgant finish in mind. ith its taprd panl dgs and roundd dsign, it fits omfortably in your hand, whil giving off a simpl yt slk look. Suitabl for us

More information

ARLINGTON DOWNS RETAIL 3400 W EUCLID AVENUE

ARLINGTON DOWNS RETAIL 3400 W EUCLID AVENUE ARLINTON DONS RTAIL 3400 ULID AVNU DIRTORY ONR: UST ADS JV L 30 RANDOL ST. #00 IAO, IL 60661 ON: (3) 929-239 ARITT: OK ARITTS 600 JAKSON LVD. ST 20 IAO, IL 60601 ON: (3) 98-00 IVIL NINR: RIKSSON NINRIN

More information

CK2 PCB LAYOUT: COMPONENT SIDE RECOMMENDED PCB THICKNESS: 1.57/ /.016M A B C AT TIP 0.25/.010M A B C 0.05/.002M A B 1 OF 5 DIM A DIM B CKTS

CK2 PCB LAYOUT: COMPONENT SIDE RECOMMENDED PCB THICKNESS: 1.57/ /.016M A B C AT TIP 0.25/.010M A B C 0.05/.002M A B 1 OF 5 DIM A DIM B CKTS S IM IM.0.0 RF..0 S NOT 0./.0M T TIP L RF 0.... TIN GOL P RF M ± 0. ±.0 NOTS:. MTRIL: NYLON, UL V-0, OLOR: WHIT. FINISH: = OVRLL RFLOW MTT 0.0/.0000 MIN. OVR 0.00/.0000 MIN. NIKL = OVRLL MTT 0.0/.0000

More information

PROPOSED REPLACEMENT STRUCTURE: CMU BLOCK SHED BUILDING AND APPROX 30' LF OF FENCE REPAIR/REPLACEMENT. FLOOR AREA = 854 SF ROOF AREA = 1158 SF

PROPOSED REPLACEMENT STRUCTURE: CMU BLOCK SHED BUILDING AND APPROX 30' LF OF FENCE REPAIR/REPLACEMENT. FLOOR AREA = 854 SF ROOF AREA = 1158 SF 200 SILVR LN PROJT INFORMTION PROJT SRIPTION: (x) RPLMNT STRUTUR FOR (2x) SHS LOST TO RSON. NO HNG OF US PROPOS RPLMNT STRUTUR: MU LOK SH UILING N PPROX 30' LF OF FN RPIR/RPLMNT. FLOOR R = 854 SF ROOF

More information

10' WATER EASEMENT. 1'x16' WATER EASEMENT. 1'x16' WATER EASEMENT. 5'x10' WATER EASEMENT 5'X10' WATER EASEMENT 5'X10' WATER EASEMENT

10' WATER EASEMENT. 1'x16' WATER EASEMENT. 1'x16' WATER EASEMENT. 5'x10' WATER EASEMENT 5'X10' WATER EASEMENT 5'X10' WATER EASEMENT 5 6'x10' WTR 1'x27' WTR 5'x5' WTR MOT 6 LVL + (NON-OSHP) - OUPNY WOMNS NTR 2 LVL + L - 01043 SP4 10' WTR HOSPITL MPUS PRIMTR 5 UTILITY TUNNL SISMILLY SPRT, NO SP NUMR XISTING NTRL PLNT TO MOLISH NTRL PLNT

More information

BILL OF QUANTITIES NAME OF WORK: ELECTRICAL AND ALLIED WORKS AT GROUND FLOOR OF HAILAKANDI BRANCH, HAILAKANDI No. Particular Qty Units Rates Amount

BILL OF QUANTITIES NAME OF WORK: ELECTRICAL AND ALLIED WORKS AT GROUND FLOOR OF HAILAKANDI BRANCH, HAILAKANDI No. Particular Qty Units Rates Amount ANNEXURE-III BILL OF QUANTITIES NAME OF WORK: ELECTRICAL AND ALLIED WORKS AT GROUND FLOOR OF HAILAKANDI BRANCH, HAILAKANDI No. Partiular Qty Units Rats Amount 1.0 ELECTRICAL WIRING Proviin & fixin POINT

More information

CAUTION: Do not install damaged parts!!!

CAUTION: Do not install damaged parts!!! Your satisfaction is important to us, plas lt us hlp! If you hav any qustions or concrns during th installation, our support rprsntativs ar availabl to assist you. Plas call: 1-877-769-3765 or Liv Chat

More information

PLUG HOUSING BACK SEAL PLUG WEDGELOCK (TPA) PLUG SEAL

PLUG HOUSING BACK SEAL PLUG WEDGELOCK (TPA) PLUG SEAL HTSHRINK HOUSING K OVR RPTL WGLOK (TP) PLUG HOUSING K SL RPTL HOUSING K OVR PLUG WGLOK (TP) K SL PLUG SL HTSHRINK HOUSING NOTS. S SHTS TO FOR LL UNSPIFI NOTS, IMNSIONS N PRT NUMRS RLS STTUS P RLS.0.0 0::

More information

RECEPTACLE HOUSING PLUG HOUSING BACK SEAL PLUG WEDGELOCK TPA

RECEPTACLE HOUSING PLUG HOUSING BACK SEAL PLUG WEDGELOCK TPA HTSHRINK HOUSING RPTL HOUSING PLUG SL K OVR PLUG HOUSING K SL K SL K OVR RPTL WGLOK TP PLUG WGLOK TP HTSHRINK HOUSING FORMT: tb-prod- RVISION: : 0/0/0 NOTS. S SHTS TO FOR LL UNSPIFI NOTS, IMNSIONS N PRT

More information

UTMDA - GAMMA KNIFE DRESSING AREA

UTMDA - GAMMA KNIFE DRESSING AREA HLLMUTH, OBATA & KASSABAUM, L.P. ARHITTUR, NGINRING, PLANNING INTRIORS, GRAPHIS, ONSULTING UTMDA - GAMMA KNIF DRSSING ARA PROJT # FM 4-0865 Prepared for MD ANDRSON ANR NTR Issue Information ISSU FOR ONSTRUTION

More information

MIT CENTER FOR TRANSPORTATION & LOGISTICS April - October 2017

MIT CENTER FOR TRANSPORTATION & LOGISTICS April - October 2017 MIT NTR OR TRNSPORTTION & LOGISTIS pril - October 2017 1 2 3 4 5 6 7 8 9 10 11 12 13 6 10.01 ONSTRUTION SS MIL ROOM 000M OORINT TH US O STIR TOWR WITH MIT SURITY 08.03 9 10.01 01 STORG 000ST VSTIUL 000SV

More information

PLUG SEAL QUALITY SYMBOLS 2016/01/ /01/ /01/12 REDRAWN AND REVISED JDWALLACE JFLETCHER FDUGGAN 1 PLACE ± 0.2 DRWN: EC NO: CHK'D: APPR:

PLUG SEAL QUALITY SYMBOLS 2016/01/ /01/ /01/12 REDRAWN AND REVISED JDWALLACE JFLETCHER FDUGGAN 1 PLACE ± 0.2 DRWN: EC NO: CHK'D: APPR: HTSHRINK HOUSING K OVR PLUG SL RPTL WGLOK (TP) K SL PLUG HOUSING RPTL HOUSING PLUG WGLOK (TP) K OVR RLS STTUS P RLS T.0.0 0:: FORMT: tb-prod- RVISION: F T: 0// HTSHRINK HOUSING NOTS:. S SHTS - FOR UNSPIFI

More information

Section 2. PROGEF Natural PP Piping System. Serviced by GF Tustin

Section 2. PROGEF Natural PP Piping System. Serviced by GF Tustin Sction 2 PROGEF Natural PP Piping Systm Srvic by GF Tustin Tabl of Contnts PROGEF Natural (PP) Spcifications 2.4 Fittings Pip 2.5 90 Elbow 2.6 45 Elbow 2.7 T 2.8 Analytical Snsor T 2.9 Rucr 2.10 Union

More information

Supply and exhaust ventilation of various premises. Formation of flat air ductworks.

Supply and exhaust ventilation of various premises. Formation of flat air ductworks. Flt ut Applition Supply n xhust vntiltion o vrious prmiss. Formtion o lt ir utworks. M o whit PVC. Siz: 55x110, 60x122, 60x204 mm. ut lngth rom 350 to 2500 mm. Connt with mthing onntors. 1 1 50035 55 110

More information

SPIRAL STAIR INSTALLATION GUIDE

SPIRAL STAIR INSTALLATION GUIDE SPIRAL STAIR INSTALLATION UI Salter -Continuous Sleeve -Aluminum Handrail -alvanized 14 Illustrations are general and may not match your specific stair design. PARTS 1 2 3 BASPLAT BOTTOM BALUSTR MAIN BALUSTR

More information

CUSTOMER COPY PCB LAYOUT RECOMMENDED E D B .075[1.90] SEE NOTE 13 2X THRU C INSERTION DEPTH

CUSTOMER COPY PCB LAYOUT RECOMMENDED E D B .075[1.90] SEE NOTE 13 2X THRU C INSERTION DEPTH RVISIONS RV. O. NO SRIPTION T Y ST KY IN POSITION & KY TWN POSITION OPTION, OSOLT WG 0(S99), (S), 0(S), (S00), 09(S, UPLIT WITH S99), 0(S00), 9(S), 9(S), 00(S), (S0), RPL WITH WG 0, POSITION OR MTG & POSI

More information

Planning Guide. Residential Winding Drum Elevators. Series Custom-Lift. Built on C Rail

Planning Guide. Residential Winding Drum Elevators. Series Custom-Lift. Built on C Rail Plannin Gui Rsintial Winin rum Elvators uilt on Rail Sris 210 - ustom-lit W ar a prou mmr o t ssiility Equipmnt Manuaturrs ssoiation. Tis symol assurs you o our ommitmnt to i quality an assiility to vryon.

More information

WIRING INSTRUCTIONS MITER SAW UPPER CONTROL BLACK WHITE

WIRING INSTRUCTIONS MITER SAW UPPER CONTROL BLACK WHITE TITL MILWAUK LTRI TOOL ORP. AS AN AID TO RASSMBLY, TAK NOT O WIR ROUTING AND POSITION IN WIR GUIDS AND TRAPS WHIL DISMANTLING TOOL. MITR SAW 13135 WST LISBON RD. BROOKILD, WIS. DAT Aug. 2008 PAG 1 O 7

More information

Direct-Fired Heating, Ventilation and Pressurization Systems

Direct-Fired Heating, Ventilation and Pressurization Systems 2000-Series irect-ired Heating, Ventilation and Pressurization Systems imension and Selection uide 1.800.536.3461 www.rapidengineering.com N: 100% OUTSI IR ONLY 2000-Series Selection uide NOT: ll information

More information

1 OF 9 2CCT ML-XT CV CONNECTOR PRODUCT CUSTOMER DRAWING BACK COVER HEAT SHRINK HOUSING PLUG SEAL PLUG WEDGELOCK TPA BACK SEAL PLUG HOUSING

1 OF 9 2CCT ML-XT CV CONNECTOR PRODUCT CUSTOMER DRAWING BACK COVER HEAT SHRINK HOUSING PLUG SEAL PLUG WEDGELOCK TPA BACK SEAL PLUG HOUSING K OVR PLUG SL HT SHRINK HOUSING PLUG WGLOK TP K SL RPTL HOUSING PLUG HOUSING K SL RPTL WGLOK TP HT SHRINK HOUSING K OVR NOTS. S SHTS TO FOR UNSPIFI NOTS, IMNSIONS N PRT NUMRS THIS RWING ONTINS INFORMTION

More information

2307/08.02 RIVKLE. Fasteners for sheet metal and plastic, offering a simple solution even for single-sided installation.

2307/08.02 RIVKLE. Fasteners for sheet metal and plastic, offering a simple solution even for single-sided installation. 23008.02 RIVK Fastnrs for sht mtal an plastic, offring a simpl solution vn for singl-si installation. RIVK lin rivt nuts an stus, our prouct portfolio Stl Stainlss stl Aluminium Sizs Flat ha Countrsunk

More information

Solar PV Standard Plan Central/String Inverter Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Central/String Inverter Systems for One- and Two-Family Dwellings Planning and evelopment Building & Safety ivision Solar PV Standard Plan entral/string Inverter Systems for One and TwoFamily wellings SOPE: Use this plan ONLY for utilityinteractive central/string inverter

More information

HARDWARE WIRE BALUSTRADING FITTINGS MARINE AND ARCHITECTURAL.

HARDWARE WIRE BALUSTRADING FITTINGS MARINE AND ARCHITECTURAL. MRIN N RHITTURL HRWR WIR LUSTRING FITTINGS OPYRIGHT Y JMS GLN PTY LT *OL: Normal stocked items, ITLI: Please contact our sales team for availabilty and price 1 WIR LUSTRING FITTINGS STINLSS MRIN & RHITTUR

More information

Solar PV Standard Plan Simplified Central/String Inverter Systems for 10 KW or less One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Central/String Inverter Systems for 10 KW or less One- and Two-Family Dwellings Town of Woodside, Building ivision 29 Woodside Rd. Woodside, a. 902 (0) 179 Fax: (0) 1219 www.woodsidetown.org Solar PV Standard Plan Simplified entral/string Inverter Systems for 10 KW or less One and

More information

DOUBLE ENVELOPING WORM GEAR SETS

DOUBLE ENVELOPING WORM GEAR SETS OUL NVLOPIN WORM R STS 172 one rive Product atalog and ngineering Manual ouble nveloping Worm ears & Speed Reducers ontents one rive ear Sets...173 one rive ear Sets - Tables of acklash... 174 one rive

More information

PROJECT: BIRMINGHAM INTERMODAL FACILITY PHASE 2 BID PACKAGE 1

PROJECT: BIRMINGHAM INTERMODAL FACILITY PHASE 2 BID PACKAGE 1 GIATTINA AYOK ARHITETURE STUIO, IN. 827 ST AVENUE NORTH, SUITE 00 P. O. OX 55488 35255 IRMINGHAM, ALAAMA 35203 205/933-9060 AENUM NO. PROJET: IRMINGHAM INTERMOAL FAILITY PHASE 2 I PAKAGE GA STUIO NO.:

More information

Direct-Fired Heating, Ventilation and Pressurization Systems

Direct-Fired Heating, Ventilation and Pressurization Systems 2000-Series irect-ired Heating, Ventilation and Pressurization Systems imension and Selection uide 1.800.536.3461 www.rapidengineering.com N: 100% Outside ir Only 2000-Series Selection uide M (m 3 /h)

More information

Factory Modifications

Factory Modifications Slction Ordring Information modifications will consist of Simns standard componnts as availabl. Standard quipmnt dimnsions and nclosur construction may not apply whn crtain modifications and spcial faturs

More information

Classic Update Series

Classic Update Series lassic Update eries FOR 1967-69 APPLIATION TI AAW KIT O NOT UPPORT T U OF A FATORY AMMTR. A A RPLAMNT FOR T AMMTR W UGGT T U OF A VOLTMTR INTA. TRMINAL KIT 92965220 A BN PROVI FOR YOU TO ONNT TI LUTR KIT

More information

FRAMED PIVOT DOOR INSTALLATION INSTRUCTIONS

FRAMED PIVOT DOOR INSTALLATION INSTRUCTIONS FRAMED PIVOT DOOR INSTALLATION INSTRUCTIONS QCI5001 Rv 0 Pag 1 Crtifid 06/21/2016 MAINTENANCE: Two primary matrials ar usd to manufactur your nw bath nclosur: tmprd glass and anodizd aluminum. To assur

More information

WATER SOURCE HEAT PUMP WSHP

WATER SOURCE HEAT PUMP WSHP WTR SOUR HT PUMP WSHP I IR Water Source Heat Pump Units 3 onsole WSHP 4 onsole imensions 5 Vertical Stack WSHP 6 Vertical Stack imensions 7 Horizontal WSHP 8 Horizontal imensions 9 Vertical loset WSHP

More information

WINDOM ICE ARENA ICE SYSTEM REPLACEMENT

WINDOM ICE ARENA ICE SYSTEM REPLACEMENT WINDOM ARNA SYSTM RPLAMNT WINDOM, MINNSOTA O'NIL ROAD HUDSON, WI 0 () - () -0 FA: () - SHT IND GNRAL G00 TITL SHT LTRIAL 00 LTRIAL MODIFIATION PLAN RFRIGRATION R00 RINK LGND, SYMBOLS & ABBRVIATIONS RD00

More information

RIVNUT. Blind Rivet Nuts and Studs

RIVNUT. Blind Rivet Nuts and Studs 230UK0.03 lin Rivt Nuts an Stus Fastnrs for sht mtal an plastic, offring a simpl solution for mounting strong thras vn for singl-si installation. www.bollhoff.comuk lin rivt nuts an stus, our prouct portfolio

More information

Revision Schedule PROJECT TEAM DIRECTORY. The Holton Companies. SHEET A000 Holiday Isle Marina 555 & TH AVE, MADEIRA BEACH FLORIDA

Revision Schedule PROJECT TEAM DIRECTORY. The Holton Companies. SHEET A000 Holiday Isle Marina 555 & TH AVE, MADEIRA BEACH FLORIDA ROP OFF ZON PAVRS ROSSING PSTRIAN WALKWAY PAVRS ROSSING PAVRS ROSSING BOA IGA BAY HOTL BUILING A RSTAURANT BUILING B ONO BUILING Sheet # Sheet Name LANSAP LANSAP LANSAP ROP OFF ZON ONRT PSTRIAN WALKWAY

More information

Keymatic Line of Locks

Keymatic Line of Locks Volume 5 a t a l o g enstan L O O M P N Y eymatic Line of Locks 2 S V X Introduction 1 am Locks 2 3 rawer/oor Locks 4 Gang Locks 5 Snap olt Lock 6 s 7 8 9 10 11 Z olt Locks 12 Ratchet Locks 13 eys 14 enstan

More information

{\fcopperplate32bc b0 i0 c0;all REQUIRED

{\fcopperplate32bc b0 i0 c0;all REQUIRED {\fopperplateb b i0 c0;timat QUANTITI {\fopperplateb b i0 c0;tabl TIMATING FATOR cript :\\ivil rojects\\\\60-0\\aviation\\esign\\a4-av-v-jnu-iib-60.dwg esigned By:. WILT hecked By: B. HANON OWL File No.

More information

BROCHURE IP BI-TORQ Valve Automation PO Box 309 1N050 Linlar Dr. La Fox, IL tel: fax:

BROCHURE IP BI-TORQ Valve Automation PO Box 309 1N050 Linlar Dr. La Fox, IL tel: fax: ROHUR IP-209-0 I-TORQ Valve utomation PO ox 309 N050 Linlar r. La ox, IL 6047 tel: 630-208-9343 fax: 630-232-6235 www.bitorq.com 2-WY RSS VLVS /4 TO 4 LMP N SNITRY VLVS /2 TO 4 PGS 4-5 ITORQ.OM/IP.HTML

More information

Catalog. Product Catalog. Setting a new standard for: Quality Reliability Value Global Compatibility

Catalog. Product Catalog. Setting a new standard for: Quality Reliability Value Global Compatibility atalog Product atalog Setting a new standard for: Quality Reliability Value Global ompatibility Table of ontents 3- Valves 3 irect Acting Solenoid Valves (M3V) 4-5 3-Way Solenoid Valves (M3V) 6-7 4-Way

More information

REMOVE EXIST. SLAB. INSTALL NEW 12" CONCRETE SLAB REINFORCED WITH 6X6 W2.1XW2.1 WWF CONCRETE SLAB CONTROL JOINT SEE TYP. DETAIL (TYP.

REMOVE EXIST. SLAB. INSTALL NEW 12 CONCRETE SLAB REINFORCED WITH 6X6 W2.1XW2.1 WWF CONCRETE SLAB CONTROL JOINT SEE TYP. DETAIL (TYP. INSTLL NW " ONRT X W.XW. WWF N. Lincoln Street Wilmington, 90 0'- /" ONRT SL ONTROL JOINT S TYP. TIL INSTLL NW " ONRT X W.XW. WWF (P) 0.. (F) 0.. abhagen@h.com www.h.com ONSULTNTS aker, Ingram & ssociates

More information

Air Handlers Series. Direct-Fired Heating Pressurization. Dimension and Selection Guide

Air Handlers Series. Direct-Fired Heating Pressurization. Dimension and Selection Guide 2000-Series ir andlers irect-ired eating Pressurization imension and Selection uide 1.800.536.3461 www.rapidengineering.com N: 100% OUTSI IR ONLY 2000-Series Selection uide IMPORTNT NOTS: ll information

More information

OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER

OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER DESCRIPTION OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER Th RD-1W Automti Controllr is hvy uty mgnt ontrollr us or mgnts whos ol urrnt rngs rom 0 A to 100 A. Col urrnt rrns th urrnt lowing through

More information

Speed Controller with One-touch Fittings

Speed Controller with One-touch Fittings In-lin Typ 4 typs of mounting variations Dirct mounting Indx plat It is possibl to idntify th product whn multipl controllrs ar mountd and idntify th flow dirction by attaching an idntification labl. Controlld

More information

BELT CONVEYOR SECTION CONTENT. Bolt-Together Straight Bolt-Together Incline/Decline Welded Straight Belt Curve Optional Equipment and Devices

BELT CONVEYOR SECTION CONTENT. Bolt-Together Straight Bolt-Together Incline/Decline Welded Straight Belt Curve Optional Equipment and Devices LT ONVYOR STION ONTNT olt-together Straight olt-together Incline/ecline Welded Straight elt urve Optional quipment and evices 15 LT ONVYOR WHY? Provides the most versatile means of handling a wide variety

More information

B30ST ! IMPORTANT SAFEGUARDS! SAVE THESE INSTRUCTIONS. Installation Instructions SELF-TESTING EMERGENCY LIGHTING EQUIPMENT

B30ST ! IMPORTANT SAFEGUARDS! SAVE THESE INSTRUCTIONS. Installation Instructions SELF-TESTING EMERGENCY LIGHTING EQUIPMENT B30 Installation Instructions SLF-TIN MRN LIHTIN QUIPMNT WHN USIN LTRIAL QUIPMNT, BASI! IMPORTANT SAFUARDS! SAFT PRAUTIONS SHOULD ALWAS B FOOWD, INLUDIN TH FOOWIN: RAD AND FOOW A SAFT INRUTIONS 1. To prevent

More information

EXHAUST SYSTEM MANIFOLD AND ELBOWS 7 B

EXHAUST SYSTEM MANIFOLD AND ELBOWS 7 B EXHAUST SYSTEM 72990 MANIFOLD AND ELBOWS 72991 7 B Tl o Contnts P Torqu Spiitions..................... 7B-1 Slnts................................ 7B-1 Rmovl................................ 7B-1 Clnin n

More information

CONCRETE PIPE SPECIFICATIONS

CONCRETE PIPE SPECIFICATIONS CONCRT INX INX P...SINGL OFFST JOINT (Metric) P...SINGL OFFST JOINT (Imperial) P...CONCRT SHIPPING WIGHTS (Canadian) P4...CONCRT SHIPPING WIGHTS (State of Maine) P5...ALTRNAT CONCRT LNGTHS P6... BNS P7...T

More information

Speed Controller with One-touch Fittings

Speed Controller with One-touch Fittings 4 typs of mounting variations Dirct mounting Indx plat It is possibl to idntify th product whn multipl controllrs ar mountd and idntify th flow dirction by attaching an idntification labl. mounting DIN

More information

How to order Renold Jeffrey Attachment Chains

How to order Renold Jeffrey Attachment Chains ttacmnt ttacmnt Rnol Jry ors a i array o attacmnt cains suitabl or narly any application. Our bas cains atur t quality tat you kno an trust. ombin tat it t sp an rliability o livry an you av ig-quality,

More information

ICT820 CAN SAE J1939 OUTPUT IN-CYLINDER LINEAR TRANSDUCER

ICT820 CAN SAE J1939 OUTPUT IN-CYLINDER LINEAR TRANSDUCER PRLIMINRY PROUT INFORMTION SUJT TO RVISION Ver. (May 201) The IT820 ontactless Inylinder Linear Transducer combines the best features associated with LVTs and potentiometers into one rugged, contactless

More information

Valves PROGEF Standard Ball valve type 546 With mounting inserts With butt fusion spigots long PE100 SDR11 metric

Valves PROGEF Standard Ball valve type 546 With mounting inserts With butt fusion spigots long PE100 SDR11 metric Valvs PROGEF Stanar Ball valv typ 546 With mounting insrts With butt fusion spigots long PE100 SR11 mtric ultifunctional moul with intgrat limit switchs Pnumatic or lctric actuators from GF Iniviual configuration

More information

SECTION C-C SCALE 1 / 2 SECTION E-E SECTION AT-AT SCALE 1 / 2 SCALE 1 / 2 SECTION F-F SCALE 1 / 2 SECTION M-M SCALE 1 / 2 DETAIL D SCALE 2 : 1

SECTION C-C SCALE 1 / 2 SECTION E-E SECTION AT-AT SCALE 1 / 2 SCALE 1 / 2 SECTION F-F SCALE 1 / 2 SECTION M-M SCALE 1 / 2 DETAIL D SCALE 2 : 1 RVIS PRT SRIPTION IN OM, TO MK - //0 Y.LI IT LRR 6 dded fillet at bottom of PM pocket in item. //0 TIO 4. R. dded a new part # //0 Y.LI T 4 (.7) Revised welding note at etail View /6/0 Y.LI WTR TIGHT Ø6.7

More information

6/24/2018 Instrument Cluster (Instrument Panel, Gauges and Warning Indicators) - ALLDATA

6/24/2018 Instrument Cluster (Instrument Panel, Gauges and Warning Indicators) - ALLDATA //08 Instrument luster (Instrument Panel, Gauges and Warning Indicators) - LLT 00 hevy Truck S0/T0 lazer W V-.L VIN W Vehicle > Instrument Panel, Gauges and Warning Indicators > iagrams > lectrical - Interactive

More information

C-1 Bar Measures 1 inch

C-1 Bar Measures 1 inch LOK 4788 LOT 35 5/21/2013 7:40:31 PM - P:\IR\08309\200-08309-13002\\MOLFILS\R 9 ONFORM\R 9 WGS\LIFT STTION\-1 LIFT STTION 545 - SIT PLN.WG - VITTITO, WYLMR VLOPR PROJT (P TUSNY) 10600 HVROLT WY, SUIT 300

More information

0.90 ±0.05 HOUSING (2X) C L OF PAD XX ±

0.90 ±0.05 HOUSING (2X) C L OF PAD XX ± SOLIWORKS GNRT RWING, O NOT HNG Y HN L OF ONNTOR 1.00 1.45 0.02 TYP. MTL P MTL SPRING 4.0.50 TYP. ONTT 2.0 (2X).2 4. 0.90 HOUSING 1 1.9 (2X) NOTS: -1-001.S Li 1. LTRIL HRTRISTIS: 1.1. ONTT URRNT RTING:

More information

INDUCTION MOTORS INDUCTION MOTORS THE POWER BEHIND THE DRIVE. Energy Efficient Motors FRAME 63 TO 355 EVERYDAY SOLUTIONS

INDUCTION MOTORS INDUCTION MOTORS THE POWER BEHIND THE DRIVE. Energy Efficient Motors FRAME 63 TO 355 EVERYDAY SOLUTIONS TH POWR BHIN TH RIV INUCTION MOTORS FRAM 63 TO 355 LOW TNSION TFC INUCTION MOTORS INUCTION MOTORS nergy fficient Motors VRYAY SOLUTIONS SPOTLIGHTS TFC CAG MOTORS nergy fficiency level 2 as per IS:12615

More information

BRIDGE INSPECTION STANDARDS IN JAPAN AND US

BRIDGE INSPECTION STANDARDS IN JAPAN AND US BRIDGE INSPECTION STANDARDS IN JAPAN AND US Masahiro Shirato 1 an Takashi Tamakoshi 2 Abstrat Elmnt-lvl brig insption has bn vlop in Japan an th US rsptivly. Convntional maintnan / rhabilitation urgny

More information

Commercial Fans & Dampers

Commercial Fans & Dampers ommercial Fans & ampers HISTORY, IATION, AN XPRIN ontinental Fan was established in 1986 to manufacture and distribute quality ventilation equipment. Our objectives then were simple... to provide superior

More information

C-1 Bar Measures 1 inch

C-1 Bar Measures 1 inch 5/28/2013 6:41:36 PM - P:\IR\08309\200-08309-13002\\MOLFILS\R 2 ONFORM\R 2 WGS\FINL SIGN\SW6-2-1-PS558.WG - MIHL N. TISO www.johnsonengineering.com 2122 JOHNSON STRT FORT MYRS, FLORI 33902 PHON: (239)

More information

MAIN HYDRAULIC FLANGES AND COMPONENTS

MAIN HYDRAULIC FLANGES AND COMPONENTS TLOG 45 LNG PTR VRSION MIN HYRULI LNGS N OMPONNTS XPRIN: Over 55 Years of ependability 48,000 square foot State-of-the-rt manufacturing facility 4-bolt langes manufactured in the US QUI LIVRY: Over 5 Million

More information

FOR BOM ENTRY ONLY NOTES: 1. CUSTOMER ASSEBLY SHEETS 2-6. MTC3606HD

FOR BOM ENTRY ONLY NOTES: 1. CUSTOMER ASSEBLY SHEETS 2-6. MTC3606HD ITM PT NO. SIPTION QTY. WIGHT NOT NO. 1 SF-QV PLLT SF-QV PLLT 1 56.72 2 MT360602 SF-QV Transition Swivel Plate 2 18.40 LS 3 SFQV01 SF-QV rm Frame Weldment 1 59.92 LS 4 MT360601 SF-QV ight rm Frame Weldment

More information

CUSTOMER COPY C M D G_C M D-S2196 SECTION A-A RECOMMENDED PCB LAYOUT D C 2X A. FITS EDGECARDS THAT ACCEPT PCB's

CUSTOMER COPY C M D G_C M D-S2196 SECTION A-A RECOMMENDED PCB LAYOUT D C 2X A. FITS EDGECARDS THAT ACCEPT PCB's RVISIONS RV. O. NO SRIPTION T Y 09 KY SOT IN POSITION, KY SOT TWN POSITIONS OPTION, OSOT WG 9 (RP WITH WG 0) //0 JH X.. +.00 +0..0 9.0 -.0-0. (.0 0. ) PTH ROM TOP O INSUTOR TO TOP O PIN ITS GRS THT PT.0.

More information

metal-enclosed switchgear assemblies

metal-enclosed switchgear assemblies Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and maintenance of arc resistant type MVS rcgard metal-enclosed switchgear assemblies ontents escription Page Introduction....

More information

TA : TRAY PACKAGING SEE NOTE 4 TR : TRAY PACKAGING SEE NOTE 4

TA : TRAY PACKAGING SEE NOTE 4 TR : TRAY PACKAGING SEE NOTE 4 RI INITS IRUIT NO..0±.0 0.±0..±.0..±0.......±.0.±0..TYP. (OPTION : S LN ) ±.0 ±0.0.0±.0 0.±0..0/.0.0±.0.±0..±.0.±0..0±.0.±0. NOTS:. MTRILS: OUSIN: 'LNK'=NYLON /, ULV-, OLOR: NTURL "" =NYLON /, ULV-0, OLOR:

More information

PFF SERIES FLANGED NETWORK PLASTIC BOX

PFF SERIES FLANGED NETWORK PLASTIC BOX PFF SERIES FLANGED NETWORK PLASTIC BOX Thnil Dt Prottion lss: IP40 Oprting tmprtur: -10 C ~ +60 C 1 Nw PF plsti s with wll mounting flng ottom dsign. Md of flm-rsistnt ABS UL94V-0 nd vill in off-whit olor.

More information

Power Distribution Board SVS201-PWR (ControlPlex )

Power Distribution Board SVS201-PWR (ControlPlex ) Powr Distribution Board SVS20PWR (ControlPlx ) Dscription Togthr with th bus controllr CPC10 and th lctronic circuit protctor ESX50D-S1xx th powr distribution board typ SVS20PWR-xx forms th intllignt powr

More information

Low-watt Type Solenoid Valve

Low-watt Type Solenoid Valve Low-watt ype Solenoid Valve Features hese solenoid valves use low-wattage type oils (: 5 W, C: 12 W). his valve an e driven diretly from a programmale sequene ontroller sine it has a low urrent requirement.

More information

Needle Felted Camping Tutorial

Needle Felted Camping Tutorial Ndl Fltd Camping Tutorial Th ndl fltd Camping World tutorial show you stp by stp, how to ndl fltd owl, tr stump, fishing rod and fish, a blazing campfir, a fox, a tr and a tnt. Ths figurins will provid

More information

INSTRUCTION MANUAL NASHVILLE KNOX CHIFFOROBE. Model No: UPC CODE: NOTE: Lot number: Date of purchase: BR (Rustic Gray)

INSTRUCTION MANUAL NASHVILLE KNOX CHIFFOROBE.   Model No: UPC CODE: NOTE: Lot number: Date of purchase: BR (Rustic Gray) INSTRUCTION MANUAL Model No: R1519-4 (Rustic Gray) NASHVILL KNOX CHIFFORO UPC COD: 0-65857-17291-1 NOT: THIS INSTRUCTION OOKLT CONTAINS IMPORTANT SAFTY INFORMATION. PLAS RAD AND KP FOR FUTUR RFRNC. Lot

More information

EXHAUST SYSTEMS RISERS

EXHAUST SYSTEMS RISERS EXHAUST SYSTEMS 7 70621 70481 B RISERS Tl o Contnts Pg Spiitions............................ 7B-1 4.3L/4.3LX............................ 7B-1 Torqu Spiitions................ 7B-1 Slnts...........................

More information

Indianapolis Power & Light Company

Indianapolis Power & Light Company Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis

More information

ANGLE HEADS ADDING MORE AXES WITH MST CATALOG 517-2

ANGLE HEADS ADDING MORE AXES WITH MST CATALOG 517-2 TLOG 57-2 NGL HS ING MOR XS WITH MST MRIN ROTRY TOOLS O. 250 West uarte Rd, Ste., Monrovia, US 906-7464 Tel: + (626) 58-8466 ax: + (626) 58-0076 mail: info@artcotools.com Website: www.artcotools.com MST

More information

W.E. ANDERSON. Series WE35 3-Way NPT Brass Ball Valve. Specifications - Installation and Operating Instructions. Bulletin V-WE35

W.E. ANDERSON. Series WE35 3-Way NPT Brass Ball Valve. Specifications - Installation and Operating Instructions. Bulletin V-WE35 y wyer Series W35 3Way NPT rass all Valve Specifications Installation and Operating Instructions ulletin VW35 W35H00T W35A0TAA0 W35T0T3A W35A0L W35A0T3NN05 The SRIS W35 incorporates a full port 3way brass

More information

COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF TRANSPORTATION BUREAU OF DESIGN

COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF TRANSPORTATION BUREAU OF DESIGN GNRAL : TYPS INDX OF SHTS. ALL DIMNSIONS AR IN MILLIMTRS UNLSS OTHRWIS NOTD. U.S. USTOMARY UNITS IN ( ) PARNTHSIS. TYP DSRIPTION SHT NO. SHT TITL GNRAL - 2. DSIGN SPIFIATIONS: AASHTO, LRFD DSIGN SPIFIATIONS

More information

MBF Series. Xe nâng Pallet chi phí thấp... Hàng chất lượng cao MB25 MB30 MB35 MB50. Frame and body

MBF Series. Xe nâng Pallet chi phí thấp... Hàng chất lượng cao MB25 MB30 MB35 MB50. Frame and body MBF Sris X nâng Pallt chi phí thấp... Hàng chất lượng cao MB25 MB30 MB35 MB50 Top quality dosn't nd to com at a high pric. Our low-cost hand pallt - trucks giv you vrything you nd to do th job - plus a

More information

Air Combination Air Filter + Regulator + Lubricator. AC20-A to AC40-A. How to Order. Description. Rc NPT 1/8 1/4 3/8 1/2 3/4

Air Combination Air Filter + Regulator + Lubricator. AC20-A to AC40-A. How to Order. Description. Rc NPT 1/8 1/4 3/8 1/2 3/4 ourtsy of /lodyn/ydradyn otion ontrol ydraulic Pnumatic Elctrical chanical (8) 26-8 www.cmafh.com I ymbol w r t y L ot ) Option ttachmnt mi-standard 3 Thrad typ a b c d f g h 2 Port siz ir ombination ir

More information

CONNECTIONS MADE SIMPLE

CONNECTIONS MADE SIMPLE ONNTIONS M SIMPL omplies with all federal & state low lead laws No more solder, glue, clamps, costly tools or clean-up! Push-on connection to copper, PV or PX asily recover from installation & deburring

More information