Belimo Applications Air handling units

Size: px
Start display at page:

Download "Belimo Applications Air handling units"

Transcription

1 Belimo Alications Air handling units International 207

2 Preface and legend Preface hank you for your interest in our roducts. In this brochure you will find information regarding the lanning of an air handling unit. he described solutions from Belimo will allow you to create an otimum room climate with minimum energy consumtion. All chaters are structured as follows: Descrition of the alication Bill of material ender secification Belimo features and benefits he descrition focuses on the resective colour-coded hydraulic circuit. he list of materials comrises water-side comonents of this highlighted circuit. Air solutions and sensors offered by Belimo are also included therein. Water-side valves, balancing valves and ums are resented in diagrams; other comonents such as non-return valves and strainers are not deicted for the sake of simlicity. Furthermore, starting on age 46, the last section rovides an overview of other solutions from Belimo relating to room and system solutions, bus and system integration, air handling units and sensors. Please contact us for more information. For detailed information on room and zone control, lease refer to our alication brochure with the same name (available searately). Legend Water roducts 2-way characterised control valve 3-way characterised control valve Electronic ressure-indeendent characterised control valve (EPIV) Pum Belimo Energy Valve Balancing valve Legend Air solutions Air damer actuator Volumetric flow controller VAV Subject to technical modifications

3 Preface and legend Legend Sensors emerature sensor Frost rotection thermostat Pressure sensor Differential ressure switch CO2 CO 2 and temerature sensor RH Humidity and temerature sensor Outside temerature sensor Legend Other ducting comonents Air filter Plate heat exchanger Fan Heating register Rotational heat exchanger Cooling register Humidifier Combined circulation system Disclaimer Please note that the illustrations are examles only and may therefore vary, deending on the air handling unit. Subject to modifications and amendments. Please get in touch with your Belimo contact erson to verify the secifications Subject to technical modifications 3

4 Eye to eye with your requirements Belimo your artner for more comfort, safety and efficiency in buildings. Behind, there is Belimo Solutions from Belimo ensure balanced temeratures, a controlled air exchange at worklaces and in ublic areas, individual air-conditioning control in zones, individual rooms and aartments as well as safe air solutions in trade, industry and sensitive working areas. Innovative valve solutions drastically reduce both energy consumtion and costs. his creates an added value for eole and the environment. Your requirement our actuator All our thoughts and actions are aimed at giving you the certainty of having chosen the best from consultation to urchasing, from delivery to service. Belimo is your artner for actuator solutions for controlling heating, ventilation and air-conditioning systems. Comfort Health, well-being and erformance increase when the climate is right. Belimo ensures a erfect climate for ideal utilisation of your rooms, deending on the secific alication. Security When it comes to rotecting eole, tangible assets and investments, there are no comromises. What counts here is not trust in safety, but the certainty of having made the right choice with Belimo. Energy efficiency Products and technologies from Belimo save energy and reduce oerating costs. You can rely on "Exerience Efficiency" our initiative for maximum energy efficiency. Facts that count Research and develoment are a high riority at Belimo. Here we can offer you the most innovative actuator, valve and sensor technologies. With Belimo's offices in more than 80 countries, you can order roducts locally and benefit from short delivery times. Wherever you lan your building: Products from Belimo are available in over 80 countries. For you, this means: simle logistics and rocurement, thanks to a comlete roduct range from a single source. As a listed comany with a turnover of aroximately 540 million CHF, we have been growing solidly and continuously since our founding in Subject to technical modifications

5 Product Overview Characterised control valve. Proven millions of times over. As a result of their sherical design, the ball valves which have already roven themselves a million times over are air bubble-tight, thus heling to avoid energy losses. he characterising disk additionally ensures excellent control stability throughout the entire flow range. Resistant against soiling due to sherical design hanks to its comact size, the characterised control valve is a flexible and sace-saving solution otorised with roven Belimo actuator technology he valve closes air bubble-tight and is resistant against oor water quality inimum energy costs due to efficient motor technology EPIV ressure-indeendent characterised control valve. he clever way to control the flow rate. he EPIV combines 4 functions in one ready-to-install unit: measuring, controlling, balancing and shutting. his is how you increase efficiency during lanning, imlementation and oeration. ime-saving and reliable valve selection in accordance with maximum volumetric flow Raid, simle installation and commissioning Automatic, ermanent hydronic balancing through the valve Securing the correct amount of water with differential ressure changes and with artial load Real-time information on the measured flow rate Belimo Energy Valve with intelligent web server. A further ste into the future. he new Belimo Energy Valve has not only been imroved, it has also become more intelligent. In addition to measuring, controlling, balancing and shutting, the energy monitoring feature is now also fully integrated in the Belimo Cloud. he ower outut of the heat exchanger is no longer influenced by water temerature and differential ressure Bus connections with BACnet, P-Bus and odbus with the same valve hanks to the newly designed user interface with its guided commissioning rocedure, the valve can be made ready for oeration in just a few stes Increase in system efficiency by using the Delta- manager to ensure the temerature sread he Belimo Cloud rovides analyses, otimisation, udates and suort BELIO CLOUD Other advantages of the Belimo Cloud hanks to the Belimo Cloud, the Belimo Energy Valve can be easily and quickly connected with the Internet. his allows the use of other services. Otimisation of the Delta- values by exerienced rofessionals at Belimo Regular reorting with a full overview of the current and ast erformance data such as flow rates, energy consumtion, suly and return temerature as well as Delta- he Belimo Cloud enables even better suort he online udates ensure that the Belimo Energy Valve is fully u-to-date at all times Straightforward access to all data over the entire life-cycle of the Belimo Energy Valves Subject to technical modifications 5

6 Product comarison Comarison of characterised control valve, electronic ressureindeendent characterised control valve (EPIV) and Belimo Energy Valve Characterised control valve Electronic ressureindeendent characterised control valve (EPIV) Belimo Energy Valve Closes air bubble-tight No activation losses Saving of heating / cooling energy Relaces control valve and shut-off valve Equal ercentage characteristic curve thanks to the characterising disc Very good control stability High control quality Reduced tendency to oscillate Low ower consumtion Reduced energy consumtion Lower energy costs Self-cleaning sherical design No sticking High oerating safety aintenance-free 5-year guarantee Long-term safety Simle design for maximum volumetric flow Simle setting of maximum volumetric flow Fast lanning Safe valve design Considerably simlified hydronic balancing Flexibility in lanning and later conversion No balancing valve required Fewer comonents Cost savings Fast and simle commissioning Pressure-indeendent flow control thanks to dynamic balancing Real-time flow measurement ransarency Correct amount of water after a differential ressure change and with artial-load oeration External stability of control Increased comfort All-in-One solution Fewer comonents Low installation outlays Energy monitoring Creates system transarency Indicates otimisation otential Increases system efficiency and reduces oerational costs Pressure-indeendent and temerature-indeendent ower control No influence on heating / cooling erformance as a result of ressure and temerature fluctuations Otimised comfort at all times Delta- manager Avoidance of "Low Delta- syndrome" Guaranteed required return temerature to the heat generator / cooling machine Increased system efficiency Reduced oerating costs Connection to the Belimo Cloud Automatic otimisation of Delta- settings Regular erformance reorts Suort via Belimo Cloud Automatic software udates Lifetime data storage Warranty extended to 7 years Subject to technical modifications

7 Page Pressure-deendent flow control 8 Electronic ressure-indeendent flow control 26 Electronic ressure-indeendent flow control with monitoring function Other solutions from Belimo 46 7

8 8 RH CO2 CO2 RH hrottling circuit Diverting circuit ixing circuit Injection circuit with 2-way valve

9 Pressure-deendent flow control Pressure-deendent flow control. hrottling circuit 0.2 Injection circuit with 2-way valve 4.3 ixing circuit 8.4 Diverting circuit 22 9

10 Pressure-deendent flow control. hrottling circuit CO2 Pressure-deendent flow control RH Illustration examle Alication descrition A change in osition at the valve causes the change in the volumetric flow in both the generator and the consumer circuits he ower outut at the heat exchanger is regulated by volumetric flow change Flow at heat generator / cooling machine: quantity-variable Flow at heat / cooling consumer: quantity-variable Pressure ratio at the manifold: ressurised anual balancing valve for static hydronic balancing of water amount Alication notes Strong recirocal influence when there is more than one consumer resent he hydronic balancing is erformed for the full load oerating oint When starting, take into account dead time induced by cooling; use circulation byass to avoid this if necessary. o avoid overheating with valve closed, equi with variable seed ums Saturation oeration of the heat exchanger leads to a reduced temerature sread. "Low Delta- syndrome" increases the energy consumtion by the ums and reduces the efficiency of the generator. yical alications Air reheater is ermissible in the event of temerature stratification in artial-load oeration Air cooler with dehumidification Subject to technical modifications

11 Pressure-deendent flow control Disturbance variables Differential ressure changes result in a change in the flow rate Change in ower outut emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Valve osition Bill of material Belimo tye Descrition Quantity Costs R2..xx-S.. (DN ) ) 2-way characterised control valve, internal thread, DN., k vs... m 3 /h R6..W..-S8 (DN 65 50) 2-way characterised control valve, flange, DN., k vs. m 3 /h + er zone LR24A-SR, NR24A-SR, SR24A-SR, SR24A-SR-5, GR24A-SR-5 3) Rotary actuator,. Nm, AC/DC 24 V, modulating Balancing valve DN. Work time required: hydronic balancing ½ h 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 22DH-.. 8) Humidity and temerature duct sensor DC 0 5/0 V 22DC-.. 8) CO 2 and temerature duct sensor DC 0 5/0 V 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 NF24A, SF24A, EF24A, Rotary actuator with emergency control function... Nm, <8 m 2, GK24A 0) AC/DC 24 V, oen-close LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units + er zone + er zone + ½ h er zone er zone 2 2 er zone Pressure-deendent flow control ) Also available with external thread (R4..) or flange (R6..Rxx-B..) 3) Other available actuator variants: - AC/DC 24 V and AC 230 V - Oen-close or 3-oint control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 8) Also available with outut signal ma 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications

12 Pressure-deendent flow control ender secification 2-way characterised control valve from Belimo Suly and installation of tight-closing 2-way valve with equal-ercentage characteristic curve and high resistance to soiling. With integrated characterising disk for water-side modulating control of air-handling and heating systems. Pressure-deendent flow control Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) k vs value: m 3 /h edia: cold and warm water, water with glycol u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in the oening range edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 400 kpa) Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD EFZEL (DN : stainless steel) anufacture: Belimo ye: R2..xx-S.. (DN ) ye: R6..W..-S8 (DN 65 50) Other versions available: external thread or flange connection (DN ) Rotary actuator from Belimo (examle LR24A-SR for CCV u to DN 25) Rotary actuator for the modulating adjustment of 2-way, 3-way and 6-way characterised control valves. Direct mounting on the ball valve with central screw. he assembly tool is integrated in the add-on osition indication. Overload rotected and without end switch, current reduction in rest osition. orque: 5 Nm Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V Oerating range: DC 2...0V Position feedback: DC V Power consumtion: - in oeration:.5 W - in rest osition: 0.4 W - for wire sizing: 3 VA Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Running time: 90 s / 90 Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC anufacture: ye: Belimo LR24A-SR 0 Nm to DN 40: NR24A-SR 20 Nm to DN 50: SR24A-SR 20 Nm for DN 65 and DN 80: SR24A-SR-5 40 Nm for DN : GR24A-SR Subject to technical modifications

13 Pressure-deendent flow control Other actuator variants: - AC 230 V - Various bus communication rotocols - Oen-close, 3-oint - odulating V - Fast runner - Emergency control function Including electrical and mechanical accessories 5 year warranty Belimo features and benefits Water alications Feature Equal-ercentage flow characteristic due to characterising disk No inlet jum Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Comact dimensions Benefit Very good control stability throughout the entire flow range Good controllability of low oututs No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 year warranty Long-term safety Great flexibility in lanning and design Pressure-deendent flow control Subject to technical modifications 3

14 Pressure-deendent flow control.2 Injection circuit with 2-way valve Pressure-deendent flow control Illustration examle Alication descrition Valve osition determines the water flow injected into the consumer circuit Regulation of ower outut on heat exchanger by changing the temerature Flow at heat generator: quantity-variable Flow at heat consumer: quantity-constant Pressure ratio at the manifold: ressurised anual balancing valve for static hydronic balancing of injected water amount Alication notes Strong recirocal influence when there is more than one consumer resent he hydronic balancing is erformed for the full load oerating oint o avoid overheating with valve closed, equi with variable seed ums yical alications Air reheater with frost hazard Air reheater Subject to technical modifications

15 Pressure-deendent flow control Disturbance variables Differential ressure changes result in a change in the flow rate Change in ower outut emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Valve osition Bill of material Belimo tye Descrition Quantity Costs R2..xx-S.. (DN ) ) 2-way characterised control valve, internal thread, DN., k vs... m 3 /h R6..W..-S8 (DN 65 50) 2-way characterised control valve, flange, DN., k vs... m 3 /h LR24A-SR, NR24A-SR, SR24A-SR, SR24A-SR-5, GR24A-SR-5 3) Rotary actuator,. Nm, AC/DC 24 V, modulating Balancing valve DN... 2 Work time required: hydronic balancing ½ h 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 3 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 LF24, NF24A, SF24A, Rotary actuator with emergency control function,... Nm, <6 m 2, EF24A 0) AC/DC 24 V, oen-close L24A-SR, N24A-SR, Rotary actuator,... Nm, <4 m 2, AC/DC 24 V, modulating S24A-SR 0) LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units er zone Pressure-deendent flow control ) Also available with external thread (R4..) or flange (R6..Rxx-B..) 3) Other available actuator variants: - AC/DC 24 V and AC 230 V - Oen-close or 3-oint control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 5

16 Pressure-deendent flow control ender secification 2-way characterised control valve from Belimo Suly and installation of tight-closing 2-way valve with equal-ercentage characteristic curve and high resistance to soiling. With integrated characterising disk for water-side modulating control of air-handling and heating systems. Pressure-deendent flow control Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) k vs value: m 3 /h edia: cold and warm water, water with glycol u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in the oening range edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 400 kpa) Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD EFZEL (DN : stainless steel) anufacture: Belimo ye: R2..xx-S.. (DN ) ye: R6..W..-S8 (DN 65 50) Other versions available: external thread or flange connection (DN ) Rotary actuator from Belimo (examle LR24A-SR for CCV u to DN 25) Rotary actuator for the modulating adjustment of 2-way, 3-way and 6-way characterised control valves. Direct mounting on the ball valve with central screw. he assembly tool is integrated in the add-on osition indication. Overload rotected and without end switch, current reduction in rest osition. orque: 5 Nm Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V Oerating range: DC 2...0V Position feedback: DC V Power consumtion: - in oeration:.5 W - in rest osition: 0.4 W - for wire sizing: 3 VA Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Running time: 90 s / 90 Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC anufacture: ye: Belimo LR24A-SR 0 Nm to DN 40: NR24A-SR 20 Nm to DN 50: SR24A-SR 20 Nm for DN 65 and DN 80: SR24A-SR-5 40 Nm for DN : GR24A-SR Subject to technical modifications

17 Pressure-deendent flow control Other actuator variants: - AC 230 V - Various bus communication rotocols - Oen-close, 3-oint - odulating V - Fast runner - Emergency control function Including electrical and mechanical accessories 5 year warranty Belimo features and benefits Water alications Feature Equal-ercentage flow characteristic due to characterising disk No inlet jum Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Comact dimensions Benefit Very good control stability throughout the entire flow range Good controllability of low oututs No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 year warranty Long-term safety Great flexibility in lanning and design Pressure-deendent flow control Subject to technical modifications 7

18 Pressure-deendent flow control.3 ixing circuit CO2 Pressure-deendent flow control RH Illustration examle Alication descrition he valve osition is used to influence the quantity of return water that is added to the suly via the byass Regulation of ower outut on heat exchanger by changing the temerature Flow at heat generator: quantity-variable Flow at heat consumer: quantity-constant Pressure ratio at the manifold: low-ressure Alication notes Recommended only for low-ressure manifolds, in case of a ressurised manifold use an injection circuit with 2-way valve Because of the dead time, this is not recommended for systems with a distance of more than 20 m between byass and temerature sensor If the temerature difference between the consumer flow and the generator flow is high, a mixing circuit with fixed remixing (double mixing circuit) is to be rovided yical alications Air reheater with frost hazard Air reheater Air cooler without controlled dehumidification Subject to technical modifications

19 Pressure-deendent flow control Disturbance variables emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Valve osition Bill of material Belimo tye Descrition Quantity Costs R3..xx-S.. 2) 3-way characterised control valve from Belimo, internal thread, DN..., k vs... m 3 /h LR24A-SR, NR24A-SR, SR24A-SR, SR24A-SR-5, Rotary actuator,... Nm, AC/DC 24 V, modulating GR24A-SR-5 3) Balancing valve DN... Work time required: hydronic balancing of consumer circuit with constant amount 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 22DH-.. 8) Humidity and temerature duct sensor DC 0 5/0 V 22DC-.. 8 ) CO 2 and temerature duct sensor DC 0 5/0 V 0APS-0.. Differential ressure switch 4 NF24A, SF24A, EF24A, Rotary actuator with emergency control function,... Nm, <8 m 2, GK24A 0) AC/DC 24 V, oen-close ½ h 3 2 Pressure-deendent flow control 2) Also available with external thread (R5..) or flange (R7..Rxx-B..) 3) Other available actuator variants: - AC/DC 24 V and AC 230 V - Oen-close or 3-oint control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 8) Also available with outut signal ma 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 9

20 Pressure-deendent flow control ender secification 3-way characterised control valve from Belimo Suly and installation of a 3-way valve with high resistance to soiling. Equal-ercentage characteristic curve and tight-closing control ath A-AB. With integrated characterising disk for water-side modulating control of air-handling and heating systems. Pressure-deendent flow control Design: mixing valve 3-way, DN 5 DN 50 Connection: internal thread R..." k vs value: m 3 /h edia: cold and warm water with glycol of u to max. 50% vol. Leakage rate control ath A-AB: leakage rate A, tight (EN 2266-) Leakage rate byass B-AB:...2% of the highest ossible k vs value of the nominal diameter (DN) used Characteristic curve control ath A-AB: equal ercentage (VDI/VDE 278), otimised in the oening range Characteristic curve byass B-AB: linear (VDI/VDE 278) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa Differential ressure dmax: 350 kpa Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: anufacture: ye: brass body nickel-lated stainless steel stainless steel O-ring EPD PFE, O-ring EPD EFZEL (R S4, R S4, R S4: stainless steel) Belimo R3..xx-S.. Other versions available: external thread or flange connection Rotary actuator from Belimo (examle LR24A-SR for CCV u to DN 25) Rotary actuator for the modulating adjustment of 2-way, 3-way and 6-way characterised control valves. Direct mounting on the ball valve with central screw. he assembly tool is integrated in the add-on osition indication. Overload rotected and without end switch, current reduction in rest osition. orque: 5 Nm Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V Oerating range: DC 2...0V Position feedback: DC V Power consumtion: - in oeration:.5 W - for rest osition: 0.4 W - for wire sizing: 3 VA Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Running time: 90 s / 90 Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC anufacture: ye: Belimo LR24A-SR 0 Nm to DN 40: NR24A-SR 20 Nm to DN 50: SR24A-SR 20 Nm for DN 65 and DN 80: SR24A-SR-5 40 Nm for DN : GR24A-SR Subject to technical modifications

21 Pressure-deendent flow control Other actuator variants: - AC 230 V - Various bus communication rotocols - Oen-close, 3-oint - odulating V - Fast runner - Emergency control function Including electrical and mechanical accessories 5 year warranty Belimo features and benefits Water alications Feature Equal-ercentage flow characteristic (A-AB) due to characterising disk No inlet jum Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Comact dimensions Benefit Very good control stability throughout the entire flow range Good controllability of low oututs No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 year warranty Long-term safety Great flexibility in lanning and design Pressure-deendent flow control Subject to technical modifications 2

22 Pressure-deendent flow control.4 Diverting circuit Pressure-deendent flow control Illustration examle Alication descrition Valve osition determines the amount of water flowing to the heat exchanger and the amount flowing via the byass directly from suly to return Regulation of ower outut on heat exchanger by changing the volume Flow at the cooling machine: quantity-constant Flow at cooling consumer: quantity-variable Pressure ratio at the manifold: ressurised anual balancing valve for static hydronic balancing of water amount Alication notes Unused water leads to a substantial reduction in temerature sread with artial loads he entire water amount is umed in the generator circuit even with zero and artial load Low temerature difference leads to an increased ower consumtion on the ums and a reduced efficiency of the generator ("Low Delta- syndrome") Increase in temerature sread and system efficiency via throttling circuit he hydronic balancing is erformed for the full load oerating oint yical alications Air reheater is ermissible in the event of temerature stratification in artial-load oeration Air cooler with dehumidification Subject to technical modifications

23 Pressure-deendent flow control Disturbance variables Differential ressure changes result in a change in the flow rate Change in ower outut emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Valve osition Bill of material Belimo tye Descrition Quantity Costs R3..xx-S.. 2) 3-way characterised control valve, internal thread, DN..., k vs... m 3 /h LR24A-SR, NR24A-SR, SR24A-SR, SR24A-SR-5, Rotary actuator,. Nm, AC/DC 24 V, modulating GR24A-SR-5 3) Balancing valve DN. Work time required: hydronic balancing ½ h 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 3 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 LF24, NF24A, SF24A, Rotary actuator with emergency control function,... Nm, <6 m 2, EF24A 0) AC/DC 24 V, oen-close L24A-SR, N24A-SR, Rotary actuator,... Nm, <4 m 2, AC/DC 24 V, modulating S24A-SR 0) L24A, N24A, Rotary actuator,... Nm, <4 m 2, AC/DC 24 V, oen-close 2 er zone S24A 0) 3 2 Pressure-deendent flow control 2) Also available with external thread (R5..) or flange (R7..Rxx-B..) 3) Other available actuator variants: - AC/DC 24 V and AC 230 V - Oen-close or 3-oint control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 23

24 Pressure-deendent flow control ender secification 3-way characterised control valve from Belimo Suly and installation of a 3-way valve with high resistance to soiling. Equal-ercentage characteristic curve and tight-closing control ath A-AB. With integrated characterising disk for water-side modulating control of air-handling and heating systems. Pressure-deendent flow control Design: mixing valve 3-way, DN 5 DN 50 Connection: internal thread R..." k vs value: m 3 /h edia: cold and warm water with glycol of u to max. 50% vol. Leakage rate control ath A-AB: leakage rate A, tight (EN 2266-) Leakage rate byass B-AB:...2% of the highest ossible k vs value of the nominal diameter (DN) used Characteristic curve control ath A-AB: equal ercentage (VDI/VDE 278), otimised in the oening range Characteristic curve byass B-AB: linear (VDI/VDE 278) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa Differential ressure dmax: 350 kpa Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: anufacture: ye: brass body nickel-lated stainless steel stainless steel O-ring EPD PFE, O-ring EPD EFZEL (R S4, R S4, R S4: stainless steel) Belimo R3..xx-S.. Other versions available: external thread or flange connection Rotary actuator from Belimo (examle LR24A-SR for CCV u to DN 25) Rotary actuator for the modulating adjustment of 2-way, 3-way and 6-way characterised control valves. Direct mounting on the ball valve with central screw. he assembly tool is integrated in the add-on osition indication. Overload rotected and without end switch, current reduction in rest osition. orque: 5 Nm Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V Oerating range: DC 2...0V Position feedback: DC V Power consumtion: - in oeration:.5 W - for rest osition: 0.4 W - for wire sizing: 3 VA Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Running time: 90 s / 90 Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC anufacture: ye: Belimo LR24A-SR 0 Nm to DN 40: NR24A-SR 20 Nm to DN 50: SR24A-SR 20 Nm for DN 65 and DN 80: SR24A-SR-5 40 Nm for DN : GR24A-SR Subject to technical modifications

25 Pressure-deendent flow control Other actuator variants: - AC 230 V - Various bus communication rotocols - Oen-close, 3-oint - odulating V - Fast runner - Emergency control function Including electrical and mechanical accessories 5 year warranty Belimo features and benefits Water alications Feature Equal-ercentage flow characteristic (A-AB) due to characterising disk No inlet jum Air bubble tight-closing characterised control valve 3-way characterised control valve with reduced byass Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Comact dimensions Benefit Very good control stability throughout the entire flow range Good controllability of low oututs No activation losses with zero load No balancing valve required in the byass line Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 year warranty Long-term safety Great flexibility in lanning and design Pressure-deendent flow control Subject to technical modifications 25

26 26 hrottling circuit Injection circuit with 2-way valve RH CO2

27 2 Electronic ressure-indeendent flow control Electronic ressure-indeendent flow control 2. hrottling circuit Injection circuit with 2-way valve

28 Electronic ressure-indeendent flow control 2. hrottling circuit CO2 Electronic ressure-indeendent flow control 2 RH Illustration examle Alication descrition Changed requirement at the valve causes the change in the volumetric flow in both the generator and the consumer circuits he ower outut at the heat exchanger is regulated by volumetric flow change Flow at heat generator / cooling machine: quantity-variable Flow at heat / cooling consumer: quantity-variable Pressure ratio at the manifold: ressurised Dynamic balancing by the electronic ressure-indeendent characterised control valve (EPIV) ensures the correct amount of water at full and artial load oerating oints System transarency (volumetric flow) Alication notes Recirocal influence with several consumers is eliminated due to the dynamic balancing Dynamic balancing is carried out automatically at each oerating oint Substantially reduced "Low Delta- syndrome" risk due to the correct amount of water Constant um otimisation is ossible due to the feedback signal regarding valve osition When starting, take into account dead time induced by cooling; use circulation byass to avoid this if necessary. o avoid overheating with valve closed, equi with variable seed ums yical alications Air reheater is ermissible in the event of temerature stratification in artial-load oeration Air cooler with dehumidification Subject to technical modifications

29 Electronic ressure-indeendent flow control Disturbance variables hanks to dynamic balancing, changes in differential ressure do not cause any changes in the rate of flow emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Real-time flow measurement Valve osition List of materials Belimo tye Descrition Quantity Costs EP..R+P (DN 5 50) 4) P6..W..E-P (DN 65 50) 4) Electronic ressure-indeendent characterised control valve (EPIV), DN..., V nom. l/s 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 6) 7) Duct/immersion 0D-.. / A-22P-A.. temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 22DH-.. 8) Humidity and temerature duct sensor DC 0 5/0 V 22DC-.. 8) CO 2 and temerature duct sensor DC 0 5/0 V 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 NF24A, SF24A, EF24A, Rotary actuator with emergency control function... Nm, <8 m 2, GK24A 0) AC/DC 24 V, oen-close LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units + er zone er zone 2 2 er zone Electronic ressure-indeendent flow control 2 4) Also available with odbus or electrical emergency control function New designation for P6..W..E-.. as from Q3/207: EP..F+.. 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 8) Also available with outut signal ma 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 29

30 Electronic ressure-indeendent flow control ender secification Communication-caable characterised control valve with sensor-oerated flow control (EPIV) from Belimo Suly and installation of a tight-closing, electronic ressure-indeendent 2-way valve with switchable characteristic curve (equal ercentage/linear) and high resistance to soiling. Electronic ressure-indeendent flow control 2 For water-side modulating control of air-handling and heating systems. Consisting of characterised control valve with actuator and measuring ie with volumetric flow sensor. Communication via Belimo P-Bus or conventional control. Conversion of active sensor signals and switching contacts. Parameterisable via ZH EU or service tool F-P from Belimo. Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) Flow V nom : l/s Flow V max : l/s, adjustable Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V / communicative Oerating range: DC V, variable Position feedback: DC V, variable Power consumtion: - in oeration: 3.5 W (DN 5 25) - in rest osition:.3 W (DN 5 25) - for wire sizing: 6 VA (DN 5 25) Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC edia: cold and warm water, water with glycol u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in oening range (switchable to linear) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 340 kpa) heoretical k vs value: m 3 /h easuring rincile: ultrasonic volumetric flow measurement easuring accuracy: +/- 6% ( % V nom ) Control recision: +/- 0% ( % V nom ) in. flow measurement: % of V nom Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: easuring ie: brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD (DN : PFE, O-ring Viton) EFZEL (DN : stainless steel) brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) anufacture: Belimo ye: EP..R+P (DN ) ye: P6..W..E-P (DN 65 50) Also available with odbus or electrical emergency control function Including electrical and mechanical accessories 5-year warranty Subject to technical modifications

31 Electronic ressure-indeendent flow control Belimo features and benefits Water alications Proerties Simle design for maximum volumetric flow All-in-One solution Pressure-indeendent flow rate due to dynamic balancing Flow measurement Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking 5-year warranty Benefit ime-saving and simle valve selection 4 functions: measuring, controlling, dynamic balancing and shutting Extremely simlified commissioning Securing the correct amount of water with differential ressure changes and with artial load Excellent control stability across the entire flow range Real-time information water quantity No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety Long-term safety Electronic ressure-indeendent flow control Subject to technical modifications 3

32 Electronic ressure-indeendent flow control 2.2 Injection circuit with 2-way valve Electronic ressure-indeendent flow control 2 Illustration examle Alication descrition Valve requirement determines the amount of suly water injected into the consumer circuit Regulation of ower outut on heat exchanger by changing the temerature Flow at heat generator: quantity-variable Flow at heat consumer: quantity-constant Pressure ratio at the manifold: ressurised Dynamic balancing by the electronic ressure-indeendent characterised control valve (EPIV) ensures the correct amount of water at full and artial load oerating oints System transarency (volumetric flow) Alication notes Recirocal influence with several consumers is eliminated due to the dynamic balancing Dynamic balancing is carried out automatically at each oerating oint Constant um otimisation is ossible due to the feedback signal regarding valve osition o avoid overheating with valve closed, equi with variable seed ums yical alications Air reheater with frost hazard Air reheater Subject to technical modifications

33 Electronic ressure-indeendent flow control Disturbance variables hanks to dynamic balancing, changes in differential ressure do not cause any changes in the rate of flow emerature changes result in a change in transfer behaviour Change in ower outut Available measuring values and information Real-time flow measurement Valve osition List of materials Belimo tye Descrition Quantity Costs EP..R+P (DN 5 50) 4) P6..W..E-P (DN 65 50) 4) Electronic ressure-indeendent characterised control valve (EPIV), DN., V nom. l/s 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 3 6) 7) Duct/immersion 0D-.. / A-22P-A.. temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 LF24, NF24A, SF24A, Rotary actuator with emergency control function... Nm, <6 m 2, EF24A 0) AC/DC 24 V, oen-close L24A-SR, N24A-SR, Rotary actuator... Nm, <4 m 2, AC/DC 24 V, modulating S24A-SR 0) LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units er zone Electronic ressure-indeendent flow control 2 4) Also available with odbus or electrical emergency control function New designation for P6..W..E-.. as from Q3/207: EP..F+.. 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 33

34 Electronic ressure-indeendent flow control ender secification Communication-caable characterised control valve with sensor-oerated flow control (EPIV) from Belimo Suly and installation of a tight-closing, electronic ressure-indeendent 2-way valve with switchable characteristic curve (equal ercentage/linear) and high resistance to soiling. Electronic ressure-indeendent flow control 2 For water-side modulating control of air-handling and heating systems. Consisting of characterised control valve with actuator and measuring ie with volumetric flow sensor. Communication via Belimo P-Bus or conventional control. Conversion of active sensor signals and switching contacts. Parameterisable via ZH EU or service tool F-P from Belimo. Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) Flow V nom : l/s Flow V max : l/s, adjustable Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V / communicative Oerating range: DC V, variable Position feedback: DC V, variable Power consumtion: - in oeration: 3.5 W (DN 5 25) - in rest osition:.3 W (DN 5 25) - for wire sizing: 6 VA (DN 5 25) Connection: cable m, 4 x 0.75 mm 2 anual override: gear disengagement with ushbutton Protection class: III rotective extra low voltage Degree of rotection: IP54 EC: CE according to 2004/08/EC edia: cold and warm water, water with glycol u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in oening range (switchable to linear) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 340 kpa) heoretical k vs value: m 3 /h easuring rincile: ultrasonic volumetric flow measurement easuring accuracy: +/- 6% ( % V nom ) Control recision: +/- 0% ( % V nom ) in. flow measurement: % of V nom Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: easuring ie: brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD (DN : PFE, O-ring Viton) EFZEL (DN : stainless steel) brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) anufacture: Belimo ye: EP..R+P (DN ) ye: P6..W..E-P (DN 65 50) Also available with odbus or electrical emergency control function Including electrical and mechanical accessories 5-year warranty Subject to technical modifications

35 Electronic ressure-indeendent flow control Belimo features and benefits Water alications Proerties Simle design for maximum volumetric flow All-in-One solution Pressure-indeendent flow rate due to dynamic balancing Flow measurement Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking 5-year warranty Benefit ime-saving and simle valve selection 4 functions: measuring, controlling, dynamic balancing and shutting Extremely simlified commissioning Securing the correct amount of water with differential ressure changes and with artial load Excellent control stability across the entire flow range Real-time information water quantity No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety Long-term safety Electronic ressure-indeendent flow control Subject to technical modifications 35

36 CO2 RH hrottling circuit Injection circuit with 2-way valve 36

37 3 Electronic ressure-indeendent flow control with monitoring function Electronic ressure-indeendent flow control with monitoring function 3. hrottling circuit Injection circuit with 2-way valve

38 Electronic ressure-indeendent flow control with monitoring function 3. hrottling circuit Electronic ressure-indeendent flow control with monitoring function CO2 RH 3 Illustration examle Alication descrition Changed requirement at the valve causes the change in the volumetric flow in both the generator and the consumer circuits he ower outut at the heat exchanger is regulated by volumetric flow change Flow at heat generator / cooling machine: quantity-variable Flow at heat / cooling consumer: quantity-variable Pressure ratio at the manifold: ressurised Dynamic balancing by the Belimo Energy Valve ensures the correct amount of water at full and artial load Power control ensures the required heating or cooling outut at any time Full system transarency (volumetric flow, temeratures, cooling / heating outut, ) with data recording and Belimo Cloud connection Alication notes Recirocal influence with several consumers is eliminated due to the dynamic balancing Dynamic balancing is carried out automatically at each oerating oint Efficient avoidance of the "Low Delta- syndrome" due to ressure-indeendent flow control and the unique Delta- manager Constant um otimisation is ossible due to the feedback signal regarding valve osition Dead time at the time of starting that has resulted from cooling should be taken into account and avoided if necessary via circulation byass; controlled byass is ossible using the extractable temerature measurement value of the Belimo Energy Valve o avoid overheating with valve closed, equi with variable seed ums yical alications Air reheater is ermissible in the event of temerature stratification in artial-load oeration Air cooler with dehumidification Subject to technical modifications

39 Electronic ressure-indeendent flow control with monitoring function Disturbance variables hanks to dynamic balancing, changes in differential ressure do not cause any changes in the rate of flow A changed transfer behaviour due to temerature changes is balanced automatically (*) no change in ower outut (*) in oerating mode 'Power control' Available measuring values and information Real-time flow measurement Flow and return temerature emerature difference "Delta-" Current ower outut Heating and/or cooling energy Characteristics of the heat exchanger Change in the system characteristics Valve osition List of materials Belimo tye Descrition Quantity Costs EV..R+BAC (DN 5 50) 5) P6..W..EV-BAC (DN 65 50) 5) Belimo Energy Valve, electronic ressure-indeendent characterised control valve with energy monitoring, DN..., V nom. l/s 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/temerature sensor, assive 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 22DH-.. 8) Humidity and temerature duct sensor DC 0 5/0 V 22DC-.. 8) CO 2 and temerature duct sensor DC 0 5/0 V 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 NF24A, SF24A, EF24A, Rotary actuator with emergency control function... Nm, <8 m 2, GK24A 0) AC/DC 24 V, oen-close LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units + er zone er zone Electronic ressure-indeendent flow control with monitoring function 3 5) Also available with electric emergency control function New designation for P6..W..EV-.. as from Q3/207: EV..F+.. 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 8) Also available with outut signal ma 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 39

40 Electronic ressure-indeendent flow control with monitoring function ender secification Belimo Energy Valve : Communication-caable, electronic ressure-indeendent characterised control valve with energy monitoring and sensor-oerated flow and ower control Electronic ressure-indeendent flow control with monitoring function 3 Suly and installation of a tight-closing, electronic ressure-indeendent 2-way valve with switchable characteristic curve (equal ercentage / linear), ower and energy-monitoring function and high resistance to soiling. For water-side modulating control of air-handling and heating systems. Consisting of characterised control valve with actuator and measuring ie with volumetric flow sensor and temerature sensors. Communication via BACnet IP, BACnet S/P, odbus RU, odbus CP, Belimo P-Bus or conventional control. Ethernet 0/00 bit/s, CP/IP with integrated Web server. Parameterisable via integrated Web server or ZH EU. Connection to the Belimo Cloud. Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) Flow V nom : l/s Flow V max : l/s, adjustable Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V / communicative Oerating range: DC V, variable Position feedback: DC V, variable Power consumtion: - in oeration: 4 W (DN 5 25) - in rest osition: 3.7 W (DN 5 25) - for wire sizing: 6.5 VA (DN 5 25) Connection: cable m, 6 x 0.75 mm 2 Ethernet: RJ45 socket anual override: gear disengagement with ushbutton Protection class: III rotective extra low voltage Degree of rotection: IP54 (for use of rotective ca or grommet for RJ45 socket) EC: CE according to 2004/08/EC edia: cold and warm water with glycol of u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in oening range (switchable to linear) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 340 kpa) heoretical k vs value: m 3 /h easuring rincile: ultrasonic volumetric flow measurement easuring accuracy: +/- 6% ( % V nom ) Control recision: +/- 0% ( % V nom ) inimum flow measurement: % of V nom easuring accuracy of absolute temerature: +/ C (P000 EN6075 Class B) easuring accuracy of temerature difference: +/ d = 20 K Resolution: 0.05 C Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: easuring ie: -iece (only DN 5 50): brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD (DN : PFE, O-ring Viton) EFZEL (DN : stainless steel) brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) brass body nickel-lated anufacture: Belimo ye: EV..R+BAC (DN ) ye: P6..W..EV-BAC (DN 65 50) Subject to technical modifications

41 Electronic ressure-indeendent flow control with monitoring function Also available with electric emergency control function Including electrical and mechanical accessories 5-year warranty (7 years if connected to Belimo Cloud) Belimo features and benefits Water alications Proerties Simle design for maximum volumetric flow All-in-One solution Pressure-indeendent flow rate due to dynamic balancing Flow measurement Power control Recording of all system data from ast 3 months Delta- manager Connection to the Belimo Cloud Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Benefit ime-saving and simle valve selection 5 functions: measuring, controlling, dynamic balancing, shutting and monitoring function Extremely simlified commissioning Securing the correct amount of water with differential ressure changes and with artial load Excellent control stability across the entire flow range Real-time information water quantity emerature and differential ressure-indeendent oeration Full system transarency indicates otimisation otential Changes in the system erformance are evident Hels ensure reservation of value of the entire system Avoidance of "Low Delta- syndrome" No saturation oeration of the heat exchanger in the resence of insufficient temerature sread Efficient oeration of ums and heat generator or cooling machine Delta- management by exerts from Belimo ransarency due to regular erformance reorts Remote maintenance and diagnostics Suort via Belimo Cloud Free software udates Data storage over the entire life-cycle Extension of warranty to 7 years No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 or 7-year warranty Long-term safety Electronic ressure-indeendent flow control with monitoring function Subject to technical modifications 4

42 Electronic ressure-indeendent flow control with monitoring function 3.2 Injection circuit with 2-way valve Electronic ressure-indeendent flow control with monitoring function 3 Illustration examle Alication descrition Valve requirement determines the amount of suly water injected into the consumer circuit Regulation of ower outut on heat exchanger by changing the temerature Flow at heat generator: quantity-variable Flow at heat consumer: quantity-constant Pressure ratio at the manifold: ressurised Dynamic balancing by the Belimo Energy Valve ensures the correct amount of water at full and artial load Power control ensures the required heating or cooling outut at any time Full system transarency (volumetric flow, temeratures, cooling / heating outut, ) with data recording and Belimo Cloud connection Alication notes Recirocal influence with several consumers is eliminated due to the dynamic balancing Dynamic balancing is carried out automatically at each oerating oint Constant um otimisation is ossible due to the feedback signal regarding valve osition o avoid overheating with valve closed, equi with variable seed ums yical alications Air reheater with frost hazard Air reheater Subject to technical modifications

43 Electronic ressure-indeendent flow control with monitoring function Disturbance variables hanks to dynamic balancing, changes in differential ressure do not cause any changes in the rate of flow A changed transfer behaviour due to temerature changes is balanced automatically (*) no change in ower outut (*) in oerating mode 'Power control' Available measuring values and information Real-time flow measurement Flow and return temerature emerature difference "Delta-" Current ower outut Heating and/or cooling energy Characteristics of the heat exchanger Change in the system characteristics Valve osition List of materials Belimo tye Descrition Quantity Costs EV..R+BAC (DN 5 50) 5) P6..W..EV-BAC (DN 65 50) 5) Belimo Energy Valve, electronic ressure-indeendent characterised control valve with energy monitoring, DN., V nom... l/s 0U-.. 6) Outdoor temerature sensor, assive 0D-.. 6) Duct/immersion temerature sensor, assive 3 6) 7) 0D-.. / A-22P-A.. Duct/immersion temerature sensor, assive with immersion ocket 0DS-0.. Frost rotection thermostat 0APS-0.. Differential ressure switch 4 22ADP-.. 9) Differential ressure sensor DC 0 5/0 V and 4 20 ma 2 LF24, NF24A, SF24A, Rotary actuator with emergency control function... Nm, <6 m 2, EF24A 0) AC/DC 24 V, oen-close L24A-SR, N24A-SR, Rotary actuator... Nm, <4 m 2, AC/DC 24 V, modulating S24A-SR 0) LV-D3-P, NV-D3-P Volumetric flow controller VAV-Comact for suly air and extract air from zones, suitable for demand-based fan control Note: VAV comonents obtainable only via the manufacturers of VAV units 2 2 er zone Electronic ressure-indeendent flow control with monitoring function 3 5) Also available with electric emergency control function New designation for P6..W..EV-.. as from Q3/207: EV..F+.. 6) Also available with active outut signal 7) Also available as stra-on temerature sensor 9) Also available with dislay 0) Other available actuator variants: - AC/DC 24 V and AC 230 V - 3-oint or modulating control - Communication-ready (P-Bus, LON, odbus, KNX) - With or without emergency control function - With or without auxiliary switch Subject to technical modifications 43

44 Electronic ressure-indeendent flow control with monitoring function ender secification Belimo Energy Valve : Communication-caable, electronic ressure-indeendent characterised control valve with energy monitoring and sensor-oerated flow and ower control Electronic ressure-indeendent flow control with monitoring function 3 Suly and installation of a tight-closing, electronic ressure-indeendent 2-way valve with switchable characteristic curve (equal ercentage / linear), ower and energy-monitoring function and high resistance to soiling. For water-side modulating control of air-handling and heating systems. Consisting of characterised control valve with actuator and measuring ie with volumetric flow sensor and temerature sensors. Communication via BACnet IP, BACnet S/P, odbus RU, odbus CP, Belimo P-Bus or conventional control. Ethernet 0/00 bit/s, CP/IP with integrated Web server. Parameterisable via integrated Web server or ZH EU. Connection to the Belimo Cloud. Construction tye: straight-through valve 2-way, DN Connection: internal thread R..." (DN 5 50) flange PN 6 (DN ) Flow V nom : l/s Flow V max : l/s, adjustable Nominal voltage: AC 24 V 50/60 Hz, DC 24 V Control: modulating DC V / communicative Oerating range: DC V, variable Position feedback: DC V, variable Power consumtion: - in oeration: 4 W (DN 5 25) - in rest osition: 3.7 W (DN 5 25) - for wire sizing: 6.5 VA (DN 5 25) Connection: cable m, 6 x 0.75 mm 2 Ethernet: RJ45 socket anual override: gear disengagement with ushbutton Protection class: III rotective extra low voltage Degree of rotection: IP54 (for use of rotective ca or grommet for RJ45 socket) EC: CE according to 2004/08/EC edia: cold and warm water with glycol of u to max. 50% vol. Leakage rate control ath: leakage rate A, tight (EN 2266-) Characteristic curve: equal ercentage (VDI/VDE 278), otimised in oening range (switchable to linear) edium temerature: C Permissible ressure s: 600 kpa Closing ressure ds: 400 kpa (DN : 690 kpa) Differential ressure dmax: 350 kpa (DN : 340 kpa) heoretical k vs value: m 3 /h easuring rincile: ultrasonic volumetric flow measurement easuring accuracy: +/- 6% ( % V nom ) Control recision: +/- 0% ( % V nom ) inimum flow measurement: % of V nom easuring accuracy of absolute temerature: +/ C (P000 EN6075 Class B) easuring accuracy of temerature difference: +/ d = 20 K Resolution: 0.05 C Housing: Closing element: Stem: Stem seal: Valve seat: Characterising disk: easuring ie: -iece (only DN 5 50): brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) stainless steel stainless steel O-ring EPD (DN : EPD Perox) PFE, O-ring EPD (DN : PFE, O-ring Viton) EFZEL (DN : stainless steel) brass body nickel-lated (DN : EN-JL040 (GG25), with rotective aint) brass body nickel-lated anufacture: Belimo ye: EV..R+BAC (DN ) ye: P6..W..EV-BAC (DN 65 50) Subject to technical modifications

45 Electronic ressure-indeendent flow control with monitoring function Also available with electric emergency control function Including electrical and mechanical accessories 5-year warranty (7 years if connected to Belimo Cloud) Belimo features and benefits Water alications Proerties Simle design for maximum volumetric flow All-in-One solution Pressure-indeendent flow rate due to dynamic balancing Flow measurement Power control Recording of all system data from ast 3 months Delta- manager Connection to the Belimo Cloud Air bubble tight-closing characterised control valve Low ower consumtion at the actuator Self-cleaning sherical design revents sticking Benefit ime-saving and simle valve selection 5 functions: measuring, controlling, dynamic balancing, shutting and energy monitoring Extremely simlified commissioning Securing the correct amount of water with differential ressure changes and with artial load Excellent control stability across the entire flow range Real-time information water quantity emerature and differential ressure-indeendent oeration Full system transarency indicates otimisation otential Changes in the system erformance are evident Hels ensure reservation of value of the entire system Avoidance of "Low Delta- syndrome" No saturation oeration of the heat exchanger in the resence of insufficient temerature sread Efficient oeration of ums and heat generator or cooling machine Delta- management by exerts from Belimo ransarency due to regular erformance reorts Remote maintenance and diagnostics Suort via Belimo Cloud Free software udates Data storage over the entire life-cycle Extension of warranty to 7 years No activation losses with zero load Small wire cross-section, low investment costs Low oerating costs High oerating safety 5 or 7-year warranty Long-term safety Electronic ressure-indeendent flow control with monitoring function Subject to technical modifications 45

46 Other solutions from Belimo Seamlessly integrated. he new sensors from Belimo. Seamless integration, reliability and intuitive design. he erfect comlement to actuators and valves. he new range of sensors is the result of Belimo s exerience and knowledge in the HVAC industry and our continuous focus on roviding added value to our customers. he innovative design offers easy installation and seamless integration to ensure otimal system erformance. he sensors from Belimo meet the highest quality and reliability demands. Proerties Benefits A variety of outut signals V, 4 20 ma or ability to communicate via BACnet or odbus Ensure a seamless connection to all major BACS on the market Sna-on cover First sensor housing on the market offering screwless no-tool design and NEA 4X / IP65 rotection. Due to this the installation becomes not only faster but also more reliable ounting late or mounting cli are sulied Serve as drill temlate and allow an easy mounting, fastening and installation Conformity with NEA 4X / IP65 All Belimo sensors with sna-on cover on housing meet these requirements. hese sensors are therefore suitable for demanding and outdoor alications including dirt, dust, humidity, condensation, rain and snow Universal design enclosure Ensures a streamlined roduct range, which makes the roduct selection rocess and installation quick and easy. he simle concet allows to avoid errors during installation and reduces the assembly time odular cable glands Suitable for additional wiring otions and mounting configurations. Removable sring loaded terminal block Allow time-saving, no-tool wiring and maximum ull-out force for highest reliability Reverse olarity rotection Reverse-olarity rotected to revent damage caused by incorrect wiring Subject to technical modifications

47 Other solutions from Belimo emerature sensors Accurate and reliable temerature readings are essential for otimal building comfort and energy efficiency. Outdoor air, duct and ie-temerature sensors are designed for easy installation and are comatible with all major BACS Variety of outut signals ensure seamless connection to all major BACS on the market U to 8 field-selectable roviding flexibility Sintered moisture rotection coating on all duct, immersion, and cable sensors rotects against condensation and mechanical stress and vibrations Humidity sensors Controlling humidity in buildings is critical to occuant comfort.it is also imortant to rotecting building infrastructure, roduction rocesses, stored goods and museum artwork. Comlementary olymer-caacitance sensor with an accuracy of ±2% relative humidity and long-term drift <±0.25% not affected by high humidity and contaminants ulti sensor with selectable outut-measurement values: relative humidity, absolute humidity, enthaly and dew oint Air Quality sensors U to 4 field-selectable temerature measurement ranges rovide flexibility in all fiels of alication Air quality sensors from Belimo, such as CO 2 and VOC sensors, guarantee otimal indoor air quality with increased comfort and maximised energy savings in buildings. Combinations with temerature and humidity sensors are also available, which hels reduce labour and material costs. Dual-channel CO 2 sensor based on NDIR technology he additional reference channel allows comensation of the long term drift, roviding recise accuracy and long-term stability; the sensor is comletely maintenance free Dual-channel self-calibration technology (Auto-Zero) allows the use of CO 2 sensors from Belimo in all buildings and alications including where the ABC method (Automatic Background Calibration) cannot be used Pressure sensor range Accurate ressure measurement is imortant for an otimum HVAC system erformance. Pressure sensors from Belimo measure very low to high ressures in air, water and refrigerants. he sensors measure ressure, differential ressure and volumetric flow accuracy for a reliable control and monitoring Selectable measuring ranges are available for alication flexibility Flow sensors Reliable measurement of flow lays an imortant role in maximising HVAC system efficiency and conserving energy. Inline flow sensors from Belimo utilise ultrasonic transit-time technology to rovide accurate and reeatable water-flow measurement. heir comact size and insensitivity to dirt make them ideal for use with HVAC chilled water, hot water and water/glycol solutions throughout the entire temerature range. he sensor consists of corrosion-resistant materials Due to the ultrasonic measurement rincile it is insensitive to contamination Low ower consumtion of 0.5 W saves energy and transformer caacity ±2% accuracy of reading and ±0.5% reeatability ensure accurate and recise flow measurement Subject to technical modifications 47

48 Other solutions from Belimo General air solutions Air treatment, distribution, control and feedback. he world's most comrehensive range of electrical actuator solutions with or without emergency control function for air damers of u to 8 m2 includes Belimo rotary, linear and full-rotation actuators with a wide-range of motorisation levels and actuating time. he actuators cover almost all ower requirements for the control of air flows in air-conditioning lants, from treatment and distribution to feedback and retreatment. he range also includes secial actuators for indoor and outdoor use in extreme conditions. Proerties Benefits ested Swiss quality since 40 years Reliable and durable roducts Comrehensive roduct range he right actuator for every alication Energy-efficient actuator technology Reduces oerating costs Low commissioning costs Cost-otimised system creation aximum system safety System availability without restriction Subject to technical modifications

49 Other solutions from Belimo Standard actuators without emergency control function Belimo offers a comrehensive range of actuators worldwide. he standard actuators without emergency control function include rotary actuators, linear actuators and full-rotation actuators. hey are sacesaving, robust, energy-saving and durable. Rotary actuators Comrehensive range of actuators Customised solutions available ex works Comrehensive electrical and mechanical accessories Linear actuators he slimmest actuator of its tye Robust comact actuator Simle installation Full-rotation actuators Flexible angle of rotation in the alication Angle of rotation limitation u to 800 Can also be used for rotation without limits Standard actuators with emergency control function Actuators with emergency control function are essential for the system safety. Difference is made between mechanical and electrical emergency control function. Rotary actuators with mechanical emergency control function Comrehensive range of actuators Connection voltage for easy lanning and commissioning Closure at voltage interrution in <20 s Rotary and linear actuator with electric emergency control function aximum energy efficiency at rest osition Bridging of voltage interrutions of u to 0s Emergency setting osition % adjustable Secial actuators Belimo is your artner if you need secial actuators. he following two otions are described in more detail. Rotary actuators for extreme conditions he most robust actuator of its tye with IP66/67 and NEA 4 With and without emergency control function u to 40 Nm Otional for ambient temeratures u to -40 C Flexible otions for individual customer versions Comact actuators with damer blade Four ie diameter of 00, 25, 50 and 60 mm Suitable for aartment ventilation Extremely quiet and energy-saving Subject to technical modifications 49

50 Other solutions from Belimo Demand controlled fans Not as much as ossible, but as much as necessary. An efficient fan control is a vital art of a modern, energy-efficient air handling unit. o this end, the required room volumes are measured by means of resence, temerature and air quality sensors and rocessed as setoint value for the local volumetric flow controllers. hese in turn generate demand signals for fans of the air handling unit. o regulate fan outut, frequency converter-controlled fans are increasingly being joined by directly controlled EC fans. his is the task and the strength of the Fan Otimiser system: the damer ositions of the volumetric flow controller VAV-Comact are detected via the bus system and used as demand signal for the energy-efficient control of the fans. he volume-variable ventilation systems from Belimo are often used in hositals, hotels, offices, administration and industrial buildings as well increasingly in the energy-efficient residential construction. Proerties Adatation of the fan erformance to the effective demand Benefits U to 50% less energy consumtion due to considering artial load situations Oen system All control functions are ossible: CAV, VAV with CO 2, VOC, temerature, resence sensors etc. Dee rimary ressure Reduced flow noise Reduced ressure loss in the duct System finds oerating oint indeendently Simle commissioning Conversion does not require adatation (rovided total air volume is sufficient) No reserves required Comensates for some design errors Subject to technical modifications

51 Other solutions from Belimo Fan control With fan control you will simly increase room comfort. It can be easily connected and addressed to make it ready for oeration. Efficient commissioning Low air duct ressure reduces the flow noise Small ressure loss via damers reduces the energy consumtion VAV-Comact controllers he VAV-Comact is a low-cost unit comrising differential ressure sensor, controller and actuator, and has been setting standards in volumetric flow control in rooms and zones since 990. Distribution through damer manufacturers as tested and reset VAV units Locally arameterisable with smart hone a, service tool & PC-ool Adjustment and service tools he setu and service tools from Belimo will facilitate your work. he PC tool is used to grahically dislay all setoint and actual values as well as control aths. In addition, this is useful for system controls With the Belimo Assistant A you can arameterise and configure your Belimo devices via NFC-interface he adjustment tool ZH EU can be used to establish a reliable and roven connection to the tool socket Belimo P-Bus t t t he use of the Belimo P-Bus solutions will significantly reduce the sace required for installation. his facilitates the installation additionally and reduces the costs. on CO 2 VOC r.h. P artner solution Cost-effective, quickly available U to 70% less wiring effort No bus connections necessary Structured, flexible toology he entire roduct range is suitable for P-Bus Simle integration in other systems Actuator relacement via redefined address odbus RU, LonWorks, KNX und BACnet t t t t In cases where the customer wishes to connect a final controlling element directly to a higher level network, Belimo rovides various actuators with an integrated interface. his enables a direct connection to field buses commonly used for HVAC without additional hardware, which eliminates additional sources of error he system integrators can integrate the actuators easily and using a software environment with which they are familiar Subject to technical modifications 5

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency Technical data sheet EV..R+KBAC Characterised control valve (CCV) with sensor-operated flow rate or power control, power and energymonitoring function, 2-way, internal thread (Energy Valve), with emergency

More information

kvs theor.: Theoretical kvs value for pressure drop calculation Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

kvs theor.: Theoretical kvs value for pressure drop calculation Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency Technical data sheet EV..R+BAC Characterised control valve (CCV) with sensor-operated flow rate or power control, power and energy-monitoring Nominal voltage AC/DC 4 V Control modulating For closed cold

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency Technical data sheet P6..W..EV-BAC Characterised control valve (CCV) with sensor-operated flow rate or power control, power and energy-monitoring (Energy Valve) Nominal voltage AC/DC 4 V Control Modulating

More information

GRUNDFOS DATA BOOKLET. CHV booster. Hydro Pack, Hydro Dome 50 Hz

GRUNDFOS DATA BOOKLET. CHV booster. Hydro Pack, Hydro Dome 50 Hz GRUNDFOS DATA BOOKLET CV booster ydro Pack, ydro Dome 5 z Contents ydro Pack General data Performance range Page 3 Alications Page 4 General descrition Page 4 Oerating conditions Page 4 Tye key Page 4

More information

Characterised Control Valves with Actuators

Characterised Control Valves with Actuators Characterised Control Valves with Actuators Technical Databook Version 8.6 Belimo Asia Pacific Contents Control Valves and Actuators Product Overview 4 Characterised Control Valve 6 Sizing of Ball Valves

More information

GRUNDFOS DATA BOOKLET. Hydro Grundfos Hydro 1000 booster sets with 1-4 CR pumps 50 Hz

GRUNDFOS DATA BOOKLET. Hydro Grundfos Hydro 1000 booster sets with 1-4 CR pumps 50 Hz GRUNDFOS DATA BOOKLET ydro Grundfos ydro booster sets with 1-4 CR ums z Contents Product data Performance range 3 ydro 4 Tye key 4 Oerating conditions 4 Other versions on request 4 Function 5 Grundfos

More information

Power consumption In operation At rest For wire sizing. Non-operating temperature

Power consumption In operation At rest For wire sizing. Non-operating temperature echnical data sheet DRC4G--7 Rotary actuator for butterfly valves for outdoor applications orque 90 Nm (not constant) Nominal voltage AC/DC 4 V Control: Open-close IP66 Optimum protection against moisture

More information

GRUNDFOS DATA BOOKLET. Hydro MPC. Booster systems with 2 to 6 pumps 50 Hz

GRUNDFOS DATA BOOKLET. Hydro MPC. Booster systems with 2 to 6 pumps 50 Hz GRUNDFOS DATA BOOKLET ydro MPC Booster systems with 2 to 6 ums 50 z Contents Introduction Benefits 3 Product data Performance range 5 Product range 6 Tye key 7 Oerating conditions 7 Construction Pum 8

More information

GRUNDFOS DATA BOOKLET. Hydro 1000 G - X. Grundfos Hydro 1000 G - X booster sets with 1-4 CR pumps 50 Hz

GRUNDFOS DATA BOOKLET. Hydro 1000 G - X. Grundfos Hydro 1000 G - X booster sets with 1-4 CR pumps 50 Hz GRUNDFOS DATA BOOKLET ydro 0 G - X Grundfos ydro 0 G - X booster sets with 1-4 CR ums z Contents Product data Performance range Page 3 ydro 0 G - X Page 4 Tye key Page 4 Oerating conditions Page 4 Other

More information

GRUNDFOS DATA BOOKLET. Hydro MPC. Booster systems with 2 to 6 pumps 50 Hz

GRUNDFOS DATA BOOKLET. Hydro MPC. Booster systems with 2 to 6 pumps 50 Hz GRUNDFOS DATA BOOKLET ydro MPC Booster systems with 2 to 6 ums 50 z Contents Introduction Benefits 3 Product data Performance range 5 Product range 6 Tye key 7 Oerating conditions 7 Construction Pum 8

More information

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Electrical data Nominal voltage AC 230 V Nominal voltage frequency echnical data sheet NRA Rotary actuator for ball valves Nominal torque Nm Nominal voltage AC V Control Open-close, -point echnical data Electrical data Nominal voltage AC V Nominal voltage frequency 5/6

More information

GRUNDFOS DATA BOOKLET UPM2, UPM GEO, UPM2K. Circulator pumps. 50/60 Hz

GRUNDFOS DATA BOOKLET UPM2, UPM GEO, UPM2K. Circulator pumps. 50/60 Hz GRUNDFOS DATA BOOKLET UPM, UPM GEO, UPMK Circulator ums /6 z UPM, UPM GEO, UPMK Table of contents. General data Introduction Alications Features and benefits ErP, Ecodesign regulation in brief Pumed liquids

More information

Globe Valves. Technical Databook Version 1.2. Belimo Asia Pacific

Globe Valves. Technical Databook Version 1.2. Belimo Asia Pacific Globe Valves Technical Databook Version 1.2 Belimo Asia Pacific Contents Globe Valves Product Overview Max. Close-off Pressure - Globe Valve Series Globe Valve Actuators Product Overview 4 5 General Information

More information

Characterised Control Valves with Actuators

Characterised Control Valves with Actuators Characterised Control Valves with Actuators echnical Databook Version 6.2 Belimo Asia Pacific Product Overview and able of Contents able of Contents 2 Control Valves and Actuators Product Overview 3 Characterised

More information

18D according to ATEX

18D according to ATEX Pneumatic ressure switch -... bar Hydraulic ressure switch 5... 4 bar For EX-alications according to ATEX 00 a: Zone 2 category ATEX 3G (gases) Zone 22 category ATEX 3D (dust) TÜV (technical insection

More information

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz GR24A-5 / -7 GR24A-5 Rotary actuator for rotary valves GR24A-7 Rotary actuator for rotary valves Nominal torque 40Nm Nominal voltage AC/DC 24V Control Open-close echnical data Electrical data Nominal voltage

More information

Product Table of overview contents and table of contents. Table of contents

Product Table of overview contents and table of contents. Table of contents Product able of overview contents and table of contents able of contents Product overview he Belimo characterized control valves (CCV) he Belimo characterized control valves (CCV), notes he sizing of ball

More information

Clamping systems. LinClamp/HLGClamp. LinClamp SA. LinClamp SK. LinClamp A

Clamping systems. LinClamp/HLGClamp. LinClamp SA. LinClamp SK. LinClamp A inlam/lam laming systems inlam S lam inlam SK inlam S inlam inlam/lam dvantages 1 Suitable for almost all sizes and manufacturers of linear guide systems as well as for surfaces (inlam ) 2 omact design,

More information

[ ] Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

[ ] Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet EP..R+KMP Communicative characterised control valve with sensor-operated flow control and emergency control function, ominal voltage CC 2 V Control Modulating or closed cold and warm

More information

WHATEVER THE DISTANCE. LINEA &TOUREA High-Comfort Bus Driver Seats.

WHATEVER THE DISTANCE. LINEA &TOUREA High-Comfort Bus Driver Seats. HOME ON THE ROAD. WHATEVER THE DISTANCE. LINEA &TOUREA High-Comfort Bus Driver Seats. SITTING RETTY WITH A HEALTHY OSTURE. Sitting Comfort with roofen Ergonomics. Otimum seat ergonomics decisively imrove

More information

JFC Series Rack & Pinion Actuators SGS MD 2006/42/EC

JFC Series Rack & Pinion Actuators SGS MD 2006/42/EC JFC Series Rack & Pinion Actuators R SGS MD 006/4/EC CE DESIGN AND CONSTRUCTION DESIGN Jflow Controls rack and inion actuators are designed to oerate in a variety of alications. Jflow Controls realizes

More information

DN [ ] DN [ ] Functional data Media Cold and hot water, water with glycol up to max. 50% vol.

DN [ ] DN [ ] Functional data Media Cold and hot water, water with glycol up to max. 50% vol. Technical data sheet R6..W..-S8 Characterised control valves, -way, with PN 16 flange For closed cold and hot water systems For modulating water-side control of air purification and heating systems Air

More information

Characterized Control Valves Actuators. Technical Databook Ver. 2

Characterized Control Valves Actuators. Technical Databook Ver. 2 Characterized Control Valves Actuators Technical Databook Ver. 2 Product overview and table of contents Table of contents 2 Control valves and actuators Product overview The Trane Ball valves The Trane

More information

P. R2...P. Two. have. become. Range of Pressure-Independent Control Valves. one

P. R2...P. Two. have. become. Range of Pressure-Independent Control Valves. one P. R2...P Two have become Range of Pressure-Independent Control alves one The pressure-independent control valve R2 P sets new standards The challenge Energy savings with maximum convenience and low installation

More information

TRF.. series spring return rotary actuators for CCV

TRF.. series spring return rotary actuators for CCV TF.. series spring return rotary actuators for CCV Spring return rotary actuators: For ball valves DN 5.. Torque: 2 Nm Modulating control TF24-S (C/DC 24 V) Floating (3-point) control TF24-2 (C/DC 24 V)

More information

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings ST2 Ball valves in conjunction with spring return and non-spring return VA-Actuators Developed for HVAC applications

More information

Butterfly Valves. Technical Databook Version 7.2. Belimo Asia Pacific

Butterfly Valves. Technical Databook Version 7.2. Belimo Asia Pacific Butterfly Valves Technical Databook Version 7.2 Belimo Asia Pacific BFV and Actuators Product Range Overview and Applications BU6..Series Motorised Butterfly Valves page 4 BU6..Series Butterfly Valves

More information

Mine Ventilation Solutions. Quiet. Efficient. Durable. a company of

Mine Ventilation Solutions. Quiet. Efficient. Durable. a company of Mine Ventilation Solutions Quiet. Efficient. Durable. a comany of TLT-Turbo - A cororate success story. Innovation for more than 140 years. As a ioneer and innovator in the fan and blower market with a

More information

20, 30, 40, 55 Turbo. Alpha SERIES. Variable speed; maximum power at flywheel at 3000 r/min: kw; bhp

20, 30, 40, 55 Turbo. Alpha SERIES. Variable speed; maximum power at flywheel at 3000 r/min: kw; bhp Alha SERIES ALPHA Marine Engines 20, 30, 40, 55 Turbo Variable seed; maximum ower at flywheel at 3000 r/min: 14.9 41.0 kw; 20-55 bh Durable, economical liquid cooled marine diesel engines Suitable for:

More information

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves - Motorized 6-port Ball Valves Description NovoCon The and NovoCon are 6-port motorized ball valves that performs a diverting function between two water circuits in 4-pipe changeover system. This diverting

More information

Special conveyor chains

Special conveyor chains 56 Secial conveyor chains iwis offers an extensive rogram of secial chains for various industrial alications and requirements. While the late chain is being used wherever smooth and reliable conveying

More information

Combi valves PN 16 with flanged connections

Combi valves PN 16 with flanged connections 4 315 ACVATIX Combi valves PN 16 with flanged connections Pressure Independent Combi Valves VPF43.. With integrated pressure differential controller Valve body made of gray cast iron GJL-250 DN 50, DN

More information

Air Handling Units. Geniox. Accessories

Air Handling Units. Geniox. Accessories Air Handling Units Geniox Accessories The right accessories are important to optimise your Geniox air handling unit to the task at hand. SystemairCAD provides you with a wide selection of accessories.

More information

Type overview. R B2 en-gb subject to changes 1

Type overview.  R B2 en-gb subject to changes 1 Technical data sheet R30..-..-..-B2 Characterised control valve, 6-way, Internal thread Two sequences (cooling/heating) with one 90 rotary actuator Switching or modulating control on the water side of

More information

Overview of types. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems

Overview of types. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems Technical data sheet R3..xx-S.. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems For modulating water-side control of HU and heating systems ir bubble-tight

More information

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing. Non-operating temperature

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing. Non-operating temperature echnical data sheet SR24P-R Robustline rotary actuator for butterfly valves and rotary valves in Retrofit applications orque 18 Nm Nominal voltage AC/DC 24 V Control: Open-close or 3-point Optimum protection

More information

MECHANICAL ENGINEERING

MECHANICAL ENGINEERING Serial : 0 PT_ME_A+B_IC Engine_6098 CLASS TEST Delhi Noida Bhoal Hyderabad Jaiur Lucknow Indore Pune Bhubaneswar Kolkata Patna Web: E-mail: info@madeeasy.in Ph: 0-56 MECHANICAL ENGINEERING I.C. Engine

More information

Overview of types. Technical data

Overview of types. Technical data Technical data sheet 6..S+NVFT24-MFT-E Globe valves, 2-way, with flange PN 16, actuator with emergency control function for closed hot water systems up to 150 C in district heating applications approved

More information

High Performance Solutions. Belimo Pressure Independent Control Valves

High Performance Solutions. Belimo Pressure Independent Control Valves High Performance Solutions 2 Energy Eff icient Valves Providing Comfort in Buildings Belimo pressure independent control valves stabilize variable flow hydronic systems for a lifetime of efficiency and

More information

pressure independent characterized control tm

pressure independent characterized control tm 5 pressure independent characterized control tm valves (PICCV ) PICCV reacts to pressure variations, performing a continual balancing function to maintain system performance at varying loads. Wide range

More information

2-way and 3-way globe valves

2-way and 3-way globe valves 2-way and 3-way globe valves Table of Contents Background Project planning 2 Flow characteristics 2 Principles of flow control 3 ydraulic circuits 4 Design and dimensioning Cavitation diagrams 5 Design

More information

BN SERIES BATTERY NOTCHING. BN Series Battery Notching. For lithium-ion battery production

BN SERIES BATTERY NOTCHING. BN Series Battery Notching. For lithium-ion battery production BN SERIES BATTERY NOTCHING BN Series Battery Notching For lithium-ion battery roduction 2 BN SERIES BATTERY NOTCHING MANZ AG 3 BN SERIES BATTERY NOTCHING MANZ AG GERMAN ENGINEERING INTERNATIONALLY STAGED

More information

TURBOFARMER 50.8 AND 45.11

TURBOFARMER 50.8 AND 45.11 MERLO 1964-2014 AN HISTORIC ITALIAN COMANY MACHINE OF THE YEAR 2014 TURBOFARMER 50.8 AND 45.11 XG Merlo's factories in San Defendente di Cervasca (Cuneo) cover an area of 300,000 m 2 (with 220,000 m 2

More information

Design of Planetary Plug-in Hybrid Powertrain and Its Control Strategy

Design of Planetary Plug-in Hybrid Powertrain and Its Control Strategy Page000544 EVS5 Shenzhen, China, Nov 5-9, 010 Design of Planetary Plug-in Hybrid Powertrain and Its Control Strategy Antoni Szumanowsi 1, Zhiyin Liu 1, Yuhua Chang 1 1 The Faculty of Automotive and Construction

More information

24 Vdc ELECTRONIC CONTROL UNIT FOR SWING GATES USE INSTRUCTIONS - INSTALLATION INSTRUCTIONS

24 Vdc ELECTRONIC CONTROL UNIT FOR SWING GATES USE INSTRUCTIONS - INSTALLATION INSTRUCTIONS 24 Vdc ELECTRONIC CONTROL UNIT FOR SWING GTES USE INSTRUCTIONS INSTLLTION INSTRUCTIONS 1. GENERL CHRCTERISTICS This 24 Vdc control unit for swing gates offers high erformance and a wide range of adjustments:

More information

TURBOFARMER COMPACTS TF TF30.9

TURBOFARMER COMPACTS TF TF30.9 MERLO 1964214 AN HISTORIC ITALIAN COMANY TURBOFARMER COMACTS TF33.7 TF3.9 XG Merlo's factories in San Defendente di Cervasca (Cuneo) cover an area of 3, m 2 (with 22, m 2 inside facilities) 9 1 11 2 7

More information

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB otorised ball zone valves with -contact control -.. BY - series 00 0/ GB replaces 0/ GB unction The motorised zone valves permit automatically shutting off the medium in air conditioning or hydraulic and

More information

A 601 A B C. 1. How it works

A 601 A B C. 1. How it works 601 W4 DXN6P25 Variable flow-control 6-way valve, series DXN6_ For 4-pipes climate ceilings with change-over Pressure independent variable flow-control Integrated flow measurement Power supply U v : 24Volt

More information

MASS FRACTION BURNED ALGORITHM BASED ON THE pv PRODUCT

MASS FRACTION BURNED ALGORITHM BASED ON THE pv PRODUCT Journal of KONES Internal Combustion Engines 2002 No. 3 4 ISSN 1231 4005 MASS FRACTION BURNED ALGORITHM BASED ON THE V PRODUCT Krzysztof Z. Mendera, Andrzej Syra, Michał Smereka Technical University of

More information

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor Technical data sheet GK24G- SuperCap rotary actuator with emergency setting function and extended functionalities in the IP66 protective housing for adjusting air dampers in ventilation and air-conditioning

More information

Figure 1 Figure 2 Figure 3

Figure 1 Figure 2 Figure 3 Installation guide Thermal Energy Meter Suercal 739 Installation The rescritions related in the standard EN1434-6 must be resected when the Suercal 739 is installed. Deending on its articular version and

More information

Investing in. Mattei Compressors. Compressed Air Industry Automotive Transit. Good morning. How is business at Mattei Compressors?

Investing in. Mattei Compressors. Compressed Air Industry Automotive Transit. Good morning. How is business at Mattei Compressors? New Flyer Bus Audit Mattei Rotary Vane O c t o b e r 2 0 0 8 1 0 / 0 8 Comressed Air Industry Automotive Transit Investing in Mattei Comressors Comressed Air Best Practices soke with Jay Hedges (General

More information

Series 32D Electronic Pressure Switch for Hydraulic and High Pressure Applications. Series 18D Hydraulic. Pressure Switch

Series 32D Electronic Pressure Switch for Hydraulic and High Pressure Applications. Series 18D Hydraulic. Pressure Switch Contents Pressure Switch Overview.......................2 Series 18D Pneumatic Pressure Switches...........6 Series 18D Hydraulic Pressure Switches...........10 Series 31D Electronic Pressure Switches

More information

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3 SRFA Rotary actuator with emergency function for ball valves Torque 20Nm Nominal voltage AC 24...240V / DC 24...125V Control: Open/Close SRFA: Deenergised NC Technical data Electrical data Nominal voltage

More information

Pneumatic re-generation system in an electric car

Pneumatic re-generation system in an electric car Pneumatic re-generation system in an electric car Ziming Qi, Vivien iang & David Hawkins Abstract As the clean energy car becomes the hot sot on the market, the electric car has been aid more attention.

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx. 2 m 2 orque 10 m ominal voltage AC/DC

More information

Your Partner for Micro and High Pressure Hydraulics

Your Partner for Micro and High Pressure Hydraulics Your Partner for Micro and High Pressure Hydraulics For any alication where sace is limited and intelligent solutions are in demand, we are your cometent solution artner. From comonents to systems. About

More information

Fan-coil valves Series

Fan-coil valves Series Fan-coil valves Series 11-11 - 411 Main features Complete range in the following versions : -way - DN: 1/, /4, 1 -way - DN: 1/, /4, 1 -way with 4 ports - DN: 1/, /4 - The -way version and the -way versions

More information

D6.. Butterfly valves. For controlled operation.

D6.. Butterfly valves. For controlled operation. D6.. Butterfly valves. For controlled operation. Water is our element. www.belimo.eu Total solutions for medium and large volumetric flows. Butterfly valves from Belimo are available as classical D6..N

More information

3M RANGE - XG. Technologies by Tre Emme Srl, a Merlo Group company. TOOL CARRIERS Multipurpose working tools. Building with confidence.

3M RANGE - XG. Technologies by Tre Emme Srl, a Merlo Group company. TOOL CARRIERS Multipurpose working tools. Building with confidence. Technologies by Tre Emme Srl, a Merlo Grou comany 3M RANGE - XG TOOL CARRIERS Multiurose working tools. Building with confidence. B Series tool carriers when the going gets tough. or all those who need

More information

RK /02.03 HED 2 OA 2X/.. HED 2 OA 2X/..L.. HED 2 OA 2X/..KL.. HED 2 OA 2X/..K.. HED 2 OA 2X/..K6.. HED 2 1/6 RK /02.

RK /02.03 HED 2 OA 2X/.. HED 2 OA 2X/..L.. HED 2 OA 2X/..KL.. HED 2 OA 2X/..K.. HED 2 OA 2X/..K6.. HED 2 1/6 RK /02. RK 0 0/0.0 K 8/ OA X/.. K 8/ OA X/..L.. K 8/ K 8/ K 8/9 OA X/..K.. OA X/..KL.. OA X/..K.. with lug-in connector with lug-in connector with lug-in connector 07 / RK 0 0/0.0 OA X Series 0 to 9 = X (0 to

More information

Zone Valves and Parts (Honeywell)

Zone Valves and Parts (Honeywell) 28/11/14 B49 Zone Valves - Two Way Fan Coil Zone Valves and Parts (Honeywell) Two-way Fan Coil Valve, the VU53 high pressure zone valves are used to control the flow of hot or chilled water in commercial

More information

2-Port and 3-Port Zone Valves PN 16

2-Port and 3-Port Zone Valves PN 16 4 842 2-port valves VVI4615 to VVI4625 3-port valves VXI4615 to VXI4625 2-port valves VVS4615 to VVS4625 3-port valves VXS4615 to VXS4625 2-Port and 3-Port Zone Valves PN 16 VVI46 VXI46 VVS46 VXS46 Hot-pressed

More information

Series 02: DN40 and DN50 Series 01: DN Three-port slipper valves PN6

Series 02: DN40 and DN50 Series 01: DN Three-port slipper valves PN6 4 241 Series 02: DN40 and DN50 Series 01: DN 65...150 Three-port slipper valves PN6 VBF21... Three-port slipper valves, PN6, flanged Grey cast iron EN-GJL-250 DN 40...150 k vs 25...820 m 3 /h Angle of

More information

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch echnical data sheet actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx 4 m 2 orque 20 m ominal voltage AC/DC

More information

ScienceDirect. Highly flexible hot gas generation system for turbocharger testing

ScienceDirect. Highly flexible hot gas generation system for turbocharger testing Available online at www.sciencedirect.com ScienceDirect Energy Procedia 45 ( 2014 ) 1116 1125 68 th Conference of the Italian hermal Machines Engineering Association, AI2013 Highly flexible hot gas generation

More information

Flywheel Energy Storage Systems for Rail

Flywheel Energy Storage Systems for Rail Imerial College London Deartment of Mechanical Engineering Flywheel Energy Storage Systems for ail Matthew ead November 2010 Thesis submitted for the Diloma of the Imerial College (DIC), PhD degree of

More information

VBF21.. Three-port slipper valves PN6. Series 02: DN40 and DN50 Series 01: DN

VBF21.. Three-port slipper valves PN6. Series 02: DN40 and DN50 Series 01: DN 4 24 Series 02: DN40 and DN50 Series 0: DN 65...50 Three-port slipper valves PN6 VBF2.. Three-port slipper valves, PN6, flanged Grey cast iron EN-GJL-250 DN 40...50 k vs 25...820 m 3 /h Angle of rotation

More information

Simple Set COMMERCIAL. Pressure Independent Control Valves 2 Way 1/2-2 02/16/18 COMMERCIAL

Simple Set COMMERCIAL. Pressure Independent Control Valves 2 Way 1/2-2 02/16/18 COMMERCIAL The Bray Simple Set is a threaded pressure independent control (PIC) valve designed for a wide variety of hot water and chilled water control applications. The SS Series combines high rangeability control

More information

MEDIUM DUTY TF TF35.7

MEDIUM DUTY TF TF35.7 MEDIUM DUTY TF.9 TF5.7 XG Merlo's factories in San Defendente di Cervasca (Cuneo) cover an area of 00,000 m 2 (with 220,000 m 2 inside facilities) 9 0 2 7 8 6 4 5. Merlo SA main offices 2. Final assembly

More information

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1.5 nominal torque 0.2 W 4 VA Auxiliary switch

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1.5 nominal torque 0.2 W 4 VA Auxiliary switch echnical data sheet Damper actuator NM4A-S-P Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air control dampers up

More information

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet LHA-MF.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control

More information

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends Application Water-side control of heating and cooling systems for AHUs and water coils. Equal Percentage/

More information

STUDIES ON DYNAMIC VISCOSITY CHANGES OF THE ENGINE S LUBRICATION OIL DEPENDING ON THE PRESSURE

STUDIES ON DYNAMIC VISCOSITY CHANGES OF THE ENGINE S LUBRICATION OIL DEPENDING ON THE PRESSURE Journal of KONES Powertrain and Transort, Vol. 20, No. 4 2013 STUDIES ON DYNAMIC VISCOSITY CHANGES OF THE ENGINE S LUBRICATION OIL DEPENDING ON THE PRESSURE Grzegorz Sikora Gdynia Maritime University Deartment

More information

2006 Product Range Overview. Belimo Project: One Bellevue Center, Seattle, Washington

2006 Product Range Overview. Belimo Project: One Bellevue Center, Seattle, Washington 2006 Product Range Overview Belimo Project: One Bellevue Center, Seattle, Washington Actuator Product Range Spring Return TF 18 in-lb [2 Nm] Approx. 4.5 sq. ft. LF 35 in-lb [4 Nm] Approx. 8 sq. ft. NF

More information

Progress made simple!

Progress made simple! Progress made simle! ELECTRONIC Piette TRUSTED RESULTS EASY & INTUITIVE USE ADVANCED ERGONOMICS ESSENTIAL ETTING FEATURES 4 essential ietting modes: FORWARD ietting, retive, mix and reverse. TRUSTED RESULTS

More information

3-port seat valves PN16 with flanged connection

3-port seat valves PN16 with flanged connection 4 440 Acvatix 3-port seat valves PN16 with flanged connection VXF41.. Grey cast iron EN-GJL-250 valve body DN 15...150 k vs 1,9...300 m 3 /h Can be equipped with SAX..-electromotoric or SKD..-, SK..- and

More information

Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented Effective December 2007

Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented Effective December 2007 Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented Effective December 2007 Belimo Project: 1100 Peachtree, Atlanta, Georgia Control Valve Product Range Electronic

More information

Modulating Control Valve PN 16 with Magnetic Actuator

Modulating Control Valve PN 16 with Magnetic Actuator 4 74 Modulating Control Valve PN 6 with Magnetic Actuator for brine circuits, hot water, steam or media containing mineral oils (MK FX NP) MK FX N MK FX NP Fast positioning time (< s) High-resolution stroke

More information

Water Product Catalogue

Water Product Catalogue www.belimo.com Water Product Catalogue Asia Pacific 2016 In addition to motorised butterfly valves and globe valves, Belimo supplies unique, air bubble-tight characterised control valves for the precise

More information

2-port seat valves PN25 with flanged connection

2-port seat valves PN25 with flanged connection 4 373 Acvatix 2-port seat valves PN25 with flanged connection VVF52.. Nodular cast iron EN-GJS-400-8-LT valve body DN 5...40 k vs 0.6...25 m 3 /h Can be equipped with SAX..-electromotoric or SKD..- or

More information

Advantages of using a Switched Reluctance Generator (SRG) for wind energy applications

Advantages of using a Switched Reluctance Generator (SRG) for wind energy applications Advantages of using a Switched Reluctance Generator (SRG) for wind energy alications Eleonora Darie, Costin Ceisca, Emanuel Darie Abstract Wind energy found to be one of the most useful solutions to hel

More information

VMP43... Two-port and three-port seat valves PN16. Siemens Building Technologies Landis & Staefa Division

VMP43... Two-port and three-port seat valves PN16. Siemens Building Technologies Landis & Staefa Division 4 84 Two-port valves (2-ports) VPM43...(2) Three-port valves (3-ports) VMP43... Three-port valves with T bypass (4-ports) VMP43...(4) Two-port and three-port seat valves PN6 VMP43... Two-port valves, type

More information

Powerful Movements The butterfly valves and actuators from Belimo.

Powerful Movements The butterfly valves and actuators from Belimo. Powerful Movements The butterfly valves and actuators from Belimo. Kuhn Champignon AG, Full-Reuenthal (CH) SwissCo AG, Sisseln (CH) Refrigerating plant at Alois Müller GmbH, Memmingen (DE) Efficiency and

More information

Modulating control valve PN16 with magnetic actuator

Modulating control valve PN16 with magnetic actuator Modulating control valve PN with magnetic actuator for hot and chilled water with positioning control and position feedback MP...GY MP...FY MP...GY MP...FY Mixing or straight-through valves with magnetic

More information

2-port ball valves with flanged connection, PN25

2-port ball valves with flanged connection, PN25 s 4 120 ACVATIX 2-port ball valves with flanged connection, PN25 VAF51.. Gray cast iron EN-GJL-250 (HT250) valve body DN 65...150 k vs 63...360 m 3 /h Angle of rotation 90 Flange connection to ISO 7005-2

More information

9SX SX PX PX SX EBM 180V 9PX EBM 180V. Installation and user manual ENGLISH. Copyright 2012 EATON All rights reserved.

9SX SX PX PX SX EBM 180V 9PX EBM 180V. Installation and user manual ENGLISH. Copyright 2012 EATON All rights reserved. ENGLISH 9SX 5000 9SX 6000 9PX 5000 9PX 6000 9SX EBM 180V 9PX EBM 180V Installation and user manual Coyright 2012 EATON All rights reserved. Service and suort: Call your local service reresentative Page

More information

Features Globe Valve 2-Way & 3-Way Assembly Features:

Features Globe Valve 2-Way & 3-Way Assembly Features: Rev: 10/22/13 Features Globe Valve 2-Way & 3-Way Assembly Features: DG Series Automated Applications for Building Automation, Temperature Controls, HVAC Two-Way and Three-Way Assemblies Chilled Water Hot

More information

2-position electric actuators with Ball valves VBZ ½...11/4

2-position electric actuators with Ball valves VBZ ½...11/4 4 831.2 & VBZ ½...11/4 2-position electric actuators with Ball valves VBZ ½ 11/4 90 angle - Unidirectional rotation VBZ ½ 11/4 Electric rotary actuators for two-port ball valves Operating voltage AC 230

More information

2-port and 3-port valves with T-bypass PN 16

2-port and 3-port valves with T-bypass PN 16 4 854 2-port valves 3-port valve with T-bypass CVTIX 2-port and 3-port valves with T-bypass PN 16 VVP45..S VMP45..S ronze CC499K valve body DN 10 and DN 15 k vs 0.63 2.5 m 3 /h Externally threaded connections

More information

2-Port Seat Valves with Flange, PN 25

2-Port Seat Valves with Flange, PN 25 4 7 2-Port Seat Valves with Flange, PN 25 VVF52... Nodular cast iron EN-GJS-400-8-LT valve body DN 5...40 k vs 0.6...25 m /h Can be equipped with SQX- electromotoric or SKD...- or SKB...- electrohydraulic

More information

Modulating control valve PN16 with magnetic actuator

Modulating control valve PN16 with magnetic actuator Modulating control valve PN with magnetic actuator for hot and chilled water with positioning control and position feedback MP80FY MP00FY Mixing or straight-through valves DN80 and DN00 with magnetic actuator

More information

SDE030 SDE060. Directional control valves with direct acting solenoid

SDE030 SDE060. Directional control valves with direct acting solenoid SDE SDE6 Directional control valves with direct acting solenoid SDE-SDE6 Features Simle, comact and heavy duty designed sectional valve from to sections. Different tye of inlet covers. Different tyes of

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet SF24G-S- Modulating spring return actuator with emergency function in the IP66 protective protecti e housing for adjusting air dampers in industrial plants and in technical building

More information

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange Data sheet Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange Description VL 2 VL 3 VL 2 and VL 3 valves provide a quality, cost effective solution for most water and chilled applications.

More information

7750 Series Installation Instructions

7750 Series Installation Instructions FLOW MEER LIMIED WARRANY Meters are warranted against defects in materials and workmanshi to the original user for a eriod of thirteen () months from the date of factory shiment, rovided the meter is installed,

More information

MVF461H Series Modulating Control Valves with Magnetic Actuators, Positioning Control and Position Feedback for Hot Water and Steam

MVF461H Series Modulating Control Valves with Magnetic Actuators, Positioning Control and Position Feedback for Hot Water and Steam Document No. 125-4361 VF461H Series odulating Control Valves with agnetic Actuators, Positioning Control and Position Feedback for Hot Water and Steam Description Control valves with magnetic actuators,

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet FA actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx. 2 m 2 orque 10 m ominal voltage

More information

2-port and 3-port ball valves PN 40

2-port and 3-port ball valves PN 40 s 4 211 VAI61.. VBI61.. ACVATIX TM 2-port and 3-port ball valves PN 40 with internally threaded connections VAI61.. VBI61.. Brass UNS C35330 (DZR) ball valve body DN 15...50 k vs 1...63 m 3 /h Internally

More information

machine design, Vol.3(2011) No.3, ISSN pp

machine design, Vol.3(2011) No.3, ISSN pp machine design, Vol.3(2011) No.3, ISSN 1821-1259. 189-194 Preliminary note ESTIMATION OF THE DRIVING FORCE AND DRAG FORCE OF THE POWERTRAIN SYSTEM WITH THE USE OF A UNIVERSAL PORTABLE DEVICE IN ROAD TEST

More information