1 .1 Low Voltage Switchgear Magnum DS Metal-Enclosed Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organization dedicated to the support of current and vintage switchgear breakers and parts that date as far back as the 1950s. These include the Magnum DS, DSII, DS and DB families. For more information, refer to YES Catalog No. CA E or call BKR-FAST ( ). Available in NEMA 3R walk-in and non-walk-in configurations. Product Description Eaton s Magnum DS Switchgear is backed by 50 years of power circuit breaker and switchgear development that have set industry standards for quality, reliability, maintainability and extended operating life. Magnum DS Switchgear is an assembly of metal enclosures housing power circuit breakers, and normally include control and measuring devices such as relays, instruments, meters and the necessary power bus work and control wiring for AC systems applications up to 600 volts. Contents Description Page Magnum DS Metal-Enclosed Features Bus Features Wiring Features Breaker Magnum DS Switchgear Trip Units Standards and Certifications Product Specifications Special Designs Product Specifications Product Selection Technical Data and Specifications Application Description Switchgear is used in the protection, controlling and monitoring of low voltage distribution systems. Although used as standalone distribution assemblies, they are quite often incorporated into secondary unit substations so that the equipment can be located more closely to the point of power usage. Magnum DS Switchgear is ideally suited to applications calling for all types of industrial, commercial and utility users having distribution systems rated 600 volts or below, 200,000 amperes or below bus bracing, and 10,000 amperes or below continuous loads. Features, Benefits and Functions Standard Finish The light gray paint finish (ANSI 61) uses a modern, completely automated and continuously monitored electrostatic powder coating. This continuously monitored system includes spray de-grease and clean, spray rinse, iron phosphate spray coating spray rinse, nonchemical seal, oven drying, electrostatic powder spray paint coating and oven curing. Integral Base The rugged formed base greatly increases the rigidity of the structure and reduces the possibility of damage during the installation of the equipment and is suitable for rolling, jacking and handling. A lifting angle is permanently welded into the bus compartment structure for increased strength. 102 Volume 3 Power Distribution and Control Assemblies CA E December For Immediate Delivery or Tech Support call KMParts.com at (866)

2 Low Voltage Switchgear Magnum DS Metal-Enclosed.1 Heavy-Duty Door Hinges Each breaker door is mounted with hinge pins. Removal of the door is easily accomplished by just lifting the hinge pin. This allows easy access to the breaker internal compartment for inspection and maintenance. Rear Cover/Doors In Magnum DS Switchgear, standard rear covers with captive hardware are the bolt-on type. They are split into two sections to facilitate handling during removal and installation. Optional rear doors are also available. Through-the-Door Design The following functions may be performed without the need to open the circuit breaker door: levering the breaker between positions, operate manual charging system and view the spring charge status flag, close and open breaker, view and adjust trip unit, and read the breaker rating nameplate. Through-the-Door Design Front Accessible When the door is open or removed, each breaker compartment provides front access to isolated, vertical wireways, primary disconnects, cell current transformers and other breaker compartment accessories for ease of field wiring and troubleshooting field connections. Four-Position Drawout Breakers can be in connected, test, disconnected or removed position. The breaker compartment door can be closed in the connected, test and disconnected positions. Closing Spring Automatic Discharge Mechanical interlocking automatically discharges the closing springs when the breaker is removed from its compartment. Breaker Cell Breaker Inspection When withdrawn on the rails, breaker is completely accessible for visual inspection; tilting is not necessary. The rails are permanent parts of every breaker compartment. Interference interlocks are supplied on breakers and in compartments where the compartments are of the same physical size to ensure that an incorrect breaker cannot be inserted. Features Bus Buses and Connections Vertical and cross bus ratings in Magnum DS Switchgear are based on a UL and ANSI standard temperature rise of 65 C above a maximum ambient air temperature of 40 C. Bus Ampacities Vertical and cross bus ratings in Magnum DS are 2000, 3200, 4000, 5000 and 6000 amperes. In addition, 8000 and 10,000 amperes continuous cross bus ratings are also available. Bus Bracing Unique vertical bus configuration provides an optional shortcircuit withstand rating of 150,000 amperes without the need for preceding current limiting fuses. Standard bracing is 100,000 amperes. The U-shaped bar is the heart of the Magnum DS vertical bus. This configuration provides a much higher mechanical strength. To further demonstrate the strength and rigidity of this bus system, it has been verified through testing to withstand 85,000 amperes short-circuit for a full 60 cycles. Silver Plating Bolted, silver-plated copper main buses are standard. The plating is over the entire length of the bar, not just at the joints. Optional tin-plated copper buses are available. Bus Joints All joints are bolted and secured with Belleville-type spring washers for maximum joint integrity. These washers reduce the potential of joint hardware loosening during the change of joint temperature associated with variations of the loads. As an option, maintenance-free hardware can be provided. Full Neutral For four-wire applications, the neutral bus is rated 100% of main bus rating as standard. Ground A ground bus is furnished for the full length of the switchgear assembly and is fitted with terminals for purchaser s connections. Glass-Reinforced Polyester Stand-Off Insulation System Glass-reinforced polyester has been used on both low and medium voltage switchgear for decades. By combining this industryproven material with our other insulation materials, a total system providing exceptional mechanical and dielectric withstand strength, as well as high resistance to heat, flame and moisture, is produced. Substantial testing to demonstrate accelerated effects of heating and cooling on the mechanical and dielectric properties of this system prove it to provide superior performance for decades of trouble-free operation. Features Wiring Cable Compartment The cable compartment gives ample room for terminating the power cables. Removable top roof sheets allow for easy conduit hub installation. The floor of the cable compartment is open to allow cable entry from underground duct banks. Optional floor plates are available. Lug Pad The lugs are located on the breaker runbacks to accommodate lug orientations at a 45 angle to reduce the bending radius of the cable needed for making the connections, thus reducing installation and maintenance time. Mechanical setscrew type lugs are standard. Optional NEMA two-hole compression lugs are available as an option. Volume 3 Power Distribution and Control Assemblies CA E December For Immediate Delivery or Tech Support call KMParts.com at (866)

3 .1 Low Voltage Switchgear Magnum DS Metal-Enclosed Control Wireway An isolated vertical wireway is provided for routing of factory and field wiring in each switchgear section. Breaker secondary terminal blocks are mounted as standard above each circuit breaker. The terminal blocks are rated 30 amperes and will accept bare wire, ring or spade terminals for wire size ranges of #22 to #10. Extruded loops are punched in side sheets of the vertical wireway to allow securing of customer control wiring without the use of adhesive wire anchors. Control Wireway Control Wire Standard wire is Type SIS insulated stranded copper, extra flexible No. 14 AWG minimum. Control Wire Marking Each wire is imprinted with ink cured under ultraviolet light for durability and for easy identification by the user. The enhanced solvent resistance and durability of the aerospace-grade UV cure ink has been tested for severe environments. The imprinting is made periodically along the length of the wire, with the ends being imprinted more frequently. The point of origin, wire designation and point of destination are imprinted in the following format: <origin zone/wire name/destination zone>. Each device has a uniquely designated zone. < indicates the direction of the wire origination and > indicates the direction of the wire destination. As an option, wire marking can be made using sleeve type or heat shrink sleeve type. Control Wire Marking Secondary Terminal Compartment Door The customer s secondary terminal connections are located behind a separate door providing access to these connections without the need to open the breaker compartment door. Shipping Split Connection At each shipping split, the control connections are made with plug-in terminal blocks rated 600 volts, 40 amperes. The terminal blocks interlock mechanically without removing the line or load connections. This method of making the shipping split control connections increases the speed of installation and reduces the potential of incorrect connections. Features Breaker Contacts The Magnum DS has silver tungsten moving contacts and silver graphite stationary contacts. The contacts provide a longwearing, low-resistance joint. The contacts are protected from arcing damage even after repeated interruptions by the heel-toe action that causes the integral arcing contacts to mate before the main contacts part. The arcing contacts then part last, striking the arc away from the main contacts. The main contacts are of the butt type and are composed of a multiplicity of fingers to give many points of contact without alignment being critical. Magnum DS Breaker Contacts (Arc Chutes Removed) Stored-Energy Mechanism A cam-type closing mechanism closes the breaker. It receives its energy from a spring that can be charged by a manual handle on the front of the breaker or by a universal electric motor. Release of the stored energy is accomplished by manually depressing a button on the front of the breaker or electrically energizing a releasing solenoid. Arc Chute There are three basic means of extinguishing an arc: lengthening the arc path; cooling by gas blast or contraction; and deionizing or physically removing the conduction particles from the arc path. The DE-ION principle is incorporated in all Magnum DS circuit breakers. This makes possible faster arc extinction for a given contact travel, and ensures positive interruption and minimum contact burning. Levering Mechanism The worm gear levering mechanism is self-contained on the breaker drawout element and engages slots in the breaker compartment. A removable crank is used to lever the breaker between the connected, test and disconnected positions. Mechanical interlocking is arranged so that levering cannot be accomplished unless the breaker is in the opened position. Protection During Levering Operation When levering the breaker between the connected, test and disconnected positions, the operator is protected from contact with live parts by the breaker door. Levering Magnum DS Breaker 104 Volume 3 Power Distribution and Control Assemblies CA E December For Immediate Delivery or Tech Support call KMParts.com at (866)

4 Low Voltage Switchgear Magnum DS Metal-Enclosed.1 True Two-Step Stored Energy Closing This sequence is required to charge and close the breaker. The breaker closing springs are charged either through the manual-charging handle or by the optional charging motor. The breaker is mechanically interlocked to prevent closing of the breaker until the closing springs are fully charged. With the closing springs fully charged, the breaker can then be closed by pressing the manual close pushbutton on the breaker, or by the optional spring release coil through a remote electrical signal. This means that the energy required to open the breaker is always prestored following a closing operation. Stored energy is energy held in waiting, ready to open or close the breaker within five cycles or less. The unique cam and spring design provides necessary energy for a single close-open sequence, as well as the energy for multiple chargeclose operations such as this possible sequence: charge-close-recharge-openclose-open. The closing springs are interlocked with the breaker racking mechanism to ensure that the closing springs are discharged before the breaker can be removed from the compartment. Manually Operated Breakers Manually operated breakers are equipped with a manual charging handle to charge the closing springs. Manual closing and tripping pushbuttons are utilized to operate the breaker. Remote closing and tripping can be accomplished by installing optional electric spring release and shunt trip coils. The breaker closing springs must be charged manually, then remote closing and tripping signals can be sent to the breaker. Electrically Operated Breakers Electrically operated breakers are equipped with a spring charging motor and electrically operated spring release and shunt trip coils. The breaker manual charging handle can be used to charge the closing springs when power is not available to the charging motor. Provisions for Padlocking All breakers include provision for padlocking open to prevent electrical or manual closing. This padlocking can secure the breaker in the connected, test or disconnected position by preventing levering of the breaker. Ease of Inspection and Maintenance Magnum DS breakers are designed for maximum accessibility and the utmost ease of inspection and maintenance. Magnum DS Switchgear Trip Units Digitrip RMS Trip Unit The Digitrip RMS trip units feature a dependent curve that is depicted in the nameplate by a blue shaded area of the trip curve. The dependent curve affords better protection flexibility. Additionally, all of the trip units have, as standard, thermal memory, 50/60 Hz operation and thermal self-protection at 90 C. Digitrip RMS Integral Microprocessor-Based Breaker Overcurrent Trip Systems These systems provide maximum reliability with true rms sensing as standard, gives excellent repeatability, and requires minimum maintenance. No external control source is required for its protective functions. Trip Functions Magnum DS trip units provide the maximum in flexibility and are available in the following configurations: LSI, LSIG and LSIA (ground fault alarm only). In each case, either the short delay or the instantaneous function (not both) may be defeated. This reduces the need for spare breaker inventories and provides maximum utilization of interchangeable breakers. Options Special Designs The Magnum DS design allows Eaton to provide special solutions to meet our customer s needs. For example, as shown below, here we embedded molded case circuit breakers into a switchgear lineup for a customer. Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Refer to TD E for application data. Standards and Certifications Magnum DS Switchgear assemblies have undergone an extensive seismic qualification program. The test program utilized ANSI standard C37.81, the Uniform Building Code (UBC) and the California Building Code (CBC) as a basis for the test program. The assemblies have been tested and qualified to exceed these requirements. Magnum DS Switchgear conforms to the following standards: CSA, ANSI C , C37.51, and UL Standard 1558, and is built in an ISO certified facility. American Bureau of Shipping (ABS) certification is also available. Contact Eaton for details and part numbers for CSA-approved units. Product Selection Refer to TD E for application data. Contact Eaton for configurations, pricing and availability. Volume 3 Power Distribution and Control Assemblies CA E December For Immediate Delivery or Tech Support call KMParts.com at (866)

5 .1 Low Voltage Switchgear Magnum DS Metal-Enclosed Technical Data and Specifications Product Specifications Refer to Section 16426A of the Product Specification Guide. Available Bus Ratings Cross Bus Ampacity Vertical section bus is sized per main cross bus maximum rating or by ANSI C Section Table 11 to a maximum of 5000 amperes. Ratings of Magnum DS Breakers Note 200 ka available; contact Eaton. Bus Bracing ka , 150, , 150, , 150, , 150, , 150, , 150, , , 150, 200 Vertical Bus Ampacity Note: In addition to the available bus bracings shown above, the bus has been tested for shortcircuit values of 85,000 amperes for a full 60 cycles. Ratings, rms Symmetrical Amperes Interrupting Rating Short-Time Rating Breaker Type Frame Amperes Volts 480 Volts 600 Volts Volts 480 Volts 600 Volts MDS ,000 42,000 42,000 42,000 42,000 42,000 MDS ,000 65,000 65,000 65,000 65,000 65,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , ,000 85,000 85,000 85,000 MDS ,000 65,000 65,000 65,000 65,000 65,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , ,000 85,000 85,000 85,000 MDS ,000 65,000 65,000 65,000 65,000 65,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , ,000 85,000 85,000 85,000 MDS ,000 65,000 65,000 65,000 65,000 65,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , ,000 85,000 85,000 85,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , , , , ,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , , , , ,000 MDS ,000 85,000 85,000 85,000 85,000 85,000 MDS-C , , , , , , Volume 3 Power Distribution and Control Assemblies CA E December For Immediate Delivery or Tech Support call KMParts.com at (866)

6 A above, 2-3, 5 ABS, 4 AC, 1 accelerated, 2 accept, 3 access, 2-3 accessibility, 4 Accessible, 2 accessible, 2 accessories, 2 accommodate, 2 accomplished, 2-4 action, 3 addition, 2, 5 Additionally, 4 adhesive, 3 adjust, 2 aerospace, 3 affords, 4 after, 3 air, 2 alarm, 4 alignment, 3 All, 2, 4 all, 1, 3-4 allow, 2-3 allows, 2, 4 along, 3 also, 2, 4 Although, 1 always, 4 ambient, 2 American, 4 Ampacities, 2 Ampacity, 5 Amperes, 5 amperes, 1-3, 5 ample, 2 An, 3 an, 1-4 anchors, 3 and, 1-5 angle, 1-2 ANSI, 1-2, 4-5 Application, 1 application, 4 applications, 1-2 approved, 4 Arc, 3 arc, 3 arcing, 3 are, 1-4 area, 4 arranged, 3 As, 2-3 as, 1-4 Assemblies, 1-5 assemblies, 1, 4 assembly, 1-2 associated, 2 At, 3 at, 1-5 automated, 1 Automatic, 2

7 automatically, 2 availability, 4 Available, 5 available, 2, 4-5 away, 3 AWG, 3 B back, 1 backed, 1 backs, 2 banks, 2 bar, 2 bare, 3 Base, 1 base, 1 Based, 4 based, 2 basic, 3 basis, 4 be, 1-4 been, 2-5 before, 3-4 behind, 3 being, 3 Belleville, 2 below, 1, 4 bending, 2 Benefits, 1 better, 4 between, 2-3 BKR, 1 blast, 3 blocks, 3 blue, 4 bolt, 2 Bolted, 2 bolted, 2 both, 2, 4 Bracing, 2, 5 bracing, 1-2 bracings, 5 Breaker, 1-5 breaker, 1-4 Breakers, 2, 4-5 breakers, 1-4 Building, 4 built, 4 Bureau, 4 burning, 3 Bus, 1-2, 5 bus, 1-2, 5 Buses, 2 buses, 2 butt, 3 button, 3 By, 2 by, 1-5 C CA, 1-5 Cable, 2 cable, 2 cables, 2 California, 4 call, 1-5 calling, 1 cam, 3-4 can, 1-4 cannot, 2-3 captive, 2 Case, 1, 4 case, 4 Catalog, 1 causes, 3 CBC, 4 Cell, 2 cell, 2 certification, 4 Certifications, 1, 4 certified, 4 change, 2 charge, 2, 4 charged, 3-4 charging, 2, 4 chemical, 1 Chute, 3 Chutes, 3 Circuit, 1, 4 circuit, 1-5 clean, 1 close, 2, 4 closed, 2, 4 closely, 1

8 closes, 3 Closing, 2, 4 closing, 2-4 coating, 1 Code, 4 coil, 4 coils, 4 com, 1-5 combining, 2 commercial, 1 Compartment, 2-3 compartment, 1-4 compartments, 2 completely, 1-2 composed, 3 compression, 2 conduction, 3 conduit, 2 configuration, 2 configurations, 1, 4 conforms, 4 connected, 2-4 Connection, 3 Connections, 2 connections, 2-3 Contact, 4 contact, 3, 5 Contacts, 3 contacts, 3 contained, 3 Contents, 1 continuous, 1-2 continuously, 1 contraction, 3 Control, 1-5 control, 1, 3-4 controlling, 1 cooling, 2-3 copper, 2-3 Cover, 2 covers, 2 crank, 3 critical, 3 Cross, 1, 5 cross, 2, 5 CSA, 4 cure, 3 cured, 3 curing, 1 current, 1-2 curve, 4 customer, 3-4 cycles, 2, 4-5 D damage, 1, 3 Data, 1, 5 data, 4 date, 1 DB, 1 DE, 3 de, 1 decades, 2 December, 1-5 dedicated, 1 defeated, 4 deionizing, 3 delay, 4 Delivery, 1-5 demonstrate, 2 dependent, 4 depicted, 4 depressing, 3 Description, 1 Design, 2 design, 4 designated, 3 designation, 3 designed, 4 Designs, 1, 4 destination, 3 details, 4 development, 1 device, 3 devices, 1 dielectric, 2 Digitrip, 4 direction, 3 Discharge, 2 discharged, 4 discharges, 2 disconnected, 2-4 disconnects, 2 Distribution, 1-5 distribution, 1 Door, 2-3 door, 2-3 Doors, 2 doors, 2 Drawout, 2 drawout, 3 drying, 1 DS, 1-5

9 DSII, 1 duct, 2 durability, 3 During, 3 during, 1-2 Duty, 2 extended, 1 extensive, 4 external, 4 extinction, 3 extinguishing, 3 extra, 3 Extruded, 3 E Each, 2-3 each, 2-4 Ease, 4 ease, 2, 4 easily, 2 easy, 2-3 Eaton, 1, 4-5 eaton, 1-5 effects, 2 either, 4 electric, 3-4 Electrical, 1 electrical, 4 Electrically, 4 electrically, 3-4 electrostatic, 1 element, 3 embedded, 4 Enclosed, 1-5 enclosures, 1 ends, 3 energizing, 3 Energy, 3-4 energy, 3-4 engages, 3 enhanced, 3 ensure, 2, 4 ensures, 3 entire, 2 entry, 2 environments, 3 equipment, 1 equipped, 4 even, 3 every, 2 example, 4 exceed, 4 excellent, 4 exceptional, 2 F facilitate, 2 facility, 4 factory, 3 families, 1 far, 1 FAST, 1 faster, 3 fault, 4 feature, 4 Features, 1-3 Feeder, 1, 4 field, 2-3 fingers, 3 Finish, 1 finish, 1 fitted, 2 five, 4 flag, 2 flame, 2 flexibility, 4 flexible, 3 floor, 2 following, 2-4 For, 1-5 for, 1-5 format, 3 formed, 1 Four, 2 four, 2 Frame, 5 free, 2 frequently, 3 from, 2-4 Front, 2 front, 2-3 Full, 2 full, 2, 5 fully, 4

10 function, 4 Functions, 4 functions, 2, 4 Functionsan, 1 furnished, 2 further, 2 fuses, 2 G gas, 3 gear, 3 give, 3 given, 3 gives, 2, 4 Glass, 2 grade, 3 graphite, 3 gray, 1 grease, 1 greatly, 1 Ground, 2 ground, 2, 4 Guide, 5 H handle, 3-4 handling, 1-2 hardware, 2 has, 1-3, 5 have, 1, 4 having, 1 heart, 2 heat, 2-3 heating, 2 Heavy, 2 heel, 3 held, 4 here, 4 high, 2 higher, 2 hinge, 2 Hinges, 2 hole, 2 housing, 1 hub, 2 Hz, 4 I ideally, 1 identification, 3 Immediate, 1-5 imprinted, 3 imprinting, 3 In, 2, 4-5 in, 1-4 include, 1, 4 includes, 1 incorporated, 1, 3 incorrect, 2-3 increased, 1 increases, 1, 3 indicates, 3 industrial, 1 industry, 1-2 information, 1 ink, 3 inserted, 2 Inspection, 2, 4 inspection, 2, 4 installation, 1-3 installing, 4 instantaneous, 4 instruments, 1 insulated, 3 Insulation, 2 insulation, 2 Integral, 1, 4 integral, 3 integrity, 2 interchangeable, 4 Interference, 2 interlock, 3 interlocked, 4 interlocking, 2-3 interlocks, 2 internal, 2 Interrupting, 5 interruption, 3 interruptions, 3

11 into, 1-2, 4 inventories, 4 ION, 3 iron, 1 is, 1-5 ISO, 4 isolated, 2-3 It, 3 it, 2 its, 2-4 J jacking, 1 joint, 2-3 Joints, 2 joints, 2 just, 2 K ka, 5 KMParts, 1-5 L last, 3 length, 2-3 lengthening, 3 less, 4 lever, 3 Levering, 3 levering, 2-4 life, 1 lifting, 1-2 light, 1, 3 limiting, 2 line, 3 lineup, 4 live, 3 load, 3 loads, 1-2 located, 1-3 long, 3 loops, 3 loosening, 2 Low, 1-5 low, 1-3 LSI, 4 LSIA, 4 LSIG, 4 Lug, 2 lug, 2 lugs, 2 M made, 3 Magnum, 1-5 main, 2-3, 5 maintainability, 1 Maintenance, 4 maintenance, 2, 4 makes, 3 making, 2-3 Manual, 4 manual, 2-4 Manually, 4 manually, 3-4 many, 3 Marking, 3 marking, 3 mate, 3 material, 2 materials, 2 maximum, 2, 4-5 may, 2, 4 MDS, 5 means, 3-4 measuring, 1 Mechanical, 2-3 mechanical, 2 mechanically, 3-4 Mechanism, 3 mechanism, 3-4 medium, 2 meet, 4

12 memory, 4 Metal, 1-5 metal, 1 meters, 1 method, 3 Microprocessor, 4 minimum, 3-4 modern, 1 moisture, 2 Molded, 1, 4 molded, 4 monitored, 1 monitoring, 1 more, 1, 3 motor, 3-4 mounted, 2-3 moving, 3 much, 2 multiple, 4 multiplicity, 3 must, 4 N name, 3 nameplate, 2, 4 necessary, 1-2, 4 need, 2-4 needed, 2 needs, 4 NEMA, 1-2 Neutral, 2 neutral, 2 No, 1, 3-4 non, 1 nonavailable, 1 normally, 1 not, 2, 4 Note, 5 numbers, 4 O of, 1-5 Off, 2 often, 1 on, 2-4 only, 4 open, 2-4 opened, 3 operate, 2, 4 Operated, 4 operated, 4 operating, 1 Operation, 3 operation, 2, 4 operations, 4 operator, 3 option, 2-3 Optional, 2 optional, 2, 4 Options, 4 or, 1-5 organization, 1 orientations, 2 origin, 3 origination, 3 other, 2 our, 2, 4 oven, 1 over, 2 Overcurrent, 4 P Pad, 2 Padlocking, 4 padlocking, 4 Page, 1 paint, 1 part, 3-4 particles, 3 parts, 1-3 path, 3 per, 5 performance, 2 performed, 2

13 periodically, 3 permanent, 2 permanently, 1 phosphate, 1 physical, 2 physically, 3 pin, 2 pins, 2 plated, 2 plates, 2 Plating, 2 plating, 2 plug, 3 point, 1, 3 points, 3 Polyester, 2 polyester, 2 Position, 2 position, 2-4 positions, 2-3 positive, 3 possibility, 1 possible, 3-4 potential, 2-3 powder, 1 Power, 1-5 power, 1-2, 4 preceding, 2 pressing, 4 prestored, 4 prevent, 4 preventing, 4 pricing, 4 primary, 2 principle, 3 produced, 2 Product, 1, 4-5 program, 4 properties, 2 protected, 3 Protection, 3 protection, 1, 4 protective, 4 prove, 2 proven, 2 provide, 2-4 provided, 2-3 provides, 2, 4 providing, 2-3 provision, 4 Provisions, 4 punched, 3 purchaser, 2 pushbutton, 4 pushbuttons, 4 Q qualification, 4 qualified, 4 quality, 1 quite, 1 R racking, 4 radius, 2 rails, 2 ranges, 3 rated, 1-3 Rating, 5 rating, 2, 5 Ratings, 5 ratings, 2 read, 2 ready, 4 Rear, 2 rear, 2 receives, 3 recharge, 4 reduce, 2 reduces, 1, 3-4 reducing, 2 Refer, 4-5 refer, 1 Reference, 1 Reinforced, 2 reinforced, 2 relays, 1 Release, 3 release, 4 releasing, 3 reliability, 1, 4 Remote, 4 remote, 4 Removable, 2 removable, 3

14 Removal, 2 removal, 2 Removed, 3 removed, 2, 4 removing, 3 repeatability, 4 repeated, 3 required, 4 requirements, 4 requires, 4 resistance, 2-3 rigidity, 1-2 ring, 3 rinse, 1 rip, 4 rise, 2 RMS, 4 rms, 4-5 rolling, 1 roof, 2 room, 2 routing, 3 rugged, 1 run, 2 S same, 2 seal, 1 Secondary, 3 secondary, 1, 3 Section, 1, 4-5 section, 3, 5 sections, 2 Sector, 1 secure, 4 secured, 2 securing, 3 seismic, 4 Selection, 1, 4 self, 3-4 sensing, 4 sent, 4 separate, 3 sequence, 4 set, 1 setscrew, 2 severe, 3 shaded, 4 shaped, 2 sheets, 2-3 Shipping, 3-4 shipping, 3 Short, 5 short, 2, 4-5 shown, 4-5 shrink, 3 shunt, 4 side, 3 signal, 4 signals, 4 Silver, 2 silver, 2-3 single, 4 SIS, 3 size, 2-3 sized, 5 sleeve, 3 slots, 3 so, 1, 3 solenoid, 3 solutions, 4 solvent, 3 source, 4 spade, 3 spare, 4 Special, 1, 4 special, 4 Specification, 5 Specifications, 1, 5 speed, 3 Split, 3 split, 2-3 spray, 1 Spring, 2 spring, 2-4 springs, 2, 4 Stand, 2 standalone, 1 Standard, 1-4 standard, 2-4 Standards, 1, 4 standards, 1, 4 stationary, 3 status, 2 Step, 4 Stored, 3-4 stored, 3 stranded, 3 strength, 1-2 striking, 3

15 structure, 1 Substantial, 2 substations, 1 such, 1, 4 suitable, 1 suited, 1 superior, 2 supplied, 2 Support, 1-5 support, 1 Switchgear, 1-5 switchgear, 1-4 Symmetrical, 5 System, 2 system, 1-2 Systems, 4 systems, 1, 4 T Table, 5 TD, 4 Tech, 1-5 Technical, 1, 5 temperature, 2 Terminal, 3 terminal, 3 terminals, 2-3 terminating, 2 test, 2-4 tested, 3-5 testing, 2 that, 1-4 The, 1-4 the, 1-5 then, 3-4 There, 3 thermal, 4 These, 1-2, 4 these, 3-4 They, 2 they, 1 This, 1-4 this, 2, 4 three, 3 Through, 2 through, 2, 4 thus, 2 tilting, 2 Time, 5 time, 2 tin, 2 To, 2 to, 1-5 toe, 3 top, 2 total, 2 transformers, 2 travel, 3 Trip, 1, 4 trip, 2, 4 tripping, 4 trouble, 2 troubleshooting, 2 True, 4 true, 4 tungsten, 3 Two, 4 two, 2 Type, 3, 5 type, 2-3 types, 1 U UBC, 4 UL, 2, 4 ultraviolet, 3 under, 3 undergone, 4 underground, 2 Uniform, 4 Unique, 2 unique, 4 uniquely, 3 Unit, 4 unit, 1-2 Units, 1, 4 units, 4 universal, 3 unless, 3 until, 4 up, 1 usage, 1 use, 3 used, 1-4

16 user, 3 users, 1 uses, 1 using, 3 utility, 1 utilization, 4 utilized, 4 utmost, 4 UV, 3 V values, 5 variations, 2 verified, 2 Vertical, 2, 5 vertical, 2-3 view, 2 vintage, 1 visual, 2 Voltage, 1-5 voltage, 1-2 Volts, 5 volts, 1, 3 Volume, 1-5 Wiring, 1-2 wiring, 1-3 With, 4 with, 1-4 withdrawn, 2 within, 4 without, 2-3 withstand, 2 work, 1 worm, 3 www, 1-5 Y years, 1 YES, 1 Z zone, 3 W waiting, 4 walk, 1 washers, 2 we, 4 wearing, 3 welded, 1 well, 2, 4 When, 2-3 when, 2, 4 where, 2 will, 3 Wire, 3 wire, 2-3 Wireway, 3 wireway, 3 wireways, 2

.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi

.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference................................................ 102 Product Description............................................. 102 Application Description...........................................

More information

Switchgear. Low Voltage

Switchgear. Low Voltage January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................

More information

Low Voltage Switchgear

Low Voltage Switchgear Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference......................................... Product Description....................................... Application Description....................................

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers Class 6037 CONTENTS Schneider Electric Brands Description Page Product Description..................................................

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Cutler-Hammer May 2001

Cutler-Hammer May 2001 Low-Voltage Power Circuit Breakers Magnum DS General Description Index Page General Description Magnum DS............. A1-1 General Description DSII/DSLII............... A1-7 Technical Data Magnum DS.

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment METAL-ENCLOSED DRAWOUT SWITCHGEAR (DSLII) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, low voltage metal-enclosed

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents

25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents .4 Molded Case Circuit Breakers Gi-, Fi, Ji-, Ki-, Li-Frames Molded Case Circuit Breaker Family Molded Case Circuit Breakers When higher interrupting ratings are not required. Product Overview Gi-, Fi,

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS

TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS om.c ww w.e lec tri ca lp ar tm an ua ls TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS Proven Technology with the Enhancements and Additional Ratings Our Customers Asked For

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Power Break II Switchboard

Power Break II Switchboard Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A

More information

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers .1 Series NRX Low Voltage Series NRX Low Voltage Product Description Series NRX is a low voltage power circuit breaker suitable for UL 1558, UL 891, and IEC switchgear and switchboards. The compact size

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service No One Does It Like Mipco Mipco Interlocked Reefer Power Outlets are used extensively in port terminals and shipboard applications to provide a safe, watertight electrical connection for refrigerated containers.

More information

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the integrated unit substation (IUS) complete from the incoming line terminals

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features Vertical Break Switch Operators/Accessories Ordering Information Furnish: Switch type Voltage Amperage Momentary rating BIL level Mounting position Operator type Accessories required Base mounting holes

More information

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2

More information

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General 13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear

More information

GE 8000-Line Motor Control Centers

GE 8000-Line Motor Control Centers GE 8000-Line -1 ENCLOSURE TYPES TYPE 1 General Purpose, Indoor Intended for use indoors, primarily to prevent accidental contact of personnel with the enclosed equipment, in areas where unusual service

More information

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035 Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker

More information

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,

More information

Aluminum Vertical Break Switch kv A.

Aluminum Vertical Break Switch kv A. Bulletin DB-C106AA05 Type V2-CA Aluminum Vertical Break Switch 7.2-69 kv 600-2000 A. Designed for Simplicity V2-CA APPLICATION The Cleaveland/Price V2-CA is a three pole, group operated, aluminum vertical

More information

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker

More information

Controlled Power HSN High Speed DC Circuit Breakers

Controlled Power HSN High Speed DC Circuit Breakers Controlled Power HSN High Speed DC Circuit Breakers Each CP Type HSN circuit breaker unit can consist of either a wheeled truck and housing or be panel mounted. The circuit breaker can be mounted on the

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Introduction. Features. Intelligent Technologies Motor Control Center Structures

Introduction. Features. Intelligent Technologies Motor Control Center Structures Intelligent Technologies Technical Data New Information Description Page Intelligent Technologies General............................................. 2 s.......................................................

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI

More information

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H) 2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of

More information

Application guide. Tmax Link OEM UL 891 Switchboard Program

Application guide. Tmax Link OEM UL 891 Switchboard Program Application guide Tmax Link OEM UL 891 Switchboard Program 04 Tmax Link Overview 04 Standards 04 UL File Extension Process Overview 05 Electrical Data 05 Technical Data 05 Ambient Conditions 08 Circuit

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1 Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 Supersedes July 1997 IB694C694-02 Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 PURPOSE This

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

Copper Vertical Break Switch kv A.

Copper Vertical Break Switch kv A. Bulletin DB-106C05 Type V2-C Copper Vertical Break Switch 7.2-69 kv 600-2000 A. Designed for Simplicity V2-C APPLICATION The Cleaveland/Price V2-C is a three pole, group operated, copper vertical break

More information

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English. -174 Series C Molded Case Circuit s July 7 Molded Case Switches Refer to Eaton for UL listed, series tested Molded Case Switch application data. Table -278. Molded Case Switches Cont. Amp Rating at 40

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

WL Low Voltage Metal-Enclosed Switchgear. Selection and Application Guide.

WL Low Voltage Metal-Enclosed Switchgear. Selection and Application Guide. WL Low Voltage Metal-Enclosed Switchgear Selection and Application Guide www.sea.siemens.com/switchgear 3 Table of Contents General Information...............................................................................................

More information

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E Supersedes PL.44B.04.P.E Dated September 1998 600 Volts AC Maximum 200 ka, RMS Sym. Short Circuit Maximum 800-5000 Amps Continuous Effective: October 1999 Page 1 Index Page Table Description/Application...

More information

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject

More information

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

Contents. General Electric Sangamo Astra CTB JCT-10 R6B TAB, TA CSF JCM-0 R6BA TCB, AA CMF JCW-0 R6M AB

Contents. General Electric Sangamo Astra CTB JCT-10 R6B TAB, TA CSF JCM-0 R6BA TCB, AA CMF JCW-0 R6M AB Panelboards and Lighting Control Metering Service Sections.7 Metering Service Section Contents Description Metering Service Sections Page Catalog Number Selection........................ 482 Product Selection..............................

More information

Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS IB E

Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS IB E Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS Read and understand these instructions before attempting to unpack, assemble, operate or

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

Electrical Switchgear Replacement Montgomery County Community College

Electrical Switchgear Replacement Montgomery County Community College Electrical Switchgear Replacement Montgomery County Community College ADDENDUM NO.1 #08-112014-SB01 November 12, 2014 The following clarifications, changes, additions or deletions for this project shall

More information

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller Number: 5344-1.1.311 Rev. 8 Portable Mine Power Centres Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller SCOPE This specification covers general material and design

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy. Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru Contents Page INTRODUCTION... 10-2 Power/Vac GUIDE FORM SPECIFICATION... 10-2 thru 10-12 10-1 Power/Vac Guide Form Specifications Guide Form Specifications INTRODUCTION Upon completion of the one-line

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

MEDIUM-VOLTAGE SWITCHGEAR

MEDIUM-VOLTAGE SWITCHGEAR REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.

More information

S&C Manual PME Pad-Mounted Gear

S&C Manual PME Pad-Mounted Gear S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,

More information