Motor Protection With The MonitorPro

Size: px
Start display at page:

Download "Motor Protection With The MonitorPro"

Transcription

1 Motor Protection With The MonitorPro This application note can show you the easy way to protect your motors and your pump stations. The MultiTrode MonitorPro can protect your motors from a wide range of common faults, and even perform routine testing to predict emerging faults and has the following features as standard: Inbuilt Insulation Resistance Tester means no wiring removal, and no site visit necessary Over-current detection can detect damaged motors, blocked pumps or seized bearings Under-current detection can detect damaged impellors or burst pipes. Electronic thermal protection ensures against degradation of windings from over-temperature far more reliably than simple thermistor or bi-metallic overloads. Supply voltage monitoring can protect against surges, brownouts, or phase dropouts. 1 Hardware To protect your motors, your site requires the following minimum hardware installed in addition to your MultiTrode Pump Controller and MultiTrode MonitorPro: One Current Transformer (CT050 or CT100) per phase per motor CT050 has a 5A output for a 50A input CT100 has a 5A output for a 100A input One Current Shunt Adapter (SR1 or SR5) per 3-phase motor o o SR1 has a 50mV output for a 1A input SR5 has a 50mV output for a 5A input 2 Wiring See the wiring diagram on the next page for connection details. 2.1 Supply Voltage Monitoring For supply voltage monitoring, you must connect 3 Phase AC supply to L1, L2, L3 inputs. The voltage measurements are performed with respect to the AC Supply Earth, so the Mains Power Terminal E must be securely earthed to the same earth as the motors. 2.2 Motor Protection For Motor Protection, you must connect Current Transformers and Current Shunt Adapters into terminals AR/AW/AB to CR/CW/CB and T1 to T9..doc 6 July 2005 Page 1 of 6

2 2.3 Motor Insulation Resistance Testing For the motor insulation resistance testing you must connect one phase of each motor to the insulation to resistance tester inputs MEGGER, MA, MB and MC. The insulation resistance test is performed with respect to the AC Supply Earth, so the Mains Power Terminal E must be securely earthed to the same earth as the motors. Figure 1 The back panel of the MonitorPro showing terminal locations. The wiring connections for motor protection and supply voltage monitoring are show in the wiring diagram at right. Note: Detail is not relevant to the supply monitoring and motor protection wiring is not shown. See the MonitorPro manual for a full wiring diagram..doc 6 July 2005 Page 2 of 6

3 3 Precautions Before attempting to program the MonitorPro, ensure you have all of the nameplate details from your motors. The MonitorPro has a built-in 500VDC Insulation Resistance Tester. If you are using an inverter or a soft starter, check with your supplier about compatibility before using the Insulation Resistance Tester function on the MonitorPro. The MonitorPro will emit 500VDC for a short period, and this is normally immediately after the motor is stopped. This test may cause damage to the inverter or soft starter, or false readings could be obtained due to leakage through the inverter or soft starter. This danger is especially likely if the inverter has a ramp-down time or a DC brake programmed, as the MonitorPro would be performing the Insulation resistance test while the inverter is still driving the motor. It should also be noted that only one wire on each motor is directly connected to the MonitorPro s Insulation Resistance Tester. The MonitorPro is relying on the internal connections of the coils to test the other coils. If a Star / Delta switcher is being used, it should be configured so that the 3 coils on the motor are connected in either format (i.e. not isolated from each other) when the test will be performed. In software versions and above, there is a one-minute delay between when the motors are stopped by the MonitorPro and the insulation resistance test is performed. This is to allow inverters to slow the motor down or perform DC braking, so that the insulation resistance test is not performed while the inverter is powering the motor. The software version of your equipment is recorded on the back of the unit, where the wiring terminals are located, or is visible on the display when the unit is reset. A reset can be performed from the front panel by pressing the Left, Right and Help buttons simultaneously. 4 Programming To set the MonitorPro up for motor protection, proceed as follows from the front panel of the MonitorPro: 4.1 Enter the menu structure of the MonitorPro, and then select the STATION SETUP menu. Motor Insuln Fault :->Disabled Level (MOhm) :01.0 Test Frequency :All pumps stopped 4.2 To set up the Automatic Insulation Resistance Testing, Enter the Motor Protection menu, then the General menu. If you don t wish to configure the Insulation Resistance Testing, ensure the screen shows the Motor Insuln Fault as Disabled, then jump ahead to step To turn the Insulation testing function on, set the Motor Insuln Fault to Enabled. 4.4 At the Level line, enter the insulation resistance level below which the MonitorPro should return a failed test. This value is entered in Mega-ohms (MΩ). If a motor fails a test, it will be locked out, and will not be available for use. Although the legal limit in Australia is 1MΩ, we recommend a much higher value, such as 5MΩ, to predict faults earlier, before they become a problem. 4.5 The test frequency will determine how often the Automatic test is performed. This can be daily, weekly, or when all the pumps are stopped. If a daily (or weekly) frequency is selected, the test will be performed upon the next motor stop 24 hours (or 7 days) after this menu is exited. If All Pumps Stopped is selected, the insulation resistance test will be performed every time the motors stop (or 1 minute after, for software versions and above). This is the optimal time to perform the test as the motors are at their operating temperature..doc 6 July 2005 Page 3 of 6

4 4.6 Pressing down will select the next screen. The Reset Mode will determine how the motor will be brought back into service in the event of a failed insulation resistance test. If an Auto setting is selected, after the nominated time the motor will be retested and if it passes the test, will be re-enabled. A Manual reset mode means that the motor will be locked out until the fault is manually reset by pressing the reset button on the front of the Pump Controller. As a failed insulation resistance test is a serious problem, we recommend that the Reset Mode be set to Manual. 4.7 Pressing Enter while the arrow is pointing at Test Now will initiate a insulation resistance test on all connected motors. Note that this test will be performed regardless of the status of the motors according to the Pump Controller. If a motor is running, or the inverter or soft starter is injecting any sort of power or signal into the motor (e.g. slowing down or DC brake) when the test is performed, incorrect readings may be obtained. When the test is complete, the MonitorPro will return to the main display. The results of the insulation resistance test can be seen by pressing the down arrow once. Reset Mode :->Auto - 1 min Immediate Test :Test Now 4.8 Re-enter the menu system and enter the Motor Protection menu, then the Pump 1 Menu. 4.9 The Motor Protection menu sets up the parameters needed to adequately protect your motor. The screens are shown sequentially below, with a brief description of the use of the specific parameter, as well as the reference to the MonitorPro manual section that contains more information on each parameter. CTPrimaryFLC(Amps) :->050.0 Locked Rotor Fault :Enabled Level (Amps) : CTPrimaryFLC(Amps) see section of the manual. The CTPrimaryFLC is the Full Load Current of the Primary coil of the Current Transformer. If the motor cable is only passed through the current transformer (normal situation), the value should be entered as read off the Current Transformers used. If the current transformer is being used to measure a much lower current than for what it is rated, then the motor cable should be passed through the Current Transformer a number of times, and the CTPrimaryFLC parameter would be entered as: Specified Current Transformer Primary Rating CTPrimaryFLC = Number of turns of motor cable through Current Transformer 4.11 Locked Rotor Fault see section of the manual. Enabling this option will set off an alarm if the measured motor current exceeds the Level shown on the next line for longer than the Operate Delay shown on screen Level (Amps) see section of the manual. This level is the level above which the Locked Rotor Fault will trip an alarm. Operate Delay(sec):->010 Reset Mode :Auto 1min Thermal Protn :Disabled.doc 6 July 2005 Page 4 of 6

5 4.13 Operation Delay see section of the manual. This is the time that the measured motor current must be above the Locked Rotor Current Level before the alarm is tripped Reset Mode see section of the manual. The Reset Mode determines how the locked rotor fault should be reset after it has been tripped. If the Reset Mode is set to Auto x min, then after the time period shown, the MonitorPro will attempt to restart the motor. If the fault still exists, the motor will not be restarted. If the Reset Mode is set to Auto (with no time period shown), the MonitorPro will reset the unit automatically as soon as the fault is cleared. As the motor is shut down when the fault occurs, the fault will immediately clear, and so the motor will immediately be re-enabled. For this reason, we recommend to not use the Auto setting Thermal Protn Section of the manual. Enabling this option allows the MonitorPro to perform Thermal Protection of the motor, and will shut the motor down if the calculated thermal current exceeds the limit set on the next screen. P 1 3/7 Motor FLC (Amps) :-> xFLC Trip Time(s):010 Reset Mode :Auto 5min 4.16 Motor FLC (Amps) see section of the manual. This is the Full Load Current of the motor, as specified by the motor manufacturer. This should be entered as read off the motor nameplate XFLC Trip Time(s) see section of the manual. This is the time that the measured current has to be above the FLC limit. This should be entered as read off the motor manufacturers data sheet. If the manufacturers data sheet cannot be obtained the recommended value of 10 seconds should be used. See section of the MonitorPro manual for calculating other values according to manufacturers data Reset Mode see section of the manual. The Reset Mode determines how the 6xFLC fault should be reset after it has been tripped, as per the reset mode for the locked rotor fault in section OTECTION: PUMP 1 4/7 UnderCurrent Flt :->Enabled Level (Amps) : Operate Delay(sec) : UnderCurrent Flt see section of the manual. Enabling this fault will cause a fault trip if the measured motor current is below the level specified on the next line Level (Amps) see section of the manual. This is the level below which the motor is determined to have failed on an undercurrent fault Operate Delay(sec) see section of the manual.. This is the time that the measured motor current must be below the under-current fault level before a fault is tripped Reset Mode see section of the manual. The Reset Mode determines how the under-current fault should be reset after it has been tripped, as per the reset mode for the locked rotor fault in section Phase Failure Fault Section of the manual.. Enabling this fault will cause a fault trip if the three measured voltages on the three-phase supply are different by the level shown on the next line. Reset Mode :->Auto 5min Phase Failure Fault :Disabled Level (%) :25.doc 6 July 2005 Page 5 of 6

6 4.24 Level (%) see section of the manual.. This is the level at which the measured voltage of any one phase of the three phase supply has to differ from the other phases before a fault is tripped. For example, if two phases are measured at 240VAC RMS, and the third phase is measured at 216VAC RMS, this is 10% error Operate delay(sec) see section of the manual. This is the time that a phase failure of the above magnitude must be present before a fault is tripped. Operate delay(sec) :->010 Reset Mode :Auto 5min Earth Fault Protn :Disabled 4.26 Reset Mode see section of the manual. The Reset Mode determines how the phase failure fault should be reset after it has been tripped, as per the reset mode for the locked rotor fault in step 4.11 of this document Earth Fault Protn see section of the manual. This fault compares the currents on all phases of the motor, and if one phase has increased relative to the other two phases, this is indicating that there is earth leakage, as the currents should always be balanced in a three-phase motor. Enabling this fault will cause a fault trip if the three measured currents on the three-phase supply are different by the level shown on the next screen Level (%) see section of the manual. This is the level at which the measured current of any one phase of the three phase supply has to differ from the other phases before a fault is tripped. For example, if two phases are measured at 100A RMS, and the third phase is measured at 110A RMS, this is 10% error. Note that this value is not editable here, as it is the same as the value set in step for the Phase Failure Fault. Setting the value in step sets the value for both the Phase Failure Fault and the Earth Fault Operate delay(sec) see section of the manual. This is the time that an earth fault of the above magnitude must be present before a fault is tripped. Level (%) :->25 Operate Delay(sec) :010 Reset Mode :Manual Reset Note: This value is not editable here, as it is the same as the value set in step 4.24 for the Phase Failure Fault. Setting the value in step 4.24 sets the value for both the Phase Failure Fault and the Earth Fault Reset Mode see section of the manual. The Reset Mode determines how the earth fault should be reset after it has been tripped, as per the reset mode for the locked rotor fault in step Conclusion This completes the parameters that need to be set up for motor protection on pump 1. Note that the procedure so far has only set up one motor. The other motors need the same information entered into them. If the motors are identical, or very similar, the easiest method of programming multiple motors is to program motor one first, then use the Copy Pump1 to Pump2 or Copy Pump1 to Pump3 options as shown in the Motor Protection Menu below. Selecting either of these functions will copy all of the motor protection parameters from the data stored for pump 1 to the next motor, which saves manually entering all of the data. Visit for the latest information.doc 6 July 2005 Page 6 of 6

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller

More information

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay. 10 Troubleshooting When a protection condition is detected, the VLT Soft Starter MCD 500 writes this condition to the event log and may also trip or issue a warning. The soft starter response depends on

More information

Section 1.0 Warnings Section 2.0. Section 3.0. Section 4.0. MCD3000 Inside Delta Connection Kits. Contents

Section 1.0 Warnings Section 2.0. Section 3.0. Section 4.0. MCD3000 Inside Delta Connection Kits. Contents Section 1.0 Warnings... 2 Section 2.0 Description 2.1 Overview... 3 2.2 Inside delta ratings... 3 2.3 Isolation... 3 2.4 Supply voltage... 3 Contents Section 3.0 Section 4.0 Kit Installation 3.1 Overview...

More information

60 Series Engine Controls

60 Series Engine Controls ECU 60 Series Engine Controls Use CAUTION since you are applying 120VAC RMS to the AC Input terminals and that it is always potentially their during engine run!!! ECU is a registered trademark of Engineering

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units Universal and Multi Split Units If there is fault on any LG universal or multi unit a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10

MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10 Contents Contents 1 Warnings 3 2 Troubleshooting 5 Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10 3 Service Instructions 13 Frame

More information

SDS Enclosed Star-Delta Starter User Guide

SDS Enclosed Star-Delta Starter User Guide SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING

More information

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4 CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power

More information

TRIPS AND FAULT FINDING

TRIPS AND FAULT FINDING WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

Open Chassis Star-Delta Starter User Guide

Open Chassis Star-Delta Starter User Guide Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...

More information

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the

More information

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599

More information

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

RVS-DX Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Operating Instructions. VLT Soft Starter - MCD 500. Phone: Fax: Web: -

Operating Instructions. VLT Soft Starter - MCD 500. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Soft Starter - MCD 500 Contents Contents 1 Safety 5 1.1 Safety 5 2 Introduction 7 2.1.1 Feature List 7 2.1.2 Type Code 8 3 Installation 9 3.1 Mechanical

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL Operations Manual Automated Fuel Maintenance System FTI-10A & 20A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies

More information

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

REVISION HISTORY REVISION HISTORY

REVISION HISTORY REVISION HISTORY FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim

More information

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down). Technical Data Sheet GENSET CONTROL MODULE A121H / A241H Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions.

More information

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9 USER MANUAL 1 CONTENTS 1. INTRODUCTION... 1 2. SAFTY INSTRUCTION... 3 3. CABLE CONNECTION... 4 4. SYSTEM DESCRIPTION... 5 5. OPERATION... 9 6. TROUBLE SHOOTING GUIDE... 25 7. OPERATION MODES..... 27 8.

More information

MAKING MODERN LIVING POSSIBLE. Service Manual VLTp Soft Starter - MCD500 *MG17L402*

MAKING MODERN LIVING POSSIBLE.   Service Manual VLTp Soft Starter - MCD500 *MG17L402* MAKING MODERN LIVING POSSIBLE www.danfoss.com/drives Service Manual VLTp Soft Starter - MCD500 175R0550 MG17L402 *MG17L402* Rev. 2010 11 05 Contents Contents 1 Warnings 3 2 Troubleshooting 4 2.1 Functional

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

Starting of Induction Motors

Starting of Induction Motors 1- Star Delta Starter The method achieved low starting current by first connecting the stator winding in star configuration, and then after the motor reaches a certain speed, throw switch changes the winding

More information

ADVANCED PID TROUBLESHOOTING

ADVANCED PID TROUBLESHOOTING ADVANCED PID TROUBLESHOOTING August 29, 2016 A KEY POINT If the drive is telling you something via a Fault, then the problem is probably not the drive. The drive is recognizing a fault and telling you

More information

ADDENDUM TO THE STC PRO LOGGER II MANUAL

ADDENDUM TO THE STC PRO LOGGER II MANUAL ADDENDUM TO THE STC PRO LOGGER II MANUAL 1. Probe Test for Testing Double Insulated Appliances (Utilities Menu) The SafeTcheck Pro Logger II now has a new feature Probe Test, available on all testers with

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY CONNECTIONS INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! READ THESE INSTRUCTIONS

More information

DRV-1. Step Motor Drive. User Manual Mentor Avenue Cincinnati, Ohio Tel (513)

DRV-1. Step Motor Drive. User Manual Mentor Avenue Cincinnati, Ohio Tel (513) DRV-1 Step Motor Drive User Manual 1776 Mentor Avenue Cincinnati, Ohio 45212 Tel (513) 318-4600 www.resolutionair.com 2 Contents 1 Introduction... 3 1.1 Overview... 3 1.2 Features... 3 1.3 Block Diagram...

More information

User s Manual: SMARTSTART Series. Models: 6R15 6R830 6V400 6V630

User s Manual: SMARTSTART Series. Models: 6R15 6R830 6V400 6V630 User s Manual: SMARTSTART 6000 Series Models: 6R15 6R830 6V400 6V630 Contents.. Introduction 2 Receiving 2 Handling & Storage 2 Handling on Installation 2 Software 2 (General Warning) Read & familiarise

More information

VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 3000

VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 3000 VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 3000 Soft starts Protect Gear, Goods, Equipment and Environment An AC motor switched directly on to the mains power supply will struggle to reach its nominal

More information

MCD 200 Series Soft Starters

MCD 200 Series Soft Starters MCD 200 Series Soft Starters AC motors often cause one or more serious problems during startup acceleration. MCD 200 Series electronic soft starters control motor current to provide a smooth start. When

More information

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

Explanation 1 Input External Switch 2 Input Hipot Safety Switch

Explanation 1 Input External Switch 2 Input Hipot Safety Switch on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the

More information

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION... CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. INVERTER OPERATION... 11 6. TROUBLE SHOOTING GUIDE....... 16 7.

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE710 AUTOSTART CONTROL MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44

More information

Series Motor Protection

Series Motor Protection 320-327 Series Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

320 to 327 M Series Low and Medium Voltage Motor Protection Relays 1. Protection Features 320 to 327 M Series Low and Medium Voltage Motor Protection Relays INSTALLATION AND SETTING UP PROCEDURE Overloading (for both cyclic and sustained overload conditions) Start stall

More information

ZENER SMARTSTART 6000 Soft Starter Instruction Manual

ZENER SMARTSTART 6000 Soft Starter Instruction Manual ZENER VARIDRIVE SOLUTIONS ZENER SMARTSTART 6000 Soft Starter Instruction Manual Contents Introduction 2 Receiving 2 Handling & Storage 2 Handling on Installation 2 Software 2 (General Warning) Read &

More information

SafetyPAT Plus A B P/N:

SafetyPAT Plus A B P/N: SafetyPAT Plus A B C P/N:110401103864 Test Instrument Solutions SafetyPat Plus Instructions A.Features SafetyPat Plus The SafetyPat Plus is a handheld battery powered unit suitable for carrying out electrical

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE720 AUTOSTART CONTROL MODULE OPERATING MANUAL http://bestgenerator.spb.ru/?page_id=6765 Deep Sea Electronics Plc Highfield House Hunmanby North

More information

Invertek. Battery Management Control System DC-SW-140 & DC-SW-140C DC-SW-70 & DC-SW-70C USER MANUAL

Invertek. Battery Management Control System DC-SW-140 & DC-SW-140C DC-SW-70 & DC-SW-70C USER MANUAL 利佳興業股份有限公司 RICH ELECTRIC CO.,LTD. Invertek Battery Management Control System DC-SW-140 & DC-SW-140C DC-SW-70 & DC-SW-70C USER MANUAL Rich Electric Co. DC-SW Battery Management Control System User Manual

More information

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...

More information

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1 BellMega BM-510 Operation Manual Ver: 1.0 Rev: 1 CONTENTS Page Description 1 Operation 2 Safety 2 Charging 3 Service / Calibration 3 Specifications 4 Description The BellMega is a continuity tester for

More information

DRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1...

DRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1... 100HP 400HP 700HP 1000HP 1400HP PCS Softstarter Controller IN-rail mountable microprocessor controller for 3-phase motors up to 480A (3...85A din-rail mountable) Provides three different starting modes

More information

VLT Soft Starter. Remote operation. Serial communication 24 V AC/DC V AC. Constant effort to improve MCD 100, MCD 201, MCD 202, MCD 3000

VLT Soft Starter. Remote operation. Serial communication 24 V AC/DC V AC. Constant effort to improve MCD 100, MCD 201, MCD 202, MCD 3000 .5 00 (mm)hxwxd (Amps) 0x,5x, CSA, A: :0 (AC5b) 5A: 8:0000 0xx8 5A: 65:0080 0xx8 0 T C V Remote operation Series + protection Remote operation of 0, 0 and 00 is facilitated by the dedicated remote operator

More information

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the

More information

Electric Motor Controls BOMA Pre-Quiz

Electric Motor Controls BOMA Pre-Quiz Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,

More information

MX431 Generator Automatic Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 1 1. SPECIFICATION Sensing Input Voltage Frequency 190 ~ 264 VAC Max, 1 phase, 2 wire 50 / 60 Hz, selectable

More information

LA Motor Protection. A South African Company to be Proud of

LA Motor Protection. A South African Company to be Proud of LA Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za

More information

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

User Manual Back-UPS BX650CI-MS 230 Vac with AVR User Manual Back-UPS BX650CI-MS 230 Vac with AVR Overview Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. Read the Safety

More information

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module EFFECTIVE DATE JULY 28 204 OF 8 Dual Hybrid Ship Propulsion System 750V BUS Generator Generator Propulsion Propulsion Bus Capacitorss 50,000µF Total Traction Inverter Dual Inverterr e Power Inverter L

More information

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI II 1400-6 ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI ACSI 1426-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1092, REV. C INSTALLATION For C-UL Listed applications,

More information

AeroVironment Universal Solar Pump Controllers

AeroVironment Universal Solar Pump Controllers AeroVironment Universal Solar Pump Controllers (Installer s business information to be affixed here.) User Manual Models: USPC-2000 (AV Part Number 03747-001 Rev. D) USPC-5000 (AV Part Number 03747-002

More information

Deep Sea Electronics Plc

Deep Sea Electronics Plc Deep Sea Electronics Plc 5120 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL Author: Anthony Manton Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH England Tel: +44 (0) 1723

More information

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS?

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS? ARM V FDBK ENSURE MOTOR IS T ROTATING DURING POWER UP This fault can only happen in the first 3 seconds after power up. The processor looks at the armature voltage. The voltage needs to be near 0. Possible

More information

825-P Modular Protection System for motors Specification Guide

825-P Modular Protection System for motors Specification Guide Specification Guide 1.0 General 1.01 The motor protection relay shall have a current operating range of 0.5 and 5000 amperes. 1.02 The motor protection relay shall provide current measurement-based protection

More information

HIB Enclosed Inverter User Guide

HIB Enclosed Inverter User Guide HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit

More information

OnCommand Troubleshooting Guide Hayward Industries

OnCommand Troubleshooting Guide Hayward Industries OnCommand Troubleshooting Guide 2010 Hayward Industries Table of Contents Safety Precautions Page 1 Overview Pages 2-5 Software Troubleshooting Page 6 Local Display Pages 7-8 Relays Pages 9-10 Heaters

More information

Flight Systems. Replacement for KASSEC DESCRIPTION

Flight Systems.   Replacement for KASSEC DESCRIPTION DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL 72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com

More information

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands

More information

OPTI-Solar SC MPPT Series

OPTI-Solar SC MPPT Series www.opt i -sola r. c o m OPTI-Solar SC MPPT Series SOLAR CHARGE CONTROLLER SC-50 / SC-80 / SC-80X / SC-160X MPPT Installation and Operation Manual CONTENTS Introduction... Feature... Specification... Dimension...VII

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 473681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

IES GRID FEED-IN LIMITER

IES GRID FEED-IN LIMITER IES GRID FEED-IN LIMITER Installation and User Manual Models SPS01101-ABB SPS01303-ABB CONTAINS IMPORTANT INSTALLATION AND TESTING PROCEDURES THAT MUST BE FOLLOWED TO ENSURE COMPLIANCE WITH ENERGEX AND

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information

Bulletin 825 SMM Smart Motor Manager

Bulletin 825 SMM Smart Motor Manager Bulletin 825 SMM Smart Motor Manager Your order must include: Cat. no. of the Smart Motor Manager selected with supply Voltage Suffix Code, Cat. no. of Converter Module selected, and, If required, Cat.

More information

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit

More information

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy otor Controllers AC Semiconductor otor Controller Type RSHP Flexy Soft starting and stopping of 3-phase squirrel cage motors Low surge and vibration-free starting User-selected ramping profiles Integral

More information

Designed for ease of integration with automation systems

Designed for ease of integration with automation systems BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C710616 32, SIEP C710616 33, and SIEP C710616 38 Introduction This supplement to the L1000A Technical Manual describes features

More information

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor

More information

DG SYNCHRONIZING &AMF PANEL

DG SYNCHRONIZING &AMF PANEL A 80, Sector 80, Phase 2, Noida 201305, Utter Pradesh, India DG SYNCHRONIZING &AMF PANEL Clients Bharat Petroleum Corp.Ltd PROJECT- DG Synchronization panel with AMF function. Design BY:- Errection By

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4 USER S MANUAL ON-LINE 1K/2K/3KVA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. UPS OPERATION...... 12 6. TROUBLE

More information

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos: PHASE CONVERTERS MODEL NO: PC40 and PC60 MODEL PART No: NO: 6012805 PC20 and PC40 6012810 PC60 PART Nos: 6012800 6012805 6012810 OPERATING & MAINTENANCE INSTRUCTIONS 0107 Specifications PC20 PC40 PC60

More information

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies D1541 D1542 D1543 D1545 D1543-X-8 D1545-X-8 D1545-4BNC D154X Series 1A 2A 3A 5A 3A fitted with 8-way output splitter

More information

Operating Instructions VLT Soft Starter MCD 500

Operating Instructions VLT Soft Starter MCD 500 MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Soft Starter MCD 500 vlt-drives.danfoss.com Contents Operating Instructions Contents 1 Safety 6 1.1 Warnings 6 2 Introduction 8 3 Installation

More information

SPEEDRIVE INSTRUCTIONS MANUAL

SPEEDRIVE INSTRUCTIONS MANUAL EN SPEEDRIVE INSTRUCTIONS MANUAL Safety warning. The following symbols shown beside a paragraph represent danger warnings associated to the failure to comply with the corresponding instructions. DANGER!

More information

QS 100 LSM Power Management

QS 100 LSM Power Management 990000717 Revision A Table of Contents Revision History...2 Overview...3 Soft Start not complete fault...3 Under voltage fault...4 Under voltage warning limit...5 Over voltage maximum limit...5 Over voltage

More information

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Quick guide. Plug-in fans GPPM with FC101_106 August 2014 Quick guide Plug-in fans GPPM with FC101_106 August 2014 Fläkt Woods permanent magnet motors and speed controllers for plug fans GPPM 1. General Fläkt Woods offers a wide range of permanent magnet motors

More information

SSW07. Soft Starters. Applications. Standard Features

SSW07. Soft Starters. Applications. Standard Features General Information CFW10 CFW100 CFW08 CFW500 CFW700 CFW701 CFW11 EDP11 CFW11M SSW05 SSW06 GPH2 TPH2 are static starting devices, designed for the acceleration, deceleration and protection of the three

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information