1 Variable Speed Pumping Jim Vukich Application Engineer ITT Corp. Malvern, PA
2 Why Do It?
3 Why Do It? Flow-Matching Minimize Starting & Stopping Flexibility Different Discharge Points, Flows Changing Conditions Present & Future
4 How To Do It? Adjustable-Speed Devices
5 How To Do It? 2-Speed Motor Two Windings in a Single Stator
6 How To Do It? Transmission Belts & Pulleys, Gears, etc.
7 How To Do It? VFD The Most Common Method Today
8 VFD Variable Frequency Drive
9 VFD Variable Frequency Drive We can change the speed of the motor by varying the frequency of the signal Frequency = Cycles per second = Hertz In the U.S. systems operate on 60Hz nominal
10 VFD Variable Frequency Drive
11 Types of VFDs Current Source Inverter Simple, but Noisy Flux Vector Control Precise, but Expensive Pulse Width Modulated Most Common for Pumps
12 Pulse Width Modulation Uses a Constant Voltage Pulsed with Integrated Bi-Polar Power Transistors Vary the Width of the Pulses to Generate a Sine Wave Switching Frequency Higher is Better (to a point)
13 Pulse Width Modulation
14 Effects on the Motor Harmonics Noise Torque Ripple Overheating Modern VFDs have eliminated most of these problems!
15 Reduced Torque
16 Effects on the Motor Steep Voltage Transients Short Rise Times Stress on the Insulation Material Reduced Motor Efficiency
17 Sizing the VFD What You Need to Know: Motor Full-Load kva Ratio of Maximum to Normal Torque
18 Sizing the VFD Do NOT size the VFD based on the horsepower!!! Size it on current and voltage Pumps are variable torque machines Pump VFDs often need to be oversized
19 Sizing the VFD Full-Load kva (Volts x Amps x 3) 1000 Size the VFD at least 10% higher than the motor
20 Sizing the VFD Older motors or cheap motors need to be de-rated 10% to 15% de-rating is typical Insist on a VFD-ready motor! Class H insulation High-fill impregnation
21 Sizing the VFD Make sure the VFD is rated for the same number of starts per hour as the motor
22 Why VFDs are Used in Pumping
23 Why VFDs are Used in Pumping A VFD allows you to change the flow and head performance of your pump
24 Why VFDs are Used in Pumping Flow Matching Match the inflow rate Maintain the outflow rate Maintain a constant liquid level in the sump Minimize the sump volume
25 Why VFDs are Used in Pumping Changing Conditions Over Time Increase flow without new pumps Maintain flow as new pump stations come online
26 Why VFDs are Used in Pumping VFDs can be used as soft start and soft stop VFDs can be used as phase converter
27 Why VFDs are Used in Pumping A VFD allows you to change the flow and head performance of your pump
28 Single Speed Curve
29 The Golden Rule for Pumps The pump can only operate at ONE point Where it intersects the system curve
30 The Golden Rule
31 Variable Speed Field
32 Many Possible Operating Points!
33 Efficiency vs. Speed
34 The System Curve
35 The Allowable Operating Range
36 Specific Energy kw-hrs per Million gallons
37 Different Kinds of System Curves
38 Risks & Limitations of VFD Pumping
39 Operation Outside of Allowable Range
40 The Allowable Operating Range
41 When you operate outside of the allowable range: Recirculation Clogging, Wear, Heat Rise Vibration Shaft Bending Stress on Seals and Bearings Cavitation
42 Recirculation Wear
43 Wear Heat Rise
44 Clogging Dirty little secret: There is no such thing as a non-clog impeller Any kind of impeller can clog if operated under the wrong conditions
45 Clogging Impeller energy drops off rapidly at reduced speeds If speed = 50%, impeller energy = 25% Turbulent zone moves further from leading edge Rags build up on the impeller Less available torque to pass the occasional mophead
46 The Turbulent Zone
47 Unstable Region Stall Point
48 Motor Cooling Motors with cooling jackets may require a minimum speed To provide heat transfer To prevent settling of solids Check with the equipment manufacturer
49 Natural Frequencies
50
51 Natural Frequencies All systems have a natural, or resonant, frequency. If that frequency is fed into the system from an external source, the system will begin to vibrate.
52 Natural Frequencies As the VFD ramps up and down, it may hit certain frequencies that excite the system The controls must be set to lock out those dangerous frequencies
53 Natural Frequencies Always install flex connectors to isolate the pump from the piping Always support the piping independent of the pump Pipe hangers Thrust blocks Base elbows
54
55 Running Above 60Hz Be very careful!!! 10% overspeed requires 33% more power NPSH goes up risk of cavitation recommends 63Hz maximum
56 Reliability A VFD is an in-line device Any in-line device will reduce the reliability and efficiency of the system
57 The Downside of Constant Liquid Level
58 Grease Ring Floating Debris
59 Operational Strategies or The Smart Way to VFD Pumping
60 Operational Strategies The #1 problem with VFD pumping is clogging Clogging usually results from running the pump too slow for too long
61 Prevent Clogging Know the limitations of your pump Set the minimum speed to stay within the A.O.R. Consider running in on/off mode at the minimum speed
62 Prevent Clogging Start at full speed and then ramp down This will clear clogs, and will open check valves fully Ramp up to full speed once in a while, to clear clogs and flush out cooling jackets
63 Grinder Pumps Don t run a grinder pump on a VFD Grinder pumps depend on torque to do their work Available torque is reduced when run on VFD
64 Keep the Sump Clean Vary the on/off level to prevent grease rings Run the pumps to snore to suck up debris
65 Keep the Sump Clean The controls may automate this for you!
66 Running Multiple Pumps on VFD Always ramp the 1st pump up to full speed before bringing the 2nd pump online Slow down the 1st pump to match the 2nd This is called synchronous operation
67 Use the Right Settings If using VFD as soft-start, ramp up to full speed as quickly as possible If using VFD as soft-stop, choose the correct setting! Otherwise, water hammer may occur
68 Use the Right Settings Make sure the VFD is set for a variable torque load This will maintain: Magnetization level Motor efficiency
69 Use the Right Settings Some VFDs have built-in presets for equipment: Pumps Blowers Compressors Fans Make sure you are using the pump settings!
70 Use the Right Settings Switching frequency Should be in the 3 to 4 khz range Any higher can damage the motor Any lower can cause audible noise
71 Installation Guidelines
72 Pump Sensors Some types of sensors may be sensitive to noise and harmonics generated by the VFD Filters may be required Check with the pump mfgr. Check with the VFD mfgr.
73 VFD Output Filter Reduces Noise Can eliminate need for motor de-rating Can reduce nuisance tripping (false alarms)
74 Pump Sensors Use shielded wire to carry the sensor signals, especially on long runs Run the power and sensor cables in separate conduits, spaced at least 12 inches apart
75 Power Factor Correction Capacitors PWM drives will keep the power factor at 95% or better Capacitors are not required Capacitors can actually be destroyed by the VFD!
76 VFD in same cabinet with other components VFD must be properly constructed to prevent interference
77 Bypass Contactor Insist on getting a bypass contactor installed Eliminates the VFD in emergency situations Helps with troubleshooting
78 Use Caution when Taking Readings You need a true RMS meter to take accurate readings of voltage, current, and power
79 Conclusions
80 Conclusions VFDs are NOT a cure-all!! They have their problems and you must use caution Be aware of the limitations of your equipment Pumps Pipe system VFDs
81 Conclusions VFDs are NOT appropriate for all systems High static head (flat system curve) may not work well with VFDs Don t use a VFD with grinder pumps
82 Conclusions VFDs can result in off-peak operation of the pumps This will lead to problems! Clogging Vibration Wear Lower efficiency Shorter life
83 Stay within the Allowable Operating Range
84 Restrict operation outside A.O.R. to short or intermittent duty ONLY
85 Conclusions Avoid VFDs if possible Consider the alternatives: Use different-sized pumps (jockey pumps) Make the wet well larger Choose pumps that can start more times per hour
86 Conclusions Avoid VFDs if possible If not correctly applied, VFDs may: Increase cost Increase complexity Decrease efficiency Decrease reliability
87 ?? Questions??
Variable Speed Drives Controlling Centrifugal Pumps Energy Savings
2018 Clean and Safe Drinking Water Workshop Hotel Gander Variable Speed Drives Controlling Centrifugal Pumps Energy Savings Presenter: Dave Galbraith What is a Variable Speed (Frequency) Drive? AKA VFD,
More informationASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.
ASHRAE - Variable Speed Drives By Dan Watkins, LEED BD+C Bornquist, Inc. Adjustable Frequency Drive Fundamentals How does a VFD actually work VS Pumping Analysis VS Pumping Features Harmonics VFDs and
More informationQuestion Number: 1. (a)
Session: Summer 2008 Page: 1of 8 Question Number: 1 (a) A single winding machine cannot generate starting torque. During starting the switch connects the starting winding via the capacitor. The capacitor
More informationSDC,Inc. SCR-Regenerative Ac Drive
SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency
More informationCódigo de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código
Letra de código Código de rotor bloqueado Rotor bloqueado, Letra de código kva / hp kva / hp A 0.00 3.15 L 9.00 10.00 B 3.15 3.55 M 10.00 11.00 C 3.55 4.00 N 11.00 12.50 D 4.00 4.50 P 12.50 14.00 E 4.50
More informationSteve Schouten. Donna Densmore
March 12, 2013 2 Steve Schouten Donna Densmore 3 Mike Carter Justin Kale 4 Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality Issues Source: Emerson Industrial Automation
More informationCT430 - Soft Starters on Motor Applications
CT430 - Soft Starters on Motor Applications Bill Bernhardt Sr. Commercial Engineer May 16, 2018 PUBLIC Copyright 2018 Rockwell Automation, Inc. All Rights Reserved. 1 Topics Traditional Motor Starting
More informationVariable Frequency Drive Basics
Variable Frequency Drive Basics Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Variable Frequency Drives are
More informationVariable Frequency Drives
We Make Energy Engaging Variable Frequency Drives Questline Academy Meet Your Panelist Mike Carter questline.com 2 Contents Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality
More informationVFD Best Practices: Getting the Most from Your VFD Investment
TECH TOPICS VFD Best Practices: Getting the Most from Your VFD Investment The purpose of this document is to outline best practices for successful application and installation of VFDs. Following these
More informationPump ED 101. Variable, Fixed Speed Control - - Float Switch Activation. Introduction
Pump ED 11 Variable, Fixed Speed Control - - Float Switch Activation Joe Evans, Ph.D http://www.pumped11.com Introduction It has been said that there is more than one way to skin a cat. In fact, there
More informationWhen to use a Soft Starter or an AC Variable Frequency Drive
White Paper When to use a or an AC Variable Frequency Product lines: Smart Motor Controllers (SMCs), AC Variable Frequency s (VFDs) Topic Page Introduction 2 Starting Methods 3 How does a VFD work? 7 Comparisons
More informationVARIABLE FREQUENCY DRIVES
262923 VARIABLE FREQUENCY DRIVES PART 1: GENERAL 1.01 SUMMARY A. Section Includes: 1. Variable Frequency Drives (VFD) B. Related Sections: 1. Section 230000 - Basic HVAC Requirements 2. Section 230900
More informationPhoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP
Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationECE1750, Spring Motor Drives and Other
ECE1750, Spring 2018 Motor Drives and Other Applications 1 Three-Phase Induction Motors Reliable Rugged Long lived Low maintenance Efficient (Source: EPRI Adjustable Speed Drives Application Guide) The
More informationPump ED 101. Power Factor (Part 2) - - Electricity Behaving Better
Pump ED 101 Power Factor (Part 2) - - Electricity Behaving Better Joe Evans, Ph.D http://www.pumped101.com Last month we took a close look at the flow of voltage and current in purely resistive and inductive
More informationIntroduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung
Introduction to Pekik Argo Dahono Electrical Energy Conversion Research Laboratory Institute of Technology Bandung Why Electric Drives Electric drives are available in any power. They cover a wide range
More informationElectric Motor Controls BOMA Pre-Quiz
Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,
More informationCSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:
CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in
More informationFundamentals of Motors
Fundamentals of Motors 5/05 FOM Fundamentals of Motors Table of Contents Electrical and Magnetic Basics................................................................ 1-2 Fluid Flow versus Electron Flow.............................................................
More informationM T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation
M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed
More informationUsing an SMC-50 Solid-State Smart Motor Controller for Pump Protection
Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection William Bernhardt and Richard Anderson, Rockwell Automation Pump system protection comes in many methods, from preventing water hammer
More informationSECTION MOTORS AND VARIABLE FREQUENCY DRIVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal
More informationDRIVE THE WATER CYCLE. January 10 TH 2013
DRIVE THE WATER CYCLE January 10 TH 2013 DRIVE THE WATER CYCLE EXTENDED FLOW CONTROLS Throttling control Bypass control Parallel Pump control VSD control THROTTLING CONTROL The operation point is modified
More informationHVW701 HVAC Drive with By-Pass
s Automation Energy Transmission & Distribution Coatings HVW701 HVAC with By-Pass Designed Especially for HVAC Systems US.HVW701.By-Pass.07/2017 www.weg.net WEG HVAC-R Products WEG, a leading supplier
More informationContinuing Education Course #206 Introduction to Designing Machine Control Systems Part 2
1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material
More informationESD5500E Series Speed Control Unit
ESD5500E Series Speed Control Unit 1 SPECIFICATIONS INTRODUCTION PERFORMANCE Isochronous Operation ± 0.25% or better Speed Range / Governor 1-7.5 KHz Continuous Speed Drift with Temperature ±1% Maximum
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationIs Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics
Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics Synopsis: This paper describes the use of AC power supplies
More informationHybrid Motor Technology to Achieve Efficiency Levels Beyond NEMA Premium
Hybrid Motor Technology to Achieve Efficiency Levels Beyond NEMA Premium Richard R. Schaefer, Baldor Electric Company ABSTRACT This paper will discuss the latest advances in AC motor design that combines
More informationHigh Frequency SineWave Guardian TM
High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation
More informationA. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.
PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the
More informationV 2.0 DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W. Instruction Manual
DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W Instruction Manual Introduction The AIMS Power 5000 Watt series inverters are the most advanced line of mobile DC to AC power
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationHow to Select a Variable Frequency Drive Based on Load Characteristics
How to Select a Variable Frequency Drive Based on Load Characteristics by Vishnuvarthanaraj (Vishnu) Balaraj, Software/Hardware Engineer KB Electronics for more information, email: info@kbelectronics.net
More informationUptime. All the time.
usa.siemens.com/perfectharmony Uptime. All the time. Siemens SINAMICS PERFECT HARMONY GH180 air-cooled drive Answers for industry. 13-SI-0186_brochure_Perfect Harmony Air-Cooled brochure_v7.indd 3 Downtime
More informationCauses and Cures of Regulator Instability
Causes and Cures of Regulator Instability Introduction Gas Pressure Regulator: Controls pressure by manipulating flow Instability is improper downstream pressure control [File Name or Event] Emerson Confidential
More informationIndustrial Motors. But first..servos!
Industrial Motors DC Motors AC Motors Three Phase Motors Specialty Motors Stepper Motors But first..servos! Servos can be AC or DC but they do one thing: Sense the output position and adjust the input
More informationInverter control of low speed Linear Induction Motors
Inverter control of low speed Linear Induction Motors Stephen Colyer, Jeff Proverbs, Alan Foster Force Engineering Ltd, Old Station Close, Shepshed, UK Tel: +44(0)1509 506 025 Fax: +44(0)1509 505 433 e-mail:
More informationDrive Fundamentals. Motor Control Bootcamp May 15-18, Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC CO900H
- 5058-CO900H Drive Fundamentals Motor Control Bootcamp May 15-18, 2017 How are these Devices Related? Variable frequency drives Variable speed drives Variable speed controllers Adjustable frequency drives
More informationOn Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual
On Line UPS LUC 1000E / LUC 2000E / LUC 3000E User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the UPS. This manual contains
More informationBenefits of VFD for single to three phase conversion
Benefits of VFD for single to three phase conversion Agenda Differences between three phase and single phase power & effects on devices they power What is a VFD and how does it work when used for phase
More informationKelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.
Kelly HSR Opto-Isolated Series Motor Controller with Regen User s Manual HSR72601 HSR72801 HSR12401 HSR12601 HSR12901 HSR14301 HSR14501 HSR14701 Rev.3.3 Dec. 2011 Contents Chapter 1 Introduction... 2 1.1
More informationSineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING
SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationPump Installation and Service Manual HRS Hydromatic Retractable System
Pump Installation and Service Manual HRS Hydromatic Retractable System NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party
More informationVariable Speed Drives in Electrical Energy Management. Course Content
Variable Speed Drives in Electrical Energy Management Course Content Introduction & Overview The basic equation for a 3 phase electric motor is: N = rotational speed of stator magnetic field in RPM (synchronous
More information& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL
72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com
More information1.1 Block Diagram of Drive Components of Electric Drive & their functions. Power Processor / Modulator. Control. Unit
Introduction Motion control is required in large number of industrial and domestic applications like transportations, rolling mills, textile machines, fans, paper machines, pumps, washing machines, robots
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationSupercapacitors & Safety
Supercapacitors & Safety A white paper on the use of supercapacitors in the railway industry Authored by Amarjit Soora, Manager of Engineering, ZTR Control Systems Locomotive Maintenance Officers Association
More informationGENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER
XXXX H02 GENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER XXXX CONTROL OR REGULATION OF ELECTRIC MOTORS, GENERATORS, OR DYNAMO-ELECTRIC CONVERTERS; CONTROLLING TRANSFORMERS, REACTORS OR CHOKE
More informationA. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings
More informationProduct Application Guide- 30mm Stacklights. 30 mm Stacklight- Light Only
Product Application Guide- 30mm Stacklights 30 mm Stacklight- Light Only Part Number Structure JR 28 - RYG - 4 Series: JR = 30mm Round Stacklight Maximum Voltage: 16 = 9 to 16 Vdc; 28 = 20 to 28 Vac/dc
More informationShaft Grounding Rings. Protecting VFD Driven Motors from Bearing Currents
Shaft Grounding Rings Protecting VFD Driven Motors from Bearing Currents Variable Frequency Drives and Electric Induction Motors When pulse width modulation (PWM) Variable Frequency Drives (VFDs) were
More informationQUESTION BANK SPECIAL ELECTRICAL MACHINES
SEVENTH SEMESTER EEE QUESTION BANK SPECIAL ELECTRICAL MACHINES TWO MARK QUESTIONS 1. What is a synchronous reluctance 2. What are the types of rotor in synchronous reluctance 3. Mention some applications
More informationPowerOhm Installation Manual for LG ATV Series Braking Modules
PowerOhm Installation Manual for LG ATV Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationEEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines
Department of Electrical Engineering Lecture Introduction to Electrical Machines 1 In this Lecture Induction motors and synchronous machines are introduced Production of rotating magnetic field Three-phase
More informationAC Line / Load Reactors
AC Line / Load Reactors Table of Contents Delivery / Lead Time.PB03-1100 -2 Selection & Pricing PB03-1100 -4 Replacement Parts..PB03-1100-8 Product Modifications / Options..PB03-1100 -9 Product Specifications..PB03-1100
More informationTechnical News. Power Factor Correction. What technology is best for you? Specialists in electrical and automation products, systems and solutions
Issue #79 - Winter 2018 Technical News Specialists in electrical and automation products, systems and solutions Power Factor Correction What technology is best for you? Written by Samuel Hodgetts NHP nhp.com.au
More informationTechnical Explanation for Inverters
CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor
More informationHVAC-R Drive Products
Motors Automation Energy Transmission & Distribution Coatings HVAC-R Drive Products Designed Especially for HVAC Systems US.HVAC-R Drive.Products.01/2017 www.weg.net/us WEG HVAC-R Products WEG, a leading
More informationFive Reasons for VFDs in HVAC Applications
Five Reasons for VFDs in HVAC Applications Save Money and Improve Performance with HVAC-Specific Drives by Larry Gardner, Yaskawa America, Inc., HVAC Drives Product Marketing Manager yaskawa.com Introduction
More informationServo and Proportional Valves
Servo and Proportional Valves Servo and proportional valves are used to precisely control the position or speed of an actuator. The valves are different internally but perform the same function. A servo
More informationM T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation
M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components
More informationMEANWELL DC/AC POWER INVERTERS
MEANWELL DC/AC POWER INVERTERS A301/A302-1K0 = 1000 Watts A301/A302-1K7 = 1500 Watts A301/A302-2K5 = 2500 Watts A301 = 12VDC input A302 = 24VDC input 230VAC output Don't disassemble Keep away from moisture
More informationHydraulic Pump Troubleshooting P & BDP Series Models
Hydraulic Pump Troubleshooting P & BDP Series Models Hydraulic Pump damage can cause traction circuit failures and problematic hydraulic system contamination. Performance problems such as weak traction
More informationFull Voltage Starting (Number of Starts):
Starting Method Full Voltage Starting (Number of Starts): Squirrel cage induction motors are designed to accelerate a NEMA inertia along a NEMA load curve with rated voltage applied to the motor terminals.
More informationPower Factor Correction
AE9-1249 R10 August 2008 Power Factor Correction Index Page 1. Introduction... 1 2. Electrical Fundamentals... 1 3. Electrical Formulas... 2 4. Apparent Power and Actual Power... 2 5. Effects of Poor Power
More information1321 Power Conditioning Products
Technical Data 1321 Power Conditioning Products Don t Ignore the Cost of Power Line Disturbance Topic Page Product Overview 2 1321-3R and 3RA Series Line Reactors 3 1321 Reflective Wave Reduction (RWR)
More informationTump User's handbook. Life 'Extension. 4th Edition. <By. 'Heinz?. *B(och & Man H Quarts. CRC Press. Taylor& Francis Group THE FAIRMONT PRESS, INC.
Tump User's handbook Life 'Extension 4th Edition
More informationApplication Note CTAN #127
Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy
More informationPrepared By: Ahmad Firdaus Bin Ahmad Zaidi
Prepared By: Ahmad Firdaus Bin Ahmad Zaidi A stepper motor is an electromechanical device which converts electrical pulses into discrete mechanical rotational movements. Stepper motor mainly used when
More informationPowerFlex 6000 Medium Voltage AC Drives
PRELIMINARY INFORMATION PowerFlex 6000 Medium Voltage AC Drives Simple. More Reliable. Easy-to-use. User-friendly Control for Variable and Constant Torque Applications Cost-effective solutions for new
More informationMotor Protection Fundamentals. Motor Protection - Agenda
Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection
More informationHALLMARK INDUSTRIES INC.
4 Deep Well Submersible Pump Part # Power Flow M 3 /H 0 1 2 2.6 3.2 3.6 4.2 4.5 Weight HP Volt Amp Flow (GPM) 0 4.6 9.1 11.5 14 16 18.4 20 (lbs) MA0343X-4 1/2 115 6.5 Head (ft) 154 142 120 103 80 56 27
More informationInverter User Manual
Inverter User Manual -------------for standard model DC TO AC Power Inverter CONTENTS Safety First 1. Introduction 2. Installation Guidelines 3. Using the inverter 4. Troubleshooting 5. Specifications
More informationAurora Single Phase Emergency Lighting Inverters
Aurora Single Phase Emergency Lighting Inverters True Sine Wave On-Line Single Phase Emergency Lighting Inverters AURORA Series Emergency Lighting AC Inverters are among the most reliable systems available
More informationQuestions Section: Do you have questions that aren't covered? Please contact us!
Questions Section: 1. What are the screw terminals on the back of my XP600 for? 2. How do I hook up a remote turn-on switch for my XP250 / XP600 / XP1100/ MX series inverter? 3. Can I sell power back to
More informationWhat you need to know about Electric Locos
What you need to know about Electric Locos When we first started building 5 gauge battery powered engines they used converted car dynamos as the motive power, this worked well but used a lot of power for
More informationMatrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING
Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
More informationFiltered PWM Speed Control for Permanent Magnet DC Motors
Instructions for Installation and Operation Filtered PWM Speed Control for Permanent Magnet DC Motors Model 0794 Speed and Direction Control up to 5/8 HP NEMA-1/IP-20 Specifications Product Type:... WPM-2148E1
More informationSECTION 3 HPS CENTURION R REACTORS AND RC DV/DT FILTERS
HPS CENTURION R REACTORS AND RC DV/DT FILTERS Single and Three Phase Why Choose a Line Reactor?... 98 Construction Features... 100 HPS Centurion R Reactors Specifications... 101 Part Number Guide... 102
More informationA Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications
A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications The Reliance Electric LiquiFlo AC drive combines high-performance variable speed drive technology with a patented liquid-cooling
More informationPOWERSOURCEPURE INSTRUCTIONS. Pure Sine Wave Inverter. RINV1200P REINV1200P RINV2200P REINV2200P
POWERSOURCEPURE Pure Sine Wave Inverter RINV1200P REINV1200P RINV2200P REINV2200P INSTRUCTIONS Retain these instructions for future reference www.ringautomotive.co.uk OVERVIEW The Ring Pure Sine Wave (PSW)
More informationCommon recommendations
Motor Overview Why are motors important? What is a motor? Optimizing the motor component power factor efficiency and losses motor/load relationships standards Common recommendations Review of CD-ROM Industrial
More informationFor motors controlled
STEVE PETERSON Technical Training Engineer Yaskawa America Inc., Waukegan, IL Electronically reprinted from November 20, 2014 Choosing the right CONTROL METHOD for VFDs For motors controlled by a variable
More informationPenn Valley Pump Company Design Information for Double Disc Pumps
Penn Valley Pump Company Design Information for Double Disc Pumps INTRODUCTION The Penn Valley Double Disc Pump utilizes a unique principle of operation whereby the discs perform the duties of pumping
More informationU1000 INDUSTRIAL MATRIX DRIVE
AC DRIVES U1000 INDUSTRIAL MATRIX DRIVE APPLICATIONS 200V CLASS: 10-100 HP (ND); 7.5-75 HP (HD) 400V CLASS: 7.5-800 HP (ND); 5-750 HP (HD) U1000 INDUSTRIAL MATRIX DRIVE THE GREEN CHOICE Ultra-low Harmonics
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationPumpSmart. Control Solutions
Control Solutions Advanced pump Control, Protection, and Optimization logic designed to prevent failures, improve pump reliability and maximize the Flow Economy of your process systems. Whereas other vendors
More informationPURE SINE WAVE DC-AC INVERTERS
AC POWER SOURCE PURE SINE WAVE DC-AC INVERTERS MODEL: PST-60S-24A OWNER S MANUAL Please read this manual before operating your inverter. INDEX Contents General Safety & Installation... 3 Warning... 4 Description
More informationPowerful & Intelligent Submersible Pumps
TM Powerful & Intelligent Submersible Pumps NW2256 (mfr. AC 22365) 1/3 HP Motor Capacity is 1250 gallons per hour Adjustable Automatic or Manual Operating Switch Assorted adapter fittings including garden
More informationTransforming Energy.. For Advanced Technology
Transforming Energy.. Manufacturers of CE approved Transformers & Reactors Five Decades of Manufacturing Experience Manufacturers of Quality Reliable Transformers. Auto C 201,4 th Cross Peenya Induatrial
More informationSolar Inverter Manual
Solar Inverter Manual Introduction SMPS series solar inverter power charging efficiency increased by 30%~60% than traditional controller charging. This inverter has automatic identification, three-stage
More informationUnderstanding The HA2500's Horiz Driver Test
Understanding The HA2500's Horiz Driver Test Horizontal output stage symptoms and component failures are often caused by problems in the horizontal driver stage. The horizontal driver stage is seldom suspected,
More informationSynchronous Motor Drives
UNIT V SYNCHRONOUS MOTOR DRIVES 5.1 Introduction Synchronous motor is an AC motor which rotates at synchronous speed at all loads. Construction of the stator of synchronous motor is similar to the stator
More informationAmerican Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module
EFFECTIVE DATE JULY 28 204 OF 8 Dual Hybrid Ship Propulsion System 750V BUS Generator Generator Propulsion Propulsion Bus Capacitorss 50,000µF Total Traction Inverter Dual Inverterr e Power Inverter L
More informationOWNER S MANUAL. Please read installation and operation instruction before using this Power inverter.
OWNER S MANUAL DP AUDIO Model No. DN350 12 Volt DC to 115 Volt AC 150 WATT 300WATT HIGH SURGE POWER INVERTER Please read installation and operation instruction before using this Power inverter. Contents
More information