INSTRUCTION MANUAL. Flow sensor FUS20 series HIR

Size: px
Start display at page:

Download "INSTRUCTION MANUAL. Flow sensor FUS20 series HIR"

Transcription

1 HIR INSTRUCTI MANUAL sensor FUS0 series P l e a s e b e s u r e t o r e a d t h i s User's Manual before using the sensor. E specially, be sure to read safety instructions carefully. P lease keep this manual handy w i t h c a r e s o y o u c a n r e f e r t o i t whenever necessary. s t e d i t i o n

2 Warning and caution in order to ensure safety Display explanations Danger Failure to heed the warning of apparent danger may result in death or serious injuries. Warning Failure to heed the warning of conditionally dangerous situations may result in death or serious injuries. Caution Failure to heed the warning of conditionally dangerous situations may result in minor or not too serious injuries or damage to properties Fluid medium and usage environment A flammable fluid must not be used. Danger Please do not use the product in flammable gas environment. Since the product is not explosion-proof, explosion or fire may be caused. Warning For wiring, turn off the power supply first. Please discharge static electricity built in body, tool and equipment before and during work. Use a wire with elasticity as wire for robot connection in the movable part. This product and wiring must be installed as far away as possible from noise source such as strong electric line, etc. Please do not short-circuit a load, or causing damage or burn. Please do not conduct improper wire connection, which result in burst or damage of the sensor Please make sure to put connector cover on after connecting connector. Please do not stress a cable drawing position directly or connector. Warning Since it is not conformed to the Measurement Law, please do not use the product for the commercial purpose. Please do not use the product with other than applicable fluid medium, or the accuracy can not be guaranteed. And, Please do not use the product in an environment containing corrosive gas, flammable gas and oxygen. Please install a filter, an air dryer and an oil mist filter (micro alescer) onto the primary side (upstream) of the sensor since the compressed air from the compressor contains drain (water, oil oxide and foreign material, etc) When using this product with suction lift verification, etc., please always install an air filter onto the upstream of suction side to prevent suction of foreign materials. Please do not use the product in an environment containing corrosive gas such as sulfurous acid gas, or etc. Please use the product within the ambient / fluid temperature ranges 0 to 50 C. Even in the specified temperature range, please do not use the product where ambient / fluid temperatures change suddenly, and form dew condensations Please use the product in accordance with specifications. If used out of the maximum working pressure and working flow range, the product may result in failures. The protective structure of this product is equivalent to IP40. Please do not install the product where moisture, salt, dust or swarf is contained, or where pressurized, or depressurized, neither. The flow rate of this product is measured by mass flow where mass flow is Caution converted to volumetric flow at 0 C and atmospheric pressure (0kpa). Piping and installation Caution It must be piped, while matching the flow direction and direction specified on the body. When the sensor is installed to the piping, avoid excessive driving torque or loading torque: Please flash the pipe by air blow to remove foreign substances before piping. Prevent the entrance of seal tape or adhesive into the piping when conduction pluming. If a quick-fitting is used, the tube must be inserted certainly. Please pulls the tube to check that it will not come out. The flow display uses liquid crystal. It may be hard to see by an angle. This product can be installed with any orientation; vertical, horizontal, right or left. Piping must be done prior to panel installation. Usage and Maintenance t Warning Caution Output accuracy is affected by self-heating caused by energizing other than temperature characteristics. At the time of usage, stand-by time (over 5 minutes after energization) must be provided. For self-diagnosis, this product does not conduct flow rate detecting switch operation for about 4 seconds immediately after energized. Please make a control circuit and programs to ignore signals for about 4 seconds after energized. Please install fail-safe devise for the applications where the malfunction of the sensor leads to major accident. When changing set points of the output, please stop the equipment, then change the set points, or an accident may occur. Disassembly and modification must not be done or causing a failure. When an error occurs during operation, please turn off power supply immediately, and terminate the operation, and contact to the sales office. Solvent/alcohol/cleaner, etc., must not be used to remove contamination, etc., or causing a resin to be corroded. Please wipe with diluted neutral detergent by tightly squeezed waste cloth, etc. Even if exceeding the flow rate range, analog output will be provided. "Hi" or "Lo" will be displayed. However, please be noticed in advance that accuracy is not guaranteed. Please do not punch sensor display. It may cause a failure. Display/operating section names and functions Main display (green/red) Display set value and flow rate Display color can be changed. rate unit display (green) Display flow rate unit Sub display (green/red) Display flow direction and operating status Display color can be changed Output (OUT) display (green) Illuminate when CH output is Flash when over current is detected Output (OUT) display (green) Illuminate when CH output is Flash when over current is detected. (UP) key Sequentially displays the CH data when the flow rate is displayed. Display the maximum value during peak hold operation When selecting a mode, determines the mode When setting each data, using count up numbers, etc. Wiring Danger Power supply voltage and outputs must be used with the specified voltage. Applying more than specified voltage may cause malfunction, damage of sensor, electric shock or fire. Please do not apply load more than the rated output. Damage of the output or fire may be caused. MODE Key Use to enter each setting mode Use to return to the flow display Use to turn off peak hold operation (DOWN)key Sequentially displays the CH data when the flow rate is displayed. Display the minimum value during peak hold operation When setting each data, using count down numbers, etc.

3 Piping and installation It must be piped, while matching the flow direction and direction specified on the body direction Please flash the pipe to remove foreign substances and swarf, etc., in inside of pipe before piping. Prevent the entrance of seal tape or adhesive into the piping when conduction pluming. If a quick-fitting is used, the tube must be inserted certainly. Please pulls the tube to check that it will not come out. This product can be installed with any orientation; vertical, horizontal, right or left. Tightening torque of fixing screw is 0.5N.m. <Vertical (female thread on the bottom)> <Bracket installation> <Horizontal (through hole)> <Panel mount installation> 3Wiring Power supply voltage and outputs must be used with the specified voltage. Applying more than specified voltage may cause malfunction, damage of sensor, electric shock or fire. Please do not apply load more than the rated output. Damage of the output or fire may be caused. For wiring, turn off the power supply first. Please discharge static electricity built in body, tool and equipment before and during work. Use a wire with elasticity as wire for robot connection in the movable part. This product and wiring must be installed as far away as possible from noise source such as strong electric line, etc. Please take other countermeasures for a surge on the power supply line. Please do not short-circuit a load, or causing damage or burn. Please do not conduct improper wire connection, which result in burst or damage of the sensor. Connector cover Please make sure to put connector cover on after connecting connector. Please do not stress a cable drawing position directly or connector. Example of internal circuit and load connection NPN output type Model:FUS0-N - < CH function selected switch output> (brown)power+ Main circuit R (black)ch SW output (white)ch SW output (gray)analog output (blue)power- + - Model no. of bracket :FUS0-B <Panel installation > 3 Install panel stopper on the reverse side of panel (by hitching to the cover stopper) and fix by the screws. Install panel holder cover on the upper side of panel. Please refer to appearance dimension for panel cut size. Panel Panel holder cover Panel stopper Sensor 4 5 Caution: Install panel holder from the reverse side of panel. Panel holder Screws Push panel holder until the sensor is firmly fixed and connect the connector. Without needle valve type Panel mount kit: FUS0-P Built-in needle valve type Panel mount kit: FUS0-PN Install the sensor on the reverse side of panel. Make sure to conduct piping before installing panel mount so as not to apply excessive force to panel mount parts.. Tightening torque of panel stopper is 0.06N m. <CH function selected external input> (brown)power+ Main circuit PNP output type Model :FUS0-P - <CH function selected switch output> (brown)power+ Main circuit (black)ch SW output (white)ch SW output ((gray)analog output ((blue)power- <CH function selected external input> (brown)power+ Main circuit R R R (black)ch SW output ((white)ch SW output ((gray)analog output (blue)power- ((gray)analog output ((blue)power- (black)ch SW output (white)ch SW output (FUS0 side) Pin No. Line color Content Brown Power supply (DC to 4V, DC 4V) Black CH(Switch output : max50ma) 3 White CH(Switch output : max50ma or External input) 4 Gray Analog voltage output : DC to 5V Connected load impedance 50kΩ and over) Analog current output : DC 4 to 0mA Connected load impedance 300Ω or less) 5 Blue 0V (GND) Analog output voltage output type R:aboutkΩ Current output type R:about00Ω

4 -3-4Function Some functions and settings are completed when the normal flow is displayed, and some after entering setting mode. The setting mode is divided into standard setting mode and detailed setting mode based on the frequency of use. <Normal mode> Item Description rate display Instantaneous flow rate is displayed. Integrating function Integrated flow rate is displayed. Peak hold function Maximum and minimum flow rate values during the specified period can be read. Setpoint Switch data (setpoint value and operation mode) are displayed to verification check. Key lock Setting changes are disabled to prevent incorrect operations. Error display function The error state is displayed. <Standard setting mode> Item Description Switch output Having pieces of switch output, 7 operation patterns and stop of operation can be set. Forcible output Switch output is turned on forcibly to check wiring connection and function initial operation of input unit. 0 point adjustment Deviation of the display from o is corrected. <Detailed setting mode> Item Description direction Only bi-directional type, flow direction can be switched. selection CH function Sets the CH function. selection Selects Switch output, External input of auto reference, or External input of integrated reset. Auto reference function Response time setting Display speed selection Sub-display selection Displayed color selection Hysteresis fixed value selection rate unit selection When CH function selected external input of auto reference, setting value of switch output can be taken by external input or key operation. Sets the response time. The response time can be selected from 0ms to 80ms. Change the speed of the displayed. Change the indication of the sub-display. Selects direction, rate unit, or Working fluid. Displayed color can be changed. Sets hysteresis of the window operation mode and the auto reference mode. (8 steps) rate unit can be changed. Standard condition (ANR): Converted to volumetric flow at 0 C and atmospheric pressure (0kPa). Reference condition (NOR): Converted to volumetric flow at 0 C and atmospheric pressure (0kPa).(calculation value) Eco mode setting Current consumption can be lowered. When the product is left for min. without any operation, it s shift to eco mode. Reset setting Return to default settings (factory settings) 5Setting method 5-.Normal mode <Changing Instantaneous flow rate display and integrated flow display> <Instantaneous flow rate> Display unit selection Instantaneous flow rate display (Unit : m ) Press M key once when Instantaneous flow (Integrated flow) is displayed. Display unit selection appears and the display blinks. Press or key to choose display and decide display by pressing M key once. Integrated flow display (Unit :ml L) ml <Peak hold function > <Instantaneous flow rate display> Press and M simultaneously Peak hold display Being held down <Peak value displayed> <Set point verification method> Note) This function is canceled when auto reference mode by external input is used. <Key lock function > Key lock <Instantaneous flow rate display (key unlock)> Being held down Reset peak hold function. <Instantaneous flow rate display> CH data display Being held down When CH selected window operation[] < setting value > Displays in turn Operation wave form < setting value > Separate Press M key and simultaneously when Instantaneous flow (Integrated flow) is displayed. Peak hold appears on the display. Peak value is displayed while key is pressed Bottom value is displayed while key is pressed. Peak hold is canceled when M key is pressed. <Bottom value displayed> When Instantaneous flow (Integrated flow) is displayed, CH setting value is displayed while key is displayed. CH setting value is displayed while key is pressed. Being held down CH data display When CH selected external input of integrated reset. Separate Press key and key simultaneously and press M key for one second at the same time, [Loc] appears and enters key lock condition. Press and M simultaneously for sec. <Instantaneous flow rate display (key lock)> Key unlock At key lock condition, press and M <Instantaneous flow rate display (key lock)> simultaneously for 3 seconds, [unl] appears and key lock is canceled. (confirmed) <Integrated flow display> ml Press simultaneously for sec. Integration reset Integration is reset when and keysarehelddownforsec. ml Press and M simultaneously for 3sec. <Instantaneous flow rate display (key unlock)> Note: Integration is reset with the external input. See auto reference function. Note: Integration is also reset or Integrating function display setting is keeping when power is turned. Note: Keys are unlocked when the controller is shipped. Lock keys if necessary. The key lock/unlock state is held even if power is turned. While key lock, all the operations are not accepted excluding the key lock release operation. While key lock, If the key is operated, it becomes a Loc display.

5 5-.Standard setting mode <How to enter to standard setting mode> <Instantaneous flow rate display> Press for 3 sec.. (The display blinks.) Press M key for 3 seconds when Instantaneous flow is displayed. Standard setting mode appears. Press M key to change mode and confirm mode by pressing key. <Setting of switch output function> Switch output CH operation mode change Choose CHoperation mode. Press or key and choose desirable operation mode and press M key to confirm. <Switch output > <Window operation []> <Window operation []> <Switch output> (Confirmed) To switch output <Integrated pulse> <Hysteresis operation []> <Forcible output function> (Confirmed) <Integrated output []> <Integrated output []> <Hysteresis operation []> To forcible output <0 point adjustment> (Confirmed) (Confirmed) To 0 point adjustment CH / data setting (window operation is chosen) < value set> < value set> <Switch output> Having pieces of switch output, 7 operation patterns and stop of operation can be set. Operation pattern Description Operation waveform Window operation[] The switch turns (Range inside ) when the level is within the designated flow rate range. Histeresis set in fixed value separately Window operation[] (Range outside ) Hysteresis operation[] ( rate small side ) Hysteresis operation[] ( rate large side ) Integrated output[] ( when higher than set integration) Integrated output[] ( when higher than set integration) The switch turns when the level is not within the designated flow rate range. when lower than set point. Hysteresis can be arbitrarily set. when higher than set point. Hysteresis can be arbitrarily set. The switch turns at the set integrated flow. The switch turns at the set integrated flow. Lower limit Upper limit Histeresis set in fixed value separately Lower limit Lower limit Lower limit Set point Set point Upper limit Upper limit Upper limit Integ.. flow Integ. flow Count UP Count down < Switch output forcible mode> Forcible output <0 point adjustment mode> 0 point adjustment Set switch / data. Press key to count UP and key for count DOWN and press M key for confirmation.. Lower limit cannot be set beyond upper limit. Please set upper limit first. When flow direction is one way, the minus setting cannot be conducted.. (CH confirmed) CH operation mode change (Set same as CH) (Operation mode confirmed ) CH / data setting (Set same as CH) (CH confirmed) Switch is forcibly set in mode. CH is on while key is pressed. CH is on while key is pressed.(ch is canceled when e by external input is used. To instantaneous flow set Press simultaneously (adjusted value reading) Adjustment value display Integrated pulse The integrated pulse is output during integration. See specifications for details on the pulse output rate. Switch output Switch output Note: Hysteresis is provided on upper and lower limit of window operation automatically. The hysteresis can be fixed in 8 steps. Refer to <Hysteresis fixed value selection> in <Detailed setting mode>. 40msec Pulse rate Integ. flow -4- To instantaneous flow (confirm) Adjust 0 point gap.. (Be sure to make flow rate 0 and take in offset value.) Press and at the same time and take in set value and confirm by M key. Note ) If the gap is more than ± 0%, [E 0] appears and offset value is cleared. Offset value is arithmetic value. Therefore, it differs from actual flow rate value.

6 5-3.Detailed setting mode <How to enter to detailed setting mode> <Instantaneous flow rate display> At instantaneous flow rate display, press M key for 8 sec. to enter to detailed setting mode. Press M key to change mode and press key to confirm. Press for 8 sec. (Indication blinks Press continuously while CH display) < direction selection(bi- directional type)> (Confirmed) <Auto reference function> (Confirmed) To flow direction To auto reference (Confirmed) <Response time setting> To response time (Confirmed) <Display speed selection> To display speed (Confirmed) <Sub-display selection> < direction selection (only bi-directional type)> Only bi-directional type, flow direction can be switched. direction LCD indication Analog output feature When reverse flow, - is <Bi-directional> (V) (ma) indicated 5 0 <One-direction (Forward)> <One-direction (Reverse)> Setting of flow direction direction Setting of flow direction The arrow changes according to flow direction The arrow indication for forward direction The arrow indication for reverse direction Analog output Analog output Analog output 3 4 -F.S. 0 F.S. () (V) (ma) F.S. () (V) (ma) F.S. () Determine flow direction.. Press key or key to select flow direction. < One-direction (Forward) <One-direction (Reverse)> <Bi-direction> To sub-display (Confirmed) <Displayed color selection> To displayed color (Confirmed) <Hysteresis fixed value selection> To hysteresis fixed value (Confirmed) < rate unit selection> To flow rate unit (Confirmed) <Eco mode setting> To eco mode (Confirmed) <Reset setting> <Model number display> (Confirmed) To reset To model number display -5- (Confirmed) To instantaneous flow rate Note )Note: When flow direction is changed, other setting value as follow is cleared. Please make sure to set flow direction first. Switch setting/zero adjusting value/integrated flow value/external input mode <Auto reference function> When CH function selected external input of auto reference, setting value of switch output can be taken by external input or key operation.the setting value can be automatically changed when workpiece is changed for example. The set point takes the flow rate when external input is turned on (or key operation). When auto reference is executed, the switch setting of CH becomes invalid. Input point point points Operation Description mode More than input when higher than input value point. Set-point=input point More than input when higher than input value point. Set-point=input point More than when higher than centre center value of value of two input points two points Set-point= (input point+input point)/ More than center value Of two pints Within two points value Within two points value when higher than centre value of two input points Set-point= (input point+input point)/ when flow rate level is within two input points. Setpoint=input point Setpoint=input point when flow rate level is within two input points. Setpoint=input point Setpoint=input point Operation waveform Input point Input point Input point Input point Input point Input pioint Input point Input point F.low Input point Input pioint

7 Setting of auto reference Auto reference Setting of CH function <Auto reference> Press or key to select CH function. <Switch output> < External input of integrated reset> < Setting of response time> Response time Setting of response time (confirmed) Press or key to select response time. Indication Response time SP 50msec SP 80msec SP 3 0msec SP 4 00msec SP 5 400msec SP 6 800msec SP 7 500msec Note ) The response time is only reference use. The actual response time differs by the piping. Condition. (confirmed) (confirmed) (confirmed) To setting of CH switch output Reference method selection (Key operation / External input) <Key operation> <External input> <Setting of display speed> Display speed Setting of display speed Press or key to select display speed. <50msec> <500msec> <000msec> (confirmed) Input point selection < point > < points> (confirmed) (confirmed) Operation mode selection (-point) <more than input value > <more than input value > (confirmed) Operation mode selection (-points) <More than center value of two points > <More than center value of two points > > <Setting of sub-display> Sub-display Setting of sub-display Press or key to select sub-display. < direction> < rate unit> <Working fluid> (confirmed) <Within two points value <Within two points value To instantaneous flow rate (confirmed) How to take set point by key operation point input : The set point takes the flow rate when press key for sec. point input : The upper limit takes the flow rate when press key for sec. The lower limit takes the flow rate when press key for sec. After taking, the set point is displayed. How to take set point by external input point input : The set point takes the flow rate when external input is turned on (keep approx. 40msec.). points input : The set point takes the flow rate when external input is turned on (keep approx. 40msec.). The big and small relations between latest two points are compared. The upper limit and lower limit are distinguished automatically. (e.g.) Input point(m) Lower limit(m) Upper limit(m) Initial value 0 0 st nd rd th th The initial point is zero for upper and lower limit. After taking, the set point is displayed. Also the pulse(/) is output from CH for the taking confirmation. The set point value is cleared if power is turned. <Setting of display color> Display color Setting of display color <Red when > (Green when ) <Green when > (Red when ) (confirmed) Main display shows the state of CH. Depending on CH, CH switch condition, the display color of main display and sub-display changes. Press or key to select display color. <Always red> Sub display shows the state of CH <Always Green> -6-

8 <Hysteresis fixed value selection> Hysteresis fixed value Hysteresis fixed value selection When window operation or auto reference is selected. Press or key to select hysteresis fixed value. <Model number display> Model number display Conduct model number display and setting value display Model number display <Model number> <Full scale flow rate> < rate unit & flow direction> <Approx. %F.S.> <Approx. %F.S> <Approx. 8%F.S.> <Working fluid> Ai : Air,N <Switch output> N : NPN output P : PNP output <0 point adjustment value>. (Confiremd) <Setting of flow rate unit> rate unit Press or key to select flow rate unit. Setting of flow rate unit <ANR:0 atmospheric pressure conversion> <NOR:0 atmospheric pressure conversion>. (Confiremd) <Setting of Eco mode> Eco mode Setting of Eco mode <Eco mode >. (Confirmed) Approx. minute later < Reset to the initial setting> Note: NOR display is calculation value. At factory shipment, the adjustment and inspection is done at ANR condition. Press or key to select eco mode. <Eco mode > Eco mode : If any key is not carried out for approx. min., the display is turned off and L appears. Press any key to show the indication. Reset Reset setting <Reset is not executed>. (Confirmed) Setting at shipping out of factory Item Switch out put Zero adjustment value Integrating flow rate value direction (bi-directional type only) Auto reference (CH setting) Response time Display speed Sub-display Displayed color Hysteresis rate unit Eco mode Press or key to select reset setting. <Reset is executed> Setting at shipping out of factory Zero Zero Bi-directional type: Bi-direction One-directional type: One-direction Switch output SP(50msec) 50msec direction display Red when. Green when. %FS ANR L 6Troubleshooting <Error displays and corrective action> Error indication Cause Corrective action Switch output indicator is blinking (No switch output) <Troubleshooting> The flow rate is not reset within the rating at zero adjusting An error occurred during EEPROM reading or writing. An error occurred during memory reading or writing. Reading exceeds the upper limit of detection range. Sensor chip is broken Reading exceeds the lower limit of detection range. Sensor chip is broken Switch output over current protection circuit is activated Please check that fluid doesn t flow at the time of zero adjustment setting. Turn power again.. If it does not return to normal condition, please contact nearest PISCO sales office. Turn power again.. If it does not return to normal condition, please contact nearest PISCO sales office. Reduce the instantaneous flow within the flow range. Turn power again.. If it does not return to normal condition, please contact nearest PISCO sales office. Increase the instantaneous flow within the flow range. Turn power again.. If it does not return to normal condition, please contact nearest PISCO sales office. Check whether load current exceeds the rating, correctly connect the controller, and turn power again. Trouble Cause Corrective action No flow display (No analog output) display remains 0. (Analog output remains V or 3V) display does not reach 0. (Analog output does not make V or 3V) Analog output is not within standard value display is not stable. (Analog output is not stable. Output is chattering.) It doesn t move at power supply on by abnormal display. Breakage of wire. Wrong connection of power source. Malfunction caused by noise. Output circuit is broken. FUS0 is broken path clogged by foreign matter. Leakage Foreign matter sticking to sensor chip. Malfunction caused by noise. Sensor chip is broken. Foreign matter sticking to sensor chip. Malfunction caused by noise. Pulsation of air Fault in power source (not enough voltage/capacity) Malfunction caused by noise. It turned on power with the button had been pushed. Recheck/repair external wiring. Connect the rated power source correctly. Keep FUS0 main body and cable away from noise source. Replace FUS0 Replace FUS0 Remove foreign matter and install filter at primary side of FUS0. Check and correct piping Replace FUS0. Keep FUS0 main body and cable away from the noise source. Replace FUS0. Replace FUS0 Keep FUS0 main body and cable away from the noise source. Reduce pulsation by installing tank, etc. Change the response time. Change the display speed. Increase the hysteresis. Supply rated voltage. Provide power source with enough capacity. Keep FUS0 main body and cable away from noise source. The power supply is put again without pushing the button. -7-

9 7Specifications Descriptions Connection size Working conditions Accuracy Output Install rate display Note, Integrating function Note)3,7 Full scale flow rate note) φ4 quick fitting 6 φ6 quick fitting 8 φ8 quick fitting 0 φ0quick fitting Type of display 4 digits+ 4 digits colors LCD rate range F R 500 m m 000 m m Display resolution m Display range mL L L L Display resolution ml 0.0L 0.L L Integrating pulse output rate 5mL 0mL 0.0L 0.05L 0.L 0.L 0.5L L L Working fluid Note) 4 Clean air(jis B ) Compressed air(jis B ) N gas Maximum working pressure 0.7MPa Minimum working pressure -0.09MPa Withstanding pressure MPa Ambient temperature / humidity 50, 90%RH or less Working fluid temperature 50 (No freezing ) Accuracy assurance range 300%F.S. Linearity (display / analog output) ±3%F.S. or less (5, atmospheric pressure) Pressure characteristics ±5%F.S. or less ( Mpa,5, atmospheric pressure criteria) Temperature characteristics ±0.%F.S./ 以下 (5 to 35 C, 5 C criteria) Repeatability (Repeat accuracy) ±%F.S. or less Response time Note)5 50ms or less N points (NPN open collector output, 50mA or less, voltage drop.4v or less) Switch output P points (PNP open collector output, 50mA or less, voltage drop.4v or less) V point ( to 5V voltage output and connected load impedance 50kΩ and over) Analog output A point (4 to 0mA current output and connected load impedance 300Ω or less) V DC-4V (0.86.4V) Power supply voltage Note)6 A DC4V (.66.4V) Current consumption Note)8 50mA or less Lead wire Φ3.7 AWG6 equivalent 5 cores(connector),outside diameter of insulator is Φ.0 Functions rate display, flow rate display-peak hold, switch output and analog output Installation attitude Both vertical and horizontal Strait piping section Not required Protective structure IEC standards IP40 Power supply and switch output reverse connection protections, and switch output Protective circuit Note)9 load short-circuit protection EMC instruction Acceptable goods Note: Converted to volumetric flow at 0 C and atmospheric pressure (0kPa) Note: late display is only the read within rough±%f.s. Therefore, the value differs from accuracy assurance range. Note3: Integrated flow display is reference value. Note4: When using compressed air, use clean air complying with JIS B 839-:003 class over.. to.6.. Compressed air from the compressor contains drainage (water, oxidized oil, foreign matter, etc.). Install a filter(filtration rating:5μm), air dryer(minimum pressure dew point 0 or less) and oil mist filter(maximum oil concentration 0.mg/m 3 ) on the primary side of the product to maintain product function. When using for purposes other than compressed air, use dry gas that does not contain corrosive elements such as chlorine, sulfur or acids, and clean gas that does not contain dust or oil mist. Note5: The response time can be selected from 50ms to 500ms (7 steps). Note6:Power supply specification vary depending on voltage output type and current output type. Note7: Integrated flow value is reset by turning power off. Note8: Current consumption is characteristics 4VDC and no load. It is changed by load. Please note it. Note9: This product s protective circuit is effective only for specific incorrect connections and load short-circuits. It does not necessarily provide protection for all incorrect connections. -8-

10 8Dimensions sensor (No needle valve ) Model:FUS sensor (Built-in needle valve) Model:FUS N (Through) (Through) Depth 5 Outer dimensions of fittings and other dimesnions(l H H H3 H4) Depth 5 Option parts outer dimensions Model:FUS0-B Model:FUS0-C5 Max. 30 Connector cover (Material : EPDM) Halogen free electric wire Half stripped wire Heat contracting tube Model L dimesnion FUS0-C5 040±0 FUS0-C ±0 Model:FUS0-P Panel cutting dimension < Single mount > Model :FUS0-PN Panel cutting dimension <Single mount> 4-MAX R 4-MAX R -fixing screw (M3X0.5) (Tightening torque 0.06N.m) Panel holder cover Panel Stopper <Sticking mount> 4-MAX R -fixing screw (M3X0.5) (Tightening torque 0.06N.m) Panel holder cover Panel Stopper <Sticking mount> 4-MAX R Panel Holder Panel Holder Each part (H H) dimension with fittings φ4 φ6 φ8 φ0 H H Thickness of the panel that can be installed :0.8-6mm. Each part (H H) dimension with fittings φ4 φ6 φ8 φ0 H H Thickness of the panel that can be installed :0.8-6mm.

11 9How to order FUS0 -N V - F B N Output type Analog output type 3 direction 4 rate range (full scale flow rate) N Integrated indicator type V Voltage output(-5v) 500 m 00 0 Switch output(npn): points F Bi-directional 005 P Analog output: point A Current output(4-0ma) R One-directional Integrated indicator type 0 00 Switch output(pnp): points 00 Analog output: point Port size 6Cable 7Bracket 8 Needle Valve 4 Quick fitting φ4 Blank None Blank None Blank None 6 Quick fittingφ6 m B With bracket N Built in needle valve 8 Quick fittingφ8 3 3m P Panel mount 0 Quick fittingφ0 Kit set Discrete option model FUS0 - B Option B C5 C53 P PN Bracket Connecter cable m Connecter cable 3m Panel mount kit set (for No needle valve type) Panel mount kit set (for built in needle valve) NIH PISCO CO., Ltd MINAMIMINOWA, KAMIINA, NAGANO-PREF., JAPAN Issued:0.6. TEL :+8-(0) FAX: :+8-(0) intl@pisco.co.jp We reserve the right to change dimensions, specifications and design without notice. -0-

INSTRUCTION MANUAL SMALL SIZE FLOW SENSOR RAPIFLOWR

INSTRUCTION MANUAL SMALL SIZE FLOW SENSOR RAPIFLOWR SM-385853-A INSTRUCTION MANUAL SMALL SIZE FLOW SENSOR RAPIFLOWR FSM2 Series Please read this instruction manual carefully before using this product, particularly the section describing safety. Retain this

More information

Small size flow sensor

Small size flow sensor Small size flow sensor FSM2 Sensors / flow sensor Refrigerating type dryer Desiccant type dryer High polymer membrane type dryer Air filter Auto. drain / others F.R.L. (Module unit) F.R.L. (Separate) Compact

More information

Flow Sensor FUS20. Suction lift verification of small workpiece, which is hard to detect bypressure sensor, or flow management is possible.

Flow Sensor FUS20. Suction lift verification of small workpiece, which is hard to detect bypressure sensor, or flow management is possible. No, IXPN E01-01E Flow Sensor FUS20 Suction lift verification of small workpiece, which is hard to detect bypressure sensor, or flow management is possible. 2011 NEW PRODUCTS Characteristics Built-in needle

More information

Compact Flow Rate Sensor. RAPIFLOW FSM3 Series Resin Body Type. Diversified High Performance. High performance. User-friendly. Compatible CC-1235A 1

Compact Flow Rate Sensor. RAPIFLOW FSM3 Series Resin Body Type. Diversified High Performance. High performance. User-friendly. Compatible CC-1235A 1 Compact Flow Rate Sensor RAPIFLOW Resin Body Type Diversified High Performance High performance User-friendly Compatible CC-1235A 1 Diversified Five types of gases can be measured with just one unit Gas

More information

Related vacuum products

Related vacuum products Vacuum component C O N T E N T S variation 420 Position locking valve () 422 Compact vacuum regulator () 426 Vacuum break unit () 436 Vacuum filter large volume union type (VSFB) 440 Compact vacuum filter

More information

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa 5.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator X Series This product is only for blowing gas. This product does not have sufficient pressure control for other applications (driving,

More information

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE High Precision, 2-color Display Digital Pressure Switch Series SE30/ISE30 SE ISE PSE I SE3 PS I SE 1 2 SP ISA2 IS SM PF2 IF Data With One-touch fittings are newly introduced. Straight type Elbow type 16-2-1

More information

2-Color Display High-Precision Digital Pressure Switch

2-Color Display High-Precision Digital Pressure Switch 2-Color Display High-Precision Digital Pressure Switch Settings can be copied to up to 1 slave sensors at once. The settings of the master sensor can be copied to the slave sensors. Reduced setting efforts

More information

Digital Flow Switch (Integrated display type)

Digital Flow Switch (Integrated display type) PRODUCT NAME Digital Flow Switch (Integrated display type) MODEL / Series / Product Number PF2A7##H Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts

More information

2-Color Display High-Precision Digital Pressure Switch

2-Color Display High-Precision Digital Pressure Switch 2-Color Display High-Precision Digital Pressure Switch Series ZSE3/ISE3 2-color digital display allows you to choose the setting according to your application requirements. 4 different display settings

More information

Operating Instructions Vaccon VDS-1000 Solid State Combination Vacuum Switch/Sensor w/ Digital Display

Operating Instructions Vaccon VDS-1000 Solid State Combination Vacuum Switch/Sensor w/ Digital Display Operating Instructions Vaccon VDS-1000 Solid State Combination Vacuum Switch/Sensor w/ Digital Display Installation The VDS-1000 combines either two (2) low voltage, high side or low side, switched outputs

More information

Digital Flow Switch (Integrated display type)

Digital Flow Switch (Integrated display type) PRODUCT NAME Digital Flow Switch (Integrated display type) MODEL / Series / Product Number PF2A7## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts

More information

2-Color Display High-Precision Digital Pressure Switch Series ZSE40A(F)/ISE40A

2-Color Display High-Precision Digital Pressure Switch Series ZSE40A(F)/ISE40A 2-Color Display High-Precision Digital Pressure Switch Series ZSEA(F)/ISEA New M8 connector type RoHS IP65 Applicable fluid Air, Non-corrosive gas, Non-flammable gas Can copy to up to 10 switches simultaneously.

More information

Flow sensor for compressed air

Flow sensor for compressed air for compressed air PF-F/PFU (display integrated type ) Sensor / Overview Compressed air consumption could reach 1/5 of energy used in manufacturing plant. Controlling air is very important for energy saving.

More information

Vacuum pump system type

Vacuum pump system type type VS*P Vacuum component C O N T E N T S Series variation 166 20 mm width universal type (/M) 168 10.5 mm width universal type (/M) 184 31.5 mm width discrete type (VSQP) 214 11 mm pitch manifold dedicated

More information

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type (ISE75H) 2-color digital. Functions

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type (ISE75H) 2-color digital. Functions Series ISE70/75/75H NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. For General Fluids For Air 2-Color Display (Green/Red) Selectable from four patterns ON Red Green Red Green

More information

Flow sensor for compressed air

Flow sensor for compressed air for compressed air PFD/PFK (display separate type ) Sensor / CONTENTS Product introduction 1432 Applications 1434 Safety precautions 1435 (PFD)display separate type 1440 Tester kit (PFK) 1446 Electric

More information

Small size flow controller

Small size flow controller size FCM Sensors / CONTENTS Product introduction 1366 Applications 1368 Series variation 1369 Safety precautions 1370 FCM 1376 Technical data 1385 Functional explanation, operation 1387 Custom 1403 sensor

More information

2-Color Display Digital Pressure Switch. NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. Rated Pressure Metal Body Type

2-Color Display Digital Pressure Switch. NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. Rated Pressure Metal Body Type Series ISE70/75/75H New NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. For General Fluids For Air 2-Color Display (Green/Red) Selectable from four patterns ON Red Green Red

More information

Series 10-ZSE40A(F)/10-ISE40A

Series 10-ZSE40A(F)/10-ISE40A Series 10-ZSEA(F)/10-ISEA RoHS 2-Color Display High Precision Digital Pressure Switch How to Order For positive pressure Clean series For vacuum/ compound pressure 01 N01 W1 10 Rated pressure range ISEA

More information

3-step setting. 2-Color Display High-Precision Digital Pressure Switch. Series ZSE30A(F)/ISE30A. Added vacuum range.

3-step setting. 2-Color Display High-Precision Digital Pressure Switch. Series ZSE30A(F)/ISE30A. Added vacuum range. 2-Color Display High-Precision Digital Pressure Switch Series ZSE3A(F)/ISE3A RoHS Can copy to up to 1 switches simultaneously. The settings of the master sensor can be copied to the slave sensors. Reducing

More information

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch 25 M ISE30 01 ZSE M. How to Order. For positive pressure

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch 25 M ISE30 01 ZSE M. How to Order. For positive pressure High Precision, Series SE30/ISE30 How Order Option 1 Without lead wire Lead wire with connecr (Lead wire length: 2 m) L For positive pressure For vacuum/low pressure ISE30 01 SE30 01 25 M 25 M 01 R 1/8

More information

Sensor specifications Model no.

Sensor specifications Model no. Miniature size Analog output type/switch output type FSM-V Series (air/nitrogen gas) Flow rate range:.5,.1,.5, 1, 5, /min. Pressure Sensor specifications Model no. Flow rate range ( /min) Note -.5 to +.5

More information

Low Differential Pressure Sensor ±1% F.S.

Low Differential Pressure Sensor ±1% F.S. CAT.ES100-49 A Low Differential Pressure Sensor Rated differential pressure range: 0 to 2 kpa Accuracy: ±1% F.S. LED display to confirm energization Series PSE550 Proof pressure: 65kPa Output: 1 to 5VDC

More information

DPS280 / DVS280 Series

DPS280 / DVS280 Series 1 2 3 4 5 6 7 8 Do not use corrosive or flammable gases or liquid with this product. Please use within the rated pressure range. Do not apply pressure beyond recommended maximum pressure, permanent damage

More information

2-Colour Display Type High-Precision Digital Pressure Switch Series ZSE30/ISE30 How to Order Option 1 Without lead wire Nil Lead wire with connector (Lead wire length: 2m) L For positive pressure For vacuum/low

More information

Digital Flow Switch (Remote type monitor unit)

Digital Flow Switch (Remote type monitor unit) PRODUCT NAME Digital Flow Switch (Remote type monitor unit) MODEL / Series / Product Number PF2A3## PF2W3## PF2D3## Table of Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of

More information

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type. MPa MPa (ISE75H) 2-color digital. Functions

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type. MPa MPa (ISE75H) 2-color digital. Functions -Color Display Digital Pressure Switch /75/75H Series NPN/PNP open collector outputs added. Zero-cut off display function added. For General Fluids For Air Rated Pressure Metal Body Type 0 5 (E75) () -Color

More information

10 switches simultaneously. The settings of the master sensor (source of copy) can be copied to the slave sensors. Reducing setting labor

10 switches simultaneously. The settings of the master sensor (source of copy) can be copied to the slave sensors. Reducing setting labor 2-Color Display High-Precision Digital Pressure Switch ZSE ISE RoHS ZSE ISE IP65 ZSE40 ISE40 M8 connector type ZSE10 ISE10 ISE70 ZSE80 ISE80 PS ISA3 ISA2 ISE35 Applicable Air, Non-corrosive gas, Non-flammable

More information

Flowsensor for compressed air

Flowsensor for compressed air TOTAL OUT1 ERROR Nkm 3 Nm3 N Nm 3/min Flowsensor for compressed air Ideal for plant energy-saving control This sensor is ideal for controlling and checking the flow of compressed air at plants and equipment

More information

2-Color Display Digital Pressure Switch

2-Color Display Digital Pressure Switch -Color Display Digital Pressure Switch Series ZSE80(F)/ISE80(H) Stainless diaphragm Oil-free (Single-layer diaphragm structure) Sensor parts: Stainless steel 630 Fitting parts: Stainless steel 304 The

More information

Clean Air Module. Digital flow switch Regulator ON/OFF valve Restrictor Filter

Clean Air Module. Digital flow switch Regulator ON/OFF valve Restrictor Filter Clean Air Module Series Digital flow switch Regulator ON/OFF valve Restrictor Filter Modularizes clean equipment (Reduced piping man-hours/space-saving). Easily obtains clean air. Built-in one-touch fitting

More information

Model Pressure range ON/OFF output Linear output

Model Pressure range ON/OFF output Linear output Digital Sensor Sensor with Easy-to-Read LED Display status can be checked at a glance from the red digital pressure value and analog bar displays. Measurement pressure is averaged by the chattering prevention

More information

* E8MS-N1 is only 1-channel pressure sensor controller. E80-C2 can be used. For more details, please refer to E80 catalogue.

* E8MS-N1 is only 1-channel pressure sensor controller. E80-C2 can be used. For more details, please refer to E80 catalogue. Authorised Distributors:- ASH & ALAIN INDIA PVT LTD S-, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-(India) Tel : -7977 Fax : -7977 E-mail : sales@ashalain.com Sensor Four-Input-Channel Sensor

More information

Digital pressure switch for energy-saving control ejector

Digital pressure switch for energy-saving control ejector PRODUCT NAME Digital pressure switch for energy-saving control ejector MODEL / Series / Product Number ZK2-ZSV####-A Table of Contents Safety Instructions 2 Model indication and How to order 9 Summary

More information

Digital Flow Switch (Sensor Part) Operation Manual

Digital Flow Switch (Sensor Part) Operation Manual Digital Flow Switch (Sensor Part) Operation Manual For Air PF2A 50/5 Series PF2A 5/ 52/ 55 Series For Water PF2W /520/50 Series PF2W 5 Series For Water (High Temperature Fluid Type) PF2W T/520T/50T Series

More information

FLOW METERS. 90 left. 90 right. Sensor. Rotary display. Models. FA Series

FLOW METERS. 90 left. 90 right. Sensor. Rotary display. Models. FA Series FLOW METERS FA Series Sensor A thermal mass sensor enables accurate measurement even in the case of gas temperature and pressure fluctuations. Sensor structure The FA Series measure flow rates using heat

More information

Unit specifications. Nil. Option 1. Power supply/output connection cable. Option 2

Unit specifications. Nil. Option 1. Power supply/output connection cable. Option 2 Series -PSE3 RoHS Remote Type 2-Color Display Digital Pressure Sensor Controller How to Order 2 3 4 5 Nil Options/Part No. L Input/Output specifications NPN2 output to 5 V output NPN2 output 4 to 2 m output

More information

2-Color Display Digital Pressure Switch

2-Color Display Digital Pressure Switch -Color Display Digital Pressure Switch Series ZSE80(F)/ISE80(H) Stainless diaphragm Oil-free (Single-layer diaphragm structure) Sensor parts: Stainless steel 630 Fitting parts: Stainless steel 304 The

More information

2-colour display. Digital Pressure Switch. Stainless diaphragm Oil-free (Single-layer diaphragm structure) IP65 compliant

2-colour display. Digital Pressure Switch. Stainless diaphragm Oil-free (Single-layer diaphragm structure) IP65 compliant -Colour Display Digital Pressure Switch Stainless diaphragm Oil-free (Single-layer diaphragm structure) Sensor parts: Stainless steel 6 Fitting parts: Stainless steel 4 The sensor and fitting parts can

More information

Construction diagram Semiconductor transducer Silicone oil. Stainless steel SUS316 pressure port Hastelloy C diaphragm.

Construction diagram Semiconductor transducer Silicone oil. Stainless steel SUS316 pressure port Hastelloy C diaphragm. SERIES LED Display Anti-corrosive Digital ure Sensor DP3 ure Measurement of Corrosive Gases and Liquids Possible! Marked Conforming to EMC Directive Superior Anti-corrosive Hastelloy C Diaphragm and Stainless

More information

ISE6B. Series ZSE6B. Digital Pressure Switch. With Backlight. (For vacuum) (For positive pressure) For General Purpose Fluids

ISE6B. Series ZSE6B. Digital Pressure Switch. With Backlight. (For vacuum) (For positive pressure) For General Purpose Fluids Leakage rating: 1 X 10-9 atm cc/s With Backlight Digital Pressure Switch Series ZSE6B (For vacuum) ISE6B (For positive pressure) Sensor and fitting section are electron beam welded. 2 kinds of metal gasket

More information

Pressure Switch with Super slim LED Display

Pressure Switch with Super slim LED Display Pressure Switch with Super slim LED Display 796 Super slim and light weight pressure sensor with a LED display. width: 8.2mm, height: 4.mm, length: 62.2mm, weight: 17g Indicator font size on the LED display

More information

Pressure Transmitter

Pressure Transmitter Specifications/Instructions Pressure Transmitter General Model PY7100A pressure transmitter is a small pressure transmitter using a semiconductor strain gauge. It detects the pressure of chilled/hot water,

More information

Helical Flow. HF-GC/GP Series

Helical Flow. HF-GC/GP Series Helical Flow A Helical Flow Type of Screw Revolution Instruction Manual for HF-GC/GP Series (SC and MP/MC Series incld. ) Caution Before use, please read this Instruction Manual thoroughly for safe operation.

More information

DPC-100 Series INSTRUCTION MANUAL WIRING I/O CIRCUIT DIAGRAMS PART DESCRIPTION

DPC-100 Series INSTRUCTION MANUAL WIRING I/O CIRCUIT DIAGRAMS PART DESCRIPTION Sensor INSTRUCTI MANUAL Head Separated Digital Sensor Controller DPC-1 Series MJE-DPC1 No.7-98V Thank you very much for using SUNX products. Please read this Instruction Manual carefully and thoroughly

More information

Digital Flow Switch PFM7##

Digital Flow Switch PFM7## PRODUCT NAME Digital Flow Switch MODEL / Series / Product Number PFM7## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts 13 Definition and terminology

More information

Model Pressure range ON/OFF output Linear output

Model Pressure range ON/OFF output Linear output Authorised Distributors:- ASH & ALAIN INDIA PV LD S-1, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-112(India) el : 11-43797575 Fax : 11-43797574 E-mail : sales@ashalain.com Digital Sensor Sensor

More information

9.8 mm. Digital Pressure Switch. 3-step setting. RoHScompliant. Series ZSE10(F)/ISE10. Vertical mounting space reduced to approx.! Reduced in depth!

9.8 mm. Digital Pressure Switch. 3-step setting. RoHScompliant. Series ZSE10(F)/ISE10. Vertical mounting space reduced to approx.! Reduced in depth! Digital Pressure Switch Series ZSE1(F)/ISE1 Low profile 26.1mm 9.8 mm 13.5 mm 53.4 mm Reduced in depth! (Actual size) RoHScompliant Vertical mounting space reduced to approx.! 1 2 Position Detection Switch

More information

ITVH Series. 3.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator. 3.0 MPa 0.2 to 2.0 MPa. 3 W or less L /min (ANR)*

ITVH Series. 3.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator. 3.0 MPa 0.2 to 2.0 MPa. 3 W or less L /min (ANR)* 3.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator ITVH Series ARJ RoHS Maximum supply pressure Set pressure range Stability 3.0 MPa 0.2 to 2.0 MPa ARX AMR Stepless control of air

More information

PG-30 PRESSURE GAUGES P G R - N FEATURES MODEL NUMBER DESIGNATION

PG-30 PRESSURE GAUGES P G R - N FEATURES MODEL NUMBER DESIGNATION marking Compatible with EMC directive INTERNAL STRUCTURE 5 1 2 6 4 3 Part name Material FEATURES 1 Pressure sensor P-2000 Compact and lightweight general-purpose pressure gauges Innovative general-purpose

More information

2-Color Display Digital Flow Switch

2-Color Display Digital Flow Switch -Color Display Digital Flow Switch Series Flow rate range:, 5, 5, l/min. Minimum unit setting:. l/min. (. l/min when the flow rate range is 5, 5, l/min.) Repeatability: ±%F.S. or less Grease-free Flow

More information

Differential Pressure Transmitter

Differential Pressure Transmitter Specifications/Instructions Differential Pressure Transmitter General Model PY9000D is a differential pressure transmitter that uses a ceramic cantilever sensor. Deflection of the ceramic cantilever caused

More information

INSTRUCTION MANUAL DIGITAL

INSTRUCTION MANUAL DIGITAL page 1 / 38 INSTRUCTION MANUAL DIGITAL Electro-pneumatic Regulator ER200 Series ANALOG INPUT TYPE ER2xx-x0/1/2xx PARALLEL INPUT TYPE ER2xx-xPxx Please read this instruction manual carefully before using

More information

Pressure sensor with built-in amplification and temperature compensation circuit

Pressure sensor with built-in amplification and temperature compensation circuit sensor with built-in amplification and temperature compensation circuit PS-A PRESSURE SENSOR (built-in amplification and temperature compensating circuit) NEW FEATURES 1. Contains built-in amplification

More information

Differential Pressure Sensor

Differential Pressure Sensor Differential Pressure Sensor "Cube" Type Differential Pressure Sensor with LED Display Offers High Precision Sensing 31 (1.) x 3 (1.18) x 3 (1.18) mm compact-cube style saves mounting space Easy-to-read

More information

2-Color Display Digital Pressure Switch

2-Color Display Digital Pressure Switch -Color Display Digital Pressure Switch (F)/(H) Series Stainless diaphragm Oil-free (Single-layer diaphragm structure) Sensor unit: Stainless steel 630 Fitting parts: Stainless steel 304 The sensor unit

More information

Digital display Pressure range ON/OFF output Linear output Model

Digital display Pressure range ON/OFF output Linear output Model Slim Digital Pressure Sensor E8CB/ CSM_E8CB DS_E 1 with Built-in Microcomputer and Digital Display Withstands a of 9 kpa and highly reliable. Incorporates a two-turn adjuster ensuring easy setting. Be

More information

ION JET NOZZLE NIH-55

ION JET NOZZLE NIH-55 ION JET NOZZLE NIH-55 INSTRUCTION MANUAL - Read this instruction manual and make sure you thoroughly understand its contents before attempting to operate, inspect or service this product. - The users and

More information

Head-separated Digital Pressure Sensor DP5 SERIES DPH SERIES

Head-separated Digital Pressure Sensor DP5 SERIES DPH SERIES 76 ORDER GUIDE DP / configuration diagram Intermediate cable s Type Vacuum pressure Positive pressure Compound pressure Appearance An intermediate cable is required to connect the controller and the sensor

More information

VSG Series Features Descriptions VSG VSG VSG Descriptions Supply valve Descriptions Vacuum filter

VSG Series Features Descriptions VSG VSG VSG Descriptions Supply valve Descriptions Vacuum filter Basic performance oriented general vacuum ejector unit Series Nozzle diameter: ø.5, ø, ø1. acuum switch and vacuum break valve, etc. are unitized, so types matching the work purpose is selectable. Features

More information

SERIES LED Display Digital Pressure Sensor. Clearly Visible LED Display with 3 1 /2 Digits

SERIES LED Display Digital Pressure Sensor. Clearly Visible LED Display with 3 1 /2 Digits SERIES LED Display Digital Pressure Sensor Complete Functionality from a Wide Model Line-up Marked Conforming to EMC Directive High Accuracy High Resolution High Speed It achieves a 2.5ms, or less, response

More information

WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB

WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB WaterMAG Electromagnetic Flowmeter for Water Applications OVERVIEW The WaterMAG is an electromagnetic flowmeter for water measurement applications based on field proven Azbil Corporation's technologies.

More information

Set value (Threshold value) Bottom value. *2 Further reduced by approx. 60% in power-saving mode (For 20 series)

Set value (Threshold value) Bottom value. *2 Further reduced by approx. 60% in power-saving mode (For 20 series) 3-Screen Display High-Precision Digital Pressure Switch New Added Variations! For general fluids IP65 2 outputs Analog output Setting is possible while checking Main screen the measured value. Sub screen

More information

Pressure Gauge. Fluid admitted Pressure indication range Accuracy Service temperature range Cap. Resin body GPC (1)

Pressure Gauge. Fluid admitted Pressure indication range Accuracy Service temperature range Cap. Resin body GPC (1) Pressure Gauge Feature The compact-size pressure gauges can be installed in small spaces. With the built-in tube fitting type, tube connection is the only necessary step before pressure indication. Graphical

More information

Super fast 1 ms Convenient intermediate cable with connector A total of 10 head variations

Super fast 1 ms Convenient intermediate cable with connector A total of 10 head variations SERIES Digital Sensor Digital Automatic sensitivity setting Auto reference With analog output /, sec. The fastest response in the industry DP DP Conforming to EMC Directive UL Recognition Super fast ms

More information

Pneumatic Drive Type Drill Bit Breakage Detection Sensor. DFM3 Series. The World's First!! Pneumatic-Drive Type. Catalog / Instruction Manual US.PAT.

Pneumatic Drive Type Drill Bit Breakage Detection Sensor. DFM3 Series. The World's First!! Pneumatic-Drive Type. Catalog / Instruction Manual US.PAT. Pneumatic Drive Type Drill Bit Breakage Detection Sensor DFM3 Series The World's First!! Pneumatic-Drive Type Catalog / Instruction Manual US.PAT. Pneumatic Drive Type Drill Bit Breakage Detection Sensors

More information

Doc. No. IZ -OML0002-B OPERATION MANUAL. Ionizer PRODUCT NAME:

Doc. No. IZ -OML0002-B OPERATION MANUAL. Ionizer PRODUCT NAME: Doc. No. IZ -OML0002-B OPERATION MANUAL PRODUCT NAME: MODEL: Ionizer IZN10 Series Read this operation manual carefully to understand before installation and operation. Pay extra attention on the clause

More information

POWER REGULATOR LD -40PSU

POWER REGULATOR LD -40PSU JZ99D4121A AMPIFIRE AMPIFIRE TYPE D-4PSU ZJ-46A ISTRUCTI MAUA Manual number JZ99D4121 Sub number A Date of preparation ov. 2 Thoroughly read this instruction manual, and then use the unit correctly. Especially,

More information

High-frequency AC Method. panasonic-electric-works.net/sunx

High-frequency AC Method. panasonic-electric-works.net/sunx 1091 PHOTO PHOTO Thin Type Ionizer High-frequency AC Method General terms and conditions... F-17 Related Information Glossary of terms... P.1401 guide... P.1075~ General precautions... P.1405 Conforming

More information

10 PSE53 0 M5. Port size. M5 x 0.8 ø6 reducer 1/4-inch reducer. the cable at the time of shipment. 10-PSE to -101 kpa

10 PSE53 0 M5. Port size. M5 x 0.8 ø6 reducer 1/4-inch reducer. the cable at the time of shipment. 10-PSE to -101 kpa Series 0-PSE50 Remote type pressure sensor How to Order Clean series 0 PSE5 0 M5 Pressure sensing range Option 0 2 High pressure [0 to MPa] Vacuum [0 to 0 kpa] Low pressure [0 to 0 kpa] Compound pressure

More information

The Multivariable Air Flow Meter

The Multivariable Air Flow Meter The Multivariable Air Flow Meter Model MVC10A/MVC10F OVERVIEW The Multivariable Mass Flow Meter model MVC10A/ MVC10F, a compact has all function necessary to measure nitrogen (N 2 ) gas, carbon dioxcide

More information

Series PSE560 Pressure Sensor For General Fluids... 90

Series PSE560 Pressure Sensor For General Fluids... 90 Table of Contents Pressure Switch Selection Guide... Electronic Pressure Switch... Mechanical Pressure... Pressure Switch Application Example... Series SE/ISE High Precision, 2-color Display Digital Pressure

More information

Series PSE100. Controller PSE10. How to Order. Controller Specifications Option. Output specifications. Mounting

Series PSE100. Controller PSE10. How to Order. Controller Specifications Option. Output specifications. Mounting Controller Series PSE100 How to Order PSE10 Output specifications 0 NPN output 1 PNP output Mounting A B Option Without cover C With cover Panel mounting Wall mounting, DIN rail Controller Specifications

More information

SERIES LED Display Digital Pressure Sensor. Clearly Visible LED Display with 3 1 /2 Digits

SERIES LED Display Digital Pressure Sensor. Clearly Visible LED Display with 3 1 /2 Digits SERIES LED Display Digital Pressure Sensor PE DP-M DP-Y DP3 High Accuracy High Resolution High Speed It achieves a 2.5ms, or less, response time at a high resolution of 1/1,000. It enables highly accurate

More information

Pattern Air Control Kit (PACK)

Pattern Air Control Kit (PACK) Instruction Sheet P/N 044445B0 WARNING: Allow only personnel with appropriate training and experience to operate or service the equipment. The use of untrained or inexperienced personnel to operate or

More information

Digital Pressure Switch

Digital Pressure Switch PRODUCT NAME Digital Pressure Switch MODEL / Series / Product Number ZSE80(F) ISE80(H) Table of Contents Safety Instructions 2 Model Indication and How to order 9 Summary of Product parts 10 Definition

More information

Vacuum Switch with LED display

Vacuum Switch with LED display Vacuum Switch with display 812 To improve visibility, an display is adopted for the vacuum switch. displays indicates set-up pressure and working pressure. Two types of vacuum switch selection: Two switch

More information

PG-30 PRESSURE GAUGES P G R - N MODEL NUMBER DESIGNATION

PG-30 PRESSURE GAUGES P G R - N MODEL NUMBER DESIGNATION INTERNAL STRUCTURE 5 1 marking Compatible with EMC directive 2 6 4 3 Part name Material 1 Pressure sensor P-2000 2 Sensor O ring NBR 3 Adaptor Aluminum Die-casting 4 Case O ring NBR 5 Case PBT (Polybutyleneterephthalate)

More information

Simple Pressure Level Setting. The threshold level is able to adjust simply. Just set the pointer suitable for the displayed pressure level.

Simple Pressure Level Setting. The threshold level is able to adjust simply. Just set the pointer suitable for the displayed pressure level. SERIES LED Bar Display Mechanical Switch is Out of Date Choose the Contemporary Pressure Sensor with LED Bar Display Marked Conforming to EMC directive Bright LED Bar Display Easy to read the pressure

More information

Digital Flow Switch (Remote type sensor unit)

Digital Flow Switch (Remote type sensor unit) PRODUCT NAME Digital Flow Switch (Remote type sensor unit) MODEL / Series / Product Number PFM5## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts 13

More information

DP5/DPH. Head Separated Digital Pressure Sensor. 1/1000 Second High-Speed Response. The advantage of the fastest response in the industry SERIES

DP5/DPH. Head Separated Digital Pressure Sensor. 1/1000 Second High-Speed Response. The advantage of the fastest response in the industry SERIES Head Separated Digital Pressure Sensor SERIES /000 Second High-Speed Response Conforming to EMC Directive UL Recognition /,000 sec. The advantage of the fastest response in the industry 55 High speed in

More information

Electro-Pneumatic Regulator Electronic Vacuum Regulator. Series Model Set pressure range Port size to 0.1MPa to 0.5MPa to 0.

Electro-Pneumatic Regulator Electronic Vacuum Regulator. Series Model Set pressure range Port size to 0.1MPa to 0.5MPa to 0. 000 Electro-Pneumatic Regulator Electronic Vacuum Regulator Series Series Model Set pressure range Port size Page Series 000 Controls air pressure steplessly in proportion to an electric signal. 0 05 to

More information

Series ITV0000. Compact Electro-pneumatic Regulator ITV N. IITV00 02 n. How to Order F.R.L. AV AU AF AR IR VEX AMR ITV IC VBA VE VY1 G PPA AL

Series ITV0000. Compact Electro-pneumatic Regulator ITV N. IITV00 02 n. How to Order F.R.L. AV AU AF AR IR VEX AMR ITV IC VBA VE VY1 G PPA AL Compact Electro-pneumatic Regulator Series For single unit and single unit for manifold Pressure range 9 Option. MPa. MPa.9 MPa kpa Option How to Order N Power supply voltage 24 VDC ±% 2 to VDC Option

More information

Digital Flow Switch for Deionized Water and Chemicals Body and sensor New PFA Tube Super PFA

Digital Flow Switch for Deionized Water and Chemicals Body and sensor New PFA Tube Super PFA CAT.ES- A for Deionized Water and Chemicals Body and sensor New PFA Tube Super PFA Three types of flow range. to l /min (PFD). to l /min (PFD). to l /min (PFD) Swept flow characteristics Tapered side seal

More information

The Multivariable Air Flow Meter

The Multivariable Air Flow Meter No. SS2-MVC200-0100 OVERVIEW The Multivariable Mass Flow Meter AIRcube, a compact has all function necessary to measure nitrogen (N 2 ) gas, carbon dioxcide (CO 2 ) gas and air. The model MVC10A/MVC10F

More information

LCD Readout Digital Pressure Switch

LCD Readout Digital Pressure Switch LCD Readout Digital Pressure Switch Series ZSE3 (For )/E3 (For Positive Pressure) For General Pneumatics The ZSE3/E3 series is to be discontinued. We recommend you consider using the Z/E10 series or the

More information

Electronic pressure switch for air

Electronic pressure switch for air pressure switch Sensors / pressure sensor Overview pressure is electrically detected, displayed and outputted. Features Various sort Wide variation is acailable from small sensor to display. CONTENTS Series

More information

Digital Pressure Switch

Digital Pressure Switch PRODUCT NAME Digital Pressure Switch MODEL / Series / Product Number ZSE10(F) ISE10 Table of Contents Safety Instructions 2 Model Indication and How to order 9 Summary of Product parts 11 Definition and

More information

Conventional specification. External Pilot air specification 0 ~ 0.7. Compact, yet keeps large capacity.» Limited space can be utilized.

Conventional specification. External Pilot air specification 0 ~ 0.7. Compact, yet keeps large capacity.» Limited space can be utilized. Compact, yet keeps large capacity.» Limited space can be utilized. Standard.» SVR 10 series takes over the functions (Valve variations) of discontinued SVA 10 series. Pneumatic Symbols 5(R) 5(R) 5(R) 5(R)

More information

CBM-105FN/FP Circuit Board

CBM-105FN/FP Circuit Board CBM-105FN/FP Circuit Board Features Adjustable acceleration and deceleration time (0 to 2.5s) Stable speed operation Manual or automatic recovery of the thermal overload device One (1) rotary switch to

More information

Electro-Pneumatic Regulator / Electronic Vacuum Regulator

Electro-Pneumatic Regulator / Electronic Vacuum Regulator Electro-Pneumatic Regulator / Electronic Vacuum Regulator Series Series Model Regulating pressure range Port size Page Series With a simplified high-density circuit board design, an extremely compact size

More information

Series ITV. Electro-pneumatic Regulator Electronic Vacuum Regulator F.R.L. AV AU AF AR IR VEX AMR ITV IC VBA VE VY1 G PPA AL

Series ITV. Electro-pneumatic Regulator Electronic Vacuum Regulator F.R.L. AV AU AF AR IR VEX AMR ITV IC VBA VE VY1 G PPA AL SMC REULATOR Electro-pneumatic Regulator Electronic Vacuum Regulator Series Series Series Model Regulating pressure range Port size With a simplified high-density circuit board design, an extremely compact

More information

Three types of flow range. 0.4 to 4 L/min (PF2D504) 1.8 to 20 L/min (PF2D520) 4.0 to 40 L/min (PF2D540) Swept flow characteristics (reference)

Three types of flow range. 0.4 to 4 L/min (PF2D504) 1.8 to 20 L/min (PF2D520) 4.0 to 40 L/min (PF2D540) Swept flow characteristics (reference) Digital Flow Switch for Deionized Water and Chemical Liquids PFD Series RoHS single controller can monitor the flow rate of different sensors. Body and New PF Tube Super PF Dust generation of particles/cc

More information

TOWA SEIDEN INDUSTRIAL CO., LTD.

TOWA SEIDEN INDUSTRIAL CO., LTD. INSTRUCTION MANUAL SOUNDING LEVEL METER MODEL: TLX-120AP/200AP Meanings of indications for safety used in this Instruction Manual are as follows. WARNING: Indicates that improper handling assumes the risk

More information

Micro-differential Pressure High-precision Digital Pressure Sensor For Gas DP-M SERIES

Micro-differential Pressure High-precision Digital Pressure Sensor For Gas DP-M SERIES MODE 729 Micro-differential Pressure High-precision Digital Pressure Sensor For Gas SERIES Related Information General terms and conditions... F-3 Glossary of terms... P.1563~ guide... P.699~ General precautions...

More information

No.EX -OME0016-A PRODUCT NAME. SI unit. MODEL / Series / Product Number EX140-SDN1

No.EX -OME0016-A PRODUCT NAME. SI unit. MODEL / Series / Product Number EX140-SDN1 No.EX -OME0016-A PRODUCT NAME SI unit MODEL / Series / Product Number EX140-SDN1 Table of Contents 1. Safety instructions 2 2. Specifications 7 2-1. General specifications 7 2-2. Electrical ant network

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #273 OPERATING INSTRUCTION MODEL 4105 Disital Earth Resistance Tester 2150 joshua's Path, Suite 302, Hauppauge, NY 11788 Phone : 1-800-645-5398 or 1-639-231-7050 Fax : 1-639-434-3128 E-mail

More information

Read and understand this manual for safely usage.

Read and understand this manual for safely usage. TS02-0180 INSTRUCTION MANUAL FOR AIR BUBBLER SYSTEM LEVEL MEASUREMENT MODEL:LA100 MODEL:LA110 MODEL:LA1000 Read and understand this manual for safely usage. This manual describes the product of standard

More information

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4 Braking Resistor Units 3G3IV-PCDBR2 B/4 B Braking Units Thank you for choosing an OMRON Braking Resistor Unit and Braking Unit. Proper use and handling

More information