Holville I.S. Uninterruptible Power Supply Unit (UPS)
|
|
- Dylan Summers
- 6 years ago
- Views:
Transcription
1 Holville I.S. Uninterruptible Power Supply Unit (UPS) The Holville range of intrinsically safe equipment has power outputs specifically designed for use in Group 1 hazardous areas. The range includes Compact Power Supplies (PSU), Uninterruptible Power Supplies (UPS), and DC/DC converters as well as modular data logging equipment. Designed and manufactured in Australia, the Holville range of power supplies is tested to meet the requirements of AS The units carry NSW MDA and ANZEx certification. Figure 1: A 28A.hr Holville Type 3 Ex m e (ia) UPS Features Available with either Ex (ia) or Ex m e (ia) protection Available with either 12.6V 0.97A or 12.6V 2.34A outputs. (The UPS IS power output may also be connected to IS DC to DC converters for a wider range of output parameters) Available with either 110V or 240V AC input Available with 7Amp.Hr, 14A.Hr or 28A.Hr battery capacity Inrush current protection Fully encapsulated IS outputs are floating (i.e. they are galvanically isolated from the mains input, the mains earth and the UPS enclosure). Status indicator LED and Buttons; o IS Power On LED o Mains On LED o Battery Charged LED o Temp/Current Limit LED. (This LED is illuminated when one of the three current limit stages shuts down due to an overload.) o Voltage Regulator Failure LED. (This LED indicates the first Voltage regulator stage has failed) o 3 current limit test buttons (if fitted). Allows the user to test the integrity of each of the 3 current limit stages. Available with an optional timer that switches off all UPS output when mains has not been applied for a specified period of time and a timer reset switch. An optional auxiliary on/off cable to connect a remote on/off switch. The power supplies have a 12 month, return to factory, replacement warranty 1 Figure 2: A 7A.hr Holville Type 3 Ex m e (ia) UPS with armoured SWA cable 1 Some exclusions apply
2 Product Specifications Ex (ia) UPS Ex m e (ia) UPS Certificates ANZEx X, MDA Ex m e ia Installation The Ex (ia) UPS is intended to be installed in a nonhazardous area. The intrinsically safe output may be used in a Group 1 Zone 0 hazardous area. The Ex m e (ia) UPS may be installed in a hazardous area of Group 1 Zone 1. The intrinsically safe output may be used in a Group 1 Zone 0 hazardous area. Conditions of Safe Use The equipment has been assessed to the entity concept and accordingly the electrical parameters given in the output table below must not be exceeded. The mains input voltage shall not exceed 250V. The UPS must not be operated in ambient temperatures > 40 o C. The Ex m e version must not be used in the presence of acetic acid vapours. The Ex m e enclosure must be earthed via the M4 stud fitted to the exterior of the enclosure. The Ex m e mains cable must be terminated in a manner suitable for the hazardous area in which the UPS is installed. It must be protected from damage. IP Rating IP54 Mains Input Factory Configured to 110VAC (max 115V) or 240VAC (max 250VAC). The mains connection is made via a flying lead. Mains fuses The Ex (ia) UPS has 2 replaceable mains fuses. The Ex m e (ia) UPS has its mains fuses encapsulated internally. The unit must be returned to the factory for the fuses to be replaced. Mains Cable A mains flex cable is fitted to this category of UPS. The cable must be selected in accordance with AS1972. Standard options available are Armoured Cable, 1.5mm 2 core + E (provided as standard) Type 2S machine cable,1.5mm 2 core + E ( please specify if required) An Ex e rated cable gland is fitted. The armouring of the Ex m e cable and the braid of the Type2S cable is earthed to the enclosure through the gland. 2m of cable is fitted as standard. A different length can be fitted in the factory if requested. The armoured and Type 2S cable for the Ex me (ia) version cannot be extended after manufacture. IS Outputs A typical Type 3 UPS has 2 IS output cables; the IS power output and the optional IS remote/timer reset cable. Both cables are a blue sheathed, twisted pair. 2m of cable is fitted as standard. Additional length can be fitted if requested.
3 IS Power Outputs The UPS can be configured with a 12.6V 0.97A or 12.6V 2.34A output. Associated I.S. parameters are as below: Model Uo (V) Io (A) Po (W) Co (uf) Lo (mh) 12.6V 2.34A V 0.97A The output voltage, current and power of any model may be reduced to meet the entity parameters of attached equipment. However the Co and Lo parameters associated with the parent model may not be changed. The UPS IS power output may be connected to IS DC to DC converters for a wider range of output parameters. The IS power outputs of the DC to DC converters are individually galvanically isolated from their inputs. IS Remote 0n/Off and Timer Reset Connection Optional Timer The UPS can be optionally factory configured with a timer that switches off all UPS outputs when mains power has not been applied for a specified amount of time. The timer is most often configured to 20 or 40 minutes but may be varied at customer request. If the timer is fitted but not required, the timer wires can be permanently short circuited to disable the timer so that IS power will remain on continuously. Optional Remote On/Off The UPS can be optionally fitted with both an IS power output switch and an auxiliary on/off cable. This cable can be used to connect the UPS to a remotely located on/off switch. For example, if the UPS is contained in an enclosure, this cable can be used to locate an on/off switch outside the enclosure. If the remote on/off cable is fitted but not required the wires may be insulated so they remain open circuit. The intrinsic safety entity concept parameters for the IS Remote Connection (both the Timer Reset and Auxiliary On/Off wire pairs) are: Ui = 18.9V, Ii = 80mA, Ci = 0uF, Li = 0mH Uo = 18.9V, Io = 80mA, Co = 7uF, Lo = 70mH, L/R < 1179uH/W Batteries and Charging The battery pack inside the UPS contains at least one 12V sealed lead-acid battery with a capacity of 7 Amp.Hours. To recharge the battery pack from flat will take approximately 5-6 hours for each battery. The battery charging circuit is connected to the mains transformer in parallel to the IS power output circuit so while mains power is applied to the UPS the IS power output may supply a load even if the battery is flat and being recharged. Weight A 7A.Hr UPS weighs approximately 15kg, a 14A.hr UPS about 25kg and a 28A.Hr UPS 35 kg. Operating Temperatures If the UPS is intended to supply more than 800mA continuously then the base of the UPS should be covered in heatsink compound before being mounted on to its base plate. The operating temperature of the base of the UPS needs to be kept below 40 o C to minimise IS Power Output voltage drop under load.
4 Ordering and Part Specification To order a Type 3 UPS its configuration needs to be specified as follows; Protection Ex (ia) or Ex me (ia) Battery Capacity 7A.hr or 14A.Hr or 28A.Hr Mains Input 110V or 240V Remote Connection Fitted Yes/No Timed Output mins Cable Type Mains Flex [Ex (ia) only] or Armoured Cable or Type 2S cable Cable Length m The following commonly ordered configurations have been allocated part no s for ease of ordering IS Output 12.6V 0.97A 12.6V 2.34A Battery Capacity Remote fitted Timer Holville Part No/Order Ref Ex (ia) Ex me (ia) Ex me (ia) Mains Flex Armoured Cable Type 2S Cable Cable Length 110V 240V 110V 240V 110V 240V 7A.Hr Yes 40min 2m A.hr Yes 40min 11m please specify please specify A.Hr No N/A 2m please specify please specify 28A.Hr No N/A 2m please specify please specify 7A.Hr Yes 40min 2m A.Hr Yes 40min 11m please specify please specify A.Hr No N/A 2m please specify please specify 28A.Hr No N/A 2m please specify please specify
5
6
LABOR ASTER INDUSTRIAL AUTOMATION. Intrinsically safe barrier with separation FIELDBUS TRANSMISSION LINES CONVERTER-SEPARATOR
LOR STER INDUSTRIL UTOMTION Intrinsically safe barrier with separation FIELDUS TRNSMISSION LINES CONVERTER-SEPRTOR type SEx-RS RS/RS, RS/, /RS, /, RS/RS - group I, category M and group II and III, category
More informationLIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX )
LIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX ) Publication# 03revA Table of Contents Publication# 03revA Table Of Contents...
More information707Ex. Users Manual. ma Calibrator
707Ex ma Calibrator Users Manual March 2003 Rev 2 3/03(English) 2003 Fluke Corporation, All rights reserved. Printed in USA All product names are trademarks of their respective companies. Table of Contents
More informationUCS-CHR24V55W. Combined Power Supply & Battery Charger. Data Sheet
Combined Power Supply & Battery Charger Data Sheet INTRODUCTION UCS-CHR24V55W is a combined charger and power supply with dedicated outputs for both charging and power supply. With a large input range
More informationK Series 3 Way Direct Acting Balanced Poppet Solenoid Valve
Ex d Ex m IP5 Series 3 Way Direct Acting Balanced Poppet Solenoid Valve DB2S-M2C \ Ex d IIC with Integral Stainless \ Steel Junction Box. \ Valve. \ Manual Override, Option M2. J77072S-M2 \ Ex m II NASS
More informationEZ-LIGHT K30L and K50L Intrinsically Safe Indicators
For use in hazardous areas with suitable zener barriers or galvanic isolators ATEX and IECEx certifications Fully sealed and rated to IP67/IP69K 1-, 2-, or 3-color models available; 5 available colors
More informationInstallation Instructions
AQU244 & AQU128 Series Installation Instructions Installation Instructions AQU244 24vdc 5A Supervised Power Supply/Charger module AQU128 12vdc 10A Supervised Power Supply/Charger module Both Mounted in
More informationANKERSMID Temperature controller ATC 510/520/525 for wall-mounting. Application
2-3.1 ATC 510/520/525 for wall-mounting Application The ATC 510/5205/525 is a modern microprocessor-based (PID) control device featuring easy handling and a digital display. The clear design of the operator
More informationHGM501 Gen-set Controller USER MANUAL. Smartgen Technology
HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...
More informationInstruction Manual. Q Series 2 Motor Control Modules - OEM
A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230
More information9.6 Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,
E X - C O N T R O L S T A T I O N S Moulded plastic Version for Zone 1 and Zone 21 Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist
More informationPOWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division
POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES GAMATRONIC, A SolarEdge Division 47505 Seabridge Drive, Fremont, CA, 94538 USA Tel: 1-800-277-5496 SalesNA.Gama@solaredge.com www.gamatronicna.com
More informationPOWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division
POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES GAMATRONIC, A SolarEdge Division 47505 Seabridge Drive, Fremont, CA, 94538 USA Tel: 1-800-277-5496 SalesNA.Gama@solaredge.com www.gamatronicna.com
More informationEndress+Hauser Wetzer GmbH+Co. KG Obere Wank Nesselwang Germany. Field Temperature Transmitter itemp, Types TMT82, TMT84 and TMT85
--~---- - ECEx Certificate NTERNATONAL ELECTROTECHNCAL COMMSSON EC Certification Scheme for Explosive Atmospheres for rules and details of the ECEx Scheme visit www.iecex.com ECEx DEK 11.0096 issue No.:O!
More informationFeatures. Description. Table of Contents
Features Very low profile Very high efficiency (typically 90%) Single and dual output versions Input voltages from 24V to 110VDC nominal voltages from 5V to 48VDC -40 C to +71 C operation without de-rating
More informationTBKS/CBKS Stainless Steel Sloping Roof Keyed Terminal Box Zones 1&2, 21&22
Hazardous Area Electrical Equipment TBKS/CBKS Stainless Steel Sloping Roof Keyed Terminal Box Zones 1&2, 21&22 Index Dimension Sheet Catalogue Information Leaflet Web Links TBKS/CBKS Information Page Ask
More informationLS200 Series Instruction Manual
LS200 Series Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage may lead to an electrical shock, damage to the unit
More informationCertificate of Conformity
Australian/New Zealand Certification Scheme for EXPLOSION-PROTECTED ELECTRICAL EQUIPMENT ANZEx Scheme Certificate of Conformity Certificate No.: ANZEx 13.3000 Issue No.: 0 Date of Issue: 31/01/2014 Applicant:
More informationRAE PowerPak User s Guide
RAE PowerPak User s Guide \\\\\ Rev. A July 2009 P/N F03-4001-000 Copyright 2009 RAE Systems, Inc. Ordering Replacement Parts: If you need replacement parts, a list is available online: http://www.raesystems.com
More informationConceptpowerTM Modular kVA
TECHNICAL SPECIFICATIONS ConceptpowerTM Modular 10-15-20-30-40kVA Uninterruptible Supply (UPS) Modular, n+1 redundant, three-phase On-line, Double-Conversion, VFI Classic-Line 10-40kVA Gemini-Line 10-30kVA
More informationPO Box 2484 Rowville Vic 3178
www.solar4rvs.com.au info@solar4rvs.com.au 0488 918 910 PO Box 2484 Rowville Vic 3178 1. Primary Functions and Features The Controller provides three primary functions: 1. The Maximum Power Point Tracking
More informationPOWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting
POWER+ PREMIUM CBS CENTRALIZED Battery System BS-EN-50171 Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS 10KVA-40KVA The systems running
More informationPhoenix Inverter
Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC
More informationAll In one uninterruptible power supply solutions
All In one uninterruptible power supply solutions For the life of your systems with Battery Care concept Integrated Electronic Solution Yet another strong proposition from Adelsystem, result of the continuing
More informationSolenoid coil for control in potentially explosive areas Type BZ
Data sheet Solenoid coil for control in potentially explosive areas Type BZ BZ is a solenoid coil with ATEX / IECEx approval, applicable for zone 1 and 2 Ex environments. The coils are designed to be used
More informationOperating Instructions
Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
More informationPower+ CLASSIC. 20/30 kva, 3x208 Vac
Power+ CLASSIC 20/30 kva, 3x208 Vac with internal batteries Power+ CLASSIC 20/30 kva, 3x208 Vac Power+ is a family of modular, parallel, redundant UPS systems from Gamatronic one of the leading companies
More information24V 3A EN54 Ancillary Power Supply
24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION
More informationD Series Ex d Stainless Steel
2 Way irect Acting Solenoid Valve IIC T4/T6 Series Stainless Steel 2 and 3 Way irect Acting Solenoid Valve IIC T4/T6 2SK-CM [ FEATURES ] Integral terminal box with coil housing. Valve do not require minimum
More informationModels. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery
AC/DC Battery Controller Power Supply TSPC-240UPS Series Compact universal 24 VDC power supply with integrated battery controller module Battery protection for over voltage, deep discharge, short circuit
More informationFor single and double operated actuators. Exhaust air recirculation (3/2 way function)
For single and double operated actuators /-, 5/- and 5/ Directional Control Valves Actuation: Electromagnetic Indirectly controlled soft seal spool valves Connection G /4 or /4 NPT NAMUR interface Exhaust
More informationAUTOMATIC BATTERY CHARGER MODELS SEC A SEC A OWNER S MANUAL
AUTOMATIC BATTERY CHARGER MODELS SEC - 1245A SEC - 2425A OWNER S MANUAL Please read this manual before operating your charger CONTENTS Important safety precautions...2 Description...3 Features...3 Components
More informationPSBSH 2012B. PSBSH 13,8V/2A/7Ah/HERMETIC
PSBSH 2012B v.1.2 PSBSH 13,8V/2A/7Ah/HERMETIC Buffer switch mode power supply unit, EN** Edition: 7 from 02.11.2017 Supercedes the edition: 6 from 08.06.2017 Features: DC 13,8V/2A uninterruptible power
More informationUser Guide. RAE PowerPak
User Guide RAE PowerPak Copyright 2009 Honeywell Analytics. Ordering Replacement Parts: If you need replacement parts please contact Honeywell Analytics Representative. Contents 1 Safety Instructions...
More informationPOWER SUPPLIES. Control Transformers p8-1 Modular Power Supplies p8-2 Switching Power Supplies p8-3 Automatic Battery Chargers p PAGE
8 POWER SUPPLIES Control Transformers p8-1 Modular Power Supplies p8-2 Switching Power Supplies p8-3 Automatic Battery Chargers p8-10 Perth (08) 9248 0410 Sydney (02) 9676 1671 Melbourne (03) 9706 4599
More informationExBin-P Pressure switches 5 Pa Pa
ExBin-P Pressure switches 5 Pa... 5.000 Pa Electrical, explosion-proof binary pressure / differential pressure switches 5 Pa...100 Pa with adjustable switch activation delay 24 VAC/DC supply voltage, potential
More informationCertificate of Compliance
Certificate of Compliance Certificate: 70054084 Issued to: Emerson - Rosemount, Micro Motion Inc. 12001 Technology Dr. Eden Prairie, Minnesota 55344 USA Attention: Paul Schilke The products listed below
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More informationInstallation Guidelines For BW Gland
Installation Guidelines For BW Gland Address: Raychem RPG Pvt. ltd. 1/62, M G Road, Off. Western express highway, Near Bharat Petroleum, Valiv Village, Post Sativali, Vasai (E) 401208, Maharashtra, India.
More informationPOE1824B. PoE 27,6V/4x0,4A/2x7Ah/PoE
v.1.0 PoE 27,6V/4x0,4A/2x7Ah/PoE Buffer switch mode power supply unit EN* Edition: 2 from 16.09.2013 Supercedes the edition: 1 from 06.02.2012 Features: DC 27,6 V/4x0,4A uninterruptible power supply fitting
More informationPower Supplies. 11/2 Introduction
Siemens AG 2009 Power Supplies 11 11/2 Introduction 4AV Non-Stabilized Power Supplies Filtered for Supply of Electronic Controls 11/4 General data 11/5 4AV2, 4AV4 power supplies, filtered, single-phase
More informationSPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W
Page 1 / 7 Full operation without need of battery Two independent 48Vdc outputs for switching and control Local monitoring with 8 LEDs Remote monitoring with 4 alarm relays Monitoring and configuration
More informationIntrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS Technical brochure
Intrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS 4751 Technical brochure Features Ex ll 1G EEx ia llc T4 - T6 in compliance with ATEX 100a Applicable
More informationTRaC Global Limited, Unit 1, Pendle Place, Skelmersdale, West Lancashire, WN8 9PN, United Kingdom
TRaC Global Limited, Unit 1, Pendle Place, Skelmersdale, West Lancashire, WN8 9PN, United Kingdom Annex to IECEx Certificate of Conformity Equipment Range: The design variants covered are either: a) Complete
More informationFlap-Type Flow Meter Prall
Suitable for H 2 O, acids, alkaline solutions and gases Spring-loaded flap Horizontal or vertical direction of flow Largely independent of viscosity Limit contacts, optional Analog output 4 20 ma, optional
More informationWolflite XT Rechargeable LED Handlamp
Wolflite XT Rechargeable LED Handlamp Zones: 0, 1, 2, 20, 21 and 22 Product Overview Features & Benefits The Wolflite XT Rechargeable Handlamp exploits advanced technology to deliver excellent performance,
More informationMaterial pressure (bar) (Cv (US) kv x 1,2 Seat
00 / way poppet valves electromagnetic actuated, directly controlled G /, / NPT or flanged with NAMUR Interface TÜV-approval based on IEC 6 08, DIN V 9 Valves for safety systems up to SIL Solenoid valve
More informationSKINNER Intrinsically Safe Series Four-Way
SKINNER Four-Way Two-Position Valves SPECIFICATIONS Mechanical Characteristics Standard Materials of Body Aluminum Seals FKM, NBR. Other diaphragm materials available upon request. Compatible Fluids Air
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More informationHCM25 Portable Sub-Sea MPI System Data Sheet
HCM25 Portable Sub-Sea MPI System Data Sheet The HCM25 hand portable MPI was designed in response to the need for a rapidly deployable and reliable system. It has six main components - an electromagnetic
More informationHazardous Area Electrical Equipment. TBKF/CBKF Stainless Steel Flat Roof Keyed Terminal Box Zones 1&2, 21&22. Index
Hazardous Area Electrical Equipment Made TBKF/CBKF Stainless Steel Flat Roof Keyed Terminal Box Zones 1&2, 21&22 Index Dimension Sheet Catalogue Information Leaflet Web Links TBKF/CBKF Information Page
More informationIntrinsically safe solenoid valves on/off controls - ATEX or IECEX certification
Table E3-/E Intrinsically safe solenoid valves on/off controls - ATEX or IECEX certification valve body valve spool intrinsically safe solenoid electrical connector manual override DHW-6/WP/6 On/off valves
More informationPower Inverter. User s Manual. Diamond Series CPD1200EILCD
Power Inverter Diamond Series CPD1200EILCD User s Manual 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5 2-2 Product Overview & Outlook..5 2-3 Power Requirements
More informationOrdering Information. Switching Power Supply S82F. Industrial-Grade Power Supply for General or Peak Load Applications SWITCHING POWER SUPPLIES
Switching Power Supply S82F Industrial-Grade Power Supply for General or Peak Load Applications Correct input voltage range is automatically selected: 1 VAC or 2 VAC. Model S82F-P is suitable for peak
More informationControl and Terminal Box Type A21-**-*****
e pd Control and Terminal Box Exepd GmbH i_park TAUBERFRANKEN Building 23 Becksteinerstrasse 100 97922 Lauda-Königshofen Germany Phone: ++49 (0) 9343 627055-0 Fax: ++49 (0) 9343 627055-99 Mail: info@exepd.de
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationData Sheet SCHISCHEK EXCOS-P. Pressure sensor 20 Pa Pa. Supplied by. .com. Call us on +44 (0)
Data Sheet SCHISCHEK EXCOS-P Pressure sensor 20 Pa... 7.500 Pa Supplied by.com Call us on +44 (0)118 916 9420 Email info@247able.com ExCos-P Pressure sensor 20 Pa... 7.500 Pa Electrical, explosion-proof
More informationManual. EN Appendix. Lynx Ion BMS 400A / 1000A
Manual EN Appendix Lynx Ion BMS 400A / 1000A 1. SAFETY INSTRUCTIONS 1.1 In general Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions
More informationMaterial pressure (bar) (Cv (US) kv x 1,2 Seat. N/en
00 / poppet valves electromagnetic actuated, directly controlled, / NPT or flanged with NAMUR Interface TÜV-approval based on IEC 6 8, DIN V Valves for safety systems up to SIL Solenoid valve also suitable
More informationLABOR ASTER INDUSTRIAL AUTOMATION. Intrinsically safe barrier with separation FIELDBUS TRANSMISSION LINES CONVERTER-SEPARATOR
LOR STER INDUSTRIL UTOMTION Intrinsically safe barrier with separation FIELDUS TRNSMISSION LINES CONVERTER-SEPRTOR type SEx-RS-[ic] RS/RS, RS/, /RS, /, RS/RS - group II and III, category () accompanying
More informationABG Cable Glands Installation Procedure
ABG Cable Glands Installation Procedure ABG Cable Gland Range Baseefa 16ATEX0004X IECEx BAS 16.0011X Installation, Operation and Maintenance Instructions Material: Brass/ Brass with Nickel plated and Stainless
More informationInstruction Manual. for Heating Cables and Cold Leads Type and Catalogue no and Hemstedt GmbH.
Instruction Manual for Heating Cables and Cold Leads Type 68994- and 68997- Catalogue no. 68994- and 68997- Hemstedt GmbH Schleicherweg 19 D-74336 Brackenheim-Botenheim Phone +49 (7135) 9898-0 Fax +49
More informationArt. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2
SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...
More informationT 3965 EN Type 3965 Solenoid Valve Island To control pneumatic actuators
T 365 EN Type 365 Solenoid Valve Island To control pneumatic actuators Application The Type 365 Solenoid Valve Island is a compact solution for the central control of pneumatic actuators in chemical and
More informationThe 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.
1 Elmdene International Ltd Tel: +44 (0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk STANDBY 220V AC POWER SYSTEM IDEAL
More informationCompact Sliding Door Operator Dor-O-Matic 2900 Series
Uniclass L4181 EPIC D181 CI/SfB (31.59) X Compact Sliding Door Operator Dor-O-Matic 2900 Series June 2008 Compact Sliding Door Operator page 1 2900 Series Features & Functions Compact - Automatic Operator
More informationEX-REPAIR AND MAINTENANCE RECEPTACLES
EX-REPAIR AND MAINTENANCE RECEPTACLES A 3 A plugs and receptacles plastic version for zones, 2, 2 and 22 For maintenance, repair and upgrading work, appliances such as drills, welding transformers, hand
More informationSwitch Mode, Automatic, Lead Acid Battery Charger Model: SEC A SEC A SEC A
Switch Mode, Automatic, Lead Acid Battery Charger Model: SEC - 1260A SEC - 1280A SEC - 2440A Owner's Manual Please read this manual before operating your charger CONTENTS Important safety precautions...2
More informationMiniature I/P, E/P Transducer for Electronic Air Pressure Control
Miniature I/P, E/P Transducer for Electronic Air Pressure Control Self-correcting to maintain precise control The Type-900X I/P, E/P transducer converts an electrical signal (current or voltage) to a proportional
More informationSilvertel. Ag Features. 2. Description. Power-Over-Ethernet Module. IEEE802.3af compliant. Small SIL and SMT package available
Silvertel V2.2 Jan 2015 Datasheet Ag9700 Pb 1. Features IEEE802.3af compliant Small SIL and SMT package available Low cost, with minimal external components required Input voltage range 36V to 57V Short-circuit
More informationNEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.
Datasheet Single- and three-phase switched-mode power supply units NEW The new power supplies offer a wide range of robust solutions for demanding application requirements. C SEMI F47 US Designed for high
More informationLPF-25 series. 25W Constant Voltage + Constant Current LED Driver
F 110 M M SELV IP67 Features Constant Voltage + Constant Current mode output Plastic housing with Class II design Built-in active PFC function Class 2 power unit Fully encapsulated with IP67 level Typical
More informationInstallation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies
Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies D1541 D1542 D1543 D1545 D1543-X-8 D1545-X-8 D1545-4BNC D154X Series 1A 2A 3A 5A 3A fitted with 8-way output splitter
More informationCentral Battery Systems Loadstar AC/DC Systems
The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape
More informationPower Conversion Systems 2005/2006. Schaefer the Power to make it happen.
Power Conversion Systems 2005/2006 Schaefer the Power to make it happen. Company profile workforce experience customer orientation flexibility reliability Schaefer Elektronik, founded in 1969, has grown
More informationELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET
ER54 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY
More informationST - II Series POWER SUPPLIES USER INSTRUCTIONS
Introduction ST - II Series POWER SUPPLIES These instructions detail the installation and operation requirements for the ST20-II & ST35-II power supplies. These have been designed for operation in RV s
More informationRUTLAND HRDi CHARGE REGULATOR INSTALLATION AND OPERATION
RUTLAND HRDi CHARGE REGULATOR INSTALLATION AND OPERATION Introduction Congratulations and thank you for purchasing Marlec s HRDi Charge Regulator. This is the latest technology for charge regulation of
More informationMiniature I/P, E/P Transducer for Electronic Air Pressure Control
Type 900X Miniature I/P, E/P Transducer for Electronic Air Pressure Control Self-correcting to maintain precise control Available with zero-based ranges The Type-900X I/P, E/P transducer converts an electrical
More informationInstallation Instructions
Installation Instructions AQU243-8C1R -8F8R -8C8R 24VDC/3.3Amp Supervised (AC & Battery) Power Supply/Charger Module, 85-264vac, 14 x 9 x 3.5" Enclosure, UL294, UL603 & UL1481 Listed AQU243 with one PDB-8C1R
More informationFisher i2p 100 Electro Pneumatic Transducer
Product Bulletin D103197X012 i2p 100 Transducer Fisher i2p 100 Electro Pneumatic Transducer The Fisher i2p 100 electro pneumatic transducer, shown in figure 1, uses a converter module that converts a milliampere
More informationEmergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0
MainswitchSurfacemounting Partno. T0-2-1/I1/SVB-SW Articleno. 207148 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches
More informationGuide for installers. METTLER TOLEDO MultiRange Explosionsproof weighing system with the ID3sTx weighing terminal.
Guide for installers METTLER TOLEDO MultiRange Explosionsproof weighing system with the ID3sTx weighing terminal Hazardous zone ID3sTx weighing terminal LWL Safe zone Dual Channel Fiber Optic Converter
More informationEx Instruction manual. Rotamass Coriolis mass flow meter. IM 01U10X03-00EN-R, 1st edition, Rev FM-1
Ex Instruction manual Rotamass Coriolis mass flow meter IM 01U10X03-00EN-R, 1st edition, 2017-02-08 Rev -1 Table of contents Table of contents 1 Introduction... 3 1.1 Scope of application... 3 1.2 Applicable
More informationBM kv Digital Insulation Tester USER MANUAL
M BM5200 5 kv Digital Insulation Tester USER MANUAL CONTENTS Safety warnings...3 Symbols used on instrument...4 Cleaning...4 General description...5 Insulation resistance test modes...5 Automatic discharge...5
More informationIES GRID FEED-IN LIMITER
IES GRID FEED-IN LIMITER Installation and User Manual Models SPS01101-ABB SPS01303-ABB CONTAINS IMPORTANT INSTALLATION AND TESTING PROCEDURES THAT MUST BE FOLLOWED TO ENSURE COMPLIANCE WITH ENERGEX AND
More informationILED Dorado. User Manual
10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...
More informationKD LV Motor Protection Relay
1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage
More informationFIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V
DSOS24V v.1.0 FIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V EN* Edition: 2 from 30.08.2017 Supercedes edition: 1 from 24.05.2016 PSU features. Compliant with the requirements of the
More informationGSL Electronics Modified Sine Wave Power Inverters
GSL Electronics Modified Sine Wave Power Inverters Congratulations on choosing one of our Modified Sine Wave Inverters for your application. There are 6 models in the range, which will meet most of your
More informationEX Series User Manual
MODELS: EX90L T4 IIB 720 DS, EX90L T4 IIB 1440 SS, EX90L T4 IIC 720 SS EXIN LIGHT EX & INDUSTRIAL LIGHTING EX Series EX90L T4 IIB 720 DS, EX90L T4 IIB 1440 SS, EX90L T4 IIC 720 SS Contents 0. Introduction
More informationThe Traveler Series: Wanderer
The Traveler Series: Wanderer RENOGY 30A PWM Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version: 2.3 Important Safety Instructions Please save these instructions.
More informationDIN Rail UPS Model: DIN-UPS Installation/Operation Manual
DIN Rail UPS Model: DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided 4 Optional Equipment 4 2) Safety Information
More informationHFX & HFXE T8 ELECTRONIC BALLAST & COMBINED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX-ENVIRONMENT
HFX & HFXE T8 ELECTRONIC BALLAST & COMBINED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX-ENVIRONMENT Author : Barel AS Rev 20 Date : 27.09.2017 Barel AS 9917 Kirkenes Norway www.barel.no CONTENTS :
More informationFor double-acting actuators. Crossover-free switching. Safety function in the event of power failure provided by mechanical return spring
For double-acting actuators 5/ Directional Control Valves Actuation: Electromagnetic Indirect solenoid operation soft seal spool valve Connections G 1/, 1/ NPT, G 1/, NAMUR Interface Crossover-free switching
More informationADE 6F ADE 6F. page 46
ADE 6F 6 F U N C T I O N S : D O U B L E C L A M P I N G > For armoured cable > IP68 > Compliance > EX 60079-0 2009 Performance > Nickel plated brass standard finishing > Optional : stainless steel, aluminium
More informationTypes of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:
Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.
More informationElmdene International Ltd
1 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44(0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk 13.8Vdc Switch Mode Power Supply GEN3-08-y
More informationOWNER S MANUAL Please read this manual before operating your power supply
AC-DC POWER SUPPLY Switch Mode AC-DC Power Supply Model No. PSU-1210 PSU-1223 PSU-1230 OWNER S MANUAL Please read this manual before operating your power supply Table of Contents Precautions 2 Description
More information