1 pplication description EN Emergency-off application Manual motor starter MS116/MS132 Undervoltage release U1 The emergency-off application allows machine and job safety for nominal currents up to 32 all in one. It complies with EN standard stop-category 0. It also complies with additional legal and standard requirements for electrical and functional safety of machinery. Introduction This publication gives an overview on functionality and on relevant standards for an emergency-off application according to category 0. It also explains how to select the necessary components to realize the application. The emergency-off for uncontrolled stopping in accordance with EN (E-off, stop category 0) interrupts the motor current directly. The torque becomes zero and the motor coasts down. This application can be found in many industries such as: - packaging - food and beverage - plastics processing - steel and aluminium - timber industry - manufacturing industry Manual motor starters Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and protection in a single device. MMS are used mainly to switch motors manually ON/OFF and to protect them and the installation fuseless against shortcircuit, overload and phase failures. Fuseless protection with a manual motor starter saves costs and space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. BB s manual motor starters can be equipped with many other accessories. To realize the emergency-off application the combination of a manual motor starter with an undervoltage release and an emergency stop device provides safety at work and machine safety all in one.
2 Manual motor starter MS116/132, undervoltage release U1 Benefits and scope The emergency-off application is useful for machinery and equipment preventing hazards for human life and machinery. It can be used for motors with nominal current up to 32 and maximum rated operating voltage up to 690 V C / 250 V DC. Electrical scope: Characteristic for this application is that after pushing the emergency-off device, voltage is not longer present and further danger excluded, e.g. Laboratory benches. Motor-operated scopes: Differently, in these cases the dangerous situation is still existing, even if voltage is no longer present after pushing the emergency-off. Typical applications include: - garage doors - mixing and kneading machines - carwash facilities - box column drills, lathes and milling machines - grinding machines - lifting devices - presses Motor-operated applications require an emergency-stop function according to IEC/EN 13850, and cannot be realized with the solution presented here. Function In case of a hazardous situation with a running engine, by pushing the emergency-off device, the MMS is tripping, which de-energizes the motor. The danger situation is averted. The signalling contacts may be used for visualization of a tripping. Standards Table 1 lists all fulfilled standards and relevant guidelines for the presented solution. The solution complies also with C TYPE 0 - system as described in ISO and IEC 62061, coming into effect in EC/EN UL IEC/EN IEC/EN UL IEC/EN IEC/EN IEC/EN DIN EN50013 UL 508 CS C22.2 No14 EN ISO Part 1: General principles for design 2006/95/EC 2006/42/EC 2004/108/EC 2002/95/EC IEC/EN IEC/EN IEC/EN IEC EN Low-voltage switchgear and controlgear Part 1: General rules Low-Voltage Switchgear and Controlgear Low-voltage switchgear and controlgear Part 2: Circuit breakers Low-voltage switchgear and controlgear Part 4-1: Contactors and Motor-Starters Low-Voltage Switchgear and Controlgear - Part 4-1: Contactors and Motor-Starters Low-voltage switchgear and controlgear Part 5: Control circuit devices and switching elements Degrees of Protection (IP-Code) Basic and safety principles for man-machine interface, marking and identification Coding principles for indicators and actuators Low-voltage Switchgear and Controlgear for Industrial Use; Terminal Marking and Distinctive Number for Particular Control Switches Industrial Control Equipment Industrial Control Equipment Safety of machinery -- Safety-related parts of control systems Low Voltage Directive Machinery Directive EMV-Directive Restriction of Hazardous Substances Directive Dimensions of Low-Voltage switchgear and controlgear Standardized mounting on rails of mechanical support of electrical devices in switchgear and controlgear installations Environmental testing Part 2: Tests Test Fc: Vibration (sinusoidal) Environmental testing- Part 2-27: Tests - Test Ea and guidance: Shock Safety of machinery - Functional safety of safety-related electrical, electronic and programmable electronic control systems Functional safety of electrical/electronic/programmable electronic safety-related systems Table 1: Referred standards and guidelines 2 2CDC131086B0201 Emergency-off application Manual motor starters MS116/132, undervoltage release U1
3 Manual motor starter MS116/132, undervoltage release U1 Components Emergency-off applications in accordance with IEC-, IEN stop category 0 using MS132 are designed for nominal currents up to 32. The components are designed according to the requirements and have to comply to international regulations and standards. Even under difficult environmental circumstances and operation conditions the components of this solution stay reliable for a long period of time. Since an emergency-off solution needs to stop the machine as quickly as possible without creating additional hazards, a risk analysis needs to be conducted in any case to ensure the correct connection. The manual motor starter (MMS) is extended by the undervoltage release U1. U1 and the emergency-off device E-off are electrically connected. When pressing E-off the MMS is tripped mechanically through the undervoltage release. ll parts are immediately de-energized and the motor stops. ccording to the standards E-off is red on yellow background, the emergency-off grab wire is red for high visibility. List of components Manual motor starter MS116/MS132 Undervoltage release U1 Short circuit signalling contact CK1 Signalling contact SK1 Enclosure for MMS IB132-x/DMS132-x Emergency-off device CombiLine-compact CombiLine-modular II Manual motor starter MS116 2 Signalling contact SK1 3 Undervoltage release U1 4 Emergency-off device MEPY1 Emergency-off application Manual motor starters M116/132, undervoltage release U1 2CDC131086B0201 3
4 Manual motor starter MS116/132, undervoltage release U1 Selection of the right MMS l CS Rated service short-circuit breaking capacity l CU Rated ultimate short-circuit breaking capacity I CC Prospective short-circuit current at installation location MS116 short-circuit breaking capacity and back-up fuses Type 230 V C 400 V C 440 V C 500 V C 690 V C MS MS MS MS No back-up fuse required up to I CC = 30 MS MS No back-up fuse required up to I CC = 50 MS MS MS MS MS MS MS MS MS Table 2: Selection table MS116 MS132 short-circuit breaking capacity and back-up fuses Type 230 V C 400 V C 440 V C 500 V C 690 V C MS MS MS MS No back-up fuse required up to I CC = 100 MS MS MS MS MS MS MS MS MS MS MS Table 3: Selection table MS CDC131086B0201 Emergency-off application Manual motor starters MS116/132, undervoltage release U1
5 Manual motor starter MS116/132, undervoltage release U1 Technical data Durability The application is suitable for a minimal durability of cycles. mbient air temperature In the enclosure (IB132) MS116 mechanical cycles Operation Table 5: mbient air temperature electrical up to cycles electrical 20 to cycles MS132 mechanical cycles electrical cycles Emergency-off device Table 4: Durability cycles Current diagram example 400 V L1, L2, L3 D1 U< D2 1 L1 3 L2 5 L U1- SK1- HK1- HKF1- CK1- MS116/MS132 I> I > I> 2 T1 4 T2 6 T N M 3 Emergency-off application Manual motor starters M116/132, undervoltage release U1 2CDC131086B0201 5
6 Contact us BB STOTZ-KONTKT GmbH Eppelheimer Straße Heidelberg, Germany Phone: +44 (0) Fax: +44 (0) You can find the address of your local sales organization on the BB home page -> Low-voltage products Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. BB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. ny reproduction, disclosure to third parties or utilization of its contents - in whole or in parts is forbidden without prior written consent of BB. Copyright 2015 BB ll rights reserved Order Number 2CDC131086B
Manual motor starter magnetic only MO325
Data sheet Manual motor starter magnetic only MO325 Manual motor starters magnetic only are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF
More informationManual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationManual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationManual motor starter MS132
Data sheet Manual motor starter MS132 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationManual motor starter MS132
Data sheet Manual motor starter MS132 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationManual motor starter MS132
Data sheet Manual motor starter MS132 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationManual motor starters Overview and benefits
Manual motor starters Overview and benefits ABB offers a complete standard motor-protection concept for the world market IEC motor branch protection UL type E/F Motor applications with fuseless protection
More informationSystem pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077
Data Sheet System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 2CDC021026S0011 2CDC021016S0012 The S 200 PR is a high-performance supplementary protector with
More informationThermal overload relay TF65 and TF96
Data sheet Thermal overload relay TF65 and TF96 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against overload and
More informationThermal overload relay TF140DU and TF140DU-V1000
Data sheet Thermal overload relay TF140DU and TF140DU-V1000 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays are the alternative to the thermal overload relays. An electronic overload relay offers reliable and fast protection
More informationMini Contactors Applications and Segments
Mini Contactors and Segments Overview and Mini Contactors ABB Mini Contactors Success story Energy for motors, machines or other electrical components has to be reliably turned on and off often by remote
More informationMini contactors B6, BC6 with 3 pole
Data sheet Mini contactors B6, BC6 with 3 pole Mini contactors from ABB are used for remotely ling motors and other loads wherever space is at a premium. These devices feature hum free coils, shallow depth,
More informationElectronic overload relays EF205 and EF370
Data sheet Electronic overload relays EF205 and EF370 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationBrochure. Motor protection and control DRAS enclosed direct-on-line starters
Brochure Motor protection and control DRS enclosed direct-on-line starters DRS09 DRS16 enclosed direct-on-line starters 4 to 7.5 kw, protected by thermal overload relays C or DC operated DRS + T16 to
More informationUncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA
Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA The next generation MCB for UL/CSA applications within the proven System pro M compact
More informationShort form catalogue Motor protection and control Manual motor starters
Short form catalogue Motor protection and control Manual motor starters Motor protection and control Index Contents Beneifits 4 Features 5 Overview 6 Manual motor starter MS116 and MS132 8 Manual motor
More informationSystem pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications
System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System pro M compact
More informationSystem pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications
Data Sheet System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System
More informationSelective main circuit breakers S 750 series Technical Data
Selective main circuit breakers S 750 series Technical Data When connecting aluminium conductors ( 4 mm 2 ) ensure that the contact surfaces of the conductors are cleaned, brushed and treated with grease.
More informationABB i-bus KNX Hotel IP Link, Bundle HIL/S , 2CDG110237R0011
Technical data 2CDC502097D0201 ABB i-bus KNX Product description HIL/S 20.1.1 The Hotel IP Link is used to connect zones of up to 20 KNX TP devices with central systems (such as Visualizations or Hotel
More informationABB i-bus KNX HIL/S , Hotel IP Link, Bundle
ABB i-bus KNX HIL/S 20.1.1, Hotel IP Link, Bundle Description of product HIL/S 20.1.1 Hotel IP Link, Bundle The Hotel IP Link is used to connect zones of up to 20 KNX TP devices with central systems (such
More informationData Sheet Manual Motor Starters Ex9SN Series
Data Sheet Manual Motor Starters Ex9SN Series www.noarkusa.com NOARK Ex9SN Series Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors
More informationABB i-bus KNX DG/S x DALI-Gateway Basic
ABB i-bus KNX DG/S x.64.1.1 DALI-Gateway Basic The lamps are variably controlled via KNX per DALI output via Broadcast (all lamps jointly) 16 lighting groups 64 individual lamps 16 scenes 64 self-contained
More informationBRIDGE-BOY Load limitation electronics with 1 or 3 set points
Change from one to two columns Data Sheet DS/BRIDGE-BOY-LCI-EN Rev. A BRIDGE-BOY Load limitation electronics with 1 or 3 set points Electronics with 1 or 3 set points designed, in combination with a load
More informationSystem pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489
System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch
More informationProtection and Connection Motorized and automatic transfer switches IEC Technical guide
Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety
More information249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h
No Filter 81.6 % Auto 9.1 m3/h 250.0 m3/h Auto 99.7 m3/h 100.0 m3/h Auto 91.3 m3/h 92.0 m3/h Auto 40.0 m3/h 7. MW Auto 50.7 m3/h 50.0 m3/h 7.2 % Auto.6 % 45.0 % ABB NF Contactor Relays Overview...3 Ordering
More informationPanorama. Contactors Motor protection Accessories
Panorama Contactors Motor protection Accessories Extensive range of contactors High performance contactors for your applications from 9 to 5000 A Mini contactors for compact equipments - up to 5.5 kw /
More informationThermal Overload Relays
Data Sheet Thermal Overload Relays Ex9RD Series Ex9RD93 Ex9RD25 www.noarkusa.com NOARK Ex9RD Series Thermal overload relays are economic electromechanical protection devices for the main circuit. They
More informationABB cable glands SCG series Stainless Steel 316L, general purpose cable glands
1 TEHNIL DT SHEET cable glands SG series Stainless Steel 316L, general purpose cable glands Stainless steel cable glands for general purpose use, OEM, industrial and commercial applications, where a high
More informationRedundancy unit CP-C.1-A-RU Accessory for CP-C.1 range power supplies
Data sheet Redundancy unit -A-RU Accessory for range power supplies ABB s redundancy units are used to establish true redundancy which increases the availability of electrical systems significantly. 2CDC
More informationFuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A Superior performance versus standard fuses ensuring up to 40% faster protection in case of low
More informationAF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101412D0201 25/03/11-30-00-.. / Z-30-00-.. 3-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 220
More informationSU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489
MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277
More informationAF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101415D0201 25/03/11 AF30-30-11-.. / AF30Z-30-11-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF30(Z) contactors are used for controlling power circuits
More informationAF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101408D0201 25/03/11-30-01-.. / Z-30-01-.. 3-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 220
More informationData Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1
Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series B Ex9BE3C0 Ex9BHC6 www.noarkus.com NORK Ex9 Series B NORK Miniature Circuit Breakers offer these advantages: highperformance, small size, exemplary
More informationProduct information. ECOSS Electronic compact starter for wound rotor drives
Product information ECOSS Electronic compact starter for wound rotor drives Controlled and safe start-up of wound rotor drives Electronic compact starters are used when slip-ring motors have to be started
More informationData Sheet DS/NGB-EN Rev. B. Multi barriers. Measurement made easy. Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1
Data Sheet DS/NGB-EN Rev. B Multi barriers Measurement made easy Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1 Change from two to one column Multi barriers Change from one to two columns
More informationAF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101419D0201 06/04/11-40-00-.. / Z-40-00-.. 4-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 440
More informationAF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet SBC042D020 06/04/ -22-00-.. / Z-22-00-.. 4-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 440 V DC.
More informationSafety stop buttons Smile, INCA and Compact
Smile, INCA and are used to safely stop a certain part of a dangerous machine. ABB offers safety stop buttons to suit different needs of connection and communication. Models are available for e.g. external
More informationPhone: Fax: Web: -
HK1-11 HKF1-11 HK-11 HKS-20 uxiliary contacts Mounting uxiliary contacts position Pilot duty rating Instantaneous Lagging / leading / max. 116 132 5x 9x quantity ac dc NO NC NO NC 2 - - - HK1-20 Right
More informationZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear Durable and reliable Minimum overall costs Safety first ZX offers maximum economy Sealed gas compartments The compact design of the panels reduces the
More informationMS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories
Page 1 of 5 MS132-10 ABB contact for United States of America General Information Extended Product Type: Product ID: EAN: Catalog Description: Long Description: MS132-10 1SAM350000R1010 4013614400100 MS132-10
More informationContact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France
Contact us ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F-69687 Chassieu cedex / France You can find the address of your local sales organisation on
More informationValve Blocks. For direct flanging to pressure and differential pressure transmitters. Drop-forging housing. Replaceable valve seat
Data Sheet 10/14-5.32-EN Valve Blocks For direct flanging to pressure and differential pressure transmitters Drop-forging housing Replaceable valve seat Valve stem with back-flow seal and crimped valve
More informationMEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices
MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect
More informationTriLine PowerModules Overview with Planing Examples
04 2012 TriLine PowerModules Overview with Planing Examples Catalog template for LSO with German prices The rates must be adjusted to country-specific from the LSO TriLine PowerModules Contents The new
More informationControl and Automation. AC500 - your PLC for solar systems Change for more energy efficiency
Control and Automation AC500 - your PLC for solar systems Change for more energy efficiency Photovoltaic and thermosolar systems Those who are close to the sun are more successful Today, the role of renewable
More informationEmergency stops Award winning design
Emergency stops Award winning design Emergency stops Choosing the right emergency stop device is vital in order to increase the safety for your personnel and equipment. ABB has a very wide range of emergency
More informationProduct index. 4 - Manual motor protectors. Phone: Fax: Web: -
Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type
More informationTwinLine The new system of wall-mounting and floor-standing cabinets
04 2012 TwinLine The new system of wall-mounting and floor-standing cabinets 04 2012 TwinLine The new system of wall-mounting and floor-standing cabinets 2 2CPC 000 170 L0201 TwinLine The new system of
More informationNF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101428D0201 28/03/11 -.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits. NF(Z)
More informationProduct index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.
Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type
More informationABB i-bus KNX Magnetic Contact EnOcean, 868 MHz MKE/A , 2CDG R0011
Technical Data 2CDC508163D0201 ABB i-bus KNX Device description The Magnetic Contact EnOcean is a surface mounted device for windows or doors. Its purpose is to recognize the opening or closing of windows
More informationTechnical data for manual motor starters Type MS325
for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations
More informationProduct Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant
Product Brochure Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant Introduction General The braking switch serves the purpose of electrical braking a machine in a hydro or pumped
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationDead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability
Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear Minimum overall costs ZX offers maximum economy The compact design of the panels reduces the space required and therefore the size of the station. Freedom
More informationZS35-PEN Screw Clamp Terminal Blocks Ground + Neutral
Technical Datasheet SNK6047D00 Catalogue Page ZS35-PEN Screw Clamp Terminal Blocks Ground + Neutral Simplify your PE.N connection with ZS35-PE block connected to ZS35-BL through a premounted jumper. SNK6063F004
More informationManual Motor Starter MS 116. Technical Catalogue
Manual Motor Starter MS 116 Technical Catalogue The task: Economic fuseless motor protection Know-how in safe-keeping ABB is a renowned manufacturer of electrical motors. But apart from the hardware in
More informationMotor Starter Reverse MSR22-FBP
Technical Description FBP FieldBusPlug V6 Motor Starter Reverse MSR22-FBP V 6 MSR22-FBPMotor Starter Reverse MSR22-FBP: Motor branch connection 1 motor, 2 directions of rotation Connecting plug for external
More informationVoltage limiting device HVL
Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3
More informationZK2.5-SP-4P PI-Spring Terminal Blocks Disconnect with plug - with test socket
Technical Datasheet 1SNK1659D01 Catalogue Page 1SNK160S01 ZK2.5-SP-P PI-Spring Terminal Blocks Disconnect with plug - with test socket The flexible solution for fitting the component of your choice in
More informationRSDE10 / RSDE20 (Contrac) Electrical Linear Actuator
Contents Data Sheet Rev. A RSDE10 / RSDE20 (Contrac) Electrical Linear Actuator For continuous positioning, In explosion-proof design, Rated force 10 kn / 20 kn (2200 lbf / 4400 lbf) Electrical actuator
More informationVoltage limiting device HVL
Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3
More informationOutdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker
More informationData Sheet Manual Motor Starter Ex9S32 Series
Data Sheet Manual Motor Starter Ex9S32 Series na.noark-electric.com NOARK Ex9S32 Series Features Ex9S32 Manual Motor Starter provides manual isolation, manual motor control, and overcurrent protection
More informationMoving Coil Indicators with direct temperature sensor input
Data Sheet 10/30-1.66-EN Rev. A Moving Coil Indicators with direct temperature sensor input Inputs Resistance thermometers, resistance-type remote sensor (thermocouples on request) Formats Square indicators
More informationEAS822 (Contrac) Power Electronic Unit
Contents Data Sheet Rev. A EAS822 (Contrac) Power Electronic Unit For continuous control of Contrac actuators PME120 AN and LME620 AN Microprocessor-controlled power electronic unit with integrated frequency
More informationZS4-PE Screw Clamp Terminal Blocks Ground
Technical Datasheet SNK60D0 Catalogue Page SNK60S0 ZS4-PE Screw Clamp Terminal Blocks Ground Improve the safety of your installation in the event of a short-circuit thanks to our screwless rail contact:
More informationMS General Information Extended Product Type: MS
MS132-1.6 General Information Extended Product Type: MS132-1.6 Product ID: 1SAM350000R1006 EAN: 4013614400063 Catalog Description: MS132-1.6 Manual Motor Starter Long Description: The MS132-1.6 manual
More informationSystem pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489
Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection
More informationZK2.5-SF-R PI-Spring Terminal Blocks For 5x20 fuses - with blown fuse indicator
Technical Datasheet SNK605D00 Catalogue Page SNK60S00 ZK.5-SF-R PI-Spring Terminal Blocks For 5x0 fuses - with blown fuse indicator - Protect your circuits with 5x0 fuse terminal blocks compliant with
More informationZS6-S Screw Clamp Terminal Blocks Disconnect with blade
Technical Datasheet SNK646D00 Catalogue Page ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,
More informationS840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en
Snap-action switches S80, S85, S86 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D0.en Snap-action switches, S80, S85, S86 Series Single-break
More informationZK6 PI-Spring Terminal Blocks Feed-through
Technical Datasheet SNK69D0 Catalogue Page SNK69S0 ZK6 PI-Spring Terminal Blocks Feed-through Combine high performance with compact dimensions: - 000 V AC / DC IEC 600 V UL, - Opt for the best marking
More informationABB central inverters PVS to 2091 kva
SOLAR INVERTERS ABB central inverters PVS980 1818 to 2091 kva 01 ABB central inverters raise reliability, efficiency and ease of installation to new levels. The inverters are aimed at system integrators
More informationZS6-D1-PE Screw Clamp Terminal Blocks Double deck with 1 ground circuit
Technical Datasheet SNK649D00 Catalogue Page ZS6-D-PE Screw Clamp Terminal Blocks Double deck with ground circuit - Save space with double deck ground terminal blocks aligned with ZS6-D double deck terminal
More informationZS10-PE Screw Clamp Terminal Blocks Ground
Technical Datasheet SNK606D00 Catalogue Page ZS0-PE Screw Clamp Terminal Blocks Ground Improve the safety of your installation in the event of a short-circuit thanks to our screwless rail contact: - Rail
More informationZS6-3S Screw Clamp Terminal Blocks Feed-through with 3 connections
Technical Datasheet SNK663D00 Catalogue Page SNK667S00 ZS6-3S Screw Clamp Terminal Blocks Feed-through with 3 connections - Recommended for energy markets and highly demanding applications requiring that
More informationUS Brochure. Tmax XT Molded case circuit breakers Simply XTraordinary
US Brochure Tmax XT Molded case circuit breakers Simply XTraordinary XTraordinary benefits ABB, a global leader in circuit breaker technology is making major investments in the United States to bring extraordinary
More informationData Sheet Manual Motor Starter Ex9S32 Series
Data Sheet Manual Motor Starter Ex9S32 Series na.noark-electric.com NOARK Ex9S32 Series Features Ex9S32 Manual Motor Starter provides manual isolation, manual motor control, and overcurrent protection
More informationPQstorI One stop solution for energy storage and power quality
ENERGY STORAGE INVERTERS PQstorI One stop solution for energy storage and power quality s.a. ABB n.v. Power Quality Products Allée Centrale 10 Z.I. Jumet B-6040 Charleroi (Jumet) Belgium Phone: +32(0)
More informationZS4-S Screw Clamp Terminal Blocks Disconnect with blade
Technical Datasheet SNK6D00 Catalogue Page SNK6S00 ZS4-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,
More informationZK4-PE PI-Spring Terminal Blocks Ground
Technical Datasheet SNK60D00 Catalogue Page SNK60S00 ZK-PE PI-Spring Terminal Blocks Ground Improve the safety of your installation in the event of a short-circuit thanks to our screwless rail contact:
More informationBrochure. Modular Systems wind portfolio Power Collection and Grid Connection products
Brochure Modular Systems wind portfolio Power Collection and Grid Connection products Wind portfolio Background ABB is one of the few suppliers that has been deeply involved in wind power segment development,
More informationZS50-PE Screw Clamp Terminal Blocks Ground
Technical Datasheet SNK607D00 Catalogue Page ZS0-PE Screw Clamp Terminal Blocks Ground - Reliable electrical and mechanical contact with the rail that exceeds the requirements of the IEC 60947-7- terminal
More informationData sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427
Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This
More informationZS10-ST Screw Clamp Terminal Blocks Test disconnect with sliding link
Technical Datasheet SNK656D0 Catalogue Page ZS-ST Screw Clamp Terminal Blocks Test disconnect with sliding link - Secure your disconnect operations in control circuits with the robust sliding link operated
More informationZS4-PE Screw Clamp Terminal Blocks Ground
Technical Datasheet SNK600D00 Catalogue Page ZS4-PE Screw Clamp Terminal Blocks Ground Improve the safety of your installation in the event of a short-circuit thanks to our screwless rail contact: - Rail
More informationZS10 Screw Clamp Terminal Blocks Feed-through
Technical Datasheet SNK6004D00 Catalogue Page SNK6004S00 ZS0 Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to 0 mm² (CB certified) 6 AWG in just 8 mm 0. in spacing. SNK6008F004
More informationZS4-SF1-R Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with blown fuse indicator
Technical Datasheet SNK63D00 Catalogue Page SNK63S00 ZS-SF-R Screw Clamp Terminal Blocks For x 0 and x fuses - with blown fuse indicator - Protect your circuit with x and x0 fuse terminal blocks (fuse
More informationZK2.5-4P PI-Spring Terminal Blocks Feed-through with 4 connections
Technical Datasheet SNK60D00 Catalogue Page SNK605S00 ZK.5-P PI-Spring Terminal Blocks Feed-through with connections Find all the features of the ZK.5 terminal block with the added option of distributing
More informationMEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJC 4 Indoor voltage transformers 2 TJC 4 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning impulse test voltage
More informationZK2.5-SP PI-Spring Terminal Blocks Disconnect with plug - with test sockets
Technical Datasheet SNK603D00 Catalogue Page SNK6038S00 ZK.5-SP PI-Spring Terminal Blocks Disconnect with plug - with test sockets The flexible solution for fitting the component of your choice in series
More informationLow Voltage Systems MNS and MNS is PowerCenter
Low Voltage Systems MNS and MNS is PowerCenter For our customers, it s all about saving space maximizing functionality for power distribution systems while reducing equipment footprint. ABB has answered
More information