TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3
|
|
- Abner Jenkins
- 6 years ago
- Views:
Transcription
1 Split System Air Conditioner N2A3 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. DANGER Immediate hazards which will result in severe personal injury or death. WARNING Hazards or unsafe practices which could result in severe personal injury or death. CAUTION Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or operation. Safety Labeling and Signal Words Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: WARNING! WARNING The signal word CAUTION is used throughout this manual in the following manner:! CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. TABLE OF CONTENTS Wiring Diagrams Charging Chart Tech Labels (Expanded Data) and Multipying Factors Condenser Only Data Exploded Drawings Parts List Number Identification ! WARNING DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments. Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C February 2006
2 Sizes: 18, 24, 30, 36, 42, Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. 5. Use copper conductors only. Use conductors suitable for at least 75 C (167 F). 6. Connection for typical cooling only thermostat. For other arrangements see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start capacitor and relay are installed, start thermistor (PTC) is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used. TECHNICAL SUPPORT MANUAL
3 Size: Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. 5. Use copper conductors only. Use conductors suitable for at least 75 C (167 F). 6. Connection for typical cooling only thermostat. For other arrangements see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start capacitor and relay are installed, start thermistor (PTC) is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used. TECHNICAL SUPPORT MANUAL
4 R 22 CHARGING CHART Find the required Subcooling Temperature on the unit Rating Plate. Use the closest column on the chart below (5, 10, 15, or 20). Add or remove refrigerant until both the Liquid Line Temperature and Liquid Pressure agree with chart data. Measured Liquid Pressure (psig) Rating Plate (required) Subcooling Temperature ( F) R 22 Required Liquid Line Temperature ( F)
5 N2A318AKA N2A318GKA N2A318*KA Outdoor With EB*2X18B** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X18B** EL*18B**** EX*24F**** MV12F19**** EB*2X18B** MV08B15**** EL*18B**** MV08B15**** FS(M,U)2X18**** EB*2X24B** EL*24B**** FS(M,U)2X24**** EB*2X24B** MV08B15**** EL*24B**** MV08B15**** FEM2X18**** EB*2X24F** EMH24F**** FEM2X24**** EB*2X24F** MV12F19**** EP*18B**** EBP18**** ED*2X18B** EP*18B**** MV08B15**** EBP24**** ED*2X18B** MV08B15**** EP*24B**** FSA2X18**** ED*2X24B** EP*24B**** MV08B15**** FSA2X24**** ED*2X24B** MV08B15**** EP*24F**** FWM18**** ED*2X24F** EP*24F**** MV12F19**** FWM24**** ED*2X24F** MV12F19**** EPP024**** EBV24**** EMA2X24D** EX*24B**** EBV36**** EHD2X24A** EX*24B**** MV08B15**** EBX18**** EHD2X24A** MV08B15**** EX*24F**** EBX24**** EHD2X24A** MV12F19**** > Indicates Tested
6 N2A324AKA N2A324GKA N2A324*KA Outdoor With EB*2X24B** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X24B** EMA2X24D** EP*24F**** *9MPV EB*2X24B** *8MPV EHD2X24A** EP*24F**** *9MPV EB*2X24B** MV08B15**** EHD2X24A** *8MPV EP*24F**** MV12F19**** EB*2X24F** EHD2X24A** *8MPV EP*30B**** *8MPV EB*2X24F** *9MPV EHD2X24A** *8MPV EP*30B**** MV08B15**** EB*2X24F** *9MPV EHD2X24A** *8MPV EP*30F**** *9MPV EB*2X24F** MV12F19**** EHD2X24A** *9MPV EP*30F**** *9MPV EB*2X30B** EHD2X24A** *9MPV EP*30F**** MV12F19**** EB*2X30B** *8MPV EHD2X24A** *9MPV EX*24B**** EB*2X30B** MV08B15**** EHD2X24A** MV08B15**** EX*24B**** *8MPV EB*2X30F** EHD2X24A** MV12F19**** EX*24B**** MV08B15**** EB*2X30F** *9MPV EHD2X24A** MV16J22**** EX*24F**** EB*2X30F** *9MPV EHD2X24A** MV20N26**** EX*24F**** *8MPV EB*2X30F** MV12F19**** EHD2X30A** EX*24F**** *9MPV ED*2X24B** EHD2X30A** *8MPV EX*24F**** *9MPV ED*2X24B** *8MPV EHD2X30A** *9MPV EX*24F**** MV12F19**** ED*2X24B** MV08B15**** EHD2X30A** *9MPV FS(M,U)2X24**** ED*2X24F** EHD2X30A** *9MPV FS(M,U)2X30**** ED*2X24F** *9MPV EHD2X30A** MV08B15**** FEM2X24**** ED*2X24F** *9MPV EHD2X30A** MV12F19**** FEM2X30**** ED*2X24F** MV12F19**** EHD2X30A** MV16J22**** EBP24**** ED*2X30B** EHD2X30A** MV20N26**** EBP30**** ED*2X30B** *8MPV EL*24B**** *8MPV FSA2X24**** ED*2X30B** MV08B15**** EL*24B**** MV08B15**** EBV24**** ED*2X30F** EL*30B**** *8MPV EBV36**** ED*2X30F** *9MPV EL*30B**** MV08B15**** EBX18**** ED*2X30F** *9MPV EP*24B**** *8MPV EBX24**** ED*2X30F** MV12F19**** EP*24B**** MV08B15**** > Indicates Tested
7 N2A330AKA N2A330GKA N2A330*KA Outdoor With EB*2X30B** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X30B** EHD2X30A** *8MPV EP*30F**** MV12F19**** EB*2X30B** *8MPV EHD2X30A** *8MPV EP*36B**** EB*2X30B** MV08B15**** EHD2X30A** *8MPV EP*36B**** *8MPV EB*2X30F** EHD2X30A** *8MPV EP*36B**** MV08B15**** EB*2X30F** *8MPV EHD2X30A** *9MPV EP*36F**** EB*2X30F** *9MPV EHD2X30A** *9MPV EP*36F**** *8MPV EB*2X30F** MV12F19**** EHD2X30A** *9MPV EP*36F**** *9MPV EB*2X36B** EHD2X30A** MV08B15**** EP*36F**** *9MPV EB*2X36B** *8MPV EHD2X30A** MV12F19**** EP*36F**** MV12F19**** EB*2X36B** MV08B15**** EHD2X30A** MV16J22**** EP*36J**** EB*2X36F** EHD2X30A** MV20N26**** EP*36J**** *8MPV EB*2X36F** *8MPV EHD2X36A** EP*36J**** *8MPV EB*2X36F** *9MPV EHD2X36A** *8MPV EP*36J**** *9MPV EB*2X36F** *9MPV EHD2X36A** *8MPV EP*36J**** MV16J22**** EB*2X36F** MV12F19**** EHD2X36A** *8MPV EPP036**** EB*2X36J** EHD2X36A** *9MPV EX*36B**** EB*2X36J** *8MPV EHD2X36A** *9MPV EX*36B**** *8MPV EB*2X36J** *8MPV EHD2X36A** *9MPV EX*36B**** MV08B15**** EB*2X36J** *9MPV EHD2X36A** *9MPV EX*36F**** EB*2X36J** MV16J22**** EHD2X36A** MV08B15**** EX*36F**** *8MPV ED*2X30B** EHD2X36A** MV12F19**** EX*36F**** *9MPV ED*2X30B** *8MPV EHD2X36A** MV16J22**** EX*36F**** *9MPV ED*2X30B** MV08B15**** EHD2X36A** MV20N26**** EX*36F**** MV12F19**** ED*2X30F** EL*30B**** EX*36J**** ED*2X30F** *8MPV EL*30B**** *8MPV EX*36J**** *8MPV ED*2X30F** *9MPV EL*30B**** MV08B15**** EX*36J**** *8MPV ED*2X30F** *9MPV EL*36B**** EX*36J**** *9MPV ED*2X30F** MV12F19**** EL*36B**** *8MPV EX*36J**** MV16J22**** > Indicates Tested continued on next page
8 Multiplying Factors for other Combinations (continued) ED*2X36B** EL*36B**** MV08B15**** FS(M,U)2X30**** ED*2X36B** *8MPV EL*36F**** FSU2X36**** ED*2X36B** MV08B15**** EL*36F**** *8MPV FEM2X30**** ED*2X36F** EL*36F**** *9MPV FEM2X35**** ED*2X36F** *8MPV EL*36F**** *9MPV FSM2X36**** ED*2X36F** *9MPV EL*36F**** MV12F19**** FEM2X36**** ED*2X36F** *9MPV EMH30F**** EBP30**** ED*2X36F** MV12F19**** EMH36F**** EBP36**** ED*2X36J** EP*30B**** FSA2X30**** ED*2X36J** *8MPV EP*30B**** *8MPV FSA2X36**** ED*2X36J** *8MPV EP*30B**** MV08B15**** FWM30**** ED*2X36J** *9MPV EP*30F**** EBV24**** ED*2X36J** MV16J22**** EP*30F**** *8MPV EBV36**** EMA2X36D** EP*30F**** *9MPV EBV48**** EHD2X30A** EP*30F**** *9MPV EBX36**** > Indicates Tested
9 N2A336AKA N2A336GKA N2A336*KA Outdoor With EB*2X36F** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X36F** EHD2X36A** MV16J22**** EP*42F**** *9MPV EB*2X36B** EHD2X36A** MV20N26**** EP*42F**** MV12F19**** EB*2X36B** MV08B15**** EHD2X42A** EP*42J**** EB*2X36F** *8MPV EHD2X42A** *8MPV EP*42J**** *8MPV EB*2X36F** MV12F19**** EHD2X42A** *8MPV EP*42J**** *8MPV EB*2X36J** EHD2X42A** *8MPV EP*42J**** *9MPV EB*2X36J** *8MPV EHD2X42A** *9MPV EP*42J**** MV16J22**** EB*2X36J** *8MPV EHD2X42A** *9MPV EPP036**** EB*2X36J** *9MPV EHD2X42A** *9MPV EX*36B**** EB*2X36J** MV16J22**** EHD2X42A** MV08B15**** EX*36B**** *8MPV EB*2X42J** EHD2X42A** MV12F19**** EX*36B**** MV08B15**** EB*2X42J** *8MPV EHD2X42A** MV16J22**** EX*36F**** EB*2X42J** *8MPV EHD2X42A** MV20N26**** EX*36F**** *8MPV EB*2X42J** *9MPV EL*36B**** EX*36F**** *9MPV EB*2X42J** MV16J22**** EL*36B**** *8MPV EX*36F**** *9MPV EB*2X42L** EL*36B**** MV08B15**** EX*36F**** MV12F19**** EB*2X42L** *9MPV EL*36F**** EX*36J**** ED*2X36B** EL*36F**** *8MPV EX*36J**** *8MPV ED*2X36B** MV08B15**** EL*36F**** *9MPV EX*36J**** *8MPV ED*2X36F** EL*36F**** *9MPV EX*36J**** *9MPV ED*2X36F** *8MPV EL*36F**** MV12F19**** EX*36J**** MV16J22**** ED*2X36F** MV12F19**** EL*42F**** EX*42F**** ED*2X36J** EL*42F**** *8MPV EX*42F**** *8MPV ED*2X36J** *8MPV EL*42F**** *9MPV EX*42F**** *9MPV ED*2X36J** *8MPV EL*42F**** *9MPV EX*42F**** *9MPV ED*2X36J** *9MPV EL*42F**** MV12F19**** EX*42F**** MV12F19**** ED*2X36J** MV16J22**** EMH36F**** EX*42J**** ED*2X42J** EMH42F**** EX*42J**** *8MPV > Indicates Tested continued on next page
10 Multiplying Factors for other Combinations (continued) ED*2X42J** *8MPV EP*36B**** EX*42J**** *8MPV ED*2X42J** *8MPV EP*36B**** *8MPV EX*42J**** *9MPV ED*2X42J** *9MPV EP*36B**** MV08B15**** EX*42J**** MV16J22**** ED*2X42J** MV16J22**** EP*36F**** FSU2X36**** ED*2X42L** EP*36F**** *8MPV FS(M,U)2X42**** ED*2X42L** *9MPV EP*36F**** *9MPV FEM2X35**** EMA2X36D** EP*36F**** *9MPV FSM2X36**** EHD2X36A** EP*36F**** MV12F19**** FEM2X36**** EHD2X36A** *8MPV EP*36J**** FEM2X42**** EHD2X36A** *8MPV EP*36J**** *8MPV EBP36**** EHD2X36A** *8MPV EP*36J**** *8MPV EBP42**** EHD2X36A** *9MPV EP*36J**** *9MPV FSA2X36**** EHD2X36A** *9MPV EP*36J**** MV16J22**** EBV36**** EHD2X36A** *9MPV EP*42F**** EBV48**** EHD2X36A** MV08B15**** EP*42F**** *8MPV EBX36**** EHD2X36A** MV12F19**** EP*42F**** *9MPV > Indicates Tested
11 N2A342AKA N2A342GKA N2A342*KA Outdoor With EB*2X42J** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X42J** EHD2X42A** EP*48F**** *8MPV EB*2X42J** *8MPV EHD2X42A** *8MPV EP*48F**** *9MPV EB*2X42J** *8MPV EHD2X42A** *8MPV EP*48J**** EB*2X42J** *9MPV EHD2X42A** *8MPV EP*48J**** *8MPV EB*2X42J** MV16J22**** EHD2X42A** *9MPV EP*48J**** *8MPV EB*2X42L** EHD2X42A** *9MPV EP*48J**** *9MPV EB*2X42L** *9MPV EHD2X42A** *9MPV EP*48J**** MV16J22**** EB*2X48F** EHD2X42A** MV16J22**** EP*48L**** EB*2X48F** *8MPV EHD2X42A** MV20N26**** EP*48L**** *9MPV EB*2X48F** *9MPV EHD2X48A** EP*48N**** EB*2X48J** EHD2X48A** *8MPV EP*48N**** MV20N26**** EB*2X48J** *8MPV EHD2X48A** *8MPV EX*42F**** EB*2X48J** *8MPV EHD2X48A** *8MPV EX*42F**** *8MPV EB*2X48J** *9MPV EHD2X48A** *9MPV EX*42F**** *9MPV EB*2X48J** MV16J22**** EHD2X48A** *9MPV EX*42J**** EB*2X48L** EHD2X48A** *9MPV EX*42J**** *8MPV EB*2X48L** *9MPV EHD2X48A** MV16J22**** EX*42J**** *8MPV ED*2X42J** EHD2X48A** MV20N26**** EX*42J**** *9MPV ED*2X42J** *8MPV EL*42F**** EX*42J**** MV16J22**** ED*2X42J** *8MPV EL*42F**** *8MPV EX*48J**** ED*2X42J** *9MPV EL*42F**** *9MPV EX*48J**** *9MPV ED*2X42J** MV16J22**** EL*48F**** EX*48L**** ED*2X42L** EL*48F**** *8MPV EX*48L**** *9MPV ED*2X42L** *9MPV EL*48F**** *9MPV EX*48N**** ED*2X48F** EMH42F**** EX*48N**** MV20N26**** ED*2X48F** *8MPV EMH48F**** FS(M,U)2X42**** ED*2X48F** *9MPV EP*42F**** FS(M,U)2X48**** ED*2X48J** EP*42F**** *8MPV FEM2X42**** > Indicates Tested continued on next page
12 Multiplying Factors for other Combinations (continued) ED*2X48J** *8MPV EP*42F**** *9MPV FEM2X48**** ED*2X48J** *8MPV EP*42J**** EBP42**** ED*2X48J** *9MPV EP*42J**** *8MPV EBP48**** ED*2X48J** MV16J22**** EP*42J**** *8MPV EBV36**** ED*2X48L** EP*42J**** *9MPV EBV48**** ED*2X48L** *9MPV EP*42J**** MV16J22**** EBV60**** EMA2X48D** EP*48F**** EBX48**** > Indicates Tested
13 N2A348AKA N2A348GKA N2A348*KA Outdoor With EB*2X48J** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X48J** ED*2X60J** *9MPV EP*48N**** EB*2X48F** ED*2X60J** MV16J22**** EP*48N**** MV20N26**** EB*2X48J** *8MPV ED*2X60L** EP*60J**** EB*2X48J** *8MPV ED*2X60L** *9MPV EP*60J**** MV16J22**** EB*2X48J** *9MPV EMA2X48D** EP*60L**** EB*2X48J** MV16J22**** EHD2X48A** EP*60N**** EB*2X48L** EHD2X48A** *8MPV EP*60N**** MV20N26**** EB*2X48L** *9MPV EHD2X48A** *8MPV EX*48J**** EB*2X60J** EHD2X48A** *9MPV EX*48L**** EB*2X60J** *8MPV EHD2X48A** *9MPV EX*48N**** EB*2X60J** *8MPV EHD2X48A** MV16J22**** EX*48N**** MV20N26**** EB*2X60J** *9MPV EHD2X48A** MV20N26**** EX*60L**** EB*2X60J** MV16J22**** EHD2X60A** EX*60L**** *9MPV EB*2X60L** EHD2X60A** *8MPV EX*60N**** EB*2X60L** *9MPV EHD2X60A** *8MPV EX*60N**** MV20N26**** ED*2X48F** EHD2X60A** *9MPV FS(M,U)2X48**** ED*2X48J** EHD2X60A** *9MPV FS(M,U)2X60**** ED*2X48J** *8MPV EHD2X60A** MV16J22**** FEM2X48**** ED*2X48J** *8MPV EHD2X60A** MV20N26**** FEM2X60**** ED*2X48J** *9MPV EL*48F**** EBP48**** ED*2X48J** MV16J22**** EL*60J**** EBP60**** ED*2X48L** EL*60J**** MV16J22**** EBV48**** ED*2X48L** *9MPV EMH48F**** EBV60**** ED*2X60J** EP*48F**** EBX48**** ED*2X60J** *8MPV EP*48J**** EBX60**** ED*2X60J** *8MPV EP*48L**** > Indicates Tested
14 N2A360AKA N2A360GKA N2A360*KA Outdoor With EB*2X60L** Cooling Outdoor Ambient Temperature F, Dry Bulb Entering Temperature F, Wet Bulb CFM MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR MBh S/T AMPS^ HI PR LO PR Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ^ System amps are total of indoor and outdoor amps. Chart data is for 80 F indoor dry bulb. For indoor db temperatures other than 80 F, measure db and CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.) Sensible Capacity at db LOWER than 80 F = ( MBh x S/T ) Sensible Capacity at db HIGHER than 80 F = ( MBh x S/T ) + Multiplying Factors for other Combinations ( 80 db ) x 835 x CFM ( db 80 ) x 835 x CFM > EB*2X60L** EHD2X60A** *8MPV EX*60L**** EB*2X60J** EHD2X60A** *8MPV EX*60N**** EB*2X60J** *8MPV EHD2X60A** MV16J22**** EX*60N**** MV20N26**** EB*2X60J** MV16J22**** EHD2X60A** MV20N26**** FS(M,U)2X60**** ED*2X60J** EL*60J**** FEM2X60**** ED*2X60J** *8MPV EP*60J**** EBP60**** ED*2X60J** MV16J22**** EP*60L**** EBV60**** ED*2X60L** EP*60N**** EBX60**** EHD2X60A** > Indicates Tested
15 Saturated Suction Temperature F Data for Condenser Only (Cooling) Condenser Entering Air Temperature F N2A318AKA, N2A318GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw N2A324AKA, N2A324GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG = Gross Cooling Capacity (x BTU/hr) SDT = Saturated Temperature Leaving Compressor kw = Outdoor Unit Kilowatts
16 Data for Condenser Only (Cooling) Saturated Suction Condenser Entering Air Temperature F Temperature F N2A330AKA, N2A330GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw N2A336AKA, N2A336GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG = Gross Cooling Capacity (x BTU/hr) SDT = Saturated Temperature Leaving Compressor kw = Outdoor Unit Kilowatts
17 Data for Condenser Only (Cooling) Saturated Suction Condenser Entering Air Temperature F Temperature F N2A342AKA, N2A342GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw N2A348AKA, N2A348GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG = Gross Cooling Capacity (x BTU/hr) SDT = Saturated Temperature Leaving Compressor kw = Outdoor Unit Kilowatts
18 Data for Condenser Only (Cooling) Saturated Suction Condenser Entering Air Temperature F Temperature F N2A360AKA, N2A360GKA TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG SDT kw TCG = Gross Cooling Capacity (x BTU/hr) SDT = Saturated Temperature Leaving Compressor kw = Outdoor Unit Kilowatts
19 B Nut, Acorn NOTE: This illustration is for reference only. Your unit may differ in appearance or may not include all components shown. L Guard Fan Motor Fan 2 32 Raceway 3 Fan Top Cover A Grille, Inlet C F D Control Box E Control Box Cover Service Panel G Base, Pan
20 NOTE: This illustration is for reference only. Your unit may differ in appearance or may not include all components shown. 6 Condenser, Coil Assembly 27 Blanket, Sound ( When Used ) 1 Compressor Plug, Compressor 9 11 Bolt, SHLDR (4) Switch, High Pressure Heater, CRKC ( When Used ) Switch, Low Pressure Valve, Service Liquid Valve, Service Suction Grommet, Compressor N Support, Coil G Base Pan 36 Switch, Temp CC Heater (When Used)
21 NOTE: This illustration is for reference only. Your unit may differ in appearance or may not include all components shown. Module, Compressor Diagnostics 25 D Box, Control CTL, 2 SPD Fan 21 Capacitor 5 P Strap, Capacitor Contactor 4 33 Lug, Ground 34 Harness Assembly
22 N2A3 PARTS LIST N2A318AKA100 N2A318GKA100 N2A324AKA100 N2A324GKA100 N2A330AKA100 N2A330GKA100 N2A336AKA100 N2A336GKA100 N2A342AKA100 N2A342GKA100 N2A348AKA100 N2A348GKA100 N2A360AKA100 N2A360GKA100 KEY NO. DESCRIPTION PART NO. 1 Compressor ZR16KAPFV ZR21KAPFV ZR26KAPFV ZR32KAPFV ZR38KAPFV ZR44KAPFV ZR54KAPFV Motor, Condenser Fan Fan Blade Contactor, 30 Amp Amp Capacitor, 370V 30+5 Mfd V 35+5 Mfd V 45+5 Mfd V 50+5 Mfd V 55+5 Mfd V Mfd V Mfd Condenser Coil Service Valve, Suction Service Valve, Liquid Plug, Compressor Harness continued on next page
TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3, 3-Phase
Split System Air Conditioner N2A3, 3-Phase DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More informationTECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A0, 3-Phase
TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A0, 3-Phase DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU TION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump N2H3**C (Coastal)
TECHNICAL SUPPORT MANUAL Split System Heat Pump N2H3**C (Coastal) DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Air Conditioner (C,H,T)4A3
Split System Air Conditioner (C,H,T)4A3 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More informationTECHNICAL SUPPORT MANUAL Split System Air Conditioner N4A3, 3 Phase
TECHNICAL SUPPORT MANUAL Split System Air Conditioner N4A3, 3 Phase DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Air Conditioner H4A3, 3 Phase
TECHNICAL SUPPORT MANUAL Split System Air Conditioner H4A3, 3 Phase DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump R2HM, R2H3, WCH3**2
TECHNICAL SUPPORT MANUAL Split System Heat Pump R2HM, R2H3, WCH3**2 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump H2H3, 3 Phase
TECHNICAL SUPPORT MANUAL Split System Heat Pump H2H3, 3 Phase DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness.
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump (C,H,T)XH5
TECHNICAL SUPPORT MANUAL Split System Heat Pump (C,H,T)XH5 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The
More informationN2H3**C. Product Specifications EFFICIENT 13 SEER HEAT PUMP. Performance Series
N2H3**C Performance Series Product Specifications EFFICIENT 13 SEER HEAT PUMP FOR COASTAL APPLICATIONS 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1-phase, 60 Hz REFRIGERATION CIRCUIT Copeland Scroll compressors
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump (C,H,T)SH5
Split System Heat Pump (C,H,T)SH5 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only
More informationENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz. Min. Circuit Ampacity
ENVIRONMENTALLY SOUND REFRIGERANT T4A3 SmartComfort TX 5300 Product Specifications EFFICIENT 13 AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase,
More informationNominal Btu/hr. Min. Circuit Ampacity x 35 x 35 3½ 42, , x 35 x , , x 35 x ,000
EFFICIENT 13 SEER 3 PHASE HEAT PUMP 3 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 3 phase, 60 Hz 460 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Copeland compressors on all models Suction line accumulator
More informationTECHNICAL SUPPORT MANUAL Split System Heat Pump NXH5
Split System Heat Pump NXH5 ANGER, WARNING, CAUTION, and NOTE The signal words ANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word ANGER is only used
More informationINSTALLATION INSTRUCTIONS
NASA003SC, NASA004SC, NASA005SC, NASA006SC, NASA007SC, NASA008SC, NASA009SC, NASA010SC, NASA011SC, NASA012SC, NASA013SC, NASA014SC These instructions must be read and understood completely before attempting
More informationTECHNICAL SUPPORT MANUAL Fan Coils FSM4X6000AT
Fan Coils FSM4X60 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product
More informationCSA6. Product Specifications. SoftSound SXC 2600
16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVERr COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 2 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland Scroll compressors on all models
More informationN4A6. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT N4A6 Product Specifications EFFICIENT UP TO 16.5 SEER/12.2 13.0 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt,
More informationWCA4**4. Product Specifications
WCA4**4 AIR CONDITIONER EFFICIENT 14 SEER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz Use of the AHRI Certified TM Mark indicates a manufacturer s participation
More informationParts List, Charging Chart, Tech Labels, Wiring Diagrams
Parts List, Charging Chart, Tech Labels, Wiring Diagrams PAT3 24 - PAT3 60 Single Phase PACKAGE AIR CONDITIONER UNITS TABLE OF CONTENTS PARTS LIST 2-4 PARTS DRAWING 5-7 CHARGING CHARTS 8-9 TECH LABELS
More informationCOMMERCIAL H4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER
ENVIRONMENTALLY SOUND REFRIGERANT COMMERCIAL H4A3 DX 1300 Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt,
More informationR4H4. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationHCH6. Product Specifications
HCH6 Product Specifications HIGH EFFICIENCY 16 SEER TWO- STAGE HEAT PUMP WITH OBSERVERt COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland
More informationN4A4 C. Product Specifications
COASTAL 14 SEER AIR CONDITIONER 14 SEER/11.5 12.5 EER R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors on all models Filter drier
More informationH4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER
ENVIRONMENTALLY SOUND REFRIGERANT EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Copeland
More informationR4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
R4A4 Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors
More informationSUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)
550.39-TG1YI (994) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H5CE090 & H3CE120 7.5 AND 10 NOMINAL TONS (World 50HZ) HCE090 SUNLINE 2000 DESCRIPTION These Sunline 2000 units are completely assembled, piped
More information6-1/3 and 7-1/2 Ton Split System Air Conditioner (3 Phase) 75 to 89 MBtuh R -22 Refrigerant. Nominal Capacity BTUH
CAE Product Specifications 6-1/3 and 7-1/2 Ton Split System Air Conditioner (3 Phase) 75 to 89 MBtuh R -22 Refrigerant REFRIGERATION CIRCUIT Copeland scroll compressors on all models with single refrigeration
More informationHSH5. Product Specifications. Quiet Comfort DXC 1500
ENVIRONMENTALLY SOUND REFRIGERANT HSH5 Quiet Comfort DXC 1500 Product Specifications 15 SINGLE STAGE HEAT PUMP WITH OBSERVER COMMUNICATING CONTROL SYSTEM 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt,
More informationTECHNICAL SUPPORT MANUAL WT A Coils for Replacement Service EXA, EPA
WT A Coils for Replacement Service EXA, EPA DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More informationtechnical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO
technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before
More informationTECHNICAL SUPPORT MANUAL Fan Coils
Fan Coils FEM4X, WAHM**4, WAHT**4 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only
More informationReplacement Parts, W/D & Tech Data HHP Series
Replacement Parts, W/D & Tech Data HHP18-6 Series NOTE: This illustration is for reference only. The appearance of your unit may differ from the unit shown. KEY NO. DESCRIPTION PART NUMBER HHP18AKA1 HHP24AKA1
More informationN2AE - 50 Hz PRODUCT SPECIFICATIONS
ISO 9001:2000 REGISTERED N2AE - 50 Hz PRODUCT SPECIFICATIONS 50 Hz AIR CONDITIONING CONDENSING UNIT 230 Volt, 1-phase, 50 Hz in 1½, 2, 2½, 3, 4 tons 400 Volt, 3-phase, 50 Hz in 3, 3½, 4, 5 tons REFRIGERATION
More informationTECHNICAL SUPPORT MANUAL Coils for Manufactured Housing EMA2X, EMA4X
Coils for Manufactured Housing EMA2X, EMA4X DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More informationC4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER
ENVIRONMENTALLY SOUND REFRIGERANT C4A3 SoftSound SX 2300 Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt,
More informationDX11S Commercial & 10-Ton, Three-Phase. Cooling Capacity: 88, ,000 BTU/h
DX11S Commercial Standard Features Energy-efficient compressor Quiet operating top discharge High-efficiency copper tube / aluminum fin coil Brass liquid and suction service valves High- and low-pressure
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting
More information50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS
R FORM NO: MS0305F Products That Perform...By People Who Care AIR - COOLED SPLIT SYSTEM AIR CONDITIONERS WITH SCROLL COMPRESSORS 50 Hz COOLING CAPACITY- 60 MBH TO 1360 MBH ACCS SERIES HEB-D, EB-D SERIES
More informationEFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER
ENVIRONMENTALLY SOUND REFRIGERANT HCA7 QuietComfort DXT+ Product Specifications HIGH EFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230
More informationReplacement Parts, W/D & Tech Data CAC Series
Replacement Parts, W/D & Tech Data CAC018-060 Series NOTE: This illustration is for reference only. The appearance of your unit may differ from the unit shown. KEY NO. DESCRIPTION PART NUMBER CAC018AKA1
More informationR4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
ENVIRONMENTALLY SOUND REFRIGERANT R4A5 Product Specifications EFFICIENT 14 SEER/11.7 12.2 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1 phase,
More informationSPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS
550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece
More informationInstallation Instructions
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment
More information10+ SEER - AIR CONDITIONER
10+ SEER AIR CONDITIONER 1 1 / 2 THRU 5 TONS SPLIT SYSTEM FEATURES Service valves on all models with 3 1 / 2 stubs External refrigerant connections Copper tube / aluminum fin coil Prepainted condenser
More informationS5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS
TECHNICAL SPECIFICATIONS S5BP Series Split System Air Conditioner 71/2 Ton Energy Star rated at 11.7 EER and 11.8 IEER 10 Ton rated at 11.2 EER and 11.5 IEER R-410A Refrigerant The S5BP Series of air conditioners
More informationTECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:
036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections
More informationSUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS
550.23-TG1Y (595) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H4CE090 & H2CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 8.9-9.5 EER SUNLINE 2000 HCE090 208/230/460 VOLT ONLY 208/230/575 VOLT ONLY DESCRIPTION
More informationParts List, Charging Chart, Tech Labels, Wiring Diagrams
Parts List, Charging Chart, Tech Labels, Wiring Diagrams PHT324 PHT360 Single Phase PACKAGE HEAT PUMP UNITS TABLE OF CONTENTS PARTS LIST 2 4 PARTS DRAWING 5 7 CHARGING CHARTS 8 9 TECH LABELS PHT324 10
More informationDESCRIPTION FEATURES
SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H5CE150, H5CE180 AND H5CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at
More informationProduct Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES
Base Series Fan Coil Sizes 018 thru 036 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split system heat pumps and air
More informationThis parts list is current as of the above revision date. See for the current revision.
Parts List This parts list is current as of the above revision date. See http://www.rheempartslists.net/92-800-.pdf for the current revision. Condensing Units Table of Contents Model Explanation...................................................................................................................
More informationE1RA, E2RA SERIES - 10 SEER, 1PH & 3PH HEAT PUMP- OUTDOOR UNIT
L2 L1 LOW SIDE PRESSURE PORT www.source1parts.com E1RA, E2RA SERIES - 10 SEER, 1PH & 3PH HEAT PUMP- OUTDOOR UNIT HVAC SERVICE PARTS Supersedes:035-13604-001 Rev. E (0603) 035-13604-001 Rev. F (0104) 1
More informationProduct Data FF1E LEGACY LINE FAN COIL SIZES 018 THRU 037 FEATURES
LEGACY LINE FAN COIL SIZES 018 THRU 037 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split-system heat pumps and air
More informationCHP
Packaged Unit Heat Pump CHP16-024-030-036-048-060 2-5 Ton Cooling 23,000-57,500 Btuh Heating 12,800-85,300 Btuh (5-25 kw) Optional Electric Heating FEATURES Designed for outdoor rooftop or ground level
More informationProduct Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES
Base Series Fan Coil Sizes 018 thru 036 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split -system heat pumps and air
More informationDZ14S Commercial 3-5 TON, THREE-PHASE SPLIT SYSTEM HEAT PUMP 14 SEER / R-410A
DZ14S Commercial Cooling Capacity: 34,600 to 56,500 BTU/h Heating Capacity: 32,800 to 59,000 BTU/h 3-5 TON, THREE-PHASE SPLIT SYSTEM HEAT PUMP 14 SEER / R-410A Contents Nomenclature...2 Product Specifications...3
More informationProduct Data. Features/Benefits. 38HDL Cooling Only Condensing Unit. 1 1 / 2 to 5 Nominal Tons
Product Data 38HDL018-060 Cooling Only Condensing Unit 1 1 / 2 to 5 Nominal Tons The 38HDL energy-efficient condensing unit incorporates innovative technology to provide reliable cooling performance. Built
More informationThis parts list is current as of the above revision date. See for the current revision.
Parts List This parts list is current as of the above revision date. See http://www.rheempartslists.net/92-801-.pdf for the current revision. Condensing Units Table of Contents Model Explanation...................................................................................................................
More informationR4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT
EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz R4A3 Product Specifications REFRIGERATION CIRCUIT S Scroll compressors
More informationSSZ14 PRODUCT SPECIFICATIONS 14 SEER HIGH-EFFICIENCY, R-410A SPLIT SYSTEM HEAT PUMP 1½ TO 5 TON
HIGH-EFFICIENCY, R-410A SPLIT SYSTEM HEAT PUMP The Goodman uses the environmentally friendly refrigerant R-410A and features operating sound levels that are among the best in the heating and cooling industry.
More informationREPLACEMENT PARTS MANUAL
REPLACEMENT PARTS MANUAL PACKAGE HEAT PUMP Models: PH242-A PH363-A PH302-A PH363-B General Notes Revised and/or additional pages may be issued from time to time. A complete and current manual consists
More informationV High Efficiency Series
UNIT DISCONNECT(S) BEHIND THIS PANAL Commercial HVAC V High Efficiency Series Wallmount Air Conditioners PERFORMANCE: Efficiency rating of 9.0/9.5 EER Electric heat available from 5 kw to 18 kw Designed
More informationInstallation Instructions
265V Subbase Receptacle Accessory Kit For Use With Packaged Terminal Air Conditioner Installation Instructions INTRODUCTION These instructions cover the installation of the 265V Subbase Receptacle Accessory
More informationGPC14H 2- to 5-Ton Packaged Air Conditioner Up to 14 SEER
Cooling Capacity: 24,000-57,500 BTU/H H 2- to 5-Ton Packaged Air Conditioner Up to 14 SEER Contents Nomenclature... 2 Product Specifications... 3 Expanded Cooling Data... 5 Airflow Data... 18 Heater Kit
More informationTSA6. Product Specifications. SmartComfort TXC 5600
ENVIRONMENTALLY SOUND REFRIGERANT TSA6 SmartComfort TXC 5600 Product Specifications 16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230
More informationProduct Data PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE:
PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 Product Data FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE: 40 -va, 208/230 -v transformer, 60 Hz, 1 Phase. FAN MOTOR:
More informationTSTAT0201CW (Sold Separately) Qualifying models only. Max. Fuse or Breaker
HVA9 Product Specifications HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS Model PSA4BG Series M1200 Product Line Ultra High Efficiency Air Conditioner 20 SEER Residential System 2-5 Ton Capacities 2 The iq Drive air conditioner system features modulating
More informationQ7RE Series Single Packaged Heat Pump, Single Phase
TECHNICAL SPECIFICATIONS Q7RE Series Single Packaged Heat Pump, Single Phase 14 SEER, 8.0 HSPF 2 thru 5 Ton Units Cooling: 23,400 to 55,500 Btuh Heating: 21,800 to 56,000 Btuh The Q7 Series single packaged
More informationPHR5. Product Specifications
PHR5 Product Specifications UP to 15.5 SEER, UP to 12.5 EER, PACKAGE HEAT PUMP UNITS, 2 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally balanced R
More informationTECHNICAL INFORMATION MANUAL
TEHNIAL INFOMATION MANUAL SSZ 16 SEE Split System Heat Pumps Models listed on page 3 efer to Service Manual S6200005 for installation, operation, and troubleshooting information. All safety information
More informationOwner s Information Manual
50ES---A and 50VL---C Comfort 13SEERThreePhase2½---5NominalTons (Sizes 30---60) Comfort 14 SEER Single and Three Phase 2---5 Nominal Tons (Sizes 24---60) Single Packaged Air Conditioner System With Puronr
More informationAFAIR12B. Features. Efficiency: 12 SEER. Warranty: 10-year limited compressor 5-year limited parts. Capacity: 1-1/2 to 5-ton.
AFAIR12B Air Conditioners Features Top discharge directs hot air and noise away from the living area Durable Copeland scroll compressor with internal pressure relief valves and inherent thermal protection
More informationCAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE
COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Single stage cooling capacity control on all 0 241 models Two stage cooling capacity control on
More informationPAB SERIES 3thru6-1/3Ton. Belt Drive 10 SEER CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT /01
PAB SERIES 3thru6-1/3Ton Belt Drive CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT 10 SEER SINGLE PACKAGE Electric cooling, self contained for year-round comfort. Systems can be installed on roof top
More informationGSC13 Split System Air Conditioner
Split System Air Conditioner 13 SEER / R-22 1½ to 5 Tons Contents Nomenclature... 2 Product Specifications... 3 Expanded Cooling Data... 4 AHRI Ratings... 18 Wiring Diagram... 19 Dimensions... 20 Accessories...
More informationThis parts list is current as of the above revision date. See for the current revision.
Parts List This parts list is current as of the above revision date. See http://www.rheempartslists.net/92-800-.pdf for the current revision. Condensing Units Table of Contents Model Explanation...................................................................................................................
More informationZHA/ZHB SERIES WARNING
Service Literature Corp. 09-L Revised 7-08 ZHA/ZHB SERIES, 4, 5 and 6 ton 0.6 to kw ZHA/ZHB06, 048, 060, 07 The ZHA/ZHB packaged electric heat pump units are available in standard cooling efficiency (06S,
More information10+ SEER - AIR CONDITIONER
10+ SEER AIR CONDITIONER 1 1 / 2 THRU 5 TONS SPLIT SYSTEM FEATURES Service valves on all models with 3 1 / 2 stubs External refrigerant connections Copper tube / aluminum fin coil Prepainted condenser
More informationFRICTION-FREE COIL TRACKS AIR-COOLED CONDENSERS FROM 28 MBH TO 4000 MBH
FRICTION-FREE COIL TRACKS AIR-COOLED CONDENSERS FROM 8 MBH TO 4000 MBH TABLE OF CONTENTS NOMENCLATURE............................. 3 FEATURES.................................... 4 KV SERIES FEATURES.........................
More informationCAC SERIES 3 to 5 Ton Split System Condensers
CAC SERIES 3 to 5 Ton Split System Condensers STANDARD FEATURES 10 11 SEER Three Phase High efficiency scroll compressors on all models Copper tube / aluminum fin coil Prepainted condenser fins Top air
More informationProduct Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES
FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system
More informationSSX14 PRODUCT SPECIFICATIONS 14 SEER / R-410A HIGH-EFFICIENCY SPLIT SYSTEM AIR CONDITIONER 1½- TO 5-TON COOLING CAPACITY 18,000 TO 56,800 BTU/H
PRODUCT SPECIFICATIONS 14 SEER / R-410A 1½- TO 5-TON COOLING CAPACITY 18,000 TO 56,800 BTU/H HIGH-EFFICIENCY SPLIT SYSTEM AIR CONDITIONER The Goodman Air Conditioner uses the environmentally friendly refrigerant
More informationProduct Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES
FFMA BASE SERIES FAN COIL SIZES 018 TO 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split- system
More informationSPLIT-SYSTEM AIR-COOLED CONDENSING UNITS
(1100) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H3CE180 & 240 15 AND 20 NOMINAL TONS DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at the factory to provide one-piece
More informationSSZ14. High-Efficiency. Split System Heat Pump. Cooling Capacity: 18,000 to 57,600 BTU/h. Up to 15 SEER & 8.5 HSPF
High-Efficiency Cooling Capacity: 18,000 to 57,600 BTU/h Heating Capacity: 18,000 to 59,000 BTU/h Split System Heat Pump Up to 15 SEER & 8.5 HSPF Contents Nomenclature... 2 Product Specifications... 3
More informationSPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS
550.13-TG11Y (0500) SPLIT-SYSTEM EVAPORATOR BLOWER K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS EER 8.5 DESCRIPTION This completely assembled dual circuit evaporator blower includes a well-insulated
More information12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT
Service Literature Corp. 9711 L7 CB29M CB30M ELITE 10 CB29M and ELITE 12 CB30M SERIES UNITS INCLUDING ECB29 The Elite 10 CB29M and Elite 12 CB30M are high efficiency blower coils. Several models are available
More informationCPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h
CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4
More informationFRICTION-FREE COIL TRACKS AIR-COOLED CONDENSERS FROM 28 MBH TO 4000 MBH
FRICTION-FREE COIL TRACKS AIR-COOLED CONDENSERS FROM 8 MBH TO 4000 MBH TAbLE Of CONTENTs NOMENCLATURE............................. 3 features.................................... 4 KV series features.........................
More informationV33B High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven
More informationCAC SERIES 12-1/2 Thru 20 Ton
CAC SERIES 12-1/2 Thru 20 Ton SPLIT SYSTEM COMMERCIAL AIR CONDITIONER CONSTRUCTION Triple step pre--painted galvanized steal pre--coated inside and out -- using a polyester top coat, over a urethane primer
More informationInstallation Instructions
00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON
More informationV33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has
More informationCPC Commercial. 7½- to 12½-Ton Three-Phase. up to 11.5 EER. Cooling Capacity: 90, ,000 BTU/h. Packaged Air Conditioners
CPC Commercial Cooling Capacity: 90,000 118,000 BTU/h 7½- to 12½-Ton Three-Phase Packaged Air Conditioners up to 11.5 EER Standard Features R-410A chlorine-free refrigerant High-efficiency scroll compressor
More informationDESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS
DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil
More informationProduct Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES
FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system
More informationAPARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R-410A and R-22 SYSTEMS
FSA Product Specifications APARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R-410A and R-22 SYSTEMS 1½ THRU 3 TONS FEATURES TXV metering device factory installed
More information