INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

Size: px
Start display at page:

Download "INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators"

Transcription

1 INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07 A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators This is a premium quality product at a reasonable price, and offers unsurpassed reliability and operating features. The following is a summary of features and capabilities: Genuine 30A DC output rating Output voltage to field: 100V DC 240V AC input Integral automatic build-up circuit works with only 1.5V AC residual Adjustable Excitation voltage limit prevents alternator damage Three-phase or single-phase application Single-phase operating range: 180V to 280V 50/60Hz Three-phase operating range: 180V to 480V 50/60Hz Three-phase sensing circuit Can be used in parallel applications with external CT and burden Very low temperature drift of voltage setpoint Totally solid-state construction (no relays) Premium quality components only are used Extremely rugged design Simplified adjustment of stability for even the slowest of alternators High energy spike protection built-in Ambient air temperature rating of 50 C Generous heatsink for good operating margin at 50 C ambient Solid, easy to use terminals Compact size: 135mm x 135mm x 115mm 1

2 TABLE OF CONTENTS 1. APPLICATIONS 2. LOCATION AND MOUNTING 3. EXTERNAL WIRING 4. OPERATIONAL BEHAVIOUR 5. SET-UP Document Status: Revision B, 9/1/2003 2

3 1. APPLICATIONS This AVR can be used in a number of applications and is designed for maximum flexibility. Alternators of brushless configuration, or with separate exciters are the normal area of application. Slip-ring machines (without exciters) can also be driven provided the current and voltage requirement does not exceed that of the AVR. The maximum voltage output of the AVR is 100V DC with a 240V AC voltage available from the machine, but will automatically deliver any voltage between zero and this figure that the machine requires at any given time. The actual current which the AVR delivers is of course dependent on the machine requirements. A feature of this unit is that an Excitation Voltage limit is presetable on the AVR to allow a limit to be set from 25V DC up to 100V DC. This Excitation Voltage limit function provides underspeed protection as well as protection in the event of other machine faults. The maximum rating of 30A DC with a field resistance of 2 Ohms would imply a voltage of 60V, which is quite OK. In summary, the AVR can be used in applications where the alternator excitation requirement is less than 100V, and a current of less than 30A. The following circumstances will require special solutions which should be obtained from the supplier: a) The field resistance (cold) is less than 2 Ohms. b) The machine output frequency is not 50 or 60Hz. c) The required DC excitation voltage exceeds one third of the AC voltage available to the AVR (e.g. 80V DC on a 240V L-N machine). If this is the case, machine output collapse may occur under sudden overload conditions. d) The required DC excitation voltage is less than 10V. e) The machine has a compound wound DC exciter with subtractive field control (very rare). 2. LOCATION AND MOUNTING Although rugged, it is always advisable to choose the best possible position for mounting the AVR. The following guidelines should be kept in mind: a) The AVR must be mounted on a vertical surface with the cooling fins vertical and the terminal block at the bottom. b) If possible, avoid locations which will expose the AVR to high levels of vibration and/or grease and oil. c) Although generously sized, the heatsink must not be enclosed in such a way as to restrict or contain the surrounding air, especially if the field current requirement is high. The ambient air temperature around the AVR must not exceed 50C. d) Use the mounting channels extruded into the heatsink base for fixing. These are designed for M5 Hex hardware. 3

4 3. EXTERNAL WIRING Follow the wiring diagrams supplied: Standard three - phase; Use drawing AVR Standard single - phase; Use drawing AVR Three phase parallel; Use drawing AVR

5 CAUTION: It is essential for safety reasons that the sensing leads coming from L1, L2, and L3 come directly from the machine output, rather than downstream of switching and protection devices. Partial loss of sensing voltage may cause abnormal drive to the exciter if the power source for the AVR remains intact. If fuses are used in the sensing wires from from L1, L2, and L3, they must be extremely reliable, and not be feeding any other equipment (not even a voltmeter). a) The power source for the AVR is fed to P1. b) Always ensure that the neutral goes to P2 of the AVR. c) For stand-alone Three-phase machines, the sensing terminals L1, L2, and L3 need to be connected to the corresponding 3 lines from the machine. d) For Single-phase machines, BOTH of the sensing terminals L1 and L2 need to be connected to the 240V line from the machine (L3 MUST be left open). e) For Three-phase machines and paralleling, the sensing terminals L1 and L3 need to be connected to phases A and C from the machine (L2 is left open). The paralleling CT then is placed in the B phase of the machine (the one NOT connected to L2). f) Terminals CT1 and CT2 are provided for connection of an external paralleling CT with a external burden resistor connected across it. The CT and Burden resistor should be chosen to produce between 3 and 5V rms at rated kva on the Alternator. CTs with 1 Amp secondaries should be used, and would therefore imply a secondary rating of 5VA for 5V output. As indicated in e) above, the CT monitors the current in B phase of the machine. WARNING: Under NO CIRCUMSTANCES CONNECT an external CT WITHOUT an appropriate burden resistor across it. Failure to observe this will destroy the AVR droop circuitry. g) The last terminal SP is a spare, and is not connected within the AVR. h) The facility for a remote voltage pot has been removed on this version of the AVR. 4. OPERATIONAL BEHAVIOUR 5

6 Although completely solid state (no relays), the AVR has its own build-up circuit and control. A voltage of 1.5 VAC or more is required between P1 and P2, for the build-up circuit to function. Once the build-up begins (and it may occur at any speed), an Excitation limiting circuit prevents over excitation of the machine. This is AVR build-up mode. Once the output frequency reaches a sufficient value, the normal regulation part of the AVR, regulates the machine output voltage without the Excitation limiting circuit coming into play. CAUTION: In build-up mode, the machine output voltage will be lower than normal, and possibly fluctuating due to AVR limiting action. It is important that load devices are not connected to the machine under these circumstances, as they will malfunction due to low voltage and frequency. This is normally standard practice, and dependent on the output control cubicle that the generating set should be fitted with, and is a consideration when using ANY type of AVR. Connection of the load should only be enabled when the alternator output is stable and within limits. 5. SET-UP a) 4-WAY DIP SWITCH It is ESSENTIAL that this switch be configured correctly for successful application of this AVR. A correct setting not only ensures proper operation, but also provides additional equipment protection. i) In deciding what Excitation Voltage limit to set, refer to the nameplate of the alternator. Set an excitation limit value which is just above the nameplate value. ii) In the absence of a nameplate value, run the machine with all switches set to OFF, and measure the no-load Excitation voltage (DC). A DIP switch setting of 3 times this noload value should be ample to drive the machine to full output. If the means are available (load bank), the actual excitation under rated load can be measured, and the setting further adjusted. iii) Note that an Excitation Voltage limit setting set too low can result in the alternator failing to deliver rated output. If the AVR starts to limit during normal machine operation, the alternator output voltage will fall below normal, and begin to fluctuate. iv) Note that an Excitation Voltage limit setting set too high compromises machine protection in the event of underspeed or external faults. v) Familiarise yourself as to which way is ON for the 4 switches in the bank. vi) The Excitation Voltage is limited to its LOWEST possible value with all switches OFF. This minimum value is 25V. The value set by the four switches is then added to the base figure of 25 as follows: SWITCH STAGE ASSOCIATED VALUE WHEN ON V 10V 20V 40V The table below provides a quick means of determining which switch to set for a particular desired Excitation Voltage limit setting: EXCITATION STAGE 1 STAGE 2 STAGE 3 STAGE 4 LIMIT 25V OFF OFF OFF OFF 30V ON OFF OFF OFF 6

7 35V OFF ON OFF OFF 40V ON ON OFF OFF 45V OFF OFF ON OFF 50V ON OFF ON OFF 55V OFF ON ON OFF 60V ON ON ON OFF 65V OFF OFF OFF ON 70V ON OFF OFF ON 75V OFF ON OFF ON 80V ON ON OFF ON 85V OFF OFF ON ON 90V ON OFF ON ON 95V OFF ON ON ON 100V ON ON ON ON AVR-07 b) STABILITY TRIMPOT The trimpot marked STAB (on its own, furthest from the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset to 15 turns clockwise during manufacture (about midway). However, it may well be necessary (and desirable) to adjust this to a more optimum value, depending on the AVR application. FULL CLOCKWISE on this trimpot corresponds to maximum stability (slowest response). FULL ANTI-CLOCKWISE on this trimpot corresponds to minimum stability (fastest response). More clockwise settings will be required to stabilise alternators that are particularly sensitive; that is, requiring relatively low levels of excitation voltage, and a correspondingly low setting for the Excitation Voltage limit. Conversely, more anti-clockwise settings will be required to get response times short enough (for motor starting etc), for alternators that are less sensitive; that is, requiring relatively high levels of excitation voltage, and a correspondingly high setting for the Excitation Voltage limit. The best set-up requires an oscilloscope, however an analogue meter or better still an incandescent globe, give a good indication of response speed and settling time. NOTE: The most critical circumstance to be monitored is UNLOADING (perhaps using the output breaker or similar to drop say 30% of the rated load). If stability problems exist, they will normally occur when the load is removed. c) VOLTS TRIMPOT The trimpot marked VOLTS (left hand one of pair, closest to the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset for 240V Line to Neutral during manufacture. Note that if your application is wired for 3-phase paralleling (sensing terminal L2 left open), it will be necessary to turn this VOLTS trimpot fully anti-clockwise before starting the machine (much lower settings apply for this paralleling AVR connection). 7

8 d) COMP (Droop) TRIMPOT The trimpot marked COMP (right hand one of pair, closest to the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset fully anti-clockwise during manufacture, and can be left there for all nonparalleling applications. This trimpot is only utilised in a paralleling application, and is used to set the quadrature droop. This droop is necessary to ensure proper reactive power sharing between alternators. To set this trimpot and ensure correct external CT wiring etc, you must be able to apply at least 50% of the rated load for the Alternator. For example, if a machine is say 300kVA 0.8 PF, the rated load is 240kW + 180kVAR. In order to set up such a machine for paralleling, you must have at least 120kW + 90kVAR load. Note that although the set up of the AVR can be done with an Inductive load only, the power sharing between prime-movers needs to be checked with resistive load also. The recommended droop for rated load is 5.0V. That is, in going from no-load to rated load, the output voltage should fall from to Line to Neutral. Presuming a 120kW + 90kVAR load is all you have, the droop will only be 2.5V with this load. A good quality DMM will be required. The machine should be run up, and the output voltage trimmed to 245.0V no-load. The load of 120kW + 90kVAR should be applied, and the COMP trimpot turned clockwise. As this trimpot is turned clockwise, the alternator output voltage should FALL, if it increases instead, it will be necessary to stop the set and reverse the wires on the paralleling CT secondary and start again. The COMP trimpot should then be adjusted to achieve the 2.5V Droop (242.5V) at the 50% rated load. This adjustment has to be done (also separately) on the other machine(s) to be paralleled, before their outputs are paralleled. The prime-mover no-load speeds and speed droop characteristics also need to be matched as per the governor manufacturers information prior to placing the machines online together. SALES & SERVICE Please Contact CONTROLPAK P/L 30 Glencairn Street Mulgrave Vic 3170 Ph: Fax: Mob: brian@controlpak.com.au Website: 8

A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-08 A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators This is a premium quality product at a reasonable price, and

More information

MX431 Generator Automatic Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 1 1. SPECIFICATION Sensing Input Voltage Frequency 190 ~ 264 VAC Max, 1 phase, 2 wire 50 / 60 Hz, selectable

More information

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual AVR 63-12 Hybrid Universal Analog Digital Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator For use in Brushless PMG and Auxiliary Winding 1. SUMMARY The AVR 63-12 is a totally

More information

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual ADVR-12 Hybrid Universal Analog Digital Voltage Regulator Operation Manual Adapter plugs for Digital Regulator Self Excited Automatic Voltage Regulator For use in Brushless PMG and Auxiliary Winding 4501

More information

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N. 010 848 389 trading as Power Drive Systems Generator Control Specialists 48A Ainsdale Street Telephone: 0500 800 225 P.O. Box 30 West Chermside, Qld

More information

INSTRUCTION MANUAL FOR

INSTRUCTION MANUAL FOR INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: SR32A Part Number: 9 0750 00 104 Publication Number: 9 0750 00 990 Date: January, 1979 Revision G: March, 1997 SECTION 1 GENERAL INFORMATION 1-1. INTRODUCTION

More information

XR500B Universal Voltage Regulator

XR500B Universal Voltage Regulator XR500B Universal Voltage Regulator The XR500B is a unique voltage regulator that is designed specifically for Professional Electrical Generator Service and Repair Technicians. The XR500B incorporates patented

More information

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages. PM500 Voltage Regulator User Manual A Regal Brand Scan here for other languages. Introduction The PM500 is an encapsulated electronic voltage regulator intended for use with Marathon Generators PMG system.

More information

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number: INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: APR 125-5 Part Number: 9 1688 00 100 Publication Number: 9 1688 00 990 Revision H: 07/2001 CONTENTS SECTION 1 GENERAL INFORMATION...1-1 DESCRIPTION... 1-1

More information

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR 125-5 P/N 9168800100 Publication: 9168800990 Revision: J 03/09 INTRODUCTION This instruction manual provides information about the operation and installation

More information

FAULT FINDING MANUAL. For Stamford AC Generators

FAULT FINDING MANUAL. For Stamford AC Generators FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar

More information

1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ

1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ Installation & Operating Procedures DG2 Series SINGLE PHASE CONVERTERS 1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ TABLE OF CONTENTS 1.0 DESCRIPTION... Pg. 1 2.0 INSTALLATION AND START-UP... Pg. 3 3.0 DRAWING

More information

EA07. Generator Automatic Voltage Regulator Operation Manual

EA07. Generator Automatic Voltage Regulator Operation Manual EA07 Generator Automatic Voltage Regulator Operation Manual Suitable for Single or Three Phase Self Excited Brushless Generator Compatible replacement for Mecc Alte SR-7 * Not a genuine Mecc Alte product.

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE

ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 023 AVR Features ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE AVRs On STAMFORD alternators, analogue AVR

More information

PM300E Voltage Regulator Instruction Manual

PM300E Voltage Regulator Instruction Manual PM300E Voltage Regulator Instruction Manual A Regal Brand 1. INTRODUCTION The PM300E voltage regulator is an encapsulated electronic voltage regulator which controls the output of a brushless AC generator

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

EA16. Generator Automatic Voltage Regulator Operation Manual

EA16. Generator Automatic Voltage Regulator Operation Manual EA16 Generator Automatic Voltage egulator Operation Manual Universal 16Amp elf Excited Automatic Voltage egulator for use in 220 / 380 / 440 / 480 VAC brushless generators with paralleling compatibility

More information

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill) GENERATOR INTERCONNECTION APPLICATION Category 2 (Combined) For All Projects with Aggregate Generator Output of More Than 20 kw but Less Than or Equal to 150 kw Also Serves as Application for Category

More information

DG SYNCHRONIZING &AMF PANEL

DG SYNCHRONIZING &AMF PANEL A 80, Sector 80, Phase 2, Noida 201305, Utter Pradesh, India DG SYNCHRONIZING &AMF PANEL Clients Bharat Petroleum Corp.Ltd PROJECT- DG Synchronization panel with AMF function. Design BY:- Errection By

More information

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual Graham TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual Vari Speed S1000 Instruction Manual TABLE OF CONTENTS Introduction 4 Unit Features 5 Operating Conditions 6 Specifications 7 Ratings

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Also Serves as Application for Category 3 Net Metering (Note:

More information

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1 Model 340i / 680i / 1220i DC drive product manual HG102938 iss 8 1 Sprint Electric Limited, Arundel, UK Tel. +44 (0)1903 730000 Fax. +44 (0)1903 730893 Email. info@sprint-electric.com www.sprint-electric.com

More information

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering

More information

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST

More information

Electric Utility Contact Information Indiana Michigan Power

Electric Utility Contact Information Indiana Michigan Power CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering

More information

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029 Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box 291509, Kerrville, Texas 78029 Phone: 830.895.4700 Fax: 830.895.4703 Email: pwrtron@power-tronics.com Web: www.power-tronics.com

More information

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator SE1500AX Static Exciter The SE1500AX Static Exciter is a 100amp complete static exciter designed to replace older rotary, electronic and magnetic amplifier types of exciters. Installation of the SE1500AX

More information

Single or Double 240VAC motor control for domestic and industrial gates and doors.

Single or Double 240VAC motor control for domestic and industrial gates and doors. COBO30 Double 240V Motor Drive Controller Features For 240Volt Motors Auto Closing Open Only Security Closing and Extended Lock Pulse (user selectable) Travel Timer Push Button Input Photo Cell Input Option

More information

Filtered PWM Speed Control for Permanent Magnet DC Motors

Filtered PWM Speed Control for Permanent Magnet DC Motors Instructions for Installation and Operation Filtered PWM Speed Control for Permanent Magnet DC Motors Model 0794 Speed and Direction Control up to 5/8 HP NEMA-1/IP-20 Specifications Product Type:... WPM-2148E1

More information

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6 FACT sheet Number 9 January 1993 A GUIDE TO FLUORESCENT DIMMING E nsuring good quality fluorescent dimming calls for more than simply using a 'fluorescent' type of dimmer. Many other factors need consideration,

More information

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1 Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG102909 iss 9 1 This drive is an isolated 4 Quadrant speed controller for shunt wound or permanent magnet motors. It utilises speed feedback

More information

Basics of Paralleling

Basics of Paralleling Basics of Paralleling Revised: February 1, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Discuss basic paralleling control functions to gain a better understanding

More information

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR TECHNICAL MANUAL MODEL DVR 2000 AND DVR 2000C FIGURE 1 - FRONT AND REAR VIEW OF VOLTAGE REGULATOR...4 SECTION 1- INTRODUCTION...5 GENERAL DESCRIPTION...5 SPECIFICATIONS...5

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled

More information

CONTROL FEATURES AVAILABLE OPTIONS

CONTROL FEATURES AVAILABLE OPTIONS Vari Speed A2000 TABLE OF CONTENTS Control Features Options Application Data Operating Condition s Control Ratings Chart Mounting Dimensions Installation and Wiring Typical Wiring Diagram Schematic (Block

More information

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER WARNING Disconnect all incoming power before working on this equipment. Follow power lockout procedures. Use extreme caution around electrical

More information

THE BATTERY CHARGER OF RON PUGH

THE BATTERY CHARGER OF RON PUGH THE BATTERY CHARGER OF RON PUGH THANKS IS DUE TO RON PUGH WHO HAS KINDLY SHARED THE CONSTRUCTION DETAILS OF HIS VERY SUCCESSFUL BATTERY CHARGER WHICH IS COP=13 WHEN OPERATING AT 24 VOLTS. IF YOU DECIDE

More information

ABB Softstarter Benefits Charnchanok Thongprad

ABB Softstarter Benefits Charnchanok Thongprad ABB Softstarter Benefits Charnchanok Thongprad tomation Technology Products AB Control - 1 - - Why Softstarters? Benefits for the Electrical network Reduces voltage drops on networks Minimizes starting

More information

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL INTRODUCTION The PM300 voltage regulator is an encapsulated electronic voltage regulator that controls the output of a brushless AC generator by regulating the

More information

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP) Rev. 02/97 SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP) TABLE OF CONTENTS SECTION TITLE PAGE I GENERAL INFORMATION 1 Introduction 1 General Description 1 Model Types 1 Motor

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Made in the U.S.A. NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Nema Enclosed DC Control Specifications Catalog Number BC140 or Features BC138 BC139 BC140-FBR BC154 BC160 BCWD140

More information

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual Operating & Service Instructions Sola Minicomputer Regulators UL White Card Listed Power Supply Classification CSA Certified Transformer Classification General Description and Specifications The Sola Micro/Minicomputer

More information

ESD5500E Series Speed Control Unit

ESD5500E Series Speed Control Unit ESD5500E Series Speed Control Unit 1 SPECIFICATIONS INTRODUCTION PERFORMANCE Isochronous Operation ± 0.25% or better Speed Range / Governor 1-7.5 KHz Continuous Speed Drift with Temperature ±1% Maximum

More information

SE450 Static Exciter Module

SE450 Static Exciter Module SE450 Static Exciter Module The Power-Tronics SE450 Static Exciter Module is a self-contained external rectifier assembly for all Power-Tronics XR and UVR series voltage regulators. The SE450 Static Exciter

More information

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI 250-0287-rev2.qxd 3/12/01 10:27 AM Page a DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D-00-010-AI M/N DC3N-12D-4X-010-AI Instruction Manual D2-3452-1 250-0287-rev2.qxd

More information

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual Electronic Motor Brake Type G Instructions and Setup Manual Table of Contents Table of Contents Electronic Motor Brake Type G... 1 1. INTRODUCTION... 2 2. DESCRIPTION AND APPLICATIONS... 2 3. SAFETY NOTES...

More information

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR User s Manual for The POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR 301 Gaddis Boulevard Dayton, Ohio 45403 U.S. Toll Free 866-261-1191 (937) 253-1191 Fax: (937) 253-1723 Web site: www.stacoenergy.com

More information

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2 RCP200 Series Motor Controls Instruction Manual Model RCP202-000 Model RCP205-000 Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2 You ve just purchased the best! Congratulations! You ve just purchased

More information

XR500D Universal Voltage Regulator

XR500D Universal Voltage Regulator XR500D Universal Voltage Regulator The Power-Tronics XR500D Universal Voltage Regulator is the latest upgrade for all UVR and XR series voltage regulators. The XR500D is also capable of replacing other

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

Euclid Full Voltage Magnet Controller

Euclid Full Voltage Magnet Controller Hubbell Industrial Controls, Inc. Euclid Full Voltage Magnet Controller Instruction & Renewal Parts Manual Instructions/Parts Manual Publication No. 180 Replaces Sept. 1991 4291 & 4295/ 96 Type 4291 Type

More information

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H) 2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved DRM TM DRM-HP TM Electronic Dynamo Regulator INSTRUCTION MANUAL COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved INTRODUCTION The Clover Systems DRM is a state-of-the art all-electronic voltage and current

More information

INDEX Section Page Number Remarks

INDEX Section Page Number Remarks INDEX Section Page Number Remarks Synchronous Alternators 2 4 General Fault Finding Capacitors 5 6 Fault Finding & Testing Diodes,Varistors, EMC capacitors & Recifiers 7 10 Fault Finding & Testing Rotors

More information

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER VARIABLE SPEED DRIVE CONTROLLER INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER With PC101 Torque Limit Control WARNING Disconnect all incoming power before working on this equipment. Follow

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101037 Document revision: A Engineering change number: 105073 Date: 1/13/2006 1840 Industrial Circle

More information

Power Solutions Manager Generac Power Systems, Inc.

Power Solutions Manager Generac Power Systems, Inc. Engine Generator Paralleling Concepts Gen. #1 Gen. #2 Gen. #3 Gen. #4 Gen. #5 Presenter: Daniel Barbersek Power Solutions Manager Generac Power Systems, Inc. RUNNING HEADLINE What Topics Will Be Covered

More information

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet - Winding 06 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international

More information

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code: Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah

More information

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet - Winding 05 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international

More information

SESL H - THREE PHASE AC VOLTAGE STABILISERS & REGULATORS. SESL H SERIES - THREE PHASE to 1500 kva. AC THREE PHASE TO 1500 kva

SESL H - THREE PHASE AC VOLTAGE STABILISERS & REGULATORS. SESL H SERIES - THREE PHASE to 1500 kva. AC THREE PHASE TO 1500 kva SESL H SERIES - THREE PHASE - 200 to 1500 COST EFFICIENT VOLTAGE STABILISATION with fast speed of response, high output voltage accuracy and inbuilt energy saving ability. FEATURES Automatic Voltage Regulation

More information

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3 User Guide 4Q2 0.55-7.5kW D.C.Motor Regenerative Speed Controller Part Number: 0400-0042-03 Issue Number: 3 General Information The manufacturer accepts no liability for any consequences resulting from

More information

PM734E - Winding 28. Technical Data Sheet APPROVED DOCUMENT

PM734E - Winding 28. Technical Data Sheet APPROVED DOCUMENT - Winding 28 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications

More information

Battery Control Center - Diesel

Battery Control Center - Diesel Service Manual CAUTION: All servicing of the Battery Control Center should be done only by a qualified Service Technician. Inadvertent shorts inside the Battery Control Center could result in severe damage

More information

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions Product Manual 82046 (Revision NEW, 1990) Original Instructions 2301A Load Sharing & Speed Control with Dual Dynamics Installation and Operation Manual General Precautions Read this entire manual and all

More information

60 Series Engine Controls

60 Series Engine Controls ECU 60 Series Engine Controls Use CAUTION since you are applying 120VAC RMS to the AC Input terminals and that it is always potentially their during engine run!!! ECU is a registered trademark of Engineering

More information

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator Publication 351-01002-00A, 09/23/05 Instruction Manual Installation Operation Maintenance KCR 760 Voltage Regulator Page 1 Kato Engineering Inc. P.O. Box 8447 Mankato, MN USA 56002-8447 Tel: 507-625-4011

More information

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data TC2000 TC2001 EUROTHERM ONTROLS Two phase thyristor power switches Product data TC2000 TC2001 Thyristor power switches Compact, two phase thyristor power switches for electrical heating applications from

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

Questions Section: Do you have questions that aren't covered? Please contact us!

Questions Section: Do you have questions that aren't covered? Please contact us! Questions Section: 1. What are the screw terminals on the back of my XP600 for? 2. How do I hook up a remote turn-on switch for my XP250 / XP600 / XP1100/ MX series inverter? 3. Can I sell power back to

More information

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending) -1260 & -2460 Generator Auxiliary Excitation ooster Operation Manual (Patent Pending) The -1260/2460 is used to boost motor starting capacity in shunt generators. It achieves boosting power by converting

More information

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2 Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand ( July 14-18, 2007) Lecture on L33-2 By S.N.Singh Senior Scientific officer ALTERNATE HYDRO

More information

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING. C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide WARNING Before troubleshooting any CEN products, the service technician should: read, understand, and agree to follow all information contained

More information

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC Instruction Manual D2-3453 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

EG3000. Generator Electronic Governor Controller Operation Manual

EG3000. Generator Electronic Governor Controller Operation Manual EG3000 Generator Electronic Governor Controller Operation Manual Smoke Limit Control, Idle Speed Control, suitable for Builtin, Non-Built-in and PT Pump Type Actuator. SP POWERWORLD LTD Willows, Waterside,

More information

MGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications

MGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications MGL Avionics AvioGuard Fault protected, wide input range, isolated, DC to DC converter for avionics applications General The MGL Avionics AvioGuard is a fault protected DC to DC converter. It is able to

More information

Expert Design...Trusted Power

Expert Design...Trusted Power Expert Design...Trusted Power 350 750 kva Range Performance I Durability I Serviceability A new power standard has arrived. The 350 750 kva range from FG Wilson is designed by our expert engineers to

More information

KBVF Adjustable Frequency Drive

KBVF Adjustable Frequency Drive INSTALLATION AND OPERATING INSTRUCTIONS KBVF Adjustable Frequency Drive Variable Speed /Soft-Start AC Motor Control with I 2 t Electronic Overload Protection for 3-Phase Induction Motors through 1 HP!

More information

Module 9. DC Machines. Version 2 EE IIT, Kharagpur

Module 9. DC Machines. Version 2 EE IIT, Kharagpur Module 9 DC Machines Lesson 38 D.C Generators Contents 38 D.C Generators (Lesson-38) 4 38.1 Goals of the lesson.. 4 38.2 Generator types & characteristics.... 4 38.2.1 Characteristics of a separately excited

More information

Synchronous motor control. 8/15/2007 Powerflow Technologies Inc 1

Synchronous motor control. 8/15/2007 Powerflow Technologies Inc 1 Synchronous motor control 8/15/2007 Powerflow Technologies Inc 1 PLC Lubrication units Cooling Water DCS PLC Dampers SUB BD Breaker Protection relay Field Application Kiln System Fan Hydraulic Unit Instrumentation

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

Series P255MM/ML Single/Dual Pressure Input Condenser Fan Speed Controllers For Three Phase Motors (incl. built-in RFI suppression filter)

Series P255MM/ML Single/Dual Pressure Input Condenser Fan Speed Controllers For Three Phase Motors (incl. built-in RFI suppression filter) PSC 0108 European Refrigeration Controls Catalogue Catalog Section 4 Product Bulletin Series Single/Dual Pressure Input Condenser Fan Speed Controllers For Three Phase Motors (incl. built-in RFI suppression

More information

EG3002. Electronic Engine Governor Controller User Manual

EG3002. Electronic Engine Governor Controller User Manual EG3002 Electronic Engine Governor Controller User Manual Engine Start Smoke Limiting function & IDLE Speed Setting For External, Built-in, PT-Pump type and hydraulic drive actuators Newly added extreme

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual

INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual Complete Installation and Operating Manual for the MEP 002/003 Auto / Remote Starter for the following MEP Power Generators: MEP 002A/003A/011A/802A/803A/811A

More information

Model NA 2 L

Model NA 2 L Model MP1500@6 2 L Frequency/Speed Voltage Prime Power Standby Power 50HZ/1500 RPM 60HZ/1800 RPM 60HZ/1800 RPM 230/400V 230/400V 277/480V 1500 KVA 1200 KW 1500 KVA 1200 KW 1650 KVA 1320 KW 1650 KVA 1320

More information

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible DC Drives Flexible & Powerful single-phase DC drives provide a complete family solution from the compact Series 2120 chassis drive to the powerful Series 2230 and it s feature rich application specific

More information

Rating Definitions and Conditions

Rating Definitions and Conditions Model Frequency/Speed Voltage Prime Power Standby Power MP13 S MP15@6 S 50HZ/1500 RPM 60HZ/1800 RPM 60HZ/1800 RPM 230/400V 230V/400V 277V/480V 12.5 KVA 10 KW 13.5 KVA 10.8 KW 15 KVA 12 KW 13.75 KVA 11

More information

elabtronics Voltage Switch

elabtronics Voltage Switch elabtronics Voltage Switch Want to trigger a device when a monitored voltage, temperature or light intensity reaches a certain value? The elabtronics Voltage Switch is an incredibly easy way of doing it.

More information

Diesel generator set QSK23 series engine

Diesel generator set QSK23 series engine Specification sheet Diesel generator set QSK23 series engine 545 kw - 725 kw 60 Hz Data Center Continuous Description Cummins commercial generator sets are fully integrated power generation systems providing

More information

SDM72 Start on Demand Modules

SDM72 Start on Demand Modules Capricorn Controls DA04SDM72-2 Revised Design Page 1 of 6 SDM72 Start on Demand Modules Genset Controls - Timers - Monitors - Trips - Battery Charging - Spares & Accessories - Custom Products Application

More information

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved DRM TM DRM-HP TM Electronic Dynamo Regulator INSTRUCTION MANUAL COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved INTRODUCTION The Clover Systems DRM is a state-of-the art all-electronic voltage and current

More information

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited. SERVICE MANUAL ELECTRIC BRAISING PANS (30 & 40 GALLON) VE30 VE40 ML-126849 ML-126850 VE40 SHOWN - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

PI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information