SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

Size: px
Start display at page:

Download "SECTION MOTORS AND VARIABLE FREQUENCY DRIVES"

Transcription

1 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section Basic Mechanical Requirements. 2. Section Motors. 3. Section Hydronic Pumps. 4. Section Centrifugal Water Chillers. 5. Section Open Circuit Mechanical Draft Cooling Towers. 6. Section Modular Indoor Air Handling Units. 7. Section Packaged Outdoor Central Station Air Handling Units. 8. Section Rooftop Replacement Air Units. 9. Section Rooftop Evaporative Cooling Units. 10. Section Fan Coil Units. 11. Section Switchboards. 12. Section Panelboards. 1.2 SUMMARY A. Section includes three phase electric motors and variable frequency drives. 1.3 REFERENCES A. AFBMA 9 - Load Ratings and Fatigue Life for Ball Bearings. B. AFBMA 11 - Load Ratings and Fatigue Life for Roller Bearings. C. ANSI/IEEE Test Procedure for Polyphase Induction Motors and Generators. D. ANSI/NEMA MG 1 - Motors and Generators. E. ANSI/NFPA 70 - National Electrical Code. F. IEEE Std Guide for Harmonic Controls and Reactive Compensation of Static Power Converters. G. ANSI/UL Std Testing by Independent Laboratories. 1.4 SUBMITTALS A. Section Basic Mechanical Requirements: Submittals and Contract requirements. B. Submit factory test results verifying nominal efficiency and power factor for three phase motors larger than 20 horsepower. C. Submit manufacturer's installation instructions under provisions of General Conditions Sections. Page 1 of 6

2 1.5 OPERATION AND MAINTENANCE DATA A. Submit operation and maintenance data under provisions of General Conditions and Section Basic Mechanical Requirements and Section Basic Electrical Materials and Methods. B. Include assembly drawings, bearing data including replacement sizes, and lubrication instructions. 1.6 QUALIFICATIONS A. Manufacturer: Company specializing in manufacture of electric motors and variable frequency drives for HVAC use, and their accessories, with minimum three years documented product development, testing, and manufacturing experience. 1.7 REGULATORY REQUIREMENTS A. Conform to applicable electrical code. B. Conform to local energy code. 1.8 DELIVERY, STORAGE, AND HANDLING A. Protect motors and controllers stored on site from weather and moisture by maintaining factory covers and suitable weather-proof covering. For extended outdoor storage, remove motors from equipment and store separately. 1.9 WARRANTY A. Provide one year manufacturer's on-site labor and material warranty. B. Warranty: Include coverage for motors and variable frequency drives. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Motors: U.S. Motors, Reliance, Baldor, or Marathon. B. Adjustable Frequency Controllers: Danfoss, VLT 4000, No Substitutions. 2.2 GENERAL CONSTRUCTION AND REQUIREMENTS A. Motors: Design for continuous operation in 40 degrees C environment, and for temperature rise in accordance with ANSI/NEMA MG 1 limits for insulation class, Service Factor, and motor enclosure type. Page 2 of 6

3 B. Design variable frequency drives for operation with the actual motor and driven pumps or fans. C. Visible Nameplate: Indicating motor horsepower, voltage, phase, cycles, RPM, full load amps, locked rotor amps, frame size, manufacturer's name and model number, Service Factor, Power Factor. D. Electrical Connection: Conduit connection boxes, threaded for conduit. For fractional horsepower motors where connection is made directly, provide conduit connection in end frame. 2.3 THREE PHASE POWER - SQUIRREL CAGE MOTORS A. Starting Torque: Between one and one and one-half times full load torque. B. Starting Current: Six times full load current. C. Power Output, Locked Rotor Torque, Breakdown or Pullout Torque: NEMA Design B characteristics. D. Design, Construction, Testing, and Performance: Conform to ANSI/NEMA MG 1 for Design B motors. E. Insulation System: NEMA Class B or better. F. Testing Procedure: In accordance with ANSI/IEEE 112, Test Method B. Load test motors to determine freedom from electrical or mechanical defects and compliance with performance data. G. Motor Frames: NEMA standard T-frames of steel, aluminum, or cast iron with end brackets of cast iron or aluminum with steel inserts. H. Bearings: Grease lubricated anti-friction ball bearings with housings equipped with plugged provision for relubrication, rated for minimum AFBMA 9, L-10 life of 20,000 hours. Calculate bearing load with NEMA minimum V-belt pulley with belt center line at end of NEMA standard shaft extension. Stamp bearing sizes on nameplate. I. Sound Power Levels: To ANSI/NEMA MG 1. J. Nominal Efficiency: Meet or exceed values in Schedules at full load and rated voltage when tested in accordance with ANSI/IEEE 112. K. Nominal Power Factor: Meet or exceed values in Schedules at full load and rated voltage when tested in accordance with ANSI/IEEE 112. L. Motors shall deliver full nameplate horsepower without de-rating due to thermal Page 3 of 6

4 considerations when on variable frequency power. 2.4 VARIABLE FREQUENCY DRIVES (VFD) A. Variable Frequency Drive Systems shall be Danfoss VLT 4000 with Adaptable Package Unit. Variable Frequency Drive Systems shall be compatible with any standard NEMA B design 3- phase induction motor. Variable Frequency Drive Systems shall be sized to insure the motor full load amps do not exceed the controller continuous RMS amps. B. The adjustable frequency drive shall convert three-phase, 60 Hz utility power to adjustable voltage and frequency, three phase, AC power for motor speed motor control from 10% to 100% of the motor's 60 Hz speed. Input voltage shall be as specified on the drawings schedules. The input section of the drive shall include line filters, line reactors or isolation transformers as required to meet IEEE 519 for distortion levels of 3% or less. The variable frequency drives shall not interfere with sensitive electronic equipment that is fed from the same power distribution system. C. The output wave form shall be sine coded pulse width modulated. To eliminate acoustical noise, PWM drives shall have a minimum of 2500 pulses per sine. The VFD's input power factor shall be.95 or better at all operating speeds. Efficiency shall be 96% minimum from 0-100% load. To eliminate RFI and EMI, the drive shall comply with FCC rules and regulations, part 15, subpart "J". D. Solid State Ground Fault Protection shall be standard. Those manufacturers that cannot provide this as a standard feature must supply an external protector. Adaptive electronic motor overload protection shall be provided which shall protect both the motor and drive at all frequencies. Electronic thermal overload circuits which properly protect the motor only at full speed shall not be acceptable. The VFD shall sense the load and speed and shall recalibrate the thermal trip curve to insure low speed motor protection. The initial trip point shall be adjustable from at least % of the VFD amperage rating. E. Isolated control inputs shall be provided. The motor speed shall be directly proportional to 0-10 volt, 4-20 ma, and variable resistance signals. Fire alarm signal for control override to maximum speed at smoke control fans. F. Drive operation options shall be switch selectable and shall include at a minimum the following functions: 1. Automatic speed holding if control signal is lost at 80% of last speed command. 2. The VFD shall provide the following operational features: a. Speed search transfer. The VFD shall be able to start from bypass or fault trip into a spinning load without stopping the motor or creating a fault condition. The VFD shall match the motor's speed and then drive the motor to its proper speed. b. Adjustable current limit threshold. c. Multiple restart upon fault trip. d. Minimum 10:1 speed ratio. e. Individually adjustable acceleration and deceleration patterns, adjustable from seconds. Page 4 of 6

5 G. The VFD shall be suitable for installation and use under the following environmental conditions: 20 to 104ºF, 0-95% RH, non condensing. H. Fault Indication and Operation 1. The following fault conditions shall cause the VFD to shut-off (trip) and shall be annunciated by LED indicators on the control board. FU: Fuse Blown, OC: Instantaneous Overcurrent, OV: Overvoltage, UV: Undervoltage, OH: Overheat, EB: External Failure, CPF: Control Function Error, CFP-SEL: Control Function Selection Error, OL: Overload. 2. The VFD shall attempt to restart a minimum of 5 times after tripping on a fault. A dry contact on the VFD shall close after the fifth unsuccessful restart attempt. 3. The VFD shall be set by the manufacturer to prevent the possibility of overamperage on the motor in the associated drive. This feature shall be coordinated with the ATC Contractor and the Mechanical Contractor for the project. I. The VFD shall be equipped with a digital operator interface which shall allow the following functions: 1. Digital frequency indication on an LCD display. 2. Digital fault indication on the LCD display. Digital fault reset. Storage and operator initiated recall of the fault conditions in the sequence of occurrence. 3. Auto/Manual operation switch. 4. Digital speed control in 0.1 Hz increments. 5. Tracking of fault/failure history. 6. Display of frequency or RPM. 7. Self diagnostics. J. Where indicated, manual bypass shall provide all the circuitry necessary to safely transfer the motor from the VFD to the power line, or from the line to the controller while the motor is at zero speed. Three motor contactors, electrically interlocked, shall be utilized. Motor protection is to be provided in both the "controller" mode and the "bypass" mode by a motor overload relay. The 115 VAC relay control logic, allowing common start-stop commands in the "controller" mode and the "bypass" mode shall also be included within this enclosure. The bypass shall include a door-interlocked, main power input disconnect circuit breaker providing positive shutdown of all input power to both the bypass circuitry and the VFD. The bypass circuit shall include a second door interlocked input disconnect circuit breaker installed in the VFD. This disconnect shall provide the ability to safely troubleshoot and test the controller, both energized, while operating in the "bypass" mode and shall mount within the controller enclosure. K. The VFD manufacturer shall maintain and staff nationwide service centers. Service engineers shall be employed by the manufacturer and provide start up service including physical inspection of drive and connected wiring and final adjustments to meet specified performance requirements. Page 5 of 6

6 PART 3 EXECUTION 3.1 APPLICATION A. Single Phase Motors need not conform to these specifications. B. Motors shall be open drip-proof type, except where specifically noted otherwise. C. Motors shall be energy efficient type. D. Motors located in exterior locations shall be totally enclosed type. E. Adjustable frequency controllers shall be as scheduled on the drawings. F. VFD manufacturer shall provide start-up service for all drives provided. The manufacturer s local representative shall participate in adjusting and balancing operations as stipulated in the specification Division 15, Commissioning of Mechanical Systems. 3.2 PERFORMANCE SCHEDULE: THREE PHASE - Motors shall be tested to IEEE-112, Method B. Minimum efficiencies and power factors are: HP NEMA PERCENT Efficiency Power Factor / / END OF SECTION Page 6 of 6

SECTION MOTOR REQUIREMENTS for HVAC

SECTION MOTOR REQUIREMENTS for HVAC PART 1 GENERAL 1.1 SECTION INCLUDES A. Single-phase electric motors B. Three-phase electric motors 1.2 REFERENCES SECTION 23 05 13 MOTOR REQUIREMENTS for HVAC A. ABMA 9 - Load Ratings and Fatigue Life

More information

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Single phase electric motors. B. Three phase electric motors. 1.2 REFERENCE STANDARDS A. ABMA STD 9

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives. SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents. PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S Revised 04/14/2016 SPECIFICATIONS - DETAILED PROVISIONS Section 16151 - Vertical Hollowshaft Electric Motors C O N T E N T S PART 1 - GENERAL... 1 1.01 SCOPE... 1 1.02 SPECIFIC PROJECT REQUIREMENTS...

More information

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK PART 1 - GENERAL 1.1 GENERAL: SECTION 15150 MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK A. The Mechanical Contractor shall furnish to the Electrical Contractor for installation,

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

SECTION VARIABLE FREQUENCY DRIVE UNITS

SECTION VARIABLE FREQUENCY DRIVE UNITS SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It

More information

VARIABLE FREQUENCY DRIVES

VARIABLE FREQUENCY DRIVES 262923 VARIABLE FREQUENCY DRIVES PART 1: GENERAL 1.01 SUMMARY A. Section Includes: 1. Variable Frequency Drives (VFD) B. Related Sections: 1. Section 230000 - Basic HVAC Requirements 2. Section 230900

More information

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities.

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities. PART 1: GENERAL 1.01 This design guidelines contained herein includes the requirements electric motors utilized for electric motor driven systems at Texas State University. It is the intention of this

More information

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL Design Standard Detailed specifications follow. PART 1 - GENERAL 1.01 SCOPE This design guidelines contained herein include the requirements of electric motors utilized for electric motor driven systems

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

SECTION OWNER FURNISHED EQUIPMENT

SECTION OWNER FURNISHED EQUIPMENT SECTION 11000 - OWNER FURNISHED EQUIPMENT PART I - GENERAL 1.01 GENERAL: A. The Owner has prepurchased and has or will have on site various pieces of equipment to be installed by the Contractor under this

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS SECTION 26 20 00 LOW-VOLTAGE AC INDUCTION MOTORS SEWPCC UPGRADING/EXPANSION PROJECT PART 1 GENERAL 1.1 RELATED SECTIONS A. This section applies only when referenced by a motor-driven equipment specification.

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

1333 (SERIES B & C) TROUBLESHOOTING GUIDE 1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be

More information

SECTION MOTORS & MOTOR CONTROLLERS

SECTION MOTORS & MOTOR CONTROLLERS SECTION 15170 MOTORS & MOTOR CONTROLLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Electric motors. B. Motor controllers for Packaged equipment. 1.02 SUBMITTALS A. Wiring diagrams with electrical characteristics

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

SYSDrive Frequency Inverter

SYSDrive Frequency Inverter SYSDrive Frequency Inverter T V/f control T PID control T Standard LED, optional LCD operator T Fieldbus options: DeviceNet T 7 configurable digital inputs T 3 configurable digital outputs T Low audible

More information

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

MaxPak Plus Analog DC V S Drive

MaxPak Plus Analog DC V S Drive Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY CONNECTIONS INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! READ THESE INSTRUCTIONS

More information

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III 1. SCOPE A. The Central Lighting Inverter shall be a solid-state three phase system designed to provide

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Made in the U.S.A. NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Nema Enclosed DC Control Specifications Catalog Number BC140 or Features BC138 BC139 BC140-FBR BC154 BC160 BCWD140

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

SECTION 16483C ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX)

SECTION 16483C ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX) ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX) PART 1 GENERAL 1.01 SCOPE A. This specification describes the electrical, mechanical, environmental, agency and reliability requirements for three-phase,

More information

Description 1/8-7.5HP

Description 1/8-7.5HP Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.

More information

TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT

TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 10KW 33KW Systems

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 10KW 33KW Systems EON Model EL3 Three Phase Centralized Emergency Lighting Inverter General Specification 10KW 33KW Systems 1.0 GENERAL This specification defines the electrical and mechanical characteristics and requirements

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

825-P Modular Protection System for motors Specification Guide

825-P Modular Protection System for motors Specification Guide Specification Guide 1.0 General 1.01 The motor protection relay shall have a current operating range of 0.5 and 5000 amperes. 1.02 The motor protection relay shall provide current measurement-based protection

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA SmartVFD HVAC APPLICATION The SmartVFD HVAC is a variable frequency drive designed for use in HVAC application to control the speed of HVAC pumps and fans in order to maximize energy efficiency. Smart

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

BAC Custom Engineered Controls

BAC Custom Engineered Controls BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com General Information The Westinghouse Accutrol 300 consists of a family of microprocessor-based, digital high efficiency, adjustable frequency motor controllers in the power range from 15 to 500 HP constant

More information

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6 I. PART 1 GENERAL 1. SCOPE A. NEMA Premium copper-wound ultra low loss isolation transformer with a higher efficiency than that required by NEMA Std. TP-1. Optimized for energy efficiency over a wide load

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 40KW 55KW Systems

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 40KW 55KW Systems EON Model EL3 Three Phase Centralized Emergency Lighting Inverter General Specification 40KW 55KW Systems 1.0 GENERAL This specification defines the electrical and mechanical characteristics and requirements

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems.

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems. Issued 2005/06/01 Section 15440 Plumbing Pumps Page 1 of 9 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780 Closeout

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information

Diesel generator set QSK95 series engine

Diesel generator set QSK95 series engine Specification sheet Diesel generator set QSK95 series engine 2750 kw - 3350 kw 60 Hz Data Center Continuous EPA Tier 2 emissions regulated Description Cummins commercial generator sets are fully integrated

More information

HVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars

HVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars HVAC Drives Lenze AC Tech MCH Series Price Book May 2015 - US Dollars Document: pcmchusd-0515_a MCH Series Drives: Model Number Designation Code The MCH Series drives are rated for variable torque applications,

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65

KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65 Installation & Operation Manual KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65 Variable Speed / Soft-Start AC Motor Drive with Electronic Motor Overload Protection for Inverter

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Fincor Series 2230 MKII/2240

Fincor Series 2230 MKII/2240 Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran 4 Project:_ Engineer:_ Mitsubishi Electric Automation, Inc. (MEAU) Variable Frequency Drives - HVAC System Submittal Summary Data Form NEMA 1 Bypass Systems Architect:_ Contractor:_ Submitted by: Date:

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

A flexible, reliable and affordable drive for 1/4 through 2 HP DC applications

A flexible, reliable and affordable drive for 1/4 through 2 HP DC applications A flexible, reliable and affordable drive for 1/4 through 2 HP DC applications DC2 drives combine application flexibility, compact size and reliability into an affordable adjustable speed package that

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

SECTION ELECTRIC MOTOR ACTUATORS FOR VALVES

SECTION ELECTRIC MOTOR ACTUATORS FOR VALVES SECTION 40 92 10 - ELECTRIC MOTOR ACTUATORS FOR VALVES PART 1 - GENERAL A. Description This section includes materials and installation of electric motor actuators for valves. B. Submittals 1. Submit shop

More information

AP/UP, AP/MIL Series Magnetic Circuit Protectors

AP/UP, AP/MIL Series Magnetic Circuit Protectors AP/UP, AP/MIL AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction 68 Single Pole 69 Multi-Pole 70 Configurations 72 Operating Characteristics 73 Delay Curves 74 Specifications 75 Decision Tables

More information

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER WARNING Disconnect all incoming power before working on this equipment. Follow power lockout procedures. Use extreme caution around electrical

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

HVAC Products. Introducing the SED2 Variable Frequency Drives

HVAC Products. Introducing the SED2 Variable Frequency Drives HVAC Products Introducing the SED2 Variable Frequency Drives Designed Specifically for HVAC Applications From a global leader in drives technology and innovation, now comes a drive specifically configured

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

Motor Protection Fundamentals. Motor Protection - Agenda

Motor Protection Fundamentals. Motor Protection - Agenda Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection

More information

Series 5 Inverter OPEN CHASSIS MOUNT - SINGLE PHASE INPUT. For Catalog Nos. ID56F50-CO, ID5601-CO & ID5602-CO

Series 5 Inverter OPEN CHASSIS MOUNT - SINGLE PHASE INPUT. For Catalog Nos. ID56F50-CO, ID5601-CO & ID5602-CO Series 5 Inverter OPEN CHASSIS MOUNT - SINGLE PHASE INPUT For Catalog Nos. ID56F50-CO, ID5601-CO & ID5602-CO 1/17 Installation & Operating Manual MN781 Table of Contents Chapter 1 Introduction Introduction...

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

Installation and Operation Manual

Installation and Operation Manual ADJUSTABLE SPEED DRIVE SERIES 5 INVERTER Installation and Operation Manual For Catalog Numbers ID56F50-CO, ID5601-CO & ID5602-CO 2/2006 MN781 TABLE OF CONTENTS Section Page 1 Quick-Start Instructions.......................................................

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3. 1332 TROUBLESHOOTING GUIDE Maintenance The Drive is convection or fan cooled by air flowing through the heat sink slots. The slots must never be allowed to become obstructed with dirt or foreign matter.

More information