Sidel Therm & CO 2 Counter Instruction & Installation Manual

Size: px
Start display at page:

Download "Sidel Therm & CO 2 Counter Instruction & Installation Manual"

Transcription

1 Sidel Therm & CO 2 Counter Instruction & Installation Manual

2 P.O. Box 1868 Atascadero, CA Fax: Sid Abma, President

3 Table Of Contents System Overview Theory Of Operation Monitoring The Heat Recovered Installation Mounting The Control Box Thermocouples Installation Flow Meter Installation And Operation Controller Settings And Calibration Accessing Parameters Temperature Settings Flow Settings Controller Settings Change Password Setting The Date And The Time Schematics Page 3

4 System Overview Theory of operation The Sidel SRU flue gas recovery unit is designed to recover almost all of the waste exhaust heat and turn it into usable heat. The waste flue gases from the boiler are redirected to the SRU recovery unit, which is placed beside the boiler or alongside the chimney. The Sidel SRU flue gas condenser unit cools the flue gasses to the point where the sensible as well as the latent heat is recovered. The Sidel SRU series is designed so that flue gas temperatures can be lowered well below the dew point temperature of 58 C or 136 F. When the temperature of the waste flue gas is lowered beyond 133 F, condensation starts to occur. Naturally the lower the flue gases can be cooled, the higher the performing efficiency of the waster heat recovery unit. The waste heat recovery unit is designed for natural gas or propane fired equipment only. The vertical construction of the SRU waste heat recovery unit provides for the best possible use of available space. Installation alongside a 110,000 lb/hr boiler Page 4

5 Monitoring the Heat Recovered In order to quantify the amount of heat recovered, Sidel Systems in conjunction with Helman Automation, has created the Sidel Therm and CO2 Counter. This is an industrial PLC capable of continuously storing data which shows how much energy is being saved by the SRU Flue Gas Condenser. The Therm and CO2 Counter control unit has two major components: the HMI (human machine interface), and the PLC (programmable logic units). The HMI displays all the important information, is the gateway to change parameters, and can communicate collected data to other terminals via the internet. One of the greatest advantages of the system is its capability to be adapted to the monitoring needs of the customer. The system can be programmed to perform all the automation control, data acquisition, and data storage. Page 5

6 The Sidel Therm and CO2 Counter works in a similar way to any utility meter, with the exception of an additional audible buzzer which sounds in response to any occurring hazard that may occur. The display screen shows the amount of energy being recovered as well as other vital information such as the temperature at several critical points, water flow, chimney valve position, and with it monitor any other information required to protect the SRU from damage. Any data that registers out of normal range will set off an alarm. The HMI used in the Sidel Therm and CO2 Counter has all the latest technology, such as: a high resolution touchscreen, Ethernet, USB and serial port connections. This allows the data collected to be displayed on any computer in the company. The HMI can be customized to display in either Metric units or British units and also can be programmed for Multi languages. This feature is very useful to see graphically how the changes of each parameter affect the heat recovery process Page 6

7 History Screen Trending Screen Page 7

8 How the monitor works: From 4 sensors that are inserted into the pipes connected to the Sidel SRU Flue Gas Heat recovery Unit, the Therm and CO2 Counter takes the temperature of: Water flowing into the SRU unit. Water flowing out of the SRU unit. Flue gas flowing into the SRU unit. Flue gas flowing out of the SRU unit. From the water flow sensor inserted into the water intake pipe, the PLC receives the rate of water flowing through the SRU in Gallons per minute (GPM). This data is received by the PLC in 5 second intervals and is displayed on the screen. The PLC calculates the Delta T in BTU s, and the flow rate in GPM and displayes the resulting calculation as BTU s saved every 5 seconds. From these figures it is possible to see, in real time, exactly how the SRU is performing. This information is also saved as history in the PLC memory and can be displayed on the History Screen. By using the touch screen the operator can open and close the Chimney Valve, control the alarm function, set the system, and navigate between the displays. The displayed calculations also can be sent over the internet or intranet to be displayed on any computer within the company. This gives the Sidel SRU a unique advantage in providing real time cost savings analysis that can be used by managers to prove that their company is reducing greenhouse gas emissions and using their energy efficiently. Installation Mounting the Control Box The control box is a NEMA 12 with dimension of 14 x16 x8. The box can be flush mounted to a wall or a post with 4 screws of ¼ diameter. The control box will require power of 120 V ac. To comply with NEC the power shall be supplied with 2 #12 wires and a #14 ground green wire This picture shows the power 120 VAC point of connection. Page 8

9 run with EMT, or liquid tite conduit. If the unit is equipped with a chimney valve control, the box will require also the installation of a compressed air valve of 80 PSI or more, or wiring to the chimney valve as per actuator requirements. Thermocouples installation Thermocouple probes are the preferred temperature sensor used for the Sidel Therm and CO2 Counter, because they provide a large temperature range and are durable. The probe tip is composed of two alloys welded together which makes them almost indestructible. The Sidel SRU unit provides ½ NPT threaded couplings for therm couple installation. One, for each water inlet and outlet, and one for each flue gas exhaust inlet and outlet. The sensors provided with the unit are made of stainless steel. Make sure to use Teflon tape or pipe sealant for sealing the fitting, especially for the water pipe. In most cases we will provide the NB4 with a sub-miniature aluminum head and a SS ½ NPT thread bushing. It has an internal terminal block for probe connection. The J type thermocouple is composed of two wires; the White wire is the (+) and the Red wire is the (-). Sidel provides 250 ft. of cable to connect the 5 sensors to the controller. This 2 wire shielded cable has one black wire and one red wire. The black wire is to be connected to the white (+) in the probe terminal and the red to the red (-) in the probe terminal. The length of the cable has little effect in the accuracy of the temperature but it is very important to isolate the routing of the cables to the control box from electrical noises to diminish fluctuation on the temperature readings. The probe comes precalibrated. Each probe will be delivered labeled for the port where it will be installed. The following picture depicts the connection to the probe terminal: Page 9

10 Notice the black wire is connected to the white wire of the thermocouple. The connection to the control box is marked clearly with color terminals. Each thermocouple has red and white terminals. Notice the white terminal is connected to the black wire of the thermocouple probe cable. The terminal connections are organized from right to left; the first is the water inlet, the second is the water outlet, the third is the exhaust inlet and the fourth is the exhaust outlet as shown in the picture. This is for the standard Sidel SRU unit. (The installation of a Sidel SRU Combi will be described in a separate manual.) Page 10

11 Flow Meter Installation and Operation Operation: The paddle wheel sensor measures the flow at of water in the pipe. Fluid moving in a pipe does not all flow at the same velocity. Toward the center of the pipe, fluid moves faster than at the wall and the relationship between the two changes as the overall flow rate increases. The recommended depth settings have been carefully chosen to minimize this source of error, and should be followed, especially in the smaller pipe sizes. Installation of the sensor: The flow meter IP100/200 series Cold Water Inlet #1 Heated Water Outlet #2 Flue Gas Exhaust Inlet #3 are adjustable depth insertion paddle-wheels. These models are designed to fit 2 to 48 pipe. Installation fittings are standard 1-1/2 or 2 NPT. Ruby bearings and a non-drag hall-effect sensor give these meters the widest flow range of any of the paddle wheel types. A sensor detects the passage of miniature magnets in the six rotor blades. The resulting square wave signal can be sent for hundreds of feet over unshielded cable without the addition of a transmitter. This cable can be connected directly to the PLC (programmable logic controller) for the flow measurement. The hot-tap models (IP115/215) can be installed or serviced without shutting down the line by means of a 2 full-port isolation valve that comes with a nipple for installation on the pipe fitting. In most circumstances, no special tool is required. Flue Gas Exhaust Outlet #4 Page 11

12 The picture bellow depicts the IP115/215 equipped with the service ball valve. Page 12

13 Specifications: Piping: For best results, the IP sensor should be installed with at least ten diameters of straight pipe upstream and five downstream. If the installation allows obtaining greater distances, then the result should be optimum. Page 13

14 See Straight Pipe Recommendations: Page 14

15 Horizontal is the preferred installation orientation, since it improves lowflow performance and avoids problems with trapped air. Bottom, top, and vertical pipe installation are all acceptable. Page 15

16 See Full Pipe Recommendations: These are several types of Full Pipe Recommendations: Page 16

17 Fitting and Meter Installation: The sensor comes with a 1-1/2 male NPT pipe thread adapter fitting. Loosen the compression nut so the adapter slides freely. Pull the meter fully upward and finger-tighten the compression nut. Do not over tighten. Now loosen the compression nut, lower the meter to the appropriate depth setting. The depth setting parameters are given by the combination of the preceding Tables. Be sure flow is in the direction of the arrow on the housing, then tighten compression nut fully. Page 17

18 Sensor without the service ball valve: Sensor with the service ball valve: Page 18

19 Sensor Depth Setting: It is important for accuracy that the sensor be inserted to the correct flow direction and depth into the pipe. Page 19

20 To find the distance D first, find the Dimension C from Table 1 corresponding to the model of sensor and the size of pipe. Then subtract the wall thickness of your corresponding size and type of pipe you use from Table 2. D is the distance measuring from the outside of the pipe to the joint in the housing, as shown in the diagram above. Adjust the sensor to Dimension D and hand-tighten compression nut. Align the strain relief housing with the center line of the pipe where the arrow on the housing points in the direction of the flow as shown in the diagram above. Page 20

21 Electrical connection: The sensor connection is very simple and straight forward. The IP115/215 come equipped with 18 ft. of cable. The 3 wires cable comes with color coded wires as shown in the picture below: Page 21

22 The picture above shows the terminal numbers to which each of the flow meter cables needs to be connected: Flow Calibration: In order to properly process pulses from the flow sensor, a number must be enter in the Operator Interface Terminal. This number, is called the K factor, and is the number of pulses the sensor puts out per unit of fluid passing through the pipe. For the sake of practicality the K factor given on Table 3 will be Pulses per Gallons. To set the K factor in the controller follow direction provided in Table 3. Page 22

23 For example, if 4 copper tubing (type L) is been used, then the K factor to be set is: pulse per gallon. This value has to be entered in the Flow Adjustment Menu. The value to be entered should be 1785 without the decimal point. Page 23

24 Repair and Parts of Sensor: The flow sensor has only one moving part, the rotor. If this is turning properly and there is no signal, the Hall-effect sensor is not operating properly. In order to test the sensor for signal, once the sensor is removed from the pipe for service, gently rotate the paddlewheel. Observe if the input signal X0 in the PLC flicked or goes from turning on and off to see if the Hall Effect changes state. If X0 changes state then the sensor is operating properly. Parts Explosion: Page 24

25 Page 25

26 Controller Settings and Calibration Accessing Parameters To enter the K factor the user should press the Settings button from the main screen. This will access the flow parameters. Once you press the Settings button the user is required to entered the security Password. This password can be set or changed by the user at any time. Warning!!! any changes made on any category of the setting menu will have a drastic effect in the way the Therm and CO 2 Counter will control or monitor the Sidel Flue Gas Condenser. Only authorized personnel should be accessing this feature of the Therm and CO 2 Counter. Main screen Setting button Page 26

27 The following is the Password screen where the user will enter the password by touching the green window. After the cursor is active in the Green window the keypad becomes active and a number can be entered. To save the password the ENT key needs to be pressed. To clear press the CR key. The password can be any number between 1111 to as shown in the picture below. When the correct password is entered the Setting Menu screen opens as shown in the picture Page 27

28 Temperature Settings It is important to calibrate all the temperature probes before installation. Since the probes are not perfectly the same when they are shipped from the factory, it is necessary to adjust the temperature offsets of each probe. Helman Automation will calibrate all sensors for all new installations so that recalabration is not required. The adjustment instructions are shown on the screen for convenience. Generally the slope for the J type thermocouples are almost identical, so the only parameters to be calibrated are the Offsets because they might differ a couple of degrees. To accomplish this calibration, the probes must be placed in a container with water at room temperature. This will allow a uniform temperature among the probes. At this point a well calibrated thermometer needs to be used as a reference. Once the temperature is stabilized, then enter the temperature of the reference thermometer in the green window. As the final step press the SINCRONIZE button. Now the program will set all of the probes to the same temperature. Page 28

29 Flow Settings Once the K factor is obtained from Table 3, enter this number as shown below. In this example the K factor used is for a 4 type L copper pipe which is pulse per gallon. The number entered must not have decimal point as shown in the picture. Controller Setting The Therm Counter comes preprogrammed to perform energy monitoring and to automatically control the opening and closing of the chimney valve as well all the safety alarms. This feature must be activated as shown in the picture. After pressing the green button, the message will indicate the Chimney Valve Control is activated. Page 29

30 Change Password To set a new password the user needs to enter a number that is easy to remember and should be at least 4 digits between 1111 to Setting the Date and the Time If the Date and Time shown in the main screen are not correct then they need to be corrected. To correct them select the Setting Date/Time button to access the following screen. Touch any green window to change any parameter and the input keypad will popup then press the appropriate value and press enter. Page 30

31 Page 31

32 Page 32

33 Schematics This system shows an optional diagram with a recirculation pump. Page 33

34 Notes Page 34

35 Page 35

36 Page 36

TX101/201 Insertion Turbine Instructions

TX101/201 Insertion Turbine Instructions TX101/201 Insertion Turbine Instructions General Information Ruby bearings and a non-drag pick-off give these adjustable insertion turbine flow sensors a wide flow and long life. A sensor detects the passage

More information

SERIES TBS INSERTION TURBINE TBS-0XX TBS-1XX

SERIES TBS INSERTION TURBINE TBS-0XX TBS-1XX F- SERIES INSERTION TURBINE instructions -0XX -1XX Table of Contents GENERAL INFORMATION General Information Features, Specifications... Page 1 Installation Piping, Immersion, Positioning the Meter...

More information

TX101/201 Insertion Turbine Instructions

TX101/201 Insertion Turbine Instructions TX101/201 Insertion Turbine Instructions General Information Sapphire bearings and a non-drag pick-off give these adjustable insertion turbine flow sensors a wide flow and long life. A Hall-effect device

More information

TX 115/215 Hot-tap Insertion Turbine Instructions

TX 115/215 Hot-tap Insertion Turbine Instructions TX 115/215 Hot-tap Insertion Turbine Instructions General Information These hot tap versions of the proven TX insertion flow sensors are designed to install or be serviced without depressurizing the pipe.

More information

TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX101/201 TX115/215 ISO 9001:2008 CERTIFIED COMPANY

TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX101/201 TX115/215 ISO 9001:2008 CERTIFIED COMPANY TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX101/201 TX115/215 ISO 9001:2008 CERTIFIED COMPANY TABLE OF CONTENTS General Information Features, Specifications...Page

More information

TX115/215 Hot-tap Insertion Turbine Instructions

TX115/215 Hot-tap Insertion Turbine Instructions TX115/215 Hot-tap Insertion Turbine Instructions General Information These hot tap versions of the proven TX insertion flow sensors are designed to install or be serviced without depressurizing the pipe.

More information

Low Profile Insertion Vortex

Low Profile Insertion Vortex Low Profile Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 24 Heavy Duty & Maintenance Free

More information

TX100/200-SERIES INSERTION TURBINE. T X / S E R I E S I N S E R T I O N T U R B I N E instru c tions TX101/201 TX115/215

TX100/200-SERIES INSERTION TURBINE. T X / S E R I E S I N S E R T I O N T U R B I N E instru c tions TX101/201 TX115/215 INSERTION TURBINE instructions T X 1 0 0 / 2 0 0 - S E R I E S I N S E R T I O N T U R B I N E instru c tions AR CH IV ED TX100/200-SERIES TX101/201 TX115/215 Table of Contents General Information Features,

More information

BI-DIRECTIONAL INSERTION FLOW TRANSDUCER

BI-DIRECTIONAL INSERTION FLOW TRANSDUCER DUALPULSE BI-DIRECTIONAL INSERTION FLOW TRANSDUCER INSTRUCTION MANUAL DUALPULSE LOCK 1.1 General arrangement Thank you for purchasing a Dualpulse Flowmeter. It is important that you read this manual to

More information

Hot Tap Insertion Vortex

Hot Tap Insertion Vortex Hot Tap Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 48 Heavy Duty & Maintenance Free Design

More information

TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX :2008 ISO CERTIFIED COMPANY TX80-SERIES FLOW SENSOR INSTRUCTIONS

TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX :2008 ISO CERTIFIED COMPANY TX80-SERIES FLOW SENSOR INSTRUCTIONS TX80-SERIES FLOW SENSOR INSTRUCTIONS TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX82 9 001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Specifications, Features...Page 1 Installation

More information

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL.

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL. LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL www.enoscientific.com Eno Scientific PO Box 1586 Hillsborough, NC 27278 USA www.enoscientific.com 910-778-2660 Copyright Notice Copyright 2015 Eno

More information

EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX :2008 ISO CERTIFIED COMPANY

EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX :2008 ISO CERTIFIED COMPANY EX100/200-SERIES INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX250 9 001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General

More information

BI-DIRECTIONAL INSERTION METER

BI-DIRECTIONAL INSERTION METER BI-DIRECTIONAL INSERTION METER INSTRUCTION MANUAL LOCK 1 Contents CONTENTS PAGE 1.0 INTRODUCTION 1.1 General arrangement 2 1.2 Overview 3 1.3 Operating principal 3 1.4 Specifications 3 2.0 INSTALLATION

More information

Model FVP General Specification. Flanged Vortex Plate. Product Features

Model FVP General Specification. Flanged Vortex Plate. Product Features Flanged Vortex Plate Product Features Our Inline meters can measure Steam, Gases or Liquids. Measures two times lower than any other Vortex Meter. Heavy Duty & Maintenance Free Design C&C Machined from

More information

IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS IP80-SERIES FLOW SENSOR INSTRUCTIONS IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP82 9 001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Features, Specifications...Page 3 Installation

More information

SeaMetrics Flow Meters and Flow Computers

SeaMetrics Flow Meters and Flow Computers Distributed Products Fact Sheet and Flow Computers WTP-PVC body turbine flow meter WT-S Stainless steel body turbine flow meter TX115/215 Hottap insertion turbine flow meter FT420 Looppowered flow computer

More information

Vortex Plate. Model VP General Specification. Product Features

Vortex Plate. Model VP General Specification. Product Features Vortex Plate Product Features Our Inline meters can measure Steam, Gases or Liquids. Heavy Duty & Maintenance Free Design C&C Machined from one piece of solid stainless steel Absolutely NO o-rings or seals

More information

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS IP80-SERIES FLOW SENSOR INSTRUCTIONS IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP820 9001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Features, Specifications...Page 3 Installation

More information

Insertion turbine INSTRUCTION SHEET. TECHNICAL PRODUCT

Insertion turbine INSTRUCTION SHEET.   TECHNICAL PRODUCT TECHNICAL PRODUCT INSTRUCTION SHEET Insertion turbine OVERVIEW These insertion flow transducers provide a cost effective and simple means of measuring the flow of a wide range of low viscosity liquids.

More information

C.W. COX COMPANY a product line of Perfecto Products, Inc

C.W. COX COMPANY a product line of Perfecto Products, Inc C.W. COX COMPANY a product line of Perfecto Products, Inc MANUFACTURERS OF PRECISION INSTRUMENTS FOR WATER FLOW MEASUREMENT HALL FLOWMETER The Hall Flowmeter is a modified pitot tube which averages the

More information

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP800-SERIES FLOW SENSOR INSTRUCTIONS

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP800-SERIES FLOW SENSOR INSTRUCTIONS -SERIES FLOW SENSOR INSTRUCTIONS -Series FLOW SENSOR INSTRUCTIONS IP810 IP820 9001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Features, Specifications...Page 3 Installation Insertion

More information

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES FLS F6.60 MAGMETER FLOW SENSOR The new F6.60 and F6.63 are flow meters without moving mechanical parts which can be applied for the measurement of dirty liquids so long as they are conductive and homogeneous.

More information

Operating Manual Model- P282 Digiflow Controller

Operating Manual Model- P282 Digiflow Controller Operating Manual Model- P282 Digiflow Controller Totalizer mode Controller 00.00 LPH 0000000.0 L t s SET SCL ENT Model- P282 Tecnical specification of flow sensor P812 Flow Rate Range : 0.5 to 5 m/s (1.6

More information

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:TRQSMAN16 Table of Contents Contents Table of Contents... 2

More information

Specification: Industrial Mixing Center

Specification: Industrial Mixing Center Specification: Industrial Mixing Center Model: IMC40 Article I. General Specifications: Section 1.01 The assembly shall be pre-piped with performance matched components and pressure tested before delivery.

More information

T21 Thermal Differential Switch

T21 Thermal Differential Switch T21 Thermal Differential Switch General Instructions The T21 Point Level Switch is a state-of-the-art in liquid level and interface measurement and control. Level detection is accomplished by using a high-resolution

More information

NC State University Design and Construction Guidelines Division 23 Energy Management

NC State University Design and Construction Guidelines Division 23 Energy Management 1.1 Purpose A. The following guidelines provide the methodology and requirements to assure that designs meet NC State standards for campus utility metering. 2.1 General Requirements A. Meters shall have

More information

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA IP800-Series Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA ISO 9001:2008 Certified Company TABLE OF CONTENTS General Information General Information...Page 3 Features...Page 3

More information

PORTAGAUGE 4 USER MANUAL

PORTAGAUGE 4 USER MANUAL PORTAGAUGE 4 USER MANUAL Contents 1. Introduction and Key Features 1.1 What does the Portagauge do? 1.2 The Portagauge 4 1.21 The Portagauge 4 Unit and Measuring Screen 1.22 The Portagauge 4 Definition

More information

General Information... Temperature/Resistance Table... Part Numbering Examples for RTD s. High Temperature MgO Elements (RA)...

General Information... Temperature/Resistance Table... Part Numbering Examples for RTD s. High Temperature MgO Elements (RA)... Page General Information... Temperature/Resistance Table... Part Numbering Examples for RTD s High Temperature MgO Elements (RA).... Leadwire Style RTD s (RB).. Leadwire Style RTD s (RD, RE, RF, or RG

More information

Multiple vacuum pumps and associated equipment ASME air receiver NEMA 12 multiplex control panel

Multiple vacuum pumps and associated equipment ASME air receiver NEMA 12 multiplex control panel GENERAL The Powerex laboratory vacuum system is designed to create a suction system to remove unwanted fluids or gases from laboratory working areas. The laboratory vacuum system package is compliant with

More information

MULTI-JET WATER METERS

MULTI-JET WATER METERS MULTI-JET WATER METERS INSTALLATION INSTRUCTIONS General Information Technical Data 3 Features 3 Applications 3 Dimensions 3 Pulse Rate 3 Pressure Loss Curve 3 Shipping Weight 3 Installation Position 4

More information

Q35 Series Automatic Vent Damper System

Q35 Series Automatic Vent Damper System Installation Sheets Manual 121 Energy Conservation and Miscellaneous Kits Section Q Technical Bulletin Q35 Issue Date 0999 Q35 Series Automatic Vent Damper System Figure 1: Q35 Automatic Vent Damper System

More information

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual Mechanical Specifications Flow Meter with Polypropylene Body (ES version) Maximum Operating Pressure: 150 PSIG Maximum

More information

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0312 Rev B TABLE OF

More information

GENERAL INFORMATION MECHANICAL INSTALLATION PRESSURE INDEPENDENT VALVES 2-1/2"-10" MVP INSTALLATION & OPERATION INSTRUCTIONS UNION CONNECTIONS

GENERAL INFORMATION MECHANICAL INSTALLATION PRESSURE INDEPENDENT VALVES 2-1/2-10 MVP INSTALLATION & OPERATION INSTRUCTIONS UNION CONNECTIONS GENERAL INFORMATION INSTALLATION & OPERATION INSTRUCTIONS 1. Clean the lines upstream of valve particles larger than 1/16" diameter (welding slag, pipe scale and other contaminants). Griswold Controls

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

ProSeries NEMA 4X SONIC-PRO. Engineering and Technical Data. Transit Time Ultrasonic Flowmeter. Industries, Ltd. s Ultrasonic Flow Meters

ProSeries NEMA 4X SONIC-PRO. Engineering and Technical Data. Transit Time Ultrasonic Flowmeter. Industries, Ltd. s Ultrasonic Flow Meters ProSeries by Blue-White Industries, Ind. Ltd. Industries, Ltd. s SNIC-PR s SNIC-PR s S4 Transit Time Ultrasonic Flowmeter ½ thru 2 diameter Pipe Sizes Inline spool piece Advanced communications Data logging

More information

Model 5000 Vortex Meter

Model 5000 Vortex Meter Model 5000 Vortex Meter Installation and Instruction Manual Table of Contents General Information... 1 1-1 General... 1 1-2 Principles of Operation... 1 1-3 Sensor Operation... 1 1-4 Calibration Factor...

More information

Manifold QF. Contents. Description. Installation & Setup Guide. Safety 3. Introduction 3. Installation Standards 4. Specifications 5.

Manifold QF. Contents. Description. Installation & Setup Guide. Safety 3. Introduction 3. Installation Standards 4. Specifications 5. Contents Description Page Safety 3 Introduction 3 Installation Standards 4 Specifications 5 Materials 5 Overall System Configurations 6 Manifold Installation 7 Fixing Unit to Wall 7 Water Connection 8

More information

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:PADDLEMAN082416 Mechanical Specifications Flow Meter with Polypropylene

More information

ATi Max Series. Pressure Independent Control Valves 2 Way 2-1/2-6

ATi Max Series. Pressure Independent Control Valves 2 Way 2-1/2-6 The Auto Touch Independent Max (ATiMX) valve brings pressure independent control technology to valves up to 6 and flow rates up to 468 GPM. It is a state-of-the-art control valve combining a high quality/

More information

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA IP800-Series Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA ISO 9001:2008 Certified Company TABLE OF CONTENTS General Information General Information...Page 3 Features...Page 3

More information

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value.

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value. E X S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s EX Series Electromagnetic FLOW SENSOR instructions EX EX The Leader in Flow Meter Value. Table of Contents General

More information

TX800-Series FLOW SENSOR INSTRUCTIONS. TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TX800-SERIES FLOW SENSOR INSTRUCTIONS

TX800-Series FLOW SENSOR INSTRUCTIONS. TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TX800-SERIES FLOW SENSOR INSTRUCTIONS TX800-SERIES FLOW SENSOR INSTRUCTIONS TX800-Series FLOW SENSOR INSTRUCTIONS TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Generial Information, Features...Page 3 Specifications...Page

More information

Oil & Gas Lubrication Systems

Oil & Gas Lubrication Systems RVmist Oil Mist Generator Oil & Gas Lubrication Systems The New Generation of Oil Mist Lubrication Systems RVmist Oil Mist Generator Thanks to the latest advances in control and operation technology, the

More information

Tracer VM with User Interface

Tracer VM with User Interface Tracer with User Interface Flowmeter with FCI (Fluid Characteristic Indication) Operating Instructions General The Tracer Flowmeter provides: 0 to 5V or 0 to 10V Selectable Analog Flow Output 0 to 5V or

More information

Tracer VMA with AutoReg

Tracer VMA with AutoReg Tracer with AutoReg Flowmeter with Automatic Flow Regulation Operating Instructions RoHS Compliant General The Tracer Flowmeter with AutoReg provides: Analog Flow Output (Selectable 0 to 3.5V, 0 to 5V

More information

Appendix. Clearance. Skewed profiles. Application Schematics

Appendix. Clearance. Skewed profiles. Application Schematics Appendix Application Schematics The purpose of the application schematics is to show different applications and the best sensor location for a particular application. Clearance Because the sensor will

More information

RIM20 Rotor Insertion Flowmeter

RIM20 Rotor Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Model 1000 Vortex Meter

Model 1000 Vortex Meter Model 1000 Vortex Meter Installation and Instruction Manual Table of Contents General Information... 1 1-1 General... 1 1-2 Principles of Operation... 1 1-3 Sensor Operation... 1 1-4 Calibration Factor...

More information

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82 E X S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s EX Series Electromagnetic FLOW SENSOR instructions EX EX The Leader in Flow Meter Value. Table of Contents General

More information

Time Delta S Fixed Transit-Time Flow Meter System

Time Delta S Fixed Transit-Time Flow Meter System Fixed Transit-Time Flow Meter System Key Features Dynamic flow correction Simple configuration Digital outputs Enhanced anti-bubble measurement technology (ABM) Rugged and reliable Maintenance free The

More information

Axial Turbine Flow Sensor Series Turbotron VTH 25 / VTI 25 / VTM 25

Axial Turbine Flow Sensor Series Turbotron VTH 25 / VTI 25 / VTM 25 Installation Instruction Axial Turbine Flow Sensor Series Turbotron VTH 25 / VTI 25 / VTM 25 Table of contents Page 1 Function of Turbotron 1 2 Safety instructions 2 3 Important notes and requirements

More information

F-1500 SERIES INSERTION TURBINE FLOW METER

F-1500 SERIES INSERTION TURBINE FLOW METER F-1500 SERIES INSERTION TURBINE FLOW METER APPLICATIONS Saturated steam Hot water to 450 F (232 C) standard 850 F (454 C) optional Applications with optional pressure sensor Superheated steam to 450 F

More information

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual COMPANY Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:SANITARYMAN16 Mechanical Specifications Measuring Accuracy ± 1.0%

More information

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations. Signet 50 High Performance Flow Sensor English *3-50.090* 3-50.090 C 05/06 English SAFETY INSTRUCTIONS 1. Do not remove from pressurized lines.. Do not exceed maximum temperature/pressure specifi cations.

More information

ISTEC MAGNETIC METERS

ISTEC MAGNETIC METERS ISTEC MAGNETIC METERS MEASURE ANY CONDUCTIVE LIQUIDS OR SLURRIES (EVEN ABRASIVE OR CORROSIVE) WITH THE NEW MICROPROCESSOR-BASED MAGNETIC METER -- A QUALITY PRODUCT - SIMPLE - RELIABLE - AT AN AFFORDABLE

More information

mass flowmeter for compressed air

mass flowmeter for compressed air mass flowmeter for compressed air VARIOMASS LC pressure and temperature compensated flowmeter easy and cost effective installation of the senor no pressure loss caused by the sensor no moving parts, i.e.

More information

Liquid Turbine Flowmeter

Liquid Turbine Flowmeter NUFLO Liquid Turbine Flowmeter User Manual 167018 Explosion-proof for use in Class I, Division I, Groups A, B, C, D Hazardous Environments ANSI 12.27.01-2003 Single Seal Part No. 9A-100062201, Rev. 01

More information

Product Instructions. Mixing Station. Features. Specifications. Materials

Product Instructions. Mixing Station. Features. Specifications. Materials Mixing Station The Viega Mixing Station provides supply water temperature modulation when connected to a variety of heat sources such as conventional or condensing boilers, water heaters, or geothermal

More information

Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water

Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water Rev: 08/19/2013 (ATiMX) Features Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water The Auto Touch Independent Max (ATiMX)

More information

Inline Flow meter for compressed air and gases DN15 (1/2 ) - DN80 (3 )

Inline Flow meter for compressed air and gases DN15 (1/2 ) - DN80 (3 ) EE771/EE772 Inline Flow meter for compressed air and gases DN15 (1/2 ) - DN80 (3 ) The inline flow meter EE771/EE772, based on the measurement principle of thermal mass flow, is ideally suited for the

More information

flow measurement solutions RIM10 series rotor insertion flowmeters

flow measurement solutions RIM10 series rotor insertion flowmeters flow measurement solutions RIM10 series rotor insertion flowmeters R I M 1 0 RIM10 series rotor insertion flowmeters Versatile enough for almost any challenge Spirax Sarco s RIM10 rotor insertion flowmeters

More information

Priming Systems Installation Instructions

Priming Systems Installation Instructions Priming Systems Installation Instructions System Components: Single Priming Pump: Single VAP Valve Systems: Control Panel Activated... 2 Auto Prime (Pressure Switch) Activated... 3 Multiple VAP Valve Systems...

More information

EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX :2008 ISO CERTIFIED COMPANY

EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX :2008 ISO CERTIFIED COMPANY EX80- SERIES ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX83 9 001:2008 ISO CERTIFIED COMPANY TABLE OF CONTENTS General Information Features,

More information

From. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951)

From. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951) SPI Mag MODEL 282L SINGLE POINT INSERTION ELECTROMAGNETIC FLOW METER 2 SENSOR SUBMITTAL PACKAGE From McCROMETER, INC. 3255 WEST STETSON AVENUE HEMET, CA 92545 Phone (951) 652-6811 Toll Free (800) 220-2279

More information

WP37 & HT37 User Manual

WP37 & HT37 User Manual WP37 & HT37 User Manual Origio WP37 & HT37 Warming Plates & Heated Trolley Warming Plates WP37 300 WP37 500 Heated Trolley HT37 Origio WP37 Component Description Heated work surface Model WP37 300 Power

More information

VIM20 Vortex Insertion Flowmeter

VIM20 Vortex Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Hydro-Flow Model 3100

Hydro-Flow Model 3100 Hydro-Flow Model 3100 Installation and Operation Guide installation and operation guide Contents: Understanding Your Flow Meter... 1 Identifying Your Flow Meter...2 Installing Your Flow Meter...3,4 Making

More information

General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual

General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual General Oceanics Inc. 1295 N.W. 163rd Street Miami, Florida 33169-5887 Fax: (305) 621-1710 Phone: (305) 621-2882 Email: sales@generaloceanics.com

More information

SECTION METERS AND GAGES FOR PLUMBING PIPING

SECTION METERS AND GAGES FOR PLUMBING PIPING PART 1 GENERAL 1.01 SECTION INCLUDES A. Positive displacement meters. B. Flow meters. SECTION 22 0519 METERS AND GAGES FOR C. Pressure gages and pressure gage taps. D. Thermometers and thermometer wells.

More information

F-2700 SERIES INSERTION VORTEX FLOW METER

F-2700 SERIES INSERTION VORTEX FLOW METER F-2700 SERIES INSERTION VORTEX FLOW METER APPLICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260

More information

Auxiliary Equipment. Option #397-12A Single Remote Pumping Unit (with Standard Pump & Motor) Duplex Remote Pumping Unit Option #397-12B

Auxiliary Equipment. Option #397-12A Single Remote Pumping Unit (with Standard Pump & Motor) Duplex Remote Pumping Unit Option #397-12B Auxiliary Equipment Option #397-12A Single Remote Pumping Unit (with Standard Pump & Motor) Duplex Remote Pumping Unit Option #397-12B 230 Fill Station AX-1 REMOTE PUMPING UNIT Option #397-12A Single Remote

More information

INSTALLATION MANUAL FSS1 HIGH SECURITY DOOR MONITORING SENSOR

INSTALLATION MANUAL FSS1 HIGH SECURITY DOOR MONITORING SENSOR INSTALLATION MANUAL 1. INTRODUCTION The FSS1 is a patented device designed to provide a high security door position monitoring solution. It is the ideal higher security replacement for traditional balanced

More information

VIM20 Vortex Insertion Flowmeter

VIM20 Vortex Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Pneumatic Isolation Module

Pneumatic Isolation Module Pneumatic Isolation Module (Cat. 2030-Pxxxxx) ATTENTION: Hazardous Voltage or other forms of energy could be present. To avoid serious injury or death: Prior to beginning the installation and wiring process,

More information

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES 1.INSTRUMENT DESCRIPTION Flow switches PL series are designed to be mounted in an upright position along horizontal pipes. These

More information

PSF50 Paddle flow switch

PSF50 Paddle flow switch Paddle Flow Switch Paddle Flow Switch PSF50 Paddle flow switch Paddle flap flow / no flow switch Economically priced flow/no flow paddle operated flow switch. Simple and reliable design for liquids up

More information

Model 1100 Turbine Flow Meter

Model 1100 Turbine Flow Meter Model 1100 Turbine Flow Meter INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267 www.hedland.com TABLE

More information

General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual

General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual General Oceanics Digital Flowmeter Mechanical and Electronic Operators Manual General Oceanics Inc. 1295 N.W. 163rd Street Miami, Florida 33169-5887 Fax: (305) 621-1710 Phone: (305) 621-2882 Email: sales@generaloceanics.com

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Alemite Carbon Shield Service Guide 1 1 Alemite Carbon Shield Product Overview Your new Carbon Shield Atomized Oil Lubrication system reflects the most advanced

More information

Operation and Maintenance Manual

Operation and Maintenance Manual BM / BMA Hydrometers ½ Operation and Maintenance Manual i This manual is intended for use by the users of this equipment. The information contained herein is the property of the Arad Ltd. Dalia and may

More information

W91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer

W91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer Design & Operation W91 Non-Indicating W94 Dial Thermometer Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company CAPILLARY

More information

Multiple vacuum pumps and associated equipment ASME air receiver NEMA 12 multiplex control panel

Multiple vacuum pumps and associated equipment ASME air receiver NEMA 12 multiplex control panel GENERAL The Powerex laboratory vacuum system is designed to create a suction system to remove unwanted fluids or gases from laboratory working areas. The laboratory vacuum system package is compliant with

More information

DW PADDLE-BELLOWS FLOWMETER & SWITCH

DW PADDLE-BELLOWS FLOWMETER & SWITCH DW PADDLE-BELLOWS FLOWMETER & SWITCH Flow Pressure Level Temperature measurement monitoring control S3 Accuracy: ±3% Full Scale Excellent for Highly Contaminated Media Orientation Independent Brass or

More information

2100 Turbine Flow Sensor

2100 Turbine Flow Sensor 200 Turbine Flow Sensor Description Engineered specifically for small pipe diameter applications, the Signet 200 Turbine Flow Sensor provides accurate readings in two flow ranges: 0.3 to 3.8 lpm and 3

More information

DUALPULSE BI-DIRECTIONAL INSERTION FLOW TRANSDUCER INSTRUCTION MANUAL IMDP DUALPULSE LOCK

DUALPULSE BI-DIRECTIONAL INSERTION FLOW TRANSDUCER INSTRUCTION MANUAL IMDP DUALPULSE LOCK BI-DIRECTIONAL INSERTION FLOW TRANSDUCER INSTRUCTION MANUAL IMDP000-3310 Contents 1 1.1 General arrangement Thank you for purchasing a Dualpulse Flowmeter. It is important that you read this manual to

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL INSTALLATION & OPERATION MANUAL MODEL T575N TEMPERATURE COMPENSATED TOTALIZER/PRINTER DOC#: MN-T575N SPONSLER, INC. Liquid and Gas Flow Measuring Devices and Controls LBS ON OFF TRUCK TOTALIZER MODEL T575N

More information

Flow Meters & Instruments. Insertion Paddle Wheel & Magnetic Flow Meters Flow & Anaytical Instruments. Technical Catalogue

Flow Meters & Instruments. Insertion Paddle Wheel & Magnetic Flow Meters Flow & Anaytical Instruments. Technical Catalogue Flow Meters & Instruments Insertion Paddle Wheel & Magnetic Flow Meters Flow & Anaytical Instruments Technical Catalogue PDF Published October 19, 2017 flow sensors Type F3.01 Direct Mount Flow Sensors

More information

Distributed by: M&M Control Service, Inc MICRO-FLO MICRO-FLO

Distributed by: M&M Control Service, Inc MICRO-FLO MICRO-FLO Digital Paddlewheel Flow meter Operating Manual Blue-White Industries, Ltd. Page 2 TABLE OF CONTENTS 1...Introduction...2 2...Features...3 3...Model number matrix...3 4...Specifications...4 4.1..Temperature

More information

Digital Manifold with Digital Hydrant Control

Digital Manifold with Digital Hydrant Control IN64302 December 2008 Aerospace Group Conveyance Systems Division Carter Brand Ground Fueling Equipment Applicable additional manuals: IN64235 IN64108 IN64702 SU64235 Installation Instructions Digital

More information

Ultrasonic heat meter

Ultrasonic heat meter Ultrasonic heat meter Installation and user guide Flow sensor-vmc-p Energy integrator Compact heat meter Temperature senor CONTENTS Kapitel Please read this manual prior to installation Page 3 2! T! Important

More information

Iron Gate Air Pump System Manual

Iron Gate Air Pump System Manual Iron Gate Air Pump System Manual Installation and Operating Instructions Iron Gate Iron Filter System Manufactured by: R.E Prescott Co., Inc. 10 Railroad Avenue Exeter, New Hampshire 03833 Phone: (603)

More information

FUEL FLOW SENSOR INSTALLATION GUIDE

FUEL FLOW SENSOR INSTALLATION GUIDE Table of content FUEL FLOW SENSOR INSTALLATION GUIDE Revision 1 1 Features... 1 2 Installation... 2 2.1 Overview... 2 2.2 Fuel compatibility... 2 2.3 Ranging jet... 3 2.4 Flow direction... 4 2.5 Location...

More information

Wilo CO-Helix Pressure Boosting Systems. Engineering Specification

Wilo CO-Helix Pressure Boosting Systems. Engineering Specification Wilo CO-Helix Pressure Boosting Systems Engineering Specification 22 PLUMBING 22 11 23.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 GENERAL 1.01 SECTION INCLUDES A. Vertical, multistage, centrifugal

More information

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL Operations Manual Automated Fuel Maintenance System FTI-10A & 20A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies

More information

Why measure viscosity in-line?

Why measure viscosity in-line? BROOKFIELD _ WHY MEASURE VISCOSITY IN-LINE Why measure viscosity in-line? Why Measure Viscosity In-Line? Practical application of viscosity measurement data often leads to the need for in-process control

More information

Full Profile Insertion

Full Profile Insertion FPI Mag Meter Full Profile Insertion High Performance Electromagnetic Flow Meter Municipal Market Product Presentation Manufactured exclusively by McCrometer, Inc. Hemet, CA USA 55+ Years of Experience

More information