1 j SEMENS DESCRPTON CurrentLimiting Fuses 2.4 and 4.8 Kv for Motor Starting Application The fuse (Fig. ) is a totallyenclosed currentlimiting fuse, designed for motorstarting applications. t is available in basic voltage ranges of 2.4 and 4.8 kv with current interrupting ratings of 8, amperes rms asymmetrical. The fuse consists of silver elements surrounded by inorganic sand, all enclosed in a strong polyester base insulating tube. Circuit connection is made by silverplated copper ferrules on each end of the tube. The silver elements are internally connected to the ferrules. When the fuse is mounted, low resistance is maintained in its supports by the completely silverplated ferrules. A mechanicaltype indicator projects from the lower end of the fuse when the fuse elements melt. The indicator is operated by a mechanism (separate from the fusible elements) that releases the indicator only after the fuse elements have melted. current designations 2R through 36R (Table ) are used to distinguish one size of fuse from another in the same voltage rating. Ampere ratings are not associated with the fuses, since fuse selection is determined by application requirements. These requirements involve both motorstarting current and timecurrent characteristics of the thermal overload relay. FUSE APPLCATON For shortcircuit protection, high voltage motor starters generally employ either fuses or circuit breakers. The standard fuses that are presently available can be classified as current limiting or noncurrent limiting. On short circuit, currentlimiting fuses reduce tne current before the first current peak (Fig. 2) and open the circuit within the first first cycle. The fuse elements melt before the peak value of available shortcircuit current is reached. Noncurrent limiting fuses open the circuit at least one or two cycles after the inception of the short circuit, allowing the peak current to pass. Practically all fuses will melt in considerably less than onehalf cycle on a 6cycle basis when subjected to high values of fault current. Because the arc is the conductor, the current will reach its maximum crest value unless some provision is made to reduce the magnitude of the arc current. When such provision is made, the fuses are classified as current limiting. For the sake of standardization, all fuse interrupting ratings are on the basis of maximum rrns current that will flow in the first cycle after the short circuit occurs (refer to Table ). These are the currents that would flow if the fuse did not limit the current. All types of fuses operate rapidly at, or near, their interrupting ratings. Because of their fast operating time, fuses are generally employed as the last circuit protective device in each voltage level of a primary power system. Typical applications are in motor starters (Figs. 3 and 4). DESCRPTON ceo 683 Page EFFECTVE FEB.. 98 Supersedes issue dated July, 8 Fig. SiemensAllis fuse and fuse clips. Currentlimiting fuses are preferred for motorstarting circuits because t; f their fast operating time and currentlimiting ability. n cases where coordination is not required, noncurrent limiting fuses which have longer time delays may be used. However, in getting this longer time delay, prevention of damage to the circuit when shortcircuit passes is sacrificed. Refer to Fig. 8 for the currentlimiting ability of the fuse. CURRENTf FUSE MELTNG WAVE OF AVALABLE SYMMETRCAL SHORT CRCUT CURRENT Fig. 2 Operating characteristics of currentlimiting fuse. www. ElectricalPartManuals ElectricalPartManuals. com com

2 Page 2 CURRENTLMTNG FUSES 2.4 and 4.8 Kv for Motor Starting Application EXPLANATON OF TYPE DESGNATONS Current Designation: Example: Fuse Type: r+r+r TYPE FM MOTOR STARTNG FUSES.. MOTOR STARTERS Number of elememts 4R /" Cross sectional area 48FM4R4 / Fuse tube size Nominal voltage kv Size 4 are single barrel fuses. Size 5 are double barrel fuses. Size 6 are triple barrel fuses. TRANSFORMER FUSE Fig. 3 Typical motorstarting fuse application. TO LOAD Current designation Fuse, Motor starting Fig. 4 SpaceMaker motor controller with Size 5 www. ElectricalPartManuals. com com double barrel fuses. }

3 CURRENTLMTNG FUSES 2.4 and 4.8 Kv for Motor Starting Application Page 3 Currentlimiting fuses have two important advantages over the noncurrent limiting type: () Because of fast operation, they limit the extreme dynamic and electrical stresses associated with the flow of shortcircuit current. (2) They limit the shortcircuit current magnitude to far less than the available shortcircuit current. n selecting fuses, all factors affecting a particular application will be considered. t will be necessary to know the motor fullload current, the motor rotor current and the overload relay characteristics to assure a properly coordinated installation. Other important factors are as follows: Voltage rating Current rating Frequency rating nterruption rating FUSE CHARACTERSTCS Coordination Location Mounting Motor data Most fuses are selfprotecting. This means that they are capable of extinguishing the arc for any value of current within their interrupting capacity rating current limit. Currentlimiting fuses for motorstarting service are de signed to carry low overload currents for long time periods to permit repetitive motor starting or jogging. This type of fuse must be used in conjunction with a control contactor, or similar device, which will interrupt currents that would require over seconds to melt the fuse. f this is not done, the entire fuse unit could become so overheated that it could not interrupt the current when the fuse finally melted. See Table for minimum interrupting ratings of fuses. Figure 5 is an osciuogram showipg the letthrough current, melting and clearing times for a typical interruption. The interrupting ability of FM fuses has been tested in accordance with AlEE and NEMA standards. The tests range from currents near the minimum flowing current to available currents up to 8, rms amperes, all with maximum design voltage. f the fuse had not been in the circuit to interrupt the fault, the current would have reached 8 ka rms(and approximately ka crest value) in the first loop of current. Fuse timecurrent operating characteristics are given in terms of the melting time for a given value of current. Unfortunately, this method has not been universally accepted. Standards do not specify whether they should be plotted on the basis of shorttime, minimum melting, maximum melting, or total clearing time. On the other hand, timecurrent characteristics of the fuses can be derived from given characteristics by adding or subtracting allowances to curves shown in Figs. 6 and. Figure 6 shows total clearing time curves and Fig. shows mimimum melting curves. The currentlimiting characteristics of the fuse is shown in Fig. 8. This curve shows the maximum instantaneous current peaks permitted by each fuse current designation for various available currents. MELTNG TME.3 () NTERRUPTNG TM 4.48 ( www. ElectricalPartManuals. com com Fig. 5let through current, melting and clearing times for typical nterruption.

4 Page4 ) 6 v looo 6 soo so 3 : 8. 3 J: OS o 3 3.tO SO 6 89 o 5 6 " 9 C " Baals for data: CURRENT UMTNG FUSES 2.4 and 4.8 Kv for Motor Starting Application CURRENT N AMPERES.. g g g g g g 88 W Cl a: a: a: a: a: a: N N C") CD ) c c,? ::>.,...,... l l. i CURRENT N AMPERES Fig. 6 Clearing Time.. Tests are made at 55 volts ac at low pf, starting at 25C with no initial load. 2. Curves are plotted to minimum test points. N a: a: CD P"N, l a: CD C") fl. r.. l r N " r... ". www. ElectricalPartManuals ElectricalPartManuals. com com <( L soo OO o : s m i. = OS OA ;

5 CURRENTLMTNG FUSES 2.4 and 4.8 Kv for Motor Starting Application..... CURRENT N AMPERES g g g. 8 g g gg c ). JO OOO !9 9( 6 5 JO s ) OJ 2.)., Fla. Minimum melting. Baals for data:. Tests are made at 55 volts ac at low pf, starting at 25C with no initial load. 2. Curves are plotted to minimum test points. a: N a: Cf) a: a:a:a: a: a: a: N CD CD "t CD ).... N C"), OwO o o o o 8ooo "l... <...., Q T CURRENT N AMPERES! l. o og g g gggg g ooogo. l l ft, T oo co o o oo oo oooooo.,., e "., o o g D g PageS "" " CD D < so < JO 8 :: s i ) = < OJ OJ,. www. ElectricalPartManuals. com com

6 www. ElectricalPartManuals. com com

7 .. to 4 to so 4 lo t l cu.. 2 2R ll 2 CUrrent n Amperes x T CURRENT CHARACTERSTC CURVES 4R Current Limiting Fuses 24 & 48 Volts (2R24R) Type A2R Current Limiting Fuses 2 Volts (3R8R) T R 9R R! 8R rr. i l T THESE FUSES ARE DESGNED TO NTERRUPT SHORT CRCUT CURRENTS GREATER THAN OR EQUAL TO T(o<A T SHOWN AT THE SECOND MNMUM MELTNG TME PROTECTVE DEVCES N SERES MUST BE COORDN ATED WTH FUSE CHARACTERSTCS TO NTERRUPT LOWER CURRENTS Current n Amperes x SEMENS ENERGY & AUTOMATON, NC. RALEGH, NORTH CAROLNA Current Characteristic CurvesMinimum Melting! 4 to so J J.2..Oil.oe..5 4 OJ 2 E u U).5 www. ElectricalPartManuals ElectricalPartManuals. com com u E i=

8 www. ElectricalPartManuals. com com l

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Each of these factors, as they apply to the selection of Types CLE and CLS current limiting fuses, is briefly outlined on the following pages.

Each of these factors, as they apply to the selection of Types CLE and CLS current limiting fuses, is briefly outlined on the following pages. Westinghouse n This Application Data Description Page Table Fig. No. No. General information... 1 Description......... 1 Let-through current.... 3 A 1,2 Threshold current... 3 A 2 Ratings, voltage and

More information

3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses

3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses .6 Limiting Fuses Motor Start Fuses Product Description Eaton s CLS current limiting fuses are used in conjunction with medium voltage motor starters to provide shortcircuit protection for individual motor

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com DE-ION CURRENT-LIMITING POWER FUSE-TYPE BAL prevents short circuit s from reaching their maximum value and thereby provides greater protective capacity for both the connected apparatus and the feeder system.

More information

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration

More information

www. ElectricalPartManuals. com Series Controller with Draw-Out Vacuum Contactors SIEMENS

www. ElectricalPartManuals. com Series Controller with Draw-Out Vacuum Contactors SIEMENS SEMENS Series 81 000 Controller with Draw-Out Vacuum Contactors 2300, 4000 and 6600 Volts AC (Utilization Voltage) 2400, 4160 and 6900 Volts AC (Distribution Voltage) 2. " -- i '.. 1...' ','', ;... ; ---'...

More information

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED A240R/A480R/A072F/A072B MED. VOTAGE FUSES / R-RATED R-RATED MOTOR STARTER FUSES Amp-trap R-rated fuses are current-limiting, high interrupting rating fuses intended for the short-circuit protection of

More information

Medium Voltage Fuses

Medium Voltage Fuses 2,400-38,000 VAC General Information Current-limiting E and rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides

More information

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED A240R/A480R/A072F/A072B MED. VOTAGE FUSES / R-RATED R-RATED MOTOR STARTER FUSES Amp-trap R-rated fuses are current-limiting, high interrupting rating fuses intended for the short-circuit protection of

More information

Evaluating Selective Coordination Between

Evaluating Selective Coordination Between Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current- Limiting Circuit Breakers selective coordination note 1 By Steve Hansen Sr. Field Engineer and Robert Lyons Jr. Product

More information

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as

More information

LOW-PEAK Time-Delay Fuses KRP-C Class L 600 Volt A

LOW-PEAK Time-Delay Fuses KRP-C Class L 600 Volt A Bussmann LOW-PEAK Time-Delay Fuses KRP-C Class L 600 Volt 601-2000A Dimensional Data All other lerances (± 0.02) 0.63" (± 0.03) All Slots and Holes 10.75" (± 0.09) 8.63" (± 0.09) 6.75" 5.75" 601A 800A

More information

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E. MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E

More information

Selective Coordination

Selective Coordination Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings

More information

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers Evaluating Selective Coordination Between And Non Current-Limiting Circuit Breakers Tech Topics: Selective Coordination Note 1, Issue 1 Steve Hansen Sr. Field Engineer Robert Lyons Jr. Product Manager

More information

General Purpose US Fuses

General Purpose US Fuses SMARTSPOT with Maximum circuit protection Amp-trap 2000 SmartSpot AJT fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product line the AJT fuse provides

More information

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor Reducing Arc Flash Energies on Transformer Secondaries arc flash note 6 By Mike Lang, principal field engineer and Dave Komm, Technical Services Supervisor 1. Introduction Arc flash incident energy calculations

More information

3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses

3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses .5 Limiting Fuses (N)CLPT Fuses Contents escription Selection................ Product Selection....................... etails........................ Page V14-T-4 V14-T-4 V14-T-48 Product escription aton

More information

CS-3 SERIES E-RATED/MEDIUM VOLTAGE FUSES

CS-3 SERIES E-RATED/MEDIUM VOLTAGE FUSES SERIES E-RATED/MEDIUM VOLTAGE FUSES 5kV, 8kV and 15.5kV FERRULE MOUNTED FUSES Amp-trap E-rated 5kV 8kV and 15kV fuses have 2 or 3 inch diameter barrels with ferrules and are mounted in spring reinforced

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH HH DRIESCHER - High-voltage high breaking capacity fuses from 1 kv up to 36 kv HH HH ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-866 MOOSBURG TEL. +9 87 61 6 81-0 FAX +9 87 61 68 11 37 http://www.driescher.com

More information

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution

More information

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.

More information

LENRK/LESRK CLASS RK1 DUAL ELEMENT TIME-DELAY FUSES

LENRK/LESRK CLASS RK1 DUAL ELEMENT TIME-DELAY FUSES LENRK/LESRK CLASS RK Catalog Number LENRK (. - 0A) 50 Volts AC or Less Catalog Number LESRK (.5-0A) 0 Volts AC or Less S LENRK 50V 0..5 75 0..5 5 0..5 9 50 5 0.5 50 0.. 70 0 0..5 5 0 50 7.5 90 0..5 0 50.

More information

Low-Peak 600V Class RK1

Low-Peak 600V Class RK1 LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:

More information

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents. .3 Power Breakers, Contactors and Fuses Fuses General Contents Description Fuses General Product Overview Power Fuse Eaton s roots in the medium voltage power fuse business began over 75 years ago under

More information

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352 8.3kV E-Rated Description: E-Rated, current-limiting, medium voltage fuses for feeder circuit, switchgear and transformer protection. Supersedes pril 2015 USSMNN SERIES Medium voltage fuses for feeder

More information

HCI General Purpose Disconnects

HCI General Purpose Disconnects 30 AMPERES 1oo AMPERES C General Purpose Disconnects AMPERES 0 AMPERES Quality Designed... Thoroughly Tested orsepower Rated 30-0 Amperes, 240, 480 and 0 Volts AC, 2 Volts DC with adjustable operating

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

NH (H.R.C) FUSES AND FUSE BASES

NH (H.R.C) FUSES AND FUSE BASES NH (H.R.C) FUSES AND FUSE BASES NH (H.R.C) Fuses NHC-FB (A...A) NH-FB (A...A) NH-FB (A...A) NH-FB (8A...4A) NH-FB (A...A) NH-FB (A...A) NH (H.R.C) Fuse Bases STEATIT NH-FA NH-FA NH-FA NH-FA NH-FA CONTENTS

More information

K-Limiter high ampere Companion II fuse

K-Limiter high ampere Companion II fuse Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently

More information

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013 Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

Fuse Link Designation

Fuse Link Designation Westinghouse The fundamental use of distribution fuse links is in fuse cutouts to provide protection for electrical equipment against faults and overloads, and increased system service continuity through

More information

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction. HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009 Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

www. ElectricalPartManuals. com Westinghouse Type DB Air Circuit Breakers For Applications up to 600 Volts Ac

www. ElectricalPartManuals. com Westinghouse Type DB Air Circuit Breakers For Applications up to 600 Volts Ac Westinghouse General nformation System Voltage Westinghouse Type DB low voltage air circuit breakers are designed for operation on ac systems up to 6 volts and de systems up to 25 volts. For higher voltage

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers 1.General The design of rectifier equipment requires specific provisions in the switchgear for the protection of power semiconductor

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction. HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 200A 1. General information P&C Medium Voltage fuse-links named PCEF are designed

More information

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES SRIS -RATD / MDIUM VOLTAG FUSS 5kV AND 15kV CLIP-LOCK MOUNTD FUSS Amp-trap -rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as well as

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories ,, FUSE BASES, AND ACCESSORIES Ferraz Shawmut NH Fuse-links, sizes 00, 0, 1, 2, 3 and 4 are rated 500 or 690 Volts AC with breaking capacities of 80kA or 120kA. All fuse-links include an indicator or striker

More information

Technical data OT16E3 OT160E3 UL & CSA

Technical data OT16E3 OT160E3 UL & CSA Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK30SP 30A 600V TD Dual Elem Class RK Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK30SP 30A 600V Class RK Low Peak Dual Element, Time Delay Fuse 600 (lbs/each)

More information

Fuseology. High Speed Fuses

Fuseology. High Speed Fuses Fuseology High Speed Fuses The protection needs for solid-state power equipment often differ from electrical equipment; hence, the high speed fuse evolved. The protection of power diodes and SCRs requires

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 0A 1. General information P&C Medium Voltage fuse-links named PCEF are designed to

More information

E-RATED/MEDIUM VOLTAGE FUSES

E-RATED/MEDIUM VOLTAGE FUSES SRIS -RATD/MDIUM VOLTAG FUSS 5kV, 8kV and 15.5kV Ferrule mounted fuses Amp-trap -rated 5kV 8kV and 15kV fuses have 2 or 3 inch diameter barrels with ferrules and are mounted in spring reinforced clips.

More information

Application Information Need to know how? You ve turned to the right place...literally.

Application Information Need to know how? You ve turned to the right place...literally. Need to know how? You ve turned to the right place...literally. Your problem: Whether your objective is optimum protection of motor control equipment, power or control transformers, cable wiring, or lighting

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

Fusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses

Fusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses Technical Data1019 Supersedes July 2013 Fusetron FRN-R Class RK5 250Vac/125Vdc Catalog symbols: FRN-R-_ (non-indicating) FRN-R-_ID (indicating) Description: Eaton Bussmann series advanced protection, energy

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

Engineering Dependable Protection

Engineering Dependable Protection Electrical Distribution System Engineering Dependable Protection Engineering Dependable Protection - Part II "Selective Coordination of Overcurrent Protective Devices" Table of Contents Page Basic Considerations

More information

Low Voltage Fuses General information

Low Voltage Fuses General information General information Description FUJI low voltage current-limiting fuses are designed to give protection to power supply and distribution circuits and equipment such as motor starter and semiconductors.

More information

4-Day Power System Analysis, Coordination, System Studies

4-Day Power System Analysis, Coordination, System Studies 4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our

More information

www. ElectricalPartManuals. com Engineering Dependable Protection

www. ElectricalPartManuals. com Engineering Dependable Protection Electrical Distribution System Engineering Dependable Protection Engineering Dependable Protection - Part II "Selective Coordination of Overcurrent Protective Devices" Table of Contents Page Basic Considerations

More information

Low Voltage Fuses AFaC and BaC types

Low Voltage Fuses AFaC and BaC types Fa and a types Fa and a type currentlimiting fuses 600V /, 3 400 mps escription The Fa and a type have an excellent current-limiting performance with an interrupting capacity as high as 100k at 600V /.

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E 1512 E47705 Report Reference E4770519970821 15OCTOBER12 Issued to: SIEMENS AG DF CP R&D V 3 WERNERVONSIEMENSSTRASSE 48 9 AMBERG GERMANY This is to certify that representative samples of MOTOR CONTROLLERS,

More information

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz. Page 2 Introduction The Westinghouse Systems Pow-R Breaker, the worlds first encased power breaker, is not just an extension of existing technology. It represents the biggest breakthrough in circuit protection

More information

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)

More information

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA: Supersedes: 160.55-PW4 (1199) FORM 160.55-PW4 (600) PRODUCT DRAWING YORK INTERNATIONAL CORPORATION P.O. Box 1592, YORK, PA 17405 CONTRACTOR ORDER NO. YORK CONTRACT NO. YORK ORDER NO. WIRING DIAGRAM FIELD

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

Protective Device Coordination ETAP Star

Protective Device Coordination ETAP Star Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC

More information

Design Standards NEMA

Design Standards NEMA Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

Medium voltage fuses Medium voltage fuses

Medium voltage fuses Medium voltage fuses European Fuses DIN Fuses 7.2kV - 36kV IBD 7.2 UP TO 36 KV HIGH-VOLTAGE FUSES DESIGNED FOR POWER TRANSFORMER PROTECTION INTERIOR/EXTERIOR USE CERAMIC HOUSING MEDIUM CLASS TRIP-INDICATOR COMBINED WITH A

More information

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com SEMENS-ALLS Medium Voltage Metalclad Switchgear Page 2 Typical Arrangements Auxiliary Cell Over 2000A Breaker Cell A Breaker Cell Over A Breaker Cell --!1 A Breaker Cell Over 2000A Breaker Cell Auxiliary

More information

Fuse Techno and Operation

Fuse Techno and Operation Fuse Techno and Operation Technology Styles Ferrule Euro/ N.Am Tag British/ German Blade Euro/ N.Am Flat Euro/ N.Am 2/ 12 General exploded of the PSC-LR Technology Fuse-elements Body Sand (inside the body)

More information

Synergy EN product information

Synergy EN product information Synergy EN60947-4-2 product information Rated operational voltages U e 200Vac to 480Vac Rated operational currents I e See Rating Table Rating index See Sizing Guide Rated frequency/frequencies 50-60Hz

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017 HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION March 2017 HV FUSE-LINKS IN THE WORLD UL STANDARD E OR R RATED: AMERICAN STANDARD DIN STANDARD: GERMAN STANDARD FR STANDARD: FRENCH STANDARD BS STANDARD: BRITISH

More information

KT4 Manual Motor Starter

KT4 Manual Motor Starter KT4 Manual Motor Starter Ideal for use as a manual starter The KT4 is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE

POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 POWER SEMICONDUCTOR DEVICES... 4 2.1 Power Semiconductor Device Classification... 4 3.0 OVERCURRENT PROTECTION

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

gg, am NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories NH DIMENSION KNIFE-BLADE FUSE-LINKS, FUSE BASES, AND ACCESSORIES

gg, am NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories NH DIMENSION KNIFE-BLADE FUSE-LINKS, FUSE BASES, AND ACCESSORIES , am, FUSE BASES, AND ACCESSORIES Ferraz Shawmut NH Fuse-links, sizes 000, 00, 0, 1, 2, 3, 4 and 4a are rated 500 or 690 Volts AC with breaking capacities of 80kA or 120kA. All fuse-links include an indicator

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Application Guide Semiconductor Fuse Links

Application Guide Semiconductor Fuse Links Application Guide Semiconductor Fuse Links Power Semiconductor Fuse Applications Guide Contents Pages Introduction... 4 Continuous current rating In... 5 Protection against overcurrents - basic concepts...

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information