SECTION FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS)

Size: px
Start display at page:

Download "SECTION FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS)"

Transcription

1 SECTION FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS) 1.1 SUMMARY A. Storage tanks, fuel oil, tank accessories, piping, valves, and specialties for fuel-oil distribution inside and outside any building must meet all applicable codes. B. General note: Any contiguous facility that has tanks and/or other vessels that can hold 55 gallons or more of oil (including oil in equipment or cooking oils) in an aggregate amount equal to or exceeding 1,320 gallons must have a Spill Prevention Control and Countermeasures (SPCC) Plan. It is important to note that additional tanks or oil-filled equipment at a site currently not subject to the SPCC rule may cause a facility to be subject. This may necessitate possible upgrades of existing equipment to comply. It is a Best Management Practice to install all oil-filled equipment with oil spill prevention and containment, even if not currently subject to the rule, in order to avoid having to upgrade storage areas during a subsequent project and to avoid spills. All petroleum storage tanks at the Medical Center, LLE/COI, River Campus, CVRI, and Data Center are currently subject to the SPCC requirement. The site s SPCC Plan must be updated to reflect any changes in the handling of oil in containers, tanks or equipment capable of holding 55 gallons or more within 6 months of installation. Projects must anticipate a professional engineering fee to upgrade the plan. Contact the Environmental Compliance Manager at prior to tank or oil-filled equipment installation. Designers of tank and other oil-containing systems subject to the SPCC rules found in 40 CFR Part 112 must incorporate these requirements into the design in addition to any other state and federal requirements. 1.2 QUALITY ASSURANCE The designer and installer both are responsible to ensure tank installations meet the requirements: EPA and State and Local Authorities. These include, but may not be limited to: A. 6NYCRR Parts B. Standards: Petroleum Equipment Institute Publications P100 and RP300, NFPA 30, 30A, and 31, requirements of University Insurance carriers such as Factory Mutual. C. 40 CFR Part 112 will apply to a facility subject to the federal SPCC rule. Contact the Manager of Environmental Compliance for a determination of applicability of the SPCC rules before any particular installation. D. NYSDEC SPOTS Memos 10 & 17 E. NYSDEC Underground Non-metallic Piping Policy. F. Any UL requirements or any other applicable standard. 1.3 WARRANTY A. Structural and Corrosion Failure: 30 years. 1.4 UNDERGROUND TANKS A. Tank Markings: 1. Permanent stencil, label, or plate with the following information: Section Fuel-Oil Distribution Page 1 of 5

2 a. Manufacturer's statement that, This tank conforms with 6NYCRR Part 614. b. The standard of design by which tank was manufactured. c. Petroleum products and percentages of volume of petroleum additives which may be stored permanently and compatibility within tank or reference to a list available from the manufacturer identifying products compatible with all tank materials. d. Year tank manufactured. e. Unique identification number (UL number). f. Dimensions, design, and working capacity and model number of tank. g. Name of manufacturer. B. Fill Port: 1. Permanent stencil, label, or plate, installed conspicuously, visible to the carrier, and permanently affixed, with the following information: a. Manufacturer's statement that, This tank conforms with NYCRR Part 614. b. The standard of design by which tank was manufactured. c. Petroleum products and percentages of volume of petroleum additives which may be stored permanently and compatibility within tank or reference to a list available from the manufacturer identifying products compatible with all tank materials. d. Year tank manufactured. e. Unique identification number (as assigned by Environmental Compliance Manager). f. Dimensions, design, and working capacity (90% full) and model number of tank. g. Name of manufacturer. h. Date of installation. i. Any other requirement of Part 614.3(a) that the Commissioner may require. 2. Permanently color code all fill ports to identify product inside tank in a manner consistent with the color and symbol code of the American Petroleum Institute, as follows: a. Fuel Oil #1: Purple with yellow bar b. Fuel Oil #2: Green (note: this is oil used in external combustion boilers) c. Diesel fuel #2: Yellow (note that NYSDEC has determined that oil used to power internal combustion engines such as emergency generators is number 2 diesel). This coding is independent of whether the fuel is taxed or not. Generator tank fill ports are to be painted yellow. d. In addition, the marking must be hexagonal in shape for distillate fuels. As required in Part 613.3(3). C. Leak-detection and Monitoring Systems: 1. Must meet current regulatory and industry standards for monitoring the tank and recording leaks. 2. Must have self diagnostic capabilities. Section Fuel-Oil Distribution Page 2 of 5

3 3. Are to be connected to the DDC system. 4. Internal twenty-four (24) character printer for reports and alarm notification which include: a. Gallons of fuel b. Ullage c. Inches of fuel d. Time and date e. Tank identification f. Temperature g. Fuel identification h. Programmable automatic report times i. Programmable alarm limits to warn of: 1) Oil or water in interstice 2) Low level 3) High level 4) High water 5) Theft j. Automatic Inventory Increase (Delivery) report consisting of: 1) Delivery start time and date 2) Beginning inventory 3) Fuel temperature 4) Delivery end time and date 5) Ending inventory 6) Ending fuel temperature 7) Net and gross increase 5. High level enunciator in close proximity to each fill station with integral horn and flasher. Enunciator shall automatically silence in ten (10) seconds without the need to access the control panel. Provide warning sign adjacent to enunciator that reads Warning Tank Overfill Alarm DO NOT OVERFILL. The enunciator shall be equipped with a self-test button and indicator so that its efficacy can be checked on a monthly basis. D. Fill Port Spill Container: A 7 gallon integrally mounted fill port spill catchment basin with full drain, lockable hinged lid, and brass non-sparking padlock. E. Automatic delivery shut-off device capable of 100% delivery shut-off without human intervention if located within 500 feet of a storm drain. No ball-float shut-off valves located within delivery drop tube are to be specified for this purpose. Section Fuel-Oil Distribution Page 3 of 5

4 F. Vent/Vapor Systems Atmospheric Vent: Upward flow vent cap with flame retardant 40-mesh screen extending a minimum of twelve feet (12') above grade. New York Fire Code G. Fuel Oil: Diesel very low sulfur diesel (required by University air permit) if for an emergency generator. H. The fill-port area should be located in a poured concrete pad to both protect the fill ports should equipment be inadvertently driven over them and to help prevent fuel spills from entering the ground. The top of the concrete pad shall be sloped in such a way as to help direct water from accumulating in the fill port and other access ways to the tank. I. As-built drawings of the tank/piping installation reduced to no larger than legal paper size suitable for filing and written certification by the installer that the system has been installed in compliance with the New York Standards for New and Substantially Modified Petroleum Storage Facilities, 6NYCRR Part 614 shall be given to the Manager of Environmental Compliance at the point of time the tanks system is turned over to the University. J. In the case of underground tanks, each component must be inspected by the owner designated representative prior to its being buried. 1.5 ABOVE GROUND TANKS A. Above ground tank systems shall be constructed and installed per the specifications found in 6NYCRR Parts , NFPA as well as other applicable state and local regulations including 40 CFR Part 112. B. Color Code all fill ports to identify product inside tank in a manner consistent with the color and symbol code of the American Petroleum Institute, as follows: 1. Fuel Oil #1: Purple with yellow bar 2. Fuel Oil #2: Green (note: this is oil used in external combustion boilers) 3. Diesel Fuel #2: Yellow (note that NYSDEC has determined that oil used to power internal combustion engines such as emergency generators is number 2 diesel). This coding is independent of whether it is taxed or not. Generator tank fill ports are to be painted yellow. 4. In addition, the marking must be hexagonal in shape for distillate fuels. As required in Part 613.3(3). C. Signage near Fill Port: The tank must be clearly marked near the fill port with the following markings on either a permanent sign or stencil that is clearly visible to the delivery person: 1. Tank ID (assigned by UR as used to register with NYSDEC) 2. Fuel type (typically diesel) 3. Design Capacity of tank 4. Working Capacity of tank (typically 90% of design) D. Spill Prevention and Containment: Refer to NYSDEC SPOTS Memo's 10 &17 regarding the need for secondary containment. Note that most University storm drains discharge directly into the Genesee River. NYSDEC SPOTS Memo #10 determines that a tank located within 500 feet of a storm drain is presumptive evidence of the likelihood of a potential for a release into the waters of the state. All of the likely scenarios for a release in Spots 10 &17 must be addressed including secondary containment configuration of the tank, filling operations and plausible generator system failures that might cause a release such as a hose breaking. Section Fuel-Oil Distribution Page 4 of 5

5 Protection must not rely on an operator or other person's response. Automatic delivery shut-off devices, adequate dikes/beams or other approved means to prevent a release must be incorporated into the tank system's design. The best means is to avoid placing generator/tank systems nears storm drains or other potential routes to the waters of the state. E. Operating valve in place on every line with a gravity head. F. Security and Structural Protection: The tank must be protected and secured from traffic and other hazards including unauthorized tampering as required in both the applicable NYSDEC regulations and Part 112 federal SPCC regulations. G. All above ground tanks installed at the University shall be double walled tanks with interstitial monitors that have a self-test circuit. H. Fill Spill Container: A 7 gallon integrally mounted fill spill catchment basin with full drain, lockable hinged lid, and brass nonsparking padlock. I. Automatic Delivery Shut-off Device: Capable of 100% delivery shut-off without human intervention if located within 500 feet of a storm drain. No ball-float valves located within delivery drop tube are to be specified for this purpose. J. Vent/Vapor Systems Atmospheric Vent: Upward flow vent cap with flame retardant 40-mesh screen extending a minimum of twelve feet (12') above grade. New York Fire Code K. Fuel Oil: Diesel very low sulfur diesel (required by University air permit) if for an emergency generator. L. All above ground tank installations at the University shall be installed so that they can be inspected per Part M. Fire protection and signage required by State and local code must be supplied and installed. This includes a NO SMOKING sign. N. At the time a tank is turned over to the University the tank shall be inspected by a qualified third party selected by the University for independent verification that the tank has been installed per the applicable codes, regulations and University requirements. This may be by the same independent inspector that will update the SPCC. END OF SECTION Section Fuel-Oil Distribution Page 5 of 5

THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS

THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS Presented by: Joyce A. Rizzo President JD2 Environmental, Inc. 800 East Washington Street West Chester, PA 19380 www.jd2env.com

More information

9.21 Tank Program Guide NYS Office of Mental Health Tank System Installation Guide

9.21 Tank Program Guide NYS Office of Mental Health Tank System Installation Guide - Design Guides A. SITE PLANS: Provide existing condition, removal plan, and proposed installation site plans for all tanks. Plans must include the following: 1. Dimensions of tank and any structural pads.

More information

1) Activity Description: Management of Petroleum Storage Tanks and Containers

1) Activity Description: Management of Petroleum Storage Tanks and Containers ES-301-4.09 Management of Petroleum Storage Tanks and Containers Document Identification Number ES-301-4.09 Document Owner: John Hambright 1) Activity Description: Management of Petroleum Storage Tanks

More information

AST REGISTRATION PIPE INSPECTION PE REQUIREMENTS. David D. Bradeson, P.E. Chemung Contracting Corporation

AST REGISTRATION PIPE INSPECTION PE REQUIREMENTS. David D. Bradeson, P.E. Chemung Contracting Corporation AST REGISTRATION PIPE INSPECTION PE REQUIREMENTS David D. Bradeson, P.E. Chemung Contracting Corporation AST REGISTRATION REQUIRED 9 VAC 25-91-20 Part II individual tank of 660 gal. or greater or aggregate

More information

(Please type or use black ink)

(Please type or use black ink) (Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of

More information

Fuel Storage Dec 2016

Fuel Storage Dec 2016 Fuel Storage Dec 2016 1 Table of Contents SECTION I. ABOVEGROUND SMALL TANKS (1,100 GALLONS OR LESS)...3 Siting a new aboveground tank or tanks...3 Understanding fuel tank types....3 Where to find the

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 7/18) ABOVEGROUND PETROLEUM STORAGE TANKS INTRODUCTION Aboveground storage tanks (ASTs) are used to store petroleum products at several UNL locations. For example, ASTs

More information

John Benson David Hanny Barton & Loguidice, P.C.

John Benson David Hanny Barton & Loguidice, P.C. John Benson David Hanny Barton & Loguidice, P.C. Environmental Regulations: An Alphabet Soup AAI UIC RCRA SPCC SPDES RMP CERCLA PBS CBS CAA CWA SPILLS DEC EPA OSHA Outline Regulatory Programs Lessons

More information

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL On January 26, 2005, the Maryland Department of the Environment (the Department) implemented, in the Code of Maryland Regulations (COMAR) 26.10,

More information

ES Fueling Aircraft, Vehicles, and Auxiliary Equipment Document Identification Number

ES Fueling Aircraft, Vehicles, and Auxiliary Equipment Document Identification Number ES-301-1.01 Fueling Aircraft, Vehicles, and Auxiliary Equipment Document Identification Number ES-301-1.01 Document Owner: John Hambright 1) Activity Description: Fueling Aircraft, Vehicles, and Auxiliary

More information

Syracuse University Petroleum Bulk Storage Tank Program Manual

Syracuse University Petroleum Bulk Storage Tank Program Manual Syracuse University Petroleum Bulk Storage Tank Program Manual August 23, 2017 Prepared by: Syracuse University Environmental Health & Safety Services Division of Campus Safety and Emergency Services 029

More information

PEI/RP Recommended Practices for Installation of Bulk Storage Plants

PEI/RP Recommended Practices for Installation of Bulk Storage Plants PEI/RP800-08 Recommended Practices for Installation of Bulk Storage Plants Recommended Practices for Installation of Bulk Storage Plants CONTENTS Foreword...iii. SECTIONS 1. Introduction Page 1.1 Background...1

More information

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Changes to Chapter 62-761, Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Rule Organization The rule sections are reorganized a bit with separate sections now for:

More information

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Understanding the Colorado Annual Compliance Package William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Overview Required Documentation: UST / AST Annual Compliance Package Release

More information

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary

More information

Spill Prevention, Control, and Countermeasure. Training Module

Spill Prevention, Control, and Countermeasure. Training Module Spill Prevention, Control, and Countermeasure Training Module Topics to Cover Introduction Regulatory Background Piedmont/US Airways SPCC Plans Introduction What is SPCC? Spill: Refers to major and minor

More information

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities Connecticut Department of Energy and Environmental Protection Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities May 15, 2015 Peter Zack, Assistant

More information

New UST Installation Inspection Checklist

New UST Installation Inspection Checklist Nebraska State Fire Marshal Fuels Division - FLST Section 246 South 14 TH Street - Lincoln, NE 68508-1804 (402) 471-9466 New UST Installation Inspection Checklist (Petroleum or Hazardous Substances) Inspection

More information

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations Code Requirements for ASTs at Motor Vehicle-Dispensing Stations This table compares aboveground storage tank requirements in the 2015 edition of, to the 2015 International Fire Code (). Please note that

More information

Electrical Power Generator Use and Procurement Guidance

Electrical Power Generator Use and Procurement Guidance Electrical Power Generator Use and Procurement Guidance For compliance with applicable air emission control regulations December 2016 Prepared by: Syracuse University Environmental Health & Safety Services

More information

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations Code Requirements for ASTs at Motor Vehicle-Dispensing Stations This table compares aboveground storage tank requirements in the 2008 edition of NFPA 30A, and the 2006 International Fire Code (IFC). Please

More information

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit FINAL UNDERGROUND STORAGE TANK RULE CHANGES Heather Peters UST Compliance and Technology Unit Regulation Changes Federal Rule Based Changes Federal Regulations finalized in July 2015 Federal Rules effective

More information

NYSDEC PBS REGULATIONS Heating Oil Tanks

NYSDEC PBS REGULATIONS Heating Oil Tanks 1 NYSDEC PBS REGULATIONS Heating Oil Tanks Central Office/Region 2 Division of Environmental Remediation Bulk Storage Compliance Program NISTM 2017 New York Storage Tank Conference Saint Francis College,

More information

TANK SYSTEM DESIGN ASSESSMENT REPORT FOR FAC POND 5 TANK T-9001

TANK SYSTEM DESIGN ASSESSMENT REPORT FOR FAC POND 5 TANK T-9001 TANK SYSTEM DESIGN ASSESSMENT REPORT FOR FAC POND 5 TANK T-9001 [NOTE: To be added to the Permit in its entirety] Tank System Design and Assessment Report for Fac Pond 5 Tank T-9001 CWM Chemical Services,

More information

AIR QUALITY PERMIT. Kennesaw State University - Marietta Campus

AIR QUALITY PERMIT. Kennesaw State University - Marietta Campus AIR QUALITY PERMIT Permit No. Effective Date February 11, 2016 In accordance with the provisions of the Georgia Air Quality Act, O.C.G.A. Section 12-9-1, et seq and the Rules, Chapter 391-3-1, adopted

More information

Mark S. Morgan, Regulatory Counsel

Mark S. Morgan, Regulatory Counsel SUBJECT: ISSUE: PMAA CONTACT: EPA UST Regulations Final UST Rules Mark S. Morgan, Regulatory Counsel mmorgan@pmaa.org DATE: November 16, 2015 U.S. EPA FINAL UNDERGROUND STORAGE TANK REQUIREMENTS: I. BACKGROUND

More information

LOADING OF ORGANIC LIQUID CARGO VESSELS. (Adopted 10/13/1992, revised 1/18/2001)

LOADING OF ORGANIC LIQUID CARGO VESSELS. (Adopted 10/13/1992, revised 1/18/2001) RULE 346. LOADING OF ORGANIC LIQUID CARGO VESSELS. (Adopted 10/13/1992, revised 1/18/2001) A. Applicability The provisions of this rule shall apply to the transfer of organic liquids into an organic liquid

More information

P.O. Box 435 Saratoga Springs, NY 12866

P.O. Box 435 Saratoga Springs, NY 12866 Petroleum Storage Equipment Design, Installation & Maintenance September 7, 2016 As a family- and employee-owned business that owns its real estate, Stewart s puts a tremendous investment into our high

More information

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext.

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext. UNDERGROUND STORAGE TANK SYSTEM INSTALLATION/UPGRADE SUPPLEMENT For use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire (CFC); Chapter 6.7, Health

More information

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR Environmental Health - UST Program CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR As part of our inter-local contract with the Nevada Division of Environmental

More information

NYSDEC CBS Compliance Requirements

NYSDEC CBS Compliance Requirements NYSDEC CBS Compliance Requirements Peter J. Petriccione, P.E. H2M - Water September 24, 2015 Introduction Definition of a Hazardous Substance and a Chemical Bulk Storage Facility Design Requirements of

More information

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION Page 3 Federal law requires the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BUSTR) to inspect

More information

401 KAR 42:020. UST systems: design, construction, installation, and registration.

401 KAR 42:020. UST systems: design, construction, installation, and registration. 401 KAR 42:020. UST systems: design, construction, installation, and registration. RELATES TO: KRS 224.01, 224.10, 224.60, Chapter 322, Chapter 322A, 40 C.F.R. Part 280 Subpart B 42 U.S.C. 6991c, 6991e,

More information

Fuel Tank Management: PBS, USTs and the Energy Policy Act of 2005

Fuel Tank Management: PBS, USTs and the Energy Policy Act of 2005 Fuel Tank Management: PBS, USTs and the Energy Policy Act of 2005 Petroleum Bulk Storage 6NYCRR Part 612 614 EPA Underground Storage Tanks 40 CFR Part 280 PBS Program Overview PART 612 PART 613 PART 614

More information

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most.

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most. New UST Regulations The long awaited UST regulations were released by the EPA on June 22, 2015 and soon will be published in the Federal Register. The new regulations will go into effect 90 days after

More information

ANNUAL UST SYSTEM INSPECTION CHECKLIST

ANNUAL UST SYSTEM INSPECTION CHECKLIST APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date

More information

ECM environmental compliance monitoring, inc. 1

ECM environmental compliance monitoring, inc. 1 Regulated Storage Tanks & Automobile Dealerships in New York State Presented for NYSADA April 13, 2010 New York State Automobile Dealers Association By Scott Hubbard, C.H.M.M. of ECM environmental compliance

More information

SPCC Marina Inspection Update Oklahoma Marina Association Inspector Tom McKay

SPCC Marina Inspection Update Oklahoma Marina Association Inspector Tom McKay SPCC Marina Inspection Update - 2018 Oklahoma Marina Association Inspector Tom McKay Recent Compliance Assistance Documents 40 CFR 112 Final & Most Recent Regulation (7/1/15) Latest SPCC Inspection Checklists

More information

Coordination with the Spill Prevention, Control, and Countermeasures Plan

Coordination with the Spill Prevention, Control, and Countermeasures Plan 1.0 Introduction Purpose of Plan This plan covers Petroleum Storage Tanks (PSTs) and Petroleum, Oil, & Lubricants (POL) storage, under the responsibility of Fort Gordon located in the City of Augusta,

More information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information Papillion/La Vista Fire Marshal s Office Fuels Division FLST Section 146 rth Adams Street Papillion, NE 68046 (402) 829-1398 Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous

More information

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63 SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63 The attached SPCC Plan contains introductory information, a description of facilities and practices employed to prevent

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 8/12) ABOVEGROUND PETROLEUM STORAGE TANKS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu) INTRODUCTION Aboveground

More information

State of California AIR RESOURCES BOARD EXECUTIVE ORDER VR-302-B

State of California AIR RESOURCES BOARD EXECUTIVE ORDER VR-302-B State of California AIR RESOURCES BOARD EXECUTIVE ORDER VR-302-B Standing Loss Control Vapor Recovery System for New Installations of Aboveground Storage Tanks WHEREAS, the California Air Resources Board

More information

3) Storage at construction sites for refueling construction equipment; or. 4) Storage at airports as addressed in Section of this Part.

3) Storage at construction sites for refueling construction equipment; or. 4) Storage at airports as addressed in Section of this Part. TITLE 41: FIRE PROTECTION CHAPTER I: OFFICE OF THE STATE FIRE MARSHAL PART 180 STORAGE, TRANSPORTATION, SALE AND USE OF GASOLINE AND VOLATILE OILS SECTION 180.20 ABOVEGROUND STORAGE DISPENSING Section

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations

Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations ESAM Lunch and Learn Dartmouth, NS October 12, 2016 Part 2 of 2 Outline of Presentation 1. Purpose of the Regulations

More information

Code Requirements on Aboveground Storage Tanks Dispensing Fuels At Motor Vehicle Fuel-Dispensing Stations

Code Requirements on Aboveground Storage Tanks Dispensing Fuels At Motor Vehicle Fuel-Dispensing Stations Code Requirements What follows is a detailed chart developed by Steel Tank Institute s executive vice president, Wayne Geyer, P.E. Fire codes play a prominent role in tank purchase decisions. As such,

More information

Fire & Rescue District

Fire & Rescue District Michael G. Irvan Commissioner/ Administrative Chief Shelley Young Sr. Administrative Assistant Margaret Dimmick Commissioner Jeff Ramey Commissioner Fire & Rescue District FLAMMABLE LIQUID TANK INSTALL

More information

Operating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper

Operating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper UPDATED 2016 Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists EPA 510-K-16-001 Printed on Recycled Paper EPA wrote this booklet for owners and operators of underground

More information

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application

More information

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3 BUREAU OF STANDARDS Effective Date: 8/19/2016 Section No. 4 Version: 1.2 Procedure No. 3 TITLE: LP Gas Bulk Plant Final Inspection PURPOSE: This document details the procedures used to conduct a Final

More information

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Larrabee Shop Winning Bid PERMIT FEES, FORMS, PLANS and NOTIFICATIONS Secure all necessary state and local permits

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 3/14) UNDERGROUND STORAGE TANKS SUMMARY OF REGULATORY REQUIREMENTS Underground storage tanks (UST) are defined as tanks containing petroleum or other regulated substances

More information

Focus on the engineering & permitting requirements for installing a new fuel facility at the Port of Olympia;

Focus on the engineering & permitting requirements for installing a new fuel facility at the Port of Olympia; Port of Olympia Marine Fueling Station Project Fuel Dock Design Overview KPFF Consulting Engineers April 8, 2015 Fueling Station ti Feasibility Analysis Focus on the engineering & permitting requirements

More information

4.5 Fueling. Best Management Practices LEGAL REQUIREMENTS. Safe Practice FUELING

4.5 Fueling. Best Management Practices LEGAL REQUIREMENTS. Safe Practice FUELING 4.5 Fueling Fueling dock at Hewitt s Cove Marina. For many marinas, fueling boats is an essential service to boaters and an important revenue generator. Marinas with fueling services must evaluate all

More information

Overview of an Underground Storage Tank Inspection

Overview of an Underground Storage Tank Inspection Overview of an Underground Storage Tank Inspection PURPOSE OF INSPECTION Protect drinking water, lakes, streams, etc. Education. Protect property value. TECHNICAL ASSISTANCE INSPECTIONS Technical Assistance

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Rocky Mountain Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system

More information

Storage Tank Risk Management Solutions Leak

Storage Tank Risk Management Solutions Leak Storage Tank Risk Management Solutions Leak Prevention and Tank Integrity Inspections for ASTs Brian Pine ATC Group Services NISTM 8th Annual Pennsylvania Storage Tank Conference 1 2 ATC GROUP SERVICES

More information

Ohio s Used Oil Regulations for Generators

Ohio s Used Oil Regulations for Generators Ohio s Used Oil Regulations for Generators Dan Sowry Office of Compliance Assistance & Pollution Prevention January 29 th, 2013 What we will cover Definition Generator responsibilities On-site management

More information

ADDENDUM #1. A. Alternate Bid Item #3A - The procurement and installation of a new 12,000 gallon UL 2085 rated AGT tank for

ADDENDUM #1. A. Alternate Bid Item #3A - The procurement and installation of a new 12,000 gallon UL 2085 rated AGT tank for ADDENDUM #1 The Plymouth Airport Commission is committed to fulfilling the New Fuel Farm Facility project within the scope of the permit, not exceeding our funding and to satisfy the time constraint associated

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

NEIWPCC-Defender Spill Containment. Interstice Monitoring-Testing - Maintenance

NEIWPCC-Defender Spill Containment. Interstice Monitoring-Testing - Maintenance NEIWPCC-Defender Spill Containment Interstice Monitoring-Testing - Maintenance DISCLAIMER Only certified contractors should perform maintenance on and/or install the products shown in this presentation.

More information

APPLICATION for BUSINESS LICENSE Licensing & Permits City of Williston PO Box 1306, Williston, ND

APPLICATION for BUSINESS LICENSE Licensing & Permits City of Williston PO Box 1306, Williston, ND APPLICATION for BUSINESS LICENSE Licensing & Permits City of Williston PO Box 1306, Williston, ND 58801 cityauditor@ci.williston.nd.us BULK STORAGE & HANDLING OF FLAMMABLE LIQUIDS & HAZARDOUS MATERIALS

More information

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES PLEASE READ THESE INSTRUCTIONS BEFORE PLACING BATTERIES INTO SERVICE. THESE INSTRUCTIONS MUST BE SHIPPED WITH THE BATTERY AND MUST BE DELIVERED TO THE USER. INSTALLATION AND OPERATING INSTRUCTIONS FOR

More information

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES CHAPTER 23 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES SECTION 2301 GENERAL 2301.1 Scope. Automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor

More information

YOUR SPCC PROGRAM: A CHECK UP

YOUR SPCC PROGRAM: A CHECK UP YOUR SPCC PROGRAM: A CHECK UP Avoid Common Issues Seen with SPCC Programs Amy M. Reed, P.E. SAFETY MOMENT PEDESTRIAN/RUNNER SAFETY Stay on the sidewalk where sidewalks are provided it s the law! If you

More information

NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING

NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING Presented by: The New York State Association of Service Stations and Repair Shops AT LEAST ONE TRAINED C OPERATOR MUST BE ON DUTY

More information

Tank Filling Systems. for Petroleum Products

Tank Filling Systems. for Petroleum Products Tank Filling Systems for Petroleum Products Tank Filling Systems for Petroleum Products page 2 What Is It Used For? Generally used with aboveground storage tanks, although some underground uses as well.

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

NCDEQ Underground Storage Tank Section

NCDEQ Underground Storage Tank Section NCDEQ Underground Storage Tank Section Operation And Maintenance Manual Revised 10/30/2015 i Table of Contents CHAPTER 1. INTRODUCTION... 1 A. Why an Operation and Maintenance Manual?... 1 B. Benefits

More information

Tune-up Information. Owners and operators of all biomass-fired and oil-fired area source boilers.

Tune-up Information. Owners and operators of all biomass-fired and oil-fired area source boilers. Tune-up Information National Emission Standards for Hazardous Air Pollutants for Area Sources: Industrial, Commercial, and Institutional Boilers 40 CFR Part 63 Subpart JJJJJJ Who must conduct a tune-up

More information

PETROLEUM PRODUCT STORAGE TANK REGULATION SAFETY AND BUILDINGS DIVISION BUREAU OF PETROLEUM INSPECTION AND FIRE PROTECTION

PETROLEUM PRODUCT STORAGE TANK REGULATION SAFETY AND BUILDINGS DIVISION BUREAU OF PETROLEUM INSPECTION AND FIRE PROTECTION PETROLEUM PRODUCT STORAGE TANK REGULATION SAFETY AND BUILDINGS DIVISION NOTE: THIS OUTLINE SHOULD NOT BE USED AS A DOCUMENT FOR DETERMINING AN OWNER'S SPECIFIC REQUIREMENTS FOR COMPLIANCE. THE FEDERAL

More information

Environment Canada (EC) Storage Tank System Identification Form

Environment Canada (EC) Storage Tank System Identification Form Environment Canada (EC) Storage Tank System Identification Form Identification of storage tank systems for the purpose of the Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations

More information

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists

More information

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Contents How to Use This Booklet...1 Section 1 Identifying The Equipment At Your UST Facility...3

More information

REVISOR CKIWru. t.tz 42, section 692L et seq.; or. A. system holding: (! a mixture of such hazardous waste and other regulated substances; {!

REVISOR CKIWru. t.tz 42, section 692L et seq.; or. A. system holding: (! a mixture of such hazardous waste and other regulated substances; {! a-' 06119118 REVISOR CKIWru RD4360 1.1 1.2 1.3 1.4 Pollution Control Agency Proposed Permanent Rules Relating to Underground Storage Tanks 71.50.001.0 APPLICABILITY. [For text of subp I, see M.R.I 1.5

More information

Title: Jet Engine Test Cell

Title: Jet Engine Test Cell Environmental Standard Operating Procedure Originating Office: Revision: Prepared By: Approved By: MCAS Miramar Environmental Original Environmental Management Department William Moog Management Department

More information

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES CHAPTER 22 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES SECTION 2201 GENERAL 2201.1 Scope. Automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor

More information

These regulations are created pursuant to and of the Colorado Revised Statutes.

These regulations are created pursuant to and of the Colorado Revised Statutes. DEPARTMENT OF LABOR AND EMPLOYMENT Division of Oil and Public Safety RETAIL NATURAL GAS (CNG/LNG) REGULATIONS 7 CCR 1101-16 [Editor s Notes follow the text of the rules at the end of this CCR Document.]

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

Underground Storage Tank. City of Burbank UST Owners & Operators

Underground Storage Tank. City of Burbank UST Owners & Operators Underground Storage Tank City of Burbank UST Owners & Operators Created by: Kern County Environmental Health CUPA, Edited by: Burbank Fire Department for the Burbank Fire Department s use Burbank Fire

More information

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section 6. Tanks - Leak Detection NCDENR Division of Waste Management Underground Storage Tank Section Why conduct Leak Detection? Required for regulated systems: EXCEPTIONS: Temporarily closed tanks Emergency

More information

PURPOSE RESPONSIBILITY

PURPOSE RESPONSIBILITY PAGE 1 OF 6 PURPOSE This Standard Operating Procedure (SOP) provides guidance and methods for Underground Storage Tank (UST) inventory control at Massachusetts Department of Transportation, Highway Division

More information

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist.

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist. Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition Compliance Checklist Note: The requirements noted against the various sections in this checklist

More information

PENNSYLVANIA ABOVE GROUND STORAGE TANKS

PENNSYLVANIA ABOVE GROUND STORAGE TANKS PENNSYLVANIA ABOVE GROUND STORAGE TANKS GZA GeoEnvironmental Inc. by Jeffrey Knepper, LRS, CPG July 27, 2017 PA CODE Chapter 245. Administration of the Storage Tank & Spill Prevention Program AST Definition

More information

540 CMR: REGISTRY OF MOTOR VEHICLES 540 CMR 22.00: MISCELLANEOUS MOTOR VEHICLE AND TRAILER EQUIPMENT AND OPERATIONS REQUIREMENTS

540 CMR: REGISTRY OF MOTOR VEHICLES 540 CMR 22.00: MISCELLANEOUS MOTOR VEHICLE AND TRAILER EQUIPMENT AND OPERATIONS REQUIREMENTS 540 CMR 22.00: MISCELLANEOUS MOTOR VEHICLE AND TRAILER EQUIPMENT AND OPERATIONS REQUIREMENTS Section 22.01: Scope and Purpose 22.02: Display of Reflectorized License Plates 22.03: Minimum Standards for

More information

On-Demand Mobile Fueling

On-Demand Mobile Fueling 2017 NFPA Conference & Expo On-Demand Mobile Fueling Andrew Henning Supervising Deputy State Fire Marshal CAL FIRE Andrew Klein Principal A S Klein Engineering Lynne Kilpatrick Fire Marshal Sunnyvale Public

More information

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer Exhibit 2 System Specifications This exhibit contains the installation, maintenance and compliance standards and specifications

More information

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities New Ulm Public Utilities Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities INDEX Document Review and History... 2 Definitions... 3 Overview... 3 Application

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES PLEASE READ BEFORE PLACING BATTERIES IN SERVICE THESE INSTRUCTIONS TO BE SHIPPED WITH BATTERY AND TO BE DELIVERED TO USER INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES

More information

Form UST FP-290 Notification for Underground Storage Tanks Regulated Under 527 CMR 9.00

Form UST FP-290 Notification for Underground Storage Tanks Regulated Under 527 CMR 9.00 Massachusetts Department of Environmental Protection Underground Storage Tank Program Form UST FP-290 Notification for Underground Storage Tanks Regulated Under 527 CMR 9.00 Forward completed form to:

More information

OIL SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN. St. Lawrence University Canton, New York. January 2007

OIL SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN. St. Lawrence University Canton, New York. January 2007 OIL SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN St. Lawrence University Canton, New York January 2007 Revised April 30, 2008 Revised December 1, 2008 Revised December 1, 2009 TABLE OF CONTENTS SECTION

More information

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program As part of our commitment to support renewable energy, Kissimmee Utility Authority

More information

Environmental Management System

Environmental Management System POLICY REQUIREMENTS Page 1 of 7 All requirements under Dangerous Goods POLICY apply ALL tanks are to be constructed to an applicable, approved design standard and are to meet all legislative and policy

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates

More information

MINIMUM REQUIREMENTS FOR PLACEMENT ON ROTATION

MINIMUM REQUIREMENTS FOR PLACEMENT ON ROTATION MANAGEMENT DIRECTIVE TOWING ROTATION LIST RULES Promulgated Pursuant to the Administrative Procedures Act Authority - Ark. Code Ann. 12-8-106(a)(2) Effective date - June 6, 2005 RULE 1: OWNER S PREFERENCE

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Sound Enclosure and Subbase Fuel Tank Package Applicable to the following models: KD800 - KD2500 (includes KD1250-A) Level 1 Sound Enclosure with Lift Base Sound Level

More information