1 An Investment in Plant Floor Safety 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

2 Notes 2

3 802C Cable Pull Safety Switches Safety and Application Safety through relying upon operational assurance of a stop switch is a relative term which depends upon the design of the switch as well as the application, installation and maintenance of the switch. While not the usual practice, ultimate operational assurance of a stop switch can be achieved by using redundant stop switches with checking for the purpose of identifying failure of the redundant stop switch. The following factors are significant to the safe operation of the stop switch and must be considered by those involved with the applications, installation and/or use of stop switches: 1. Use of proper system safety analysis for the application and installation of the stop switch, as well as the circuit for the stop switch. A system safety analysis should use applicable standards such as: OSHA 1910 Code of Federal Regulation. EN , Safety of Machinery Electrical Equipment of Machines. ANSI/NFPA 79, Electrical Standard for Industrial Machinery. ANSI B11, series of safety standards. EN 292, Safety of Machinery. Local applicable standards. 2. The application involving the stop switch should provide for a separate disconnect switch(es) with provision for lockout/tagout of the circuit. The stop switch must not be used as a disconnect switch. 3. The installation of a stop switch must be in accordance with the manufacturer s instructions, as well as good practice. 4. Follow the manufacturer s recommendations for short circuit protection in order to minimize the chance for welded contacts. 5. An effective and complete maintenance procedure and schedule must be established and implemented for the stop switch and its application utilizing: The Rockwell Automation/ Allen-Bradley Maintenance of Industrial Control Equipment found in the Rockwell Automation/ Allen-Bradley Industrial Control catalog. NEMA ICS 1.3, Preventative Maintenance of Industrial Control and Systems Equipment. NFPA 70B, Electrical Equipment Maintenance. NFPA 703, Part II (As Adopted by OSHA), Electrical Safety-Related Work Practice. It is the responsibility of the individual(s) who apply, install and/or use the stop switch to assure themselves that all the requirements for the application, installation and maintenance of the stop switch are satisfactorily met. Mounting Position the conduit entering the switch in such a manner that any fluid inside the conduit will not drain into the switch enclosure. Apply sealing compound to the conduit threads to prevent against the entry of fluids through the threads. The conduit threads in the body are metric Pg13.5 or Pg16. Adaptors are supplied to convert the conduit threads to 1/2 14 NPT. Clearance holes have been provided in the enclosure for mounting purposes. Use #10 (M5) screws for mounting. When mounting switches which have polymeric enclosures, it is recommended that washers be used under the mounting screw heads. Wiring The wiring terminals will accept #14 AWG (2.5mm 2 ) and smaller solid or stranded wire. For proper tightening, it is suggested that wires no smaller than #18 AWG (0.75mm 2 ) be used. If the switch is equipped with pressure plate type wiring terminals, strip the insulation approximately inch (9.5mm) before inserting the wire under the pressure plates. Be sure that all strands of the wire are retained by the pressure plate. If the switch is equipped with binding screw type terminals, strip the insulation approximately 1/2inch (12.7mm) before inserting the wire under the binding screw. Be sure that the wire is curved around the screw and that all strands of the wire are retained under the binding screw head.! ATTENTION: The normally open and normally closed contacts must be wired in series to detect cable breakage (see Figure 4A). A grounding screw is located inside the enclosure on those switches that have metal enclosures. Some of the metal enclosures may also have an untapped hole on the exterior of the enclosure near the conduit opening which can also be used for grounding purposes. 1

4 802C Cable Pull Safety Switches After wiring has been completed, check that all wires are placed in such a manner that they will not interfere with the switch portion of the device or with the proper positioning of the cover gasket. Recheck all wiring terminal screws for tightness. Replace and securely tighten or latch the cover and check for proper mechanical action before applying power to the switch. Actuation A cable is attached to the actuator. The switch is actuated by pulling on the cable. Some switches are spring return while others are maintained position switches that will remain in the operated position until a reset button on the switch is pressed.! ATTENTION: The contacts of MAINTAINED POSITION SWITCHES will change state electrically before the mechanical latch or maintained action takes place. The actuator must be moved a distance sufficient to cause the maintained action to occur or the system could restart upon release of the actuation cable (see adjustment). On three wire control systems, the premature release of the actuating cable, before mechanical latch, would allow the system to be restarted from any start station without any reset action at the pull switch. IF THERE IS A CONCERN, PROCEDURES SHALL BE PUT IN PLACE TO ASSURE THAT THE SWITCHED LATCH HAS OPENED, E.G., A GENTLE PULL ON THE CABLE. Normally the installation is such that the actuating cable is positioned in a horizontal plane. See Figure 1A, the Typical Installation Example diagram. Care must be taken to insure that the cable does not become too slack, preventing proper actuation. Too much slack could cause delayed response and/or require excessive motion by the operator to effect switch action. If the cable is too tight, however, false actuation of the switch might occur especially in installations that are subject to wide variations in temperature. If the switch is installed in such a manner that the weight of the actuating cable is supported by the actuator, be sure that the cable weight does not cause false operation of the switch.! ATTENTION: The system should be tested after installation by actuating the cable. The circuit should perform as intended with a minimum of effort on the cable. Be sure that the switch will reset properly when the reset button is depressed. Cable tension and/or cable size should be adjusted as necessary to obtain proper operation. Installation Recommendations Cable pull switches have two main requirements for operation. One requirement is direct opening action contacts. The second requirement is overlapping contacts to monitor the cable tension. It is important to follow the installation instructions as well as the applicable codes and standards for these types of switches. Cable Installation Adjustment: 802C B, 802C C, and 802C E During adjustment of the switch the cable is stressed using a turnbuckle until the normally open contact closes. Once the normally open contact is closed and the normally closed contact remains closed, the switch is adjusted properly. Adjustment: 802C H, 802C J During adjustment of the switch the cable is stressed using a turnbuckle until the normally open contact closes. This is easily accomplished by adjusting the turnbuckle until the mark on the shaft aligns with the edge of the housing. At this point both the normally open and the normally closed contact are closed, and the switch is adjusted properly. Cable Length Where the cable is freely stressed the standard cable length is outlined in the product selection guide in the catalog. When installing a switch with a cable run between the standard length and the maximum length, the following shall be considered: Pulleys are used for all supports, The ambient temperature will not vary by any more than 10C (18F), A spring is installed at the anchoring end of the cable. It is recommended that the cables be installed on a straight run (see Figure 1A). However, if the installation requires the cable to be installed around corners, pulleys shall be used (see Figure 1B). Figure 1B ÇÇÇÇÇÇÇ Ç Ç Ç Ç ÇÇÇÇÇÇ Ç The switching distance (distance to operate contacts) must be taken into account when determining the operating distance X. This distance must be greater than the operating travel of the switch. This will assure there is sufficient room to move Figure 1A Typical Installation Example Note: When installing a switch with a cable run between the standard length and the maximum length, a spring shall be installed at the anchoring end (see Figure 3 for spring installation). 2

5 802C Cable Pull Safety Switches the cable and operate the switch. The maximum distance the cable can be freely stressed (distance between supports) is 5m (16.4ft). Care should be taken to assure that the cable will slide freely through all supports. It is important not to exceed the maximum length of cable as specified in the selection guide and assure that the cable properly operates the switch. Attach the red PVC coated cable to the switch, turnbuckle, eye stiffener, clamps, and eye loop as shown in Figures 1 and 2. Attach the turnbuckle about halfway along the cable span, then attach the other half in a similar manner. Figure 2 Typical Installations of 802C N Switches For installations with large ambient temperature variation or cable runs up to 50m (150ft) (25m (75ft) on each side of switch) the cable pull switch 802C N should be used. The operation of this switch is by means of connecting a cable and two tension springs to an operating lever (see Figure 3 for details). The cable configuration is shown in Figure 3. The cable is connected to the turnbuckle, eye loops and spring as outlined in Figure 2. Figure 3 mm (inches) Temperature Effects on Cable The normal operating temperature range is 30 o C to 80 o C ( 22 o F to 176 o F). The supplied cable will expand and contract at a rate of 6.89 x 10 6 inches per degree per inch (3µm per meter per degree). Operation When the cable is pulled the normally closed contacts will open, interrupting the circuit (see Figure 4C). If the cable breaks or becomes slack the normally open contact will reopen (see Figure 4B) and interrupt the control circuit. Maintained Some of the cable pull switches are also available with a latch feature and manual reset. This requires the operator to manually reset the switch after the problem has been cleared.! ATTENTION: After actuation and before resetting the maintained switch, the machinery should be inspected in order to detect the reason for activation. 3

6 802C Cable Pull Safety Switches Figure 4A Cable Stressed at Rated Force Figure 4B Cable Broken or Slack, Stop Signal Would Be Initiated Figure 4C Cable Pulled to Initiate Stop Signal Maintenance The stop switch, cable, and application must be inspected periodically to evaluate the operability of the stop switch and cable assembly. An initial inspection must be made within 3 to 4 months after installation. If inspection reveals contamination has reached the stop switch or cable assembly, the cause must be eliminated. Replace the stop switch and/or cable assembly when any damaged, broken, deformed, or badly worn parts (including contacts) or assemblies are found to be a part of the stop switch and/or cable assembly. The pulleys and other moving parts associated with the cable should be periodically lubricated. In the event any short circuit protection device in the circuit (such as a fuse or circuit breaker) should trip, the stop switch must be inspected for damage before restoring power and replaced if the switch is damaged. In any event, the stop switch and cable assembly should be replaced at specified intervals based upon the environment and operating conditions. Replacement of the stop switch and cable assembly should be considered no later than 500,000 operations. Always test the control system for proper functioning under control conditions to avoid hazards in the event of control malfunction after maintenance or replacement of the stop switch. For additional information, refer to the maintenance section of this catalog and the installation instruction for the safety switch. 4

7 Specifications Safety Switches 802C Cable Pull Safety Switches Description 802C cable pull switches are intended for applications such as material handling conveyors, transfer machines, painting lines, etc. These switches are typically wired in a control circuit to interrupt the machine operation when an operator pulls a cable. These switches comply IEC , CSA, UL, DIN VDE 0660 T200. The switches are available in many mounting configurations. Features Enclosure rating IP65 (IEC 529), NEMA 1, 2, 3, 4, and 12 Overlapping contacts to monitor cable tensions Positive opening NC contacts per IEC Contacts rated NEMA A300/P300 Conduit entries available are 1/2 NPT (with Pg to 1/2 NPT conduit adaptor), Pg 11, Pg 13.5 and Pg 16 depending on the control (metric to U.S. conduit adaptor available) Available with or without reset CSA certified, UL listed, and CE marked for applicable directives Variable pull forces available for different lengths of cable 5

8 802C Cable Pull Safety Switches Selection Guide mm (inches) 6

9 802C Cable Pull Safety Switches Selection Guide mm (inches) 7

10 8 Dimensions mm (inches) Figure 1 Figure 3 Figure 4 Figure 2 802C Cable Pull Safety Switches

11 9 Dimensions mm (inches) (continued) Figure 5 Figure 6 Figure 7 Figure 8 802C Cable Pull Safety Switches

12 802C Cable Pull Safety Switches Dimensions mm (inches) (continued) Figure 9 Figure 10 10

13 802C Accessories Cable Pull Safety Switches 11

14 802C Accessories Cable Pull Safety Switches 12

15 802E Hinge Safety Interlock Switches Safety and Application Safety through relying upon operational assurance of each safety interlock switch is a relative term which depends upon the design of the switch, as well as the application, installation, and maintenance of the switch. The application of each safety interlock switch must use redundant interlock switches, as well as a checking circuit. The following factors are significant to the safe operation of a safety interlock switch and must be considered by those involved with the application, installation and/or use of safety interlock switches: 1. Use of a proper system safety analysis for the application and installation of each safety interlock switch, as well as the circuit for each of the switches. Such a system safety analysis should use applicable standards such as: EN , Safety of Machinery Electrical Equipment of Machines. ANSI/NFPA/79, Electrical Standard for Industrial Machinery. ANSI B11 Series, Machine Safety Standards including B11.19 Control Reliability. EN, 292, Safety of Machinery. Other local applicable standards. 2. The application of each safety interlock switch must use redundant interlock switches with a checking circuit which identifies any malfunction or improper sequencing of any switch (whether an intermittent, momentary, or permanent malfunction) and, thereupon, initiates a pre-determined corrective action (i.e., stopping or preventing further operation of the control equipment) to include a maintenance procedure for replacement of the failed interlock switch before further use of the controlled equipment. 3. The installation of the safety interlock switch must be in accordance with the manufacturer s instructions, as well as good practice. Refer to NEMA Standard ICS 5 Clause 9 Part Follow the manufacturer s recommendations for short circuit protection in order to minimize the chance for welded contacts. 5. An effective and complete maintenance procedure and schedule must be established and implemented for the safety interlock switch and its application utilizing: The Rockwell Automation/ Allen-Bradley Maintenance of Industrial Control Equipment found in the Rockwell Automation/ Allen-Bradley Industrial Control catalog. NEMA ICS 1.3, Preventative Maintenance of Industrial Control and Systems Equipment. NFPA 70B, Electrical Equipment Maintenance. NFPA 703, Part II (As Adopted by OSHA), Electrical Safety-Related Work Practice. Only qualified individuals should apply, install, use, and/or maintain the safety interlock switch; it is the responsibility of such individuals to see that the requirements for the application, installation, use, and/or maintenance of the safety interlock switch are satisfactorily met. Installation Recommendations The switch shall not be used as a mechanical stop. Application consideration must be given to the maximum listed travel capabilities of the switch. For reliable contact operation, the actuator should be adjusted to provide overtravel beyond the operating point, but not damage the switch by excessive overtravel. Installation Consideration IEC Direct Opening Action Contacts The safety interlock switch has an IEC direct opening action feature. The actuator must move a distance beyond the trip point to engage the IEC direct opening action feature. For proper operation of the IEC direct opening action system, the switch actuator must be adjusted to provide at least 3.5 of overtravel beyond the trip point. 13

16 802E Hinge Safety Interlock Switches Maintenance The interlock switch and application must be inspected periodically to evaluate the operability of the switch. An initial inspection must be made within 3 to 4 months after installation. If inspection reveals contamination has reached the interlock switch, the cause must be eliminated. Replace the interlock switch when any damaged, broken, deformed, or badly worn parts (including contacts) or assemblies are found to be a part of the interlock switch. In the event any short circuit protection device in the circuit (such as a fuse or circuit breaker) should trip, the interlock switch must be inspected for damage before restoring power and replaced, if the switch is damaged. In any event, the interlock switch should be replaced at specified intervals based upon the environment and operating conditions. Replacement of the interlock switch should be considered no later than 500,000 operations. Always test the control system for proper functioning under control conditions to avoid hazards in the event of control malfunction after maintenance or replacement of the interlock switch. For additional information, refer to the maintenance section of this catalog and the installation instruction for the safety switch. 14

17 802E Hinge Safety Interlock Switches Specifications Description Rockwell Automation/Allen-Bradley hinge safety interlock switches are intended for interlocking applications and are usually permanently mounted on machine guards, covers and doors to verify that they are in the proper position. These switches are typically wired in a control circuit to interrupt the machine operation when the door is opened, or when the hinge actuator is moved. These switches comply with GS ET 15, IEC, EN The switches are available in three mounting configurations. Type B housing is glass fiber-reinforced thermoplastic. Type B switches are available in both lever type and rotating shaft type actuators. Type E and R housings are die-cast aluminum and available in lever type actuators only. Features Enclosure rating IP65 (IEC529), NEMA 1, 2, 3, 4, 12, and 13 Direct acting normally closed contacts per IEC, EN and DIN VDE 0660 Contacts rated NEMA A300, P300 Conduit entries available are 1/2 NPT (conduit adaptor supplied with the switch), Pg11 and Pg13.5 depending on the control (metric to US conduit adaptor available) The profile of the operator head provides a high degree of tamper resistance for the switch CSA certified, UL listed, CE marked for all applicable directives and BG pending Actuator head can be rotated in 90 increments. 15

18 16 Selection Guide mm Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á ÁÁÁÁÁ Á Á 802E Hinge Safety Interlock Switches

19 17 Selection Guide mm Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á 802E Hinge Safety Interlock Switches

20 18 Dimensions mm (inches) Figure 2 Figure 1 Figure 4 Figure 3 802E Hinge Safety Interlock Switches

21 19 Dimensions mm (inches) Figure 6 Figure 5 802E Hinge Safety Interlock Switches

22 20 Dimensions mm (inches) Figure 7 Figure 8 802E Hinge Safety Interlock Switches

23 802F Key Safety Interlock Switches Safety and Application Safety through relying upon operational assurance of each safety interlock switch is a relative term which depends upon the design of the switch, as well as the application, installation, and maintenance of the switch. The application of each safety interlock switch must use redundant interlock switches, as well as a checking circuit. The following factors are significant to the safe operation of a safety interlock switch and must be considered by those involved with the application, installation and/or use of safety interlock switches: 1. Use of a proper system safety analysis for the application and installation of each safety interlock switch, as well as the circuit for each of the switches. Such a system safety analysis should use applicable standards such as: EN , Safety of Machinery Electrical Equipment of Machines. ANSI/NFPA/79, Electrical Standard for Industrial Machinery. ANSI B11 Series, Machine Safety Standards including B11.19 Control Reliability. EN, 292, Safety of Machinery. Other local applicable standards. 2. The application of each safety interlock switch must use redundant interlock switches with a checking circuit which identifies any malfunction or improper sequencing of any switch (whether an intermittent, momentary, or permanent malfunction) and, thereupon, initiates a predetermined corrective action (i.e., stopping or preventing further operation of the control equipment) to include a maintenance procedure for replacement of the failed interlock switch before further use of the controlled equipment. 3. The installation of the safety interlock switch must be in accordance with the manufacturer s instructions, as well as good practice. Refer to NEMA Standard ICS 5 Clause 9 Part Follow the manufacturer s recommendations for short circuit protection in order to minimize the chance for welded contacts. 5. An effective and complete maintenance procedure and schedule must be established and implemented for the safety interlock switch and its application utilizing: The Allen-Bradley Maintenance of Industrial Control Equipment found in the Allen-Bradley Industrial Control catalog. NEMA ICS 1.3, Preventative Maintenance of Industrial Control and Systems Equipment. NFPA 70B, Electrical Equipment Maintenance. NFPA 703, Part II (As Adopted by OSHA), Electrical Safety-Related Work Practice. Only qualified individuals should apply, install, use, and/or maintain the safety interlock switch; and it is the responsibility of such individuals to see that the requirements for the application, installation, use, and/or maintenance of the safety interlock switch are satisfactorily met. Installation Recommendations The switch shall not be used as a mechanical stop. Application consideration must be given to the maximum listed travel capabilities of the switch. For reliable contact operation, the actuator key should be adjusted to provide overtravel beyond the operating point, but not damage the switch by excessive overtravel. Installation Consideration IEC Direct Opening Action Contacts The safety interlock switch has an IEC direct opening action feature. The actuator must move a distance beyond the point to engage the IEC direct opening action feature. For proper operation of the IEC direct opening action system, the switch actuator must be adjusted to provide at least 1mm (0.4in) of overtravel beyond the trip point. 21

24 802F Key Safety Interlock Switches Maintenance The interlock switch and application must be inspected periodically to evaluate the operability of the switch. An initial inspection must be made within 3 to 4 months after installation. If inspection reveals contamination has reached the interlock switch, the cause must be eliminated. Replace the interlock switch when any damaged, broken, deformed, or badly worn parts (including contacts) or assemblies are found to be a part of the interlock switch. In the event any short circuit protection device in the circuit (such as a fuse or circuit breaker) should trip, the interlock switch must be inspected for damage before restoring power and replaced if the switch is damaged. In any event, the interlock switch should be replaced at specified intervals based upon the environment and operating conditions. Replacement of the interlock switch should be considered no later than 500,000 operations. Always test the control system for proper functioning under control conditions to avoid hazards in the event of control malfunction after maintenance or replacement of the interlock switch. For additional information, refer to the maintenance section of this catalog and the installation instruction for the safety switch. 22

25 Specifications Safety Switches 802F Key Safety Interlock Switches Description Rockwell Automation/Allen-Bradley key interlock switches are intended for interlocking applications on machine guards, covers and doors to verify they are in the proper position. These switches are typically wired in a control circuit to interrupt the machine operation when the key is removed. These switches comply with GS ET 15, IEC The switches are available in three mounting configurations. Type S housing is thermoset polyester and type E and R housings are die-cast aluminum. Features Enclosure rating IP65 (IEC 529), NEMA 1, 2, 3, 4, 12, and 13. Separate actuator key. Direct opening action normally closed contacts per IEC and DIN VDE Contacts rated NEMA A300, P300. Conduit entries available are 1/2 NPT (conduit adaptor supplied with the switch), Pg 11 and Pg 13.5 depending on the control (metric to U.S. conduit adaptor available). Features (continued) High degree of tamper resistance due to the triple coding of the actuator key. Actuator protected against dismantle by one way notch on actuator cover (S Style). CSA certified, UL listed, CE marked for all applicable directives, and BG pending. Variable actuator approach direction with different actuator openings and the ability to rotate the head. Models are available with keys that allow for a high degree of misalignment. Replacement Keys! ATTENTION: Replacement keys are made available for replacement purposes only (mounting) and shall not be used for any other purposes such as defeating any other interlock switch. For replacement keys, please contact your local Rockwell Automation sales office. 23

26 802F Key Safety Interlock Switches Selection Guide mm Wiring 5-Pin Micro-Type Receptacle Pin Mini-Type Receptacle

27 802F Key Safety Interlock Switches Selection Guide mm 25

28 802F Key Safety Interlock Switches Selection Guide mm Wiring 2 Circuit Switches With LED

29 Specifications Safety Switches 802F Key Safety Interlock Switches Description The Magnetically Operated Key Interlock Switches are intended for safety interlocking applications requiring separate actuator key and interlocking mechanisms. These switches are typically used on machines to assure that protective guards will remain closed until an operating sequence is complete. The switches comply with GS ET 19, IEC , DIN VDE 0660 T200. Features Requires separate control signal to release key. Designed to assure the machine/ process cannot operate when the actuator key is not in the closed and locked position. Monitors the switch and the interlocking system. High-impact, heavy-duty die-cast aluminum housing. Compact/space saving design. Actuator key triple coded for prevention of false manipulation. Features (continued) Actuator approach can be turned in 90 increments. Mounting according to DIN EN Designed to IEC and GS ET 19. CSA certified, UL listed, CE marked for all applicable directives, and BG pending. Available with operating voltages 24V DC, 120V AC, 230V AC. Direct opening action contacts per IEC Replacement Keys! ATTENTION: Replacement keys are made available for replacement purposes only (mounting) and shall not be used for any other purposes such as defeating any other interlock switch. For replacement keys, please contact your local Rockwell Automation sales office. 27

30 802F Key Safety Interlock Switches The Key Operated Interlocking Switch (802F T) Comes With Two Types of Locking Methods: Mechanical Lock Mechanically locked solenoid unlocked. The key is locked in place after full insertion. The key is released when an operational voltage is applied to the solenoid. Solenoid Lock Solenoid locked mechanically unlocked. The key is locked in place when fully inserted and when an operational voltage is applied. Release of the key occurs when the operational voltage is removed from the solenoid. E1 E2 E1 E E1, E2 solenoid control safety contacts safety contacts auxiliary contacts auxiliary contacts 28

31 802F Key Safety Interlock Switches Selection Guide mm Mechanically Locked Solenoid Unlocked 29

32 802F Key Safety Interlock Switches Selection Guide mm Solenoid Locked Mechanically Unlocked 30

33 31 Dimensions mm (inches) 802F T 802F E60 Y X Y X Z Z 90 Standard Key Spring Loaded Key 802F Key Safety Interlock Switches

34 32 Dimensions mm (inches) 802F R60 802F E68 802F Key Safety Interlock Switches

35 802F Key Safety Interlock Switches Dimensions mm (inches) 2 and 3 Contact Switch 802F S Pivoting Operation Single N.C. Output Switch 802F S 33

36 802F Key Safety Interlock Switches Dimensions mm (inches) Thermoset Plastic and Stainless Steel Key Vertical Radius 34

37 802F Key Safety Interlock Switches Dimensions mm (inches) Horizontal Radius Universal Radius Key 35

38 Notes 36

39 Notes 37

40 38

Compact Rope-Activated Emergency Stop Switch. DIN mounting pattern for a globally recognized mounting configuration

Compact Rope-Activated Emergency Stop Switch. DIN mounting pattern for a globally recognized mounting configuration C R US Conforms to EN418, EN292, EN0947-5-1, EN50041, BS504, ISO1850 UL and C-UL listed ER4020 Compact Rope-Activated Emergency Stop Switch Compact size allows this switch to be used on smaller machines

More information

Integral E-stop the lid-mounted E-stop button provides emergency stopping capability at the extreme end of the installation

Integral E-stop the lid-mounted E-stop button provides emergency stopping capability at the extreme end of the installation C R US Conforms to EN418, EN292, ISO/IEC1850, EN0947-5-1 UL and C-UL listed ER019 Combination Rope and Push-Button Actuated Emergency Stop Switch Long rope spans of up to 75 m (24 ft.) for standard model

More information

Installation and Operating Instructions

Installation and Operating Instructions Plastic encased safety interlocking switch Type PSEN me2/psen me3 Intended use The plastic encased safety switches PSEN me2 and PSEN me3 with separate actuator are suitable for the mounting on safety guards.

More information

Integral E-stop the lid-mounted E-stop button provides emergency stopping capability at the extreme end of the installation

Integral E-stop the lid-mounted E-stop button provides emergency stopping capability at the extreme end of the installation C R US Conforms to EN418, EN292, ISO/IEC1850, EN0947-5-1 UL and C-UL listed ER019 Combination Rope and Push-Button Actuated Emergency Stop Switch Long rope spans of up to 75 m (24 ft.) for standard model

More information

Hinge Wing Safety Interlock Switches

Hinge Wing Safety Interlock Switches Hinge Wing Safety Interlock Switches SI-HG80 Series Safety Interlock Switches Encapsulated in a Load-Bearing Hinge Inline QD Fitting Right-Angle QD Fitting Features Safety switch is integrated and encapsulated

More information

Installation and Operating Instructions

Installation and Operating Instructions Plastic encased safety interlocking switch Type PSEN me4 Intended use The plastic encased safety switches PSEN me4 with separate actuator are suitable for the mounting on safety guards. They are designated

More information

SG-B1 SERIES / SG-A1 SERIES

SG-B1 SERIES / SG-A1 SERIES 643 Door with Solenoid Interlock / Door Ultra-slim SG-B1 SERIES / SG-A1 SERIES Related Information General terms and conditions... F-7 General precautions... P.1501 PHOTO PHOTO Conforming to Machine &

More information

SERIES AZM170. Solenoid-Latching Machine Guard Safety Interlock Switch. Features & Benefits. Description. Typical Applications

SERIES AZM170. Solenoid-Latching Machine Guard Safety Interlock Switch. Features & Benefits. Description. Typical Applications SERIES AZM170 Description The AZM170 Series is designed for machines/work cells where access to a hazardous work area must be controlled until safe conditions exist. Their solenoid-latching feature permits

More information

Shock/Vibration Control Switches

Shock/Vibration Control Switches Shock/Vibration Control Switches Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 ` Installation Instructions 00-02-0185 2013-02-01 Section 20 Please read the following information before installing.

More information

Safety Interlock Switches

Safety Interlock Switches Interlock Switches Interlock Switches Selection and Application of Switches..... 186 Flat Pack Style Switches................... 191 Limit Switch Style Switches................. 199 Locking Style Switches....................

More information

ZB0050 / ZB0051 ZB0070 / ZB0071

ZB0050 / ZB0051 ZB0070 / ZB0071 Operating instructions Safety Rope Emergency Stop Switches UK ZB0050 / ZB0051 ZB0070 / ZB0071 7390877 / 02 08/2013 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4 2.2

More information

Standard Product Low Profile Type 12 One-Door Disconnect Enclosures

Standard Product Low Profile Type 12 One-Door Disconnect Enclosures 763.422.2600 Spec-00005 M763.422.2211 Wall-Mount Preferred-Cutout s Low-Profile Type 12 s and Accessories Wall-Mount Preferred-Cutout s Low-Profile Type 12 s and Accessories Low-Profile, One- to Five-Door

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS Series Rolling Fire Door Operators CORPORATION GENERAL NOTES TO REDUCE THE RISK OF SEVERE INJURY OR DEATH, READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS

More information

Solenoid interlocks AZM 190 range. 128 Schmersal ,3 4,5 M20 17,5 23,5

Solenoid interlocks AZM 190 range. 128 Schmersal ,3 4,5 M20 17,5 23,5 2.19 AZM 19 range 13 44 32 2,3 3 1 Features Voltage variants Approvals Thermoplastic enclosure Manual / Emergency release Long life Actuation on de-energisation or energisation Slim design, particularly

More information

CAUTION CM-SE CM-S21 CM-S41

CAUTION CM-SE CM-S21 CM-S41 CAUTION Safety, Technology & Innovation CM Series Operating Instructions for, CM-S21,, CM-S11, CMS31 CM Series Safety System This information is designed to help suitably qualified personnel install and

More information

IEC Limit Switches Selection Guide

IEC Limit Switches Selection Guide IEC Limit Switches Selection Guide Limit Switches Selection Guide ABM Series ABP Series AAP Series Series ABM Series ABP Series AAP Series Prices start at Description Heavy duty IEC Double-insulated,

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL Cornell RG Operator RGRL Series (w/ Internal Interlock sensor) ES 10-288 GENERAL NOTES TO REDUCE THE RISK OF SEVERE INJURY OR DEATH, READ AND FOLLOW ALL INSTALLATION

More information

CONTROLLERS & MODULES EMERGENCY STOP & STOP CONTROL SAFETY LIGHT SCREENS

CONTROLLERS & MODULES EMERGENCY STOP & STOP CONTROL SAFETY LIGHT SCREENS SAFETY LIGHT SCREENS CONTROLLERS & MODULES EMERGENCY STOP & STOP CONTROL Emergency Stop & Stop Control Rope pull emergency stop switches, when used with steel wire rope, provide emergency stop actuation

More information

F3S-TGR-KHL1/-KHL3/-KHL3R

F3S-TGR-KHL1/-KHL3/-KHL3R Safety guard-lock door switches with full stainless steel body F3S-TGR-KHL1/-KHL3/-KHL3R The F3S-TGR-KHL3 safety-door switch keeps medium to large guard doors closed until hazards have been removed. It

More information

XCS Safety Interlock Selection

XCS Safety Interlock Selection Steven Engineering-2 Ryan Way-South San Francisco, CA 980-6370-Main Office:(650)588-9200-Outside Local Area:(800)258-9200-www.stevenengineering.com Selection Plastic, Double, Turret Head c, Type, locking

More information

D4BL. Protective Doors Are Locked Until Machines Completely Stop Operating. Guard Lock Safety-door Switch. Model Number Structure.

D4BL. Protective Doors Are Locked Until Machines Completely Stop Operating. Guard Lock Safety-door Switch. Model Number Structure. Guard Lock Safety-door Switch Protective Doors Are Locked Until Machines Completely Stop Operating A mechanical lock is applied automatically when the Operation Key is inserted. A high level of safety

More information

IEC Limit Switches Selection Guide

IEC Limit Switches Selection Guide IEC Limit Switches Selection Guide Limit Switches Selection Guide ABM Series ABP Series AAP Series Series ABM Series ABP Series AAP Series Prices start at Description Heavy duty IEC Double-insulated,

More information

HS1B Series Full Size Interlock Switch. GS-ET-15 BG standard in Germany. Part Number Key

HS1B Series Full Size Interlock Switch. GS-ET-15 BG standard in Germany. Part Number Key HSB Series Full Size Interlock Switch HSB features: Rugged aluminum die-cast housing Direct Opening Action: If the door is forced open, the contacts are disconnected even if they are welded or stuck Available

More information

Safety Interlock Switches

Safety Interlock Switches Safety Interlock Switches D4BL D4BL uard Lock Safety-Door Switch Release protective cover locks using controller signals or pushbutton switches after the cutting tool stops moving due to inertia A mechanical

More information

Solenoid interlocks AZM 170 range. 98 Schmersal 22 8,2 60. ø4,2. ø Pg 11

Solenoid interlocks AZM 170 range. 98 Schmersal 22 8,2 60. ø4,2. ø Pg 11 2.4 AZM 170 range Features Thermoplastic enclosure Compact design Manual release Long life Double insulated X High holding force 1,000 N N latching force Cut clamp termination Actuation on de-energisation

More information

D4BS. Safety-door Switch. Model Number Structure. Switch D4BS - S Operation Key D4BS - K. Ordering Information

D4BS. Safety-door Switch. Model Number Structure. Switch D4BS - S Operation Key D4BS - K. Ordering Information Safety-door Switch Safety-door Switch s Special Operation Key Directly Pulls Apart the Contacts from Each Other and Contributes to the Safety of the Production Site Conforms to EN (TÜV) standards corresponding

More information

1370 DC Loop Contactors and Lug Kits

1370 DC Loop Contactors and Lug Kits Installation Instructions 1370 DC Loop Contactors and Lug Kits 1370 DC Contactors are electromagnetically held contactors specially designed to switch the armature current from a DC drive module to a shunt

More information

Safety Switches NP GP TP. More than safety.

Safety Switches NP GP TP. More than safety. Safety Switches NP GP TP More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in

More information

HS1B R - R. Door Interlock Switches. HS1B Series. HS1B Series Full Size Interlock Switch. Part Number. HS1B features: Part Number Key.

HS1B R - R. Door Interlock Switches. HS1B Series. HS1B Series Full Size Interlock Switch. Part Number. HS1B features: Part Number Key. HSB Series HSB Series Full Size Interlock Switch HSB features: Body Rugged aluminum die-cast housing Direct Opening Action: If the door is forced open, the contacts are disconnected even if they are welded

More information

GKR/GKL Series Dual Entry Solenoid Key Operated Safety Interlock Switch

GKR/GKL Series Dual Entry Solenoid Key Operated Safety Interlock Switch Series Dual Entry Solenoid Key Operated Safety Interlock Switch FEATURES Solenoid power to lock or power to unlock Side or top key entry Separate switches for key position and solenoid status Available

More information

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE USER MANUAL IMI vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0929039_A ISSUED 03/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Overview General

More information

Solenoid interlocks AZM 415 range. 134 Schmersal 29,5 6,5 24,7. 8,6 Pg 13,5 46,5 24,5

Solenoid interlocks AZM 415 range. 134 Schmersal 29,5 6,5 24,7. 8,6 Pg 13,5 46,5 24,5 2.22 415 range Features Metal enclosure Two switches in one enclosure Problem-free opening of stressed doors by means of bell-crank system Robust design Long life High holding force 3,500 N Adjustable

More information

Shock/Vibration Control Switches Installation Instructions Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 GENERAL INFORMATION LISTED*

Shock/Vibration Control Switches Installation Instructions Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 GENERAL INFORMATION LISTED* Shock/Vibration Control Switches Installation Instructions Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 VS-7037N Revised 04-05 Section 20 (00-02-0185) Please read the following instructions before

More information

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE 4 NHP SAFETY REFERENCE GUIDE CONTENTS SAFETY TECHNOLOGY Risk Reduction Options Permanent Fixed Guard 4-02 Interlocked Guard: 4-03 Limit Switches 4-08 Presence Sensing Technology 4-09 Safety Laser Scanners

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS Series Rolling Fire Door Operators UL325-2010 Compliant Restricted Duty Operators CORPORATION IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the

More information

Cable (Rope) Pull Switches Lifeline 4

Cable (Rope) Pull Switches Lifeline 4 Emergency Stop Devices Description The cable/push button operated system can be installed along or around awkward machinery such as conveyors and provide a constant emergency stop access. The is the only

More information

Manual Reset Limit Switch

Manual Reset Limit Switch Manual Reset Limit Switch A Series of Pull-reset Models Available Ideal for elevators (EN81), escalators (EN115), and conveyors. Positive opening mechanism insulation approved by TÜV and BIA. and double

More information

Model 550 Series Vibration Switches

Model 550 Series Vibration Switches OPERATION MANUAL Vibration Switches Includes: 550 550M 550-X 550M-X Page 2 SECTION TITLE PAGE 1. INTRODUCTION... 2 2. FEATURES... 3 3. WIRING... 4 4. ANALOG METER... 4 5. TESTING... 4 6. INSTALLATION...

More information

Operating instructions Solenoid interlock TKM/TKF. 1. About this document. Content

Operating instructions Solenoid interlock TKM/TKF. 1. About this document. Content 1. About this document Operating instructions.............pages 1 to 6 Original 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning

More information

Hinge Wing Safety Interlock Switches

Hinge Wing Safety Interlock Switches SI-HG80 Series Safety Interlock Switches encapsulated in a load-bearing hinge Safety switch is integrated and encapsulated into a load-bearing hinge, providing a high degree of protection from intentional

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Installation Instructions

Installation Instructions Installation Instructions Bulletin 1494V Variable Depth, Flange Operated Circuit Breaker Operating Mechanisms For use with Circuit Breakers 140G-G, 140MG-G, 140G-H, 140MG-H, 140G-I, 140MG-I, 140G-J, 140MG-J,

More information

Operating Instructions

Operating Instructions DuroSite & SafeSite Area Light with Adapters Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury,

More information

Safety switches for hinged doors

Safety switches for hinged doors 4 Safety switches for hinged doors Selection diagram FR FM FX FZ FK 5 18 7 9 snap action overlapped CONTACT BLOCKS 20 21 22 33 34 1NO+ CONDUIT ENTRIES Threaded conduit entries (standard) With cable gland

More information

Door Interlock Switches

Door Interlock Switches HS5B Series HS5B Series Miniature Interlock Switch HS5B features: mm x mm x 9mm Compact Housing Available with Contact Confi gurations (NO + NC or NC) Flexible Installation: By turning the head of the

More information

Solenoid interlock AZM 200 The non-contact interlock.

Solenoid interlock AZM 200 The non-contact interlock. Solenoid interlock AZM 200 The non-contact interlock. Solenoid interlock AZM 200 The non-contact Solenoid interlocks demand accurate alignment of actuator and device. This requirement is met on new machinery.

More information

Wall-Mount Preferred-Cutout Disconnects Preferred Cutout, Disconnects, Type 12

Wall-Mount Preferred-Cutout Disconnects Preferred Cutout, Disconnects, Type 12 763.422.2600 SPEC-00245 L763.422.2211 DISCONNECT WALL-MOUNT PREFERRED-CUTOUT DISCONNECTS PREFERRED CUTOUT, DISCONNECTS, TYPE 12 Wall-Mount Preferred-Cutout Disconnects Preferred Cutout, Disconnects, Type

More information

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key!

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key! 655 Door with Key SERIES Related Information General terms and conditions... F-7 General precautions... P.50 PHOTO PHOTO Conforming to Machine & EMC Directives Recognition Certified MEASURE ITY panasonic.net/id/pidsx/global

More information

Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66

Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66 Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66 Double Insulation (for thermoplastic type) High mechanical resistant Degree of protection IP65 (thermoplastic) IP66

More information

HS1C Interlock Switches with Solenoid

HS1C Interlock Switches with Solenoid HSC es with The guard door remains locked until the machine stops completely. With the actuator mounted on the guard door and the interlock switch on the machine, the door is mechanically locked when closed.

More information

HS1E Series Full Size Solenoid Locking Switches

HS1E Series Full Size Solenoid Locking Switches HS1E Series Full Size Solenoid Locking Switches AS-Interface Safety at Work Barriers Enabling Switches Door Interlock Switches X Series E-Stops Overview HS1E features: Basic unit and solenoid unit in one

More information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service No One Does It Like Mipco Mipco Interlocked Reefer Power Outlets are used extensively in port terminals and shipboard applications to provide a safe, watertight electrical connection for refrigerated containers.

More information

Safety switches with solenoid and separate actuator

Safety switches with solenoid and separate actuator 4 Safety switches with and separate Selection diagram VF KEYF20 VF KEYF21 VF KEYF22 VF KEYF28 CTUTORS HED TYPE ND WORKING PRINCIPE D locked with de-energized E locked with energized SIGNING ED B Z two

More information

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1

More information

D4DL. Guard Lock Safety-door Switch. Ordering Information. Model Number Legend Switches D4DL- -

D4DL. Guard Lock Safety-door Switch. Ordering Information. Model Number Legend Switches D4DL- - Guard Lock Safety-door Switch Polymer housing, IP65, and slow-action contacts with positive opening. 2 versions Mechanical lock/solenoid release Solenoid lock/mechanical release Rotatable operating head

More information

A. This Section includes the following types of sectional overhead doors:

A. This Section includes the following types of sectional overhead doors: SECTION 08361 - SECTIONAL OVERHEAD DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Solenoid interlocks AZM 161 range Schmersal. a 5,5. Pg11/M16x1,5

Solenoid interlocks AZM 161 range Schmersal. a 5,5. Pg11/M16x1,5 .1 AZM 11 range Features Thermoplastic enclosure Manual and emergency release Long life Double insulated X High holding force, N N latching force Wiring compartment Actuation on de-energisation or energisation

More information

Heavy Duty Industrial Foot Switches

Heavy Duty Industrial Foot Switches P-1303 819-0523 Heavy Duty Industrial Foot Switches Installation Instructions Failure to follow these instructions may result in product damage, equipment damage, and serious or fatal injury to personnel.

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL UL325-2010 Compliant Commercial and Industrial Door Operator Logic Control Continuous Duty IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the risk

More information

Safety Limit Switch

Safety Limit Switch Safety Limit Switch D4B-@N CSM_D4B-_N_DS_E_5_1 Snap-action contact with certified direct operation certification. Maintenance, seal, and resistance to shock increased and direct mechanism added. Three-conduit

More information

OSYSU Series Outside Screw and Yoke Valve Supervisory Switch

OSYSU Series Outside Screw and Yoke Valve Supervisory Switch Features NEMA 4X* (IP 65) and 6P (IP 67) *Enclosure is 4X. For additional corrosion protection of mounting hardware, use model OSYSU-2 CRH -40º to 140º (-40ºC to 60ºC) operating temperature range Visual

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Safety switches with solenoid and separate actuator

Safety switches with solenoid and separate actuator Safety switches with solenoid and separate actuator These switches are used on machines where the hazardous conditions remain for a while, even after the machines have been switched off, for example because

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Safety door-handle system STS

Safety door-handle system STS Safety door-handle system STS Full body access ha Safety door-handle system STS EN 1037 Features The safety door-handle system is suitable for all types of safety guards. Safety switches and solenoid interlocks

More information

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject

More information

1329I Integrated Drive/Motor CE Filter Option Kit

1329I Integrated Drive/Motor CE Filter Option Kit Instruction Sheet 1329I Integrated Drive/Motor CE Filter Option Kit CE filter options are designed to be used with the 1329I Integrated Drive/Motor. The main function of the CE filter is to reduce the

More information

Type N550 Snappy Joe Emergency Shutoff Valves

Type N550 Snappy Joe Emergency Shutoff Valves Instruction Manual MCK-1149 Type N550 March 2010 Type N550 Snappy Joe Emergency Shutoff Valves Failure to follow these instructions or to properly install and maintain this equipment could result in an

More information

Position switches FR series

Position switches FR series Position switches FR series Selection diagram 01 A1 08 14 01-7 0 A 05 A5 external rubber gasket external rubber gasket for electrical panels external rubber gasket external rubber gasket 0 1 5 34 50 33

More information

Preferred Cutout, Disconnect Enclosure, Type 12

Preferred Cutout, Disconnect Enclosure, Type 12 763.422.2600 Spec-00245 J763.422.2211 Wall-Mount Preferred-Cutout s Preferred Cutout, s, Type 12 Wall-Mount Preferred-Cutout s Preferred Cutout, s, Type 12 Preferred Cutout, Enclosure, Type 12 INDUSTRY

More information

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service Installation Instructions VA-908x Code No. LIT-12011566 Issued August 24, 2009 Applications The VA-908x Series Electric

More information

DIRACT BRAKES 70 SERIES 4 POST BRAKE INSTRUCTIONS

DIRACT BRAKES 70 SERIES 4 POST BRAKE INSTRUCTIONS Bulletin No. BK4605 (3/18) DIRACT BRAKES 70 SERIES 4 POST BRAKE INSTRUCTIONS IMPORTANT Read this bulletin carefully before installing or operating this brake. Failure to comply with these instructions

More information

Selection Guide. Control Circuit and Load Protection

Selection Guide. Control Circuit and Load Protection Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

Locking Style mm AUTOCAD, STEP, IGES & PDF. Kits Actuator Type Interlock Kit Model * Contact(s) SI-LS42DMSG SI-LS42WMSG

Locking Style mm AUTOCAD, STEP, IGES & PDF. Kits Actuator Type Interlock Kit Model * Contact(s) SI-LS42DMSG SI-LS42WMSG Locking Style Spring or Solenoid Locking Two locking mechanisms are available: spring lock with energized solenoid release and energized solenoid lock with spring release. Rigid and flexible in-line actuators

More information

HS1E Series Full Size Interlock Switch with Locking Solenoid

HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Series HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Key features include: Basic unit and solenoid unit in one housing Plastic Housing: Light weight Ease of Wiring: All the terminal

More information

PCVS Series Control Valve Supervisory Switch

PCVS Series Control Valve Supervisory Switch Features NEMA 4X* (IP 65) and 6P (IP 67) *Enclosure is 4X. For additional corrosion protection of mounting hardware, use model PCVS-2 CRH -40º to 140º (-40ºC to 60ºC) operating temperature range Visual

More information

Hinge Wing Safety Interlock Switches

Hinge Wing Safety Interlock Switches Datasheet SI-HG80 Series Safety Interlock Switches Encapsulated in a Load-bearing Hinge Safety switch is integrated and encapsulated into a load-bearing hinge, providing a high degree of protection from

More information

2.11. Limit Switches. Contents Description. Special Purpose Limit Switches. Special Purpose Limit Switches

2.11. Limit Switches. Contents Description. Special Purpose Limit Switches. Special Purpose Limit Switches Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) 46-5480 www.cmafh.com.11 Product Description Features Special Purpose (Type F), Rotating Shaft (Type J),

More information

Company Switch Installation Instructions and User Manual

Company Switch Installation Instructions and User Manual Lex Products Corporation 15 Progress Drive Shelton, CT 06484 203.363.3738 203.363.3742 Fax Lex West 11847 Sheldon Street Sun Valley, CA 91352 818.768.4474 818.768.4040 Fax www.lexproducts.com info@lexproducts.com

More information

Schaltgeräte GmbH GmbH Geschäftsbereich Leuchten

Schaltgeräte GmbH GmbH Geschäftsbereich Leuchten ,, INC. INC. GmbH 9001 Knight Road Houston, TX 77054 Tel: 800-782-4357 FAX: 713-792-9301 E-mail: sales@rstahl.com Website: www.rstahl.com & SHEET EXLUX 6000 Series 6000/5 6000/8 Explosion Protected Fluorescent

More information

Door Interlock Switches

Door Interlock Switches HSE Series HSE Series Full Size Locking Switches Overview X Series E-Stops HSE features: Basic unit and solenoid unit in one housing Plastic Housing: Light weight Ease of Wiring: All the terminal screws

More information

Instructions for Installation, Operation and Maintenance of: "WSRD" Interlocked Receptacles 30, 60 & 100 Ampere

Instructions for Installation, Operation and Maintenance of: WSRD Interlocked Receptacles 30, 60 & 100 Ampere 331114-1 INSTRUCTION SHEET Instructions for Installation, Operation and Maintenance of: "WSRD" Interlocked Receptacles 30, 60 & 100 Ampere Read instructions carefully and with full understanding for safe

More information

HS6B Series Subminiature Interlock Switch

HS6B Series Subminiature Interlock Switch HS6B Series Subminiature Interlock Switch HS6B features: Only 78 x 30 x 15mm Allows highest level of safety by having 3 contacts: dual load contacts + monitoring contact (ISO13849-1, EN954-1) Two actuator

More information

Hinged Safety Door Switch

Hinged Safety Door Switch Hinged Safety Door Switch Polymer housing, IP65, and slow-action contacts with positive opening. Two actuator types are available: Shaft Arm lever Arm lever type can be adjusted to allow a right (180 ),

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 835-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics

More information

Selection diagram. Actuators. Bodies. Contact blocks. Cable entry AB BB CB. Thermoplastic

Selection diagram. Actuators. Bodies. Contact blocks. Cable entry AB BB CB. Thermoplastic Safety switches Selection diagram Actuators AB BB CB TB S5 SC Thermoplastic Bodies E0 I E20 I E0 I Contact blocks 0 NO+NC slow action 0 2NC slow action 08 2NC slow action (for pull-wire switches) Pg 3,5

More information

Bulletin 871P Can Sensors

Bulletin 871P Can Sensors Bulletin 871P Can Sensors Description Bulletin 871P inductive proximity can sensors are self-contained solid state devices, designed specifically for sensing size 202 to 704 metal cans without physical

More information

Model Description Vac. Max rating Pedestal Only: 36 Utility Pedestal W/O Disconnect General Duty Series:

Model Description Vac. Max rating Pedestal Only: 36 Utility Pedestal W/O Disconnect General Duty Series: MAPA Products MPD-XX / Pedestal Disconnect 30, 60, 100 amp February 2014 Pedestal Disconnect Installation Instructions Parts List MAPA Products Fusible Rainproof Pedestal Mounted Safety Switch provides

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Installation, Operation & Maintenance Manual

Installation, Operation & Maintenance Manual APL-2 Series Valve Position Monitor Installation, Operation & Maintenance Manual Address : Seonggok-dong, 155, Byeolmang-ro, Danwon-gu, Ansan-si, Gyeonggi-do, South Korea Tel : +82-31-488-8266, Fax : +82-31-488-8269,

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

HS1C Series Full Size Interlock Switch with Locking Solenoid. GS-ET-15 BG standard in Germany. HS1C Series Functionality

HS1C Series Full Size Interlock Switch with Locking Solenoid. GS-ET-15 BG standard in Germany. HS1C Series Functionality Full Size Interlock Switch with Locking Solenoid HSC Key features include: Rugged Aluminum Die-cast Housing With the actuator mounted on a movable door, and the switch on a machine, the door can be mechanically

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTUCTIONS AND OPEATION MANUAL FS-50 Series olling Fire Door Operators UL325-200 Compliant estricted Duty Operators COPOATION 3-3966-02(0) BY G ECN 5 5/9/ 2/0 IMPOTANT INSTALLATION INSTUCTIONS

More information

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module The following specification defines the minimum requirements for the supply of motor operated valve actuators with a field communication bus system for remote control. The complete system shall consist

More information

Safety switches with solenoid and separate actuator

Safety switches with solenoid and separate actuator 4 Safety switches with solenoid and separate Selection diagram VF KEYF20 VF KEYF VF KEYF22 VF KEYF28 CTUTORS D1D locked with De-energized solenoid WORKING PRINCIPLE D1E locked with Energized solenoid D5D

More information

Locktite Manual Reset Gas Shut-Off Valves

Locktite Manual Reset Gas Shut-Off Valves Instruction Manual 750, 10/25/04 Locktite Manual Reset Gas Shut-Off Valves Series 200 LT Eclipse 200 LT valves are manually opening valves that automatically shut off the gas supply to a combustion system

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL NEMA 4X UL325-2010 Compliant Commercial and Industrial Door Operator Logic Control Continuous Duty IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the

More information