Comparison of Partial Discharges in SF 6 and Fluoronitrile/CO2 Gas Mixtures

Size: px
Start display at page:

Download "Comparison of Partial Discharges in SF 6 and Fluoronitrile/CO2 Gas Mixtures"

Transcription

1 Comparison of Partial Discharges in SF 6 and Fluoronitrile/CO2 Gas Mixtures Boya ZHANG, Yang CAO University of Connecticut, USA Nenad UZELAC G&W Electric Company, USA 1

2 Agenda 1. Background 2. Fluoronitrile gas 3. Setup and test procedure 4. Results and analysis 5. Summary 2

3 1. Background SF6 has been used successfully for decades in the power industry. One big shortcoming has a high global warming potential (23,500) Included in Kyoto Protocol (1997) on the list to be limited. Global annual SF6 emissions from electrical equipment are reported by ECOFYS: 1,600 t to 2,800 t SF 6. That equals to 37,600 kt to 65,800 kt CO 2! 3

4 1. Background Since 1997, lots of effort to find alternative to SF6 Proved to be hard task due to unique SF6 properties 4 High dielectric strength (2 x air) Nontoxic, nonflammable, noncorrosive Excellent arc extinction Excellent thermal conductivity Chemically stable (good material compatibility) Failures in the switchgear due to long-term PDs.

5 2. Fluoronitriles One of the promising options is Novec TM 4710 fluid. 2x better dielectric than SF6 High boiling temp. (-4.7C) need to be diluted into buffer gas CO2 selected over N2 and air due to reported better arc quenching capability In this paper we ve compared the PD between SF6 and fluoronitrile/co2 5 mixture Molecular structure of the Novec TM 4710

6 2. Fluoronitriles Dielectric strength of the gas mixture/sf kPa (14.5 psi) 140kPa (20.3 psi) 180kPa (26.1 psi) 120kPa (17.4 psi) 160kPa (23.2 psi) 200kPa (29.0 psi) Novec TM 4710 mixing ratio (%) Dielectric strength for Novec TM 4710 fluid in mixture with CO 2 compared with SF 6. The E B of pure Novec is more than two times that of SF 6. E B of pure CO 2 is found only 32-37% of SF 6, while it is doubled by adding only 5% of Novec 4710 into CO 2. For 15% Novec 4710 /CO 2 mixture, the E B is equivalent to SF 6.

7 3. Setup & procedures First vacuumed for 30 min. Then filled with CO 2 to 150 kpa and vacuumed again. Repeated three. Novec and CO 2 were filled to the designed ratio according to their partial pressures. To determine the PDIV, the applied voltage was increased gradually from 0 until the detection of PD. 10 pc was chosen as threshold of PDIV. To obtain PRPD pattern, the PD signal was recorded for 120 s. 0mm To PC H.V. R 25mm δ=2mm r 20μm θ=30 Configuration of PD defect model 7 PD measuring system

8 4. Results & Analysis PDIV and breakdown voltage Voltage (kv) rms % Novec + 95% CO 2 10% Novec + 90% CO 2 15% Novec + 85% CO 2 20% Novec + 80% CO 2 SF 6 breakdown voltage (psi) 10 PD inception voltage δ=2mm d=10mm (kpa) Pressure 8 PDIV and breakdown voltage of the Novec TM 4710/CO 2 mixture and SF 6 at different pressures

9 4. Results & Analysis phase-resolved partial discharge (PRPD) pattern P=100kPa (14.5 psi) 9 PRPD pattern of 20%Novec/80%CO2 mixture and SF6 under different voltages.

10 4. Results & Analysis P=100kPa (14.5 psi) 10 PRPD pattern of 20%Novec/80%CO2 mixture and SF6 under different voltages.

11 4. Results & Analysis phase-resolved partial discharge (PRPD) pattern Counts per second SF6 20% Novec+20%CO2 SF6 20% Novec+20%CO Average charge magnitude (pc) Applied voltage (kv) Comparison of the PD number and PD magnitude for the Novec TM 4710/CO 2 mixture and SF 6 under different voltages. 5

12 4. Results & Analysis A better PD suppression with the increase of mixing ratio, especially in the positive half cycle. PRPD pattern of fluoronitrile/co 2 mixtures with different ratios. (V=22.5 kv) 12

13 4. Results & Analysis Comparison of PD levels through PRPD statistics the comparison of their PD amplitudes at different phases. Even 15% mixture has a lower PD level in the positive half cycle compared with SF 6. 13

14 4. Results & Analysis (a) Comparison of PD levels through PRPD statistic trigger level (b) % Novec + 95% CO 2 10% Novec + 90% CO 2 15% Novec + 85% CO 2 Cumulative Count % Novec + 95% CO 2 10% Novec + 90% CO 2 Count % Novec + 80% CO 2 SF PD charge (pc) 15% Novec + 85% CO 2 20% Novec + 80% CO 2 SF 6 0 trigger level PD charge (pc) PD number of SF6 is in between 15% mixture and 20% mixture. In SF 6, there are much more PDs with low magnitude compared with the 20% fluoronitrile/co 2 mixture. 14

15 5. SUMMARY 15% Fluoronitrile/CO 2 mixture shows equivalent dielectric strength compared with SF 6 under uniform field 15% Fluoronitrile/CO 2 mixture and SF 6 have almost the same PDIV under 11.6psi, 14.5 psi and 17.4psi. Both slightly lower than 20% mixture. PD counts in SF 6 are in-between 15% and 20% mixture. SF 6 has much more PDs with low magnitude and the 20% fluoronitrile/co 2 mixture has less PDs but with higher magnitude. 15

16 Thank you! Questions? 16

ABB Medium Voltage Days MEA 2016 Medium-voltage gas insulated switchgear Technologies for a smarter and greener network

ABB Medium Voltage Days MEA 2016 Medium-voltage gas insulated switchgear Technologies for a smarter and greener network ABB Medium Voltage Days MEA 2016 Medium-voltage gas insulated switchgear Technologies for a smarter and greener network Technical session Medium-voltage gas insulated switchgear Part 1 Speaker / title

More information

Enhanced Breakdown Voltage for All-SiC Modules

Enhanced Breakdown Voltage for All-SiC Modules Enhanced Breakdown Voltage for All-SiC Modules HINATA, Yuichiro * TANIGUCHI, Katsumi * HORI, Motohito * A B S T R A C T In recent years, SiC devices have been widespread mainly in fields that require a

More information

AirPlus TM. An alternative to SF 6. as an insulation and switching medium in electrical switchgear

AirPlus TM. An alternative to SF 6. as an insulation and switching medium in electrical switchgear AirPlus TM An alternative to S 6 as an insulation and switching medium in electrical switchgear THOMAS DIGGELMANN, DENIS TEHLAR, JOELYN HANG, SEBASTIAN ZAHE or decades, the unique properties of sulfur

More information

Fluid characteristics impact performance capabilities in transformer application

Fluid characteristics impact performance capabilities in transformer application Fluid characteristics impact performance capabilities in transformer application Mineral Oil Natural Ester Synthetic Ester Silicone Oil Base Fluid Petroleum Oil Vegetable Oil Hydrocarbons Polydimethylsiloxanes

More information

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. George Fofeldea Power Engineer, 3M Canada August 2018 Abstract 3M invented cold shrink

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

HD4. Gas insulated MV circuit-breakers kv A ka

HD4. Gas insulated MV circuit-breakers kv A ka HD4 Gas insulated MV circuit-breakers 12... 40.5 kv - 630... 3600 A - 16... 50 ka 1 DESCRIPTION Autopuffer breaking technique Electric arc extinction without chopped current No restriking after breaking

More information

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated

More information

HIGH VOLTAGE POWER SUPPLY DESIGN AND MANUFACTURING PRACTICES

HIGH VOLTAGE POWER SUPPLY DESIGN AND MANUFACTURING PRACTICES PAGE 1 OF 5 PREFERRED RELIABILITY PRACTICES Practice: Thoroughly test high voltage power supply packaging on flight configured engineering models, in a simulated space flight environment, to evaluate corona

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

Noise and Vibration Comparison Steel Lining versus Rubber Lining. Charles Hillmann

Noise and Vibration Comparison Steel Lining versus Rubber Lining. Charles Hillmann Noise and Vibration Comparison Steel Lining versus Rubber Lining Charles Hillmann Course Agenda Study Generated By Elna Hoven Aim of the study: Study the effect of noise and vibration levels on Equipment

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information

Application of the. to NRMM. Alois Krasenbrink European Commission

Application of the. to NRMM. Alois Krasenbrink European Commission Application of the PMP Protocol to NRMM Alois Krasenbrink European Commission Joint Research Centre PMP Background Health Concerns over Nano-Particles The Clean Air for Europe (CAFE) Programme has forecast

More information

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number: 15kV 200A Loadbreak Fuse Elbow Design Test Report Report Number: Date: RN-R2601 9/3/2015 Table of Contents 1. Partial Discharge Test Fuse Elbow... 2 2. AC Withstand Voltage Test - Fuse Elbow... 3 3. DC

More information

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast. ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW High performance alternative to air

More information

engineered to order solutions

engineered to order solutions DM-Series engineered to order solutions for Transformer Bushing and Partial Discharge (PD) Monitoring Features & Benefits Bushing Monitoring Partial Discharge Monitoring Optional Thermal Modelling with

More information

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series 3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination

More information

ENGINEERED TO ORDER SOLUTIONS

ENGINEERED TO ORDER SOLUTIONS DM-Series ENGINEERED TO ORDER SOLUTIONS for Transformer Bushing, Winding Hot Spot and PD Monitoring Features & Benefits Advanced Analytics Flexible and Modular Hardware Platform Bushing Monitoring Optional

More information

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) M-RING 24 SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) Contents General Description Advanced facilities and process Advanced design philosophy Definition of M-RING 24 Standards Service conditions

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

One-Fit,UFES, Reyrolle LM

One-Fit,UFES, Reyrolle LM EPDS SERVICE, SOUTH AFRICA, FRANS BOUWER, 2018. Retrofit Solutions One-Fit,UFES, Reyrolle LM AMEU Namibia,March 2018 Retrofit Agenda 1. Safety 2. One-Fit overview 3. UFES overview 4. Reyrolle LM-Switchgear

More information

COMPARISON OF FULL FLOW DILUTION, PARTIAL FLOW DILUTION, AND RAW EXHAUST PARTICLE NUMBER MEASUREMENTS

COMPARISON OF FULL FLOW DILUTION, PARTIAL FLOW DILUTION, AND RAW EXHAUST PARTICLE NUMBER MEASUREMENTS COMPARISON OF FULL FLOW DILUTION, PARTIAL FLOW DILUTION, AND RAW EXHAUST PARTICLE NUMBER MEASUREMENTS M. Yusuf Khan 1, Sagar Sharma 1, Chet Mun Liew 1, Abhay Joshi 1,Daniel Barnes 1, Nathan Scott 1, Benjamin

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650523200 Ed.1 of 23/07/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and

More information

Limitor -G General Purpose Fuses

Limitor -G General Purpose Fuses Limitor -G General Purpose Fuses HIGH VOLTAGE IEC FUSES DIN HV GENERAL PURPOSE FUSES FOR TRANSFORMERS FEATURES & BENEFITS Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING 1 DEPARTMENT OF ELECTRICAL ENGINEERING Introduction to High Voltage Testing It is essential to ensure that the electrical equipment is capable of withstanding the overvoltages that are met within the service.

More information

CASE STUDY ON RESOLVING OIL WHIRL ISSUES ON GAS COMPRESSOR

CASE STUDY ON RESOLVING OIL WHIRL ISSUES ON GAS COMPRESSOR CASE STUDY ON RESOLVING OIL WHIRL ISSUES ON GAS COMPRESSOR John J. Yu, Ph.D. Nicolas Péton Sergey Drygin, Ph.D. GE Oil & Gas 1 / Abstract This case is a site vibration issue on a Gas compressor module.

More information

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv 3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv Data Sheet September 2014 Description 3M Cold Shrink QT-III Silicone Rubber Termination Kits, 7640-T

More information

HIGH VOLTAGE MODULE TEST SYSTEM

HIGH VOLTAGE MODULE TEST SYSTEM HIGH VOLTAGE MODULE TEST SYSTEM 4.0/4 Module Test Systems n AC, DC, and impulse testing n Factory testing n R&D n Education / training MODULES FOR VOLTAGE GENERATION Test transformers for 100 and 200 kv

More information

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Extra-High-Voltage SF 6 Gas-Insulated Switchgear Extra-High-Voltage SF 6 Gas-Insulated Switchgear Shuichi Sugiyama Masahiko Fujita Takahiro Shinohara 1. Introduction Due to location criteria and toughened restrictions on transportation, it has become

More information

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction. HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Eaton s Cooper Power Systems

Eaton s Cooper Power Systems Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton

More information

Analysis of Generator Stator Remaining Breakdown Voltage for Power Plant

Analysis of Generator Stator Remaining Breakdown Voltage for Power Plant American Journal of Electrical Power and Energy Systems 2016; 5(3): 22-27 http://www.sciencepublishinggroup.com/j/epes doi: 10.11648/j.epes.20160503.11 ISSN: 2326-912X (Print); ISSN: 2326-9200 (Online)

More information

30A BLDC ESC. Figure 1: 30A BLDC ESC

30A BLDC ESC. Figure 1: 30A BLDC ESC 30A BLDC ESC Figure 1: 30A BLDC ESC Introduction This is fully programmable 30A BLDC ESC with 5V, 3A BEC. Can drive motors with continuous 30Amp load current. It has sturdy construction with 2 separate

More information

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets OKAZAKI, Takayuki KIKUCHI, Masanori TOKUNAGA, Yoshihide A B S T R A C T As Southeast Asia continues to experience

More information

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction. HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main

More information

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 15 kv or 25 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic

More information

Application of Thick-Film Substrate Technology in High Voltage HRC Fuses

Application of Thick-Film Substrate Technology in High Voltage HRC Fuses Application of Thick-Film Substrate Technology in High Voltage HRC Fuses M. Wilniewczyc (1), G. Hoffmann (2) and U. Kaltenborn (3) ABB Sp. z o.o. (1), ul. Zeganska 1, PL-4-713 Warszawa, Poland, mariusz.wilniewczyc@pl.abb.com

More information

Appendix L-2 Calculating Combined-Cycle and Cogeneration

Appendix L-2 Calculating Combined-Cycle and Cogeneration Appendix L-2 Calculating Combined-Cycle and Cogeneration Block Data Using the Fleet-type Rollup Method When Reporting Each Gas Turbine/Steam Turbine Unit Overview This document will explain the fleet-type

More information

Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors.

Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors. Date: 30.05.2005 Page 1 Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors. According to DIN IEC 60747 the maximum rated surge current is the maximum allowable non periodical,

More information

Ignition Strategies for Fuel Mixtures in Catalytic Microburners.

Ignition Strategies for Fuel Mixtures in Catalytic Microburners. Ignition Strategies for Fuel Mixtures in Catalytic Microburners. V I K R A M S E S H A D R I AND N I K E T S. K A I S A R C O M B U S T I O N T H E O RY AND M O D E L L I N G VOL. 1 4, N O. 1, 2 0 1 0,

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Equipment Connection Bus Bar, or Grounded Metal Equipment Plate F Series Mounting Holes ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric

More information

High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators

High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators Christian Hückler, Sales Manager Air-Insulated Switchgears siemens.at/future-of-energy High voltage in

More information

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV The recloser you want, all in one package. Single- and Three-Phase, 15 38kV The need for automated reclosers has never been greater, but many of today s reclosers come with penalties. They weigh too much,

More information

JOHANSON DIELECTRICS INC Bledsoe Street, Sylmar, Ca Phone (818) Fax (818)

JOHANSON DIELECTRICS INC Bledsoe Street, Sylmar, Ca Phone (818) Fax (818) Impact of Pad Design and Spacing on AC Breakdown Performance John Maxwell, Vice President of Engineering, Johanson Dielectrics Inc. Enrique Lemus, Quality Engineer, Johanson Dielectrics Inc. 15191 Bledsoe

More information

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection ABB AG - EPDS Ultra-Fast Earthing Switch UFES active internal arc protection Agenda Arc fault Protection concepts Ultra-Fast Earthing Switch type UFES Principle Components Differentiation of protection

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester

More information

15A (2 Form C), 10A (4 Form C) COMPACT POWER RELAYS WITH HIGH SENSITIVITY

15A (2 Form C), 10A (4 Form C) COMPACT POWER RELAYS WITH HIGH SENSITIVITY 5A ( Form C), A (4 Form C) COMPACT POWER RELAYS WITH HIGH SENSITIVITY RELAYS RoHS Directive compatibility information http://www.mew.co.jp/ac/e/environment/ Taking advantage of the 4-gap balanced armature

More information

Appendix L-1 Calculating Combined-Cycle and Cogeneration

Appendix L-1 Calculating Combined-Cycle and Cogeneration Appendix L-1 Calculating Combined-Cycle and Cogeneration Block Data Using the Synthesis Event and Performance Method When Reporting Each Gas Turbine/Steam Turbine Unit Overview This document will explain

More information

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng. First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650515200 Ed.1 of 21/02/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and

More information

Contemporary technological solutions

Contemporary technological solutions Contemporary technological solutions ATOMEXPO-2018. 15 MAY. ROUND TABLE RUSSIA'S OPPORTUNITIES IN NEW POWER GENERATION To enable energy transformation Enver Shulgin, Vice President, Local Division Manager,

More information

15 kv and 25 kv Thru-Bushings

15 kv and 25 kv Thru-Bushings Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation

More information

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017 HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION March 2017 HV FUSE-LINKS IN THE WORLD UL STANDARD E OR R RATED: AMERICAN STANDARD DIN STANDARD: GERMAN STANDARD FR STANDARD: FRENCH STANDARD BS STANDARD: BRITISH

More information

High Speed Fuse Applications Module 5

High Speed Fuse Applications Module 5 High Speed Fuse Applications Module 5 Power Semiconductors GTO SSR Semiconductors: High speed electronic switches used to manipulate electrical power Diode Thyristor IGBT Module 5 - page 2 2 Application

More information

Time Delay Technique for Pinpointing PD Noise on Combined Cycle Systems Troy Coleman, Plant Technical Services

Time Delay Technique for Pinpointing PD Noise on Combined Cycle Systems Troy Coleman, Plant Technical Services Time Delay Technique for Pinpointing PD Noise on Combined Cycle s Troy Coleman, Plant Technical Services Puget Sound Energy >1 Million Customers 772 MW Wind 3 Farms 276 MW Hydro 2 Projects 2481 MW Thermal

More information

25 kv Apparatus Bushings

25 kv Apparatus Bushings Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation

More information

Contents. Design Test Results for Specimen Design Test Results for Specimen Voltage Impulse Oscillograms...9

Contents. Design Test Results for Specimen Design Test Results for Specimen Voltage Impulse Oscillograms...9 3M Electrical Markets Division Test Report Contents Purpose...3 Test Specimens...3 Tests...4 Design Test Results for Specimen 92615...5 Design Test Results for Specimen 92652..7 Voltage Impulse Oscillograms.....9

More information

N1240/N1243 Series Troubleshooting Guide for N1240-3/N Alternators

N1240/N1243 Series Troubleshooting Guide for N1240-3/N Alternators N1240/N1243 Series Troubleshooting Guide for N1240-3/N1243-2 Alternators Hazard Definitions These terms are used to bring attention to presence of hazards of various risk levels or to important information

More information

ELECTRONIC FUEL INJECTION

ELECTRONIC FUEL INJECTION Table of Contents ELECTRONIC FUEL INJECTION Section 3B - Troubleshooting and Diagnostics TROUBLESHOOTING AND DIAGNOSTICS Specifications........................... 3B-1 Special Tools...........................

More information

Module 2:Genesis and Mechanism of Formation of Engine Emissions Lecture 9:Mechanisms of HC Formation in SI Engines... contd.

Module 2:Genesis and Mechanism of Formation of Engine Emissions Lecture 9:Mechanisms of HC Formation in SI Engines... contd. Mechanisms of HC Formation in SI Engines... contd. The Lecture Contains: HC from Lubricating Oil Film Combustion Chamber Deposits HC Mixture Quality and In-Cylinder Liquid Fuel HC from Misfired Combustion

More information

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...

More information

(Addendum to the March 1994 Evaluation) March 11, 1999

(Addendum to the March 1994 Evaluation) March 11, 1999 Evaluation of the Red Jacket Fx1DV and Fx2DV Installed in the Big-Flo Diaphragm Valve (BFDV) for Hourly Testing on Flexible Pipelines Containing Diesel Fuel (Addendum to the March 1994 Evaluation) PREPARED

More information

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control Connect - Contact - Control 3 Contactors CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en More information at: schaltbau-gmbh.com 42 CH1130/02 Single pole high-voltage contactor

More information

Thermodynamic Properties of DuPont ISCEON MO99

Thermodynamic Properties of DuPont ISCEON MO99 DuPont ISCEON REFRIGERANTS Technical Information Thermodynamic Properties of DuPont ISCEON MO99 SI Units Thermodynamic Properties of DuPont ISCEON MO99 SI Units Physical Properties Refrigerant Classification

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

High Voltage Surge Arresters Station Class

High Voltage Surge Arresters Station Class Power Transmission and Distribution High Voltage Surge Arresters Station Class Product Overview High Voltage High Protection Just as the Golden Gate Bridge has successfully defied all winds, weather and

More information

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY Sheet 1 of 5 Order Number Serial Number PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY Issue Date Level B 27/05/1999 Initial issue. Summary of changes Due to RMS continuous product improvement policy

More information

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description Quick Splice II 5461 (CN) Cable (JCN) Cable 35 kv Molded Rubber Inline Splicing Kit Data Sheet Accessory Splice Jacket 1. Product Description The 3M 5461 Quick Splice II is a 35 kv class inline splice

More information

Dr Joerg Friedel Product Application Specialist Shell Technology Centre Hamburg, Germany

Dr Joerg Friedel Product Application Specialist Shell Technology Centre Hamburg, Germany Dr Joerg Friedel Product Application Specialist Shell Technology Centre Hamburg, Germany An inhibited transformer oil based on Shell gas-to-liquids (GTL) technology The evolution of hydrocarbon transformer

More information

factsheet Field Sprayer Calibration Introduction Pre-Calibration Checklist Using a Calibration Bottle

factsheet Field Sprayer Calibration Introduction Pre-Calibration Checklist Using a Calibration Bottle Field Sprayer Calibration Introduction It is important to properly calibrate your sprayer for maximum performance. Improper spray application can be costly in terms of poor pest control, crop injury and

More information

DYNACOMP. The top-class reactive power compensator

DYNACOMP. The top-class reactive power compensator DYNACOMP The top-class reactive power compensator Dynacomp vs Electromechanical switching of capacitors Electromechanical switching of capacitors The Dynacomp : the top-class dynamic compensator Transients

More information

Transient Measurement of Diesel Nano-Particles by a Newly Developed DDMA

Transient Measurement of Diesel Nano-Particles by a Newly Developed DDMA Transient Measurement of Diesel Nano-Particles by a Newly Developed DDMA Terunao KAWAI Rahman M. Montajir*, Yuichi GOTO, Matsuo Odaka N T S E L National Traffic Safety and Environment Laboratory JAPAN

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic

More information

Study on Emission Characteristics Test of Diesel Engine Operating on. Diesel/Methanol Blends

Study on Emission Characteristics Test of Diesel Engine Operating on. Diesel/Methanol Blends Study on Emission Characteristics Test of Diesel Engine Operating on Diesel/Methanol Blends Yuanhua Jia1, a, Guifu Wu2,b, Enhui Xing3,c,Ping Hang 4,d,Wanjiang Wu5e 1,2,3, 4,5 College of Mechanical Engineering

More information

SF6 free high-voltage GIS installation in Zürich, CH.

SF6 free high-voltage GIS installation in Zürich, CH. SF6 free high-voltage GIS installation in Zürich, CH. Dr. Walter Holaus, Global Product Manager, ABB Switzerland. 25.11.2015 Current developments in High-voltage switchgear Some examples November 27, 2015

More information

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE MITIGATE ARC EFFECTS WITHIN AN E-HOUSE Jérôme DOUCHIN Anthony BROWN Juha RINTALA Schneider Electric France Schneider Electric Singapore Schneider Electric Finland Jerome.douchin@ Anthony.brown@ juha.rintala@

More information

COMPANDER VIBRATION TROUBLESHOOTING. Sébastien Jaouen, Cryostar Cliff Bauer, MOL Stéphane Berger, Flender Alain Guéraud, Cryostar

COMPANDER VIBRATION TROUBLESHOOTING. Sébastien Jaouen, Cryostar Cliff Bauer, MOL Stéphane Berger, Flender Alain Guéraud, Cryostar COMPANDER VIBRATION TROUBLESHOOTING Sébastien Jaouen, Cryostar Cliff Bauer, MOL Stéphane Berger, Flender Alain Guéraud, Cryostar Bios Sébastien Jaouen is currently the structural calculation team leader

More information

Normal vs Abnormal Combustion in SI engine. SI Combustion. Turbulent Combustion

Normal vs Abnormal Combustion in SI engine. SI Combustion. Turbulent Combustion Turbulent Combustion The motion of the charge in the engine cylinder is always turbulent, when it is reached by the flame front. The charge motion is usually composed by large vortexes, whose length scales

More information

Getting the Lead Out December, 2007

Getting the Lead Out December, 2007 Getting the Lead Out December, 2007 Tom DeBonis Assembly & Test Technology Development Technology and Manufacturing Group Summary Intel has removed the lead (Pb) from its manufacturing process across its

More information

Chain Cam Drive Efficiency Optimization and Comparison to Belt Drives

Chain Cam Drive Efficiency Optimization and Comparison to Belt Drives Chain Cam Drive Efficiency Optimization and Comparison to Belt Drives October 2012 Our Beliefs Respect Collaboration Excellence Integrity Community Outline Intro to Timing Drive Friction Test Stand & Procedure

More information

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

Smart Fume Extractor

Smart Fume Extractor Smart Fume Extractor The most efficient solution. It only works when soldering and features a unique system integrated into the stand JBC takes fume extractors to a higher level with its new smart Fume

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications Quick Splice II 5451R (CN) Cable (JCN) Cable Accessory Splice Jacket 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet 1. Product Description The 3M 5451R Quick Splice II is a 25/28 kv class

More information

Bangkok Technical Conference Bangkok, Thailand 30 June, 2013

Bangkok Technical Conference Bangkok, Thailand 30 June, 2013 Cost-Effective Alternative In PU Foam Applications Bangkok Technical Conference Bangkok, Thailand 30 June, 2013 ecomate: International Perspective, Trends & Developments Outline ecomate Technology Review

More information

ACCURL HYDRAULIC CNC PUNCH PRESS

ACCURL HYDRAULIC CNC PUNCH PRESS ACCURL HYDRAULIC CNC PUNCH PRESS SMART-FAB P SERIES Shaping your future ACCURL HYDRAULIC CNC PUNCH PRESS SMART-FAB P SERIES Accurl MAX-SF Series CNC Punch Press is the newly developed Multi Index Tools

More information

THIN FILM FUSE LINK. R D Harrison*, I Harrisont, A F Howet.

THIN FILM FUSE LINK. R D Harrison*, I Harrisont, A F Howet. 169 THIN FILM FUSE LINK R D Harrison*, I Harrisont, A F Howet. *Bussman Division Cooper (UK) Ltd, Burton on the wolds, Leicestershire, LEI 2 5TH, UK. tdepartment of Electrical and Electronic Engineering,University

More information

Reliability Evaluations and Test Functions Devised for Automotive Power Devices

Reliability Evaluations and Test Functions Devised for Automotive Power Devices Technology Report Reliability Evaluations and Test Functions Devised for Automotive Power Devices Batteries & Energy System Equipment Headquarters ESPEC CORP. Michiya Kusaka Norihito Kan Makoto Kitagawa

More information

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide 1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Testing of particulate emissions from positive ignition vehicles with direct fuel injection system. Technical Report

Testing of particulate emissions from positive ignition vehicles with direct fuel injection system. Technical Report Testing of particulate emissions from positive ignition vehicles with direct fuel injection system -09-26 by Felix Köhler Institut für Fahrzeugtechnik und Mobilität Antrieb/Emissionen PKW/Kraftrad On behalf

More information

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable

More information

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment : NTT Group R&D for Reducing Environmental Load Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment Yousuke Nozaki Abstract This article describes the development of a higher-voltage

More information

3AP1 DTC for 145 and 245 kv

3AP1 DTC for 145 and 245 kv The Hybrid Solution 3AP1 DTC for 145 and 245 kv siemens.com/answers Solutions for switchgears and substations fully encapsulated h y b r i d Grade of encapsulation partly encapsulated not encapsulated

More information

BM16LP. Thanks for your purchasing the cell monitor for your vehicle.

BM16LP. Thanks for your purchasing the cell monitor for your vehicle. BM16LP 8S-16S LiPo CELL Monitor Low power consumption High accuracy TFT LCD display Programmable Thanks for your purchasing the cell monitor for your vehicle. Read the ENTIRE instruction manual to become

More information

Recent progress on R&D toward Neutral Beam Injector for ITER and JT-60SA

Recent progress on R&D toward Neutral Beam Injector for ITER and JT-60SA Recent progress on R&D toward Neutral Beam Injector for ITER and JT-60SA Rapporteur; Hiroyuki TOBARI (Japan Atomic Energy Agency) (FIP/2-5Ra) Development of DC ultra-high voltage insulation technology

More information

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester This report records the results of the design tests made on Type PDV 100 Optima Distribution

More information

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

HGM1750 Genset Security Module USER MANUAL Smartgen Technology HGM1750 Genset Security Module USER MANUAL Smartgen Technology CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 5 3. SPECIFICATION... 7 4. OPERATION... 8 5. PROTECTION... 9 6. PARAMETER RANGE

More information