Start display at page:

Download "CODE OF GOOD PRACTICE"

Transcription

1

2

3 CODE OF GOOD PRACTICE FOR THE OPERATION OF LIQUID FUEL FIRED COMMERCIAL, INDUSTRIAL AND DOMESTIC APPLIANCES 1st June 1972 PRINTED BY THE GOVERNMENT PRINTER HONG KONG

4 K 7/72

5 INTRODUCTION CONTENTS Page FUEL 1 FUEL OIL PREHEATERS 1 FILTERS 1 ATOMISATION OF FUEL 2 AlR FOR COMBUSTION 2 FUEL OIL BURNERS 3 Pressure jets or gun type 3 Air pressure atomisers 3 low, medium, high Steam atomisers 3 Rotary cup burners 4 Vapourising burners. 4 BURNER MAINTENANCE. 4 STARTING UP LIQUID FUEL FIRED INSTALLATIONS FROM COLD FROM WARM INSTRUCTION MANUALS 6 AUTOMATIC CONTROLS. 7 SHUTDOWN PROCEDURE 7 CARBON BUILD-UP IN FURNACE 7 LIQUID FUEL IN FIRE TUBE BOILERS 8 COMBUSTION CHAMBER VOLUME BRICK SETTINGS 8 EXAMINATION OF FLAME 8 v

6 ?^

7 INTRODUCTION This code of good practice aims to reduce air pollution in Hong Kong while saving money in fuel bills. Quite simply, if proper methods are used to achieve good combustion in furnaces and boilers, the maximum amount of useful heat will be extracted from a minimum amount of fuel. The result: down go the bills and down goes pollution. If this code achieves its purpose, the colony will become not only more prosperous, but also a cleaner, better place to live in.

8 CODE OF GOOD PRACTICE FOR OF LIQUID FUEL FIRED INDUSTRIAL, COMMERCIAL AND DOMESTIC APPLIANCES This Code of Good Practice is applicable to any liquid fuel fired boiler, oven or furnace. FUEL Liquid fuels used in Hong Kong are generally either grade 1 or grade 3 fuel oils. Grade 1 fuel oil can be used successfully without any preheat conditioning before the fuel oil burner. Grade 3 fuel must be preheated before admission to the burner to achieve complete combustion, prevent the formation of dark smoke, and reduce fuel costs. The usual range of preheat for grade 3 fuel oil lies between 160 and 170 F (71 to 77 C) but the actual preheat temperature required should be ascertained from the supplier. Some of the grade 3 fuel oils differ in wax content and may need a slightly higher preheat temperature. FUEL OIL PREHEATERS Preheaters for use with grade 3 fuel oil may receive their heat as steam or as electricity. Both types should be fitted with thermostatic controls to ensure a steady preheat temperature. It is preferable to have a thermometer inserted into the fuel supply line between the preheater and the burner, and as close as is practicable to the burner. The thermostat controlling the preheater should also be close to the burner. For start-up periods on a steam installation, an electric preheater should be used for a short time until steam is available from the boiler to operate a steam preheater. If steam is not available, an electric preheater is essential. FILTERS Screen-type filters should be inserted in the fuel supply lines between the fuel tank and the preheaters. However because the viscosity of the fuel is reduced in the preheater, the carrying capacity of the fuel reduced. For this reason it is desirable to have additional screen filters between the preheater and the burner to trap any solid material released by the lower viscosity. 1

9 ATOMISATION OF THE FUEL The purpose of the fuel oil *, urner is to break down fuel into tiny droplets; this is called atomisation. Heavier grades of fuel cannot be made to burn without atomisation. Small droplets of fuel have three advantages: they heat up quickly to ignition temperature; the surface area is increased and exposes a greater area of the fuel to the air required for combustion; good atomisation also promotes a steady and stable flame. The size of the droplet is affected by the viscosity. High viscosity, as with an unheated fuel, gives large droplets; low viscosity permits the formation of small droplets. Preheated grade 3 fuel oil results in better combustion efficiency with reduced fuel costs, and much less risk of producing of dark smoke. Although it might seem that the higher the fuel temperature, the lower the viscosity and the better the atomisation, there is a limit to how high you can go. Too high preheat temperature can promote a break-down of the fuel in the burner, causing carbon build-up in the burner which will itself interfere with atomisation and may lead to the formation of dark smoke. Too high preheat also wastes steam or electricity on the preheater. AIR FOR COMBUSTION Liquid fuel will not burn unless sufficient air is provided. The theoretical air requirement for liquid fuels is about 185 ft 3 per pound of fuel, but to ensure complete combustion, it is necessary to admit some extra air. This raises the air requirement to about 220 ft 3 per pound of fuel. Too little combustion air will result in dark smoke formation, and a waste of fuel. Too much combustion air may produce white smoke, and again a waste of fuel. A good guide to the correct air to fuel ratio is to see a light brown haze emerging from the top of the chimney. Some of the air for combustion may be admitted through the burner. In some installations part or all of the combustion air may enter the furnace through ports around the burner tip, or alongside the burner mounting. All air admission ports should be kept clean and free of obstruction, but it is desirable to have some form of damper control which can be adjusted to control the air input.

10 Air for combustion comes from the room where the appliance is situated, so the room must be adequately ventilated. FUEL OIL BURNERS There are many different makes of fuel oil burners, but they generally fall into the following types: Pressure jets or gun type Fuel is atomised by passing it at pressure through a small orifice at the burner tip. The pressure required may be in the range 80 to 150 lb/in 2 and variation alters the amount of fuel supplied through the burner. It also alters the flame shape. Higher pressures generally tend to give a wider flame. Low pressures tend to increase the size of the droplet of atomised fuel. When a pressure jet has to work at a low throughput of fuel, it is preferable to change to a smaller jet than to reduce the fuel oil pressure below the given limits. Do not increase the fuel pressure on a pressure jet burner above 150 lb/in 2. If more throughput of fuel is required, a slightly larger burner tip should be used. On any pressure jet installation always ensure that there is a range of jet sizes in stock. Low air pressure atomisers Fuel is atomised by an air blast delivered concentrically with the fuel oil at the burner tip. The usual air pressures required are in the range 6 to 30 inches water gauge, which is obtainable from a centrifugal fan. Medium air pressure atomisers These operate on a similar principle, but the required air pressure is in the range 3 to 15 lb/in 2, supplied from a rotary compressor, or a compressed air supply. High air pressure atomisers Again of similar type, but the air pressure required is in excess of 15 lb/in 2. Steam atomisers Steam atomisers operate on the same principle, but using pressures generally higher than 15 lb/in 2. They have the disadvantage that on

11 boilers which have to be brought up from a cold condition, steam is not available. In these circumstances it is sometimes possible to start up by using air pressure. Rotary cup burners This burner atomises the fuel by centrifugal force. The droplets of fuel are thrown off the edge of a spinning cup. Fuel is fed into the inner surface of the cup, which is spun by an electric motor, or by an air or steam driven turbine. For electrically driven burners the speed of rotation generally lies within the range 2,850 to 3,500 rpm; for turbine driven burners the speed of rotation may be as high as 5,000 to 7,000 rpm. Because the speed of rotation of the cup governs the size of the droplet, and the shape of the flame envelope, it is advisable to check on the rpm frequently. This is particularly important on electrically driven burners incorporating a belt drive. Vapourisiiig burners These should only be used for grade 1 fuel as they are not suitable for grade 3 fuels. The fuel oil vapour and the air for combustion must mix intimately; this can only be effective if all perforations in the pots are kept constantly clean. Air admission to the burner must also be kept clear of obstruction other than control dampers, BURNER MAINTENANCE No fuel oil burner can give effective atomisation for long without careful routine maintenance. Cleaning of all burners other than the rotary cup burner, should be done only when there is carbon build-up in the furnace, when the flame shape is distorted, or when carbon forms on the burner tip. Rotary cup burners should be cleaned more frequently, and at regular intervals, because some of the faults through failure to clean are masked by the rotation of the cup. The burner should be shut down, allowed to cool, and then stripped down to the burner tip. The fuel orifice of pressure jets and air atomising burners, should be soaked in diesoline or kerosene to soften any carbon or gummy material It should then be wiped clean with a soft rag. The orifice should be examined for any deformation or damage. Any carbon inside should be removed with a soft wood probe; hard metals will deform the orifice and make it unfit for further use. Some burner manufacturers provide soft metal "Dollies" which

12 are a clearance fit in the orifice. These should be used for cleaning. Some burners have a diaphragm or spin plate; these also should be soaked in kerosene to soften any deposit and then wiped clean with soft rag. If spare nozzles, jets, and cups are kept in stock, then the time needed to clean a faulty burner is much reduced. The dirty part can be replaced quickly with only a short shut down, and then cleaned later. On rotary cup burners the nose cone should be removed, and cleaned. Straighten any bent or distorted swirl vanes in the nose cone. If any vanes are broken, replace the nose cone. The rotary cup should be removed from the end of the fuel tube, and soaked in diesoline or kerosene, and cleaned with a soft rag. The edge of the cup should be examined. If the edge is bent over, or if there is any irregularity in the edge, the cup should be replaced. Examine the inner surface; if it is scratched, the cup should be replaced. Some attempts have been made with badly scratched cups to skim the inner surface on a lathe. Although the surface can be restored in this way the inner diameter of the cup has been enlarged, with the result that the flame envelope shape has also been changed. A rotary cup should be resurfaced in this way only if the scratches are very shallow. When a rotary cup burner is stripped for cleaning, the speed of rotation of the fuel shaft should be checked. STARTING UP LIQUID FUEL FIRED INSTALLATIONS FROM COLD 1. Switch on electric preheater and make sure the thermostat is set to the correct temperature and that the fuel oil supply to the preheater is open. Use the thermometer at outlet from the preheater to check that the temperature is correct. 2. Check that all gas dampers in the flues leading to the chimney are open. 3. When the preheater is fully warmed up, and the fuel oil temperature is correct, open up any air supplies to the burner(s) and allow a short time for air purge to clear any inflammable gases. Turn on the fuel supply and light the flame at the burner tip. If the method

13 of ignition is by torch through a port at the front of the burner, do not stand close while watching for ignition. A minor blowback can cause bad burns to face or eyes. Check after igmition that the flame is stable. 4. Adjust the air supply to the burner for complete combustion without dark smoke. Control the air supply so that there is a light brown haze at the top of the chimney; remember that white smoke indicates too much combustion air. For a short time when starting up from cold there may be an emission of smoke darker than Ringlemann L 5. Do not open up the burner to its full capacity. Let the boiler, furnace or oven warm up slowly, allowing ample time for thermal expansion to take place. This avoids cracks in brickwork, or undue distortion inside the appliance. 6. When the normal fuel is grade 3 fuel, it is sometimes helpful to start up from cold using grade 1 fuel. This may mean that only a steam heated preheater need be installed. When this is possible, it is preferable to use grade 1 fuel for a short time before shutting down to ensure that the fuel supply lines between the preheater and the burner are full of the lighter grade fuel. STARTING UP FROM WARM 1. With a steam boiler installation, turn on the steam preheater. If no steam is available, use the electric preheater. 2. Follow normal procedure as for cold start. 3. When relighting under hot or warm conditions, ensure that the combustion air is turned on first, and allow sufficient time for air purge. NOTE In some cases where both electric and steam preheaters are installed, it is possible to set the thermostat controls on the preheater to ensure that the steam heater is at work when steam is available, and the electric heater out of commission. INSTRUCTION MANUALS All burner manufacturers, and all suppliers of package boilers can supply instruction manuals. These should be carefully read before any fuel oil burner is started up.

14 AUTOMATIC CONTROLS Many installations, particularly package boilers are fitted with comprehensive automatic controls. Again the instruction book should be read carefully until the controls are fully understood. Many automatic installations include a light-up sequence which may repeat if ignition fails at the first attempt. If ignition fails on the second attempt the automatic control will go over to lock-out. When this happens the entire system should be examined before any attempt is made to ignite manually. Automatic controls, in good condition, will always give a better performance than manual control. They should be checked at frequent intervals by a competent person. The safety of the appliance rests with the control. If an appliance has a pressure control on the steam pressure of the boiler, the relative times when control opens up the burner or shuts it down should be noted. If the shut down time is greater than the run time, it may be necessary to fit a slightly smaller burner control. SHUTDOWN PROCEDURE When a fuel oil burner is to be shut down for more than a few minutes the burner should be retracted from its housing so that a heat shield can be placed between the burner tip and the furnace. Heat radiated back from the furnace to the burner will cause a break down of any fuel left in the burner creating a carbon build-up which will interfere with atomisation when the burner is restarted. Any air ports should be shut, or at least closed down to reduce the amount of cold air drawn into the furnace. If the shut down is for more than a few minutes, turn off the fuel oil preheater; this saves heat expenditure, and prevents any break down of the fuel in the heater which might produce carbon or gum and reduce the effective heating surface. CARBON BUILD-UP IN THE FURNACE Examine the furnace tubes in any boiler, or the walls in ovens or furnaces for any build-up of carbon. This build-up will interfere with the correct development of the flame and may cause dark smoke.

15 If carbon build-up persists in one area, for example at one side of the furnace tube, check the alignment of the burner in the tube. If the alignment is correct, then the build-up is probably due to a distorted burner, and the part should be replaced. The flame should never impinge against the wall of the furnace. This also causes carbon build-up. LIQUID FUELS IN FERE TUBE BOILERS Any boiler of the economic type, or any modern package boiler, uses a large number of fire tubes to increase the heat transfer surface. These fire tubes tend to pick up deposits of soot and dust, which reduce the heat transfer rate. Whenever possible for example during a temporary shut down the tubes should be cleaned. Always use an unworm, correct size cleaning brush. COMBUSTION CHAMBER VOLUME The combustion chamber volume is critical and controls the amount of fuel burned in a given time. The volume is already decided by the manufacturers and any attempt to install a larger burner on an existing combustion chamber as or increase the throughput of the fuel oil burner may result in a waste of fuel and the formation of dark smoke. BRICK SETTINGS Furnaces or boilers with a brickwork setting should be examined for cracks when running at operating temperature. Any cracks should be filled in with fireclay to prevent ingress of air which will reduce the thermal efficiency, and the chimney draught. EXAMINATION OF FLAME Never try to examine a flame without using a blue glass screen, The light emitted from the flame can cause lasting damage to the sight.

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

FUEL OIL BURNERS. By Mark Butterfield March 09

FUEL OIL BURNERS. By Mark Butterfield March 09 FUEL OIL BURNERS By Mark Butterfield March 09 INTRODUCTION The history of burners dates back to the early shipping days, when fuel oil first started replacing coal as the ships primary fuel source. Since

More information

COMBUSTION EFFICIENCY

COMBUSTION EFFICIENCY COMBUSTION EFFICIENCY Don Hunter Pr.Eng. MSc(struct)MSAICE Chief Executive Officer FFS Refiners (Pty) Ltd Durban South Africa The efficiency of a heating appliance or application is dependent on the efficiency

More information

Installation- and maintenance instruction ST120 S75/21

Installation- and maintenance instruction ST120 S75/21 Installation- and maintenance instruction ST120 S75/21 1 171 615 30 05-01 178 058 15 DESCRIPTION Components 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting PAGE 1 This document outlines questions to ask and components to check during TES troubleshooting. More detailed troubleshooting procedures are available in the TES Troubleshooting Guide. 1. Flow Light

More information

Installation- and maintenance instruction BENTOFLEX ST120KAV

Installation- and maintenance instruction BENTOFLEX ST120KAV Installation- and maintenance instruction BENTOFLEX ST120KAV 1 171 625 61 05-01 178 001 16 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

Installation- and maintenance instruction BENTOFLEX ST 108 PL

Installation- and maintenance instruction BENTOFLEX ST 108 PL Installation- and maintenance instruction BENTOFLEX ST 108 PL 1 171 625 30 03-01 178 001 13 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

Combustion Equipment. Combustion equipment for. Solid fuels Liquid fuels Gaseous fuels

Combustion Equipment. Combustion equipment for. Solid fuels Liquid fuels Gaseous fuels Combustion Equipment Combustion equipment for Solid fuels Liquid fuels Gaseous fuels Combustion equipment Each fuel type has relative advantages and disadvantages. The same is true with regard to firing

More information

Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility

Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility -.9- KINEDIZER LE High capacity low NOx gas burners Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility Lower NOx and less excess air than standard KINEDIZER

More information

COMBUSTION EFFICIENCY THE EFFECT OF COMBUSTION ON THE EFFICIENCY OF THE HEATING APPLIANCE

COMBUSTION EFFICIENCY THE EFFECT OF COMBUSTION ON THE EFFICIENCY OF THE HEATING APPLIANCE COMBUSTION EFFICIENCY THE EFFECT OF COMBUSTION ON THE EFFICIENCY OF THE HEATING APPLIANCE INTRODUCTION The Combustion Efficiency is affected by the manner in which the combustion occurs. That is, the Air

More information

Heating and Gas Installations - December 2014

Heating and Gas Installations - December 2014 This is an example of good practice maintenance specifications. It is not exhaustive and should only be used to assist with facilities management or specification of a maintenance contract. Emergency Gas

More information

Lecture 27: Principles of Burner Design

Lecture 27: Principles of Burner Design Lecture 27: Principles of Burner Design Contents: How does combustion occur? What is a burner? Mixing of air and gaseous fuel Characteristic features of jet Behavior of free (unconfined) and confined jet

More information

Specifications of STICKTITE and PILOTPAK Nozzles

Specifications of STICKTITE and PILOTPAK Nozzles Low Temperature urners - STICKTITE and PILOTPK Nozzles 1-1.1-5 Specifications of STICKTITE and PILOTPK Nozzles This graph indicates the relationship between capacity and applied mixture differential pressure

More information

Specifications of STICKTITE and PILOTPAK Nozzles

Specifications of STICKTITE and PILOTPAK Nozzles -.-5 Specifications of STICKTITE and PILOTPK Nozzles This graph indicates the relationship between capacity and applied mixture differential pressure for STICKTITE and PILOTPK nozzles when fed with an

More information

Boiler Operation, Maintenance, and Settings. Matthew Baxter Technical Director, Core Biomass

Boiler Operation, Maintenance, and Settings. Matthew Baxter Technical Director, Core Biomass Boiler Operation, Maintenance, and Settings Matthew Baxter Technical Director, Core Biomass How is a boiler designed to Operate? The boiler must be designed around the key characteristics of the fuel,

More information

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM DIESEL SPACE HEATER - SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER ASSEMBLY 3. FUEL PUMP ASSEMBLY

More information

Operating & Maintenance Manual

Operating & Maintenance Manual Operating & Maintenance Manual HOT WATER PETROL HIGH PRESSURE CLEANER SW15200PE AND SW21200PE Made By : Spitwater Australia 953 Metry St North Albury, NSW, Australia WARNING: FAILURE TO FOLLOW OPERATING,

More information

Diesel Cooker x100. Operating and Maintenance Instructions

Diesel Cooker x100. Operating and Maintenance Instructions Diesel Cooker x100 Operating and Maintenance Instructions Dear Webasto customer, Congratulations for buying the Webasto Diesel Cooker X100. You have purchased a high-quality Webasto product which will

More information

Preventative Maintenance Tune-ups

Preventative Maintenance Tune-ups Chapter 14 Preventative Maintenance Tune-ups The preventive maintenance tune-up is the most important service our industry offers. A properly performed tune-up assures the customer that their heating system

More information

R&D on Oil-Burning, Environment - Friendly, High-Efficiency Boiler

R&D on Oil-Burning, Environment - Friendly, High-Efficiency Boiler 2001.M4.3.1 R&D on Oil-Burning, Environment - Friendly, High-Efficiency Boiler (Environment-Friendly, High-Efficiency Boiler Group) Takashi Murakawa, Hiroshi Kato, Hiroshi Matsumoto, Kentaro Sato, Yasuhiro

More information

Low Temperature Burners - STICKTITE and PILOTPAK Nozzles

Low Temperature Burners - STICKTITE and PILOTPAK Nozzles Low Temperature Burners - STICKTITE and PILOTPK Nozzles STICKTITE & PILOTPK Flame retention nozzles -.- For open-port firing or open environment firing Provides positive flame retention and stable clean

More information

RULE EMISSIONS OF OXIDES OF NITROGEN FROM SMALL INDUSTRIAL, INSTITUTIONAL, AND COMMERCIAL BOILERS, STEAM GENERATORS, AND PROCESS HEATERS

RULE EMISSIONS OF OXIDES OF NITROGEN FROM SMALL INDUSTRIAL, INSTITUTIONAL, AND COMMERCIAL BOILERS, STEAM GENERATORS, AND PROCESS HEATERS RULE 1146.1. EMISSIONS OF OXIDES OF NITROGEN FROM SMALL INDUSTRIAL, INSTITUTIONAL, AND COMMERCIAL BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (a) Definitions 1. ANNUAL HEAT INPUT means the actual amount

More information

Oxygen Probe Troubleshooting Guide Marathon Monitors, Inc.

Oxygen Probe Troubleshooting Guide Marathon Monitors, Inc. Oxygen Probe Troubleshooting Guide 2010 Marathon Monitors, Inc. NOTE All of the following tests assume that the oxygen sensor is operating above 1100 F and the process that is being read is stable. Sensor

More information

Chapter 5 Oxygen Based NOx Control

Chapter 5 Oxygen Based NOx Control Chapter 5 Oxygen Based NOx Control Editor s Note: Chapter 5 is written by Dr. Brian Doyle and is drawn primarily from personal knowledge and the material developed for the NOx Emissions course offered

More information

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

X4 Installation and Operation Manual - POWER FLAME INCORPORATED 7.13.2 Set the burner s combustion air inlet damper to the approximate setting as shown in this manual for the desired firing rate. Also, verify that the correct main orifice is installed in the main orifice

More information

2.0 Burner Operating Parameters and Requirements

2.0 Burner Operating Parameters and Requirements ECLIPSE INFORMATION GUIDE Silicon Carbide Radiant Auto-Recupes Info 322 2/99 WARNING Handle silicon carbide tubes carefully. Do not drop them or hammer on them. Although they feature excellent mechanical

More information

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the

More information

UNDERSTANDING TURBOCHARGERS THE ENGINEERS MANUAL TURBOCHARGER SERVICE & FAULT FINDING

UNDERSTANDING TURBOCHARGERS THE ENGINEERS MANUAL TURBOCHARGER SERVICE & FAULT FINDING UNDERSTANDING TURBOCHARGERS THE ENGINEERS MANUAL TURBOCHARGER SERVICE & FAULT FINDING WHY TURBOCHARGE? Ever since the introduction of diesel engines the demand has always been for small engines capable

More information

Section 3 Technical Information

Section 3 Technical Information Section 3 Technical Information In this Module: Engine identification Modes of operation Battery charging and heat manage operation Service and repair procedures Maintenance requirements Engine Identification

More information

CLEANING, INSPECTION AND REPAIR. Valve Spring Compressor (Part No. HD-34736B) Figure Compressing Valve Springs

CLEANING, INSPECTION AND REPAIR. Valve Spring Compressor (Part No. HD-34736B) Figure Compressing Valve Springs b0134x3x 5694 8 7 12 10 1 6 13 11 Valve Spring Compressor (Part No. HD-34736B) 9 Figure 3-11. Compressing Valve Springs 5 14 4 3 2 15 2767a 1. Right crankcase half 2. Pin (2) 3. O-ring (2) 4. Plate 5.

More information

Engine Oil Transmission Oil + Filter

Engine Oil Transmission Oil + Filter Part Desc Engine Oil Transmission Oil + Filter Oil Filter Air Filter A/C Filters Fuel Filter Spark Plugs Battery Tires Brake Pads (Front & Rear) Disc brakes Wiper Blades Leather Seats taking care Check

More information

FABER BURNER ROUTINE MAINTENANCE

FABER BURNER ROUTINE MAINTENANCE FABER BURNER ROUTINE MAINTENANCE Version 2016 The Faber burner is designed for minimal maintenance; however, the frequency and quantity of maintenance that is required depends upon many factors which vary

More information

Installation- and maintenance instruction BENTOFLEX ST133KA/K

Installation- and maintenance instruction BENTOFLEX ST133KA/K Installation- and maintenance instruction BENTOFLEX ST133KA/K 178 007 17 DESCRIPTION Components 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly 6. Nozzle 7.

More information

Retrofitting of Mitsubishi Low NOx System

Retrofitting of Mitsubishi Low NOx System 111 Retrofitting of Mitsubishi Low NOx System Susumu Sato *1 Yoshinori Kobayashi *1 Takao Hashimoto *2 Masahiko Hokano *2 Toshimitsu Ichinose *3 (MHI) has long been engaged in low NOx combustion R & D

More information

PROCEDURE TO BE FOLLOWED WHEN COMBUSTION PROBLEMS ARE EXPERIENCED WITH APPLIANCES HAVING VAPORISING BURNERS

PROCEDURE TO BE FOLLOWED WHEN COMBUSTION PROBLEMS ARE EXPERIENCED WITH APPLIANCES HAVING VAPORISING BURNERS OFG/102 PROCEDURE TO BE FOLLOWED WHEN COMBUSTION PROBLEMS ARE EXPERIENCED WITH APPLIANCES HAVING VAPORISING BURNERS Cover Price 10 (ex.vat and p&p) (Please note this information sheet is available from

More information

AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM)

AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM) AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM) FREQUENTLY ASKED QUESTIONS AIMS was discontinued as a factory option for 13amp electric and gas AGAs in 2015 however the

More information

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KA/K Installation- and maintenance instruction B20KA/K 1 171 615 27 05-01 178 091 07 DESCRIPTION COMPONENTS 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition cables

More information

Installation- and maintenance instruction B20KAV/KV

Installation- and maintenance instruction B20KAV/KV Installation- and maintenance instruction B20KAV/KV 1 171 615 33 05-01 178 035 08 DESCRIPTION COMPONENTS 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition

More information

PRINCIPLES OF COMBUSTION

PRINCIPLES OF COMBUSTION PRINCIPLES OF COMBUSTION INTRODUCTION Combustion is a chemical reaction Rapid oxygenation/oxidation Compounds move from a high to a low energy state by releasing some energy Usually produces visible radiance

More information

Intake and Exhaust System, Design and Function

Intake and Exhaust System, Design and Function Volvo Trucks North America Greensboro, NC USA DService Bulletin Trucks Date Group No. Page 12.2006 250 34 1(6) Intake and Exhaust System Design and Function D13F Intake and Exhaust System, Design and Function

More information

MULTIFIRE. High temperature dual fuel burner

MULTIFIRE. High temperature dual fuel burner MULTIFIRE High temperature dual fuel burner High temperature burners - MULTIFIRE 3-11.3-1 Operates on-ratio or with excess air to meet the specific demands of your combustion process needs Burns most clean,

More information

Installation- and maintenance instruction B80-2/3

Installation- and maintenance instruction B80-2/3 Installation- and maintenance instruction B80-2/3 1 171 625 22 05-01 178 002 64 DESCRIPTION COMPONENTS 1. Flame cone 2. Shrouded disc 3. Nozzle 4. Nozzle assembly 5. Ignition electrodes 6. Ignition cable

More information

ATOMIZATION OF LIQUID FUELS COMBUSTION AND FUELS

ATOMIZATION OF LIQUID FUELS COMBUSTION AND FUELS ATOMIZATION OF LIQUID FUELS THE PRINCIPLE OF LIQUIDS ATOMIZATION Atomization is the process whereby bulk liquid is transformed into a collection of drops. This transformation goes through the break-up

More information

UNIT IV INTERNAL COMBUSTION ENGINES

UNIT IV INTERNAL COMBUSTION ENGINES UNIT IV INTERNAL COMBUSTION ENGINES Objectives After the completion of this chapter, Students 1. To know the different parts of IC engines and their functions. 2. To understand the working principle of

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence The Universal TM gas LowNOx series water heaters contain an electronic spark ignition system. The heater is connected to a 120VAC power source required by the transformer. The transformer steps down the

More information

Water pump Owner's Manual

Water pump Owner's Manual Water pump Owner's Manual Safety Precautions I. General Safeguards Please read this operation manual to have a thorough understanding of the content there before use the product. Failure to do so may lead

More information

TROUBLESHOOTING. 1. What is the model and serial number? If you don t know, how old is it? Give description.

TROUBLESHOOTING. 1. What is the model and serial number? If you don t know, how old is it? Give description. TROUBLESHOOTING There is excellent literature on our website: heatec.com. Look under TEC-NOTE. You will find our newest heater manual. This is full of information (complete with great pictures) on our

More information

E Series CE Approved Intermittent Pilot Ignition Control

E Series CE Approved Intermittent Pilot Ignition Control Installation Instructions Issue Date January 11, 2013 E Series CE Approved Intermittent Pilot Ignition Control Application The E Series CE Approved Intermittent Pilot Ignition Control is a safety control

More information

Here below is a technical description on how to perform a complete cleaning and restoration of a PETROMAX CP.

Here below is a technical description on how to perform a complete cleaning and restoration of a PETROMAX CP. Here below is a technical description on how to perform a complete cleaning and restoration of a PETROMAX 829 500CP. Preface The description below is based on the work I did and the experiences I had during

More information

Oil - kerosene burner

Oil - kerosene burner Installation, use and maintenance instructions Oil - kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 9038 () TECHNICAL FEATURES Thermal power output 8 0 kw.3 5 kg/h Fuel Gas oil 35s,

More information

White paper. MARPOL Annex VI fuel strategies and their influence on combustion in boilers

White paper. MARPOL Annex VI fuel strategies and their influence on combustion in boilers MARPOL Annex VI fuel strategies and their influence on combustion in boilers May 2018 Intro In 2004, MARPOL Annex VI Regulations for the Prevention of Air Pollution from Ships were adopted and in regulation

More information

Internal Combustion Engines

Internal Combustion Engines Internal Combustion Engines The internal combustion engine is an engine in which the burning of a fuel occurs in a confined space called a combustion chamber. This exothermic reaction of a fuel with an

More information

Maintenance. Part A, Section 5. This section covers the following unit configurations.

Maintenance. Part A, Section 5. This section covers the following unit configurations. Part A, Section 5 This section covers the following unit configurations. Model 3100V 3400V 3830V 3860V 3890V 3930V Voltage 1, 2 Pump AC Gear (K or L) Manifold 4-Port (J)) Control Vista Standard (V) Vista

More information

SECTION 6 5 SERVICE PROCEDURES AND SPECIFICATIONS. Body

SECTION 6 5 SERVICE PROCEDURES AND SPECIFICATIONS. Body SECTION 6 5 SERVICE PROCEDURES AND SPECIFICATIONS Body Specifications 236 Protecting your vehicle from corrosion 237 Washing and waxing 238 Cleaning the interior 239 235 SPECIFICATIONS DIMENSIONS AND WEIGHT

More information

MP V 8A Electronic Smart Charger. Instruction and Information Manual

MP V 8A Electronic Smart Charger. Instruction and Information Manual MP7428 12V 8A Electronic Smart Charger Instruction and Information Manual In order to ensure correct and safe usage of your battery charger, you should read these instructions carefully. Please retain

More information

DURAFire Oil Igniter User Manual. Publication Rev H

DURAFire Oil Igniter User Manual. Publication Rev H DURAFire Oil Igniter User Manual Publication INTRODUCTION This manual contains information for the DuraFire Oil Igniter from Forney Corporation, 16479 North Dallas Parkway, Suite 600 Addison, TX 75001.

More information

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25 V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25 www.republicsales.com Revised 10.14 2014 Republic Sales & Manufacturing Single Stage Rotary Vane Vacuum

More information

TFL Gas Log Lighter (TFLGLL)

TFL Gas Log Lighter (TFLGLL) TFL Gas Log Lighter (TFLGLL) For Jetmaster Metal Fireboxes and Logpans CONTENTS Description Page No. Important information 2 Operation and Design 3 Controller Solenoid Cavity 4 Contents of a Kit 5 To install

More information

HVF110, 210, 310, 410HD

HVF110, 210, 310, 410HD 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. HVF110, 210, 310, 410HD

More information

Installation- and maintenance instruction B20K-2

Installation- and maintenance instruction B20K-2 Installation- and maintenance instruction B20K-2 1 171 615 51 05-01 178 017 09 DESCRIPTION COMPONENTS 1. Damper motor 2. Air damper 3. Photocell 4. Scale, nozzle assembly 5. Test nipple 6. Nozzle assembly

More information

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw LOW NOx T The RL/M BLU burners series covers a firing range from 360 to 1023 kw, and it has been designed for use in hot or superheated water boilers, hot air or steam generators and diathermic oil boilers.

More information

First Correlating Revision No. 1-NFPA [ Section No ]

First Correlating Revision No. 1-NFPA [ Section No ] First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion

More information

MAINTENANCE SCHEDULE

MAINTENANCE SCHEDULE MAINTENANCE SCHEDULE System Check Item Daily 50 250 500 1000 1500 2000 Grease PTO anti-rotating shields Grease and lubricate ales and PTO bearings Grease fan motor (1 pump) (DO NOT OVER GREASE) Grease/Lube

More information

Table of Contents Foreword I. Product Introduction II. Notice For Safety III. Main Technical Parameters IV.

Table of Contents Foreword I. Product Introduction II. Notice For Safety III. Main Technical Parameters IV. Foreword Thank you for choosing the LGK-ID IGBT Digital Air Plasma Cutter of Delixi (Hangzhou) Inverter Co., Ltd. Before use LGK-ID IGBT Digital Air Plasma Cutter, please carefully read this Manual to

More information

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor OPERATIONS MANUAL The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor Safe, reliable ignition and flame failure protection combined with a proven, completely self-powered

More information

CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER

CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER ABSTRACT This paper discusses the measures taken to upgrade controls for a coal-fired boiler which was experiencing problems with primary air flow, furnace

More information

INSTRUCTIONS FOR MAINTENANCE AND USE KITCHEN EXTRACTOR HOOD ZRW 50/60

INSTRUCTIONS FOR MAINTENANCE AND USE KITCHEN EXTRACTOR HOOD ZRW 50/60 INSTRUCTIONS FOR MAINTENANCE AND USE KITCHEN EXTRACTOR HOOD ZRW 50/60 Dear Customer You are now a user of a kitchen extractor hood of ZRW type. This hood has been designed and manufactured specially with

More information

Oil Metering Valve. Information and rebuild instructions. #905005

Oil Metering Valve. Information and rebuild instructions. #905005 Sig Marine Products #407-204 Cayer St. Coquitlam B.C. Canada V3K 5B1 www.sigmarine.com info@sigmarine.com T: 800 659 9768 Oil Metering Valve Information and rebuild instructions. #905005 Do not plug the

More information

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart Service Manual Contents 1. Names of components 2 2. Safety Devices 3 3. Specifications 4 4. Wiring Diagam 4 5. Sequence Time Chart 5 6. 7. 8. Troubleshooting 6 Standard resistance & Voltage 13 Check &

More information

Light condition and operation Windshield glass condition Wiper blade condition Paint condition and corrosion Fluid leaks Door and hood lock condition

Light condition and operation Windshield glass condition Wiper blade condition Paint condition and corrosion Fluid leaks Door and hood lock condition GENERAL CHECKS Engine Compartment The following should be checked regularly: Engine oil level and condition Transmission fluid level and condition Brake fluid level Clutch fluid level Engine coolant level

More information

SEASONAL MAINTENANCE CHECKLISTS Johnson Controls

SEASONAL MAINTENANCE CHECKLISTS Johnson Controls SPRING CHECK LIST ABSORPTION CHILLERS Check starter and control panel. Leak test. Check hand valve diaphragms and replace as required. Check operation of purge unit. Change oil in the purge pump. Lubricate

More information

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53 Installation, use and maintenance instructions Kerosene burners One stage operation CODE MODEL TYPE 3749053 G3BF 490T53 374957 G5BF 49T57 3748953 G5BF 489T53 9036 (6) TECHNICAL FEATURES TYPE - Boiler

More information

www.thecarproblems.com/automotive-service-centre How You Diagnose Your Car Problems And Save Money A Quick Look At An Automotive Service Turbo For Your Car - Benefits, Precautions And Just How Does It

More information

AHE S - 12 VDC AHE X - 12 VDC AHE X - 12 VDC

AHE S - 12 VDC AHE X - 12 VDC AHE X - 12 VDC Shop Manual Model Numbers AHE-100-04S - 12 VDC AHE-120-04X - 12 VDC AHE-130-04X - 12 VDC TABLE OF CONTENTS Section 1 Section 2 Section 3 Section 4 General Heater Information 1.1 Component Overview 1.2

More information

Sales : Mobile : The Zenith 24 T-2 carburettor

Sales : Mobile : The Zenith 24 T-2 carburettor The Zenith 24 T-2 carburettor is an up draught carburettor, developed principally for use on your Ferguson TEA20 (Vaaljapie) tractor. It can be supplied in several versions, the main variations being the

More information

Service Bulletin Published by Sudden Service, Inc.

Service Bulletin Published by Sudden Service, Inc. Service Bulletin Published by Sudden Service, Inc. Volume 18 / Number 2 / February 1, 2018 Louisville, Mississippi Preventative Maintenance (PM) Requirements for Diesel Engines Equipped With EPA Tier 4

More information

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course Mobile Diesel Heaters GRY-D / GRY-I Service Training Course 1 Rev. No. 3 January 24, 2011 GRY-I Indirect-fired Diesel Heaters GRY-I 15 WU GRYP 50 AP GRY-I 25 WU GRYP 90 AP GRY-I 40 WU GRYP 135 AP 2 GRY-D

More information

HOW - TO EMISSION CONTROL BASICS EMISSION CONTROL BASICS

HOW - TO EMISSION CONTROL BASICS EMISSION CONTROL BASICS HOW - TO EMISSION CONTROL BASICS EMISSION CONTROL BASICS Tool And Material Checklist Bore Brush Thermometer Portable Vacuum Pump Screwdriver Combination Wrench Set 3/8 Drive Socket Set Tachometer Rag Service

More information

Air Management System Components

Air Management System Components AIR M anagement Sys tem Air Management System Components Air Management System Features Series Sequential The series sequential turbocharger is a low pressure/high pressure design working in series with

More information

1-50 KVA SINGLE-PHASE SERVO REGULATOR INSTRUCTIONS FOR USE SERVO SINGLE-PHASE VOLTAGE REGULATOR

1-50 KVA SINGLE-PHASE SERVO REGULATOR INSTRUCTIONS FOR USE SERVO SINGLE-PHASE VOLTAGE REGULATOR 1-50 KVA SINGLE-PHASE SERVO REGULATOR INSTRUCTIONS FOR USE SERVO SINGLE-PHASE VOLTAGE REGULATOR I Important Notice! Thank you for preferring us. Your product has been designed to protect your sensitive

More information

Routine Burner Service

Routine Burner Service Routine Burner Service WARNING Rural Energy Enterprises, Inc. does not accept liability for the improper use of this information. Installation, service, and maintenance of heating equipment should be performed

More information

Accucraft Decauville 3.5t Type 1 1:13.7

Accucraft Decauville 3.5t Type 1 1:13.7 Accucraft Decauville 3.5t Type 1 1:13.7 B77-531 7/8ths Type 1 Maroon B77-532 7/8ths Type 1 Green B77-533 7/8ths Type 1 Black Instruction Manual for Decauville Type 1 Note: Please read the entire manual

More information

Boiler Fuel Firing System

Boiler Fuel Firing System Boiler Fuel Firing System COMBUSTION Everywhere, at all times, oxygen combines with other elements. This general process is called Oxidation Burning, or Combustion, is a special form of oxidation: - Oxygen

More information

SHAFT ALIGNMENT FORWARD

SHAFT ALIGNMENT FORWARD Service Application Manual SAM Chapter 630-76 Section 24 SHAFT ALIGNMENT FORWARD One of the basic problems of any installation is aligning couplings or shafts. Therefore, this section will endeavor to

More information

Midge-Tech Limited Troubleshooting Guide

Midge-Tech Limited Troubleshooting Guide Midge-Tech Limited Troubleshooting Guide 1 of 15 Index Cover Page... 1 Index.. 2 FAQ Defender.. 3 Liberty Plus.. 4 Pro & Pro Plus. 5 Fault Codes / Troubleshooting Defender Start Sequence.. 6 Liberty Plus

More information

ZEECO BURNER DIVISION

ZEECO BURNER DIVISION ZEECO BURNER DIVISION Enhanced Jet Flat Flame Burners GLSF Series 22151 EAST 91ST STREET BROKEN ARROW OK 74014 USA +1-918-258-8551 SALES@ZEECO.COM ZEECO.COM INTRODUCTION: This document discusses the advantages

More information

RULE BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (Adopted 5/11/93, Revised 6/13/95, 6/13/00, 9/11/12)

RULE BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (Adopted 5/11/93, Revised 6/13/95, 6/13/00, 9/11/12) VENTURA COUNTY AIR POLLUTION CONTROL DISTRICT RULE 74.15.1 - BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (Adopted 5/11/93, Revised 6/13/95, 6/13/00, 9/11/12) A. Applicability The provisions of this

More information

KH E, KH E

KH E, KH E INSTRUCTIONS FOR USE Kitchen extractor hood Type: KH 17101 E, KH 17106 E Dear Customer!! You are now a user of the newest generation kitchen extractor hood of KH 17101, KH 17106. This hood has been designed

More information

What is the secret to INOV8 s Burner Technology?

What is the secret to INOV8 s Burner Technology? What is the secret to INOV8 s Burner Technology? 1 1.0 INOV8 s Approach INOV8 Approach to Industry Challenges 1. What are the Technical Challenges to Burning Waste Oil? 2. How does INOV8 Solve these Challenges?

More information

Combustion Gas Turbine Fuel Pumps. CIRCOR White Paper

Combustion Gas Turbine Fuel Pumps. CIRCOR White Paper Combustion Gas Turbine Fuel Pumps CIRCOR White Paper The modern combustion gas turbine is one of the most reliable machines in use and a workhorse of the electric power generation industry. It can be on-site

More information

Airejet. Low NOx Coal Burner. Type: Design features: NO X removal efficiencies:

Airejet. Low NOx Coal Burner. Type: Design features: NO X removal efficiencies: Airejet Low NOx Coal Burner Unique low NO X coal burner with center air jet for use with overfire air (OFA) systems. Sleeve Damper Actuator Core Air Inlet Duct and Damper Pitot Grid Outer Spin Vanes Inner

More information

(2) ANNUAL HEAT INPUT means the actual amount of heat released by fuels burned in a unit during a calendar year.

(2) ANNUAL HEAT INPUT means the actual amount of heat released by fuels burned in a unit during a calendar year. 1 of 11 8/21/2012 10:19 AM SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1146 - EMISSIONS OF OXIDES OF NITROGEN FROM INDUSTRIAL, INSTITUTIONAL, AND COMMERCIAL BOILERS, STEAM GENERATORS, AND PROCESS

More information

TEST DATA REPORT TRGA Homogenizer on the Boiler Nr.5, Heat Station (Period of Tests: )

TEST DATA REPORT TRGA Homogenizer on the Boiler Nr.5, Heat Station (Period of Tests: ) APPROVED General Manager of.. 2010 Date: 08.10.2010 Fria TEST DATA REPORT TRGA Homogenizer on the Boiler Nr.5, Heat Station (Period of Tests: 01.09.2010-01.10.2010) (Boiler 5: model БКЗ-160-9,8-490М, Manufacturer:

More information

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100 V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100 www.republicsales.com Revised 02.15 2015 Republic Sales & Manufacturing Single Stage Rotary Vane

More information

Light oil - kerosene burner

Light oil - kerosene burner Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 3747455 G0KI 474T5 90403 (4) - 0/008 TECHNICAL DATA Thermal power output 95 3 kw 8 8 kg/h

More information

AUTOMATIC AIRSPRAY GUN

AUTOMATIC AIRSPRAY GUN INSTRUCTION MANUAL AUTOMATIC AIRSPRAY GUN Manual : 0407 573.011.212 Date : 19/07/04 Supersede : KREMLIN REXSON - Site de Stains : 150, avenue de Stalingrad 93 245 - STAINS CEDEX - FRANCE Téléphone : 33

More information

VICTRIX PRO Wall-hung modular condensing boiler for heating only

VICTRIX PRO Wall-hung modular condensing boiler for heating only PRO Wall-hung modular condensing boiler for heating only Wide range (5 models) High efficiency and low pollutant emissions thanks to condensing technology Modulating heat output from 10 to 100% Possible

More information

Kerosene - oil burner

Kerosene - oil burner Installation, use and maintenance instructions Kerosene - oil burner Two stage operation CODE MODEL TYPE 3746686 G0D 76T8 90 (0) TECHNICAL FEATURES Thermal power output 44 / 54 0 kw 3.7 / 4.5 0 kg/h Fuel

More information

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KA/K Installation- and maintenance instruction B20KA/K 178 091 07 DISCRIPTION Components 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition cables 6. Schrouded

More information

MAINTENANCE CHECKLIST & SCHEDULE FOR THE IDH RANGE

MAINTENANCE CHECKLIST & SCHEDULE FOR THE IDH RANGE MAINTENANCE CHECKLIST & SCHEDULE FOR THE IDH RANGE INDUSTRIAL DIESEL HEATERS Details about recommended maintenance checks, components brief and how to check and replace parts as part of the maintenance

More information

CODE MODEL TYPE PRESS GW 605 T80

CODE MODEL TYPE PRESS GW 605 T80 Installation, use and maintenance instructions Pressure jet burner CODE MODEL TYPE 3473784 PRESS GW 605 T80 291 (2) - 08/2012 Thermal power 107 / 178-350 kw - 92.000 / 153.000-301.000 kcal/h Output 9/15-30

More information