MTEP13 SPM #2- Central Region. March 25, 2013

Size: px
Start display at page:

Download "MTEP13 SPM #2- Central Region. March 25, 2013"

Transcription

1 MTEP13 SPM #2- Central Region Ameren Missouri March 25, 2013

2 Ameren Missouri Project Review

3 Central Region: Ameren Missouri Ameren Missouri has a total of 10 project proposals that are recommended for moving to Appendix A or Appendix B in MTEP13 Four (4) project proposals are recommended for moving to Appendix A in MTEP13 2 Baseline Reliability 2 Other Of those four projects: 2 project proposals have estimated cost greater than (or equal to) $5M 2 project proposals have estimated cost between $1M and $5M Six (6) project proposals s are recommended e for moving to Appendix B in MTEP13 3

4 MTEP13 Central SPM #2 Projects Moving to Appendix A in MTEP13 4

5 AmerenMO: P3699 Bland 345/138 kv Substation Install new 345/138 kv, 560 MVA transformer at Bland Substation Install 138 kv bus at Bland Substation Split Tegeler-Osage 138 kv line into a Tegeler- Bland 138 kv line and a Bland-Osage 138 kv line. Expected In Service Date: 12/1/2015 Estimated Cost: $13,780,000 The status of this project has changed since the first SPM, where it was presented as an Appendix B project

6 AmerenMO: P3699 System Needs: Outage of Gray Summit 138 kv 1-2 Bus-Tie (NERC Category C2 event) would cause Wildwood-Gray Summit lines to be loaded to about 108% of summer emergency rating in 2015 summer Target Appendix: A in MTEP13 Preliminary Project Type: Baseline Reliability (Cost Shared) The status of this project has changed since the first SPM, where it was presented as an Appendix B project 6

7 AmerenMO: P2998 Overton Substation Transformer Replacement Replace the existing 300 MVA, 345/161 kv transformer with a 560 MVA unit. Expected In Service Date: 6/1/2014 Estimated Cost: $7,128,000

8 AmerenMO: P2998 System Needs: For an outage of Thomas Hill- Kingdom City 345 kv Line with Thomas Hill #3 generation offline (NERC Category C3 event), the existing transformers would be overloaded Loading as high h as 120% during contingency Target Appendix: A in MTEP13 Preliminary Project Type: Other Reliability (TBD) 8

9 AmerenMO: P4062 Osage Substation Transformer Replacement Replace the MVA 161/138 kv transformers with a 300 MVA unit. Expected In Service Date: 6/1/2014 Estimated Cost: $1,965,000

10 AmerenMO: P4062 System Needs: For an outage of Montgomery-Overton kv Line with Thomas Hill #3 generation offline (NERC Category C3 event), the existing transformers would be loaded to about 104% of their rating (TO study) Target Appendix: A in MTEP13 Preliminary Project Type: Other Reliability (Not Cost Shared) 10

11 AmerenMO: P3693 Mauer Lake 161 kv Breaker Install a 161 kv breaker on the Missouri City line terminal, with a minimum current carrying capability of 1200 A. Expected In Service Date: 6/1/2013 Estimated Cost: $1,793,000

12 AmerenMO: P3693 System Needs: Low voltages on the 161 kv and 69 kv at Maurer Lake for an outage of the Missouri City- Maurer Lake 161 kv line (NERC Category B event) Voltage low of 0.91 per unit at Excelsior Springs161 kv bus, assume lower downline at Maurer Lake bus, which is not modeled but equivalized at Excelsior Springs Target Appendix: A in MTEP13 Preliminary Project Type: Baseline Reliability (Not Cost Shared) 12

13 MTEP13 Central SPM #2 Projects Moving to Appendix B in MTEP13 13

14 AmerenMO: P2996 Montgomery-Spencer Creek-Sub T 345 kv Line Upgrade Install new structures on 187 miles between Montgomery Hills and Spencer Creek to allow for 110 degree C operation. Expected In Service Date: 12/1/2014 Estimated Cost: under development System Needs: Age and condition of existing structures. Alternatives: None Target Appendix: B in MTEP13 Preliminary Project Type: Other (Condition) 14

15 AmerenMO: P4075 Sioux-Huster kv Reconductor Reconductor 5.9 miles of ACSR conductor with conductor capable of carrying 1600 A under summer emergency conditions. Replace 1200 A terminal equipment (disconnect switches, CT's, bus conductor) at Huster with equipment capable of carrying 1600 A or better. Expected In Service Date: 6/1/2020 Estimated Cost: $5,900,000 System Needs: For an outage of Sioux-Belleau kv Line with Callaway generation offline, the existing conductor would be loaded to about 104% of its rating in 2021 summer case, with 1- in-10 load levels. Target Appendix: B in MTEP13 Preliminary Project Type: Other Reliability

16 Projects Moving to Appendix B Less than $5M Target Appendix PrjID Project Name Project Description B in MTEP Meramec Watson kv Line Reconductoring Reconductor 3.7 miles of 795 kcmil AA conductor between Watson Substation and the Mackenzie Switch Rack with conductor capable of carrying 1200 A under summer emergency conditions. Expected ISD Estimated Cost System Need 1 Jun 18 $2,107,484 C3: Existing conductor would be loaded to 123.6% of its 233 MVA rating for the coincident outage of the Central Watson 1 and Baumgartner Watson kv Lines, based on 2011 analysis. Possible loss of Watson Substation load should this line trip. B in MTEP Maurer Lake 161 kv Capacitor Bank Install 30 Mvar, 161 kv capacitor bank and PCB. B in MTEP Pike Substation Transformer Reconnectiion Reconnect Pike kv Transformer #1 to 161 kv Bus #1. B in MTEP Rush Joachim kv Position Upgrade Rush Island 345 kv Switchyard Upgrade the Rush Island terminal of the Rush Island Joachim kv line to a minimum of 2500 A capability by replacing the 2000 A wavetrap and reconnecting the 2000:5A CTs to 2500:5A. 1 Jun 15 $1,250,000 Need voltage support to Maurer Lake for the outage of the Missouri City Maurer Lake 161 kv Line. Maurer Lake 161 kv voltage would be about 87% in 2016 summer following the line outage, based on 2011 analysis. 1 Jun 14 $100,000 Voltage support to Pike area in response to outage of Pike Bus Tie Breaker #16082 or Pike Peno Creek outage. Pike 161 kv voltage would be 94% in 2016 summer following these outages or an outage to Pike Dundee 3 with Peno Creek generation offline, based on 2011 analysis. 1 Jun 17 $100,000 Maintain import capability into Ameren Missouri.

17 The following list of projects are in the MISO planning database, but are not currently scheduled to change appendices. These are provided for informational purposes. Projects Currently in Appendix B and C 17

18 Projects Currently in Appendix B and C (cont.) Expected Appendix PrjID Project Name Project Description ISD Estimated Cost System Need B 2774 Adair Wind Farm Connect Wind Farm at Adair Substation 1 Nov 20 G578 generator connection. (In suspension) C 3870 MTEP11 TCFS Flowgate C Option 6 Baldwin Grand Tower NW Cape 345 kv; Grand Tower EW Frankfurt 345kV; Grand Tower Joppa 345kV; Norris Albion 345kV; Baldwin 345/138kV Xfmr 1 Jan 17 $392,500,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line C 3871 MTEP11 TCFS Flowgate C Option 7 Baldwin Grand Tower NW Cape 345 kv; Norris Albion 345kV; Baldwin 345/138kV Xfmr C 3866 MTEP11 TCFS Flowgate C Option 2 Baldwin Grand Tower NW Cape 345 kv; Grand Tower 345/138kV Xfmr 1 Jun 99 1 Jun 99 $212,500,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line $162,500,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line C 3868 MTEP11 TCFS Flowgate C Option 4 Grand Tower Joppa 345kV line 1 Jun 99 $100,000, MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line C 3867 MTEP11 TCFS Flowgate C Option 3 Grand Tower EW Frankfurt 345kV line 1 Jun 99 $80,000,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line C 3869 MTEP11 TCFS Flowgate C Option 5 Norris City Albion 345kV line 1 Jun 99 $50,000,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line

19 Projects Currently in Appendix B and C (cont.) Appendix PrjID Project Name Project Description C 3025 Rivermines N. Farmington Second 138 Rivermines N. Farmington 138 kv Line kv Line Construct a second 5.5 mile 138 kv line. Expected ISD Estimated Cost System Need 1 Jun 19 $7,500,000 Avoid loss of North Farmington load for outage of existing Rivermines N. Farmington 138 kv (Category B event) 1 Jun 16 $6,600,000 Performance/ Reliability Issue; Re evaluating project scope in light of projected load growth in area C 2993 Dupo Ferry Buck Knob Reconductoring Dupo Ferry Buck Knob 138 kv Line 1 Jun 16 $ Performance/ Reliability Issue; Re evaluating Replace 22 mi. of ACSR with maximum size conductor existing towers will support. C 3865 MTEP11 TCFS Flowgate C Option 1 Upgrade Fredericktown Fredericktown Tap 161kV to 297 MVA C 2990 Conway Tyson 3 and 4 Increase Ground Clearance Conway Tyson 3 and kv Increase ground clearance on Tyson Orchard Gardens sections (7 miles) C 2298 AECI Enon 345/161 kv Substation Install kv Breakers on incoming 345 kv lines 1 Jun 99 $3,900,000 MTEP11 Top Congested Flowgate Study: Relieves projected contingency overload on Fredericktown Fredericktown Tap 161kV line 1 Jun 22 $700,000 Category C3 line + gen (coincident outage of Mason Wildwood kv with Meramec gen #4) 1 Jun 99 $0 Upgrade to reduce extent of outage for Belleau 345 kv Breaker V31 failure to reduce loading on Warrenton Big Creek 161 kv line. 1 Jun 99 $0 Upgrade substation capacity to handle loading for outage of Kelso Lutesville 345 kv line outage with Callaway generation offline (Category C3). Need contingent upon non Ameren load located in Northwest Kentucky 1 Jun 99 $0 Gen. Related voltage support during pump conditions? C 2292 Kelso 345/161 kv Substation ti Replace 336 MVA, 345/161 kv 1 J 99 $0 U d b t ti it t h dl l di f Transformer with 450 MVA Transformer C 2987 Taum Sauk Capacitor Banks Taum Sauk 138 kv Capacitor Banks 2 30 Mvar banks; kv synchronous PCBs.

20 Projects Currently in Appendix B and C (cont.) Appendix PrjID Project Name Project Description C 3000 Miller Substation Transformer Addition Miller 138/161 kv Substation Install a new 300 MVA 138/161 kv transformer to convert Miller Zion line to 161 kv operation and increase voltage support to Jefferson City, Missouri area. C 3008 Overton Capacitor Bank Overton 161 kv Capacitor Bank 1 90 Mvar capacitor bank, kv synchronous PCB, kv reactor. C 3027 Campbell Substation 2nd. 345/138 kv Campbell 345/138 kv Substation 2nd Transformer 560 MVA transformer; New 12.8 mi. Roxford Campbell 345 kv 3000 A summer emergency capability line; kv PCBs (1 Campbell, 1 Roxford); kv Campbell. C 3028 Campbell Euclid Page 138 kv Line Campbell Euclid Page 138 kv Line Rebuild Rebuild 5.25 mi. double circuit 138 kv 2000 A SE capability kv PCBs (2 Campbell, 1 Page). Operate Euclid 138 kv Bus Tie normally closed. C 3031 Page Area 345/138 kv Substation Page Area 345/138 kv Substation MVA transformers kv PCBs: 2 transformer, 1 bus tie, 6 line (2 Warson, 2 Page, 2 Hunter). Expected ISD Estimated Cost System Need 1 Jun 99 $0 Enhance support to Jefferson City area 1 Jun 99 $0 System Upgrade voltage support to Booneville area 1 Jun 99 $0 System Upgrade 1 Jun 99 $0 System Upgrade, Relief for Mason 345/138 kv Xfmrs, Reinforcement for Callaway 2, retirement of Meramec generation 1 Jun 99 $0 System Upgrade, Relief for Mason 345/138 kv Xfmrs, Reinforcement for Callaway 2

21 Projects Currently in Appendix B and C (cont.) Appendix PrjID Project Name Project Description C 3032 Campbell Page Mason 345 kv Line Campbell Page Mason 345 kv Line New 16.5 mi A summer emergency capability line, plus reutilization of 14.5 miles of existing Page Sioux 4 at 345 kv. Expected ISD Estimated Cost System Need 1 Jun 99 $0 Relief for Mason 345/138 kv Xfmrs (Category C3 contingency events line + generator outages) C 3034 Loose Creek Kingdom City 345 kv Line Loose Creek Kingdom City 345 kv Line 1 Jun 99 $0 Transfer Capability; Callaway 2 Outlet New 25 mile 345 kv, 3000 A line kv PCBs at Loose Creek, kv PCBs at Kingdom City.. C 3038 Loose Creek Barnett Windsor Pleasant Loose Creek Barnett Windsor Pleasant 1 Jun 99 $0 Transfer capability, access to renewables Hill 345 kv Line Hill 345 kv Line New 138 mile 345 kv, 3000 A line. 560 MVA, 345/161 kv transformer at Barnett Substation. 345 kv PCBs: 2 at Loose Creek, 2 at Barnett, 2 at Windsor, 2 at Pleasant Hill. C 3042 Palmyra Tap Thomas Hill Fairport 345 kv Palmyra Tap Thomas Hill Fairport New 1 Jun 99 $0 Transfer capability; Wind Integration Line 122 mile 345 kv, 3000 A line. 345 kv PCBs: 2 at Palmyra, 2 at Thomas Hill, 2 at Fairport. C 3045 St. Francois Fletcher 345 kv Line St. Francois Fletcher 345 kv Line New 1 Jun 99 $0 Transfer capability 48 mi A SE capability. 345 kv terminals at St. Francois & Fletcher. Install WAMS PMU at St. Francois on new line terminal.

22 Projects Currently in Appendix B and C (cont.) Appendix PrjID Project Name Project Description Expected ISD Estimated Cost System Need C 3171 West Adair Fairport 345 kv Line New 113 mile 345 kv, 3000 A line 1 Jun 99 $0 Renewables Integration C 3173 Fairport Palmyra Tap 765 kv Line New 176 mile 765 kv, approx A line 1 Jun 99 $0 Renewables Integration C 3174 Palmyra Tap 765/345 kv Substation New 2250 MVA, 765/345 kv Substation 1 Jun 99 $0 Renewables Integration C 3179 Palmyra Tap Montgomery 765 kv Line New 68 mile 765 kv, approx A line 1 Jun 99 $0 Renewables Integration C 3180 Montgomery 765/345 kv Substation New 2250 MVA, 765/345 kv Substation 1 Jun 99 $0 Renewables Integration C 3181 Montgomery St. Francois 765 kv Line New 104 mile 765 kv, approx A line 1 Jun 99 $0 Renewables Integration C 3182 St. Francois Grand Tower 765 kv Line New 63 mile 765 kv, approx A line 1 Jun 99 $0 Renewables Integration C 3187 St. Francois 765/345 kv Substation New 2250 MVA, 765/345 kv Substation 1 Jun 99 $0 Renewables Integration

23 City of Columbia, MO (CWLD) No projects currently in the planning database for CWLD 23

24 Contact Information William Kenney Michael Dantzler 24

Chapter 7 - Appendix A

Chapter 7 - Appendix A Chapter 7 - Appendix A Transmission and Distribution Supplemental Information Table 7A.1 MTEP Transmission Projects in Missouri 1 Project Approved Project Title Project Description Category Estimated Cost

More information

MTEP14 South SPM #2. MISO Texas Project Information. April 7, 2014

MTEP14 South SPM #2. MISO Texas Project Information. April 7, 2014 MTEP14 South SPM #2 MISO Texas Project Information April 7, 2014 MISO Southern Region EAST TEXAS ELECTRIC COOPERATIVE 2 East Texas Electric Cooperative (ETEC) No projects submitted for moving to Appendix

More information

Impacts of MISO DPP-2016-February (West, ATC, MI, South) Projects on PJM Facilities

Impacts of MISO DPP-2016-February (West, ATC, MI, South) Projects on PJM Facilities Impacts of MISO DPP-2016-February (West, ATC, MI, South) 1. MISO generators studied: Projects on PJM Facilities Net MW size (Summer) Net MW size (Winter) Service DPP Project Type Region Fuel Type POI J432

More information

Market Efficiency Planning Study

Market Efficiency Planning Study Market Efficiency Planning Study West SPM June 12, 2013 SPM : Market Efficiency Planning Study Update March 25, 2012 Market Efficiency Planning Study Recap Objective is to execute an annual structured

More information

ATTACHMENT Y STUDY REPORT

ATTACHMENT Y STUDY REPORT Attachment Y Study Edwards Unit 1: 90 MW Coal Retirement December 31, 2012 ATTACHMENT Y STUDY REPORT 7/5/2013 PUBLIC / EXECUTIVE SUMMARY MISO received an Attachment Y Notification of Potential Generation

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic November 04, 2013 2013 RTEP Baseline Analysis Update 11/04/2013 AE Transmission Zone Cost Change for B2354 Install second 230/69kV transformer and 230kV circuit

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 28 Blythewood 115 kv Switching Station: Construct 03087A Construct Blythewood Switching Station with four 115 kv line terminals, with plans to expand to 230 kv at a future date. Fold in the

More information

Black Hills Project Summary

Black Hills Project Summary 2016 Rule 3627 Report Black Hills Project Summary Page 1 of 38 Black Hills Project Summary Colorado PUC E-Filings System D 1 2016 Rule 3627 Report Black Hills Project Summary Page 2 of 38 Category Transmission

More information

Annual Issues Review: MISO Issues Near the PJM Seam MISO-PJM IPSAC 3/30/18

Annual Issues Review: MISO Issues Near the PJM Seam MISO-PJM IPSAC 3/30/18 Annual Issues Review: MISO Issues Near the PJM Seam MISO-PJM IPSAC 3/30/18 MTEP17 Report MTEP17 Report and Appendices finalized December 2017 Appendix AB Appendix A: Board approved projects Appendix B:

More information

MILLIGAN SOLAR PROJECT

MILLIGAN SOLAR PROJECT February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission

More information

MTEP14 West SPM #2. ATC, DPC, XEL Project Review. April 2, 2014

MTEP14 West SPM #2. ATC, DPC, XEL Project Review. April 2, 2014 MTEP14 West SPM #2 ATC, DPC, XEL Project Review April 2, 2014 MISO West Region AMERICAN TRANSMISSION COMPANY, LLC 2 Project Count ATC A in MTEP14 Project Summary 30 Projects by type 25 20 15 10 5 Other

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic July 26, 2016 Reliability Analysis Update MetEd Transmission Zone N-1 First Energy Planning Criteria (FERC Form 715): The North Boyertown West Boyertown 69 kv is

More information

Twin Cities Minnesota Zone Meeting Xcel Energy. May 11, 2005 Bloomington, MN

Twin Cities Minnesota Zone Meeting Xcel Energy. May 11, 2005 Bloomington, MN Twin Cities Minnesota Zone Meeting Xcel Energy May 11, 2005 Bloomington, MN Overview of Presentation Xcel Energy Projects: Aldrich to St Louis Park 115 kv line Eden Prairie to Edina 115 kv line Eden Prairie

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Appendix B. Summary of Changes to the Year Assessment

Appendix B. Summary of Changes to the Year Assessment Appendix B Summary of Changes to the 2003 10- Assessment For the below tables, the following color-coding scheme was utilized for indicating what type of change has been made to the 10- Assessment from

More information

Sub Regional RTEP Committee - Southern. August 19, 2011

Sub Regional RTEP Committee - Southern. August 19, 2011 Sub Regional RTEP Committee - Southern August 19, 2011 2011 RTEP Analysis Summary 2010 2015 Project Updates 2016 Analysis NERC Category A, B NERC Category C (N-1-1 in progress) Load Deliverability Generator

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Generation Deactivation Notification Update

Generation Deactivation Notification Update Generation Deactivation Notification Update Transmission Expansion Advisory Committee November 8, 2018 Generation Deactivations for 2018 2 Generation Deactivation ATSI Transmission Zones Bruce Mansfield

More information

Western Area Power Administration

Western Area Power Administration 2014/15 Integrated System (IS) 890 Local Planning Stakeholder Meeting #2 Western Area Power Administration Upper Great Plains Region Transmission Planning Stakeholder Meeting Wednesday, December 10 th,

More information

Sub-Regional RTEP Committee PJM South

Sub-Regional RTEP Committee PJM South Sub-Regional RTEP Committee PJM South SRRTEP - South December 1, 2016 www.pjm.com PJM Baseline Project B2185 Update Problem: NERC Category B Violation (DVP Analysis) The 2017 summer base case indicates

More information

Entergy Gulf States, Inc. (Texas) Proposed Transmission Reliability Projects

Entergy Gulf States, Inc. (Texas) Proposed Transmission Reliability Projects Entergy Gulf States, Inc. (Texas) Proposed Transmission Reliability Projects Entergy Transmission Planning Summit New Orleans, LA July 14, 2005 1 2004-06 EGSI-TX Transmission Western Region Reliability

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 34 Aiken Trans - Aiken Hampton 115 kv Line: Upgrade 1272A Upgrade the 115 kv line between Aiken and Aiken Hampton substations from 336 ACSR to 1272 ACSR. Total line length approximately 3.7

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

South Dakota 890 Study

South Dakota 890 Study South Dakota 890 Study September 16, 2011 South Dakota 890 Study Presentation of 890 Study results from 2011 Includes WAPA suggested system improvements and timelines Stakeholder Feedback Questions? 2

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section

More information

Status of PNM s Completed Transmission Construction Projects 11/30/2017

Status of PNM s Completed Transmission Construction Projects 11/30/2017 Status of s Completed Transmission Construction Projects Second Tah Ta Hey 115/345 kv Transformer Yah Ta Hey Switching Station On January 9, 2015, filed with the NMPRC under NMPRC Rule 440 information

More information

Pacific Gas and Electric Company s Revised 2016 Annual Progress

Pacific Gas and Electric Company s Revised 2016 Annual Progress March 06, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff 155 North 400 West Salt Lake City, UT 84103-1114 Subject: Report Pacific Gas and Electric

More information

2016 SPP Transmission Expansion Plan Project List Kansas Projects

2016 SPP Transmission Expansion Plan Project List Kansas Projects WR Zonal Reliability $9,308,090 Build 6.7 mile Clay Center Switching Station to TC Riley 115 kv line 6/1/2018 10/1/2012 115 6.7 Install a 2000 Amp bus system, GOAB switches, metering and WR Zonal Reliability

More information

SERTP rd Quarter Meeting

SERTP rd Quarter Meeting 2015 SERTP SERTP 2015 3 rd Quarter Meeting 2nd RPSG Meeting September 24 th, 2015 APC Headquarters Birmingham, AL 2015 SERTP Process Information The SERTP process is a transmission planning process. Please

More information

Market Congestion Planning Study (South)- Robustness Analysis. Economic Planning Users Group Meeting August 11 th, 2017

Market Congestion Planning Study (South)- Robustness Analysis. Economic Planning Users Group Meeting August 11 th, 2017 Market Congestion Planning Study (South)- Robustness Analysis Economic Planning Users Group Meeting August 11 th, 2017 Key Takeaways The benefit calculations were updated due to a flowgate rating correction

More information

CUSTOMER/ TWIN ARROWS PROJECT

CUSTOMER/ TWIN ARROWS PROJECT A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset

More information

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission

More information

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 24 Queensboro 115 kv Switching Station: Construct 0062A,B,C,D Build 4-terminal 115 kv switching station at Queensboro substation. Terminate the existing Queensboro St. Andrews, Church Creek

More information

Falcon-Midway 115 kv Line Uprate Project Report

Falcon-Midway 115 kv Line Uprate Project Report Falcon-Midway 115 kv Line Uprate Project Report 12/1/2008 1 Background The function of this project is to uprate the 26.7 miles of Tri-State s 115 kv line between Midway and Falcon substations from 50

More information

Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co)

Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co) Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co) Participants: Great River Energy Xcel Energy Inc. Executive Summary This study is done to address various load serving

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Tyler 60 kv Shunt Capacitor Installation of a 2x10 MVAR capacitor bank at Tyler 60 kv bus Objectives

More information

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PJM Sub Regional RTEP Committee Mid-Atlantic January 22, 2016 Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PSE&G System Characteristics New Jersey utility characterized by densely populated

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic March 23, 2018 First Review Baseline Reliability and Supplemental Projects 2 AEC Transmission Zone: Supplemental Project 69/12kV Wenonah Substation Retire/Bypass

More information

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia

More information

Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project.

Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project. Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project April 23, 2003 Introduction Eurus originally requested an interconnection

More information

Entergy Texas, Inc. Transmission Draft Construction Plan Update 1 Projects

Entergy Texas, Inc. Transmission Draft Construction Plan Update 1 Projects Entergy Texas, Inc. Transmission 2014 2018 Draft Construction Plan Update 1 Projects 1 2014-2018 ETI Draft Construction Plan Update 1 Projects Completed in the Fall of 2012 & 2013 to date 1) Cedar Hill

More information

APPENDIX F: Project Need and Description

APPENDIX F: Project Need and Description APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

Transmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona

Transmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona Transmission Planning & Engineering P.O. Box 53933 MS 3259 Phoenix, Arizona 85072-3933 March 9, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff

More information

2013 ANNUAL PROGRESS REPORT

2013 ANNUAL PROGRESS REPORT March 1, 2013 Mr. David Franklin, Chairman WECC Technical Studies Subcommittee Southern California Edison 1 Innovation Way Pomona, CA 91768-2560 Mr. Enoch Davies WECC Technical Staff 155 North 400 West,

More information

Key to Status Fields in the Project List

Key to Status Fields in the Project List Key to Fields in the Project List Load Growth Interconnection Economic Reliability Concept Proposed Planned Under Construction In Cancelled N/A Backstop Too early TO Update Base case Increasing load served

More information

SERTP rd Quarter Meeting

SERTP rd Quarter Meeting 2014 SERTP SERTP 2014 3 rd Quarter Meeting 2 nd RPSG Meeting September 30 th, 2014 APC Headquarters Birmingham, AL 2014 SERTP Process Information The SERTP process is a transmission planning process. Please

More information

Reliability Analysis Update

Reliability Analysis Update Reliability Analysis Update Transmission Expansion Advisory Committee September 15, 2016 2016 RTEP Window #3 Anticipated Scope and Timeline Anticipated 2016 RTEP Window #3 Anticipated 2016 RTEP Window

More information

Interconnection Feasibility Study Report GIP-157-FEAS-R2

Interconnection Feasibility Study Report GIP-157-FEAS-R2 Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia

More information

Q0044 interconnection at

Q0044 interconnection at Generation Interconnection Feasibility Study Report for Q0044 interconnection at Utah County Utah on PacifiCorp s Transmission System (138 kv Transmission System) September 15, 2004 Page 1 1.0 Description

More information

Sub Regional RTEP Committee Western Region ATSI

Sub Regional RTEP Committee Western Region ATSI Sub Regional RTEP Committee Western Region ATSI February 20, 2019 1 ATSI Needs Stakeholders must submit any comments within 10 days of this meeting in order to provide time necessary to consider these

More information

North Oregon Coast Area Study. Adam Lint

North Oregon Coast Area Study. Adam Lint North Oregon Coast Area Study Adam Lint PAGE 2 North Oregon Coast System Overview - Clatsop Study Covers: Transmission Switching Stations (Clatsop District): Astoria Lewis and Clark 115 kv Distribution

More information

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting BHE Wyoming Q4 Stakeholder Meeting November 17, 2016 @ 1:00PM MT Black Hills Energy Service Center 409 Deadwood Avenue, Rapid

More information

ATC Year Asessment Network Project List. Zone 2 switching initiative ASAP*** Operating flexibility Proposed -- --

ATC Year Asessment Network Project List. Zone 2 switching initiative ASAP*** Operating flexibility Proposed -- -- ATC 20 10-Year Asessment Project List Project ACEC Dellwood Substation: Install line breakers to sectionalize Y- 146 20*** 20 1 T-D interconnection Planned A 7741 Zone 2 switching initiative ASAP*** 20

More information

QP 311 Kingdom Community Wind Project Interconnection Feasibility Study. July, 2010 FINAL REPORT. Prepared by:

QP 311 Kingdom Community Wind Project Interconnection Feasibility Study. July, 2010 FINAL REPORT. Prepared by: FINAL REPORT QP 311 Kingdom Community Wind Project Interconnection Feasibility Study July, 2010 Prepared by: i For ISO New England and Vermont Electric Power Company Table of Contents Executive Summary...

More information

ATC Year Assessment Network Project List. MTEP Cost Reason for Change since Previous System Addition

ATC Year Assessment Network Project List. MTEP Cost Reason for Change since Previous System Addition TC 208 0- ssessment Network Project List 2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 9 20 2 22 23 24 Sherman Street SS, DIC - Replace High Side Circuit Switcher 208*** 208 T-D Interconnection Proposed targeted 8 372

More information

Transmission Coordination and Planning Committee 2014 Q4 Stakeholder Meeting. December 18, 2014

Transmission Coordination and Planning Committee 2014 Q4 Stakeholder Meeting. December 18, 2014 Transmission Coordination and Planning Committee 2014 Q4 Stakeholder Meeting December 18, 2014 Agenda 1. Introductions 2. TCPC Policies 3. BHCE Planning Department Update 4. 2014 LTP Study Results 5. Stakeholder

More information

System Impact Study Report

System Impact Study Report Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS

More information

Market Efficiency RTEP Proposal Window

Market Efficiency RTEP Proposal Window Market Efficiency RTEP Proposal Window Market Efficiency RTEP Proposal Window Status Window opened on 8/12/2013 Closed on 9/26/2013 17 individual proposals addressing congestion from Market Efficiency

More information

Transmission Improvements Plan for 575 MW Network Service Request Wansley CC 7 Generation Facility (OASIS # ) Georgia Transmission Corporation

Transmission Improvements Plan for 575 MW Network Service Request Wansley CC 7 Generation Facility (OASIS # ) Georgia Transmission Corporation Transmission Improvements Plan for 575 MW Network Service Request CC 7 Generation Facility (OASIS # 143556) Georgia Transmission Corporation November 11, 2010 CC7 TIP 11-11-2010 (2).docx PROBLEM STATEMENT

More information

Transmission Expansion Advisory Committee

Transmission Expansion Advisory Committee Transmission Expansion Advisory Committee March 6, 2014 1 2014 RTEP Update 2 2014 RTEP Update Initial 2019 Summer base case and corresponding machine list update complete PJM staff has been reviewing and

More information

Market Efficiency RTEP Proposal Window

Market Efficiency RTEP Proposal Window Market Efficiency RTEP Proposal Window Market Efficiency RTEP Proposal Window Status Window opened on 8/12/2013 Closed on 9/26/2013 17 individual proposals addressing congestion from Market Efficiency

More information

Reliability Analysis Update

Reliability Analysis Update Reliability Analysis Update Transmission Expansion Advisory Committee October 11, 2018 Proposal Window Exclusion Definitions The following definitions explain the basis for excluding flowgates and/or projects

More information

Pacific Gas and Electric Company s Revised 2015 Annual Progress

Pacific Gas and Electric Company s Revised 2015 Annual Progress March 02, 2015 Mr. Tracy Rolstad Chair, WECC Technical Studies Subcommittee Avista PO Box 3727 MSC-16 1411 East Mission Ave Spokane, WA 99220-3727 Mr. Enoch Davies WECC Technical Staff 155 North 400 West

More information

ATTACHMENT B - Table 1: LIST OF MANAGEMENT-APPROVED PROJECTS UNDER $50M

ATTACHMENT B - Table 1: LIST OF MANAGEMENT-APPROVED PROJECTS UNDER $50M of Need In-service Cost Alternatives Service Projects in PG&E Service Territory Mare Island - Ignacio 115 kv NERC Category 2010 Reconductor the limiting 19 $19M Connect Highway May 2012 Line re-rates and

More information

APPENDIX I: Description and Functional Specifications for Transmission Facilities Eligible for Competitive Solicitation

APPENDIX I: Description and Functional Specifications for Transmission Facilities Eligible for Competitive Solicitation APPENDIX I: Description and Functional Specifications for Transmission Facilities Eligible for Competitive Solicitation Intentionally left blank F1 Description and Functional Specifications of Proposed

More information

Highly Constrained Elements Within ATC Footprint

Highly Constrained Elements Within ATC Footprint Highly Constrained Elements Within ATC Footprint Feb. 21, 2008 Presented by Dale Burmester Compiled by ATC Economic Planning Team: Tom Dagenais, Todd Tadych, Arash Ghodsian, Chris Hagman Solutions to Market

More information

March 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1

March 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1 Energy Division P.O. Box 937 333 E. Barioni Blvd. Imperial, CA 92251 www.iid.com March 18, 2014 Mr. Tracy Rolstad Chair, WECC Technical Studies Subcommittee Senior Power System Consultant Avista System

More information

SMUD 2014 Ten-Year Transmission Assessment Plan. Final. December 18, 2014

SMUD 2014 Ten-Year Transmission Assessment Plan. Final. December 18, 2014 SMUD 2014 Ten-Year Transmission Assessment Plan Final December 18, 2014 I CONTENTS Executive Summary... III 1 Introduction... 2 1.1 Reliability Criteria and Guidelines... 2 1.2 Load Forecast... 2 1.3 Demand

More information

Interconnection Feasibility Study Report GIP-084-FEAS-R2

Interconnection Feasibility Study Report GIP-084-FEAS-R2 Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power

More information

Transmission Expansion Advisory Committee

Transmission Expansion Advisory Committee Transmission Expansion Advisory Committee February 12, 2015 1 Interregional Planning Update 2 EIPC non-grant 2014 Analysis 2025 summer and winter scenario build Initial SSMLFWG kickoff February 4 Modeling

More information

SPP Notification to Construct

SPP Notification to Construct February 19, 2014 SPP Notification to Construct Mr. Mo Awad Westar Energy, Inc. P.O. Box 889 Topeka, KS 66601 RE: Notification to Construct Approved Reliability Network Upgrades Dear Mr. Awad, Pursuant

More information

Local Transmission Plan. October 11, 2013 Revised August 25, 2014

Local Transmission Plan. October 11, 2013 Revised August 25, 2014 Local Transmission Plan October 11, 2013 Revised August 25, 2014 2 Central Hudson s System Zone G: Majority of Central Hudson s load Zone E: One small distribution substation Interconnections with Consolidated

More information

2018 Annual Progress Report to WECC Pacific Gas and Electric Company

2018 Annual Progress Report to WECC Pacific Gas and Electric Company 2018 Annual Progress Report to WECC Pacific Gas and Electric Company Waiver of Significant Transmission Project Status Table 1 and 2 update the planned transmission and generation projects, respectively,

More information

Gateway South Transmission Project

Gateway South Transmission Project Phase 1 Comprehensive Progress Report Volume 1 - Technical Report Report Prepared by PacifiCorp Transmission Planning Department November 21, 2008 WECC1-V4 Phase 1 Comprehensive Progress Report Executive

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic September 24, 2014 1 Reliability Analysis Update 2 AE Transmission Zone Generation Deliverability Violation: The Middle 230/69 kv is overloaded for line fault stuck

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

PREPARED DIRECT TESTIMONY

PREPARED DIRECT TESTIMONY Application No.: A.0-04- Exhibit No.: SDG&E-4 Witness: William V. Torre In the Matter of San Diego Gas & Electric Company s Application for Authorization to (1) to Participate in the Steam Generator Replacement

More information

BC Hydro System 2017 Annual Progress Report

BC Hydro System 2017 Annual Progress Report March 14, 2017 Philip Augustin, P.E. Chair, Technical Studies Subcommittee 503-464-7783 philip.augustin@pgn.com Mr. Enoch Davies WECC Technical Staff 155 North 400 West, Suite 200 Salt Lake City, UT 84103-1114

More information

Interconnection System Impact Study Final Report February 19, 2018

Interconnection System Impact Study Final Report February 19, 2018 Interconnection System Impact Study Final Report February 19, 2018 Generator Interconnection Request No. TI-17-0225 248.4 MW (Alternate Project Output of 217.35 MW) Wind Energy Generating Facility In Goshen

More information

PG&E s 2012 Request Window Proposals

PG&E s 2012 Request Window Proposals 1 PG&E s 2012 Request Window Proposals Central Valley Patrick Tan Transmission System Planning PG&E September 27, 2012 Transmission Projects Overview 2 Projects Seeking CAISO Approval Pease 115/60 kv Transformer

More information

May 11, Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway Post Office Box Lansing, MI 48909

May 11, Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway Post Office Box Lansing, MI 48909 Amy C. Monopoli Counsel Regulatory & Legislative Phone: 774-452-4227 amonopoli@itctransco.com May 11, 2017 Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway

More information

Merchant Transmission Interconnection PJM Impact Study Report. PJM Merchant Transmission Request Queue Position X3-028.

Merchant Transmission Interconnection PJM Impact Study Report. PJM Merchant Transmission Request Queue Position X3-028. Merchant Transmission Interconnection PJM Impact Study Report For PJM Merchant Transmission Request Queue Position X3-028 Breed 345 kv October/2014 System Impact Study Breed 345 kv Merchant Transmission

More information

Attached is Idaho Power s 2013 WECC Annual Progress Report. Please contact me if you have any questions.

Attached is Idaho Power s 2013 WECC Annual Progress Report. Please contact me if you have any questions. March 8, 2013 David Franklin Chair, Technical Studies Subcommittee Southern California Edison 1 Innovation Way Pomona, CA 91768 MHanson@idahopower.com (208) 388-2253 Enoch Davies Western Electricity Coordinating

More information

Feasibility Study Report

Feasibility Study Report Report For: Orion Renewable Resources LLC ( Customer ) Queue #: Service Location: Rockingham County, NC Total Output Requested By Customer: 100 MW Commercial Operation Date Requested By Customer: 11/1/2019

More information

Minnesota Biennial Transmission. Zone Meeting 8

Minnesota Biennial Transmission. Zone Meeting 8 Minnesota Biennial Transmission Plan Zone Meeting 8 Today s Agenda Purpose of meeting Transmission What is it? How it works? Why improve it? System and Zone Overview Deficiencies Improvement Alternatives

More information

SPS Planning Criteria and Study Methodology

SPS Planning Criteria and Study Methodology SPS Planning Criteria and Study Methodology SPS subscribes to the Southwest Power Pool ("SPP") Reliability Criteria, which incorporates compliance with the appropriate North American Electric Reliability

More information

Market Efficiency Update

Market Efficiency Update Market Efficiency Update Transmission Expansion Advisory Committee July 13, 2017 Agenda Where we are in the process Interregional Projects Status RPM Projects Status Reevaluation Analysis Status Next Steps

More information

Interconnection Feasibility Study Report GIP-369-FEAS-R1

Interconnection Feasibility Study Report GIP-369-FEAS-R1 Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic August 24, 2018 Proposal Window Exclusion Definitions The following definitions explain the basis for excluding flowgates and/or projects from the competitive planning

More information

2012 LOCAL TRANSMISSION PLAN:

2012 LOCAL TRANSMISSION PLAN: Colorado PUC E-Filings System 2012 LOCAL TRANSMISSION PLAN: TRANSMISSION COORDINATION AND PLANNING COMMITTEE ANNUAL TRANSMISSION ASSESSMENT FOR BLACK HILLS/COLORADO ELECTRIC UTILITY COMPANY, L.P., D/B/A

More information

Entergy Louisiana, LLC (South) & Entergy New Orleans, Inc. Proposed Transmission Reliability Projects

Entergy Louisiana, LLC (South) & Entergy New Orleans, Inc. Proposed Transmission Reliability Projects Entergy Louisiana, LLC (South) & Entergy New Orleans, Inc. Proposed Transmission Reliability Projects Entergy Transmission Planning Summit New Orleans, LA July 13, 2006 1 Approved 2006 2010 ELL-South Transmission

More information

Market Efficiency Update

Market Efficiency Update Market Efficiency Update Transmission Expansion Advisory Committee December 13, 2018 2018/19 Long Term Window 2 2018/19 Long Term Window Problem Statement and Eligible Congestion Drivers posted on the

More information

Interconnection Feasibility Study Report Request # GI

Interconnection Feasibility Study Report Request # GI A. Executive Summary Interconnection Feasibility Study Report Request # GI-2011-04 587 MW Combined Cycle 2x1 Generators Cherokee Station, Denver, Colorado Public Service Company of Colorado Transmission

More information

Market Efficiency Update

Market Efficiency Update Market Efficiency Update Transmission Expansion Advisory Committee October 12, 2017 Market Efficiency Proposal Window 2016-2017 Long Term Proposal Window 1A 2 2016-2017 Long Term Proposal Window 1A Addendum

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information