HIGH TEMPERATURE SUSTAINED LOAD TEST ON A COMPRESSION DEAD-END CONNECTOR INSTALLED ON 1020 KCMIL, ACCC/TW DRAKE CONDUCTOR

Size: px
Start display at page:

Download "HIGH TEMPERATURE SUSTAINED LOAD TEST ON A COMPRESSION DEAD-END CONNECTOR INSTALLED ON 1020 KCMIL, ACCC/TW DRAKE CONDUCTOR"

Transcription

1 To: AFL 104 Hidden Lake Circle Duncan, SC USA 4 HIGH TEMPERATURE SUSTAINED LOAD TEST ON A COMPRESSION DEAD-END CONNECTOR INSTALLED ON 1020 KCMIL, ACCC/TW DRAKE CONDUCTOR Kinectrics North America Inc. Report No.: July 30, 2015 Dmitry Ladin Transmission and Distribution Technologies Business A High Temperature (200 C maximum conductor temperature) Sustained Load Test was performed on one (1) compression dead-end connector for AFL. An ambient temperature Maximum Load Test was performed on the dead-end connector after completion of the High Temperature Sustained Load Test. The test connector was installed on 1020 kcmil, Aluminum Conductor, Composite Core, Trapezoidal Wire, (ACCC/TW), Drake conductor. The catalogue number stamped on the tested connector is AFL B11381-A. The tested dead-end connector is rated as Class AA, Extra Heavy Duty connector. AFL provided the test sample in fully assembled condition for testing. Kinectrics received the test sample in good condition on January 22, The tests were performed in general accordance with ANSI C , American National Standard for Electric Connectors Connectors for Use Between Aluminum-to- Aluminum and Aluminum-to-Copper Conductors Designed for Normal Operation at or Below 93 C and Copper-to-Copper Conductors Designed for Normal Operation at or Below 100 C, Clauses and The tested dead-end compression connector, as tested, met the High Temperature Sustained Load Test acceptance criteria as specified in ANSI C The tests were performed under Kinectrics ISO Quality Management Program. A copy of Kinectrics ISO Registration Certificate is included in Appendix A. The test was carried out from March 10, 2015 to March 18, 2015 by Kinectrics North America Inc. (KNAI) personnel at 800 Kipling Avenue, Unit 2, Toronto, Ontario, M8Z 5G5, Canada, under AFL Purchase Order # , dated December 3, PRIVATE INFORMATION Contents of this report shall not be disclosed without authority of the client. Kinectrics North America Inc., 800 Kipling Avenue, Unit 2, Toronto, Ontario M8Z 5G5.

2 1.0 TEST STANDARD AND OBJECTIVE The High Temperature Sustained Load and Maximum Load Tests were performed in general accordance with ANSI C , American National Standard for Electric Connectors Connectors for Use Between Aluminum-to-Aluminum and Aluminum-to- Copper Conductors Designed for Normal Operation at or Below 93 C and Copper-to- Copper Conductors Designed for Normal Operation at or Below 100 C, Clauses and The tested dead-end connector is rated as Class AA, Extra Heavy Duty connector for ACCC/TW Drake conductor. The objective of the test was to determine long term tensile load carrying capacity, at elevated temperature, of the dead-end connector installed on 1020 kcmil, ACCC/TW Drake conductor. The purpose of this custom designed test is to give a reasonable assurance to the user that the tested connector is meeting ANSI C Sustained Load Test requirements and will perform in a satisfactory manner, provided the connector has been properly selected for the intended application and is installed with the manufacturer s recommendation. 2.0 DESCRIPTION OF TEST COMPONENTS, PREPARATION AND SET-UP Dead-end Connector Assembly The compression dead-end connector was installed by AFL on approximately 13 m length of 1020 kcmil, ACCC/TW Drake conductor. At the opposite (free) end of conductor, Kinectrics personnel terminated conductor using a high temperature epoxy resin deadend. Both the compression dead-end connector and the epoxy resin dead-end mouth were marked with paint at the test start to monitor conductor slippage during the test. The effective conductor length between compression dead-end and epoxy resin dead-end was m, and the exposed conductor length was m. Test Apparatus Test schematic for the High Temperature Sustained Load Test is shown in Figure 1, and the general arrangement used for the High Temperature Sustained Load is shown in Figures 2 through 8. The test span is designated as Golden Span and located in room KB019 of the Main Mechanical Laboratory of Kinectrics. During the initial set-up and preloading steps, the sample was supported along its entire length to keep the sample as straight as possible and to minimize creep during the set-up of the test. A current transformer, shown in Figure 4, was configured to provide the circulating current to increase the temperature of the test conductor. A 600 Volt variable transformer (variac) supplied the current to the power transformer. The motor-driven variac was controlled by a data acquisition system (DAQ) in order to provide the necessary current to increase the temperature in the test loop to the desired test temperature. Also, capacitor banks were connected to the primary side of the power transformer in order to balance the impedance of the test loop. Page 2 of 16

3 Conductor Tension One (1) strain gauge load cell measured tension in the conductor assembly during the test. The signals from the load cell were amplified to provide a 0 to 5 volt signal for the data acquisition system. Tension data was collected and recorded continuously throughout the entire length of the test. Connector and Conductor Temperatures The temperature of the tested compression dead-end connector and conductor was measured at several locations on the assembly using calibrated thermocouples. Conductor thermocouples were located at the center of the span. The thermocouples were positioned in the outer layer of the conductor assembly as seen in Figure 6. The thermocouples were electrically isolated from other instruments to prevent electrical interference in the data acquisition system. Data Acquisition and Control A Labview-based data logging system (DAQ) recorded the measurements from the thermocouples and the load cell. To achieve the target conductor temperature, the circulating current was adjusted by the DAQ using a 600 Volt variac on the primary side of the current transformer. Maximum Load Test Upon completion of 168 hours of the High Temperature Sustained Load Test, the test assembly installed on ACCC Drake Conductor was placed in a 100 kip hydraulicallyactivated horizontal test machine, located on the strong floor of the Main Mechanical Laboratory of Kinectrics, to measure the connector s remaining tensile strength (see Figure 9). Both compression dead-end and epoxy dead-end paint marks were verified to detect conductor slippage during the test. The measuring instruments and equipment used in this test are listed in Appendix B. 3.0 TEST PROCEDURE The test assembly was subjected to a total of 168 hours of constant tensile load at elevated conductor temperature. Initially, the test assembly was pre-tensioned to approximately 824 lb or 2% of the conductor s Ultimate Tensile Strength (UTS) of 41,208 lb. Once the test conductor was loaded to 2% UTS, the heating process was started. Electric current was injected in the conductor to heat it by Joule-effect. The conductor temperature was increased gradually up to 200 C temperature, allowing the temperature to stabilize for a minimum of ten (10) minutes. During the heating, the conductor tension was manually maintained at 2% UTS. Conductor and connector temperatures were recorded continuously. The conductor was then loaded to achieve the target tension of 8,241 lb or 20% of the conductor s UTS in five (5) minutes. Once the target tension was achieved, a servo- Page 3 of 16

4 controlled tensioning system ensured near constant tension for the duration of the test. The rate of loading was kept linear to avoid impacting or overloading of the conductor sample. Conductor tension was also measured and recorded continuously. The conductor then stabilized at a temperature of 200 ± 5 C for the 168 hours test period. After the 168 hour of thermal exposure under tensile load, the A/C transformer was disconnected, and test assembly was allowed to cool down to ambient temperature. The tensile load was dropped as well. Maximum Load Test On completion of the High Temperature Sustained Load Test (i.e. 168 hours), the test assembly was subjected to a Maximum Load Test (i.e. Breaking Load) as per ANSI C , Clause Once the sample was installed in the hydraulically activated horizontal test machine, it was pre-loaded to 824 lb or 2% of the conductor s UTS and dead-end connector and epoxy dead-end mouth paint marks were verified. The load was then increased at a steady rate until the failing load was reached. The steady loading rate for the UTS Test was 8,242 lb/min and was chosen based on achieving 100% UTS in five (5) minutes. 4.0 TEST RESULTS The test sample remained at the specified load and elevated temperature for 168 hours. There was no slippage detected at either dead-end compression connector or the epoxy resin dead-end, and the conductor condition remained unchanged. Figure 7 depicts a typical connector mouth condition after the test. Maximum Load Test The test sample broke at 36,353 lb or 88.2% of the conductor s UTS. The failure occurred off the epoxy dead-end (test setup is shown in Figure 9). Tested compression dead-end condition after the test is shown in Figure 10, and the conductor core appearance after failure is shown in Figure 11. Slippage measurements at the compression dead-end connector were also taken. There was no slippage observed in the tested dead-end connector. 5.0 ACCEPTANCE CRITERIA Following acceptance criteria should be met by all full tension (Class AA) compression connectors in accordance with ANSI C : High Temperature Sustained Load Test The sustained load test is classified as a failure if slippage or breakage of the conductor occurs during the test. Page 4 of 16

5 Maximum Load Test The pullout strength of connector/wire assembly shall be equal or greater than 95% of the conductor s RTS. The RTS of 1020 kcmil, ACCC/TW Drake conductor is 41,208 lb. 6.0 CONCLUSIONS Sustained Load Test The High Temperature Sustained Load performed on AFL compression dead-end connector installed on 1020 kcmil, ACCC/TW Drake conductor met the ANSI Std. C test criteria, as tested. The test assembly maintained the 20% of the conductor s RTS tension at elevated conductor temperature (200 ± 5 C) for 168 hours (7 days) without any slippage. Maximum Load Test In the Maximum Load Test performed on AFL compression dead-end connector installed on 1020 kcmil, ACCC/TW Drake conductor, conductor failed at the epoxy resin dead-end prior to reaching 95% of conductor s RTS. At the maximum load % of the conductor s UTS there was no slippage observed on the AFL dead-end connector. Page 5 of 16

6 Prepared by: D. Ladin Engineer/Scientist Transmission and Distribution Technologies Business P. Adams Senior Technologist Transmission and Distribution Technologies Business Reviewed by: P. Fong Lead Technologist Transmission and Distribution Technologies Business A. Rizzetto Engineer/Scientist Transmission and Distribution Technologies Business Approved by: _ Zsolt Peter, PhD Department Manager Line Asset Management Dept. Transmission and Distribution Technologies Business DL:PA:PF:AR:ZsP DISCLAIMER Kinectrics North America, Inc (KNAI) has taken reasonable steps to ensure that all work performed meets industry standards as set out in Kinectrics Quality Manual, and that, for the intended purpose of this report, is reasonably free of errors, inaccuracies or omissions. KNAI DOES NOT MAKE ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, WITH RESPECT TO THE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE OF ANY INFORMATION CONTAINED IN THIS REPORT OR THE RESPECTIVE WORKS OR SERVICES SUPPLIED OR PERFORMED BY KNAI. KNAI does not accept any liability for any damages, either directly, consequentially or otherwise resulting from the use of this report. Kinectrics North America Inc., Page 6 of 16

7 Figure 1 High Temperature Sustained Load Test Schematic Figure 2 Typical High Temperature Sustained Load Test Set-Up, Span View Page 7 of 16

8 Figure 3 High Temperature Sustained Load Test Set-Up, Cantilever Weight Arm System View Capacitor Bank Current Transformer 600 V Variac Figure 4 AC Current Transformer and Variable Transformer Page 8 of 16

9 Figure 5 Load Cell Connected to Insulator Figure 6 Thermocouple Installed in Outer Conductor Layer Page 9 of 16

10 Figure 7 Mouth of Connector Marked with Orange Paint to Monitor Slippage Figure 8 Mouth of Epoxy Resin Dead-end Marked with Orange Paint to Monitor Slippage Page 10 of 16

11 Figure 9 Test Sample Located in Hydraulically Activated Horizontal Test Machine for Maximum Load Test Figure 10 Test Connector after Maximum Load Test Page 11 of 16

12 Figure 11 Conductor Failure at Epoxy Resin Dead-end after Maximum Load Test Page 12 of 16

13 APPENDIX A KINECTRICS ISO QUALITY MANAGEMENT SYSTEM REGISTRATION CERTIFICATE Page 13 of 16

14 Page 14 of 16

15 ISO-9001 Form: QF11-1 Rev 0, APPENDIX B INSTRUMENT SHEET (Ref. HT SUSTAINED LOAD TEST ON ACCC/TW DRAKE DEAD-END CONNECTOR) Test Description: High Temperature Sustained Load Test on ACCC/TW Drake Dead-end Connector Test Start Date: March 10, 2015 Project Number: K Test Finish Date: March 18, 2015 TEST DESCRIPTION EQUIPMENT DESCRIPTION MAKE MODEL ASSET # or SERIAL # ACCURACY CLAIMED CALIBRATION DATE CALIBRATION DUE DATE TEST USE Data Logger Agilent 34970A KIN ±1% of Reading May 2, 2014 May 2, 2015 Data Acquisition Page 15 of 16 High Temperature Sustained Load Test Maximum Load Test Load Cell Conditioner Aries Daytronics TRC (10,000 kgf) # Thermocouple Omega 5TC GG J KIN Current Transformer (CT) Current Transducer Measuring Tape A/D Datalogger Load Cell (MTS) 100 KIP Conditioner Flex Core Ratio 5000 to 5 A ±1% of Reading < 0.1% of Reading April 1, 2014 April 1, 2015 September 16, 2014 September 16, 2015 KIN ±0.25% of FS May 29, 2014 May 29, 2016 Flex Core ACT-005CX5 KIN ±0.5% of FS December 8, 2014 December 8, 2015 Mastercraft KIN National Instruments Lebow MTS PCI (100,000 lbs) DC Channel: S2-J2A KIN I KIN KIN < 0.1% of Reading ±0.1% of Reading ±1% of Reading April 30, 2014 April 30, 2015 Conductor Tension Temperature Current Measurements Current Measurements Conductor Length January 28, 2015 January 28, 2016 Data Acquisition September 25, 2014 September 25, 2016 Breaking Load

16 DISTRIBUTION Mr. Ben Freeman (2) AFL 104 Hidden Lake Circle Duncan, SC USA Mr. Dmitry Ladin (1) Kinectrics North America Inc., Unit Kipling Ave, KB 223 Toronto, Ontario, M8Z 5G5 Canada Page 16 of 16

Kinectrics North America Inc. Report No.: K RC-0002-R00. October 2, Zsolt Peter Transmission and Distribution Technologies Business

Kinectrics North America Inc. Report No.: K RC-0002-R00. October 2, Zsolt Peter Transmission and Distribution Technologies Business To: CTC Global 2026 McGaw Avenue Irvine, CA 92614, USA THERMO-MECHANICAL CYCLE TEST ON 540 mm 2 ACCC/TW CONDUCTOR Kinectrics North America Inc. Report No.: K-419506-RC-0002-R00 October 2, 2013 Zsolt Peter

More information

Conductor Strength Tests on ACCR 1622TW T13 Pecos Conductor

Conductor Strength Tests on ACCR 1622TW T13 Pecos Conductor Conductor Strength Tests on ACCR 1622TW T13 Pecos Conductor 3M HCC Testing Laboratory August 5, 2011 Phu Trac Sr. Quality Engineer: Phu Trac Technical Manager: Dr. Herve Deve Lead Development Specialist:

More information

Composite Conductor 267-T16 ACCR. Deadend Strength Tests for 267-T16 ACCR

Composite Conductor 267-T16 ACCR. Deadend Strength Tests for 267-T16 ACCR Composite Conductor 267-T16 ACCR Deadend Strength Tests for 267-T16 ACCR Principal Investigator: Dr. Colin McCullough Reviewed by: Dr. Herve Deve Date of Report: March 24, 2010 Deadend Strength Tests for

More information

3M Brand Composite Conductor Connector Current Cycle Qualification Test for 795 kcmil Compression Connectors

3M Brand Composite Conductor Connector Current Cycle Qualification Test for 795 kcmil Compression Connectors 3M Brand Composite Conductor Connector Current Cycle Qualification Test for 7 kcmil Compression Connectors 3M Company Purchase Orders 0000797063 and 0000866974 NEETRAC Project Number: 03-071 September,

More information

477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength

477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength 3M 477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength Principal Investigator: Dr. Kamal Amin Reviewed by: Dr. Colin McCullough Date of Report: June 1, 2003

More information

477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength

477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength 3M 477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength Principal Investigator: Dr. Kamal Amin Reviewed by: Dr. Colin McCullough Date of Report: June 1, 2003

More information

TEMPERATURE RISE TESTS

TEMPERATURE RISE TESTS CP No.: CP0511 Rev. 01 Page: 1 of 6 CERTIFIED TEST REPORT TEMPERATURE RISE TESTS Type CMU Power Fuses REV. 01 DATE: August 12, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems, Inc. CP No.:

More information

Impact, Torsion, and Crush Tests for 477 kcmil and 795 kcmil 3M Brand Composite Conductor. 3M Company Purchase Order

Impact, Torsion, and Crush Tests for 477 kcmil and 795 kcmil 3M Brand Composite Conductor. 3M Company Purchase Order Impact, Torsion, and Crush Tests for 477 kcmil and 795 kcmil 3M Brand Composite Conductor 3M Company Purchase Order 0000620410 NEETRAC Project Number: 02-229 October, 2002 A Center of The Georgia Institute

More information

How Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the Smart Grid. D.C. BRYANT 1 CTC Global Corporation United States

How Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the Smart Grid. D.C. BRYANT 1 CTC Global Corporation United States 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium How Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the

More information

KM26z 20N; 50N; 100N, 200N, 500N, 1kN, 2kN, 5kN

KM26z 20N; 50N; 100N, 200N, 500N, 1kN, 2kN, 5kN KM26z 20N; 50N; 100N, 200N, 500N, 1kN, 2kN, Description The load cell KM26z is a membrane-type force sensor with small dimensions. It is suitable for measuring compressive and tensile forces. For force

More information

USER MANUAL RHF SERIES

USER MANUAL RHF SERIES Hukseflux Thermal Sensors USER MANUAL RHF SERIES Ring heat flux sensors Copyright by Hukseflux manual v1824 www.hukseflux.com info@hukseflux.com Warning statements Follow the installation instructions

More information

Photograph 1, Current feed to connector test loop

Photograph 1, Current feed to connector test loop Photograph 1, Current feed to connector test loop Photograph 2, control conductor and instrument leads outside test chamber Page 3 of 6 Photograph 3 Salt Fog Chamber with Connector Loop Photograph 4, Connector

More information

User s Guide. TQ513 Series Rotating Torque Sensors Shaft-to-Shaft Configuration. Shop online at omega.com

User s Guide. TQ513 Series Rotating Torque Sensors Shaft-to-Shaft Configuration. Shop online at omega.com TM User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info NORWALK, CT TQ513 Series Rotating Torque Sensors Shaft-to-Shaft Configuration omega.com

More information

Displacement Sensor. Model 8739, 8740, 8741

Displacement Sensor. Model 8739, 8740, 8741 w Technical Product Information Displacement Sensor 1. Introduction... 2 2. Preparations for use... 2 2.1 Unpacking... 2 2.2 Grounding and potential connection... 2 2.3 Storage... 2 3. Principle of operation...

More information

3. DESCRIPTION OF SHAKING TABLE SYSTEM COMPONENTS

3. DESCRIPTION OF SHAKING TABLE SYSTEM COMPONENTS 17 3. DESCRIPTION OF SHAKING TABLE SYSTEM COMPONENTS 3.1. INTRODUCTION The earthquake simulator is a system that consists of several components which must be designed to effectively work together. Each

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

User s Guide CDCE-90-X SERIES. Conductivity Sensors. Shop online at omega.com SM

User s Guide CDCE-90-X SERIES. Conductivity Sensors. Shop online at omega.com SM User s Guide Shop online at omega.com SM e-mail: info@omega.com For latest product manuals: www.omegamanual.info CDCE-90-X SERIES Conductivity Sensors omega.com info@omega.com U.S.A. Headquarters: Servicing

More information

User s Guide FP-5060 SERIES. Micro-Flow Sensors. Shop online at omega.com SM For latest product manuals:

User s Guide FP-5060 SERIES. Micro-Flow Sensors. Shop online at omega.com SM   For latest product manuals: User s Guide Shop online at omega.com SM e-mail: info@omega.com For latest product manuals: www.omegamanual.info FP-5060 SERIES Micro-Flow Sensors omega.com info@omega.com U.S.A. Headquarters: Servicing

More information

3M Mechanical Shearbolt Connectors, QCI Series

3M Mechanical Shearbolt Connectors, QCI Series M Mechanical Shearbolt Connectors, QCI Series Data Sheet November 2011 Description Connector Contents M Mechanical Shearbolt Connectors, QCI Series are designed to cover a wide range of conductor sizes

More information

PRG 350 Series Stainless Steel Regulators

PRG 350 Series Stainless Steel Regulators PRG 350 Series Stainless Steel Regulators omega.com info@omega.com U.S.A. Headquarters: Servicing North America: Omega Engineering, Inc. Toll-Free: 1-800-826-6342 (USA & Canada only) Customer Service:

More information

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING January 009 I4-403C A1800 APHA Meter Installation Instructions General This leaflet contains general installation instructions for 4-wire and 3-wire applications of the A1800 APHA meters. All meters are

More information

MPL Technology Hopper Applied Top of Rail Lubrication Test

MPL Technology Hopper Applied Top of Rail Lubrication Test MPL Technology Hopper Applied Top of Rail Lubrication Test Letter Report No. P-12-038 Prepared for MPL Technology, Inc. by Scott Gage and Steve Luna Transportation Technology Center, Inc. a subsidiary

More information

CREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System

CREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System Architectural Testing CREEP PERFORMANCE TEST REPORT Rendered to: TREX COMPANY LLC Seclusions Composite Privacy Fence System TYPE: Composite Fence System Report No.: Report Date: Expiration Date: 130 Derry

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems.

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems. TEST REPORT Ceram Reference: 121557 (QT21489/2/SL)/Ref: 1.0A Project Title: Tensile and Frictional Tests on the Fast Fit BeamClamp Systems Client: Kee Safety Limited For The Attention of: Mr Phil Higgs

More information

Volume-III : Section-I 370 Technical Specifications

Volume-III : Section-I 370 Technical Specifications Volume-III : Section-I 370 TECHNICAL SPECIFICATION-PIERCING INSULATOR 5.1 Insulation Piercing Connectors (IPC) 5.1.1 Insulation Piercing Connectors (IPC) are used for making Tee/Tap-off/Service connectors

More information

Determination of Spring Modulus for Several Types of Elastomeric Materials (O-rings) and Establishment of an Open Database For Seals*

Determination of Spring Modulus for Several Types of Elastomeric Materials (O-rings) and Establishment of an Open Database For Seals* Determination of Spring Modulus for Several Types of Elastomeric Materials (O-rings) and Establishment of an Open Database For Seals* W. M. McMurtry and G. F. Hohnstreiter Sandia National Laboratories,

More information

600 Amp Surge Arrester

600 Amp Surge Arrester R&D Center 497 Schooley s Mountain Road Hackettstown, NJ 07840-3906 Tele: 908-852-1122 Fax: 908-813-2091 TEST REPORT NUMBER: 379-17-12164 DATE: 4-3-2012 REPORT OF TEST ON 600 Amp Surge Arrester Statements

More information

INSTALLATION, CALIBRATION & TROUBLESHOOTING MANUAL

INSTALLATION, CALIBRATION & TROUBLESHOOTING MANUAL INSTALLATION, CALIBRATION & TROUBLESHOOTING MANUAL Model 7200 Transducers GP:50 2770 Long Road, Grand Island, NY 14072 Tel: 716-773-9300 Fax: 716-773-5019 Email: sales@gp50.com Website: http://www.gp50.com

More information

gskin Instruction Manual gskin Heat Flux Sensors for greenteg AG Technoparkstrasse 1 greenteg.com

gskin Instruction Manual gskin Heat Flux Sensors for greenteg AG Technoparkstrasse 1 greenteg.com gskin Instruction Manual for gskin Heat Flux Sensors 2 / 16 gskin Heat Flux Sensors: Instruction Manual CONTENT 1. SHORT USER GUIDE... 4 2. gskin HEAT FLUX SENSOR INTRODUCTION... 5 3. FUNCTIONALITY TEST...

More information

TECHNICAL BRIEF OKLAHOMA GAS & ELECTRIC (OG&E) FIVE TRIBES PECAN CREEK 161 KV LINE

TECHNICAL BRIEF OKLAHOMA GAS & ELECTRIC (OG&E) FIVE TRIBES PECAN CREEK 161 KV LINE Company: Oklahoma Gas & Electric (OG&E) is a regulated electric utility serving more than 800,000 retail customers in Oklahoma and western Arkansas, and a number of wholesale customers throughout the region.

More information

Low voltage bushings for pad-mounted distribution transformers Technical information guide

Low voltage bushings for pad-mounted distribution transformers Technical information guide Transformer components Low voltage bushings for pad-mounted distribution transformers Technical information guide ABB low voltage bushings terminate a transformer s internal low voltage leads at the tank

More information

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan XXXXX Kokish River Hydroelectric Project Interconnection Facilities Study and Project Plan March 16, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All

More information

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable 3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable Data Sheet September 2010 Description 3M Cold Shrink 3-Conductor

More information

MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, CMOS, ANALOG SWITCH WITH DRIVER, MONOLITHIC SILICON

MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, CMOS, ANALOG SWITCH WITH DRIVER, MONOLITHIC SILICON INCH-POUND 4 February 2004 SUPERSEDING MIL-M-38510/116 16 April 1980 MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, CMOS, ANALOG SWITCH WITH DRIVER, MONOLITHIC SILICON This specification is approved for

More information

Contents. Pressure measurement technology Pressure calibrators 18 Exercises 19-20

Contents. Pressure measurement technology Pressure calibrators 18 Exercises 19-20 1 Pressure Contents Topics: Slide No: Pressure measurement technology 03-17 Pressure calibrators 18 Exercises 19-20 2 Pressure Gauges Barometer Used to measure Barometric Pressure Reference is 0 psia,

More information

Mountable with O-ring seal Urea level ±0.5% Accuracy Urea pressure ±2.0 Total Error Band Air Brakes Corrosive fluid measurement for E&V applications

Mountable with O-ring seal Urea level ±0.5% Accuracy Urea pressure ±2.0 Total Error Band Air Brakes Corrosive fluid measurement for E&V applications Mountable with O-ring seal Stainless Steel wetted surfaces Amplified ASIC calibrated Absolute, sealed gage Cable option Analog output DESCRIPTION The U86B is a small profile, media compatible, piezoresistive

More information

KD45 ±20N. Description

KD45 ±20N. Description KD45 ±20N The force sensor KD45 has the geometry of a miniature load cell. It is fastened on one side using the through holes ø3.2. There is a thread M3 for force transmission. Force transmission is displaced

More information

MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS

MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MM series proportional control valves utilize ProportionAir's unique closed loop control technology for superior control

More information

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH Contego Latex Fire Barrier Intumescent (Also marketed in Canada by Pyrologistics,

More information

SPEC No.: ZP REVISION: 1.1 ZP ELECTRON CO.,INC. Designer. Division. Approver

SPEC No.: ZP REVISION: 1.1 ZP ELECTRON CO.,INC. Designer. Division. Approver TECHNICAL SPECIFICATION FOR Optical Fiber Overhead Ground Wire (OPGW) Designer Approver SPEC No.: ZP10-15389 REVISION: 1.1 Technical Supporter ZP Int ternational Division Chief Technical Engineer ZP Int

More information

Wind Turbine Generator System Safety and Function Test Report. Bergey Excel-S with Gridtek-10 inverter

Wind Turbine Generator System Safety and Function Test Report. Bergey Excel-S with Gridtek-10 inverter May 2003 NREL/EL-500-33963 Wind Turbine Generator System Safety and Function Test Report for the Bergey Excel-S with Gridtek-10 inverter by National Wind Technology Center National Renewable Energy Laboratory

More information

R E P O R T N U M B E R

R E P O R T N U M B E R R E P O R T N U M B E R 72128540 PREPARED FOR DURGIN AND CROWELL LUMBER CO. 231 FISCHER CORNER RD. NEW LONDON, NH 03257 ATTENTION JON BAKER PO# 061707 REPORT DATE JUNE 27, 2017 TÜV SÜD America, Inc. 1755

More information

Bonstrand PSX L3, PSX L3C, PSX JF and PSX JFC Polysiloxane-phenolic Fire-resistant Fiberglass Pipe and Fittings

Bonstrand PSX L3, PSX L3C, PSX JF and PSX JFC Polysiloxane-phenolic Fire-resistant Fiberglass Pipe and Fittings Bonstrand PSX L3, PSX L3C, PSX JF and PSX JFC Polysiloxane-phenolic Fire-resistant Fiberglass Pipe and Fittings For offshore platforms, marine and onshore service Description Bondstrand PSX JF and PSX

More information

Spring-Loaded MgO Thermocouple/ Thermowell Assemblies with Connection Heads (GP04, XP04, XP06)

Spring-Loaded MgO Thermocouple/ Thermowell Assemblies with Connection Heads (GP04, XP04, XP06) Operating Instructions Connection Heads (GP04, XP04, XP06) Beyond Measure Speed, Service, Solutions PYROMATION P/N: -006-SL-8HN31 IOIGP04 08/14 Choosing the right temperature sensor for each application

More information

User s Guide PSW12 SERIES. Pressure Switches. Shop online at CERTIFIED DUAL SEAL

User s Guide PSW12 SERIES. Pressure Switches. Shop online at CERTIFIED DUAL SEAL User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info DUAL SEAL CERTIFIED PSW12 SERIES Pressure Switches omega.com info@omega.com Servicing North America:

More information

6.0 SPECIFICATIONS CONTENTS. Calibration. According to factory procedureeeeeeeeeeeeeee Accuracy*

6.0 SPECIFICATIONS CONTENTS. Calibration. According to factory procedureeeeeeeeeeeeeee Accuracy* 6.0 SPECIFICATIONS Calibration According to factory procedureeeeeeeeeeeeeee Accuracy* ± 1% full scale (FS) or ± 1 graduation on scale Scale diameter 41 mm Temperature range 45 to 115 F (10-45 C) Air humidity

More information

a Nexans company Catalogue 2006

a Nexans company Catalogue 2006 a Nexans company Catalogue 2006 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium

More information

1 st Quarter Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations. Prepared for:

1 st Quarter Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations. Prepared for: 1 st Quarter 2018 Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations Prepared for: Prepared by: Mr. Bryce C. Bird Director Division of Air Quality 195 North

More information

HDI inch Choke Position Indicator User s Manual Rev Indicator Gauge Linear Potentiometer

HDI inch Choke Position Indicator User s Manual Rev Indicator Gauge Linear Potentiometer HDI 2522 4-inch Choke Position Indicator User s Manual Rev 2 New 2522 Indicator Gauge Linear Potentiometer w/open Housing 2200 Indicator Gauge Linear Potentiometer TABLE OF CONTENTS HDI 2522 4-inch Indicator

More information

MIL-STD-883G METHOD LEAD INTEGRITY

MIL-STD-883G METHOD LEAD INTEGRITY LEAD INTEGRITY 1. PURPOSE. This method provides various tests for determining the integrity of microelectronic device leads (terminals), welds, and seals. Test condition A provides for straight tensile

More information

PX140 Series. Pressure Transducers

PX140 Series. Pressure Transducers PX140 Series Pressure Transducers INSTRUCTION SHEET M0258/1105 The OMEGA @ PX140 Series pressure transducers are solid state piezoresistive devices ideally suited to applications requiring exact measurement

More information

OMEGA. HH63KF-MV Temperature Transducer

OMEGA. HH63KF-MV Temperature Transducer OMEGA HH63KF-MV Temperature Transducer omega.com TM OMEGAnet SM On-Line Service http://www.omega.com Internet e-mail info@omega.com Servicing North America: USA: ISO 9001 Certified Canada: One Omega Drive,

More information

QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS

QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION The QB4 is a closed loop electronic pressure regulator consisting of two solenoid valves, an internal pressure transducer,

More information

Installation Manual Model 3800/3810

Installation Manual Model 3800/3810 Installation Manual Model 3800/3810 Thermistors & Thermistor Strings No part of this instruction manual may be reproduced, by any means, without the written consent of Geokon, Inc. The information contained

More information

Model Battery Powered Milliohm Meter

Model Battery Powered Milliohm Meter User s Guide Model 380580 Battery Powered Milliohm Meter Introduction Congratulations on your purchase of Extech s Model 380580 Battery Powered Milliohm Meter. This device offers five resistance ranges

More information

Installation Instructions for: Channel Thermocouple Amplifier

Installation Instructions for: Channel Thermocouple Amplifier Installation Instructions for: 30-2204 4 Channel Thermocouple Amplifier WARNING: This installation is not fo r the electrically or mechanically challenged! Use this sensor with EXTREME caution! If you

More information

AIR CORE REACTORS. Phoenix Electric Corporation

AIR CORE REACTORS. Phoenix Electric Corporation AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed

More information

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1

More information

WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests

WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests EMRS Working Practice Public Version: 2.0 Date: 13 October 2017 Table of Contents Change Amendment Record 3 1. Introduction

More information

R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests

R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests Materials Testing Canada Inc. R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests Presented to: 100 South Santa Fe Dr. Denver, Colorado 80223 Attn: Walter Vizcaino, Date Issued 03 March

More information

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions CP-90 CP-90 Electronic Drives General Instructions Application The CP-90 and CP-90 electronic actuator drives process a variable input signal from a controller to provide proportional control of an electric

More information

User s Guide. OM-EL-WiFi-ALERT. Shop online at omega.com. Windows 7, 8, Vista and XP Configuration Software Installation with Operations Guide

User s Guide. OM-EL-WiFi-ALERT. Shop online at omega.com. Windows 7, 8, Vista and XP Configuration Software Installation with Operations Guide User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info Windows 7, 8, Vista and XP Configuration Software Installation with Operations Guide OM-EL-WiFi-ALERT

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Cold Shrink QS T Trifurcating Transition Splice Kit

Cold Shrink QS T Trifurcating Transition Splice Kit Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2

More information

1st Quarter Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations

1st Quarter Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations 1st Quarter 2014 Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations Steven A. Root Digitally signed by Steven A. Root DN: cn=steven A. Root, o=weatherbank,

More information

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

LV Bushing Oil to Air Dry Insulation PTAB-SLV832 LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing General Description The ABB low voltage

More information

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper

More information

INSTRUCTION MANUAL ANCHOR LOAD CELL. Model ANCLO

INSTRUCTION MANUAL ANCHOR LOAD CELL. Model ANCLO INSTRUCTION MANUAL ANCHOR LOAD CELL Model ANCLO Roctest Limited 2009. All rights reserved This product should be installed and operated only by qualified personnel. Its misuse is potentially dangerous.

More information

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings Electro Composites (2008) ULC Tel: (450) 431-2777 Web site: http://www.hubbellpowersystems.com/about/ec/ Revision

More information

HATCHGRIP Installation Instructions/Operation and Maintenance Manual

HATCHGRIP Installation Instructions/Operation and Maintenance Manual HATCHGRIP Installation Instructions/Operation and Maintenance Manual Models: HTG-PCG Contact Information Table of Contents: Safety Precautions... 2 Product Information... 2 Operation... 3 Installation

More information

a Nexans company Catalogue 2012

a Nexans company Catalogue 2012 a Nexans company Catalogue 2012 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated

More information

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist.

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist. DC1333 Testing of aier Plasterboard to AS/NZS 2588 (Electronic copy (PDF format) original signed by author) Author: Neil Lee Materials Scientist Reviewer: ryan Keen Senior Technician Contact: RANZ Limited

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

Ministry of New and Renewable Energy Block-14, CGO Complex, Lodhi Road, New Delhi ,

Ministry of New and Renewable Energy Block-14, CGO Complex, Lodhi Road, New Delhi , MNRE STD 01:2013 MNRE Standard ALL GLASS (GLASS IN GLASS) EVACUATED SOLAR COLLECTOR TUBES Ministry of New and Renewable Energy Block-14, CGO Complex, Lodhi Road, New Delhi-110 003, May 2013 1 MNRE STD

More information

Preliminary Report on Oak Ridge National Laboratory Testing of Drake/ACSS/MA2/E3X

Preliminary Report on Oak Ridge National Laboratory Testing of Drake/ACSS/MA2/E3X ORNL/TM-2015/549 Preliminary Report on Oak Ridge National Laboratory Testing of Drake/ACSS/MA2/E3X Approved for public release. Distribution is unlimited. Philip Irminger Dan King Drew Herron Cody Davis

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

THORNE & DERRICK UK TEL FAX TEL FAX

THORNE & DERRICK UK TEL FAX TEL FAX WWW.CABLEJOINTS.CO.UK THORNE & DERRICK UK TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 WWW.THORNEANDDERRICK.CO.UK a Nexans company Catalogue 2006 EUROMOLD COMPANY PRESENTATION

More information

Spring-Loaded RTD/Thermowell Assemblies with Connection Heads (GP03, XP03, XP05)

Spring-Loaded RTD/Thermowell Assemblies with Connection Heads (GP03, XP03, XP05) Operating Instructions (GP03, XP03, XP05) Beyond Measure Speed, Service, Solutions PYROMATION P/N: -006-SL-8HN31 IOIGP03 07/14 Choosing the right temperature sensor for each application is critical, but

More information

TEST REPORT INTERTEK TESTING SERVICES NA, INC Arlingate Lane Columbus, OH, 43228

TEST REPORT INTERTEK TESTING SERVICES NA, INC Arlingate Lane Columbus, OH, 43228 TEST REPORT INTERTEK TESTING SERVICES NA, INC. 1717 Arlingate Lane Columbus, OH, 43228 PROJECT NO.: G101483861 ISSUE DATE: February 21, 2014 INTERIM REPORT NO. 101483861COL-001B RENDERED TO Client: TSI

More information

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Report Number: G CRT-001A Model Number: Ionflow 50 Surface ARB Number: 1334

Report Number: G CRT-001A Model Number: Ionflow 50 Surface ARB Number: 1334 3933 US Route 11 Cortland, NY 13045 Telephone: +01 607 753 6711 Facsimile: +01 607 756 9891 www.intertek-etlsemko.com Order No. G100222377 28 January 2011 Revised 11 November 2011 Report Number: G100222377CRT-001A

More information

Analysis of Aquawrap for use in Repairing Pipelines with a Dent / Gouge Defect

Analysis of Aquawrap for use in Repairing Pipelines with a Dent / Gouge Defect Analysis of Aquawrap for use in Repairing Pipelines with a Dent / Gouge Defect Procedure and Evaluation of Cycle Test Prepared By Franz Worth, PE April 19, 2005 Air Logistics Corporation F.A.C.S. Group

More information

User s Guide. FLSC790-ND-P Pulse Output Module. omega.com.

User s Guide. FLSC790-ND-P Pulse Output Module. omega.com. User s Guide omega.com http://www.omega.com e-mail: info@omega.com FLSC790-ND-P Pulse Output Module omega.com OMEGAnet On-Line Service http://www.omega.com Internet e-mail info@omega.com Servicing North

More information

User s Guide Shop online at omega.com SM For latest product manuals: CDE-285X SERIES Conductivity Sensors

User s Guide Shop online at omega.com SM   For latest product manuals:   CDE-285X SERIES Conductivity Sensors User s Guide Shop online at omega.com SM e-mail: info@omega.com For latest product manuals: www.omegamanual.info CDE-285X SERIES Conductivity Sensors omega.com info@omega.com U.S.A. Headquarters: Servicing

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

Technical information

Technical information Technical information General Regulations WTL current transformers are special transformers which transfer the primary circuits with prescribed accuracy in smaller secondary circuits. Primary and secondary

More information

Defender 3000 Series Base Instruction Manual

Defender 3000 Series Base Instruction Manual Defender 3000 Series Base Instruction Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Compliance This product conforms to

More information

PSX-240 Enclosed Autotransformer Installation Manual

PSX-240 Enclosed Autotransformer Installation Manual PSX-240 Enclosed Autotransformer Installation Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS! This manual contains important instructions for the OutBack PSX-240 Autotransformer. All of the

More information

2018 North America Course Schedule Hydraulic Technology Pneumatic Technology Mobile Hydraulic Technology

2018 North America Course Schedule Hydraulic Technology Pneumatic Technology Mobile Hydraulic Technology 2018 North America Course Schedule Hydraulic Technology Pneumatic Technology Mobile Hydraulic Technology Motion & Control Training Dept. 6035 Parkland Blvd., Cleveland, OH 44124-4141 Phone: 216.896.2495

More information

D ISM Lubricant Performance Test. Report Packet Version No. Method. Conducted For:

D ISM Lubricant Performance Test. Report Packet Version No. Method. Conducted For: D 7468 - ISM Lubricant Performance Test Report Packet Version No. Method Conducted For: V = I = N = Valid; The reference oil / non-reference oil was evaluated in accordance with the test procedure. Invalid;

More information

PRODUCT EVALUATION REPORT

PRODUCT EVALUATION REPORT SPUTO AND LAMMERT ENGINEERING, LLC STRUCTURAL ENGINEERS 10 SW 1 ST AVENUE, GAINESVILLE, FL 32601 PHONE: 352-378-0448 FAX: 352-373-1331 E-MAIL: sputoandlammert@mindspring.com PRODUCT EVALUATION REPORT MANUFACTURER:

More information

maintains a tolerable engine temperature. Additionally, engines can be liquid cooled if

maintains a tolerable engine temperature. Additionally, engines can be liquid cooled if maintain a lower temperature in sensitive components in the near surroundings of the engine. In rotary engines, the circumferential or axial cooling that occurs naturally from the engine motion maintains

More information

EStrong-series Emergency Stop

EStrong-series Emergency Stop Original instructions EStrong-series Emergency Stop ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand

More information

Installation Instructions Model Geobeam

Installation Instructions Model Geobeam Installation Instructions Model 6700 Geobeam No part of this instruction manual may be reproduced, by any means, without the written consent of Geokon, Inc. The information contained herein is believed

More information

a Nexans company Catalogue 2007

a Nexans company Catalogue 2007 a Nexans company Catalogue 2007 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium

More information

WEB CONTROL PRODUCTS

WEB CONTROL PRODUCTS WEB CONTROL PRODUCTS User Manual MB Tension Sensor (i) FORM NO. L-20127-G-0501 In accordance with Nexen s established policy of constant product improvement, the specifications contained in this manual

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004 U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004 READ THIS MANUAL PRIOR TO INSTALLATION This manual

More information