Installation Instructions

Size: px
Start display at page:

Download "Installation Instructions"

Transcription

1 05A00 053A00 VERTICAL AND HORIZONTAL ECONOMIZER IV ACCESSORY MEDIUM ROOFTOP UNITS 5 to 5 TONS TABLE OF CONTENTS PACKAGE USAGE... SAFETY CONSIDERATIONS... PACKAGE CONTENTS... GENERAL... ACCESSORIES LIST... VERTICAL INSTALLATION... HORIZONTAL INSTALLATION... 7 CONFIGURATION... 9 OPERATION... 3 TROUBLESHOOTING... IMPORTANT: Read these instructions completely before attempting to install the accessory Economizer IV. PACKAGE USAGE UNIT SIZE Installation Instructions PART NUMBER 7, 0, 05A A00 SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Recognize safety information. This is the safety-alert symbol. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. PACKAGE CONTENTS UNIT QTY CONTENTS Damper Assembly Upper End Economizer Panel Bottom Panel w/relief Damper (for vertical only) Bottom Panel # (for horizontal only) Side Replacement Panel (for horizontal only) Hood Angles 05A00 Hood Side Plates Hood Top Side Filter Supports Side Drip Angles TopHoodDiverters Supply Air Temperature Sensor (SAT) 60 Screws Seal Strip Damper Assembly Upper End Economizer Panel Bottom Panel w/relief Damper (for vertical only) Bottom Panel # (for horizontal only) Hood Angles Hood Side Panels 053A00 Hood Top Outdoor Air Screens Side Filter Supports Side Drip Angles TopHoodDiverters Supply Air Temperature Sensor (SAT) 60 Screws Seal Strip

2 APPLICATION Outdoor Air Dry Bulb Differential Dry Bulb Single Enthalpy Differential Enthalpy CO for DCV Control using a Wall --- Mounted CO Sensor CO for DCV Control using a Duct --- Mounted CO Sensor Table EconoMi$erIVSensorUsage ECONOMI$ER IV WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required None. The outdoor air dry bulb sensor is factory installed. CRTEMPSN00A00* HH57AC078 HH57AC078 and CRENTDIF00A00* 33ZCSENCO or CGCDXSEN00A00 33ZCSENCO or CGCDXSEN00A00{ and 33ZCASPCO or OR CRCBDIOX005A00{{ CGCDXASP00A00** * CRENTDIF00A00 and CRTEMPSN00A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. { 33ZCSENCO and CGCDXSEN00A00 are accessory CO sensors. ** 33ZCASPCO and CGCDXASP00A00 are accessory aspirator boxes required for duct---mounted applications. {{CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO and 33ZCASPCO accessories.! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury and/or death. Disconnect power supply and install lockout tag before attempting to install the accessory. GENERAL The EconoMi$er IV system utilizes the latest technology available for integrating the use of free cooling with mechanical cooling for packaged rooftop units. The solid-state control system optimizes energy consumption, zone comfort, and equipment cycling by operating the compressors when the outdoor-air temperature is too warm, integrating the compressor with outdoor air when free cooling is available, and locking out the compressor when outdoor-air temperature is too cold. Demand ventilation is supported. The EconoMi$er IV system utilizes gear-drive technology with a direct -mount spring return actuator that will close upon loss of power. The Economizer IV system comes standard with an outdoor air temperature sensor, supply air temperature sensor, and low temperature compressor lockout switch. Return air temperature, indoor enthalpy, and outdoor enthalpy sensors are available for field installation. Field-installed CO sensors are available. Barometric relief dampers provide natural building pressurization control. Barometric relief dampers are built into the design and are standard. An optional power exhaust system is available for applications requiring even greater exhaust capabilities. The power exhaust set point is adjustable at the EconoMi$er IV controller. See Package Contents and Package Usage tables for more information. See Table for sensor usage. ACCESSORIES LIST The EconoMi$er IV has several field-installed accessories available to optimize performance. Refer to Table for authorized parts. Table EconoMi$er IV Field -Installed Accessories DESCRIPTION Power Exhaust v 3 Ph Power Exhaust 60 v 3 Ph Power Exhaust 575 v 3 Ph Return Air Temperature Sensor Outdoor Air Enthalpy Sensor Indoor Air Enthalpy Sensor Return Air CO Sensor ( to 0 ma) CO Room Sensor ( to 0 ma) Aspirator Box for Duct Mount CO ( to 0 ma) Space Temperature and CO Room Sensor with Override ( to 0 ma) Space Temperature and CO Room Sensor with Override and Set Point ( to 0 ma) PART NUMBER CRPWREXH068A00 CRPWREXH069A00 CRPWREXH070A00 CRTEMPSN00A00 HH57AC078 CRENTDIF00A00 CRCBDIOX005A00 33ZCSENCO or CGCDXASP00A00 33ZCASPCO or CGCDXASP00A00 33ZCT55CO 33ZCT56CO VERTICAL INSTALLATION These economizers are designed to work in both a vertical and horizontal applications. These instructions are for a vertical installation.. Turn off unit power supply and install lockout tag.. Prepare the unit for economizer installation: a. For units with position damper installed, remove the outside air hood. Unplug the damper actuator and remove assembly from unit. b. For units with manual damper installed, remove the manual damper and hood. 3. Remove the upper panel and bottom panel (provided with the HVAC unit) on the end of the unit to expose the return section. (See Fig..) Save the screws for use later when replacing the panel. The panels can be discarded.

3 ! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in personal injury and damage to unit. Cover the duct opening as a precaution so objects cannot fall into the return duct opening. Be sure to remove the cover when installation is complete. Indoor-fan Panel Upper End Panel Shipped on Base Unit Bottom Panel Shipped on Base Unit Fig. - Upper and Bottom Panel on End of Unit C0937. Remove the unit s left side corner post and left side panel from the unit to allow for easy economizer installation. (See Fig..) 5. Install economizer, as shown in Fig, into the return air section of the unit. Be careful not to pinch the wires during installation. Bottom of economizer will rest on the base of the unit. (See Fig. 5.) 6. Reinstall the left side corner post on to the unit. Note the corner post will sit behind the economizer flange. (See Fig. 3.) Screw through the corner post and through the economizer. (See Fig. 3 and.) 7. Insert provided screw through the bottom left rear of the economizer and into the unit base. (See Fig. 5.) Reinstall the unit s left side panel. 8. Before the economizer is secured in place on the right hand side, remove and save the -pin jumper plug from the unit wiring harness. (See Fig. 6.) Insert the economizer plug into the unit wiring harness plug. NOTE: The -pin jumper plug should be saved for future use in the event that the EconoMi$er IV is removed from the unit. The jumper plug is not needed as long as the EconoMi$er IV is installed. Left Corner Post Unit s Left Side Panel Economizer Outside Air Damper Insert Screw Left Front Corner Post Insert Screw Fig. 3 - Top View Fig. - Front Left View Fig. 5 - Side View C0939 C09330 C Remove the indoor-fan motor access panel. (See Fig.) EconoMi$er IV Fig. - Unit Left Side Panel and Corner Post C0938 3

4 0. Install the supply air temperature sensor (SAT). The sensor looks like and eyelet terminal with attached wires, and is shipped in the economizer hardware bag. The sensor is located on the crimped end and is sealed for moisture. Mount the SAT to the indoor blower housing. (See Fig. 7.) Use the provided screw to secure in place. Attach the PINK and VIOLET wires in the unit to the sensor.. Replace the indoor-fan motor access panel.. Install the bottom panel with the relief damper attached on the unit. (See Fig 8.) Screw panel in place. NOTE: Remove the bottom screw holding the relief blade closed. 3. Install the upper end economizer panel over the economizer s outside air damper, and above the bottom panel. Screw panel in place and screw panel into economizer in places. (See Fig 8.) Provided Upper Panel Fig. 7 - Blower Housing Insert () screws thru panel and into economizer C09333 Economizer Outside Air Damper Provided Bottom Panel with Relief Relief Damper Remove shipping screw Fig. 8 - End View of Unit C0933 Outside Air Damper Economizer Actuator Low Temp. Lockout Wiring Harness EconoMi$er IV Controller Outside Air Temp (OAT) sensor Fig. 6 - Unit Wiring Harness C0933 Return Air Damper Fig. 9 - EconoMi$er IV Component Locations C09335

5 . Assemble the outside air hood per Fig 0 and. a. Install four hood angles to the upper end panel using the screws provided. b. Apply seal strip to mating flanges on the side plates of the hood and the hood top. c. Secure the hood side plates to the panel using screws provided. d. On inch chassis, remove screws across top cover. Attach hood top to hood side plates (on inch chassis, flange will slide behind flange of top cover). e. On inch chassis, reinstall the screws previously removed. On the 5 inch chassis, secure top flange using screws provided in kit. f. Install the front outdoor air screens by sliding them into the channel formed by the four angles installed previously. Make sure the screens extend across the entire length of the hood. NOTE: Screens may be left out at this time to allow for EconoMi$er IV adjustments. g. Install the side filter supports using the screws provided. h. Install the side drip edge angles using the screws provided. i. Run a continuous length of seal strip across the hood covering the engagement hole in the lower hood. j. Install top diverter using screws provided. 5. Install the hood assembly on to the unit. (See Fig. and.) 6. Through the outdoor air hood, review and adjust the EconoMi$er IV controller settings. See Operation section of this manual for details. a. The standard EconoMi$er IV controller has a factory setting of C for the outdoor air temperature changeover and 55_F (fixed) for the supply air temperature sensor. The outdoor air temperature setting can be adjusted at the controller. b. The low temperature compressor lockout switch is fixed at _F. c. The minimum position for the outdoor air damper can be configured for specific job requirements at the controller. d. Settings for the optional return air temperature sensor, outdoor enthalpy sensor, indoor enthalpy sensor, power exhaust, and CO sensor can be configured at the controller. 7. Install the hood screens and other approved Econo- Mi$er IV accessories. Apply Seal Strips to the back of these flanges Apply Seal Strip to the front of this flange 7 Apply Seal Strips to the back of these surfaces 3 7 Apply Seal Strip to the front of this flange 5 6 Seal Strips 5 6 Apply Seal Strip to the back of this flange Item # Description Qty Angles Side Plates 3 Hood Outdoor Air Screens 5 Side Filter Supports 6 Side Drip Angles 7 Top Diverters Fig. 0 - Hood Assembly C

6 Fig. - Hood Assembly C09090 Outdoor Air Hood Relief Damper Fig. - Hood Assembly Installed on Unit C09338 POTENTIOMETER POWER EXH MINIMUM POS. DCV MAX. DCV SET ENTHALPY DEFAULTS SETTINGS: MIDDLE FULLY CLOSED MIDDLE MIDDLE C SETTING BRN ECONOMIZER (FIOP / ACCESSORY) PNK VIO RED RED (ACCESSORY) REMOTE MIN POSITION POT REMOTE POT (35 ohm) BRN RED (FIOP / ACCESSORY) IAQ SENSOR 8 BLK 7 BLU OAT TEMP / ENTHALPY SENSOR BLK RED (ACCESSORY) RAT/ENTHALPY SENSOR + 5 PNK N N P T BLK P T AQ AQ SO+ SO SR+ SR 60Ω VIO EXH DCV V V V FREE COOL B A 0V 0V 0V EXH SET MIN POS OPEN DCV MAX DCV SET ECONOMIZER NOTES:. 60 OHM, WATT 5% RESISTER SHOULD BE REMOVED ONLY WHEN USING DIFFERENTIAL ENTHALPY OR DRY BULB.. IF A SEPERATE FIELD SUPPLIED V TRANSFORMER IS USED FOR THE IAQ SENSOR POWER SUPPLY, IT CANNOT HAVE THE SECONDARY OF THE TRANSFORMER GROUNDED. 3. FOR FIELD INSTALLED REMOTE MINIMUM POSITION POT. REMOVE BLACK WIRE JUMPER BETWEEN P AND P AND SET CONTROL MINIMUM POSITION POT TO THE MINIMUM POSITION. C D RED ECONOMISER IV BOARD BRN TR Vac HOT + 3 EF TR BRN Vac COM - 5 EF TAN BRN TO PWR EXHAUST ACCESSORY RED GRA GRA YEL ORN BLU ECONOMIZER MOTOR BLK WHT LA 3 PNK VIO (NOT USED) (NOT USED) YEL BLK BRN RED GRA ORN (NOT USED) YEL PL6 - R FOR STD UNIT PL6 BLU PNK VIO YEL BLU BLK BRN RED GRA ORN PNK (FIOP / ACCY) ECONOMIZER BLU SAT BLU GRA GRA ESL ECONOMIZER Fig. 3 - Economizer Wiring Diagram 6 UNIT WITHOUT ECONOMIZER C09339

7 HORIZONTAL INSTALLATION These economizers are designed to work in both vertical and horizontal applications. These instructions are for a horizontal application. The unit has a horizontal duct opening next to the horizontal supply duct opening. However, in this application, with an economizer, the horizontal duct will actually come into the unit underneath the outdoor air hood. (See Fig. 7.). Turn off unit power supply and install lockout tag.. Prepare the unit for economizer installation: a. For units with position damper installed, remove the outside air hood. Unplug the damper actuator and remove assembly from unit. b. For units with manual damper installed, remove the manual damper and hood. 3. Remove the upper panel and bottom panel (provided with the HVAC unit). On the end of the unit to expose the return section. (See Fig.) Save the screws for use later when replacing the panel. The panels can be discarded.. Remove the unit s left side corner post and left side panel from the unit to allow for easy economizer installation. (See Fig.) NOTE: The unit s left side panel has a duct opening in it, but this panel / duct opening will not be used in this application and can be discarded. Unit s Left Side Panel with Duct Opening 7. Insert provided screw through the bottom left rear of the economizer and into the unit base. (See Fig. 5.) Install the new (provided) left side panel - without the duct opening on the unit. 8. Before the economizer is secured in place on the right hand side, remove and save the -pin jumper plug from the unit wiring harness. Insert the Econo- Mi$er IV plug into the unit wiring harness plug. (See Fig 6.) NOTE: The -pin jumper plug should be saved for future use in the event that the EconoMi$er IV is removed from the unit. The jumper plug is not needed as long as the EconoMi$er IV is installed. 9. Remove the indoor-fan motor access panel. (See Fig..) 0. Install the supply air temperature sensor (SAT). The sensor looks like an eyelet terminal with attached wires, and is shipped in the economizer hardware bag. The sensor is located on the crimped end and is sealed for moisture. Mount the SAT to the indoor blower housing. (See Fig. 7.) Use the provided screw to secure in place. Attach the PINK and VIOLET wires in the unit to the sensor.. Replace the indoor-fan motor access panel.. Install the (provided) bottom panel with the horizontal return duct opening on the unit. (See Fig. 5.) Screw panel in place. 3. Install the upper end economizer panel in place over the economizer s outside air damper, and above the bottom panel. Screw panel in place and screw panel into economizer in places. (See Fig. 6.) Left Front Corner Post C0930 Fig. - Remove Unit Corner Post and Side Panel 5. Install economizer, as shown in Fig., into the return air section of the unit. Be careful not to pinch the wires during installation. Bottom of economizer will rest on the base of the unit. (See Fig. 5.) 6. Reinstall the left side corner post on to the unit. Note the corner post will sit behind the economizer flange. (See Fig. 3.) Screw through the corner post and through the economizer. (See Fig. 3 and.) Bottom Panel with Return Duct Opening Fig. 5 - Install Bottom Panel with Horizontal Return Duct Opening C093 7

8 Economizer Outside Air Damper Provided Upper Panel 8 3/8 Provided Bottom Panel with Return Duct Opening 6 9/6 Fig. 6 - End View C093. Assemble the outside air hood per Fig. 0 and. a. Install four hood angles to the upper end panel using the screws provided. b. Apply seal strip to mating flanges on the side plates of the hood and the hood top. c. Secure the hood side plates to the panel using screws provided. d. On inch chassis, remove screws across top cover. Attach hood top to hood side plates (on inch chassis, flange will slide behind flange of top cover). e. On inch chassis, reinstall the screws previously removed. On the 5 inch chassis, secure top flange using screws provided in kit. f. Install the four outdoor air screens by sliding them into the channel formed by the four angles installed previously. Make sure the screens extend across the entire length of the hood. NOTE: Screens may be left out at this time to allow for EconoMi$er IV adjustments. g. Install the side filter supports using the screws provided. CRBARHOD00A00 Relief Hood Ordered Separately Outdoor Air Hood h. Install the side drip edge angles using the screws provided. i. Run a continuous length of seal strip across the hood covering the engagement hole in the lower hood. j. Install top diverter using screws provided. 5. Install the hood assembly on to the unit. Fig and. 6. Through the outdoor air hood, review and adjust the EconoMi$er IV controller settings. See Operation section of this manual for details. a. The standard EconoMi$er IV controller has a factory setting of C for the outdoor air temperature changeover and 55_F (fixed) for the supply air temperature sensor. The outdoor air temperature setting can be adjusted at the controller. b. The low temperature compressor lockout switch setting can be adjusted at the controller. c. The minimum position for the outdoor air damper can be configured for specific job requirements at the controller. d. Settings for the optional return air temperature sensor, outdoor enthalpy sensor, indoor enthalpy sensor, power exhaust, and CO sensor can be configured at the controller. 7. If barometric relief is required remove the relief damper and hinges from the (provided) bottom panel used on vertical applications. Reinstall the hinges and damper on the side of the field supplied return duct. (See Fig. 7.) NOTE: A relief hood for the horizontal application can be ordered separately (part number CRBARHOD00A00) or can be field-supplied. 8. Install the hood screens and other approved Econo- Mi$er IV accessories. Field Supplied Return Duct Relief Damper Fig. 7 - Reinstall Hinges and Damper on Return Duct C0933 8

9 CONFIGURATION EconoMi$er IV Standard Sensors Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC07) is a 0 to 0 ma device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. (See Fig. 9.) The operating range of temperature measurement is 0_ to 00_F. Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3K thermistor located at the inlet of the indoor fan. (See Fig. 9.) This sensor is field installed. The operating range of temperature measurement is 0_ to 58_F. See Table 5 for sensor temperature/resistance values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the crimp end and is sealed from moisture. Table 3 Supply Air Sensor Temperature/Resistance Values TEMPERATURE (F) RESISTANCE (ohms) , , , ,09 6, , , , ,000 86,6 0,597, Low Temperature Compressor Lockout Switch The EconoMi$er IV is equipped with a low ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a_fambient temperature. (See Fig. 9.) EconoMi$er IV Control Modes Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. (See Table.) The EconoMi$er IV is supplied from the factory with a supply air temperature sensor, a low temperature compressor lockout switch, and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit. Outdoor Dry Bulb Changeover The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor air damper to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point controlled by the free cooling set point potentiometer located on the control. (See Fig 8.) The scale on the potentiometer is A, B, C, and D. See Fig 9 for the corresponding temperature changeover values. C07385 Fig. 8 - EconoMi$er IV Controller Potentiometer and LED Locations 9

10 ma LED ON D LED OFF LED ON C LED OFF LED ON LED OFF LED ON 0 LED OFF DEGREES FAHRENHEIT C06035 Fig. 9 - Outdoor Air Temperature Changeover Setpoints Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory return air sensor (part number CRTEMPSN00A00). The accessory sensor must be mounted in the return airstream. (See Fig. 0.) In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the free cooling/enthalpy set point potentiometer fully clockwise to the D setting. (See Fig. 8.) Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig 9.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. B A The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set point are A, B, C and D. (See Fig.) The factory-installed 60-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. (See Fig 3.) Differential Enthalpy Control For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF00A00), one in the outside air and one in the return airstream. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air and is below the set point, the EconoMi$er IV opens to bring in outdoor air for free cooling. Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig 9.) Mount the return air enthalpy sensor in the return air duct. (See Fig 0.) When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation control based on the level of CO measured in the space or return air duct. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ terminals of the controller. Adjust the DCV voltage output of the indoor air quality sensor at the user-determined set point. (See Fig 3.) If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged. Differential (Return) Temperature Sensor or Enthalpy Fig. 0 - Return Air Temperature or Enthalpy Sensor Mounting Location C093 0

11 CONTROL CURVE CONTROL POINT APPROX. 0 F ( 0 C) AT 50% RH A 73 (3) B 70 () C 67 (9) D 63 (7) Fig. - Enthalpy Changeover Setpoints C0935 CO SENSOR MAX RANGE SETTING N N P P T T AQ AQ SO+ SO SR+ SR V EXH V DCV V Free Cool B EXH Set 0V Min Pos Open A DCV Max 0V DCV Set 0V C D TR Va c HOT + TR Vac COM EF _ 5 3 EF RANGE CONFIGURATION (ppm) DAMPER VOLTAGE FOR MAX VENTILATION RATE Fig. 3 - CO Sensor Maximum Range Setting 800 ppm 900 ppm 000 ppm 00 ppm C06039 Fig. - EconoMi$er IV Controller C06038

12 Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. (See Fig. 8.) The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 5±5 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload. Minimum Position Control There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 8.) The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 0_F temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting perform the following procedure:. Calculate the appropriate mixed air temperature using the following formula: T O OA 00 + (T R RA 00 ) = T M T O = Outdoor-Air Temperature OA = Percent of Outdoor Air T R = Return-Air Temperature RA = Percent of Return Air T M = Mixed-Air Temperature. Disconnect the supply air sensor from terminals T and T. 3. Ensure that the factory-installed jumper is in place across terminals P and P. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 3 and that the minimum position potentiometer is turned fully clockwise.. Connect vac across terminals TR and TR. 5. Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value. 6. Reconnect the supply air sensor to terminals T and T. Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B8) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper position remotely remove the factory-installed jumper on the P and P terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P terminals on the EconoMi$er IV controller. (See Fig. 3.) Damper Movement Damper movement from full open to full closed (or vice versa) takes -/ minutes. Thermostats The EconoMi$er IV control works with conventional thermostats that have a Y (cool stage ), Y (cool stage ), W (heat stage ), W (heat stage ), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box. Occupancy Control The factory default configuration for the economizer control is occupied mode. Occupied status is provided by the black wire from Pin 3. When unoccupied mode is desired, install a field-supplied time clock function in place of the jumper between TR and N. (See Fig. 3.) When the time clock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the time clock contacts are open (removing the -v signal from terminal N), the economizer will be in unoccupied mode. Demand Control Ventilation When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air. Typically the maximum ventilation rate will be about 5 to 0% more than the typical cfm required per person, using normal outside air design criteria. An exponential anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. An exponential -anticipatory strategy will cause the fresh air supplied to increase as the room CO level increases even though the CO set point has not been reached. By the time the CO level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.

13 In order to have the CO sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside -air entering the building for a given damper position. For best results there should be at least a 0 degree difference in outside and return-air temperatures. T O OA 00 + (T R RA 00 ) = T M T O = Outdoor-Air Temperature OA = Percent of Outdoor Air T R = Return-Air Temperature RA = Percent of Return Air T M = Mixed-Air Temperature Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rat of 0% (or base plus 5 cfm per person). Use Fig. 3 to determine the maximum setting of the CO sensor. For example, a 00 ppm set point relates to a 5 cfm per person design. Use the 00 ppm curve on Fig. 3 to find the point when the CO sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO sensor should be 800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO sensor to the actuator when the CO concentration in the space is at 00 ppm. The DCV set point may be left at volts since the CO sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position as this can result in over-ventilation to the space and potential high-humidity levels. CO Sensor Configuration The CO sensor has preset standard voltage setting that can be selected anytime after the sensor is powered up. (See Table.) Use setting or for this equipment. (See Table.). Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.. Press Mode twice. The STDSET Menu will appear. 3. Use the Up/Down button to select the preset number. (See Table.). Press Enter to lock in the selection. 5. Press Mode to exit and resume normal operation. The custom settings of the CO sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enter the Edit mode.. Press Mode twice. The STDSET Menu will appear. 3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached. 5. Press Mode to move through the variables. 6. Press Enter to lock in the selection, then press Mode to continue to the next variable. Dehumidification of Fresh Air With DCV Control Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some application, an energy recovery unit can be added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications. If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, and energy recovery unit and/or a dehumidification option should be considered. OPERATION Sequence of Operation When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50_ to 55_F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55_ or below 50_F, the dampers will be modulated (open or close) to bring the Supply-air temperature back within the set points. For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode. Above 50_F supply-air temperature, the dampers will modulate from 00% open to the minimum open position. From 50_F to 5_F supply-air temperature, the dampers will maintain at the minimum open position. Below 5_F, the dampers will be completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open position once the supply-air temperature rises to 8_F. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. 3

14 Table CO Sensor Standard Settings SETTING EQUIPMENT OUTPUT VENTILATION RATE (cfm/person) Proportional Any Interface w/standard Building Control System Proportional Any 3 Exponential Any Proportional 5 5 Proportional 0 Economizer 6 Exponential 5 7 Exponential 0 8 Health & Safety Proportional 9 LEGEND ppm Parts Per Million Parking/Air Intakes/Loading Docks Proportional If field-installed accessory CO sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO level in the zone increases above the CO set point, the minimum position of the damper will be increased proportionally. As the CO level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode. Damper movement from full closed to full open (or vice versa) will take between -/ and -/ minutes. If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_F. As the supply air temperature drops below the set point range of 50_ to 55_F, the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature. TROUBLESHOOTING See Table 9 for EconoMi$er IV logic. EconoMi$er IV Preparation This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9-v battery,. kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV. IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting. ANALOG OUTPUT CO CONTROL RANGE (ppm) OPTIONAL RELAY SETPOINT (ppm) RELAY HYSTERESIS (ppm) V ma V ma V ma V ma V ma V ma V ma V ma V ma Disconnect power at TR and TR. All LEDs should be off. Exhaust fan contact should be open.. Disconnect device at P and P. 3. Jumper P to P.. Disconnect wires at T and T. Place 5.6 kilo-ohm resistor across T and T. 5. Jumper TR to. 6. Jumper TR to N. 7. If connected, remove sensor from terminals S O and +. Connect. kilo-ohm 07EJM checkout resistor across terminals S O and Put 60-ohm resistor across terminals S R and Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise). 0. Set DCV maximum position potentiometer fully CW (clockwise).. Set enthalpy potentiometer to D.. Apply power ( vac) to terminals TR and TR. Differential Enthalpy To check differential enthalpy:. Make sure EconoMi$er IV preparation procedure has been performed.. Place 60-ohm resistor across S O and Place. kilo-ohm resistor across S R and +. The Free Cool LED should be lit.. Remove 60-ohm resistor across S O and +. The Free Cool LED should turn off. 5. Return EconMi$er IV settings and wiring to normal after completing troubleshooting.

15 Single Enthalpy To check single enthalpy:. Make sure the EconoMi$er IV preparation procedure has been performed.. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit. 3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.. Return EconoMi$er IV settings and wiring to normal after com. pleting troubleshooting. DCV (Demand Control Ventilation) and Power Exhaust. Make sure EconoMi$er IV preparation procedure has been performed.. Ensure terminals AQ and AQ are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed. 3. Connect a 9-v battery to AQ (positive node) and AQ (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position. 5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9-v. The actuator should drive fully closed. 6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contact will close 30 to 0 seconds after the Exhaust LED turns on. 7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. ECV Minimum and Maximum Position To check the DCV minimum and maximum position:. Make sure EconoMi$er IV preparation procedure has been performed.. Connect a 9-v battery to AQ (positive node) and AQ (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 0 and 80% open.. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed. 5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 0 and 80% open. 6. Turn the Minimum Position potentiometer fully CW. The actuator should drive fully open. 7. Remove the jumper from TR and N. The actuator should drive fully closed. 8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. Supply -Air Input To check supply-air input:. Make sure EconoMi$er IV preparation procedure has been performed.. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 0 and 80% open. 3. Remove the 5.6 kilo-ohm resistor and jumper T to T. The actuator should drive fully open.. Remove the jumper across T and T. The actuator should drive fully closed. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. EconoMi$er IV Troubleshooting Completion This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure:. Disconnect power at TR and TR.. Set enthalpy potentiometer to previous setting. 3. Set DCV maximum position potentiometer to previous setting.. Set minimum position, DCV set point, and exhaust potentiometers to previous settings. 5. Remove 60-ohm resistor from terminals S R and Remove. kilo-ohm checkout resistor from terminals S O and +. If used, reconnect sensor from terminals S O and Remove jumper from TR to N. 8. Remove jumper from TR to. 9. Remove 5.6 kilo-ohm resistor from T and T. Reconnect wires at T and T. 0. Remove jumper from P to P. Reconnect device at P and P.. Apply power ( vac) to terminals TR and TR. 5

16 Table 5 EconoMi$er IV Input/Output Logic Demand Control Ventilation (DCV) Below set (DCV LED Off) Above set (DCV LED On) INPUTS Enthalpy* Outdoor High (Free Cooling LED Off) Low (Free Cooling LED On) High (Free Cooling LED Off) Low (Free Cooling LED On) Return Low High Low High Y Y Compressor Stage Stage On On On On On Off On Off Off Off Off Off On On On Off On Off Off Off OUTPUTS NTerminal{ Occupied Unoccupied Damper Minimum position Modulating** (between min. position and full --- open) Closed Modulating** (between closed and full --- open) Off Off Off Off Minimum position Closed On On On On Modulating{{ Modulating{{ On Off On Off (between min. position and DCV (between closed and DCV Off Off Off Off maximum) maximum) On On On Off On Off Off Off Modulating*** Modulating{{{ Off Off Off Off * For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point. { Power at B terminal determines Occupied/Unoccupied setting: vac (Occupied), no power (Unoccupied). ** Modulation is based on the supply---air sensor signal. {{ Modulation is based on the DCV signal. *** Modulation is based on the greater of DCV and supply---air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply---air signal). {{{ Modulation is based on the greater of DCV and supply---air sensor signals, between closed and either maximum position (DCV) or fully open (supply---air signal). Copyright 009 CAC / BDP D 730 W. Morris St. D Indianapolis, IN 63 Printed in U.S.A. Edition Date: 7/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No:IIK---CRECOMZ5---0 Replaces: NEW 6

Installation Instructions

Installation Instructions 024A02 025A02 SMALL ROOFTOP UNITS HORIZONTAL ECONOMI$ER IV ACCESSORY 2TO12-1/2TONS Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS... 1 GENERAL...

More information

Installation Instructions

Installation Instructions 020A02 021A03 008C00 SMALL ROOFTOP UNITS VERTICAL ECONOMI$ER IV ACCESSORY 2to12-1 / 2 TONS LARGE ROOFTOP UNITS VERTICAL AND HORIZONTAL ECONOMI$ER IV ACCESSORY 13 to 25 TONS Installation Instructions TABLE

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR011A00 & CPECOMZR012A00 Installation Instructions Read these instructions completely before attempting to install the Horizontal Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR008A00 & CPECOMZR009A00 Installation Instructions Read these instructions completely before attempting to install the Vertical Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR010A00 Read these instructions completely before attempting to install the Vertical Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2 ACCESSORIES LIST...2 INSTALLATION...2-6

More information

Installation Instructions

Installation Instructions CRECOMZR024A02 CRECOMZR025A02 CRECOMZR064A00 Small Rooftop Products 3 to 2 ½ Tons Horizontal Accessory Read these instructions completely before attempting to install the Horizontal Accessory. CONTENTS

More information

CRECOMZR054B00 CRECOMZR055B00. VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS WARNING TABLE OF CONTENTS

CRECOMZR054B00 CRECOMZR055B00. VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS WARNING TABLE OF CONTENTS CRECOMZR05B00 CRECOMZR055B00 VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS TABLE OF CONTENTS PACKAGE USAGE...1 SAFETY CONSIDERATIONS...1 PACKAGE CONTENTS...1 GENERAL...2

More information

Installation Instructions DNECOMZR020A02, DNECOMZR021A03 (For 3 to 12.5 Ton Units) and DNECOMZR062A00 (For RHS 12.5 Ton Heat Pump Units)

Installation Instructions DNECOMZR020A02, DNECOMZR021A03 (For 3 to 12.5 Ton Units) and DNECOMZR062A00 (For RHS 12.5 Ton Heat Pump Units) Installation Instructions DNECOMZR020A02, DNECOMZR021A03 (For 3 to 12.5 Ton Units) and DNECOMZR062A00 (For RHS 12.5 Ton Heat Pump Units) Vertical Economizer Accessory for Rooftop Units TABLE OF CONTENTS

More information

Installation Instructions

Installation Instructions ROOFTOP UNITS, 3 to 25 TONS ACCESSORY TEMPERATURE FOR SINGLE OR DIFFERENTIAL DRY BULB CONTROL FOR ECONOMI$ERt IV Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 SAFETY CONSIDERATIONS...

More information

Installation Instructions

Installation Instructions HH57AC078 CRENTDIF004A00 ROOFTOP UNITS, 2 to 25 TONS ACCESSORYENTHALPYAND DIFFERENTIAL ENTHALPY FOR ECONOMI$ERt IV Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS - HH57AC078... 1 PACKAGE

More information

Installation Instructions

Installation Instructions CRPWREXH068A00 CRPWREXH069A00 CRPWREXH070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 15 to 25 TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION...

More information

Installation Instructions

Installation Instructions 08A0, 09A0, 08A00, 08A00 For Use With Horizontal EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY HORIZONTAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS

More information

Installation Instructions

Installation Instructions CRPWREXH08A0, CRPWREXH09A0, CRPWREXH08A00, CRPWREXH08A00 For Use With Horizontal EconoMi$er IV, EconoMi$er, or EconoMi$er X (W70) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... PACKAGE

More information

Installation Instructions

Installation Instructions 00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON

More information

Installation Instructions

Installation Instructions H068A00 H069A00 H070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 12.5to25TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION... 2 Power Exhaust

More information

Installation Instructions

Installation Instructions 010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...

More information

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

Blank-off. HVAC unit screws. Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for NPECOMZR00A00 ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

MicroMetl. INSTALLATION INSTRUCTIONS Dual Stage Relief Economizer ECD-SRT12DR, ECD-SRT34DR, ECD-SRT5SDR & ECD-SRT5LDR

MicroMetl. INSTALLATION INSTRUCTIONS Dual Stage Relief Economizer ECD-SRT12DR, ECD-SRT34DR, ECD-SRT5SDR & ECD-SRT5LDR MicroMetl INSTALLATION INSTRUCTIONS Dual Stage Relief Economizer ECD-SRT12DR, ECD-SRT34DR, ECD-SRT5SDR & ECD-SRT5LDR SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for (NPECOMZR006A00) ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw MicroMetl INSTALLATION INSTRUCTIONS for 0637-0311 (CPECOMZR006A00) MicroMetl's 0637 economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions

More information

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

EconoMi$er, Power Exhaust, and Sensor Installation Instructions Small Rooftop Units Gas Heating/Electric Cooling, Electric Cooling, and Heat Pump Units 3 to.5 Tons (50/60 Hz) EconoMi$er Package for Vertical and Horizontal Duct Systems Issue Date /0/0 EconoMi$er, Power

More information

Installation Instructions Read these instructions completely before attempting to install the Vertical EconoMi$er X Accessory.

Installation Instructions Read these instructions completely before attempting to install the Vertical EconoMi$er X Accessory. CRECOMZR076A00 CRECOMZR078A00 CRECOMZR080A00 Installation Instructions Read these instructions completely before attempting to install the Vertical EconoMi$er X Accessory. CONTENTS SAFETY CONSIDERATIONS..............

More information

Installation Instructions

Installation Instructions CRECOMZR077A00 CRECOMZR079A00 CRECOMZR08A00 Small Rooftop Products 3 to 2 ½ Tons Horizontal EconoMi$er X Accessory Read these instructions completely before attempting to install the Horizontal EconoMi$er

More information

ECONOMIZERS. 5/2012 Supersedes

ECONOMIZERS. 5/2012 Supersedes Litho U.S.A. 2012 ECONOMIZERS 507031 01 5/2012 Supersedes 506747 01 K1ECON ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS AND OUTDOOR AIR HOODS USED WITH KG/KC/KH 024, 030, 036, 048, 060, 072, 090

More information

ECONOMIZERS. 1/2012 Supersedes

ECONOMIZERS. 1/2012 Supersedes ECONOMIZERS Litho U.S.A. 2012 506948 01 1/2012 Supersedes 506394 01 K1ECON20C 1 ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZER AND OUTDOOR AIR (604592 03; 54W77) USED WITH KG/KC/KH 180 300S UNITS

More information

Package Unit Modulating Economizer Installation Instructions

Package Unit Modulating Economizer Installation Instructions Package Unit Modulating Economizer Installation Instructions Downflow Unit Warning: Recognize this symbol as an indication of Important Safety Information! Read all instructions prior to installation.

More information

Installation Instructions

Installation Instructions Installation Instructions ECONOMIZER X, FACTORY INSTALLED OPTION LOW LEAK ECONOMIZER FOR 2 SPEED INDOOR FAN CONTROL UNITS This document is a supplemental installation instruction for the factory-installed

More information

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas Installation Manual IOM-MBC-00 08-30-04 Mixing Box Control Systems Installation,, and Maintenance Manual Contents Page Introduction...1 General...1 Safety...1 Inspection...1 Mixing Box Control Systems...2

More information

Installation Instructions

Installation Instructions 018A00 CALOWAMB023A00 CALOWAMB037A00 - CALOWAMB042A00 SPLIT SYSTEM AC UNITS ACCESSORY MOTORMASTER R I HEAD PRESSURE CONTROLLER 15 & 20 TONS Installation Instructions IMPORTANT: Read these instructions

More information

Package Unit Modulating Economizer Installation Instructions

Package Unit Modulating Economizer Installation Instructions Package Unit Modulating Economizer Installation Instructions Downflow Unit Warning: Recognize this symbol as an indication of Important Safety Information! Read all instructions prior to installation.

More information

INSTALLATION INSTRUCTIONS MODELS (-)XRD-RGCM3 HORIZONTAL AIRFLOW ECONOMIZERS

INSTALLATION INSTRUCTIONS MODELS (-)XRD-RGCM3 HORIZONTAL AIRFLOW ECONOMIZERS INSTALLATION INSTRUCTIONS MODELS (-)XRD-RGCM3 HORIZONTAL AIRFLOW ECOMIZERS WARNING THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE

More information

INSTALLATION INSTRUCTIONS MODELS (-)XRD-MCCM3 & (-)XRD-MECM3/TECM3 CONVERTIBLE AIRFLOW ECONOMIZERS

INSTALLATION INSTRUCTIONS MODELS (-)XRD-MCCM3 & (-)XRD-MECM3/TECM3 CONVERTIBLE AIRFLOW ECONOMIZERS INSTALLATION INSTRUCTIONS MODELS (-)XRD-MCCM3 & (-)XRD-MECM3/TECM3 CONVERTIBLE AIRFLOW ECOMIZERS WARNING THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY

More information

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012 COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES 506953-01 3/2014 Supersedes 8/2012 Litho U.S.A. MSAV Supply Air Blower VFD Kit INSTALLATION INSTRUCTIONS FOR MSAV (MULTI-STAGE AIR VOLUME) SUPPLY AIR BLOWER

More information

wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS

wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS 580F 036-150 3 to 12 1 / 2 Tons Cancels: New WD 580F.36.1 10/15/00 *Low NOx/California compliant units. DIAGRAM INDEX UNIT LABEL

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION FORM# 609A-0808 (609A-0298) I - SHIP PING AND PACK ING LIST Package 1 of 1 contains: 1 - Economizer Assembly 1 - Fresh Air Hood w/ Filter 1 - Control Package 1 - Barometric Relief Hood 1 - Filter Access

More information

INSTALLATION INSTRUCTIONS MODELS (-)XRD-PDCM3 & (-)XRD-SDCM3 VERTICAL AIRFLOW ECONOMIZERS

INSTALLATION INSTRUCTIONS MODELS (-)XRD-PDCM3 & (-)XRD-SDCM3 VERTICAL AIRFLOW ECONOMIZERS WARNING INSTALLATION INSTRUCTIONS MODELS (-)XRD-PDCM3 & (-)XRD-SDCM3 VERTICAL AIRFLOW ECOMIZERS THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION

More information

Installation Instructions

Installation Instructions CRLOWAMB039A00 CRLOWAMB040A00 CRTRXKIT002A00 ACCESSORY MOTORMASTER I HEAD PRESSURE CONTROL KIT 12.5 TON HEAT PUMP Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PRODUCT USAGE... 2 SAFETY

More information

Installation Instructions

Installation Instructions CALOWAMB001A00 - CALOWAMB011A00 CALOWAMB030A00 - CALOWAMB036A00 SPLIT SYSTEMS ACCESSORY MOTORMASTER R I HEAD PRESSURE CONTROLLER 6to12.5TONS Installation Instructions IMPORTANT: Read these instructions

More information

INSTRUCTIONS FOR (-)XRX-AW04 or (-)XRX-AW05 MOTORIZED FRESH AIR DAMPER KIT

INSTRUCTIONS FOR (-)XRX-AW04 or (-)XRX-AW05 MOTORIZED FRESH AIR DAMPER KIT INSTRUCTIONS FOR (-)XRX-AW04 or (-)XRX-AW05 MOTORIZED FRESH AIR DAMPER KIT WARNING Recognize this symbol as an indication of Important Safety Information! THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED

More information

Installation Instructions

Installation Instructions 8/0A,A,A,A,AJ,AK,AW,AY00-00 Power Exhaust, Barometric Relief, and Conversion Package Accessories Installation Instructions Power Exhaust Part Numbers: CRPWREXH0A00, CRPWREXH0A00, CRPWREXH0A00, CRPWREXH0A00

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODELS CRVMWH-3 For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since

More information

Installation Instructions

Installation Instructions CRLVHLGD004A00 CRLVHLGD011A00- CRLVHLGD016A00, CRLVHLGD020A00- CRLVHLGD024A00 CRLVHLGD032A00 SMALL ROOFTOP UNITS ACCESSORY LOUVERED HAIL GUARD GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING AND HEAT PUMP

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CRVMP-5 For Use with Bard 3 through 5 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing Company Bryan, Ohio 43506

More information

Supplemental Installation Instructions -- August 2016

Supplemental Installation Instructions -- August 2016 EnergyX R System Factory---Installed Energy Recovery Ventilator 48/50HC WeatherMasterr Commercial Rooftop Units 7.5 to 12.5 Nominal Tons with Puronr (R---410A) Refrigerant and ComfortLink Controls Supplemental

More information

Supplemental Installation Instructions -- August 2016

Supplemental Installation Instructions -- August 2016 EnergyX R System Factory---Installed Energy Recovery Ventilator 48/50HC WeatherMasterr Commercial Rooftop Units 15 to 25 Nominal Tons with Puronr (R---410A) Refrigerant and ComfortLink Controls Supplemental

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

LF Series At A Glance

LF Series At A Glance LF Series Spring Return Direct Coupled Actuator Minimum 35 in-lb Torque For damper areas up to 8 sq-ft* Applications Cost effective quality and performance for a range of applications including: Classroom

More information

LF24-ECON-R03(-R10) US Operation, Installation and Wiring

LF24-ECON-R03(-R10) US Operation, Installation and Wiring LF24-ECON-R03(-R0) US Operation, Installation and Wiring Operation LF24-ECON-R03(-R0) US The LF24-ECON-R03(-R0) US provides a direct coupling solution for RoofTop Unit(RTU) economizer dampers. Control

More information

Installation, Start-Up and Configuration Instructions

Installation, Start-Up and Configuration Instructions Installation, Start-Up and Configuration Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 GENERAL.......................................1,2 INSTALLATION................................

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

Library Product Section Product Model Literature Type Sequence Date File No. Supersedes

Library Product Section Product Model Literature Type Sequence Date File No. Supersedes INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Library Product Section Product Model Literature Type Sequence Date File No. Supersedes ACC-SVN85B-EN

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators Installation Sheets Manual 121 Relays and Contactors Section R Technical Bulletin R81EAA Application R81 plug-in electronic

More information

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN

More information

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. OUTDOOR AIR S Litho U.S.A. 507214-01 2014 12/2014 Supersedes 9/2013 OUTDOOR AIR S INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR S AND OUTDOOR AIR USED WITH 156-300S UNITS Shipping and Packing List Package

More information

Installation Instructions

Installation Instructions Installation Instructions Part No. 50DJ902791 48/50FP,JP,MP,NP 50FPX,FPY,JPX,JPY 50FB,JB,NB Accessory Outdoor-Air Cfm Kit CONTENTS GENERAL........................................ 1 INSTALLATION................................

More information

Installation Instructions

Installation Instructions PLOWAMB001A00 SMALL ROOFTOP UNITS GAS HEAT/ELETRI OOLING, ELETRI OOLING AND HEAT PUMP UNITS AESSORY MOTORMASTERR II HEAD PRESSURE ONTROLLER 60Hz 3to12---1/2tons Installation Instructions IMPORTANT: Read

More information

WIRING DIAGRAMS FB4C FE4A/FE5A FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL

WIRING DIAGRAMS FB4C FE4A/FE5A FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL FAN COILS ACCESSORY ELECTRIC HEATERS WIRING DIAGRAMS FIG. FIELD-INSTALLED HEATER MODEL FB4C FE4A/FE5A FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL 1 KFCEH0401N03A 18,24 x 001 x 19,25 18,24 18,19,24,25 x 340816-101

More information

Economizer Controls Package I/O/M manual

Economizer Controls Package I/O/M manual Economizer Controls Package I/O/M manual PD 2/26/2014 - v 1.1 Table of Contents Economizer Controls Package Installation Overview... 3 Tool / Parts... 4 Hardware Included with Controls Package... 4 Economizer

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-3 For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps NOTE: CHCRV-3 Models must be installed with TCURB

More information

Installation Instructions

Installation Instructions Installation Instructions Power Exhaust Part Numbers: CRPWREXH07A00 THROUGH CRPWREXH079A00 Conversion Package Numbers: CRPECONV005A00, CRPECONV006A00 CONTENTS Page SAFETY CONSIDERATIONS......................

More information

R81EAA-2 Economizer Circuit Board

R81EAA-2 Economizer Circuit Board FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration

More information

Installation and Start Up Instructions

Installation and Start Up Instructions SYSTXCC4ZC01 Infinityr Control Installation and Start Up Instructions A97040 NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment,

More information

Installation and Start-Up Instructions

Installation and Start-Up Instructions Visit www.carrier.com SYSTXCC4ZC01 Infinity Control Installation and Start-Up Instructions Infinity Control SYSTXCC4ZC01 A97040 NOTE: Read the entire instruction manual before starting the installation.

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

INSTALLATION INSTRUCTIONS ECOHLX Series Horizontal Economizer and PEHALX Series Economizer with Power Exhaust for York LX Series. Warning.

INSTALLATION INSTRUCTIONS ECOHLX Series Horizontal Economizer and PEHALX Series Economizer with Power Exhaust for York LX Series. Warning. Before Starting Installation Warning Shut power to unit prior to any work being done. Personal injury or death could result. Only qualified HVAC service personnel should install, troubleshoot, repair or

More information

Installation Instructions

Installation Instructions Smart Start Assist Kit For use with Single-Phase Residential Geothermal Heat Pumps 8-733-934-497 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY

More information

SYST0101ZP Ion Damper Control Installation and Start---Up Instructions

SYST0101ZP Ion Damper Control Installation and Start---Up Instructions SYST0101ZP Ion Control Installation and Start---Up Instructions A97040I NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment,

More information

Installation, Service, and Troubleshooting Instructions

Installation, Service, and Troubleshooting Instructions Installation, Service, and Troubleshooting Instructions Page GENERAL........................................ 2 INSTALLATION................................. 2-4 Zone Controller Placement.......................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT MODEL AIR CONDITIONERS Gen eral The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 3 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT General The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment. Economizer Model

More information

ECON-ZIP-DETF; ZIP PACK

ECON-ZIP-DETF; ZIP PACK 71765-00001_A INSTUTION MANUAL EON-ZIP-DETF; ZIP PAK EON-ZIP-DETF; ZIP PAK Differential Enthalpy with DV apability and TF Spring eturn Actuator ontains: Application This kit offers all the components to

More information

Engineering Bulletin. Recirculation Energy Recovery Unit Controls CLCH-PRB009-EN

Engineering Bulletin. Recirculation Energy Recovery Unit Controls CLCH-PRB009-EN Engineering Bulletin Recirculation Energy Recovery Unit Controls Introduction The following represents just one of many configurations that are possible with the Trane Climate Changer air handler with

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS 50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS KSAIF0401AAA Wi-Fi Interface Kit for Ductless Systems INSTALLATION INSTRUCTIONS NOTE: Read and become familiar with these instructions before beginning installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18) AF Series Spring Return Direct Coupled Actuator Minimum 133 in-lb torque For damper areas up to 35 sq-ft* (For lower torque, see NF, LF, or TF series) Applications Remove for 3/4 to 1.05 shafts ZG106 or

More information

Hoffman Controls. Installation & Operating Instructions. General. Installation. Determining Damper Shaft Rotation. Stop Pin Installation

Hoffman Controls. Installation & Operating Instructions. General. Installation. Determining Damper Shaft Rotation. Stop Pin Installation Hoffman Controls Installation & Operating Instructions General 1. This instruction is a guide for connecting and operating the 200-3 Series Flow Controller with the 207 Series Thermostat and the 241-2

More information

Versatile and Powerful

Versatile and Powerful LM Series Direct Coupled Actuator Versatile and Powerful Minimum 45 in-lb torque in a compact package. For damper areas up to 11 sq-ft* Actuators in bold have BDCM LM Series - At A Glance LMB(X)24-3(-S)(-T)

More information

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910) LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS IMPORTANT!

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL BYPASS ECONOMIZER OPTION

INSTALLATION, OPERATION & MAINTENANCE MANUAL BYPASS ECONOMIZER OPTION INSTALLATION, OPETION & MAINTENANCE MANUAL Bypass Economizer Option for: HE1XIN, HE1.5XIN, HE2XIN, HE3XIN, HE4XIN, HE6XIN, HE8XIN WWW.RENEWAIRE.COM IMPORTANT SAFETY INFORMATION WARNING Arc flash and electric

More information

Mated ERV I/O/M manual

Mated ERV I/O/M manual Mated ERV I/O/M manual PD 2/4/2014 - v 1.1 2 Table of Contents DEFINITIONS... 3 ERV UNIT DESCRIPTIONS... 4 MATED ERV OPTIONS... 4 OPTION DESCRIPTIONS... 4 GENERAL OPERATIONS... 5 GENERAL INSTRUCTIONS...

More information

Owner s Information Manual

Owner s Information Manual 50ES---A and 50VL---C Comfort 13SEERThreePhase2½---5NominalTons (Sizes 30---60) Comfort 14 SEER Single and Three Phase 2---5 Nominal Tons (Sizes 24---60) Single Packaged Air Conditioner System With Puronr

More information

RHS. Product Specifications. PACKAGE HEAT PUMP UNIT R 410A SINGLE PACKAGE ROOFTOP TONS (1 & 3 Phase)

RHS. Product Specifications. PACKAGE HEAT PUMP UNIT R 410A SINGLE PACKAGE ROOFTOP TONS (1 & 3 Phase) RHS Product Specifications PACKAGE HEAT PUMP UNIT R 410A SINGLE PACKAGE ROOFTOP 3 12.5 TONS (1 & 3 Phase) BUILT TO LAST, EASY TO INSTALL AND SERVICE One piece, single packaged heat pump units that are

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Electrical Data Supplement

Electrical Data Supplement 48TC 3 to 15 Nominal Tons Single Package Rooftop Gas Heating/Electric Cooling Unit with Puronr (R---410A) Refrigerant Sizes: 04---16 Electrical Data Supplement FOR MODELS PRODUCED ON OR AFTER JULY 30,

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Electrical Data Supplement

Electrical Data Supplement 48HC15to25NominalTons Single Package Rooftop Gas Heating/Electric Cooling Unit with Puronr (R---410A) Refrigerant Sizes: 17---28 Electrical Data Supplement FOR MODELS PRODUCED ON OR AFTER JULY 30, 2012

More information

POWER EXHAUST START UP PRE START UP ONCE THE POWER EXHAUST ECONOMIZER IS INSTALLED, REMOVE THE ACCESS DOORS ON THE EXHAUST CABINET. ROUTE LINE VOLTAGE CABLE FROM THE VFD TO THE DISCONNECT OR UNIT POWER

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

Installation Instructions

Installation Instructions Installation Instructions Downflow Conversion Kit KFADC NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

LF Series Spring Return Direct Coupled Actuator

LF Series Spring Return Direct Coupled Actuator LF Series Spring Return Direct Coupled Actuator Minimum in-lb torque LF actuator For damper areas up to 8 sq-ft* Applications Cost effective quality and performance for a range of applications including:

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev. Installation Guide DigiTract 4 Two Stage Heat/Cool Comfort Control System Part #DT4MAN Rev. October 2013 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION...1 SYSTEM DESCRIPTION...1

More information

IMPORTANT ATTENTION INSTALLERS:

IMPORTANT ATTENTION INSTALLERS: Power Exhaust Kit for P7TQ, Q7TQ & R7TQ Series INSTALLATION INSTRUCTIONS IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev. Installation Guide DigiTract Two Stage Heat/Cool Comfort Control System Part #DTMAN Rev. February 008 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION... SYSTEM DESCRIPTION... COMPONENT

More information