PROBLEM IN COMMISSIONING PROCESS OF 125VDC STATIONARY BATTERY IN LAM-LUK-KA SUBSTATION

Size: px
Start display at page:

Download "PROBLEM IN COMMISSIONING PROCESS OF 125VDC STATIONARY BATTERY IN LAM-LUK-KA SUBSTATION"

Transcription

1 PROBLEM IN COMMISSIONING PROCESS OF 125VDC STATIONARY BATTERY IN LAM-LUK-KA SUBSTATION K. Paramate, Electricity Generating Authority of Thailand, , ABSRACT This paper presents the problem in commissioning process of 125VDC stationary battery in Lam-Luk- Ka substation which has one string of 58cells stationary battery. This construction project was a turnkey project and contractor has selected a battery from manufacturer, while it has never been used in EGAT. In this commissioning was revealed numerous of problems such as the test results of stationary battery that do not meet the standard, The conclusion of each process is quite slow due to many parties concerned. And in the hustle of the schedule in the power supply system. The problems and obstacles, as mentioned above, enabling organizations to gain experience and knowledge to be used as a guideline to action for the commissioning phase in construction projects that will be occur more in the future. KEYWORDS: Commissioning, Stationary Battery, Substation 1. Introduction These days, electricity demand is becoming more significant increase in year over year. In order to provide a maximum confidence in terms of stability and reliability in a power supply especially in the metropolitan area where the most of important business, industry and economy of the country, as well as to prevent unplanned power failures or electricity outages. Therefore EGAT has required to ensure that electric very closely matches the demand by construct a new power plant, substation and transmission line in order to meet sufficient on increasing the demand of electricity. In terms of construction, there are a commissioning phase procedure which is very important since the idea of intensive inspection in commissioning phase could be reduced a load of maintenance Lam-Luk-Ka substation is one of the substation that was constructed to provide a maximum confidence in terms of stability and reliability in a power system. Which located in Pratumthani, in responsibility of Metropolitan Area Operation Division. Lam-Luk-Ka substation is 230/115kV Gas Insulated Substation type consist of Power Transformer 300MVA, 230/115kV 3 units. Lam-Luk-Ka substation has one string of stationary battery and each string contain 58 cells. This construction project was a turnkey project and contractor has selected a battery from manufacturer, while it has never been used in EGAT. There are OPzS type, nominal voltage 2 volt and nominal capacity This clause shall consider carefully for the specification and capabilities of the battery. During inspection of the battery, there are step procedures for testing battery such as Visual Inspection, Discharge Test to measure capacity of the battery, Measuring the specific gravity and the volt/cell while Equalize Charge and Floating Charge and Measurement Impedance of batteries in each Cell, if it was found that the battery fails the test, a plan could be revised in a problem solving meeting to find the best solution. Figure 1: Stationary Battery 125VDC in Lam-Luk-Ka substation

2 2. Main Contents 2.1 Stationary Battery Stationary lead acid battery is Battery that use in substation. Normally Stationary battery will use at 125VDC. In one string contain of 58cell and each cell have nominal voltage at 2volt, Float Charge Voltage around 2.23±0.05 volt/cells, Equalize Charge Voltage around 2.35±0.05 volt/cells. 2.2 Testing and Commissioning Procedure Figure 2: DC Supply in Substation Standard and Specification In the commissioning process, EGAT was follow to Specification from Transmission System Engineering Division, EGAT, Specification No.310 Stationary Battery which covers the general requirements for design, manufacture, test and supply of the stationary battery. Moreover, EGAT was follow to Standard EGAT TS EGAT Testing Standard Stationary Battery which cover Test procedure, Test item and standard values for stationary lead acid battery Test Item for Stationary Battery Visual Inspection Before commissioning all cells/blocks must be inspected for mechanical damage, cells must be connected with the correct polarity and connectors firmly seated. If necessary, the terminal covers must be put on. With charger off and loads isolated, connect battery to the direct current power supply, maintaining correct polarity (positive terminal to positive post) Discharge Test or Capacity Test Equalizing charge battery until specific gravity and volt/cell are at steady state Before doing Discharge test Discharge current equal to Amp. Hour rate divided by Hour rate Using time for Discharge 100% of Hour connect battery to Load discharge resistor During Discharge test must to record specific gravity and volt/cell in every hour until the final hours Impedance Test Impedance Test is the test method to follow the condition of battery when the same state at full charge Impedance/Cells should not deviate from group over than 10%.

3 2.3 Problem in Commissioning Problem of Battery Room During the construction of Lam-Luk-Ka substation. We found that there was constructed a window glass in the battery room, however from some experience, standards and specifications related to the construction of a battery rooms. Practically battery room should be closed room without windows installation in order to prevent heat from the sun s radiant throughout the battery, which could be affected the ability to control the temperature inside the room. However, when an inevitable for the window installation, these should be required a sunblind installation to exposure sunlight. Figure 3: Battery room, which found that the construction of windows glass From the information above, EGAT request to the contractor to correct it. The contractor was resolve by building a brick wall instead of the window Figure 4: Battery room after correction Problem of Station Battery 125VDC First Commissioning When the contractor has already done with the battery room. They had done the Discharge Test and deliver the test result to EGAT. The result has found that battery can pass Discharge Test, on the other hand when the Equalize Charge and Floating Charge found the volt/cell was abnormally high and the deviation was over tolerance of the manufacturer. Table 1 shows the value of volt/cell when Equalize Charge and Floating Charge. To find the best solution for the project by setting up the meeting for clarify the issues. It was concluded that the manufacturer would be resolved by discharge to 60% of the battery capacity and then fully charge. Then adjustment the specific gravity. However, after the manufacturer has complete resolved and measure it again, volt/cell still unstable. After this problem, the manufacturer presents the last plan to repair this battery by follow this plan

4 During repairing process the manufacturer will provide mobile battery and will calculated capacity of load in Lum-Luk-Ka substation to supply 125VDC The manufacturer will bring back all string of battery to manufacturer s factory to recondition In the process of repairing the manufacturer has grouping the battery by volt/cell into two group. Group 1 is volt/cell over than standard (19 Unit) and Group 2 is volt/cell meet the standard Group 1 will discharge at 60% and recharge at current 0.05CA = 5Hr and adjust to 0.1CA = 10Hr during charging and record specific gravity and thermal every hour until battery full charge Group 2 will charge to full charge by adjust voltage charge to 2.35±0.05 volt/cells Gather Group 1 and Group2 and charging to balance voltage by adjust voltage charge to 2.33±0.05 volt/cells Return all string of battery back to Lam-Luk-Ka substation Table 1: volt/cell was abnormally high and the deviation was over tolerance of the manufacturer Second Commissioning After the manufacturer has complete resolved. The manufacturer transport all battery back to Lam-Luk-Ka substation and ask for commissioning again. In the new commission process EGAT found that the specific gravity in the prior of the process Discharge Test was not meet the standard criteria. EGAT provides manufacturers clarify and find a solution. The manufacturer resolve by recharging include adjust specific gravity Third Commissioning After the second resolved, During the Discharge Test the specific gravity over scale from the manufacturer s instrument, therefore EGAT request to stop the Discharge Test and test again with new one of specific gravity instrument which has certificate.

5 Last Commissioning In the last commissioning EGAT told the manufacturer that if this time the Discharge Test was not pass EGAT will reject all sting of battery from this manufacturer. In this commissioning the manufacturer brings the new one of specific gravity instrument with the certification. Battery can pass Discharge Test, volt/cell and specific gravity are meet the standard criteria. 3. Result The result of the commissioning has found that battery can pass Discharge Test, on the other hand when the Equalize Charge and Floating Charge found the volt/cell was abnormally high and the deviation was over tolerance of the manufacturer. To find the best solution for the project by setting up the meeting for clarify the issues. It was concluded that the manufacturer would be resolved by discharge to 60% of the battery capacity and then fully charge. Then adjustment the specific gravity. After the manufacturer has complete resolved. In the new commission process EGAT found that the specific gravity in the prior of the process Discharge Test was not meet the standard criteria. EGAT provides manufacturers clarify and find a solution. After the second commissioning, the manufacturer has resolved again but during the Discharge Test the specific gravity over scale from the manufacturer s instrument, therefore EGAT request to stop the Discharge Test and test again with new one of specific gravity instrument which has certificate. In the last commissioning the that battery can pass Discharge Test, volt/cell and specific gravity are meet the standard criteria. 4. Conclusion In this commissioning was revealed numerous of problems such as the test results of stationary battery that do not meet the standard, the conclusion of each process is quite slow due to many parties concerned. And in the hustle of the schedule in the power supply system. The problems and obstacles, as mentioned above, enabling organizations to gain experience and knowledge to be used as a guideline to action for the commissioning phase in construction projects that will be occur more in the future. REFERENCES [1] IEEE Recommended Practice for Installation Design and Installation of Vented Lead-Acid Batteries for Stationary Applications, IEEE [2] IEEE Recommended Practice for Installation Design and Installation of Valve-Regulated Lead-Acid Storage Batteries for Stationary Applications, IEEE [3] IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead Acid Batteries for Stationary Applications, IEEE [4] EGAT Testing Standard Stationary Battery, EGAT TS [5] Specification No.310 Stationary Battery, Transmission System Engineering Division, EGAT [6] Design Guide for Power Station Battery Rooms, Eskom

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA) INSTRUCTION MANUAL Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA) DESCRIPTION / TYPE: SUN BATTERY Nominal values Nominal voltage UN: 2V Cells 6V Blocks 12V

More information

Battery Storage Systems

Battery Storage Systems Battery Storage Systems Agenda System Components Applications How to Size Batteries System Components Basic battery theory Electro-chemical reaction Two dissimilar metals Positive electrodes Negative electrodes

More information

TYPE TEST REPORT. OPzS CELLS AND BLOCK BATTERIES. According to IEC

TYPE TEST REPORT. OPzS CELLS AND BLOCK BATTERIES. According to IEC TYPE TEST REPORT OPzS CELLS AND BLOCK BATTERIES According to IEC 60896-11 Systems Sunlight SA, 2 Ermou & Nikis Str, Syntagma Square 105 63 Athens, Attica, Greece Report Type Type Test acc. to IEC 60896-11,

More information

GASTON GTF range battery manual

GASTON GTF range battery manual GASTON GTF range battery manual Type 1. Brief introduction GTF stationary lead-acid battery (acid spray-proof type), ranging from 200ah to 3000ah at 10hr rate in 17 models, are mainly applied in power

More information

CITY OF CHARLEVOIX REQUEST FOR BIDS WESTENBROEK SUBSTATION 48VDC BATTERY BANK

CITY OF CHARLEVOIX REQUEST FOR BIDS WESTENBROEK SUBSTATION 48VDC BATTERY BANK CITY OF CHARLEVOIX REQUEST FOR BIDS WESTENBROEK SUBSTATION 48VDC BATTERY BANK The City of Charlevoix is requesting bids for the furnishing and delivery (F.O.B. project material site, Charlevoix, Michigan)

More information

TOTALFLOW Technical Bulletin 59 Lead Acid Battery Inspection and Maintenance Procedures

TOTALFLOW Technical Bulletin 59 Lead Acid Battery Inspection and Maintenance Procedures TOTALFLOW Technical Bulletin 59 Lead Acid Battery Inspection and Maintenance Procedures Totalflow Technical Bulletin Version 1.0, Revision AC (8 January, 2001) \\isntsrv1\tffiles\documentation\techbulls\insert

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

Battery Monitoring Why Technology Matters. Mats Karlstrom V.P. Sales & Marketing, Alber

Battery Monitoring Why Technology Matters. Mats Karlstrom V.P. Sales & Marketing, Alber Battery Monitoring Why Technology Matters Mats Karlstrom V.P. Sales & Marketing, Alber 1 Agenda Introduction Why is battery monitoring needed? Example of battery failure Why are resistance measurements

More information

IEC APPROVAL TESTS

IEC APPROVAL TESTS IEC61427-1 APPROVAL TESTS Edition 1.0 : 2013-04 Secondary cells and batteries for renewable energy storage General requirements and methods of test Part 1 : Photovoltaic off-grid application Flooded lead-acid

More information

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A) A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where

More information

UPS Battery Maintenance Training

UPS Battery Maintenance Training UPS Battery Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This UPS Battery Maintenance

More information

White Paper. Direct Current Load Banks for Battery Capacity Testing

White Paper. Direct Current Load Banks for Battery Capacity Testing White Paper Direct Current Load Banks for Battery Capacity Testing Direct Current Load Banks for Battery Capacity Testing Reliable Direct Current (DC) power requires battery systems to be maintained according

More information

STATIONARY BATTERY SEMINAR

STATIONARY BATTERY SEMINAR Consulting Associates, Inc. Introduction & Stationary Battery Basics Page STATIONARY BATTERY SEMINAR Developed by Marco W. Migliaro, PE, Life Fellow IEEE Copyright 994-95, 00, 004, 006, 008, 0-, 04-5 by

More information

Sentry Battery Charger. Installation and Operations Manual Section 75

Sentry Battery Charger. Installation and Operations Manual Section 75 Sentry Battery Charger Installation and Operations Manual 00-02-0616 03-03-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change our

More information

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems Version:- 2.1 Date of Issue:- July 2016 Page 1 of 29 NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems 1. Purpose This document is to detail the technical requirements

More information

1. INTRODUCTION AND SYSTEM DESCRIPTION CONDENSED OPERATING INSTRUCTIONS SPECIFICATIONS CONTROLS AND DISPLAYS...

1. INTRODUCTION AND SYSTEM DESCRIPTION CONDENSED OPERATING INSTRUCTIONS SPECIFICATIONS CONTROLS AND DISPLAYS... TABLE OF CONTENTS 1. INTRODUCTION AND SYSTEM DESCRIPTION... 5 2. CONDENSED OPERATING INSTRUCTIONS... 8 2.1 Constant Current Charge (normal mode)... 8 2.2 Constant Voltage... 9 2.3 Peak Voltage Charge...

More information

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Wide operating temperature range: Our battery will operate from -30C to (-22F) to 60C when it is fully charged.

Wide operating temperature range: Our battery will operate from -30C to (-22F) to 60C when it is fully charged. Introduction Our batteries are manufactured under the guidelines of ISO 9002. Each battery undergoes a series of rigid manufacturing and quality control before the battery leaves the factory. Features

More information

Revise model name, charging level and printing mark. Battery cell P/N and MSDS included. Revise spec to comply with certification conditions

Revise model name, charging level and printing mark. Battery cell P/N and MSDS included. Revise spec to comply with certification conditions LITHIUM IRON PHOSPHATE BATTERY Multi-application - LiFePO4 Power Battery Module Specifications Rev. Date Comments A1 2017/11/06 Initial release A2 2017/12/26 Revise model name, charging level and printing

More information

Tubular Flooded (OPzS) Batteries

Tubular Flooded (OPzS) Batteries Tubular Flooded (OPzS) Batteries Stationary & Renewable Energy Applications BATTERIES SOLAR PV WIND GENSET Overview Vented Tubular Plate Batteries for Stationary & RES Applications Discover RE Tubular

More information

Table of Contents. Chapter 1 Product Summary... 2

Table of Contents. Chapter 1 Product Summary... 2 Table of Contents Chapter 1 Product Summary... 2 1.1 Product Profile... 2 1.2 Product Function... 2 1.3 Technical Parameters... 2 1.4 Working Environment Requirement... 3 Chapter 2 Tester Structure...

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS Manual No LI-4159-MIL OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS NAVY BATTERY CHARGER / ANALYZER P/N 4159-MIL MODEL CA-1550-MIL NSN: 4920-01-498-2543 Issued By: LamarTechnologies LLC 14900 40th Ave.

More information

BOOST POWER 1212 Product Description

BOOST POWER 1212 Product Description BOOST POWER 1212 Product Description Contents 1 Introduction...4 2 General Description...4 2.1 Compatibility with standard Lead-Acid Batteries... 4 3 Battery Performance...5 3.1 Discharge Capability...

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Vented / Flooded STT Series Batteries used in Stationary Applications

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Vented / Flooded STT Series Batteries used in Stationary Applications INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Vented / Flooded STT Series Batteries used in Stationary Applications Commissioning by:... Date:... Number of cells/blocks:... Model #:... SAFETY

More information

Guangzhou Vkan Certification and Testing Institute (CVC former GTIHEA)

Guangzhou Vkan Certification and Testing Institute (CVC former GTIHEA) CNAS L0095 age 1 of 14 ages No.: GJW2009-0893 TEST REORT NAME OF SAMLE: Valve Regulated Lead Acid Battery CLIENT: Shenzhen Center ower Tech. Co., Ltd. CLASSIFICATION OF TEST: Commission Test Guangzhou

More information

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AEP Texas (comprised of its Central and North Divisions

More information

CELEBRATING 48 YEARS OF INNOVATION. 48 years BSI We ve Got The Power.

CELEBRATING 48 YEARS OF INNOVATION. 48 years BSI We ve Got The Power. 48 years 1970-2018 CELEBRATING 48 YEARS OF INNOATION We ve Got The Power. BSI REGISTERED General Purpose Design A.H. Current @ 20-hr. rate in. mm in. mm in. mm in. mm lbs. kgs. PS-260 2 6.0 300 1.97 50

More information

Stationary Battery Basics

Stationary Battery Basics Stationary Battery Basics Course Name Stationary Battery Basics Course Length Two days Delivery Options Cost Pompano Beach Training Center...N/A Customer "In-House" - 25 persons max...$8500 Public Web

More information

Owner and Operating Manual for

Owner and Operating Manual for Owner and Operating Manual for 120VAC Manual Control 12VDC Solar Battery Manual Control 120VAC Remote Control 12VDC Solar Battery Remote Control GEN2 Remote Versions Only Boat Lifts Please read this manual

More information

Guardian Battery Charger Series. Installation and Operations Manual Section 75

Guardian Battery Charger Series. Installation and Operations Manual Section 75 Guardian Battery Charger Series Installation and Operations Manual 00-02-0615 02-29-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to

More information

TROJAN BATTERY COMPANY Renewable Energy Warranty Claim Form

TROJAN BATTERY COMPANY Renewable Energy Warranty Claim Form Date: CUSTOMER INFORMATION Name: Address: City: Country: Email: Company: State: Phone: Fax: TO RECEIVE WARRANTY SUPPORT FOR TROJAN BATTERY PRODUCTS USED IN RENEWABLE ENERGY APPLICATIONS, THE FOLLOWING

More information

Smart Battery Charger GPC-35-MAX GPC-45-MAX GPC-55-MAX GPC-75-MAX GPC-100-MAX. Owner s Manual

Smart Battery Charger GPC-35-MAX GPC-45-MAX GPC-55-MAX GPC-75-MAX GPC-100-MAX. Owner s Manual Smart Battery Charger GPC-35-MAX GPC-45-MAX GPC-55-MAX GPC-75-MAX GPC-100-MAX Owner s Manual Table of Contents Important Safety Instructions 2 Features 3 Installation Guidelines 5 Warranty 8 1.0 Important

More information

IEEE IAS Atlanta Chapter

IEEE IAS Atlanta Chapter Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com

More information

Product Guide. An Invensys company

Product Guide. An Invensys company Product Guide An Invensys company Contents Page I/ The principle of the gas-recombination battery... 2 II/ Charge characteristics... 4 III/ Electrical performance tables... 5 IV/ Battery calculations Float

More information

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell -11 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per Cell FEATURES & benefits APPLICATIONS Data Centers Network Operations Centers Industrial

More information

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101194 Document revision: D DCN number: 105128 Date: 3/23/2006 1840 Industrial Circle Longmont, CO 80501 Fax: 303-678-7504 Tel: 303-678-7500

More information

XHP. Low maintenance high performance batteries

XHP. Low maintenance high performance batteries Low maintenance high performance batteries Range Low maintenance, high performance Ni-Cd batteries Powerful assurance for critical applications Depend upon where vital UPS, engine starting and emergency

More information

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1. -1029 Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications. APPLICATIONS Data Centers Network Operations Centers Industrial Process Control Facilities Internet Housing Sites Semiconductor

More information

C&D VRLA Batteries Extended Run Time for Small UPS Machines

C&D VRLA Batteries Extended Run Time for Small UPS Machines TECHNICAL BULLETIN 41-7954 C&D VRLA Batteries Extended Run Time for Small UPS Machines 41-7954/0112/CD www.cdtechno.com Small UPS machines, in the range of 400 to 2500 VA, are typically used to provide

More information

4.28±0.05V 2.4±0.1V. W :29.0mm T :11.1mm

4.28±0.05V 2.4±0.1V. W :29.0mm T :11.1mm age 3 of 16 articulars: test item vs. test requirements Max. charge voltage...: 4.2V Max. Charge current...: Standard discharge current...: 1050mA 210mA Overcharge protection voltage...: Over discharge

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Nickel Cadmium (Ni-Cd) Batteries used in Stationary Applications

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Nickel Cadmium (Ni-Cd) Batteries used in Stationary Applications INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Nickel Cadmium (Ni-Cd) Batteries used in Stationary Applications Commissioning by:... Date:... Number of cells/blocks:... Model #... SAFETY PRECAUTIONS

More information

Gay E. Canough. OFF-GRID Design. Dr. Gay E. Canough, Master trainer. Living Off the Grid

Gay E. Canough. OFF-GRID Design. Dr. Gay E. Canough, Master trainer. Living Off the Grid OFF-GRID Design Dr. Gay E. Canough, Master trainer 1 Understand the Customer s load 2 Load sizing Gay E. Canough AC Appliance watts amps how many of these? number of hours it is used per day equals watt-hr/

More information

Battery Maintenance Solutions for Critical Facilities

Battery Maintenance Solutions for Critical Facilities Battery Maintenance Solutions for Critical Facilities Chapter Two: Meeting Regulatory Requirements and Observing Best Practices Click a section below In chapter one of Emerson Network Power s ebook entitled

More information

Industrial Batteries / Network Power. Classic OCSM.»Exceptional combination of high power, long life and excellent cycling capability«

Industrial Batteries / Network Power. Classic OCSM.»Exceptional combination of high power, long life and excellent cycling capability« Industrial Batteries / Network Power»Exceptional combination of high power, long life and excellent cycling capability« Network Power > Product overview Industrial Batteries The powerful range of Network

More information

FLOODED (VLA ), SEALED (VRLA), GEL, AGM TYPE, FLAT PLATE, TUBULAR PLATE: THE WHEN, WHERE, AND WHY. HOW DOES THE END USER DECIDE ON THE BEST SOLUTION?

FLOODED (VLA ), SEALED (VRLA), GEL, AGM TYPE, FLAT PLATE, TUBULAR PLATE: THE WHEN, WHERE, AND WHY. HOW DOES THE END USER DECIDE ON THE BEST SOLUTION? BATTCON 2006 FLOODED (VLA ), SEALED (VRLA), GEL, AGM TYPE, FLAT PLATE, TUBULAR PLATE: THE WHEN, WHERE, AND WHY. HOW DOES THE END USER DECIDE ON THE BEST SOLUTION? Dr. Wieland Rusch Keith Vassallo Gary

More information

NorthStar Battery (NSB) Telecom Application Manual

NorthStar Battery (NSB) Telecom Application Manual NorthStar Battery (NSB) Telecom Application Manual Contents Silver Star Technology TM... 3 1 Introduction... 3 1.1 The Silver Star Technology TM and Semi-Stable Mains... 3 1.2 Discharge Rate... 3 2 Charge...

More information

Automatic DC Power Supply/Battery Charger

Automatic DC Power Supply/Battery Charger Automatic DC Power Supply/Battery Charger PATENTED U.S. 9,270,140; 9,385,556; 9,413,186; 9,509,164 NEW in 2015: Field selectable AC input voltage in high-powered units Automatic battery commissioning mode

More information

POWER-plus. Ni-Cd XHP. Capacity: 10 Ah to 250 Ah

POWER-plus. Ni-Cd XHP. Capacity: 10 Ah to 250 Ah Ni-Cd XHP Capacity: 10 Ah to 250 Ah XHP Range Low maintenance, high performance Ni-Cd batteries Powerful assurance for critical applications Depend upon XHP series where vital UPS, engine starting and

More information

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007 STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007 LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES ICS: 43.040.00 LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES

More information

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell UPS 12-1121 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per APPLICATIONS Data Centers Network Operations Centers Industrial Process Control

More information

Section V DC Nickel Cadmium Alkaline BATTERY

Section V DC Nickel Cadmium Alkaline BATTERY Section - 7 TECHNICAL SPECIFICATION OF 110V DC Nickel Cadmium Alkaline BATTERY TECHNICAL SPECIFICATIONS & REQUIREMENTS OF 110V DC Nickel Cadmium Alkaline Battery 7. 1 GENERAL This section of the document

More information

Open-circuit voltages (OCV) of various type cells:

Open-circuit voltages (OCV) of various type cells: Open-circuit voltages (OCV) of various type cells: Re-Chargeable cells: Lead Acid: 2.10V/cell to 1.95 NiMH and NiCd: 1.20 V/cell Li Ion: 3.60 V/cell Non-re-chargeable (primary) cells: Alkaline: 1.50 V/cell

More information

AgriCUltUre ConstrUCtion equipment generators emergency vehicles CleAning

AgriCUltUre ConstrUCtion equipment generators emergency vehicles CleAning agriculture construction EQUIPMENT generators emergency vehicles CLEANING OPTIMA YELLOWTOP DUAL PURPOSE BATTERY (STARTING & SEMI TRACTION) Up to 3 times quicker recharging Over 15 times more vibration

More information

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS MIL-STD-1539 (USAF) 1 AUGUST 1973 MILITARY STANDARD ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS FSC 1810 Electrical Power, Direct Current, Space Vehicle Design Requirements MIL-STD-1539

More information

NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems

NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems Version:- 2.1 Date of Issue:- August 2016 Page 1 of 28 NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems 1. Purpose The purpose of this document is to detail the technical

More information

Installation Instructions

Installation Instructions Installation Instructions AQU243-8C1R -8F8R -8C8R 24VDC/3.3Amp Supervised (AC & Battery) Power Supply/Charger Module, 85-264vac, 14 x 9 x 3.5" Enclosure, UL294, UL603 & UL1481 Listed AQU243 with one PDB-8C1R

More information

Battery Technology for Data Centers and Network Rooms: Site Planning

Battery Technology for Data Centers and Network Rooms: Site Planning Battery Technology for Data Centers and Network Rooms: Site Planning White Paper # 33 Executive Summary The site requirements and costs for protecting information technology and network environments are

More information

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems Technical Note Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems Automation Products Introduction As more and more remote monitoring is installed on sites ranging

More information

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical

More information

EV Traction Dry Cell Battery Technology

EV Traction Dry Cell Battery Technology EV Traction Dry Cell Battery Technology High performance comes standard Superior performance. Engineered to last. RESPONSIBLE Solution Non-gassing and non-spillable Maintenance-free Approved for environmentally

More information

EV Traction Dry Cell Battery Technology

EV Traction Dry Cell Battery Technology EV Traction Dry Cell Battery Technology High performance comes standard Superior performance. Engineered to last. RESPONSIBLE Solution Non-gassing and non-spillable Maintenance-free Approved for environmentally

More information

Tubular Gel (OPzV) Batteries. Stationary & Renewable Energy Applications

Tubular Gel (OPzV) Batteries. Stationary & Renewable Energy Applications Tubular Gel (OPzV) Batteries Stationary & Renewable Energy Applications BATTERIES SOLAR PV WIND GENSET Overview Valve Regulated Tubular Gel Batteries for Stationary & RES Applications Discover RE Tubular

More information

EU RO Mutual Recognition Technical Requirements

EU RO Mutual Recognition Technical Requirements 1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.

More information

Tubular Flooded (OPzS) Batteries

Tubular Flooded (OPzS) Batteries Tubular Flooded (OPzS) atteries Stationary & Renewable Energy pplications TTERIES SOLR PV WIND GENSET Overview Vented Tubular Plate atteries for Stationary & RES pplications Discover RE Tubular Flooded

More information

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System 2004 Specifications CSJ 1068-04-126, 0197-02-108 SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System 1. Description. This work shall consist of furnishing and installing an integrated solar Panel

More information

Installation, Maintenance and Warranty Flat Plate Battery

Installation, Maintenance and Warranty Flat Plate Battery Installation, Maintenance and Warranty Flat Plate Battery Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or

More information

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations 1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope

More information

Industrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«

Industrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems« Industrial Batteries / Network Power Classic Solar»Powerful energy storage for renewable energy systems« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

Verification/Report Number(s): HEARTWAY MEDICAL PRODUCTS Co., Ltd. Applicant Name/Address:

Verification/Report Number(s): HEARTWAY MEDICAL PRODUCTS Co., Ltd. Applicant Name/Address: Test Verification Of Conformity On the basis of the tests undertaken, the sample(s) of the below product have been found to comply with the essential requirements of the referenced specifications at the

More information

MHR VRLA batteries are manufactured in compliance with TL, NEBS, GR, SR, IEC, BS, UL, ISO, OSHAS and CE quality and performance standards.

MHR VRLA batteries are manufactured in compliance with TL, NEBS, GR, SR, IEC, BS, UL, ISO, OSHAS and CE quality and performance standards. APPLICATIONS UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEMS COMMUNICATIONS DATA CENTERS ALTERNATIVE ENERGY The MHR Modular High Rate Valve Regulated Lead Acid batteries feature the latest advancement in plate

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

TORKEL 840/860. Battery Load Units TORKEL 840/860

TORKEL 840/860. Battery Load Units TORKEL 840/860 TORKEL 840/860 Battery Load Units Batteries in power plants and transformer substations must provide the equipment they serve with standby power in the event of a power failure. Unfortunately, however,

More information

Baintech PowerTop. User Operation Manual. This manual must be read in its entirety before operating the PowerTop and retained for future reference.

Baintech PowerTop. User Operation Manual. This manual must be read in its entirety before operating the PowerTop and retained for future reference. Baintech PowerTop User Operation Manual This manual must be read in its entirety before operating the PowerTop and retained for future reference. Baintech PowerTop User Operation Manual V9 1 Contents Contents...

More information

6 & 12 Volt Monobloc. Haze Battery Company Ltd

6 & 12 Volt Monobloc. Haze Battery Company Ltd 6 & 12 Volt Monobloc Haze Battery Company Ltd The Haze HZB - AGM range covers Ah capacities from 18Ah to 230Ah (C10) with dimensions suitable for racking systems for maximum space utilisation. Specially

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Valve Regulated Lead Acid Batteries used in Stationary Applications

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Valve Regulated Lead Acid Batteries used in Stationary Applications INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS For Valve Regulated Lead Acid Batteries used in Stationary Applications Commissioning by:... Date:... Number of cells/blocks:... Model #:... SAFETY PRECAUTIONS

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Product and Sales Enquiries EN-0b Within Australia tel 00 fax 00 New Zealand tel 00 fax 00 Head Office Enquiries - Cobalt St, Carole Pk, Qld 00. PO Box, Goodna 00 tel 00 fax 00 Installation & Maintenance

More information

CALL FOR A QUOTE (877)

CALL FOR A QUOTE (877) LiFePO4 Energy Storage Systems Overview POWERSYNC Lithium Iron Phosphate (LiFePO4) Energy Storage Systems (ESS) are designed for residential, commercial, or industrial scale projects where long lasting,

More information

1. Production Features

1. Production Features 1. Production Features LEOCH Battery adopt unique plate grid alloy formula with a high corrosion resistance and the active material formula,while the use of advanced production technology and the special

More information

Are Your UPS System Batteries Really Ready to Load Test?

Are Your UPS System Batteries Really Ready to Load Test? Are Your UPS System Batteries Really Ready to Load Test? In a critical power application, stationary batteries should be properly installed, inspected, commissioned and tested before being placed into

More information

MORE CONTROLLERS ON A BATTERY BATTERY CHARGE LIMITATIONS

MORE CONTROLLERS ON A BATTERY BATTERY CHARGE LIMITATIONS Avigliana - 8 March 2015 TECHNICAL REPORT MORE CONTROLLERS ON A BATTERY BATTERY CHARGE LIMITATIONS Photovoltaic panels can be wired in series or in parallel. In the first case only panels with the same

More information

User's Guide of BST-360 Battery System Tester. BST-360 Battery System Tester User's Guide 1 / 15

User's Guide of BST-360 Battery System Tester. BST-360 Battery System Tester User's Guide 1 / 15 BST-360 Battery System Tester User's Guide 1 / 15 Table of Contents Table of Contents Chapter 1 Product Summary 3 1.1 Product Profile 3 1.2 Product Function 3 1.3 Technical Parameters 4 1.4 Working Environment

More information

INSTRUCTION MANUAL CAUTION

INSTRUCTION MANUAL CAUTION FILE: IM_091-128-12E-40-115 Rev B., 2-16-2006 INSTRUCTION MANUAL AUTO CHARGE ODY q AUTOMATIC BATTERY CHARGER MODEL #091-128-12E-40-115 for ODYSSEY AGM BATTERIES CAUTION This charger is calibrated to the

More information

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,

More information

Battery Management Innovation. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

Battery Management Innovation. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL Battery Management Innovation For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL ! CAUTION Because of the possibility of personal injury, always use extreme caution

More information

There are two leading power conversion technologies used in formation charging rectifiers

There are two leading power conversion technologies used in formation charging rectifiers 1 2 3 A goal of any progressive battery manufacturer is to shorten formation time while reducing energy consumed during the process. The requirement to increase capacity while reducing operating expense

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER INSTRUCTION MANUAL FILE: IM_091-120-XX-XX-(XXX)(XX)_revA.P65 REV: A REVISED BY: PSS DATE: 07-19-13 AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER R MODEL #091-120-XX-XX-(XXX)(XX) 3 YEAR WARRANTY 170 Cherry

More information

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017 MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017 REVIEWABLE OPERATING INCIDENT REPORT UNDER THE NATIONAL ELECTRICITY RULES Published: 3 August 2017 INCIDENT CLASSIFICATIONS

More information

Specification of Soneil Battery Charger

Specification of Soneil Battery Charger SONEIL INTERNATIONAL LIMITED 6033 Shawson Dr., Unit 29, Mississauga, Ontario, Canada L5T 1H8 Ph.: (905) 565-0360 Fax: (905) 565-0352 http://www.soneil.com Revision No.: R01 06/13/2008 Specification of

More information

- Optional Audio warning when discharge test is complete or tester malfunction.

- Optional Audio warning when discharge test is complete or tester malfunction. INTRODUCTION Congratulations on acquiring your new LT360 battery discharge tester. The LT360 battery discharge tester has been designed to provide the operator with accurate battery discharge testing and

More information

SOLAR POWER SYSTEMS MANUAL

SOLAR POWER SYSTEMS MANUAL SOLAR POWER SYSTEMS MANUAL Gordon L.Gibby KX4Z Version 1.00 Friday June 22 2018 Two solar power systems have been constructed as follows: System Solar Panel & Connections 1 250 Watt 30-volt nominal solar

More information

Specification Approval Sheet

Specification Approval Sheet Specification Approval Sheet Name: Model: SPEC: Approved By Checkup Make Signature Date Customer Confirmation Company Name: Stamp:, U.S.A. Tel: 510.687.0388 Fax: 510.687-0328 www.tenergybattery.com TABLE

More information

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service POWER FOR TOMORROW TODAY The Eternity Technologies range is built using only the highest quality and most efficient production processes at our state-of-the-art manufacturing centre in the UAE. It is this

More information

Components for your PV Solar Electric System

Components for your PV Solar Electric System Components for your PV Solar Electric System Here is a brief description of the major components of a Solar Electric System. The components vary depending on whether batteries will be used in your system.

More information

Stationary Batteries: Why they fail and what can be done to prolong battery life

Stationary Batteries: Why they fail and what can be done to prolong battery life Stationary Batteries: Why they fail and what can be done to prolong battery life J. Allen Byrne Tech. Support & Services Mgr. Interstate PowerCare A Division of Interstate Batteries April 13, 2016 Schaumburg,

More information

SPECIFICATIONS OF Ni-Cd BATTERY BANK

SPECIFICATIONS OF Ni-Cd BATTERY BANK SPECIFICATIONS OF Ni-Cd BATTERY BANK ANNEXURE-Z Supply, Installation and commissioning of Ni-cd battery bank for high rate of discharge type KPH 125V 210 AH consisting of 103 number of cells. Detail technical

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information