1 Service Installation S T U D E N T M A N U A L March 31, 2005

2 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards Manual, you will be able to explain and/or demonstrate the application and installation procedure for services. Rationale: The proper service installation will prevent future customer interruptions and voltage problems. Learning Objectives Explain the five types of service classifications. Explain the regulations of the Electric Service Guide regarding customer interface locations. Determine the appropriate conductor for a service installation. Explain the clearance regulations for services. Explain the procedure to install or change a three-phase service. Demonstrate the procedure to install or change a three-phase service. Learning Methods Self-learning + On-the-job Self-learning + On-the-job Self-learning + On-the-job Self-learning + On-the-job Self-learning + On-the-job On-the-Job Demonstration and Practice EVALUATION METHODS Written test Written test Written test Written test Written test On-the-Job Evaluation

3 SERVICE INSTALLATION 3 STUDENT RESOURCES Learning Steps Construction Standards Manual Electric Service Guide 1. Read the Learning Guide. 2. Follow the steps outlined in the Learning Guide. 3. Clarify any questions or concerns you may have. 4. Complete the Practice and Feedback. 5. Complete the Evaluation.

4 4 STUDENT TRAINING MANUAL Lesson 1: Service Classifications Learning Objective:Explain the five types of service classifications. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction Residential Farm General Oilfield Service installations can be divided into various classifications. There are five basic service classifications found in an electrical distribution system. The classification covering a service depends on what the service provides power to and the power requirements. A residential classification is an extension of service to any dwelling unit used primarily for domestic purposes on a permanent or seasonal basis. A farm classification is an extension of service to any standard farmstead, farm irrigation, feedlot or other qualified farm operation. This includes those located on Indian reserves or seasonally operated irrigation systems used exclusively for agricultural purposes. A general classification is an extension of service to any premise used primarily for non-residential or non-agricultural purposes on a permanent or seasonal basis and having demands not exceeding 2000kVA. An oilfield classification is an extension of service to any premise of facilities used primarily for oil production, processing and in-field pumping.

5 SERVICE INSTALLATION 5 Street Lights Street lights account for SaskPower s fifth largest load.

6 6 STUDENT TRAINING MANUAL Lesson 2: Electric Service Guide Regulations Learning Objective:Explain the regulations of the Electric Service Guide regarding customer interface locations. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction The Electric Service Guide contains the requirements of all new or altered services before connection to the utility s service is performed. There is important information found in the Electric Service Guide which pertains to point of delivery and supply service. These topics should be reviewed as they are relevant to the various service classifications. Reference For additional information, refer to Section 2.0 of the Electric Service Guide.

7 SERVICE INSTALLATION 7 Lesson 3: Conductor for Service Installations Learning Objective:Determine the appropriate conductor for a service installation. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction There are several factors which determine the conductor required for a supply service. These factors include: Type of service Overhead - conductor must be designed to hold tension Underground - all conductors are coated to insulate them from ground. Number of conductors required Single-phase, 3-wire Three-phase, 3-wire Three-phase, 4-wire Load - conductor size must be large enough to handle the current of the connected service Voltage - sufficient insulation must coat the conductor for the voltage rating Voltage must be a consideration as it affects the amount of current Length - the longer the supply service, the greater the resistance and voltage drop Load - any load the customer may add in the future must be taken into consideration Service Conductors Due to the high cost of copper, light weight aluminum is usually

8 8 STUDENT TRAINING MANUAL preferred as the service conductor. Reference For additional information on service conductor size, refer to A- 22-XX in the Overhead Construction Standards manual and B- 22-XX in the Underground Construction Standards manual.

9 SERVICE INSTALLATION 9 Lesson 4: Clearance Regulations for Services Learning Objective:Explain the clearance regulations for services. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction Maintaining the proper clearance for service conductors is important as it provides: safety to the public and the worker continuity of service protection of property The clearance regulations are found in the Construction Standards manuals. They have been put in place to conform to the CSA standards and guidelines specified in the Standard Engineering Practices manual and the Electric Service Guide. Point of Attachment The point of attachment refers to the location where the utility s cables attach to a customer owned structure. Reference For additional information on point of attachment, refer to C , Sheet 1 of 1, in the Overhead Construction Standards Manual. Ground Clearances Ground clearance refers to the minimum clearance from the utility s

10 10 STUDENT TRAINING MANUAL conductor to ground that must be maintained to protect the public. Reference For additional information on clearances, refer to C in the Overhead Construction Standards manual. Building Clearances Various clearance standards apply when stringing conductor over or near buildings and must be maintained at all times. ---Note--- Various clearance standards apply when stringing conductor over or near buildings and must be maintained at all times. Reference For information on building clearances, refer to C in the Overhead Construction Standards manual. Underground ---Note--- Services are not to be strung over wells, swimming pools or around antenna structures. An underground service must maintain minimum clearances from buildings, gas lines, high voltage lines and decks or fences. The minimum clearance requirements can be found in the Underground

11 SERVICE INSTALLATION 11 Construction Standards manual. Reference For additional information on underground clearances, refer to C in the Underground Construction Standards manual.

12 12 STUDENT TRAINING MANUAL Lesson 5: Changing Three-Phase Services Learning Objective:Explain the procedure to install or change a three-phase service. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction Voltage Check Phase Rotation Change Service The procedure below must be followed when changing the service conductors on a three-phase service. This procedure will maintain a positive phase rotation once the service conductors have been changed. Check the name plate(s) of the transformer(s). With the use of a voltmeter and a visual inspection, confirm the reference phase (red phase) on the delta connected secondary. The red phase will measure 208V to ground. Hook the phase rotation meter to RYB (red, yellow, blue) to verify the rotation. Mark the phases accordingly using colored tape on both the supply and consumer ends of the service. Notify the customer of the outage. Open main (switch, breaker). Remove the service. Replace the service. Hook the neutral and R (reference phase) up permanently on both ends. Hook up Y and B temporarily on the supply side and permanently on the consumer end. Check the rotation with a phase rotation meter using the same phasing as previously marked. The phase rotation meter should have the same rotation as the previous test - if not, reverse the Y and B leads. Complete the connections.

13 SERVICE INSTALLATION 13 Close main (switch, breaker).

14 14 STUDENT TRAINING MANUAL Lesson 6: Procedure to Install or Change a Three-Phase Service Learning Objective:Demonstrate the procedure to install or change a three-phase service. Learning Method:On-the-Job Demonstration and Practice Evaluation Method:On-the-Job Evaluation

15 SERVICE INSTALLATION 15 Skills Practice 1. Voltage check: 1. Perform a voltage check. 2. Identify the red phase (where applicable). 2. Phase rotation check: 1. Verify the phasing using a phase rotation meter. 2. Mark the phasing with phasing tape. 3. Change service: 1. Open the main switch. 2. Remove and replace the service. 3. Hook up the neutral and red phase completely. 4. Hook up the Y and B phase temporarily. 5. Check the phasing using a phase rotation meter. 6. Correct the phasing if incorrect. 7. Complete the connections. 8. Close the main switch.

16 16 STUDENT TRAINING MANUAL Summary To summarize this module, you have learned: Five types of service classifications. The regulations of the Electric Service Guide regarding customer interface locations. To determine the appropriate conductor for a service installation. The clearance regulations for services. To install or change a three-phase service. Practice Feedback Review the lesson, ask any questions and complete the self-test. Evaluation When you are ready, complete the final test. You are expected to achieve 100%.

17 SERVICE INSTALLATION 17 Review Questions 1. The extension of a service to the premise of a facility used primarily for infield pumping is called: (a) General. (b) Farm. (c) Residential. (d) Oilfield. 2. The extension of a service to a premise having demands not exceeding 2000kVA is called: (a) General. (b) Farm. (c) Residential. (d) Oilfield. 3. The extension to a dwelling unit used primarily for domestic purposes and not commercially operated is called: (a) General. (b) Farm. (c) Residential. (d) Oilfield. T / F 4. When an overhead system exists, SaskPower normally installs an underground supply service to new customers requesting a residential service. T / F 5. SaskPower owns the facilities up to the point of delivery on a residential service. T / F 6. A polyphase farm service is normally served from an underground system. T / F 7. For single-phase farm services up to 200A and 300V, the customer will supply and install a metering centre for service support and attachment. T / F 8. For an underground general service application, transformation is located on the consumer s property.

18 18 STUDENT TRAINING MANUAL T / F 9. Transformation for an oilfield service is required to be on SaskPower property. T / F 10. Overhead and underground service conductors differ in that underground service conductors are designed to hold tension. T / F 11. All conductor in an underground service is enclosed in a protective coating. 12. Which factors determine the supply service conductor required? (a) The voltage supplied to the consumer is 120/ 240V. (b) The length of the supply service is 105m. (c) The supply service is buried. (d) All of these T / F T / F T / F T / F 13. Aluminum conductors are most commonly used for supply service applications. 14. Safety of the public and the worker is one reason for clearance regulations. 15. Property damage and service interruptions can occur if clearance regulations are not met. 16. Clearance regulations are only required for overhead services. 17. Which of the following is the requirement for stringing a residential service over a habitable building? (a) It may cross over the building with 1.0m clearance. (b) It may cross over the building with 2.5m clearance. (c) It may cross over the building with 4.0m clearance. (d) It may not cross over the building.

19 SERVICE INSTALLATION Which of the following is the requirement for stringing a residential service over a swimming pool. (a) It may cross over with 3.0m clearance. (b) It may cross over with 4.5m clearance. (c) It may cross over with 5.5m clearance. (d) It may not cross over. T / F 19. It is not necessary to verify phase rotation on a threephase service change.

20 20 STUDENT TRAINING MANUAL Review Question Solutions 1. Oilfield. 2. General. 3. Residential. 4. T 5. T 6. F 7. F 8. T 9. F 10. F 11. T 12. All of these 13. T 14. T 15. T 16. F 17. It may not cross over the building. 18. It may not cross over. 19. F

Overhead Switching Devices

Overhead Switching Devices Overhead Switching Devices S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Oil Circuit Recloser Operating Principles module Objectives: Given the Construction Standards

More information

Single-Phase Meter Components

Single-Phase Meter Components Single-Phase Meter Components S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: From memory, you will be able to explain the parts and function of a single-phase

More information

Single-Phase Underground Operating

Single-Phase Underground Operating Single-Phase Underground Operating S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Introduction to Underground Systems module Objectives: Given an underground distribution

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

GENERAL INFORMATION 1.01 PURPOSE

GENERAL INFORMATION 1.01 PURPOSE GENERAL INFORMATION 1.01 PURPOSE The purpose of this manual is to supply essential information to customers, employees, architects, engineers, contractors, and others concerned with electrical installations

More information

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE 201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.

More information

Circuit Concepts (Residential)

Circuit Concepts (Residential) Youth Explore Trades Skills Circuit Concepts (Residential) Description This Activity Plan will allow students to understand how electrical circuits work in a home. Students will also gain knowledge of

More information

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 Candidate Code No. Result Date Int For Board Use Only ER38 Version of AS/NZS 3000 used (tick ONE Box) 2000 2007 & Amend 1 ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 QUESTION AND ANSWER BOOKLET

More information

INSTALL SERVICE- ENTRANCE SYSTEMS

INSTALL SERVICE- ENTRANCE SYSTEMS SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 32 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 ER42 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 Int QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

For Conduit Inspections

For Conduit Inspections Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit

More information

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET ER54 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

ELECTRICIANS REGULATIONS EXAMINATION 29 June 2013 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 29 June 2013 QUESTION AND ANSWER BOOKLET ER52 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 29 June 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Requirements for Secondary Voltage Revenue Metering (750 V and less)

Requirements for Secondary Voltage Revenue Metering (750 V and less) Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

SECTION 500 METERING AND ASSOCIATED EQUIPMENT

SECTION 500 METERING AND ASSOCIATED EQUIPMENT SECTION 500 METERING AND ASSOCIATED EQUIPMENT 500.0 General Meter sockets shall be provided, installed and maintained by Customer. When the ratings of meter sockets are exceeded, transockets shall be used.

More information

ELECTRIC SERVICE MANUAL

ELECTRIC SERVICE MANUAL ELECTRIC SERVICE MANUAL Issued: November 2018 For the most current version of the Jo-Carroll Energy electric service manual please visit www.jocarroll.com TABLE OF CONTENTS Chapter 1. General Information...1

More information

Transmission & Distribution Glossary of Electrical Terms

Transmission & Distribution Glossary of Electrical Terms Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The

More information

Electrical Equipment and Terminology

Electrical Equipment and Terminology Youth Explore Trades Skills Description Understanding the language of the electrical trade and knowing what electrical equipment is named and its purpose are very important. Anyone who is exposed to a

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

Renewable Energy Systems 14

Renewable Energy Systems 14 Renewable Energy Systems 14 Buchla, Kissell, Floyd Chapter Outline The Electric Power Grid 14 Buchla, Kissell, Floyd 14-1 THREE-PHASE AC 14-2 THREE-PHASE TRANSFORMERS 14-3 GRID OVERVIEW 14-4 SMART GRID

More information

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally. This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering

More information

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Fees and Charges PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY 1 Fees and Charges SECTION TABLE OF CONTENTS PAGE TABLE OF CONTENTS... 2 DELEGATED AUTHORITY... 3 ELECTRICAL FEES AND CHARGES... 4 ENGINEERING

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

Electric & Gas Service Requirements (Greenbook) Overview

Electric & Gas Service Requirements (Greenbook) Overview INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed

More information

NZQA registered unit standard version 1 Page 1 of 6

NZQA registered unit standard version 1 Page 1 of 6 Page 1 of 6 Title Demonstrate knowledge of theory and legislation for registration of electrical appliance servicepersons Level 3 Credits 3 Purpose This unit standard covers the theory assessment required

More information

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection

More information

10. METERING General Requirements

10. METERING General Requirements 10. METERING 10.1 General Requirements A. The Company will not supply service to a Customer whose wiring is designed for resale of electricity through submetering except for recreational campgrounds, marinas,

More information

PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Fees and Charges PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY 1 SECTION TABLE OF CONTENTS Fees and Charges PAGE TABLE OF CONTENTS... 2 DELEGATED AUTHORITY... 3 ELECTRICAL FEES AND CHARGES... 4 SERVICE

More information

Demonstrate knowledge of electrical theory for Electrical Service Technician B

Demonstrate knowledge of electrical theory for Electrical Service Technician B Demonstrate knowledge of electrical theory for Electrical Service Technician B 10937 version 4 Page 1 of 5 Level 3 Credits 3 Purpose 'Electrical Service Technician B' (EST B) refers to a class of electrical

More information

H. J. Arnett Industries, LLC SW Avery Court Tualatin, OR 97062

H. J. Arnett Industries, LLC SW Avery Court Tualatin, OR 97062 H. J. Arnett Industries, LLC 20460 SW Avery Court Tualatin, OR 97062 Phone: 503-692-4600 Fax: 503-692-4661 Toll free: 800-684-9844 Web address: www.arnettindustries.com USE OF THE MEGA BEAST SERVICE CONDUCTOR

More information

Emerald People s Utility District RATE SCHEDULES. Rate Schedules Effective April 1, 2018

Emerald People s Utility District RATE SCHEDULES. Rate Schedules Effective April 1, 2018 Emerald People s Utility District RATE SCHEDULES 2018 Rate Schedules Effective April 1, 2018 Connect With Us 33733 Seavey Loop, Eugene, OR 97405 Phone: 541-746-1583 Toll-free: 800-422-4086 Fax: 866-284-7953

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

BREAK-SAFE Load Break & Pick-up Tool

BREAK-SAFE Load Break & Pick-up Tool BREAK-SAFE Load Break & Pick-up Tool USBS-15-1-PS USBS-27-1-PS USBS-46-1-PS USBS-15-2-PS USBS-27-2-PS USBS-46-2-PS Available Options: H - Hard Case S - Soft Case Second Generation Models Only. For tools

More information

3.1 Overview of ATCO Electric s URD System Design

3.1 Overview of ATCO Electric s URD System Design Page: 3-1 3.0 URD DESIGN GUIDELINES 3.1 Overview of ATCO Electric s URD System Design The power supply to all single lot underground residential services is through front lot service. Single phase transformers

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location.

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. I N T R O D U C T I O N - M-1 RIGHTS: PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. NOTIFICATION: Customers planning to install or

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

Introducing Electricity and Electrical Safety

Introducing Electricity and Electrical Safety Lesson A4 1 Introducing Electricity and Electrical Safety Unit A. Mechanical Systems and Technology Problem Area 4. Electrical Systems Lesson 1. Introducing Electricity and Electrical Safety New Mexico

More information

ELECTRICAL METERING RESIDENTIAL

ELECTRICAL METERING RESIDENTIAL ELECTRICAL METERING RESIDENTIAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 UNDERGROUND FED METER SOCKET (226-320 AMPS) 5.0 METER SOCKET (0-320 AMPS, 120/208V) 6.0 UNDERGROUND SERVICE W/CURRENT

More information

M A N I T O B A Order No. 48/13. Régis Gosselin, BA, CGA, MBA, Chair Before: Raymond Lafond, BA, CMA, FCA, Member Larry Soldier, Member

M A N I T O B A Order No. 48/13. Régis Gosselin, BA, CGA, MBA, Chair Before: Raymond Lafond, BA, CMA, FCA, Member Larry Soldier, Member M A N I T O B A Order No. 48/13 THE PUBLIC UTILITIES BOARD ACT May 1, 2013 Régis Gosselin, BA, CGA, MBA, Chair Before: Raymond Lafond, BA, CMA, FCA, Member Larry Soldier, Member AN ORDER APPROVING MANITOBA

More information

ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET34 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 A. GENERAL 1. The character of service available at any particular location must be ascertained by the Company business office, and will depend upon the

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AEP Texas (comprised of its Central and North Divisions

More information

METERING REQUIREMENTS

METERING REQUIREMENTS METERING REQUIREMENTS KUA will not accept a non-securable service trough entrance. That is, all enclosed conductors prior to the meter (line side) will be securable by and accessible to KUA personnel only.

More information

FINAL-ER 42 Electrician Regulations Answer Schedule

FINAL-ER 42 Electrician Regulations Answer Schedule FINAL-ER 42 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

A. Basic Customer Charge: $ B. Energy Charge: $.09316/kWh

A. Basic Customer Charge: $ B. Energy Charge: $.09316/kWh Electric Rates Residential Service (RS1) This Schedule is available for separately metered and billed electric service to any Customer for use in and about (a) a single-family residence or apartment, (b)

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

EARTHING YOUR QUESTIONS ANSWERED

EARTHING YOUR QUESTIONS ANSWERED 18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to:

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to: City & Guilds 2381 Test 2382 Level 3 Q1 Which one of these electrical installations does BS 7671:2008 not apply to: Temporary Construction sites Distributor s Equipment Caravans Public Premises Q2 Which

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

UPPCO SERVICE MANUAL

UPPCO SERVICE MANUAL Revised 01/2015 Section 6 ELECTRIC SERVICE - GENERAL Page 1 of 10 Section 6 Electric Service - General 6-1 Number of Services and Voltages / Meter... 2 6-2 Energy Conversion Factors... 7 6-3 Lightning

More information

DIRECTORATE OF TECHNICAL EDUCATION DIPLOMA IN ELECTRICAL AND ELECTRONICS ENGINEERING III YEAR M SCHEME V SEMESTER.

DIRECTORATE OF TECHNICAL EDUCATION DIPLOMA IN ELECTRICAL AND ELECTRONICS ENGINEERING III YEAR M SCHEME V SEMESTER. DIRECTORATE OF TECHNICAL EDUCATION DIPLOMA IN ELECTRICAL AND ELECTRONICS ENGINEERING III YEAR M SCHEME V SEMESTER 2015 2016 onwards ELECTRICAL ESTIMATION AND ENERGY AUDITING CURRICULUM DEVELOPMENT CENTRE

More information

TEMPORARY ELECTRICAL SERVICE

TEMPORARY ELECTRICAL SERVICE ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION

More information

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JEA SHALL MAKE ALL METER SPOTS BEFORE ELECTRICAL WORK BEGINS AS TO DETERMINE THE POINT OF ATTACHMENT

More information

Electric Service Guides 2017

Electric Service Guides 2017 Electric Service Guides 2017 Electric Service Guide Residential January 1, 2017 Contact MID s Electric Engineering Department (electric.standards@mid.org) with any questions about this Service Guide.

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service. UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later

More information

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 36 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray

Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray Product LINE Guide Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray Voltage Isolation Power Factor Correction

More information

Scale of Inspection Fees of Electrical Inspectorate Schedule. I. Fees for Initial Inspections:

Scale of Inspection Fees of Electrical Inspectorate Schedule. I. Fees for Initial Inspections: PART 7 Scale of Inspection Fees of Electrical Inspectorate Schedule I. Fees for Initial Inspections: SCALE A For an inspection or test of any generating station, receiving station or other places in which

More information

See NT POWERCOS , Classification Based On Service Size.

See NT POWERCOS , Classification Based On Service Size. Newmarket-Tay Power Distribution Ltd. Conditions of Service Number: NT POWER COS 310 01 Issue Date: July, 2007 Next Review Date: February, 2020 Residential 1. Preamble This section covers all items that

More information

The cost estimation methodology used to update the charges and credits is the same methodology the Company utilized in the prior year s filing.

The cost estimation methodology used to update the charges and credits is the same methodology the Company utilized in the prior year s filing. LISA D. NORDSTROM Lead Counsel lnordstrom@idahopower.com December 28, 2018 Public Utility Commission of Oregon Filing Center 201 High Street SE, Suite 100 P.O. Box 1088 Salem, Oregon 97301 Re: Tariff Advice

More information

Bulletin Interconnection of electric power production sources Rules 2-010, , , , , , and

Bulletin Interconnection of electric power production sources Rules 2-010, , , , , , and Bulletin 84-1-11 Interconnection of electric power production sources Rules 2-010, 64-078, 64-110, 84-004, 84-008, 84-018, 84-022 and 84-030 Scope Issued May 2018 Supersedes Bulletin 84-1-10 1) Requirements

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

UNS Electric, Inc. Rules and Regulations

UNS Electric, Inc. Rules and Regulations Original Sheet No.: 902 A. In these, the following definitions will apply unless the context requires otherwise: 1. Actual Cost: The cost incurred by the Company for labor, materials and equipment including

More information

Edmond Electric Standard Pricing Schedules

Edmond Electric Standard Pricing Schedules Edmond Electric Standard Pricing Schedules Effective April 1, 2017 STANDARD PRICING SCHEDULE TABLE OF CONTENTS SHEET NO. 1.1 TYPE OF SERVICE DESCRIPTION SHEET NUMBERS Residential Table of Contents 1.1-1.2

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

Electrical Safety. Introduction

Electrical Safety. Introduction Electrical Safety Introduction Electrical hazards 300 electrocutions every year in the U.S. Leading cause is insufficient training ALL were preventable What is Electricity? How Electricity Works Created

More information

Engineering Recommendation P26

Engineering Recommendation P26 Engineering Recommendation P26 The Estimation of the Maximum Prospective Short-Circuit Current for Three Phase 415V Supplies Document originally produced by the Electricity Association. 2003 Energy Networks

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

BREAK-SAFE Load Break & Pick-up Tool

BREAK-SAFE Load Break & Pick-up Tool BREAK-SAFE Load Break & Pick-up Tool USBS-15-1-PS USBS-15-2-PS USBS-27-1-PS USBS-27-2-PS USBS-38-1-PS USBS-38-2-PS USBS-46-1-PS USBS-46-2-PS Available Options: H - Hard Case S - Soft Case Second Generation

More information

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS REVISED FEBRUARY 2017 TABLE OF CONTENTS Metering Equipment & Installation Standards... 1 Metering Equipment & Installation Standards

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

AVOIDING ELECTROCUTION HAZARDS

AVOIDING ELECTROCUTION HAZARDS Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing

More information

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018. SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic

More information

NZQA registered unit standard version 1 Page 1 of 5

NZQA registered unit standard version 1 Page 1 of 5 Page 1 of 5 Title Demonstrate and apply knowledge of theory and practice for registration of electrical workers (stage 3) Level 4 Credits 3 Purpose This unit standard is for people who are completing an

More information

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1 Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide Version 1.1 October 21, 2016 1 Table of Contents: A. Application Processing Pages 3-4 B. Operational Modes Associated

More information

Revision of the CNP Service Standards Book (Effective Date )

Revision of the CNP Service Standards Book (Effective Date ) 0 9-7-2018 Revision of the CNP Service Standards Book (Effective Date 10-8-2018) 1. FOREWORD Add Turn Down/Unexecutable Codes (Page 4). For service connection issues, please refer to the Turn Down/Unexecutable

More information

SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL. Estimation and Costing & Utilization of Electrical Energy

SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL. Estimation and Costing & Utilization of Electrical Energy 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Estimation and Costing & Utilization of Electrical Energy Estimation and Costing & Utilization of electrical Energy Estimation

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

ELECTRICAL TECHNOLOGY 3 March 2008

ELECTRICAL TECHNOLOGY 3 March 2008 I. Course Description ELECTRICAL TECHNOLOGY 3 March 2008 The purpose for this course is to instruct potential electricians in the skills necessary for entry into the job market. During this course, the

More information

Commercial Electric Service Handbook

Commercial Electric Service Handbook Commercial Electric Service Handbook January 2011 CONTACTS Clark Public Utilities: Website........................................... www.clarkpublicutilities.com Construction Services department (To initiate

More information

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE

More information

4/1/2016 Revision of the CNP Service Standards Book (Effective Date )

4/1/2016 Revision of the CNP Service Standards Book (Effective Date ) 0 4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016) 1. Article 422.1 Meter Pole Installations - Requirements (Page 59). Revised paragraph - Steel poles shall be truck accessible.

More information