HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

Size: px
Start display at page:

Download "HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA"

Transcription

1 Document: VF00W103 Rev. 7 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA MAY 2008

2 MAY 2008

3 INTRODUCTION Page 2 READ THIS MANUAL carefully for important information about safety, handling, and maintenance, for general-purpose NEMA Class E magnetic controllers. This manual and all accompanying drawings should be considered a permanent part of the equipment. They should be readily available for review and reference at all times. DIMENSIONS shown in the manual are in metric and/or their English equivalent. These instructions are not intended to cover all details, combinations, or variations of the equipment, storage, or installation. PROBLEMS OR QUESTIONS should be addressed to: Field Service Department Toshiba International Corporation West Little York Road Houston, Texas USA Telephone: (713) (800) (800) (Canada) FAX: (713) Use only Toshiba-authorized replacement parts. This equipment is designed and built in accordance with applicable safety standards in effect on the date of manufacture. Unauthorized modifications can result in severe injury, death and property damage. Do not make any modifications to this equipment without the written approval of Toshiba. MAY 2008

4 TABLE OF CONTENTS Page 3 Page SAFETY DATA 4 Safety Data Information 4 GENERAL 6 Recommended Procedure 6 Page MAINTENANCE 17 General Inspection 17 Vacuum Interrupter 18 Bearing 19 Closing Coils 19 Latch Mechanism 19 Auxiliary Switch 19 RECEIVING & HANDLING 7 Receiving 7 Handling 7 Storage 7 GENERAL DESCRIPTION 8 Application 8 Load Data 8 Location Condition 8 Ratings 9 Construction 10 PRE-OPERATION SET-UP 11 VACUUM INTERRUPTER 20 Replacement Procedure 20 Removing 20 Mounting 21 Adjustment of Contacts 21 Operation Check 21 TROUBLESHOOTING 22 OUTLINE DIAGRAM 23 WARRANTY AND LIMITATION OF LIABILITY 24 Application Precautions 11 Installation 11 Controls 12 Power Connections-Standard 13 Power Connections-Latched 13 Drive Unit Configuration 14 Standard Circuit Diagram 14 Latched Circuit Diagrams 15 Trial Operation 16

5 Page 4 SAFETY DATA QUALIFIED OPERATORS ONLY Only qualified persons are to install, operate, or service this equipment according to all applicable codes and established safety practices. A qualified person must: 1) Carefully read the entire instruction manual. 2) Be skilled in the installation, construction or operation of the equipment and aware of the hazards involved. 3) Be trained and authorized to safely energize, de-energize, clear, ground, lockout and tag circuits in accordance with established safety practice. 4) Be trained and authorized to perform the service, maintenance or repair of this equipment. 5) Be trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shield, flash clothing, etc. in accordance with established practices. 6) Be trained in rendering first aid. SAFETY CODES Toshiba medium voltage controllers are general purpose, Class E, magnetic controllers designed and built in accordance with the latest applicable provisions of NEMA ICS 3 Part 2, UL 347 and the National Electrical Code. Installations must comply with all applicable state and local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions provided in this manual.

6 SAFETY DATA Page 5 IMPORTANT MESSAGES Read this manual and follow its instructions. Signal words such as DANGER, WARNING, CAUTION, and NOTE will be followed by important safety information that must be carefully reviewed. Indicates a situation which will result in death, serious injury, and severe property damage if you do not follow instructions. Means that you might be seriously injured or killed if you do not follow instructions. Severe property damage might also occur. Means that you might be injured if you do not follow instructions. Equipment damage might also occur. NOTE Gives you helpful information. READ SAFETY SIGNS To avoid injury, you must read and follow the instructions in this manual and on the safety signs located on the equipment. Keep the safety signs visible and in good shape. Never remove, damage, or cover any safety sign.

7 Page 6 GENERAL Please read this manual and all accompanying documentation in its entirety prior to installation and operation. These instructions are not intended to cover all details, combinations or variations of the equipment, storage or installation. Toshiba medium voltage open vacuum type magnetic motor controllers are UL recognized and built in accordance with the latest applicable provisions of NEMA ICS 3 Part 2, UL 347 and the National Electrical Code. There is a hazard of shock or burn whenever working on or near electrical equipment. ALL POWER supplying the equipment should be turned off before starting work, and disconnecting means should be locked out and/or tagged out in accordance with NFPA 70 E, Part II and ANSI Z Where it is not feasible to de-energize the unit, the following precautions should be taken; A. Persons working near exposed parts that are or may be energized should be instructed to and should use practices (including appropriate apparel, equipment and tools) in accordance with NFPA 70 E, Part II. B. Persons working on exposed parts that are or may be energized should, in addition to A, be qualified persons who have been trained to work on energized equipment. RECOMMENDED PROCEDURE The successful and safe operation of medium voltage control equipment is dependent upon handling, installation, operation and maintenance by qualified personnel. Failure to follow fundamental installation and maintenance recommendations could lead to personal injury and damage to the equipment and other property. When referred to in this manual and on product labels, a qualified person is one who is familiar with installation, construction or operation of the equipment and the hazards involved. In addition, this person should have the following qualifications; 1) Is trained and authorized to energize, de-energize, clear, ground and tag circuits in accordance with established safety practices. 2) Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc. in accordance with established practices. 3) Is trained in rendering first aid.

8 KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE

9 RECEIVING & HANDLING Page 7 RECEIVING Upon receipt of the equipment, make an immediate inspection for any damages which may have occurred during shipment. When the contactor is received it should be unpacked sufficiently to inspect for concealed damage and to determine that the shipment is complete and correct. If any damage is found it should be noted prior to accepting the shipment if possible. Check for things such as, damage to the container, water seepage or moisture on the contactor. Check the nameplate to confirm that the ratings meet the intended application. If any parts are damaged or missing, file a claim immediately with the carrier and notify the Toshiba sales office. Try to give as much information as possible when filing a claim. HANDLING & STORAGE Vacuum contactors should be handled with care to avoid damage. Contactors should be kept in an upright position and moved with suitable equipment. If the contactor is to be stored over any length of time, the packing material should be restored for protection during that period. Where conditions permit, the packing should be left intact until the contactor is ready for installation. Store the contactor in a dry and dust free area. It should not be left outdoors or in adverse conditions. If unprotected, corrosion, rust and insulation deterioration will occur.

10 Page 8 GENERAL DESCRIPTION SERVICE CONDITIONS Application Condition The type HCV vacuum contactor is manufactured in accordance with IEC (1974), NEMA ICS 3 Part 2 (1993). The vacuum contactor should be used in the following conditions. Table 1 Normal Service Conditions - Altitude: Less than 2,000 m (6600 ft) Above 2,000 m consult factory -Ambient temperature: -5 C min. to +40 C max. Its average over a period of 24 hr does not exceed +35 C. -Relative humidity: 45% min. to 85% max. -Vibration: 20 Hz - 1G or less -Shock -Weight 30G 43 lbs. Latched type 44 lbs. If the contactor is to be used in conditions other than those specified above, please consult Toshiba International Corporation. Table 2 General Application and Load Data System Voltage 0.8PF Ind/Syn Motor 1.0PF Syn Motor 3 Phase Transformer 3 Phase Capacitor kV kV kV kV 1750HP 2250HP 3000HP 4500HP 2000HP 1500kVA 1500kVAR 2500HP 2000kVA 2000kVAR 3500HP 3000kVA 2000kVAR 5000HP 4000kVA 2000kVAR The above table is based on general load data and standard application. Lower limitations may apply on specific applications (i.e. applications above 6600 feet elevations). Location condition The location where the contactor is to be installed should be free from dust, corrosive gas and moisture. When it is to be used in a chemical plant or in outdoor applications, take necessary precautions against corrosion, water seepage and condensation.

11 GENERAL DESCRIPTION Page 9 CONTACTOR RATINGS Rated Voltage Rated Current HCV-5HA 7200 Volts 400 Amps Interrupting Capacity Permissible Switching Frequency Mechanical Life Electrical Life Closing Time Opening Time * Arcing Time Pick-Up Voltage AC or DC Drop-Out Voltage AC or DC Rated Control Voltage AC Rated Control Voltage DC Coil Circuit Inrush Coil Circuit Holding Auxiliary Contact Arrangement 7000A RMS Max. 4500A RMS Max. 1200/Hour 2,500,000 Operations 250,000 Operations ms ms 10 ms or less 85% Rated (Hot) - 70% Rated (Cold) 50% Rated (Hot) - 40% Rated (cold) 115/120 or 230/240 V 50/60 Hz 120/125 or 240/250 V 670 VA AC (700 W DC) 85 VA AC (85 W DC) 3 N.O. - 3 N.C. Auxiliary Contact Rating 10 A, 600 V (NEMA Class A600) * - DC switching, opening terminals 3 & 4. HCV-5HAL (Latched Type Only) Permissible Switching Frequency Mechanical Life Tripping Voltage Tripping Current 300/Hour 250,000 Operations 40-60% Rating DC 4.8 A DC Max

12 Page 10 STRUCTURE Fig. 1 Construction of HCV-5HA & HCV-5HAL

13 PRE-OPERATION SET-UP Page 11 APPLICATION PRECAUTIONS 1) Verify that the voltage and current applied is within the specified ratings. (See application table, page 5). 2) When the contactor is used with an induction heater facility, the switching life of the vacuum interrupter is approximately 250,000 operations. The vacuum interrupter should be replaced after 250,000 operations. 3) When the contactor is applied to a capacitor load, be sure to use a space heater to keep the temperature above the dew point and prevent condensation. Be sure to use a heater adequately sized for the compartment in which the contactor is installed. The contactor should always be applied with a protective power fuse. INSTALLATION During installation, protect the contactor from dust and falling debris. The following precautions should be taken, 1) The mounting surface should be horizontal (level: ±1 mm). If the mounting surface is not level, adjust with spacers or shims. 2) The contactor base has four (4) mounting holes. Use M8 or 5/16 bolts to securely mount the contactor. 3) In wiring the main circuit, wires should be given sufficient length to be flexible for service. The ground wires should be #10 AWG or larger. 4) Avoid touching the surface of the vacuum interrupter with soiled hands. You can damage the silicon finish on the interrupter. If the interrupter becomes dirty, simply clean it with a non-tracking cleaner such as rubbing alcohol.

14 Page 12 PRE-OPERATION SET-UP CONTROLS The drive unit for the closing coil assembly is installed in a cavity in the molded frame housing. The closing circuit can be operated by applying either AC or DC to this drive unit. The optional latch trip circuit uses DC as standard. When a latched contactor is operated using AC power, it is recommended that a capacitor trip device be used. The standard control voltage (factory preset) is 120V AC. To operate at other ratings see the selection chart below. Fig. 2 Control Voltage Selection for Closing Coils The following is a list of the available trip coil voltages for a latched type contactor: 24 V DC 32 V DC 48 V DC 125 V DC 250 V DC

15 PRE-OPERATION SET-UP Page 13 CONNECTION OF CONTROL POWER SUPPLY Figures 3 and 4 show the internal connections of the magnetically held (normally energized) type and the latched type respectively. Connect control power and open/close control signals according to these connection diagrams. Note: Connections are the same for 100V and 200V class. Only the drive unit settings should be changed to match the application control voltage. Jumper or 2 Relay Contacts Power Supply Closing Coils Control Terminal Block (Drive Unit is Attached) Fig. 3 Connections for Magnetically Held Type. Note: Terminals 3 and 4 are rated for 4.8A DC max. A wire jumper (14 AWG or larger) can be used instead of a relay on 3 and 4. Note: Connections are the same for 100V and 200V class. Only the drive unit settings should be changed to match the application control voltage. Contactor Auxiliary Switch Contact Trip Power Supply Jumper or 2 Relay Contacts Power Supply Control Terminal Block (Drive Unit is Attached) Closing Coils Trip Coil Fig. 4 Connections for Mechanically Latched Type. Note: Terminals 3 and 4 are rated for 4.8A DC max. A wire jumper (14 AWG or larger) can be used instead of a relay on 3 and 4.

16 CPage ONTRO 14 LS CONTROLS Page 14 Contacts or Jumper Wire STANDARD OPERATION CIRCUIT Fig. 5 Internal Configuration of Drive Unit. The following figures illustrate the vacuum contactor and its auxiliary circuits (control and monitoring). Fig. 6 represents the standard operation circuit diagram of the normally energized type and Fig. 7 (a & b) the latched type. Wiring should be implemented according to these circuit diagrams. Remote Operation Switch OFF OFF V AC/DC V AC/DC CR ON ON LOCAL REMOTE CR VACUUM CONTACTOR START INTERLOCK DU STOP INTERLOCK CONTROL RELAY DOOR SWITCH 2E (OVERLOAD) Fig. 6 Standard Operation Circuit Diagram of Normally Energized Type.

17 LATCHED CIRCUIT Page 15 Fig. 7a Standard Operation Circuit Diagram of Latched Type Using Shunt Trip REMOTE OPERATION SWITCH ON ON OFF OFF 2E LOCAL START INTERLOCK REMOTE CR VCTT DC DU CONTROL RELAY Fig. 7b Standard Operation Circuit Diagram of Latched Type Using Capacitor Trip Device REMOTE OPERATION SWITCH ON ON LOCAL OFF OFF 2E REMOTE START INTERLOCK CR VCTT AC CTD DU P N CONTROL RELAY

18 Page 16 TRIAL OPERATION TRIAL OPERATION MAKE SURE MAIN POWER IS OFF. After mounting and wiring of the vacuum contactor, make the following inspections. 1) Check for any loose connections. 2) Check for any wiring errors. Perform this test with only the control circuit energized. Confirm that the operation is correct. For the latched type contactor, check that the latch correctly engages and trips when the close/trip signals are applied. Also, manually trip the contactor using the trip lever to verify proper operation. For latch kit adjustment and maintenance please refer to manual no. 6F9G Installation Instructions of Latch Kits for HCV-5HA.

19 MAINTENANCE Page 17 GENERAL INSPECTION MAINTENANCE AND INSPECTION The following maintenance and inspections are recommended to maintain the performance level and extend the operational life of the vacuum contactor. BEFORE CONDUCTING MAINTENANCE AND INSPECTIONS, MAKE SURE THAT ALL POWER IS TURNED OFF. ITEMS FOR INSPECTION Table 3 PARTS TO BE INSPECTED MAIN CIRCUIT MECHANISM SECTION ELECTRO- MAGNET LATCH MECHANISM OTHERS NOTE INSPECTION ITEM CRACKS DISCOLORATION CONTAMINATION RUST WEAR LOOSE PARTS INCOMPETE OPERATION VIBRATION SOUND VACUUM INTERRUPTER O O O O MOVABLE CONDUCTOR O O UPPER & LOWER O O TERMINALS MOLDED FRAME O O O INSULATION FLANGE O O BEARING O O CLOSING COIL O ARMATURE & CORE O O AUXILIARY SWITCH O O O TRIP COIL O ROLLER O O O O BOLTS & NUTS INSULATION WIRE O O INSPECTION INTERVALS THE LIFE EXPECTANCY OF THE ELECTRICAL PARTS (VACUUM INTERRUPTER, AUXILIARY SWITCH) IS 250,000 OPERATIONS VISUAL CHECK ONCE A YEAR OR EVERY 20,000 OPERATIONS

20 Page 18 MAINTENANCE Make Sure Power Is Turned Off. MAINTENANCE Location Maintenance Procedure Vacuum Interrupter Check the upper and lower flanges and interrupter shaft to see if they are contaminated or corroded. If contaminated...use a clean cloth and rubbing alcohol. UPPER FLANGE If corroded...replace with a new interrupter. NOTE: Avoid touching the ceramic surface. Skin oils may harm the silicon varnish. Check the main contact wear in the vacuum interrupter. If the wear gauge can be inserted, then there is sufficient contact material available for continued use. If the gauge cannot be inserted, replace the interrupter. NOTE: This check is made with the contactor closed. LOWER FLANGE WEAR GAUGE 2.7mm MINIMUM INSULATING FLANGE SHAFT Check vacuum in the vacuum interrupter. Fig. 8 Vacuum Interrupter Apply 10kVAC between the upper and lower terminals for one minute. If there is no voltage breakdown, the vacuum interrupter is acceptable for continued use. If there is voltage breakdown, replace with a new vacuum interrupter before continued use. NOTE: If there is a vacuum failure, it can be confirmed by pushing down on the insulating flange below the vacuum interrupter. If the interrupter shaft can easily be moved, then the interrupter has lost vacuum.

21 MAINTENANCE Page 19 Location Vacuum Interrupter Bearing Closing Coil Latch Mechanism Auxiliary Switch Gap/Wipe Standard Values (contactor in new condition) Contactor Contact Gap Wipe (new) Allowable Wear Normally Energized Type mm >2.3mm 1.8mm Latched Type mm >2.1mm 1.6mm * Check for loose mounting bolts. Tighten if loose. Torque M6 bolts to 48 in-lb. * Check for discoloration. Yellow (Gold) available for continued use. Dark Brown or Black replace with new coil. If the closing coil is overheating, contact Toshiba. * Check that the holding latch reliably engages. Note: To manually close the latch, hold the central area of the rotating shaft with a wrench and operate it. * Check the condition of the roller. It should be smooth. * Lubricate the rotating parts with a molybdenum disulfide or gear lubricant. * Verify that there is remaining auxiliary shaft travel. Approximately mm. * Check for burnt or worn contacts. Replace if burnt or worn. * Check if auxiliary switch is mounted at an incline or if mounting plate is loose. If inclined or loose, correct it. (Reference) Values for gap and wipe Contact Type Normally Open Contact Normally Closed Contact Maintenance Procedure Contact Gap Wipe 4mm +/ mm +/ mm +/ mm +/- 0.3 Delayed N.C. Contact (For latched type contactor only. Contacts 16-26) 2.5mm +/ mm +/- 0.5

22 Page 20 MAINTENANCE PROCEDURE FOR REPLACING VACUUM INTERRUPTERS When a vacuum interrupter has reached a specified life (250,000 operations) or when it is damaged, it is recommended that it be replaced in the following sequence: B (M8 BOLT) Removing CONDUCTIVE COLLAR VACUUM INTERRUPTER CONDUCTIVE NUT A (M8 NUT) REMOVE UPPER TERMINAL FLEXIBLE CONDUCTOR INSULATING FLANGE 1) Hold the insulating flange with one hand and loosen nut "A" (below the flexible conductor) with a wrench. 2) Turn the insulating flange clockwise by hand until it comes off the movable shaft of the vacuum interrupter. 3) With the vacuum interrupter held in one hand, loosen and remove bolt B (above the interrupter) with a wrench. 4) While pushing down on the insulating flange, pull the vacuum interrupter forward to remove it. At this time, the conductive collar can also be removed. Keep the collar for later use. Fig. 9 Mounting of Vacuum Interrupter.

23 MAINTENANCE Page 21 MOUNTING 1) Remove the conductive nut from the vacuum interrupter being replaced and attach it to the new vacuum interrupter as shown in Fig ) Put the conductive collar on the upper part of the vacuum interrupter (stationary terminal) and assemble the vacuum interrupter. 3) Hold the vacuum interrupter and fasten bolt "B" (torque to 120kg-cm or 102in-lb). CONDUCTIVE NUT Fig mm 4) Push down the insulating flange and align the insulating flange stud with the movable shaft of the vacuum interrupter. Then, while turning the flange counterclockwise, insert it. (Install the insulating flange with only 3 to 4 turns, then stop). ADJUSTING THE MAIN CONTACT GAP OF THE VACUUM INTERRUPTER 1) With the control circuit energized, close the vacuum contactor. Check that the armature is attracted to the coil cores. WEAR GAUGE (SUPPLIED) 41.5mm VACUUM INTERRUPTER CONDUCTIVE NUT "A" (M8 NUT) INSULATING FLANGE 2) As shown in Fig. 11, turn the insulating flange until the distance is 41.5mm or use the wear gauge supplied. 3) With the adjustment made, hold the insulating flange still with the hand and secure nut "A". Note: -Arrange so that the movable conductor is straight and flat. -Check that the conductive nut does not rotate. 4) Turn off the control circuit power supply. 5) Operate manually to confirm that the vacuum interrupters close simultaneously. Fig. 11 Adjusting the Main Contact Gap. 6) Operate the contactor electrically and check that the main contact gap is 4mm +0.2mm. If necessary, loosen nut A and turn the insulating flange (clockwise or counterclockwise as necessary) until the correct contact gap is achieved. Then tighten nut A. OPERATION CHECK In a no-load condition, electrically operate the contactor through 20 operations to confirm normal operation.

24 Page 22 MAINTENANCE TROUBLESHOOTING SYMPTOM Turn off main power before any inspections are conducted. Table 4 SOURCE OF TROUBLE/PROBLEM SOLUTION Contactor does not close. Contactor does not open (Latch type). Trip coil overheated. Closing coil overheated. Latch does not engage. Conduct investigation with main power "OFF". If inspection and/or countermeasure is difficult, inform Toshiba immediately Control power supply is low. Lower the voltage drop to increase the voltage to 90% or more of the rating Incorrect control voltage. Apply proper rating. 0 0 Defective control circuit. Check connection diagram Bad connection and/or loose connection. Make proper connection. 0 0 Bad control switch contact. Clean or replace device Incorrect terminal connection. 0 0 Blown power supply fuse(s). 0 0 Disconnected coil. Connect correctly. Remove cause of fault and replace fuse(s). Survey cause and reconnect coil. 0 0 Faulty drive unit. Replace drive unit Defective latch mechanism. 0 0 Mechanism jammed. 0 Incorrect auxiliary adjustment. 0 Bad auxiliary contact. Excite closing coil and check latch hook. Lubricate corresponding portion. Adjust delayed N.C. contact gap to 2.5mm +/- 0.3mm when connected. Clean or replace auxiliary contact block.

25 OUTLINE Page 23 MOUNTING HOLE LAYOUT Fig. 12 Types HCV-5HA, HCV-5HAL

26 Page 24 WARRANTY AND LIMITATION OF LIABILITY Toshiba International Corporation ("Company") warrants that all equipment and parts described herein will be free from defects in materials and workmanship. THIS WARRANTY WILL EXPIRE EIGHTEEN (18) MONTHS AFTER THE DATE ON WHICH SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS WARRANTY) ARE SHIPPED BY THE COMPANY TO THE INITIAL PURCHASER OR TWELVE (12) MONTHS AFTER SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS WARRANTY) ARE FIRST PLACED IN OPERATION, WHICHEVER PERIOD FIRST EXPIRES. The Company will, at its option, repair or replace such equipment or part which is defective under the terms of the foregoing warranty, free of charge; provided the purchaser (1) promptly notifies the Company in writing of such defect, and (2) furnishes the Company satisfactory proof thereof, and (3) establishes that the equipment or part has been properly installed, maintained and operated within the limits of rated capacity and normal usage and in accordance with this manual, and (4) if requested by the Company, returns the defective equipment or part to the Company and pays all expenses incurred in connection with such return. The repaired or replacement equipment or part will be delivered, free of charge, to the purchaser F.O.B. the Company's warehouse or, at the Company's option, F.O.B. a Company authorized service shop, not loaded on truck or other carrier. The purchaser will pay the costs applicable to the equipment or part following such delivery, including, without limitation, all handling, transportation, assembly, insurance, testing and inspection charges. THE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL BE THE SOLE AND EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USERS OF THE EQUIPMENT AND PARTS FOR BREACH OF THE FOREGOING WARRANTY. THE COMPANY WILL HAVE NO OBLIGATIONS TO DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COSTS INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. THE COMPANY, TOSHIBA CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTORS HEREBY DISCLAIM ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, ALL EQUIPMENT AND PARTS FURNISHED PURSUANT TO THE FOREGOING WARRANTY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY. The total liability of the Company, Toshiba Corporation and their suppliers and subcontractors for any loss, damage or claim, whether in contact, tort (including negligence and liability without fault), or otherwise, arising out of, connected with or resulting from the equipment and parts described in this manual or the performance or breach of any contract for the sale or supply of such equipment and parts, or from the design, manufacture, sale, delivery, resale, installation, technical direction or supervision of installation, inspection, testing, repair, replacement, operation, maintenance or use of any such equipment or part or any service relating thereto furnished by the Company shall not in any event exceed the price allocable to the equipment, part or service which gives claim, loss or damage. In no event, whether as a breach of contract or warranty, alleged negligence, liability without fault, or otherwise, shall the Company, Toshiba Corporation or their suppliers or subcontractors be liable for special or consequential damages, including, without limitation, loss or profits or revenue, loss of equipment described herein or any associated equipment, cost of capital, cost of substitute equipment or parts, facilities or services, down-time costs, labor costs or claims of customers of the purchaser for such damages.

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE Document: VF00W103 Rev. 8 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA AUGUST 2013

More information

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA Document: VF010H08A INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA Issued: 12/05 Manufactured in the

More information

INSTRUCTION MANUAL. HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A

INSTRUCTION MANUAL. HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A Document: VF010H07A INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A Issued: 12/05 Manufactured in the USA TOSHIBA

More information

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE Document: GF07Z303 Rev 1 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) APPLICABLE MODEL NUMBERS: (Motor Operation

More information

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE Document: GF07Z301 Rev. 1 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes APPLICABLE MODEL NUMBERS: (Manual Operation Types)

More information

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Document: GF07Z304 Rev. 2 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Issued: 10/2006

More information

Manual Transfer Switch

Manual Transfer Switch Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

SPC-PANEL Simplex, Single Phase Pump Control Panel

SPC-PANEL Simplex, Single Phase Pump Control Panel Pump Installation and Service Manual SPC-PANEL Simplex, Single Phase Pump Control Panel Pump Controls for 2 HP Grinder Pumps NOTE! To the installer: Please make sure you provide this manual to the owner

More information

Pump Installation and Service Manual HRS Hydromatic Retractable System

Pump Installation and Service Manual HRS Hydromatic Retractable System Pump Installation and Service Manual HRS Hydromatic Retractable System NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY GC-1 Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY GENERAL INFORMATION The GC-1 heating cable controller has been designed and manufactured for

More information

HPV 100 Hydraulic Elevator Soft-Starter Technical Manual

HPV 100 Hydraulic Elevator Soft-Starter Technical Manual HPV 100 Hydraulic Elevator Soft-Starter Technical Manual WARRANTY Standard products manufactured by the Company are warranted to be free from defects in workmanship and material for a period of one year

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

CRD610 Automatic Fitting Inserter

CRD610 Automatic Fitting Inserter CRD610 Automatic Fitting Inserter OPERATIONS MANUAL VERSION 1.2 LAST EDITED 12.12.2018 cleanroomdevices.com 1 Table of Contents Title Page. 1 Table of Contents...2 1.0 General Product & Safety Information....3

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

60 Series End-Mount Brake Instructions Standard Housing

60 Series End-Mount Brake Instructions Standard Housing Bulletin No. BK4655 (04/18) 60 Series End-Mount Brake Instructions Standard Housing Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information

II DISTRIBUTION & SUBSTATION TYPE C

II DISTRIBUTION & SUBSTATION TYPE C CapCheckIII DISTRIBUTION & SUBSTATION TYPE Ca p a c i t o r C h e c ke r Operating & Instruction Manual 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980 f a x 8 4 7. 4 7 3. 4 9 8 1 w e

More information

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY Issue 5 24/48 VOLT DC SWITCHING POWER SUPPLY INTRODUCTION These instructions provide the specifications, installation and maintenance information for the VP-4124 and VP-4124-E, 24/48 Volt Power Supplies.

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Effective November 2016 Supersedes February 2012 (S )

Effective November 2016 Supersedes February 2012 (S ) Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling

More information

T300MVi JK OEM POWER CELLS MEDIUM VOLTAGE VACUUM CONTACTOR. Reliability in motion. Reliability in motion

T300MVi JK OEM POWER CELLS MEDIUM VOLTAGE VACUUM CONTACTOR. Reliability in motion. Reliability in motion MEDIUM VOLTAGE VACUUM CONTACTOR T300MVi JK OEM POWER CELLS Reliability in motion Reliability in motion 400 AMPERE AT 2300-6600 VOLTS (7200 VOLT MAX) DRAWOUT AND FIXED APPLICATIONS JK OEM PART NUMBER DESCRIPTION

More information

Effective June 2016 New Issue

Effective June 2016 New Issue Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation

More information

Installation and Operation

Installation and Operation S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction

More information

Installation Power Management Unit Battery Cables and Battery Harness

Installation Power Management Unit Battery Cables and Battery Harness Installation Power Management Unit Battery Cables and Battery Harness Important Safety Messages SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation

More information

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

CLEAN ROOM DEVICES, LLC WHERE TUBING AND FITTINGS COME TOGETHER CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER" CRD600 Automatic Fitting Inserter OPERATIONS MANUAL VERSION 2.1 LAST EDITED 7.25.14 DOCUMENT NUMBER 001 cleanroomdevices.com 1 Table of

More information

CRD600 Automatic Fitting Inserter

CRD600 Automatic Fitting Inserter CRD600 Automatic Fitting Inserter OPERATIONS MANUAL VERSION 2.3 LAST EDITED 12.07.2018 cleanroomdevices.com 1 Table of Contents Title Page.. 1 Table of Contents. 2 1.0 General Product & Safety Information...3

More information

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers User manual W-VACi W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers 65A7355H01 Rev.04 January 2013 www.eaton.com 2 Table of contents 1 Safety... 5 1.1 Safety precautions...5 1.2 Safety practices...5

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

McCANNA Actuation Systems B

McCANNA Actuation Systems B 17710-B Ramcon Series 8/25 C/CR, 50/100 B/BR, 250/500 B/BR Electric Actuators Installation, Operation and Maintenance Instructions Contents Storage...........................................................................................................

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Effective March 2015 Supersedes S August 2012

Effective March 2015 Supersedes S August 2012 Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER

More information

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3 SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious

More information

HIGH VOLTAGE DIGITAL AMMETER

HIGH VOLTAGE DIGITAL AMMETER HIGH VOLTAGE DIGITAL AMMETER Operating & Instruction Manual HVA-2000 Making the Invisible Visible TM 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980 f a x 8 4 7. 4 7 3. 4 9 8 1 w e b s

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

Operating Instructions for PAC800 Battery Charger

Operating Instructions for PAC800 Battery Charger Operating Instructions for PAC800 Battery Charger General Safety The charger may only be used for the specified battery types. This battery charger is supplied with pre-set charging curves that are adapted

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

CLEAN ROOM DEVICES, LLC WHERE TUBING AND FITTINGS COME TOGETHER CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER" CRD600AF Automatic Fitting Inserter With Auto Feed OPERATIONS MANUAL (Shown with optional alcohol dispenser) 1 VERSION 1.1 LAST EDITED

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

Dispenser & Warmer RIC-1909 RIC-1909EXP

Dispenser & Warmer RIC-1909 RIC-1909EXP Dispenser & Warmer RIC-1909 RIC-1909EXP Safety Precautions CAUTION This equipment is designed and sold for commercial use only. This equipment is not to be used by the consumer in home use. Do not allow

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 B R A N D Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 For Sales, Support and Service phone: 407-331-4793 fax: 407-331-4708 website: www.xenotronix.com email: information@xenotronix.com

More information

StormPro BA Series Sump Pump

StormPro BA Series Sump Pump Page 1 of 8 Marks & Meanings DANGER: Keep the pump equipment out of the reach of children! Warns that the failure to follow the directions given could cause serious risk to individuals or objects. WARNING:

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Installation Sheet January, 2016 Supersedes June 2013

Installation Sheet January, 2016 Supersedes June 2013 s Installation Sheet January, 016 Supersedes June 01 E87010-A0105-T00-A6-CLM0 Lighting and Heating Contactor 60, 100, 00 Amp,, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

Level One Electric Vehicle Charging Station FREE STANDING Product Guide

Level One Electric Vehicle Charging Station FREE STANDING Product Guide Level One Electric Vehicle Charging Station FREE STANDING Product Guide Model # SC2-120 Shorepower Technologies 2351 NW York St. Portland, OR 98664 503-892-7345 info@shorepower.com www.shorepower.com 2

More information

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus: 1.0 Introduction: This probe is designed to provide an additional help to automotive technicians in trouble shooting of electrical circuits problems in the car. Apart from using the normal multi tester,

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 B R A N D Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 For Sales, Support and Service phone: 407-331-4793 fax: 407-331-4708 website: www.xenotronix.com email: information@xenotronix.com

More information

Factory Authorized Mechanism Enhancement (FAME)

Factory Authorized Mechanism Enhancement (FAME) Instruction Leaflet IL182403EN Supersedes April 2017 Effective July 2018 Factory Authorized Mechanism Enhancement (FAME) FAME Upgrade Shown Factory Authorized Mechanism Enhancement (FAME) DISCLAIMER OF

More information

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL L007 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Side-Mounted Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the L007 Side- Mounted

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

AD-7 THERMAL INDICATING AMMETER

AD-7 THERMAL INDICATING AMMETER AD-7 THERMAL INDICATING AMMETER a nd ACCESSORIES Operating & Instruction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E W A U K E G A N, I L L I N O I S 6 0 0 8 5 U. S. A. P H O N E 8 4 7.

More information

EV-2051-M Electric Motor. Operation and Maintenance Manual

EV-2051-M Electric Motor. Operation and Maintenance Manual EV-2051-M Electric Motor Operation and Maintenance Manual Table of Contents Safety... 3 General...3 Safety Notices...6 Cautions, Warnings and Dangers...7 Cautions...8 Warnings...11 Dangers...13 Important

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES

More information

ARC 1850 LIST OF FIGURES

ARC 1850 LIST OF FIGURES PAGE 1.0 INTRODUCTION... 1 2.0 WARRANTY... 1 3.0 UNPACKING YOUR UNIT... 1 4.0 SUGGESTED SAFETY PRECAUTIONS...... 1 4.1 PERSONAL SAFETY PRECAUTIONS. 1 4.2 POWER SUPPLY SAFETY PRECAUTIONS.. 2 5.0 GENERAL

More information

XPC-EBP64 External Battery Pack User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

XPC-EBP64 External Battery Pack User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. XPC-EBP64 User & Installation Manual www.xpcc.com 2015. All rights reserved. (Rev 9/28/15) Table of Contents Introduction...5 Product Description...5 Extended Battery Pack Configurations...6 Safety Information...7

More information

StormPro BCV400 Sewage Ejector Pump

StormPro BCV400 Sewage Ejector Pump Page 1 of 8 Marks & Meanings DANGER: Keep the pump equipment out of the reach of children! Warns that the failure to follow the directions given could cause serious risk to individuals or objects. WARNING:

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause

4 ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause 4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL BEFORE INSTALLING PUMP, BE SURE TO READ THIS OWNER S MANUAL CAREFULLY. CAUTION Fill pump with water before starting or pump will be damaged. The motor on

More information

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES Instruction D12043 June 2016 DeZURIK Instructions These instructions provide installation, operation and maintenance information for APCO CRF-100A Rubber

More information

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction

More information

READ AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion

READ AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion READ AND SAVE THESE INSTRUCTIONS ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner Trion www.trioniaq.com Installation, Operation, & Maintenance Manual 1. Warranty 2. Safety & Warnings ComfortBreeze

More information

MOTORIZED FOLDING CAMPER WINCH

MOTORIZED FOLDING CAMPER WINCH OWNER'S MANUAL MOTORIZED FOLDING CAMPER WINCH With 1200lb Lift Capacity The 12 Volt Motorized Folding Camper Winch is used to raise and lower folding campers with the touch of the switch, eliminating hand

More information

CSA products for treated water. Water Combination air valve. Mod. FOX 3F RFP and Lynx 3F RFP

CSA products for treated water. Water Combination air valve. Mod. FOX 3F RFP and Lynx 3F RFP CSA products for treated water Water Combination air valve Mod. FOX 3F RFP and Lynx 3F RFP Instructions These instructions provide installation, operation and maintenance information for CSA water combination

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

LESTRONIC II BATTERY CHARGER TAYLOR-DUNN MODEL TYPE 24LC25-8ET

LESTRONIC II BATTERY CHARGER TAYLOR-DUNN MODEL TYPE 24LC25-8ET LESTRONIC II BATTERY CHARGER TAYLOR-DUNN 79-301-10 MODEL 13110-32 TYPE 24LC25-8ET AC Supply: DC Output: Battery Capacity: Specifications 120 volts, 60 Hertz, single-phase 24 volts, 32 amps Use only on

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

DeZURIK 2 20" BOS BUTTERFLY VALVES

DeZURIK 2 20 BOS BUTTERFLY VALVES 2 20" BOS BUTTERFLY VALVES Instruction D10459 October 2013 2-20 BOS Butterfly Valves Instructions These instructions provide information about BOS Butterfly Valves. They are for use by personnel who are

More information

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF

More information

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES APCO ASR-400/450 SEWAGE AIR RELEASE VALVES Instruction D12005 December 2012 Instructions These instructions provide installation, operation and maintenance information for the APCO ASR- 400/450 Sewage

More information

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY Issue 6 VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY INTRODUCTION These instructions provide the specifications, installation and maintenance information for the VP-6124 and VP-6124-E, 24Volt Power

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Effective November 2016 Supersedes September 1998 (S )

Effective November 2016 Supersedes September 1998 (S ) Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES

More information

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL S003 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

USER S MANUAL FOR F & Q. Submersible Sewage Pumps

USER S MANUAL FOR F & Q. Submersible Sewage Pumps USER S MANUAL FOR F & Q Submersible Sewage Pumps 100WQ Series The F&Q pumps are carefully inspected and tested to ensure operating performance and safety. However, failure to follow the instructions and

More information

High-voltage primary bushings installation instructions

High-voltage primary bushings installation instructions OEM Equipment Effective November 2013 Supersedes April 2013 S800-35-2 High-voltage primary bushings installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls P-269-89-0408 Installation Installation & Operating Instructions Contents Introduction........................... 2 Specifications.........................

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES

More information

Outdoor Nema Enclosure For Dotworkz CoolDome Power Supply Product Code: NM-CDPS. User Manual

Outdoor Nema Enclosure For Dotworkz CoolDome Power Supply Product Code: NM-CDPS. User Manual Outdoor Nema Enclosure For Dotworkz CoolDome Power Supply Product Code: NM-CDPS User Manual Revision June 2008 Outdoor Nema Enclosure For Dotworkz CoolDome Power Supply LIMITED WARRANTY FOR DOTWORKZ SYSTEMS

More information

User s Manual D-Series Blowers and Exhausters

User s Manual D-Series Blowers and Exhausters User s Manual D-Series Blowers and Exhausters D05-1 ½ HP TEFC 115/230 VOLTS, 1 PH D05-3 ½ HP TEFC 208/230/460 VOLTS, 3 PH D10-1 1 HP TEFC 115/230 VOLTS, 1 PH D10-3 1 HP TEFC 208/230/460 VOLTS, 3 PH D15-1

More information