Product Manual & Installation Guide Vertical Rack Mount 5.0 to 8.6 kw
|
|
- Steven Morgan
- 6 years ago
- Views:
Transcription
1 Product Manual & Installation Guide Vertical Rack Mount 5.0 to 8.6 kw 30A 208V 20A 208V 3 Phase 30A 208V 3 Phase Important Information Specifications Installation & Operation Outline & Wiring Drawings Compliance Warranty PDM0001 Rev. 01 Wright Line, LLC All rights reserved
2 Important Information Important Notes: The electrical receptacle used to provide power to this unit must be installed near the equipment and must be easily accessible. SYSTEMS SHOULD ONLY BE CONFIGURED BY A PERSON KNOWLEDGEABLE OF NATIONAL AND LOCAL ELECTRICAL CODES. The minimum wire size that shall be used for an earth bonding (ground) connection to the power strip is 12awg. Grounded (white) conductors within this equipment are not protected by an integral circuit breaker. In order to allow earth faults within the unit to be cleared by the branch circuit devices. The installer must ensure that the neutral (white) conductor of the supply installation is grounded. IT IS ESSENTIAL THAT THIS EQUIPMENT IS CONNECTED TO AN ELECTRICAL SUPPLY THAT HAS A PROTECTIVE GROUND CONDUCTOR. WARNING: ATTENTION: CAUTION: ATTENTION: TO ISOLATE THIS EQUIPMENT DISCONNECT POWER SUPPLY PLUG. AFIN D'ISOLER TOTALEMENT CET APPAREIL DEBRANCHER FICHE D'ALIMENTATION. USE ONLY IN DRY LOCATIONS UTILISER UNIQUEMENT DANS DES EMPLACEMENTS SECS THE INFORMATION GIVEN IN THIS MANUAL IS SUBJECT TO CHANGE WITHOUT NOTICE. ANY GUIDANCE NOTES GIVEN WITH REGARDS TO COMPLYING WITH SPECIFIC STANDARDS ARE PROVIDED AS AN AID TO THE INSTALLER AND ARE INTERPRETATIONS OF THOSE STANDARDS ONLY. THESE INSTRUCTIONS ARE PRIMARILY INTENDED TO PROVIDE DETAILS ON THE SAFE USE AND INSTALLATION OF THIS PRODUCT. This product has been designed to conform to the latest safety requirements. In addition to compliance with standards for general use, it has been configured for use in rack mounting environments. Inspection: Inspect the product prior to installation. If product is damaged, please contact Wright Line LLC. by Wright Line LLC,
3 Specifications General Specification: Maximum Input voltage Input frequency Input cord length 250V 50/60Hz 10 ft. Physical unit width x depth 1.75 x 1.90 For unit length, see table below. 30A product has a circuit breaker section with a 3.20 depth. See outline drawing for detailed information. Ambient temperature 40 C Elevated Operating Ambient Temp: If product is installed in a closed environment, ensure that the internal temperature within the enclosed space does not exceed the temperature stated above. Specification by Model: Model Number Physical Input Output Receptacles Basic Meter (RS232) Unit Amps** Volts Length* Nom / Max Plug kw Rating Receptacle Type Qty. PDBA PDME in. C13, C19 24, 4 208V 30A / 24A L PDBA PDME in. C13 30 PDBA PDME in. C13 45 PDBA PDME in. C13, C19 30, 6 208V 3PH 20A / 16A L21-20P 5.8 PDBA PDME in. C13, 5-20R 30, 6 PDBA PDME in. C19, 5-20R 12, 6 PDBA PDME in. 5-20R 30 PDBA PDME in. 5-20R, L6-20R 18, 6 PDBA PDME in. C13, C19 30, 6 PDBA PDME in. C13, C19 24, 9 208V 3PH 30A / 24A L21-30P 8.6 PDBA PDME in. C13 45 PDBA PDME in. C13, 5-20R 30, 6 PDBA PDME in. C13, C19 12, 15 PDBA PDME in. C19, 5-20R 12, 6 * Unit length excluding input cord and end mounting brackets. See outline drawing for detailed information. ** Maximum rated amperage is 80% of the nominal rated branch circuit rating as defined by the National Electrical Code (NEC). by Wright Line LLC,
4 Installation & Operation Mounting: This product is intended for integration into an information technology equipment rack. Product may be mounted onto a set of keyhole slots (see diagram) located In the Vantage S2 TM and Paramount TM equipment racks. Tool free buttons are positioned on in. centers to correspond with keyhole slots in the equipment rack. Vantage S2 TM Alternatively, product may be mounted to a flat surface by use of the end mounting brackets. End mounting bracket are included with this product but are not attached to the unit. Remove the tool free buttons if end mounting brackets are to be used. (see diagrams) Tool Free Button Paramount TM End Mounting Bracket Electrical Connection: When installing this product, it is essential that the distribution circuit supply is protected by a branch circuit protection device that is compatible with the specifications of this product. (See the specification section of this manual.). 12 AWG is the minimum wire size that shall be used for an earth bonding (ground) connection for this product. The output circuits of this product are connected to different phases. The installer must ensure that the equipment powered from this system is compatible with this arrangement. The installation receptacle used for providing power to this product must be installed near the equipment and must be easily accessible. Ammeter Operation: This diagram shows the ammeter display and the RJ 45 connection for remote access. Remote access uses the RS232 communication protocol. The ammeter display will function properly without using the remote access feature. RS232 OUTPUT Ammeter type: True RMS measurement, three (3) digit The ammeter measures load current in this product using Current Transformers (CTs). Load current is measured without directly interfering with the integrity of the power supply circuit. by Wright Line LLC,
5 Installation & Operation Ammeter Operation (cont.): Ammeter display legends and function CIRCUIT Displays the circuit being monitored. Scroll UP / DOWN keys manually select the circuit being monitored. AMPS Displays true RMS current of the measured circuit. Accuracy is +/- 5%. A M Places ammeter display in AUTO mode. The ammeter display automatically scrolls through the applicable circuits. AUTO mode is the default mode. Select to place ammeter in MANUAL mode. In this mode the scroll UP or DOWN buttons may be used as described above. Ammeter channel assignment Product Type 30A 208V 20A 3 Phase & 30A 3 Phase Circuit Ammeter positions 1 Input current 1 3 Phase output current 4 6 Phase input current Ammeter Operation Three Phase 208V: Ammeter positions 1, 2 & 3 read the current in each output circuit. Ammeter positions 4, 5 & 6 read the current in each input phase. The maximum equipment load that can be placed on an output circuit is 13.9A for 30A 3 Phase and 9.2A for 20A 3Phase product. This will ensure that the input load current will not exceed 24A and 16A respectively. Use the pushbutton switch to select the phase being displayed. (See meter diagram) With a three phase circuit, a load of 13.9A on each of the three output circuits will result in an input current of 24A or 9.2A per output circuit for an input current of 16A. Connect equipment to the receptacles of this product such that load is distributed evenly between the three output circuits. As more equipment is plugged in, monitor the load current level of each input phase using the ammeter to avoid exceeding the input current limits. Ammeter Operation Single Phase 208V: Ammeter position 1 is the only available position for a product with single phase input. The total amperage should not exceed 24A to be in compliance with NEC requirements. Ammeter Remote Access: Product is supplied with a RJ45 to 9 pin DIN cable. The ammeter transmits the load current values using a simple protocol when communication is enabled. Commands cannot be sent to the ammeter. Connection to a console port switch which supports VT100 code is possible. The ammeter when connected will continually transmit the load current at 6.4 second intervals for an 8 CT system (0.8 seconds per CT) to the terminal emulator until disconnected. by Wright Line LLC,
6 Outline & Wiring Drawings 30A 208V Outline Drawing: Metered product shown with C13 and C19 receptacle types. Additional receptacle configurations have the same outline drawing. 30A 208V Wiring Drawing: Metered product shown with multiple receptacle options. 20A 208V 3 Phase Outline Drawing: Metered product shown with C13 and C19 receptacle types. Additional receptacle configurations have the same outline drawing. by Wright Line LLC,
7 Outline & Wiring Drawings 20A 208V 3 Phase Wiring Drawing: Metered product shown with multiple receptacle options 30A 208V 3 Phase Outline Drawing: Metered product shown with C13 and C19 receptacle types. Additional receptacle configurations will have the same outline drawing. 30A 208V 3 Phase Wiring Drawing: Metered product shown with multiple receptacle options by Wright Line LLC,
8 Compliance Certification Approvals: All products are certified to the following test standards; UL CAN/CSA C22.2 No FCC [Part 15 Class A] Operational Factory Testing: 100% of products are tested at the factory prior to shipping. These tests include; Earth Continuity Conductor Continuity and Polarity Insulation Resistance Flash Test Warranty Wright Line LLC warrants to the original purchaser that its products are free from defects in material and workmanship for the warranty period of 3 years. This warranty does not cover any damage to the customer s equipment that is caused by an AC power disturbance or any other causes unrelated to the quality and/or functionality of the product. Power Product Selector Quickly access Wright Line s power product information based on application, input power and/or receptacle type. Go to or go to by Wright Line LLC,
miconverter 18-Module Rack-Mount Power Chassis User Manual 38 Tesla, Irvine, CA USA Phone: (949) ; Fax: (949) Page 12
miconverter 18-Module Rack-Mount Power Chassis User Manual Page 12 38 Tesla, Irvine, CA 92618 USA Phone: (949) 250-6510; Fax: (949) 250-6514 General and Copyright Notice This publication is protected by
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationPowerLogic High Density Metering System 4-Meter Enclosure Installation Guide
PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More information1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8
Contents : 1. INTRODUCTION...1 2. IMPORTANT SAFETY INSTRUCTIONS...2 3. SYSTEM DESCRIPTION...4 3.1 Front Panel...4 4. CONNECTION AND OPERATION...6 5. TROUBLESHOOTING...8 6. MAINTENANCE...9 6.1 Operation...9
More informationINSP-3 Wiring Inspection Tester
INSP-3 Wiring Inspection Tester Users Manual For detailed specifications and ordering info go to www.testequipmentdepot.com INSP-3 Wiring Inspection Tester Users Manual English December 2009, Rev.1 2009
More informationWF-5110R True Sine Wave Inverter
Operator s Manual WF-5110R True Sine Wave Inverter WF-9900 Series WF-5110R ( The Inverter model number is located on the label on top of the enclosure) Distributed in the U.S.A. and Canada by ARTERRA DISTRIBUTION
More informationPDI PowerWave 2 Bus System
1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening, low voltage, vertical or horizontal power busway distribution system. System
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More informationQuick Start Guide TS 910
Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible
More informationpoollux Power plx-pw60 & plx-pw100
poollux Power plx-pw60 & plx-pw100 ETL LISTED Conforms to UL STD 379; Certifi.ed.to.CSA.STD.C22.2.#218.1 5005508 Installation Instructions Read all instructions before attempting to perform installation
More informationDIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual
DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided
More informationSTOREDGE TM. SolarEdge Single Phase StorEdge TM Solutions for North America SolarEdge StorEdge Solutions Benefits:
SolarEdge Single Phase StorEdge TM Solutions for North America 12-25 STOREDGE TM SolarEdge StorEdge Solutions Benefits: More Energy - DC-coupled architecture stores PV power directly to the battery without
More informationPUMP PLUS 2000 PLC MODEL #: PP AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL
INSTRUCTION MANUAL PUMP PLUS 2000 PLC AUTOMATIC DUAL OUTPUT BATTERY CHARGER Supplied with Dual Bar Graph Display MODEL #: 091-237-12-PP INPUT: 120 Volt, 60 Hz, 3.5 Amps OUTPUT BATTERY 1 and 2: 15 or 18
More informationMODEL 422 Submersible Pump Controller
MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and
More informationINSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.
INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL INS120P TASCO, INC. THIS TESTER IS DESIGNED FOR USE ONLY BY QUALIFIED ELECTRICIANS. IMPORTANT SAFETY WARNINGS mwarning Read and understand this material
More informationSpecial Specification 6058 Battery Back-Up System for Signal Cabinets
Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power
More informationProduct Overview. Product Identification. Amps One CT Two CTs Three CTs
AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationRT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input Vac Output Vac User Guide
RT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input 208-240 Vac Output 208-120 Vac User Guide UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY
More informationDC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual
DC AC POWER INVERTER LIV 10 / LIV 20 / LIV 30 User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the Power Inverter. This
More informationTPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family
TPM Fuse Panel Installation Guide Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family Table of Contents Section 1- General Information... 3 1.1 - Product Description...
More informationAUTO CHARGE 12 DV AUTOMATIC BATTERY CHARGER
File: 091-165-12-DV_revD.PDF Rev: D, Date: 02-25-16 INSTRUCTION MANUAL AUTO CHARGE 12 DV AUTOMATIC BATTERY CHARGER MODEL #091-165-12-DV INPUT: 115 or 230VAC, 50/60Hz OUTPUT: 13.2VDC (nom.), 12 Amperes
More informationSmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9
SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 MODEL NUMBER: AL-84111 Specifications OUTPUT Output Volt Amp Capacity (VA) 2200 Output kva Capacity
More information3 year warranty. (1) Treo Micro fiberglass, gunite fitting, 3/4 PVC. FLED-TM-W-PK10 (10) Treo Micros (WHITE) 80 NEW! Treo Micro fitting adapter
pool lighting The Treo Micro LED light is 12VAC, 2 Watt LED underwater light designed for accent Available in lengths of 30, 50, 80', 150 50,000 hour lamp life No Earth bonding required White or color
More informationOTEC Transfer switch open transition
Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator
More informationAUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL
INSTRUCTION MANUAL AUTO CHARGE 4000 LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER Unit supplied with this display MODEL #: 091-89-12 INPUT: 120 Volt, 50/60 Hz, 5 Amps OUTPUT: 45 Amps File:
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationSmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option
SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation
More informationFLO Home TM G5 Model. Installation guide
FLO Home TM G5 Model Installation guide Table of Contents Safety Instructions 3 Planning your Installation 4 Box Contents 5 Installing the Station 6 Setting the Current Limit 9 Light Indicator 11 Compliance
More informationDocument: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger
Document: PRODSPEC-140 Revision: G DCN No. 106512 Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger 1. GENERAL DESCRIPTION 1.1 General Description Fully regulated, constant voltage,
More informationECET Distribution System Protection. Overcurrent Protection
ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.
More informationTEMPERATURE RISE TESTS
CP No.: CP0511 Rev. 01 Page: 1 of 6 CERTIFIED TEST REPORT TEMPERATURE RISE TESTS Type CMU Power Fuses REV. 01 DATE: August 12, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems, Inc. CP No.:
More informationBUSWAY Low Voltage (Pow-R-Flex)
BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and
More informationPD404-AN V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V. Serial Number
0-10V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V 4 circuit Analog 1-10V 4 x 4 A. Dimmer pack Serial Number Dimmers Indicators Digital Lighting Systems,Inc Info@digitallighting.com
More informationInstalling Power Components
This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco
More informationQuick Start Guide TS 910 & TS 920
Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More informationTransfer switch OTEC open or delayed transition
Transfer switch OTEC open or delayed transition 40-1000 Amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets.
More informationGenerator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit
Instruction Sheet 10 2004 Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit 541 0810 GENERAL INFORMATION This kit contains one Control Communications Module (CCM-G) with
More information3 Uninterruptible Power Systems
3 Uninterruptible Power Systems S4K2U and S4K2U-5 Industrial On-Line UPS The true on-line (double conversion) protection offered by the S4K2U Industrial UPS series eliminates a wider range of potential
More informationTransient Fault Location for Branch Circuit Breakers TFT Turquoise Circle Newbury Park, CA Toll Free:
TFT100 2450 Turquoise Circle Newbury Park, CA 91320 Toll Free: 800-749-5783 User Manual Introduction Fault Trapper is a new class of tester intended to locate the distance to a circuit anomaly that is
More informationCIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT
GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT INSTALLATION AND WIRING INSTRUCTIONS MANUAL 8030 MANUAL PART NUMBER JANUARY 2011. 4304 MATTOX RD. KANSAS CITY, MO 64150 TABLE OF CONTENTS
More informationLPC 40 MODEL #: LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL
INSTRUCTION MANUAL LPC 40 LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-200-12 INPUT: 120 Volt, 50/60 Hz, 5 Amps OUTPUT: 40
More informationAUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:
INSTRUCTION MANUAL AUTO CHARGE DUAL AUTOMATIC DUAL OUTPUT BATTERY CHARGER MODEL #: 091-145-12 INPUT: 120 Volt, 50/60 Hz, 3.5 Amps OUTPUT BAT 1: 10 Amps OUTPUT BAT 2: 10 Amps File: IM_091-145-12_revb.indd
More informationWF-5110R True Sine Wave Inverter
Operator s Manual WF-5110R True Sine Wave Inverter WF-9900 Series WF-5110R ( The Inverter model number is located on the label on top of the enclosure) Distributed in the U.S.A. and Canada by ARTERRA DISTRIBUTION
More informationTPM/GMT Panel Installation Guide
TPM/GMT Panel Installation Guide Document INS-837xxxxxxx This manual covers the following part numbers- Trimm 837xxxxxxx Family Table of Contents Table of Contents... 2 Section 1- General Information...
More informationFuse holders and fuses
Modular size for 10x38, 14x51 and 22x58mm fuses Finger safe - IEC IP20 degree of protection against accidental contact with live parts and with sealable cover for operators safety Version with status indicator
More informationDKG-114 MANUAL AND REMOTE START UNIT
DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional
More informationACC Series Power Conditioner OPERATION & INSTALLATION MANUAL
ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide
More informationAurora Single Phase Emergency Lighting Inverters
Aurora Single Phase Emergency Lighting Inverters True Sine Wave On-Line Single Phase Emergency Lighting Inverters AURORA Series Emergency Lighting AC Inverters are among the most reliable systems available
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationAUTO CHARGE D PUMP PLUS
INSTRUCTION MANUAL AUTO CHARGE D PUMP PLUS AUTOMATIC DUAL OUTPUT BATTERY CHARGER Designed Specifically for Vehicles with DDEC ENGINES MODEL #: 091-9-DPP INPUT: 120 Volt, 60 Hz, 8 Amps OUTPUT VEHICLE BATTERY:
More informationSURFACE TRACK (120/250V) SPECIFICATIONS
SURFACE TRACK (120/250V) SPECIFICATIONS GENERAL Lighting Track shall allow fixtures to be located anywhere along the track length. Fixtures shall be easily focused, switched, dimmed, accessorized and removed
More informationDemand Switch NEFA20 Plus. Installation Guide. Please read this entire guide before beginning the installation!
Demand Switch NEFA20 Plus Installation Guide Please read this entire guide before beginning the installation! Supplied Parts Protective Covers DIN Mounting Rail NEFA20 Plus Mounting Rail Spacer Warning
More informationTotal Front Access Wall Mount Fuse Panel Installation Guide. Document INS This manual covers the following part numbers
Total Front Access Wall Mount Fuse Panel Installation Guide Document INS-7473121031 This manual covers the following part numbers- 7473121031 Table of Contents Section 1- General Information... 3 1.1 -
More information50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual
Operating & Service Instructions Sola Minicomputer Regulators UL White Card Listed Power Supply Classification CSA Certified Transformer Classification General Description and Specifications The Sola Micro/Minicomputer
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationGo Power! Manual. GP-SW1500 Inverter. Table of Contents. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4
Table of Contents 1. INTRODUCTION... 3 Go Power! Manual GP-SW1500 Inverter 2. SPECIFICATIONS... 3 3. NAME AND MAIN FUNCTION... 3 4. INSTALLATION... 5 5. OPERATION... 7 6. OPERATING LIMITS... 9 7. TROUBLESHOOTING...
More informationCBC-802 Plug-In Clutch/Brake Control with Solid State Switching
DIST. AUTORIZADO Plug-In Clutch/Brake Control with Solid State Switching P-29-5 19-0409 Service & Installation Instructions An Altra Industrial Motion Company DIST. AUTORIZADO Brake (Red) and clutch (Green)
More informationGMT Fuse Panel Installation Guide
GMT Fuse Panel Installation Guide Document INS-707XXXXXXX This manual covers the following part numbers- Trimm 707XXXXXXX Family Table of Contents Section 1- General Information... 3 1.1 - Product Description...
More informationTHE DLS SERIES BATTERY CHARGING POWER CONVERSION
THE DLS SERIES IOTA s DLS Series Battery Chargers and Power Converters provide reliable AC/DC power conversion for a variety of application needs. With a record of proven performance throughout several
More informationPowerware Vdc Extended Battery Cabinet User s Guide.
Powerware 9125 48 Vdc Extended Battery Cabinet User s Guide www.powerware.com FCC Part 15 Class A EMC Statements NOTE This equipment has been tested and found to comply with the limits for a Class A digital
More informationCBC-802 Plug-In Clutch/Brake Control with Solid State Switching
CBC-02 Plug-In Clutch/Brake Control with Solid State Switching P-2104-WE 19-054 Service & Installation Instructions An Altra Industrial Motion Company Brake (Red) and clutch (Green) indicator lights When
More informationThree-Phase Soft Starters
Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (+61) 2 4229
More informationModels beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.
Models beginning with MO, MK, 7B, 6S, 6F or 5B The Mini Meter Product Description Technical Specifications Installation Instructions February 28 th, 2013 1. Product Description...2 1.1 General Description...2
More informationPUMP PLUS 1000 PLC MODEL #: PP AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL
INSTRUCTION MANUAL PUMP PLUS 1000 PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-215-12-PP INPUT: 120 Volt, 60 Hz, 3.5 Amps OUTPUT BATTERY 1 and 2: 15
More information2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00
DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations
More information8300 Series Installation Guidelines
1-800-443-4859 8300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER
More informationSmartBoost 50 INSTALLATION INSTRUCTIONS & OWNER S MANUAL LT93 SMTBST50 1. Issue 1 Print 2 AUTOMATIC SHORELINE TRANSFORMER
SmartBoost 50 AUTOMATIC SHORELINE TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL 1 Contents INTRODUCING... THE SmartBoost 50............................................................ 3 Manual
More informationWestell FUSE PANEL. Technical Practice N Position Type VDC Floating
530-101760 REV C 0808-03C December 7, 2012 Westell FUSE PANEL Technical Practice 180108-N-0808 8 Position Type 70 130 VDC Floating FEATURES Single floating input distributing power via Type-70 fuses each
More informationGo Power! Manual. GP-1750HD Inverter GP-2500 Inverter
Go Power! Manual GP-1750HD Inverter GP-2500 Inverter Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: 866-247-6527 Fax: 866-607-6527 Email: info@gpelectric.com Table of Contents 1. INTRODUCTION...
More information2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationInstallation and Construction Notes for EVSE4
Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process
More informationAIS 5000 UPS kva 480 V. Installation Manual
AIS 5000 UPS 10-100 kva 480 V Installation Manual IMPORTANT! THIS DOCUMENT CONTAINS IMPORTANT SAFETY INSTRUCTIONS - PLEASE SAVE THESE INSTRUCTIONS! Contents Safety...1 IMPORTANT SAFETY INSTRUCTIONS - SAVE
More informationUser s Guide Includes Mounting, Installation, and Product Registration
User s Guide Includes Mounting, Installation, and Product Registration 250 T M About OutBack Power Systems OutBack Power Systems is a leader in advanced energy conversion technology. Our products include
More informationUser Manual Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...
More informationTOPAZ 24 DIMMER RACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)
TOPAZ 24 DIMMER RACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29132-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the
More informationPD-Series Ground Fault Circuit Protection
PD-Series Ground Fault Circuit Protection SmartGuard is an equipment ground fault protection device that functions as a standard high-quality Carling hydraulic/ magnetic circuit breaker, offering customized
More informationRental Industry Safety Tester Safe Check 5s
Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More informationches UL File No. E101598
Instrument Transformers, Inc. Series Series 95 95 Swit Switches ches UL File No. E101598 INSTRUMENT AND CONTRC ONTROL OL s Instrument and Control Switch is a heavy-duty rotary switch that satisfies the
More informationDIN Rail UPS Model: DIN-UPS Installation/Operation Manual
DIN Rail UPS Model: DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided 4 Optional Equipment 4 2) Safety Information
More informationAUTO CHARGE 4000 MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:
INSTRUCTION MANUAL AUTO CHARGE 4000 AUTOMATIC DUAL OUTPUT BATTERY CHARGER MODEL #: 091-89-12 INPUT: 120 Volt, 50/60 Hz, 8 Amps OUTPUT BATTERY CHARGER: 40 Amps OUTPUT BATTERY SAVER: 5 Amps File: IM_091-89-12_reve.indd
More informationADI-125/750 ADI-125/1500 ADI-125/2500
Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121094B OWNERS
More informationPUMP PLUS 1200 MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL
INSTRUCTION MANUAL UM LUS 1200 AUTOMATIC SINGLE OUTUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-193-12 INUT: 120 Volt, 60 Hz, 10 Amps OUTUT: 40 Amps File: IM_091-193-12_revH.indd
More information6170 Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free
IF Instruction Manual Model 2000-01 Power Supply April 2012, Rev. D 2000 SUPPLY CAUTION - RISK OF ELECTRICAL SHOCK - DO NOT OPEN!!! -15 GND +15 Data, drawings, and other material contained herein are proprietary
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements
More informationUninterruptible Power Systems
S4K4U 6 kva and S4K6U 10 kva Industrial On-Line UPS The S4K4U6000 and the S4K6U10000 Industrial UPS Series are the first true On-Line industrial UPS that provide flexible output voltage, an integrated
More informationEaton Corp. - Marina Power and Lighting, Inc. General Specifications for Hatteras Light Pedestals
Hatteras Light Power Pedestal Dimensions Height: 31.00" (787.40 mm) Width: (190.50 mm) Depth: (190.50 mm) Hatteras Light Base Diagram Approximate Weight: 14 lbs. (6.4 kg) 1.73" UL FILE # E133781 Ø0.41
More informationSmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option
SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT20K Highlights On-line double-conversion topology, VFI operation
More informationBack-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software
Back-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software APC's Back-UPS ES series is now "greener" than ever. The ES 350 utilizes an ultra-efficient design that consumes less power
More informationINSTRUCTION MANUAL MODEL # NOTE : This charger is designed for vehicles with dual batteries and negative ground.
INSTRUCTION MANUAL FILE: 091-9-2000.P65 DATE: 4-23-2000 REV. A AUTO CHARGE 2000 PUMP-PLUS AIR COMPRESSOR / BATTERY CHARGER MODEL #091-9-2000 NOTE : This charger is designed for vehicles with dual batteries
More informationAquaPure Ei TM Series Replacement Kits
AquaPure Ei TM Series Replacement Kits for Models APURE35/35C WARNING FOR YOUR SAFETY - This product must be installed and serviced by a contractor who is licensed and qualified in pool equipment by the
More informationMBS AG. CTB Plug-in current transformer MBS AG. Dimensions: General technical specifications:
CTB 31.35 Plug-in current transformer Dimensions: Primary conductor 1: 30x10 mm Primary conductor 2: 25x12 mm Primary conductor 3: 20x20 mm Round conductor: 26 mm Transformer width: 60 mm Transformer height:
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationPage 12-2 Page Page Page DC FUSES FOR PHOTOVOLTAIC APPLICATIONS 10x38mm, IEC class gpv Rated current: 20A Rated voltage: 1000VDC.
Page -2 Page -2 AC FUSE HOLDERS Version without indicator: 1P, 1P+N, 2P, 3P, 3P+N Version with indicator: 1P For fuses x38, 14x51 and 22x58mm IEC class gg or am. IEC rated current: 32A, 50A, 0A IEC rated
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More information