Technical Specification No.- S-168/DD KV Switchgear Panel. Vacuum Type

Size: px
Start display at page:

Download "Technical Specification No.- S-168/DD KV Switchgear Panel. Vacuum Type"

Transcription

1 DAKSHIN HARYANA BIJLI VITRAN NIGAM Office of the Chief General Manager/P&D, Vidyut Sadan, Vidyut Nagar, Hisar Tel: , (GM/P&D) Fax: Technical Specification No.- S-168/DD KV Switchgear Panel Vacuum Type Issue of Month: Feb Chief General Manager/P&D DHBVN, Hisar

2 2

3 TECHNICAL SPECIFICATION FOR 11 KV SWITCHGEAR PANELS VACUUM TYPE WITH 11KV CAPACITOR CONTROL PANELS 1. SCOPE: This specification covers the design, manufacture, assembly, testing at manufacturer s works before dispatch, supply and delivery FOR destination of 350MVA, 11KV Vacuum type switchgear panels with 11KV capacitors control panel. 2. STANDARDS: The Switchgear panels shall comply in all respects the requirement laid down in the latest editions of IS-3427, IS-3231, IS: 2705, IS: 3156 & IS CLIMATIC CONDITIONS: conditions: The equipment is required to operate satisfactorily under the following site 3.1 Max. Ambient Temperature 60 ºC 3.2 Min. Ambient Temperature -5 ºC 3.3 Max. Relative humidity 100% 3.4 Min. Relative humidity 26% 3.5 Average no. of rainy days per annum Nearly 120 days 3.6 Average annual rainfall 900 mm 3.7 Average number of dust storm days per annum Isoceraunic level Max. Wind pressure 195Kg / sq. meter 3.10 Altitude above mean sea level Less than 1000 meter 4. TYPE AND RATINGS: The 11KV Switchgear panels shall comprise of 11KV Vacuum Type circuit breakers, control relay panel, instrument panel and instrument transformers (complete in all respect) etc., suitable for indoor use. The equipment shall be totally enclosed in metal clad cubical, dust and vermin proof with necessary isolation arrangement. Each panel shall be easily extensible on either side and should be complete with necessary internal copper connections, small wiring, L.T. fuses and supporting framework with bolts to secure it to the floor. Each panel shall be provided with space heater, door switch with lamps and 15 - Ampere power receptacle. The breakers shall have the following ratings: 4.1 Type Vacuum type 4.2 No. of poles Nominal System Voltage 11 KV 4.4 Highest System Voltage 12 KV 4.5 Rated frequency Hz 4.6 Rated continuous current rating at Ambient 800 Amp for incoming; 400 Amp for temperature, as specified in IS: outgoing feeders 4.7 Symmetrical breaking capacity 350 MVA 4.8 Impulse withstand test voltage 75 KV (peak) 4.9 One minute power frequency withstand test 28 KV (rms) voltage 4.10 Short time current rating Not less than 18.4 KA for 1 Second System neutral Solidly earthed 3

4 5. GENERAL DESIGN OF SWITCHGEAR PANELS: 5.1 OPERATING MECHANISM: The vacuum type circuit breaker shall be trip free and the breaker control shall be draw out type. The VCBs shall be suitable for operation from 24 DC auxiliary supply. The operating mechanism shall be motor operated spring charged type. There shall be provision (s) for manual charging of closing spring and emergency hand trip. The motor used for the purpose will be suitable for 240 V AC. All auxiliaries shall be supplied from AC and arrangement shall be made for automatic switch over to DC in case of AC supply failure. The operating mechanism shall works satisfactorily between % of rated supply voltage. 5.2 INSTRUMENT PANELS: Each unit shall have its own instrument panel provided at the top & complete with small wiring connections from relays, instrument transformers, metering instruments, indicating instruments, selector switches & circuit breaker control switch. All wiring shall be carried out by using stranded single annealed copper conductor, insulated with poly vinyl chloride insulation suitable for 650 V service and in accordance with IS: CT/PT circuits shall use wire of not less than 2.5 mm² cross - sectional area whereas control/alarm/supervision circuit shall use wire of not than 1.5 mm² cross - sectional area. All wires will be continuous from one terminal to the other and also will have no T - Junction enroute. The connections shall be securely made with the help of suitable connecting lugs duly crimped on the copper conductor. The meters and relays shall be mounted in a convenient position so as these are readily accessible for inspection or repair. The terminal board provided in the instrument panel of VCBs will be made of molded dielectric having brass studs, washers, holding nuts & locking nuts. All holding nuts shall be secured by locking nuts. The connection studs shall project 6 mm from the lock nut surface. No OTHTER TYPE OF TERMINAL BORAD IS ACCEPTABLE. The panels shall have a degree of protection of IP - 4X. The leads from the metering CTs shall be directly terminated at TTB and there from at the KWH meter with a provision to seal TTB and KWH meter. The said CT leads will be effectively concealed to prevent their tempering enroute as well as at TTB. Similarly PT leads from secondary box of the PT to TTB & there from to energy meter, including inter panel PT leads, will also be effectively concealed to prevent their tempering. The mode and extent of concealing the metering leads of CTs & PTs, to prevent their tempering (by unscrupulous operating personnel), will be discussed and mutually agreed upon with the successful bibber (s). TTB, used on the instrument panel, should be suitable for front connections. Earthing of current free metallic parts or metallic bodies of the relays switches mounted on the instrument panel and metal enclosed switchgear shall be done by a suitable sized copper conductor. Earth bus made of 25 X 3 mm bare copper flat will be extended through entire length of 11KV switch-board with suitable provision to connect it to the sub-station earth at the extremities. The earthing arrangement will meet with the requirements laid down in IS: 3427, read with its latest amendments. 5.3 INSTRUMENT TRANSFORMER: The secondary voltage & current rating of the instrument transformers shall match with the metering and protective equipment. The CTs shall have ratio & accuracy class as mentioned in the schedule of requirement. The CTs shall be wound/ring type in accordance with their ratings. The terminal boards, associated with REF CTs & Over Current / Earth Fault Protection CTS will be of disconnecting type, having short circuiting facility & thus facilitate secondary testing of concerned protective relay without disturbing the associated small wiring. Interchangeability of housing of CTS, from one panel to another, must be ensured. A resin cast potential transformer of ratio ( )/(110 3) volts, having 100 VA output per phase with 4

5 accuracy class 0.5 as per ISS: 3156 (Part-II) 1965, shall be provided on the incoming side of each panel set and shall be star / star connected. It shall be provided with HT and LT fuses. The neutral point, of star connected secondary windings of instrument transformers, shall be earthed to the main earth bus referred to in concluding paragraph of clause Multiple earthing of any instrument transformers shall be avoided. 5.4 BUS BAR: All the panels shall be provided with insulated copper bus bar of 800 Amps current rating for all switch boards. These shall be connected in a separate moisture and vermin proof sheet metal chamber. The bus - bar connection & insulator supports shall be mechanically strong & rigidly supported so as to withstand the stresses, generated by vibrations, variation in temperature and severe short circuits. The bus - bar should be in horizental formations to enable DHBVN to connect with existing Circuit Breaker Panel Board without any difficulty in matching. The Adopter Panel, if required to match the loose panel with the existing panels, shall be prepared / fabricated as per site conditions by the Nigam at its own cost. The bus - bar shall be supported on insulator at short intervals, keeping adequate clearance between the bus bar and earth. The bus - bar chamber shall be provided with inspection cover with gaskets & bus bar shutters. Provision shall be made for future extension of bus bar & switch board. 5.5 LIMIT OF TERPERTURE RISE: The temperature rise, of current carrying parts, shall not exceed the permissible limits above the ambient temperature as per relevant standards (latest edition). 5.6 BUSHING INSULATORS: These shall comply with latest version of IS: 2099 in all respects. 5.7 DISCONNECTORS OF CIRCUIT BREAKER & THEIR INTERLOCKS: All disconnector s (isolators) of 11KV VCBs & interlocks between different pieces of apparatus, provided for reasons of safety & for convenience of operation of switchgear, shall meet with the requirement of IS: read with its latest amendment. 5.8 CABLE BOXES: Each 11 KV incoming VCBs shall be provided with cable boxes, complete with jointing kits & sealing material for receiving 3 Core, 11 KV XLPE type outer PVC sheathed cable of size 630 mm² (Panel with CT ratio /5 5 5 A). The outgoing 11KV VCBs, including 11KV capacitor controlling VCB, shall be provided with cable boxes suitable to receive 3 Core, 11 KV XLPE type outer PVC sheathed cables of size up to 300 mm² (Panel with CT ratio /5-5A). The 11 KV station transformer VCB shall be provided with cable boxes ( Epoxy Resin Type ) suitable to receive 3 Core, 11KV XLPE type outer PVC sheathed cables of size up to 50 mm² (Panel with CT ratio 60-30/5-5A). Each cable box shall have vertical entry from below. These cable boxes shall be complete in all respects, including cable glands of requisite size. It is clarified that one jointing kit/cable box is required to connect one 11KV XLPE cable with one 11KV VCBs. No separate (extra) jointing kit is required. 5

6 5.9 RELAYS: All the relays, except the relays for DC failure alarm, supervision alarm, annunciation scheme, shall be draw out type and mounted on the front of each circuit breaker control panel in a flush pattern case. All relays shall be provided with testing facilities. In case the same can not be provided within the relay, a separate test block and test plugs shall be provided. The relay adjustment devices shall be easily accessible when the relays have been mounted on the panels. The relays shall conform to the latest edition of IS: The relays shall not operate at a current equal to or less than the setting. The minimum operating current shall not exceed 110% of the setting. The coils & CT circuit of the relay should be suitable to withstand the minimum operating current continuously, in case the minimum operating current is around 110%. The relays covers and cases shall be dust tight, moisture and vermin proof. Operation Indicators shall be provided on all relays and on their immediate auxiliaries for indication, regarding type of fault and phase involved. It shall be possible to reset the operation indicator, without opening the relays covers. All relays shall be tested at manufacturer s works and test certificates got approved, before dispatch of material. The bidder shall submit the descriptive and pictorial literature, in quadruplicate, in respect of each relay proposed, along with the tender. All relays in the specification shall be suitable for 24 V DC auxiliary voltages ALARM EQUIPMENTS: The incoming feeder panel shall be provided with one alarm bell and alarm indicating auxiliary relays. It shall indicate tripping of circuit breaker, under fault conditions, with the help of auto trip lamp and alarm. It shall be complete with the indicating lamp and push button switches for Accepts and Resets alarm SUPERVISION SCHEME: 11KV switches panels, covered by this specification, shall be provided with the following lamp indication: Circuit breaker Open Circuit breaker Close Auto trip Spring Charged Green Red White Blue For monitoring the trip circuit healthy conditions, both in open and close position of the circuit breaker, 1 No. trip circuit supervision relay is proposed. In case of trip circuit being faulty, the operation of this relay shall be accompanied by audio - visual annunciation. It shall be possible to silence the buzzer by pressing the accept push button but the lamp shall continue to glow till the fault has been attended. Circuit breaker Close & Open lamps shall be wired so as to be on 240 V AC under normal condition METERING SCHEME: The 11 KV Incoming VCB will be provided with a digital Voltmeter along with a selector switch. The selector switch shall facilitate the measurement of Phase - Phase and Phase - Neutral voltage, one by one. The static voltmeter shall be rated for 110 V (Phase Phase Voltages). The instrument shall be static type of industrial grade A classification with accuracy class 1.0 & shall confirm to IS: 1248 (1968). 6

7 Each of the 11 KV VCB Panel will be provided with a suitably sealed digital ammeter, rated for 5Amp (additional dials; if any, required to cover all the taps of the CTs, shall be included at the time of bidding) & a selector switch, facilitating measurement of phase currents. The instrument shall be of static type, industrial grade A classification, having accuracy class 1.0 & shall conform to IS: 1248 (1968) Each of the 11 KV VCB, except the 11 KV capacitor VCB, will be equipped with a three phase four wire static trivector meter (Confirming to Technical Specification no. S 45 / SE / P & D / XEN / DD II; Static CT / PT Operated Trivector Meter for 11 KV Feeders) & suitable for three phase four wire unbalanced load conditions with accuracy class 0.5 and having RS 232, RS 485 Port for Data Logging / Data -Downloading facility. The trivector meter shall be rated for 5 Amp CT secondary and 110/ 3 V (phase to neutral), available from 11 KV PT mounted on the incoming VCB. Each of the 11KV VCB will be provided with a static power factor meter. The static PF meter, having range of 0.5 lag one lead, shall be of static type; suitable for use on three phase three wire unbalanced system. It shall be rated for 5A CT secondary & 110 Volts (Phase Phase Voltage), having accuracy class 1.0 with digital display. NOTE: Routine test certificates of all the indicating & integrating instruments will be submitted along with the routine test certificates of 11 KV switchgear PADLOCK: Padlock or some other arrangement of approved design shall be provided for locking the equipment in OFF position. All locks shall have two keys, in addition to the master key which shall be provided for each panel set. Approved racks or cabinets, for accommodation of padlocks and keys while in use, shall be provided along with each panel set and it shall be suitably labeled and numbered for identification AUXILIARY SWITCHES: In addition to the auxiliary contacts required for normal operation, each circuit breaker shall be provided with 2 NO & 2NC spare auxiliary contacts duly wired up to terminal block MONITORING FROM REMOTE: Suitable arrangement should be provided to make it possible to monitor the following conditions of the 11 KV VCB at the remote end, through a communication system to be provided by the Nigam. Sr. No. CONDITIONS 1 D C is healthy 2 Breaker is off 3 Breaker is on 4 Breaker is mechanically free to close 5 Spring, for closing mechanism, is charged 6 Trip Circuit is healthy 7 Breaker is not anti pumping 8 Tripping of Breaker with the operation of Instantaneous High Set Element, installed on Phase & Earth Fault Units, indicating the Phase or Earth Fault involved 9 Tripping of Breaker with the operation of Inverse Definite Minimum Time Unit, 7

8 installed for Phase & Earth Fault, indicating the Phase or Earth Fault involved 10 Breaker has not tripped with the operation of Master Trip Relay (Applicable for 11 KV VCB only) 11 Bus Bar is charged (Not applicable for 11 KV Incoming VCB) 5.16 CLOSING FROM REMOTE: Suitable arrangement should be provided to make it possible for the Nigam to close 11 KV VCB from the remote end, through a communication system to be provided by the Nigam, in case the following conditions are satisfied. Sr. No. CONDITIONS 1 D C is healthy 2 Breaker is Off 3 Breaker is mechanically free to close 4 Spring, for closing mechanism, is charged 5 Trip Circuit is healthy 6 Breaker is not anti pumping 7 Breaker has not tripped with the operation of Instantaneous High Set Element 8 Breaker has not tripped with the operation of Master Trip Relay (Applicable for 11 KV VCB only) 9 Bus Bar is charged (Not applicable for 11 KV Incoming VCB 5.17 TRIPPING FROM REMOTE: Suitable arrangement should be provided to make it possible for the Nigam to trip 11 KV VCB from the remote end, through a communication system to be provided by the Nigam, in case the breaker is on & certain preset conditions, to be decided later on. 6. PROTECTION SHEMES: 6.1 FOR INCOMING PANELS: Each incoming panel shall be provided with a single pole restricted earth fault relay, suitable for 5 Amps C.T. Secondary, with a setting range of 10% to 40% of 5 Amp (strictly in steps of 5%). The relay shall be housed in draw out flush pattern case. The back up protection shall be in the form of combined over current and earth fault relay, consisting of two over current & one earth fault unit which shall be triple pole having inverse definite minimum time (I.D.M.T.) characteristics with a 3/10 time current curve i.e. the relay operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer elements of the relay shall be arranged for over current protection and shall have a setting range of % of 5 Amps, adjustable in suitable equal steps by means of plug boards. The central element shall be used for earth fault protection with a setting range of 20-80% of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three elements shall be fitted with shunt reinforcing unit with hand reset operation indicator. Two nos. over current high set instantaneous elements, having setting range of % of 5A and one no. earth fault high set instantaneous element, having setting range of % of 5A and adjustable in suitable steps, shall be wired in series with the IDMT type over current and earth fault relay respectively. The high set instantaneous element shall have low transient over reach with a high pickup / drop out ratio. The high set instantaneous element shall 8

9 be so wired so as to take this element (instantaneous) out of circuit, if so desired by the Nigam, at any time during the operation of equipment. 6.2 FOR OUTGONG FEEDER PANELS: The back up protection shall be in the form of combined over current and earth fault relay, consisting of two over current & one earth fault unit which shall be triple pole having inverse definite minimum time (I.D.M.T.) characteristics with a 3/10 time current curve i.e. the relay operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer elements of the relay shall be arranged for over current protection and shall have a setting range of % of 5 Amps, adjustable in suitable equal steps by means of plug boards. The central element shall be used for earth fault protection with a setting range of 20-80% of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three elements shall be fitted with shunt reinforcing unit with hand reset operation indicator. Two nos. over current high set instantaneous elements, having setting range of % of 5A and one no. earth fault high set instantaneous element, having setting range of % of 5A and adjustable in suitable steps, shall be wired in series with the IDMT type over current and earth fault relay respectively. The high set instantaneous element shall have low transient over reach with a high pickup / drop out ratio. The high set instantaneous element shall be so wired so as to take this element (instantaneous) out of circuit, if so desired by the Nigam, at any time during the operation of equipment. 6.3 FOR STATION TRANSFORMER FEEDER PANEL: The back up protection shall be in the form of combined over current and earth fault relay, consisting of two over current & one earth fault unit which shall be triple pole having inverse definite minimum time (I.D.M.T.) characteristics with a 3/10 time current curve i.e. the relay operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer elements of the relay shall be arranged for over current protection and shall have a setting range of 20-80% of 5 Amps, adjustable in suitable equal steps by means of plug boards. The central element shall be used for earth fault protection with a setting range of 10-40% of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three elements shall be fitted with shunt reinforcing unit with hand reset operation indicator. Two nos. over current high set instantaneous elements, having setting range of % of 5A and one no. earth fault high set instantaneous element, having setting range of % of 5A and adjustable in suitable steps, shall be wired in series with the IDMT type over current and earth fault relay respectively. The high set instantaneous element shall have low transient over reach with a high pickup / drop out ratio. The high set instantaneous element shall be so wired so as to take this element (instantaneous) out of circuit, if so desired by the Nigam, at any time during the operation of equipment. 6.4 FOR 11KV CAPACITOR CONTROL PANEL: The 11KV capacitor control panel shall be provided with the following protection The back up protection shall be in the form of combined over current and earth fault relay, consisting of two over current & one earth fault unit which shall be triple pole having inverse definite minimum time (I.D.M.T.) characteristics with a 3/10 time current curve i.e. the relay operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer elements of the relay shall be arranged for over current protection and shall have a setting range of % of 5 Amps, adjustable in suitable equal steps by means of plug boards. The central element shall be used for earth fault protection with a setting range of 20-80% of 5 Amps, 9

10 adjustable in suitable equal steps by means of a plug board. Each of the three elements shall be fitted with shunt reinforcing unit with hand reset operation indicator For the protection of the bank against unbalancing, an inverse time Neutral Voltage displacement relay having setting 5.4, 7.5, 12.5 and 20 volts and suitable for 190 V AC operation shall be provided. The relay will be fed from the open delta connected secondary of residual voltage transformer (Discharge coil) and shall have suitable setting range to afford adequate protection to the capacitor bank against unbalancing For over voltage protection of the capacitor bank, over voltage relay; having setting range of 110% to 170% in steps of 10% & rated for 110 Volts A.C. supply, obtainable from the secondary of 11KV Bus P.T s mounted on 11KV Incoming Panel shall be provided For under voltage protection of the capacitor bank, under voltage relay; having setting range of 50% to 90% in steps of 10% & rated for 110 Volts A.C. supply, obtainable from the secondary of 11KV Bus P.T s mounted on 11KV Incoming Panel shall be provided minute adjustable timer contact shall be wired in series with the closing circuit so as to ensure that the capacitor bank is fully discharged, once it has been switched OFF. 7. FREQUENCY OF OPERATION: Mostly the VCB panels are expected to be used for feeding heavily concentrated load. As such they are expected to be subjected to frequent tripping due to overload & earth fault. Any specific design features, adopted or proposed to be provided, by the bidder in the switchgear on this account should be indicated clearly in the tender. 8. TESTS: All type tests & routine tests shall be carried out in accordance with IS: /1991 (Latest version thereof). The type test certificate shall be supplied as per IS: / 1991, in quadruplicate along with the tender to judge the adequacy of the equipment offered. In case the offered equipment varies in its details vis-à-vis the certified copy of the drawing annexed with the Type Test Report, the bidder (s) will be required to submit the fresh Type Test Reports. The date of Type Test Report shall be within five years from the date of opening of the bids against this specification. The following Type Tests in respect of VCBs are required to be submitted along with the tender. 8.1 Lightning & switching Impulse voltage test 8.2 Power frequency voltage Test (Dry & wet) 8.3 Temperature rise test 8.4 Measurement of Resistance of main circuit 8.5 Short Time withstand 8.6 Peak withstand current 8.7 Mechanical operation test at Ambient air temperature. 8.8 Basic short circuit test duties (Test duties 1,2,3,4 a, 4 b, 5) and Critical current Test 8.9 Capacitor current switching test The tenders, without Type Test Certificates of the offered equipment, are liable to be rejected. The Type Test Certificates for CTs & PTs, as stipulated in the latest version of IS: 10

11 3156 & IS: 2705, can be supplied by the successful Bidder after placement of the purchase order, being bought out items. The PT s and CT s shall be subjected to routine tests, as specified in the latest version of relevant ISS in the presence of purchaser - authorized representative, if so desired by the purchaser. The routine test certificates of the bought out component such as relays, switches, indicating instruments & KWH metering will also be presented to DHBVN s authorized inspecting officer who will forward the same to the purchaser along with his inspection report for the main equipment. All test reports should be got approval from purchaser before dispatch of equipment. 9. DRAWINGS & LITERATURE: In addition to any other drawing, which the bidder may like to furnish to explain the merits of his proposal, following drawings shall be submitted along with the tender in quadruplicate:- 9.1 Principal Dimensional Details of 11KV Switchgear. 9.2 ` General arrangement of 7 - panel 11KV switchboard including its foundation details. 9.3 Schematic drawings of control, metering & protection circuits in respect of 11KV incoming VCB, 11KV outgoing VCB including station transformer VCB & 11KV capacitor VCB along with detailed write-up. 9.4 Drawing showing height of 11KV bus bars & arrangements of bus bars. 9.5 Vacuum interrupter drawing. 9.6 Name plate drawing. Four copies of the descriptive literature in respect of 11KV switchgear, relays KWH meters, voltmeters, ammeters and selector switches etc, proposed to be used shall also be supplied. The successful bidder shall submit the above drawings in quadruplicate on A - 3 size paper to the CGM/MM, DHBVN, Hisar for approval. The purchaser shall communicate his comments / approval on / to the drawing to the successful bidder within a period of four weeks. The supplier shall, if necessary, modify the drawings and resubmit four copies of the modified drawings for the purchaser s approval within two weeks from the date of receipt of purchaser s comments. The modified drawings will be approved within 15 days of their receipt. After receipt of approved drawings, a set of reproducible of approved drawings & five sets of all the approved drawings & operating manuals containing, erection, operation & maintenance instructions per 11 KV switchboard shall be supplied to CGM / MM, DHBVN, Hisar for use by various agencies of the purchaser. However, one set of drawing and operating manual will be dispatched along with each 11 KV switchboard. The 11 KV switchgear will not be fabricated without getting the drawing approved from the purchaser. 10. SPECIAL TOOLS: The bidder shall separately quote for a set of special tools, if so required, for erection and maintenance of the switchgear panels. 11. DEVIATION FROM SPECIFICATION: Should the tender wish to deviate from the provisions of the specifications, either on account of manufacturing practice or any other reasons, he shall draw attention to the proposed point of deviation in the tender and submit such full information, drawing and specification so that merits of his proposal may be fully understood. The specification shall be held binding unless the deviations have been fully accepted as requested. 11

12 12. TRAINING FACILITIES: The successful tenderer(s) may be called to arrange for training of Nigam s Engineer/Technician s at their works so as to make them familiar with the manufacture and assembly process of the equipment, covered in the specification. Two to three engineers/technicians may be sent for a period of 2 weeks and full training facilities shall be made available to them. 13. GUARANTEED AND OTHER TECHNICAL PARTICULARS: These particulars shall be furnished strictly as per Annexure A in duplicate. Any deviation from this specification shall clearly be brought out separately. 14. PLACE OF MANUFACTURE: The bidder shall state the place of manufacture, testing and name of the manufacturer of the various items, included in his tender. 15. STANDARD MARK (S) OFRELAYS/OTHER FITMENTS: Annexure C. The make(s) of relays / other fitments may be restricted to, as depicted in 16. INSPECTION: Inspection of material and supervision of tests, in accordance with the relevant ISS (as mentioned in clause 2 above), approved drawings and schedules shall be carried out by the purchaser or his duly authorized representative. The material shall be inspected and tested, before dispatch, by authorized representative of the Nigam. The manufacture shall provide to the inspecting officer all reasonable facilities, without charge, to satisfy him that the material is being furnished in accordance with the specifications. The purchaser or his authorized representative shall have access, at all reasonable time, to the manufacture s works to inspect and witness the tests of the equipment manufactured. The purchaser has the right to have the tests carried out, at cost of supplier, by an independent Govt. Agency wherever there is a dispute regarding the quality of material supplied. 17. PACKING AND TRANSPORT: The supplier shall be responsible for suitable packing of all the material and ing on the consignment so as to avoid any damage during the transport and storage and to ensure correct dispatch to the destination. 18. VACUUM BOTTLES: The vacuum bottles should be capable of withstanding minimum 100 full short circuit operations as per test duty 1 to 5 of IEC-56. The vacuum bottles, capable of withstanding less than 100 full short circuit faults, would not be considered and therefore should not be offered. 12

13 A manufacture s type test reports / literature for vacuum bottles, may, therefore be supplied along with tender in duplicate. 19. OPERATING MECHANISM: As clearance between contacts, when VCB is in off condition, is very small, so it is essential that operating mechanism is such that all the three poles open & close simultaneously. 20. INTERLOCKING: conditions. Efficient mechanical interlocking shall be provided to meet the following 20.1 It should be possible to lower / withdraw the breaker only after the circuit breaker has been opened It should be possible to raise or lower the circuit breaker when it is in the fully home position as well as it is in the isolated position It should not be possible to remove the circuit breaker until the moveable plug unit having secondary connections has been with drawn It should not be possible to replace, in position, moveable plug unit & unless the breaker has been racked in Provision of shutters or lock off doors with locks shall be made to prevent access to the bus bar chamber and receptacles when the circuit breaker is withdrawn Provision should be made for locking the circuit breaker closing mechanism in the open position & locks provided. 21. MARKING: ed:- The switchgear panels shall have nameplate carrying the following data indelibly 21.1 Name of the manufacture or a by which he may be readily identified Serial number or type designation making it possible to get all relevant information from the manufacturer and year of manufacture Rated voltage Rated normal Current Rated frequency Rupturing capacity Breaking capacity 21.8 Making capacity Operating D.C. Voltage P.O. No. & Date. GM/P&D CGM/P&D CGM/MM CGM/Commercial 13

14 GUARANTEED AND OTHER TECHNICAL PARTICLATS FOR 11KV SWITCHGEAR PANELS A. CIRCUIT BREAKERS: 1. Maker s name and country of manufacture. 2. Type 3. Nominal system voltage 4. Highest system voltage 5. Frequency 6. Nominal current rating 6.1 At Ref. Ambient temp. as per relevant standard 6.2 At site conditions 7. Symmetrical breaking capacity (KA and MVA) 8. Asymmetrical breaking capacity (KA) 8.1 Symmetrical breaking current 8.2 Short time current rating for 1 sec. 9. Making capacity (peak KA) /50 microsecond impulse wave withstand test voltage 11 One minute power frequency withstand test voltage 12 No. of poles 13 No. of breaks per pole 14 Length of breaks per phase 15 Opening time (ms) 16 Making time (ms) 17 Arc duration (ms) 18 Type and material of main contacts 19 Material and thickness of plating of contacts 20 Type of arcing contacts and /or arc control device 21 Whether the circuit breaker is trip free 22 Whether lock out mechanism for preventing closing provided 23 Closing coil voltage and power required to close the breaker 24 Minimum clearance in vacuum 24.1 Between phases 24.2 Between live parts & earth 25 Minimum clearance in Air 25.1 Between phases 25.2 Between live parts & earth 26 Short Circuit Type Tests: Certificate or report No. (Attach photocopy) 27 Normal/operating voltage of closing mechanism 28 Total weight of complete breaker ( Kg.) 29 Dimensions and mounting details 30 Standard to which conforms 31 Detail of reference drawing attached. B. INSTRUMENT TRANSFORMERS (CURRENT TRANSFORMERS) 1. Rated primary current 2. Rated secondary current 3. Rated transformation ratio 4. V.A burden at rated current and accuracy. 5. Class of accuracy 6. Rated over current factor with time in seconds 7. Type of CTs ( whether wound or bar type) 8. Standard to which conform 14

15 9. One minute power frequency withstand test voltage /50 micro second impulse withstand voltage 11. Make of CT s C RELAYS 1. Type and make 2. Time setting range 3. Other details like No. of auxiliary contacts 4. Standard to which conform 5. No. & Auxiliary contacts D BUS BAR 1. Material 2. Normal current rating in amp. 3. Normal area (mm 2 ) 4. Shape 5. Type of Insulation E. VOLTAGE TRANSFORMER 1. Rated primary voltage 2. Rated secondary voltage 3. Rated burden 4. Class of accuracy 5. Rated voltage factor & time 6. One minute power frequency withstand test voltage /50 micro sec. impulse withstand voltage 8. Make of PT s F PARTICULARS OF INSTRUMENTS & METERS: 1. Type of equipment(whether flush mounted or projected type) 2. Guaranteed % errors at different loads 3. Make & size of Ammeters, Voltmeters, KWH & Power Factor Meters G PARTICULARS OF VACUUM BOTTLES: 1. Name of manufacture 2. Whether imported or indigenous 3. Manufacturer s type, normal amps and rupturing capacity for vacuum bottles used for Incoming panel do for outgoing panels do for capacitor control panel 6. Degree of vacuum inside the vacuum interrupters 7. Short time rating of vacuum bottles 8. Number of full short circuit operations as per test duly 1to 5 of IEC-56, which the vacuum bottles offered can safely withstand 9. Whether the vacuum bottles used on incoming and outgoing panels are same or different. 10. Whether the operating mechanism is imported or indigenous. 15

16 Annexure-B SCHEDULE OF REQUITEMENT 7 panel, 11KV switchboards with each switchboard comprising of the following as per Nigam s specification No No. Incoming panel equipment as below: - a. 1 No. Triple Pole, 350 MVA, 11KV 800 Amps circuit breaker fitted with arc control device, interlocks, auxiliary switches, isolating contacts, emergency hand trip device, mechanical ON and OFF indicator & motor operated spring charging mechanism. b. One set of 3 phase 800 amps bus bars. c. One set of isolating plug and sockets. d. One set of single phase cluster type isolating contacts. e. 1 No. Trifurcating main cable boxes located at the rear of the unit for reception of 3- core XLPE cables of up to 630-mm2 size and complete with wiping glands and clamps. 2. A set of 3 core CT s with ratio 400/200/5-5-5A :- a. One core for REF protection having minimum knee point voltage of 90 X RCT on 400 Amps taps. It shall conform to accuracy class PS of ISS: 2705 (part-iv) and shall have magnetizing current as low as possible but in no case exceeding the value corresponding to class 5P of ISS: 2705 (part IV). b. Second core for over current and earth fault protection with 15VA as out put burdenhaving accuracy of 5P10. c. Third core for metering with 15VA burden output and the class of accuracy as No. 3 phase star/star connected bus bar type resin cast draw out voltage transformer of ratio (11000/ 3)/(110/ 3) volts and 100 VA output per phase with class 1.0 accuracy as per IS: 3516 (part-ii)-1965 complete in all respect with HT and LT fuses, isolating plugs and sockets for HT& LT copper connectors, current limiting resistances and first filling with insulating oil. a. 1 No. 230 V.A.C. panel space heater. b. 2 set of vermin and dust proof fitments. c. 1 earthing set for earthing the breakers individually instrument panel mounted on top and equipped as below:- a. 1 No. suitably sealed C.T s operated static ammeter of 5 Amps. with digital display b. 1 No. 3 way ON/OFF ammeter selector switch. c. 1 No. 0 to 15 KV static voltmeter with digital display. d. 1No. 3 way ON/Off voltmeter selector switch e. 1 No. Static power factor meter for reading both the leading and lagging PF. f. 1 No. 3 elements electronic KWH meter suitable for 3 phase 4 wire unbalanced load conditions with accuracy class 0.5 (as per DHBVN specification) and with RS 485 port with MODBUS protocol for Data Logging/ Data-down-loading facility. 5. One set of triple pole combined over current and earth fault IDMTL relay with two outer elements for over current protection with setting of % of 5 Amps and central element for E/F protection with setting range of 20-80% of 5 Amps mounted in horizontal draw-out type flush pattern case. 16

17 One set of high set instantaneous elements, consisting of two elements for over current, having setting range of % of 5A and one no. earth fault high set instantaneous element, having setting range of % of 5A and adjustable in suitable steps having low transient over reach with a high pickup / drop out ratio. The high set instantaneous element shall be so wired so as to take this element (instantaneous) out of circuit, if so desired by the Nigam, at any time during the operation of equipment. 6. One No. single pole restricted E/F relay with setting of 10-40% of 5 Amps and complete with a tuned 50c/s circuit and stabilizing resistance mounted in draw-out type flush pattern case with a provision of inter-tripping the circuit breaker No. 230 volt A.C. indicating lamps with fittings to indicate breaker open, breaker closed auto trip and spring charged. a. 1 indicating lamp with fitting and push button switch to indicate trip healthy. Trip circuit supervision scheme and D.C. fail scheme as per foregoing specification. b. 1 No Breaker control switch. c. 1set of alarm equipment wired so as to be common to the complete board and comprising of alarm initiating auxiliary relay, alarm bell, indicating lamp and push button for alarm cancellation and lamp resetting. d. 1No. Test terminal block for testing of instrument and relay Outgoing Feeder Panels each Comprising No. Triple pole 400 amps 350 MVA 11KV circuit breaker fitted with arc control devices, interlock arrangement, auxiliary switches, isolating contacts, alarm Contacts, emergency hand trip device, mechanism ON&OFF indicators and spring charged closing mechanism operating at 240 V AC motors set of 3 phase 800 amps bus bars set of Isolating plugs and sockets No. Trifurcating main cable box for reception of 11KV, 3-core, XLPE cable of 300mm 2 and complete with wrapping glands and clamps No. Double core CT s with ratio 300/150/5-5A having one core for metering with 15 VA Burden and Class of Accuracy as 0.5 and the other core with 15VA as burden and Class of Accuracy as 5P 10 for O/C and E/F protection No. 230V.A.C. panel space heater set of vermin and dust proof fitments intrument panel mounted on top and equipped as below: No. suitably sealed CT operated Static Ammeter of 5 Amps, with digital display No. 3-way on/off ammeter selector/switch No. 3 element electronic KWH meter suitable for 3 phase, 4wire unbalanced load and flush mounted with Accuracy class 0.5 (as per DHBVN specification) and with 485 with MODBUS protocol for Data-logging/Data-down-loading facility P.T. leads should come direct from 11KV P.T. Secondary to avoid any tempering in between. 1set of triple pole combined O/C and E/F IDMTL relay with two outer elements for O/C protection having setting of % of 5 Amps and central elements for E/F protection with setting range of 20-80% of 5 Amps mounted in draw-out type flush pattern case. A set of triple pole combined over current & earth fault instantaneous high set relays with two elements for over current protection having a setting range of 500% to 2000% of 5 Amps and the central element for earth fault protection having a setting range of 200%-800% of 5 17

18 Amps. The relay shall have low transient over reach with a high pick up/drop off ratio. Relay will be connected in series with the triple pole combined over current and earth fault relay referred to above and shall be so wired as to take this element (instantaneous) out if so desired by the purchaser at any time during operation of equipments Nos. 230 Volts AC indicating lamps with fittings to indicate Breaker Open, Breaker CLOSED and AUTO TRIP Nos. 230 Volts DC indicating lamp with fittings and push button switch to indicate TRIP CIRCUIT HEALTHY No. Breaker Control switch No. Test Terminal Block for testing instruments & relays No. 3 - way ON/OFF Ammeter selector switch No. Station Transformer Feeder Panel:- 9.1 Similar to item No. 8 but with the following C Ts:- 3 Nos. having double core C Ts of 60/30/5-5 A with one core having 15 VA output as burden and 5P10 accuracy for over current and earth fault protection and the other core for metering having 15VA as burden and class of accuracy as No. 11KV Capacitor control panel: No. Triple pole 400 Amps, 350 MVA, 11KV circuit breaker fitted with arc control device, interlock arrangement, auxiliary switches, isolating contacts, alarm contacts, emergency hand trip device, mechanical ON & OFF indication and under voltage release set of 800 A bus bars set of isolating plugs & sockets set of single-phase cluster type isolating contacts No. Trifurcating main cable box for reception of 3 core XLPE up to 185 mm2 size and complete with wiping glands and clamps Nos. CTs of ratio /5A with 15 VA output burden of 5 P 10 accuracy for protection 1 No. 230 V AC Panel Space heaters set vermin and dust proof fitment Instrument panel mounted on top and equipped as below: No. suitably sealed CT operated static Ammeter of 5 Amp., with digital display No. 3-way ON/OFF Ammeter selector switch Nos. 230 VAC indicating lamps with fitting to indicate breaker open, breaker closed and auto trip No. 24 VDC indicating lamps with fitting to indicate trip healthy No. Breaker control Switch set of triple pole combined over current & earth fault IDMT relay with two outer elements for O/C protection having setting of % of 5 AMPS, and central elements for earth fault protection with setting range of 20 to 80% of 5 amps mounted in drawn out type flush pattern case One Set of inverse time Neutral (Voltage) displacement relay suitable for 190 V AC operations for protection of the bank against unbalancing One set of over voltage relay with setting range 110% to 170% along with auxiliary transformers (for external mounting) having ratio 121/115 to 127 (in Steps of 1 Volt) to be used for compensating the error of over voltage relay One no. under Voltage Relay with setting range of 50% to 90%. 18

19 Minute adjustable timer to ensure that the capacitor bank is fully discharged once it has been switched off before it can be switched ON again The capacitor controlling breaker should be suitable to meet all conditions required for capacitor operation and should be suitable for controlling capacitive current up to 400 Amps at 11 KV which is equivalent to 7.5 MVAR approx 110V supply shall be available from existing (11000/ 3) (110/ 3) Volts PT s. Standard make (S) of Relays/Fitments 1 Relays ALSTOM/EASUN REYROLLE/ABB/SIEMENS Or other equivalent reputed make with IS 2 Breaker Control Switch Kaycee/Alstom/Recom or other equivalent reputed make with IS 3 Ammeter/Voltmeter/Selector/Switch Kaycee/Recom or other equivalent reputed make with IS. 4 Static Ammeter/Voltmeter/Static Power Factor Meter with Digital Display 5 Electronic type KILOWATT Hour Meter with RS Port for Data Logging /Data Down Loading Facility AE/IMP/MECO Or other equivalent reputed with IS SECURE/L&T ABB Or other equivalent reputed make with IS 6 PUSH BUTTONS ALSTOM/KAYCEE/VAISHNO Or other equivalent reputed make with IS 7 Indicating lamps with lenses ALSTOM/KAYCEE/VAISHNO Or other equivalent reputed make with IS 8 Cable termination kits DENSON/M-SEAL Or other equivalent reputed make with IS 9 Cable glands DENSON/M-SEAL /COME Or other equivalent reputed make with IS 10 Panel Wiring ECKO/PHOENIX Or other equivalent reputed make with IS 11 Hooter/Buzzer/Bell ANCHOR/KAYCEE Or other equivalent reputed make with IS 12 CTs /PTs VISHAL/CONCORD/ZENITH/SARAF/GYRO Or other equivalent reputed make with IS 19

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).

Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Sr. No. Clause No Existing Proposed 1 8.0 Dischar ge device 2 15.0

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date: 10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 11 kv Indoor VCB SWITCHGEAR PANEL/BOARD GETCO / E / TS HTPB 5401 / R0

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

HARYANA VIDYUT PRASARAN NIGAM LTD.

HARYANA VIDYUT PRASARAN NIGAM LTD. HARYANA VIDYUT PRASARAN NIGAM LTD. TECHNICAL SPECIFICATION SSD/S-03/R-1/DGM-605 TECHNICAL SPECIFICATION FOR 33 KV CAPACITOR BANKS CHIEF ENGINEER/MM HVPNL, PANCHKULA TELEPHONE & FAX: 0172-2583724 MARCH-2017-0

More information

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum

More information

West Bengal State Electricity Distribution Co. Ltd.

West Bengal State Electricity Distribution Co. Ltd. West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

31-SDMS-01 REV. 03 SPECIFICATIONS FOR

31-SDMS-01 REV. 03 SPECIFICATIONS FOR 31-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PANEL This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1.0 SCOPE

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

32-SDMS-02 SPECIFICATIONS FOR

32-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV METERED RING MAIN UNIT UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES 3

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB Annexure-V (Under Two Part Bid System) Tender No: NFV/ PUR/ BEC 160546 K for VCB Technical specification for NIT SL NO 1 S.No. Description NFL requirement as per NIT Vendors Comment [Agreed / If not agreed,

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077

TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077 spec- 200 Amp. & 400 Amp. LT Dist. Kiosk.doc - 1 - SCHEDULE-III TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

32-SDMS-03 SPECIFICATIONS FOR

32-SDMS-03 SPECIFICATIONS FOR SPECIFICATIONS FOR EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

Metal Clad VCBs ~ Mk1

Metal Clad VCBs ~ Mk1 Metal Clad VCBs ~ Mk1 DUVI 150/40 ROLL ON FLOOR VCBs Range: 6kV, 00A, 1.5kA, 12kV, 150A, 40kA ( 4A000A Bus-Bars ) ` Widest range for MV (up to 6kV) Distribution Networks Megawin make metal clad VCB Panels

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.

More information

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011 Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents

More information

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

: Material Description Quantity UOM

: Material Description Quantity UOM Page : 1 / 2 OIL INDIA LIMITED (A Govt. Of India Enterprise) Tel :033 2230 1657, 1658 4, India Exchange Place, Fax :91 33 2230 2596 Kolkata-700001 E-mail :oilcalmn@cal2.vsnl.net.in ANNEXURE-I Item No./

More information

32-SDMS-01 REV. 02 SPECIFICATIONS FOR

32-SDMS-01 REV. 02 SPECIFICATIONS FOR 32-SDMS-01 REV. 02 SPECIFICATIONS FOR NON-EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

More information

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

43-SDMS-04 REV. 00 SPECIFICATIONS FOR 43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/696/411 FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / 2005-06 SR.NO ITEM PAGE 1. SCOPE 2 2. WEATHER CONDITIONS 2 3. RATED VOLTAGE & FREQUENCY 2 4. GENERAL REQUIREMENT

More information

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (100A) & BOOST CHARGER (60A) FOR WITH REQUIREMENT FOR SCADA

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED)

66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED) GETCO/E/06TS CB/R3 May12 Page

More information

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA WESCO ( APDRP Scheme ) Technical Specification for 33 kv Outdoor Circuit Breaker

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA WESCO ( APDRP Scheme ) Technical Specification for 33 kv Outdoor Circuit Breaker Technical Specification for 33 Outdoor Circuit Breaker TABLE OF CONTENTS PART 1: GENERAL 1. SCOPE... 5 2. STANDARDS... 6 3. SERVICE CONDITIONS... 7 4. SYSTEM CONDITIONS... 8 PART 2: TECHNICAL 5. BASIC

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR GETCO/E/TS-50V BCHR(SCADA)

More information

D.C. DISTRIBUTION BOARD

D.C. DISTRIBUTION BOARD PRAMBL: The TC is maintaining 50-volt battery backup system for the PLCC communication. The 50-volt D.C. supply from the Float cum Boost charger is brought to D.C. Distribution Board from where supply

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

Technical Specification for 11 kv Outdoor Circuit Breaker

Technical Specification for 11 kv Outdoor Circuit Breaker WESCO ( APDRP Scheme) Technical Specification for 11 Outdoor Circuit Breaker - 1 - TABLE OF CONTENTS PART 1: GENERAL 1. SCOPE...4 2. STANDARDS...5 3. SERVICE CONDITIONS...6 4. SYSTEM CONDITIONS...7 5.

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB. TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ Date:

SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB. TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ Date: SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ 13099 Date: 14.12.16 Tech. Specification NIT No. NESCO Utility/ VCB/20/ 11.10.17

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution

More information

026-2 : 1996 CEB STANDARD

026-2 : 1996 CEB STANDARD 026-2 : 1996 CEB STANDARD COMPRESSION CONNECTORS & TERMINATIONS FOR OVERHEAD LINE CONDUCTORS CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable

More information

Technical Specification of GECOL. Packaged Transformers

Technical Specification of GECOL. Packaged Transformers GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...

More information

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : : DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : FOREWORD : Even though 11KV Drop Cut Fuse Cut Outs are widely used for protection / isolation of distribution transformers, their quality

More information

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Specification Medium Voltage Metalclad Switchgear Medium Voltage Number: 5342-02.01.310 Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Rev. 2 SCOPE This specification

More information