ABL FIRE PROTECTION RALEIGH, NORTH CAROLINA

Size: px
Start display at page:

Download "ABL FIRE PROTECTION RALEIGH, NORTH CAROLINA"

Transcription

1 ABL FIRE PROTECTION RALEIGH, NORTH CAROLINA Job Name : Building : TOWER Location : 4501 CREEDMOOR ROAD RALEIGH NORTH CAROLINA System : 16-1TH FLOOR Contract : Data File : SOLEIL 16-1.WXF

2 ABL FIRE PROTECTION Page 1 Hydraulic Design Information Sheet Name - SOLEIL CENTER Location CREEDMOOR ROAD RALEIGH NORTH CAROLINA Building - TOWER System No TH FLOOR Contractor - Contract No. - Calculated By - JSB Drawing No. - FP-43 Construction: ( ) Combustible (X) Non-Combustible Ceiling Height - VARIES Occupancy - MECHANICAL S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By E M Area of Sprinkler Operation System Type Sprinkler/Nozzle Density -.2 (X) Wet Make VIKING D Area Per Sprinkler ( ) Dry Model M E Elevation at Highest Outlet ( ) Deluge Size 1/2 S Hose Allowance - Inside ( ) Preaction K-Factor 5.6 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside N Note 720 GALLONS ADDED FOR DOMESTIC WATER Calculation Flow Required Press Required AT PUMP DISCHARGE Summary C-Factor Used: 150 Overhead 150 Underground W Water Flow Test: Pump Data: Tank or Reservoir: A of Test - Cap. - T Time of Test - Rated Cap Elev.- E Static Press - Press R Residual Press - 92 Elev. - 0 Well Flow Proof Flow S Elevation - 0 U P Location - P L Source of Information - Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided:

3 Water Supply Curve (C) ABL FIRE PROTECTION Page 2 City Water Supply: Pump Data: Demand: C1 - Static Pressure : 106 C2 - Residual Pressure: 92 C2 - Residual Flow : 1470 City Water Adjusted to Pump Inlet for Pf - Elev - Hose Flow A1 - Adjusted Static: A2 - Adj Resid : 1000 A3 - Adj Resid : 1500 P1 - Pump Churn Pressure : 198 P2 - Pump Rated Pressure : 180 P2 - Pump Rated Flow : 1000 P3 - Pump Max Flow : 117 P3 - Pump Max Flow : 1500 City Residual 0 = City Residual 20 = City 150% of Pump = D1 - Elevation : D2 - System Flow : D2 - System Pressure : Hose ( Adj City ) : 870 Hose ( Demand ) : 100 D3 - System Demand : Safety Margin : Al + P1 260 P 240 R 220 E 200 S 180 S 160 U 140 R 120 E C1 D1 A1 D2 D3 A2 + P2 A2 A3 + P3 C2 A FLOW ( N ^ 1.85 )

4 Fittings Used Summary ABL FIRE PROTECTION Page 3 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ B Generic Butterfly Valve E 90' Standard Elbow F 45' Elbow G Generic Gate Valve Mb B Ball Milw BB-SC S Generic Swing Check Valve T 90' Flow thru Tee Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Zai Ames 4000SS Fitting generates a Fixed Loss Based on Flow

5 Pressure / Flow Summary - STANDARD ABL FIRE PROTECTION Page 4 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req na na na na H na na na H na H na na na na na na na na H na na 11A na na na na na na na na na na 16TH na 10 LZT na CON na LZD na LZS na RED na MF na DI na HDI na 15 HD na 72 POC na The maximum velocity is and it occurs in the pipe between nodes 21 and 22

6 Final Calculations - Hazen-Williams ABL FIRE PROTECTION Page 5 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn K Factor = 5.60 to Vel = T K Factor = 5.60 to Vel = K Factor = F K Factor = 5.60 to Vel = T K Factor = 5.60 to Vel = K Factor = H T K Factor = 5.60 to Vel = K Factor = K Factor = 5.60 to Vel = T K Factor = 5.60 to Vel = K Factor = H T K Factor = 5.60 to Vel = K Factor = H T K Factor = 5.60 to Vel = to Vel = T K Factor = 5.60 to Vel = 9.03

7 Final Calculations - Standard ABL FIRE PROTECTION Page 6 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn K Factor = T K Factor = 5.60 to Vel = K Factor = T K Factor = 5.60 to Vel = E to Vel = K Factor = 5.60 to Vel = E K Factor = 5.60 to Vel = K Factor = H T K Factor = 5.60 to Vel = T to Vel = K Factor = A T K Factor = 5.60 to Vel = K Factor = to Vel = to Vel = to Vel = 9.24

8 Final Calculations - Standard ABL FIRE PROTECTION Page 7 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn to Vel = to Vel = to Vel = E to 120 2T Vel = E to 120 1Mb Vel = to * Fixed loss = 15 16TH Vel = TH E Qa = 100 to 120 1T LZT B Vel = 5.88 LZT T to 120 1B CON Vel = 5.88 CON S to 120 1E * Fixed loss = 10 LZD B Vel = K Factor = System Demand Pressure Safety Margin Continuation Pressure Pump Outlet Pressure From Pump Curve Pump Inlet LZS E to 120 1G RED T Vel = 5.88 RED B to 120 1T MF Vel = 3.49

9 Final Calculations - Standard ABL FIRE PROTECTION Page 8 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn MF Zai to 120 1E * Fixed loss = DI Vel = 3.49 DI F to 140 1G HDI T Vel = E HDI F Qa = 150 to 140 1T HD G Vel = 2.83 HD F Qa = 720 to 140 2G * Fixed loss = POC Zaf Vel = K Factor =

ABL FIRE PROTECTION 300 HOKE STREET RALEIGH, NC

ABL FIRE PROTECTION 300 HOKE STREET RALEIGH, NC ABL FIRE PROTECTION 300 HOKE STREET RALEIGH, NC 919-835-2225 Job Name : Building : TOWER Location : 4501 CREEDMOOR DR RALEIGH NORTH CAROLINA System : 18TH-2 FLR Contract : Data File : SOLEIL 18-2TH.WXF

More information

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS 815-463-9985 Job Name : 66 ORLAND SQUARE DRIVE - MRA 1 Building : FP1 Location : 66 ORLAND SQUARE DRIVE, ORLAND PARK, ILLINOIS System : MRA

More information

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS 815-463-9985 Job Name : 66 ORLAND SQUARE DRIVE - MRA 3 Building : FP1 Location : 66 ORLAND SQUARE DRIVE, ORLAND PARK, ILLINOIS System : MRA

More information

SA COMUNALE 1399 OHLEN AVENUE COLUMBUS, OHIO

SA COMUNALE 1399 OHLEN AVENUE COLUMBUS, OHIO SA COMUNALE 1399 OHLEN AVENUE COLUMBUS, OHIO 43211 614-291-7001 Job Name : DREXEL DORMS CORRIDOR Drawing : 2 OF 2 Location : 25721 COSHOCTON ROAD Remote Area : 1 Contract : 56597-036 Data File : CORRIDOR

More information

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS. Page 1 of Telephone: 29-95-9501 Technical Services: 877-38-5 Fax: 29-818-180 Email: techsvcs@vikingcorp.com 1. GENERAL DESCRIPTION The Halar Coated Concentrate Control (CCV) is utilized in Viking foam

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 407 Rev. T Model E Alarm Check Valve Bulletin 407 Rev. T Instructions for Installation, Operation, Care and Maintenance 4 (100 mm), 6 (150 mm), 8 (200 mm) Sizes With Model E3 Trim Listed by Underwriters

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 59 Model DDX Deluge Valve (50 mm), ½ (65 mm), (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (00 mm) Bulletin 59 Instructions for Installation, Operation, Care and Maintenance Wet Pilot Line,

More information

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 inch to inch (DN40 to DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

TECHNICAL DATA. mixture, with a freeze temperature

TECHNICAL DATA. mixture, with a freeze temperature September 16, 2005 45 a 1. SYSTEM DESCRIPTION The Viking ESFR Cold Storage System is fixed fire protection for refrigerated or cold warehouse storage. This system is also appropriate for unheated storage

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Acceptance Inspection Date of Review / / BLD20 - Project Address: Project Name: Numbers following worksheet comments represent an NFPA

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev.C Bulletin 507 Rev.C Instructions for Installation, Operation, Care and Maintenance 1 1 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TotalPac 3 Firecyle III Wet pipe Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Wet pipe low flow foam/water manifold system

Wet pipe low flow foam/water manifold system December 6, 2010 Foam 15a 1. Description With the Wet Pipe Low Flow Foam/Water Manifold System, multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev. D Bulletin 507 Rev. D Instructions for Installation, Operation, Care and Maintenance 1 1 / 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50 Instructions for Installation, Operation, Care and Maintenance Model AGCX Deluge Valve (50 mm), ½ (65 mm), 3 (80 mm), 4 (00 mm), 6 (50 mm), 8 (00 mm) Wet Pilot Line, Dry Pilot Line, and Electric Actuation

More information

TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Deluge system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/ Inch to Inch (DN40 to DN00) General Description The TYCO DV-5a Automatic

More information

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

Model DDX Deluge Valves 4 (100 mm), 6 (150 mm) and 165 mm Sizes Features 1. Differential-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat &

More information

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P S 1 of 9 1. DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction

More information

TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Deluge, Electric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

VALVE ASSEMBLY. Form No "A" "A" Parts List for: (1/4 N.P.T.F.-REF.) (1/4 N.P.T.F.-REF.)

VALVE ASSEMBLY. Form No A A Parts List for: (1/4 N.P.T.F.-REF.) (1/4 N.P.T.F.-REF.) Parts List for: Form No. 108100 SPX Corporation 5885 11th Street Rockford, IL 61109-3699 USA Internet Address: http://www.powerteam.com Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800)

More information

Model DDX Deluge Valve 8 (200mm) Features

Model DDX Deluge Valve 8 (200mm) Features Model DDX Deluge Valve 8 (200mm) Bulletin 514 Bulletin 514 Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot

More information

Technical Information

Technical Information IMPORTANT INFORMATION: Product must be installed and used in strict conformance with NFPA Pamphlet 58 and/or NFPA pamphlet 54 and all other codes, regulations and manufacturer recommendations. Failure

More information

Features 1. Differential Latch-type, lightweight, dependable

Features 1. Differential Latch-type, lightweight, dependable Bulletin 516 Rev. B Model DDX-SS Deluge Valve (100mm), (150mm) & (200mm) Bulletin 516 Rev. B Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by:

More information

DSC3/DSCA3, DSZ3. EBARA Submersible Sewage and Propeller Pumps. Technical Data Contents Project: Model: Chk d: Date:

DSC3/DSCA3, DSZ3. EBARA Submersible Sewage and Propeller Pumps. Technical Data Contents Project: Model: Chk d: Date: Technical Data Contents Section Page Motor Protection 3-238 Thrust Bearing Thermal Protection 3-239 Leakage Detector 3-20 Cable Entry 3-21 Cable Connector 3-21.1 Mechanical Seal Sectional DWG 3-22 Mechanical

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4 Page 1 of 5 Model F Dry Valve with Trim Valve Size Part Number 3 13764PTR 4 13765PTR 6 13766PTR Standard Trim Sets include galvanized nipples and fittings. 4 Dry Valve Shown General Notes: Notes: For use

More information

Data Sheet 3.03 Issue D

Data Sheet 3.03 Issue D Description Rapidrop Flexible Sprinkler Hose connects the sprinkler to the branch pipe. The flexible stainless steel hose and fittings are particularly suited for use in suspended ceiling applications.

More information

Installation & Design Maintenance for ILBP System

Installation & Design Maintenance for ILBP System Installation & Design Maintenance for ILBP System Before installation of the Chemguard ILBP system(s), check all components to ensure that no damage has occurred during shipment and read the manual before

More information

Data Sheet 3.01 Issue C

Data Sheet 3.01 Issue C Description Rapidrop Flexible Sprinkler Hose connects the sprinkler to the branch pipe. The flexible stainless steel hose and fittings are particularly suited for use in suspended ceiling applications.

More information

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA. Trimpac 249a. September 16, 2013 September 16, 2013 Trimpac 249a 1. DESCrIpTION DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked with a pneumatic release module in a metal enclosure.

More information

Chapter Quiz. Directions: Write the correct letter on the blank before each question.

Chapter Quiz. Directions: Write the correct letter on the blank before each question. Chapter 12 Quiz Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe dry-barrel and wet-barrel hydrants. 1. Most fire hydrants are made of: (605) A.

More information

In-Line Balanced Pressure Proportioner (ILBP) Proportioning Devices Model KBP

In-Line Balanced Pressure Proportioner (ILBP) Proportioning Devices Model KBP 1 General description The KCA In-Line balanced pressure proportioner (ILPB) is a foam proportioning device which is used to balance the higher foam concentrate pressure to the lower system water pressure

More information

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system (Optional) Description This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

HPH PCB/MALE CABLE HPH SERIES PERFORMANCE/SPECIFICATION

HPH PCB/MALE CABLE HPH SERIES PERFORMANCE/SPECIFICATION PCB/ CABLE Straight TBS, R/A TBS, male crimp, Flex SMT, solder bucket, stacking, pin carrier Pin size/current: 0.6mm/4 amp Pitch: 1.905mm/0.075" on a staggered pitch of 0.953mm/0.0375 No. of contacts:

More information

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA 1-1/2 (dn40) July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control

More information

Flammability Characterization of Li-ion Batteries in Bulk Storage

Flammability Characterization of Li-ion Batteries in Bulk Storage Flammability Characterization of Li-ion Batteries in Bulk Storage Benjamin Ditch Global Research Update: High Challenge Storage Protection 22 May 2014, London, England Goal Develop sprinkler protection

More information

Foam Ratio Controller Proportioning Devices Model KFP

Foam Ratio Controller Proportioning Devices Model KFP 1 General description The KCA ratio controller accurately proportions foam concentrate into a water stream over a wide range of water flow rates. The controller proportions foam at concentrations of 1%

More information

Flood Dosed System Worksheet

Flood Dosed System Worksheet Number of bedrooms Flood Dosed System Worksheet Septic tank size Minimum 1000 gallons Dosing tank size Minimum 800 gallons or 1 bedroom smaller than septic tank size whichever is larger Filter: gravity(in

More information

Easy Riser swing check valve Models E-1 & F-1

Easy Riser swing check valve Models E-1 & F-1 Page 1 of 7 1. DESCRIPTION The Viking Easy Riser Swing Check Valve is a general purpose rubber-faced approved for use in fire service systems. The valve is for use in wet system risers, preaction system

More information

PARTS MANUAL FOR HEAVY DUTY GAS BROILERS

PARTS MANUAL FOR HEAVY DUTY GAS BROILERS PARTS MANUAL FOR HEAVY DUTY GAS BROILERS CERAMIC MODELS Model HCB00 HCB HMCB HCB1 HCB SUNGLOW MODELS Model IR1 IR IR MODEL GHCBO0 SHOWN FORM 0907 (10-9) VULCAN-HART COMPANY, P.O. BOX 696, LOUISVILLE, KY

More information

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P) 1 of 9 1. DESCRIPTION The Viking 2 (DN50) is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction sprinkler

More information

GW THERMOCOOL NOZZLE STRUCTURAL STEEL PROTECTION

GW THERMOCOOL NOZZLE STRUCTURAL STEEL PROTECTION DESCRIPTION The GW Thermocool nozzle is a reverse action open nozzle. It is designed for fire protection of structural steel, and the specially developed water distribution pattern provides protection

More information

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE Page 1 of 20 1. DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked preaction system with a pneumatic release module in a metal enclosure. The standard

More information

Lift Repair Parts for. Mohawk Lifts. Table of Contents - Parts for Mohawk Models A System 1A LMF TP-15...

Lift Repair Parts for. Mohawk Lifts. Table of Contents - Parts for Mohawk Models A System 1A LMF TP-15... Lift Repair Parts for Mohawk Lifts Table of Contents - Parts for Mohawk Models -7...2 5 System 1...6 9 LMF-12...10 12 TP-15...10 12 Parts for Model -7 1 BH-7341-22 601-300-045 Power Unit 2 BH-7340-51 601-410-030

More information

Wet alarm valves. Wet alarm valves. CE trim

Wet alarm valves. Wet alarm valves. CE trim Description Usually, a wet alarm valve station includes: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges

More information

Model VKFD28 Flexible Sprinkler Drops (LPCB Approved) Installation Manual. January 2016 Form No. F_ Rev 16.1

Model VKFD28 Flexible Sprinkler Drops (LPCB Approved) Installation Manual. January 2016 Form No. F_ Rev 16.1 Model VKFD28 Flexible Sprinkler Drops (LPCB Approved) Installation Manual January 2016 Page 2 of 10 TABLE OF CONTENTS Section Description Page 1 Benefits 3 2 Installation Instructions 3 3 Technical Data

More information

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Non interlock Preaction system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

FireFlex DUAL Single Interlock, Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler system combined with a clean agent fire extinguishing

More information

SPRING LOADED VENTS. Set Points of 3 PSIG and Above PROTECTOSEAL

SPRING LOADED VENTS. Set Points of 3 PSIG and Above PROTECTOSEAL SPRING LOADED VENTS Set Points of 3 PSIG and Above PROTECTOSEAL SERIES STYLE 9540 End-of-Line Pressure/Vacuum Breather Vent 19540 Pipe-Away Pressure/Vacuum Breather Vent 9240 End-of-Line Vacuum Relief

More information

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description Worldwide Contacts www.tycofire.com DV Deluge Valve, Diaphragm Style, / thru Inch (DN0 thru DN00), Deluge System Wet Pilot Actuation General Description The DV Deluge Valve (described in Technical Data

More information

TECHNICAL DATA. Table Standard Materials

TECHNICAL DATA. Table Standard Materials Page 1 of 9 1. GENERAL DESCRIPTION The In-Line Balanced Pressure (ILBP) Proportioner is a foam proportioning device which is used to balance the higher foam concentrate pressure to the lower system water

More information

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804 Worldwide Contacts www.tyco-fire.com Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The Type D3S Protectospray Nozzles are open (non-automatic) directional

More information

Instructions for Installation, Operation Care and Maintenance

Instructions for Installation, Operation Care and Maintenance Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.

More information

model E Spray nozzles vk810 - vk817

model E Spray nozzles vk810 - vk817 Page 1 of 10 1. DESCRIPTION Viking Model E, 3D Spray Nozzles are open type spray nozzles designed for directional spray applications in fixed fire protection systems. They have an open design only (nonautomatic)

More information

Model F1 Model F1 Recessed Standard Response Sprinklers

Model F1 Model F1 Recessed Standard Response Sprinklers The Designer Model F Standard Upright Standard Pendent Extended Coverage Pendent Conventional Vertical Sidewall HSW Deflector Extended Coverage EC-6 Deflector The Designer II Model F Recessed Recessed

More information

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data Worldwide Contacts www.tyco-fire.com Model CV-FR Grooved-End Riser Check Valves Inch to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Grooved- End Riser Check Valve is a compact and rugged

More information

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER

More information

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description The TYCO Aluminum Bronze DV-5 Deluge Valves are available to provide an alternative material

More information

GENERAL ELECTRIC CONCEALED CHILLED WATER FAN COIL UNITS

GENERAL ELECTRIC CONCEALED CHILLED WATER FAN COIL UNITS GENERAL ELECTRIC CONCEALED CHILLED WATER FAN COIL UNITS ACWL Series ACWL0 thru ACWL4 00 CFM thru 400 CFM GE_ACWL_series.indd 3// : PM CONTENTS Model decoding 3 Unit features 3 Standard specifications 3-4

More information

Installation Instructions

Installation Instructions Contents Page General Information and Installer Tips.......... 2 Panels & Posts............................. 3 Enclosure Description..................... 4 Hinge Door Hardware................... 4-5 Step-by-Step

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model D Dry Pipe Valve Bulletin 350 Rev. S Bulletin 350 Rev. S Instructions for Installation, Operation, Care and Maintenance 4 (100mm) 6 (150mm) Valve With Model D Trimmings Listed by Underwriters Laboratories,

More information

HOUR DESPATCH. double sided

HOUR DESPATCH. double sided 56 Wall Racks Wall Storage 2 or 3 cylinder units for 2 cylinder sizes. These racks must be fixed to the wall at a height of at least two-thirds of cylinder height. Supplied with pre-drilled fixing holes.

More information

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST Date Documents Submitted: Log No.: File No.: Plan Examiner: Permit No.: Property Information Building Name: Building Address: Building Manager's Name: Building Manager's Phone: Fax: System Designer/Contractor

More information

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5a Automatic

More information

Below is quick summary of the pumping capabilities of each alternative:

Below is quick summary of the pumping capabilities of each alternative: Memorandum June 8, 17 To: From: cc: Re: Michael Bumbaco, City of Virginia Beach Scott Morrow, Hazen and Sawyer Emiliee Auyang-Jessen, City of Virginia Beach Mark Jones, City of Virginia Beach North Sherwood

More information

Application & Reference Data Typical Specifications. Section 914 Vertical Turbine Fire Pump

Application & Reference Data Typical Specifications. Section 914 Vertical Turbine Fire Pump Section 914 Page 101 Supersedes Section 913 Page 101 Dated November 1, 199p Application & Reference Data Typical Specifications Section 914 Section 914 Page 102 Supersedes Section 913 Page 102 Dated November

More information

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME.

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME. FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME. DATA SHEET INDEX 36m x 19mm FIRE HOSE REEL RISER INSTALLATION DETAIL

More information

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

SOLID CONE SPRAY NOZZLES TECHNICAL DATA

SOLID CONE SPRAY NOZZLES TECHNICAL DATA November 2, 2007 Spray Nozzle 20 SOLID CONE SPRAY NOZZLES 1. DESCRIPTION Viking Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles are non-automatic pattern, open, directional discharge spray

More information

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 13, 2007 Spray Nozzle 31a 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however

More information

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however they may be ordered

More information

1 CHASSIS, AEP, ASSY, E1000-C, E2000-C, E3000-C 1 JP TANK, SOLUTION, STEEL, PAINTED, 6GAL, ASSY 1 JP7725-A 3 PANEL, COVER, REAR, STEEL,

1 CHASSIS, AEP, ASSY, E1000-C, E2000-C, E3000-C 1 JP TANK, SOLUTION, STEEL, PAINTED, 6GAL, ASSY 1 JP7725-A 3 PANEL, COVER, REAR, STEEL, 1 CHASSIS, AEP, ASSY, E1000-C, E2000-C, E3000-C 1 JP7712 2 TANK, SOLUTION, STEEL, PAINTED, 6GAL, ASSY 1 JP7725-A 3 PANEL, COVER, REAR, STEEL, PAINTED, AEP 1 JP7729 4 WHEEL, PNEUMATIC, 10"ODX3/4"ID, BALL

More information

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet) Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off

More information

CHAPTER 7 PUMPING SYSTEM DESIGN

CHAPTER 7 PUMPING SYSTEM DESIGN CHAPTER 7 PUMPING SYSTEM DESIGN 7-1. FORCE MAIN HYDRAULICS. a. General. The pipeline which receives waste-water from a pumping station, and conveys it to the point of discharge, is called a force main.

More information

McQuay. Central Station Air Handlers Low Pressure. LHD, LYF, LSL, LML, LWL Vintage C. LML, LSB Vintage E. Last Manufactured: 1999

McQuay. Central Station Air Handlers Low Pressure. LHD, LYF, LSL, LML, LWL Vintage C. LML, LSB Vintage E. Last Manufactured: 1999 Replacement Parts List No. 055222600 Revision F 11/2011 McQuay Central Station Air Handlers Low Pressure LHD, LYF, LSL, LML, LWL 103-228 Vintage C LML, LSB 106-111 Vintage E Last Manufactured: 1999 To

More information

HT and VHT High pressure pumps

HT and VHT High pressure pumps Horisontal type HT and Vertical type VHT The HT and VHT models are multi-stage centrifugal pumps. The number of stages depends on the required head. The number of stages is variable, and the pump running

More information

GF-SERIES GLOBALFRAME CABINET SYSTEM

GF-SERIES GLOBALFRAME CABINET SYSTEM P R O D U C T D ATA S H E E T GF-SERIES GLOBALFRAME CABINET SYSTEM K E Y F E AT U R E S Cost-effective cabinet solution adaptable to server, network and mixed-use applications Available in two configurations

More information

Air Handling Unit Fan Selection Guide

Air Handling Unit Fan Selection Guide KEES Air Handling Unit Fan Selection Guide This document applies to models: DFG Direct Fired Gas Heater IFG Indirect Fired Gas Heater MUA Tempered Air NTS Non-Tempered Supply Table of Contents: Page 2-4

More information

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 244a. April 15, 2011 April 15, 2011 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally required

More information

NFPA , Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY

NFPA , Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY NFPA 25-2017, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY 1) NFPA 25 REVISION SUMMARY For the 2017 edition, new fire pump terms are defined

More information

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

A Division of Nailor International Inc. ECONOMY AIR HANDLERS A Division of Nailor International Inc. MODEL : ECONOMY AIR HANDLERS Thermal Model Standard Specification MODEL 800-4000 CFM AIR HANDLERS Description Model air handlers are designed for efficient and economical

More information

Engineering & Design Data

Engineering & Design Data PVC & CPVC Corrosion Resistant Industrial Pressure Pipe Engineering & Design Data Engineering & Design Data Hydraulic Shock Hydraulic shock is the term used to describe the momentary pressure rise in a

More information

PRODUCT DATA. Tower system. The tower system can be. Higher loads per parking. upon request

PRODUCT DATA. Tower system. The tower system can be. Higher loads per parking. upon request KLAUS Multiparking GmbH Hermann-Krum-Straße D-889 Aitrach Fon +9 (0 ) 75 65 5 08-0 Fax +9 (0 ) 75 65 5 08-88 info@multiparking.com www.multiparking.com PRODUCT DATA system The automatic shelf system optimally

More information

Head - m. Flow - US gpm. Comments. Customer : Contact : Re Cotizacion Metro Linea 4 EDB Project : Quote No. :

Head - m. Flow - US gpm. Comments. Customer : Contact : Re Cotizacion Metro Linea 4 EDB Project : Quote No. : Customer : Project : Re Cotizacion Metro Linea 4 Page No : 3 Contact : Phone : Fax : Type: PVF - In-Line Close Coupled Fire Item : RCI Electrica Pump Model: Nom. Speed: 2950 RPM, 50 Hz Electric Impeller

More information

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation Deluge Valve DV-5 Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation GeneralDescription The Model DV-5 Deluge Valve (described in Technical

More information

TECHNICAL DATA SPRINKLER ESCUTCHEONS

TECHNICAL DATA SPRINKLER ESCUTCHEONS Page 1 of 8 1. DESCRIPTION Viking sprinkler escutcheons are ornamental plates used with ½ NPT (15 mm BSP)*, and ¾ NPT (20 mm BSP)* pendent sprinklers. The escutcheons are installed between the sprinklers

More information

Tray Box Former. Parts List & Illustrations FIGURE 8-28A RAIL & FINGER ASSEMBLY AUTO LIDDER ~ = VARIABLE PART. W. E. Plemons Machinery Services, Inc.

Tray Box Former. Parts List & Illustrations FIGURE 8-28A RAIL & FINGER ASSEMBLY AUTO LIDDER ~ = VARIABLE PART. W. E. Plemons Machinery Services, Inc. FIGURE 8-28A RAIL & FINGER ASSEMBLY ITEM PART NO. DESCRIPTION QTY. 1 0032700 BAR, LID HOPPER GUIDE MT (34") 1 ~ 0032701 BAR, LID HOPPER GUIDE MT (42") 1 2 0061300 SUPPORT PAD, LIDDER 1 3 0033800 LEFT RAIL,

More information

- (Ref , P. Block 001) - (Ref , P. Block 301) - (Ref , P. Block 301)

- (Ref , P. Block 001) - (Ref , P. Block 301) - (Ref , P. Block 301) ENGINE PUMP PRESSURE SWITCH 113GK (112GK) REMOVAL/INSTALLATION WARNING: 1. Equipment and Materials CHECK THAT THE LANDING GEAR GROUND SAFETIES INCLUDING WHEEL CHOCKS ARE IN POSITION. BEFORE APPLING OR

More information

VERTICAL MULTI-STAGE PUMPS

VERTICAL MULTI-STAGE PUMPS VR SERIES - 6 HZ FEATURES All 316 SS hydraulic components for superior durability, efficiency, and performance over a wide variety of applications Rugged NEMA motor mounting with oversized ball bearings

More information

Level 2 NVQ Diploma in Specialist Installation Occupations (Construction)

Level 2 NVQ Diploma in Specialist Installation Occupations (Construction) Qualification Title: Level 2 NVQ Diploma in Specialist Installation Occupations (Construction) Pathway 1: Level 2 NVQ Diploma in Specialist Installation Occupations (Insulated Enclosures Industrial) Pathway

More information

VNIV.EX454 Sprinklers, Automatic and Open. Sprinklers, Automatic and Open

VNIV.EX454 Sprinklers, Automatic and Open. Sprinklers, Automatic and Open VNIV.EX454 Sprinklers, Automatic and Open Page Bottom Sprinklers, Automatic and Open See General Information for Sprinklers, Automatic and Open RELIABLE AUTOMATIC SPRINKLER CO INC 1470 SMITH GROVE RD LIBERTY,

More information

Hobart Model AM Dishwasher

Hobart Model AM Dishwasher CONDUIT (R.H. CONTROLS) PL-18580 NO. NAME OF PART AMT. 1 P-77657-38 Conduit - 3/4" x 32" (Waterproof) 1 2 FE-8-25 Connector-90 0 Sealtite" (3/4" Male Thd. x 3/4" Flex.Cnd.) 1 3 FE-8-11 3/4"Gasket Any 1

More information

PRESSURE LIMITING DRIVERS

PRESSURE LIMITING DRIVERS PLD Models for Discharge & Suction Pressure Limiting Control FM-UL-cUL APPROVED RATINGS BHP/kW Certified Models NSPS Emissions Tier Engine Fuel Management Control Discharge Control Limiting Pressure (psi)

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Section 502 Definition 2009 International Fire Code Access Road Requirements 502.1 Fire Apparatus Access Road is a road that provides fire apparatus

More information

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW non-interlock preaction valve is a hydraulically operated external resetting differential latching style valve designed for use where quickopening and total flooding

More information

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim Actuated Valve with LPCB Approved Preaction Trim 104g/01 with: - Electric Activation with Redundant Solenoid Valve - Electric Activation with Redundant Solenoid Valve and AutoConvert Dry Trim - Double

More information

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information