NRB Disconnector for outdoor installation
|
|
- Leona Thomas
- 6 years ago
- Views:
Transcription
1 NRB Disconnector for outdoor installation Rated voltage: Rated current: 12 72, 5 kv A Several erection alternatives Simple structure, easy to install Self cleaning contacts with magnetic locking All steel parts hot dip galvanized Designed and tested according to IEC 129 ABB Avangard AD
2 DESCRIPTION The disconnector type NRB consists of separate poles, which can be arranged for single pole operation or linked together by operating rods to form 2- or 3-pole units. Each disconnector pole consists of base frame with bearings, three post insulators (two fixed and one rotating), current carrying paths with contacts and terminals. BASE FRAME The base frame consists of a U - beam N12 with four fixing holes. The fixed insulators are erected at the outer ends of the U-beam. The rotating insulator is erected on a bearing in the centre of the U-beam. CURRENT CARRYING PATHS WITH CONTACTS AND TERMINALS The current carrying paths consist of a horizontal aluminum bar painted red, in the middle bolted to the rotating centre insulator and fitted with spring loaded copper contacts at both ends. When the disconnector is closed the contacts grip a contact bar. The contacts are fitted with magnetic locks which increase the contact pressure in the event of a short circuit. The terminals consist of aluminium plates bolted to the fixed insulators. Via a bimetalic strip they also provide a mounting point for the fixed contacts. Disconnectors for rated current 1250A will at delivery be supplied with bimetallic strips which allow connection to aluminium as well as copper cables. OPERATION The disconnectors are operated by rotating the vertical operating shaft 190º by means of a suitable operating mechanism. Two kinds of operating mechanisms are available, either a manual operating mechanism or a motor driven operating mechanism. EARTHING SWITCHES The three pole disconnector can, if so desired, be fitted with earthing switches, operated by eather a manual or motor operating mechanism as described above. The earthing switches should always be provided with mechanical interlocking to prevent incorrect operation. ERECTION ALTERNATIVES Disconnector type NRB / is designed in three erection alternatives horizontal parallel erection, horizontal row erection and vertical parallel erection.
3 Electrical parameters Rated values type NRB Rated voltage kv 12 / / / / ,5 / ,5 12 / / / / Rated current A Rated short circuit making current ka peak Rated short circuit breaking current 1s k A , ,5 Rated and withstand voltages Withstand voltage Rated voltage kv Switching impulse withstand voltage 1.2/50 µs between open to earth and between contacts poles, kv kv Power withstand voltage 50 Hz - 1 min to earth and between open between poles, contacts, kv kv , Isolators Rated voltage kv Creapage distance, mm , Gross weigth,kg Earthing Fig.А Disconnector type NRB 12-72,5/1250 horisontal parallel mounting Fixed holes for mount to the support structure
4 Disconnector type NRB 12 72,5 / 1250 (fig.а) Type NRB А А1 А2 А3 А4 В С Е Е1 F F1 F2 R 12/ / / / ,5/ Disconnector type NRB 12 72,5 / 2500 (fig.в) Type NRB А А1 А2 А3 А4 В С Е Е1 F F1 F2 R 12/ / / / L3( 11/4 ) Fig.С Disconnector type NRB with earthing blades horizontal parallel mounting Mechanical lock Earthing L3 Operating mechanism mounted on disconnector pole one Support beam Fixed holes for mounting to the support structure Operating mechanism mounted on extra support beam Fig.В Disconnector type NRB 12-75,5/2500 horizontal parallel mounting
5 Disconnector type NRB with earthing switches Horizontal parallel erection (fig.с) Type NRB N min N1 min L3 L4 R3 12/ L1+290 L2+L / L1+290 L2+L / L1+290 L2+L / L1+290 L2+L ,5/ L1+290 L2+L / L1+290 L2+L / L1+290 L2+L / L1+290 L2+L / L1+290 L2+L3 570 Mechanical lock Disconnector type NRB with earting switches Horizontal line erection (fig.d) Type NRB N min N1 min L3 R3 12/ L / L / L / L ,5/ L / L / L / L / L Fig.D Disconnector type NRB 12-75,5/ 1250 horizontal line erection
6 Mechanical lock Disconnector type NRB with earthing blades vertical parallel mounting (fig.е) Type NRB N min L3 R3 12/ L / L / L / L ,5/ L / L / L / L / L Fig.Е Disconnector type NRB with earthing switches vertical We reserve the right to make changes in the course of technical development of the product. ABB Avangard AD 32 Nikola Petkov Str Sevlievo, Bulgaria Tel.: ; ; Fax:
Horizontal center break disconnector Type SDF, up to 550 kv Maximum reliability and minimal maintenance
Horizontal center break disconnector Type SDF, up to 550 kv Maximum reliability and minimal maintenance Table of contents Disconnectors from ABB 2 Applications 2 Standards 2 Maximum reliability and minimal
More informationPantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance
Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance Table of contents 02 03 04 05 06 07 08 Disconnectors from ABB Maximum reliability and minimal maintenance Technical
More informationIndoor disconnectors ITr. single- and three-pole design rated voltage 12, 25 and 38.5 kv rated current A
Indoor disconnectors ITr single- and three-pole design rated voltage 12, 25 and 38.5 kv rated current 630 6300 A Indoor disconnectors Disconnectors as shown in the data sheet are intended to be used for
More informationElimsan High Voltage Disconnectors
Elimsan High Voltage Disconnectors Pantograph Type Center-Break Type Double-Break Type Vertical-Break Type Standards IEC 62271-102 IEC 62271-1 Nature is our most distinguished partner YG-EN-12-01 Elimsan
More informationSemi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance
Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance 2 Semi-pantograph
More informationRetrofit of medium voltage switchgears
Retrofit of medium voltage switchgears Increased reliability and safety Significantly reduced maintenance costs Increased remaining life time with minimum 2 years Cost effective Concept of retrofit The
More informationSection 2 - Substation Switchgear
Switchgear & Protection : Section 2 Section 2 - Table of Contents Section/Page Introduction to DB36 - D362 Disconnectors (36kV - 362kV)... 2-2 Popular Options For DB36, DB72 & DB145... 2-3... 2-3 Popular
More informationHigh voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv
High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element
More informationIndoor switches for railway lines. single-pole design rated voltage up to 27,5 kv rated current up to 4000 A
Indoor switches for railway lines single-pole design rated voltage up to 27,5 kv rated current up to 4000 A General These Driescher indoor switching devices are specifically designed for railway applications.
More informationZinc Oxide Surge Arrester EXLIM R
Zinc Oxide Surge Arrester EXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. For use when requirements of lightning intensity, energy
More informationCATALOGUE TRACTION OUTDOOR DISCONNECTORS TYP QAD 3. 3 kv DC; 2500; 3000; 4000; 4500 A
CATALOGUE TRACTION OUTDOOR DISCONNECTORS Unsere Handelsvertretung in Deutschland TYP QAD 3 3 kv DC; 2500; 3000; 4000; 4500 A ISO 9001:2009 ISO 14001:2005 APPLICATION The outdoor traction disconnectors
More informationCATALOGUE. ON Medium Voltage Outdoor Disconnectors
CATALOGUE ON Medium Voltage Outdoor Disconnectors 2 O N M E D I U M V O LTA G E O U T D O O R D I S C O N N E C TO R S ON MEDIUM VOLTAGE OUTDOOR DISCONNECTORS 3 Table of conteants 004 1. Introduction 004
More informationZinc Oxide Surge Arrester PEXLIM Q
Zinc Oxide Surge Arrester Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. in areas with high lightning intensity and high
More informationOutdoor load disconnectors DRIBO Flc GB. three-pole design rated voltage 25 and 38.5 kv rated current 630 A
Outdoor load disconnectors three-pole design rated voltage 25 and 38.5 kv rated current 630 A outdoor load disconnectors The breaking operation at the load disconnectors uses the energy of spring-based
More informationOUTDOOR OFF LOAD DISCONNECTORS HCB/HDB Range
OUTDOOR OFF LOAD DISCONNECTORS HCB/HDB Range SWITCHGEAR COMPLEX SWITCHGEAR COMPLEX Crompton Greaves Ltd. the name to reckon in Electrical Industry, brings a product with its leading edge technology to
More informationGas Insulated Switchgear
Gas Insulated Switchgear Your partner in energy solutions CG Electric Systems Hungary CG Electric Systems Hungary (previously known as Ganz Electric) has a history of over a 130 years as a high technology
More informationRAPIER DSB Disconnectors
RAPIER DSB Disconnectors and Copper and Aluminium Substation Connectors ENGINEERING BRILLIANT SOLUTIONS Rapier DSB disconnector The Rapier Double Side Break 'DSB' range provides a powerful and cost effective
More informationOutdoor load disconnectors Fla 15/97 GB. three-pole design rated voltage 25 kv rated current 630 A
Outdoor load disconnectors Fla 15/97 GB three-pole design rated voltage 25 kv rated current 630 A Fla 15/97 GB outdoor load disconnectors Outdoor design, load disconnectors of Fla 15/97 GB series, with
More informationDisconnectors and earthing switches up to 25 kv AC
Disconnectors and earthing switches up to 25 kv AC Sicat 8WL6144 for overhead contact line systems in main-line railways siemens.com/rail-electrification The disconnectors and earthing switches of the
More informationSF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch
FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages
More information023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA
023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir
More informationOutdoor disconnectors FTr (previously 6400 and 6410) single- and three-pole design rated voltage 25 and 38.5 kv rated current 400 and 630 A
Outdoor disconnectors FTr (previously 6 and 6410) single- and three-pole design rated voltage 25 and 38.5 kv rated current and 6 A 1 Outdoor disconnectors Outdoor disconnectors, produced in accordance
More informationZinc-Oxide Surge Arrester TEXLIM Q-C
Zinc-Oxide Surge Arrester TEXLIM Q-C Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. in areas with very high lightning intensity where
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM R
High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching
More informationOutdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker
More informationMedium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A
Medium voltage compact switchgears rated voltage 12 and 25 kv rated current 400 and 630 A 1 General The new air-insulated DRIESCHER medium voltage compact switchgears are ideal for application in secondary
More informationNH DIN Dual Indication Fuse Links
Class gg/gl, 400Vac, 2 to 630 Amps, Sizes 000 to 3 Standards/Approvals IEC 60269, VDE 0636, DIN 43620 Part 1 and 3 Description A square bodied range of industrial fuse links for a wide variety of applications.
More informationELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & S HNE GMBH :85366 MOOSBURG TEL. ( ) FAX ( )
DRIESCHER Outdoor Hand-Operated Actuators and Accessories Get connected http://www.driescher.com ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & S HNE GMBH :85366 MOOSBURG TEL. (0 87 61) 6 81-0 FAX (0 87 61)
More informationChange-over Disconnectors HUVS Range 36kV (630 to 6300Amp)
Changeover switches 7.2kV to 40.5kV For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time off-load disconnectors. These devices offer high performances
More informationFA Off-Load Switches. Up to 8000 A and 3000 V AC/DC Expertly engineered for reliable performance
F Off-Load Switches Up to 8000 and C/DC Expertly engineered for reliable performance For more than years has been providing safe and reliable solutions for switching and disconnecting high power. High
More informationMULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole
MULTIBLOC 3.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 3.ST8 comprises NH fuse switch disconnectors for 630A. They are designed for bottom
More informationHigh Power Switchgear. We can create a solution that s both effective and cost-effective
High Power Switchgear We can create a solution that s both effective and cost-effective Switch Application Questionnaire Customer: Address: State/Zip: Contact: Project Name: Electrical Data Switch to operate:
More informationAll rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.
Issued: January 2013 Copyright by ZPUE Katowice S.A. All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.
More informationChange-over Disconnectors HUVS Range 12kV (630 to 6300Amp)
Changeover switches 7.2kV to 40.5kV For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time off-load disconnectors. These devices offer high performances
More informationDisconnectors MF range (0,5 to 3000 Hz) (1250 to Amp)
High Frequency Disconnectors For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time off-load disconnectors. These devices offer high performances and robustness
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS STANDARD METAL CLAD INDOOR VCB TECHNICAL DATA Rated Voltage (Ur) in kv 12 Rated Normal Current (Ir) in Ampere 630/1250 Rated Frequency (fr) in Hz 50 Rated Insulation level (1 min)
More informationRapier AX Air Break Switch Disconnector. engineering brilliant solutions
Air Break Switch Disconnector engineering brilliant solutions Air Break Switch Disconnector engineering brilliant solutions Lucy Switchgear would like to present its Air Break Switch Disconnector. The
More informationMEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation
KON^AR KONCAR MEDIUM VOLTAGE APPARATUS, Inc. MEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation Series RSN General Information Disconnector switches are part of traditional medium voltage assortment.
More informationDBM Range 1500VDC (13,5kA to 20kA)
Load Break Switches For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time on-load disconnectors.these devices offer high performances and robustness for
More informationatalog Welcome to ATO.com! Contact us... Tel: (Toll-free) Website:
atalog Welcome to.com! Contact us... Email: sales@ato.com Tel: +1 800-585-1519 (Toll-free) Website: ZMQ2E Series Dual Power Automatic Transfer Switch (ATS) Applications ZMQ2E dual auto transfer switch
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationOutdoor vacuum breaker for railway applications - FSK II
Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationSF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv
Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application
More informationZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear Minimum overall costs ZX offers maximum economy The compact design of the panels reduces the space required and therefore the size of the station. Freedom
More informationPower IT Compact Secondary Substations, CSS. Low Voltage Switchboard, LVS2
Power IT Compact Secondary Substations, CSS Low Voltage Switchboard, LVS2 LVS ABB s New Low Voltage Switchboard for Power IT CSS LVS2 is a freestanding low voltage switchboard, as it is designed with a
More informationSurge arrester POLIM-H..SD
Data sheet Surge arrester POLIM-H..SD Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationIEC Low Voltage General Purpose Protection
, 6A, 0/400VAC (/440VAC) Complying with DIN VDE 0660 Part 07 EN / IEC 60947- DIN VDE 066 Part IEC 6069- DIN VDE 068 DIN VDE 4880 The D0-LINOCUR is a combination of switch-disconnector-fuse and NEOZED 6
More informationTransmission Switching
CATALOG BULLETIN GENERAL APPLICATION Southern States supplies a wide offering of Transmission Switching solutions in response to an increasing need for improved system reliability and reduced installation
More informationVarius SUMMARY OF MODELS
SUMMARY OF MODELS Type 10 14 22 OPT22/OPT20 OPVF10 Rated operating current I e / Rated current I n 32 A / - 63 A / - 125 A / - 63 A / - - / 30 A Rated operating voltage U e / Rated voltage U n AC 690 V
More informationONIII. Outdoor disconnector DTR EN
Installation and service manual ONIII Outdoor disconnector DTR.01.02.02.EN Dear customer! Thank sincerly for purchasing our product. We are glad to deliver you an outdoor disconnector ONIII, which has
More informationMedium voltage switchgear type W 12. rated voltage 12 kv rated current 630 A
Medium voltage switchgear type W rated voltage kv rated current 0 A General The metal-encapsulated, air-insulated medium voltage switchgears, type W are for universal application. They range from compact
More informationTYPE V CENTER BREAK SWITCH
TYPE V CENTER BREAK SWITCH 3-PHASE, GROUP-OPERATED (SUBSTATION AND TRANSMISSION APPLICATIONS) *Available in Copper Horizontal upright, vertical or underhung mounting 15KV through 230KV 600A through 4000A
More informationSABRE VRN2a ENGINEERING BRILLIANT SOLUTIONS
SABRE VRN2a ENGINEERING BRILLIANT SOLUTIONS Design The Sabre VRN2a is a compact SF6 insulated Vacuum Ring Main Unit (RMU). The unit can be mounted to the smallest distribution transformer or be sited in
More informationNH DIN Dual Indication Fuse Links Class am, 690Vac, 6 to 500 Amps, Sizes 000 to 3 NH Series
Description: A range of Class am square bodied industrial fuse links for a wide variety of motor protection applications. Packaging: MOQ: 3 Catalogue Symbol: Class of Operation: (amp)nhm(size)b-690 am
More informationUniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions
UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that
More informationPower IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB
Power IT MV Live Tank Vacuum Circuit Breaker Model OVB-SDB ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable
More information2013 JEAN MÜLLER Products
2013 JEAN MÜLLER Products Company JEAN MÜLLER JEAN MÜLLER was founded in 1897 in Germany, when the applications of electricity were still in their very early days. The company chose as its basic activity
More informationAuxiliary Relay. Type RXP8n, RXPQ8n
Auxiliary Relay Type RXP8n, RXPQ8n ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
More informationTechnical Specification for 33 KV 200 AMPs,H.G,Fuse set.
Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable
More informationCOMPONENTS. Off-load Switch for Fixed Installation Title type SW
COMPONENTS Off-load Switch for Fixed Installation Title type SW General information The SW off-load switch is a complete range designed to cover all the applications to be met in DC traction power substations
More informationDisconnectors FA range 750VDC 250 to 2000Amp
750VDC On Board Disconnectors Switch For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time off-load disconnectors. These devices offer high performances
More informationDisconnectors FA range 1500VDC 250 to 2000Amp
Disconnectors FA range 1500VDC 250 to 2000Amp ON BOARD DISCONNECTOR SWITCH 1500VDC ON BOARD DISCONNECTORS SWITCH FEATURES & BENEFITS For more than 100 years, Mersen have been providing the market with
More information15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationEuroload Changeover Switch
Euroload Features: Quick make & quick break mechanism. High electrical & mechanical endurance. Advance neutral. Enclosed housing to avoid dust ingress. Staggered terminals upto 800A. Load and Line reversibility.
More informationUniSec licensed by ABB, produced by Metix WHERE ENERGY LIVES COMPLETE SOLUTIONS
COMPLETE SOLUTIONS WHERE ENERGY LIVES METAL AND CONCRETE TRANSFORMER SUBSTATIONS DISTRIBUTION SWITCHGEAR UP TO KV - UNISEC ELECTRICAL SWITCHBOARDS LOW AND MEDIUM VOLTAGE ELECTRICAL EQUIPMENT UniSec licensed
More informationFuse switch disconnectors
SWITCHGEAR RBK Fuse switch disconnectors intended for distribution of electricity and protection of electrical equipment against short-circuits and overloads, with industrial fuse links ENERGY SAFELY SWITCHED
More informationPower IT MV Live Tank Vacuum Circuit Breaker Model VBF
Power IT MV Live Tank Vacuum Circuit Breaker Model VBF ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable utility
More informationSERIES TAP-CHANGER
SERIES 090 - TAP-CHANGER Main characteristics This is an off-circuit tap changer. It means DO NOT OPERATE WHILE THE TRANSFORMER IS ENERGISED. Main characteristics of this tap-changer series are: dimensional
More informationDISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus
DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution
More informationMotor-drive mechanism, type BUL. Technical guide
Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationLINOCUR Size D02 63A 230VAC/440VAC
IEC FUSE SWITCH DISCONNECTORS D0 FUSE COMBINATION UNITS The D0 Linocur is a combination of switch disconnector fuse and Neozed 63A fuse-link, equiped with significant safety characeristics and sophisticated
More informationProduct selection guide Kabeldon cable cabinet, kv. Document name
Product selection guide Kabeldon cable cabinet, 12 36 kv Document name Kabeldon HDC-A cable cabinet, 12 36 kv A robust and safe solution Application area Kabeldon HDC-A offers unique capabilities for jointing
More informationUrgent Support to the Agriculture and Electricity Sector in the Gaza Strip
Project Number: PAL -10-00063805 Project Name: Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip Bill of Quantities Package # 2 LOT 2: Supply of Electrical Materials The contract
More informationClass gg/gl, 690Vac, 2 to 500 Amps, Sizes 000 to 3 NH Series
Description: A range of Class gg/gl square bodied industrial fuse links for a variety of applications. Packaging: MOQ: 3 Catalogue Symbol: Class of Operation: (amp)nhg(size)b-690 gg/gl Fuse Size: 000 to
More informationcor Long Run Experience
Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30
More informationCable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.
Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More informationHIGH VOLTAGE SURGE ARRESTER SPECIFICATION
HIGH VOLTAGE SURGE ARRESTER SPECIFICATION Applications: (Polymer housed MOA for 110kv) (The polymer housed MOA for 10kv) (Porcelain housed MOA for 220kv) (35kv MOA without gaps for middle phase) (110kv
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationSF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)
SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationMULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole
MULTIBLOC 1.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 1.ST8 comprises NH fuse switch disconnectors for 250A. They are designed for bottom
More informationWESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2
Sl. No. WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO GUARANTEED TECHNICAL PARTICULARS 1 of 2 REQUIREMENTS 11 Kv, 200 Amps, A.B Switches. Particulars 1 Maker's name and Country of origin. 2 Type
More informationProduct Specification
KYN28-12 Series H.V Metal Clad Switchgear Product Specification 10/08/2015 Electrical Treasure One-Stop Supplier Of Electrical Equipment 1 KYN28-12 Series With Prevent Wrong Operation Of Metal Clad Switchgear
More informationMULTIVERT 1000A Main Incomer, 690VAC
IEC FUSE SWITCH DISCONNECTORS NH VERTICAL FUSE SWITCH DISCONNECTOR FEATURES & BENEFITS MULTIVERT NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed
More informationHand operated drives and accessories. for outdoor switching devices
Hand operated drives and accessories for outdoor switching devices 1 Outdoor hand operated drives Outdoor hand operated drives are used for manual control of outdoor switching devices, specially the medium
More informationMULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole
MULTIBLOC 2.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 2.ST8 comprises NH fuse switch disconnectors for 400A. They are designed for bottom
More informationAIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR
AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector
More informationSurge arrester POLIM-H.. ND
DATA SHEET Surge arrester POLIM-H.. ND Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10
More informationHigh Voltage and Extra High Voltage Cables
High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high
More informationEd rev.0 CATALOGUE SWITCHGEAR 2015
Ed. 2015 rev.0 CATALOGUE SWITCHGEAR 2015 SV24NC GENERAL SV24NC voltage metal enclosed switchgears for indoor use are constructed by placing standardized units side by side in a coordinated way. Insulation
More informationBenefits, typical uses
R-HA26-013. eps Switchgear Type 8BT1, up to 24kV,Air-Insulated Contents Application Page Application Benefits 2 Typical uses 2 and 3 Technical Data Ratings 4 Classification, dimensions, 5 room planning
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y
High Voltage Surge Arresters uyer s Guide Section PEXLIM P-Y Zinc Oxide Surge Arrester PEXLIM P-Y Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationSF 6 Gas Insulated Load Break Switch
Distribution Automation Solution SF 6 Gas Insulated Load Break Switch Pole-mounted type : PGS series (630A) DB-GS-M-630MC (Manual / Moldcon Busing Type) DB-GS-M-630TM (Manual / Terminal Busing Type) DB-GS-A-630MC
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More information