Underground Cable Thermal Analysis Case Study

Size: px
Start display at page:

Download "Underground Cable Thermal Analysis Case Study"

Transcription

1 Underground Cable Thermal Analysis Case Study Authors - Chulanga Niriella - B.Sc (Eng) Hons, AMIESL chulanga.niriella@gmail.com Nadeera Wijesinghe - M.Sc., B.Sc (Eng) Hons, PMP, AMIESL nadeerawije@gmail.com Introduction The use of underground cables for the purpose of distribution and transmission of electricity has been rapidly increased in the past decades throughout the world specially in the urban areas. With this development electrical related authorities are interested in knowing the maximum possible power that can be transmitted via an underground cable to optimize the use of the cable. This arises the question at what ampacity the cable reaches its maximum possible operating temperature. The Ampacity is the Current Carrying Capacity (CCC) of the Cable, a term which was first used by Del Mar in If the temperature is exceeded the maximum allowable limit, the reliability of the cable will reduce and also may risk of having a premature permanent failure. The maximum temperature which a cable can withstand is defined by the type of the insulation the cable is having. Determination of the safe conditions for the cable which is buried becomes a significant factor in a gulf country like United Arab of Emirates or State of Qatar where the ambient air temperature rises up to 50 0 C during the summer which leads to a soil temperature of 40 Deg. C. In addition, that soil in this region is at a relatively higher dry state (low moisture content) which affects a higher thermal resistance, resulting lower CCC. Actual Underground Cable Laying in a construction site Image Courtesy of / Heat is generated when a current is passed through the conductor which is governed by the simple equation, Heat Generation (Watts) = I 2 R Where R is the resistance of the conductor and I is the current. To prevent the cable undergoing a thermal failure, it is a must to extract this heat in a manner such that cable does not reach the maximum permissible temperature limit (90 0 C as specified by most manufactures). Therefore the ampacity of the cable is governed by the capacity of the installation to extract heat from the cable and dissipate the heat to the soil and the atmosphere.

2 When considering ampacity of a cable, the ampacity is defined at three conditions. 1. Steady state 2. Transient 3. Short Circuit In this article, the cables are analyzed only with respect to the first condition - steady state condition using the electrical/power system simulation software called - ETAP (14.1 version). Methodology & Standards There are two applicable approaches when it comes to thermal analysis of underground cables. 1. Analytical methods based on Neher-McGrath method (IEC & NEC) 2. Numerical method (Finite Element Method) In this paper the ETAP V14.1 electrical simulation software has been used to simulate the thermal behavior of the underground cable system according to the method specified in the IEC method. An underground cable system having 4 number of cables 11kV 3core cables having cross section of 240 mm 2 has been analyzed. The current rating I (ampere) used in the IEC method is governed by the following equation, where Δθ [ o C] is temperature rise between ambient temperature and cable conductor temperature, W d [W/m] is dielectric loss of cable insulation, T 1, T 2, T 3 [K.m/W] are equivalent thermal resistances calculated from the cable material s thermal properties, T 4 [K.m/W] is the cable external thermal resistance, R ac [Ω/m] is the AC electrical resistance of the cable conductor at maximum temperature and λ 1 and λ 2 are the ratio of losses in the metal sheath to total losses in all conductors and the ratio of losses in the armouring to total losses in all conductors, respectively. Cable Underground Thermal Simulation Generally manufacturers provide cable data for specific conditions when it comes to under ground ampacity. But to use the manufacturer data practically for a site installation, we need to adjust the given conditions for the site condition where there are nearby cables (which emits heat and effects one another) as well as the thermal resistivity and temperature of the soil varies. The effect of the nearby power cables as well as the increased ground temperature together with the increased resistance for heat transfer comes with the increased thermal resistivity has to be accounted when it comes to a typical design calculation in Gulf region where the soil temperature reaches 40 0 C. The simulation was first done for the running current, 436 Amperes (the rated current given in the manufacturer cable catalogue - Ducab) in each cable. First the load flow analysis has been done.

3 Conditions given in the cable catalogue Actual Site Conditions Ground temperature C 40 0 C Maximum steady state temperature of the cable C 90 0 C Spacing between 11kV cables Singly laid 750mm Depth of the cable (from earth surface) 800mm 800mm Thermal Resistivity of the back filling material C m/w 2 0 C m/w Current Carrying Capacity (CCC) Ampacity 436 Amps??(Need to find) ETAP Single Line Diagram Cross Section of the Cable System simulated For the above cable arrangement ETAP model has been built and the simulation has been run. For the actual site conditions the temperature of the cable was simulated using the running current of 436Amps (the ampacity given in the cable manufacturer catalogue). Screen shot of the ETAP simulation Temp of cables Since the site conditions are worse than that of the manufacturer specified conditions, the cables heat beyond C (when carrying 436Amps) as per the ETAP simulation results.

4 Neher-McGrath method has been used to find the uniform current which each cable can carry without exceeding the 90 0 C limit in any cable. This can be done with IEC method using a trial and error iterations. But for the purpose of reducing the iterations, Neher-McGrath method has been used. However after finding the maximum current from Neher McGrath method, the simulation was run using the maximum possible current of Amperes with the IEC method and the result is verified with the IEC methodology. Using the ETAP simulation, it has been found that Amperes running in each cable is the maximum current each cable can carry without exceeding the cable temperature of 90 0 C under normal laying conditions. Summary of the ETAP Simulation Results Etap model has been simulated to find the ampacity of each cable system in different site conditions. The cross section of the cable has been kept constant 240 mm 2 three core 11kV cable system. The following factors has been varied to analyze the effect 1. Cable laying depth 2. Thermal resistivity of the backfilling material 3. Cable spacing The summary is given in the below table. Conclusion Determining the ampacity or Current Carrying Capacity (CCC) of the underground buried cables plays a vital role when it comes determining the optimum power which the cable system can transmit. This become far important when the application is in a gulf country where the soil temperature reaches 40 0 C. The manufacturer catalogues typically gives ampacity at specific conditions and most of the time these values can not be directly applied to the prevailing site conditions.

5 The summary of the results has been produced in the earlier section. It has been noted that by decreasing the cable depth, using lesser thermal resistive back filling material or by increasing the spacing between the cables, it is possible to increase the ampacity of the cable. When there is restriction on the depth and also when there are space restrictions, it is possible to increase the ampacity with using of the special backfilling material which have been engineered to have lesser thermal resistance.

Your Partner in Safe Power Solutions. About RESCAB

Your Partner in Safe Power Solutions. About RESCAB Your Partner in Safe Power Solutions About RESCAB Red Sea Cables Company (RESCAB) was established as a closed joint stock company in 2008 in the Kingdom of Saudi Arabia with a capital of 370 million SAR.

More information

TECHNICAL GUIDELINE. Medium Voltage Conductor Ampacities ALUMINUM COPPER. Single Conductor 5kV - 35kV

TECHNICAL GUIDELINE. Medium Voltage Conductor Ampacities ALUMINUM COPPER. Single Conductor 5kV - 35kV Medium Voltage Ampacities Single 5kV - 35kV 2 130 145 150 165 2 100 115 115 130 1 155 175 170 190 1 120 135 130 150 1/0 180 200 195 215 1/0 140 155 150 170 2/0 205 225 225 255 2/0 160 175 175 200 3/0 240

More information

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets OFFSHORE WIND FEASIBILITY STUDY APPENDICES 10-7 10.3.2 Appendix C.2 Subsea Cable Data Sheets Design data for TFVA 36 kv 3x1x240 mm 2 KQ Metallic Laying up Inner sheath Bedding Armor Diameter of conductor

More information

Chapter 7: Thermal Study of Transmission Gearbox

Chapter 7: Thermal Study of Transmission Gearbox Chapter 7: Thermal Study of Transmission Gearbox 7.1 Introduction The main objective of this chapter is to investigate the performance of automobile transmission gearbox under the influence of load, rotational

More information

H07RN-F TITANEX (industrial flexible)

H07RN-F TITANEX (industrial flexible) Description Application TITANEX flexible cable is intended for installations with moving equipment, electric appliances and for building sites. The cable may be rated 0,6/1 kv where the installation has

More information

Earthing Calculation. Contents. Introduction. From Open Electrical

Earthing Calculation. Contents. Introduction. From Open Electrical Earthing Calculation From Open Electrical Contents 1 Introduction 1.1 Why do the calculation? 1.2 When to do the calculation? 1.3 When is the calculation unnecessary? 2 Calculation Methodology 2.1 Prerequisites

More information

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran Effect of Increasing the Grounding Grid Resistance of a Ground System at a Substation on the Safety and Transient Overvoltage on the Interior Equipments M. Bashir M.Sc student, Student Member, IEEE Ferdowsi

More information

High Voltage Aluminum, Smooth Aluminum Shield/Sheath

High Voltage Aluminum, Smooth Aluminum Shield/Sheath High Voltage Aluminum, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric

More information

Cooling System Simulation for Indian Utility Vehicle using COOL3D

Cooling System Simulation for Indian Utility Vehicle using COOL3D Indian GT SUITE Conference 2013 Cooling System Simulation for Indian Utility Vehicle using COOL3D Paper presented by Rishabh Pandey, M&M Gopakishore Gummadi, M&M Copyright 2012 Mahindra & Mahindra Ltd.

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

Analyses of the grid resistance measurement of an operating transformer station

Analyses of the grid resistance measurement of an operating transformer station Ŕ periodica polytechnica Electrical Engineering 53/1-2 (2009) 73 77 doi: 10.3311/pp.ee.2009-1-2.09 web: http:// www.pp.bme.hu/ ee c Periodica Polytechnica 2009 Analyses of the grid resistance measurement

More information

High Voltage Copper, Smooth Aluminum Shield/Sheath

High Voltage Copper, Smooth Aluminum Shield/Sheath High Voltage Copper, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric

More information

Cable category. B Multi-core cables for domestic/handheld equipment Rubber insulation PVC insulation TPE insulation 0.

Cable category. B Multi-core cables for domestic/handheld equipment Rubber insulation PVC insulation TPE insulation 0. Table 12-1: current rating Technical Tables T12 Current ratings basic table ÖLFLEX For cables with a nominal voltage of up to 1000 V and for heat-resistant cables at an ambient temperature of +30 C. You

More information

Quintas & Quintas Group

Quintas & Quintas Group Electric Conductors Quintas & Quintas Group Index Quintas & Quintas and Solidal 2 Bare Conductors l uminium Conductors for overhead lines 3 l uminium loy Conductors for overhead lines 4 uminium Conductors

More information

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide 1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

EARTHING YOUR QUESTIONS ANSWERED

EARTHING YOUR QUESTIONS ANSWERED 18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

STEEL CASING OVERHEATING ANALYSIS OF OPERATING POWER PIPE-TYPE CABLES

STEEL CASING OVERHEATING ANALYSIS OF OPERATING POWER PIPE-TYPE CABLES STEEL CASING OVERHEATING ANALYSIS OF OPERATING POWER PIPE-TYPE CABLES F. P. Dawalibi, J. Liu, S. Fortin, S. Tee, and Y. Yang Safe Engineering Services & technologies ltd. 1544 Viel, Montreal, Quebec, Canada

More information

FR-N1X1G1. Low voltage - Energy, cabling, signalling and control

FR-N1X1G1. Low voltage - Energy, cabling, signalling and control Low voltage - Energy, cabling, signalling and control FR-N1X1G1 Construction: NF C 32-323 NF C 32-323/1 Fire propagation: NF EN 60332-3-24 NF C 32-070 C1 IEC 60332-3-24 C Flame propagation: NF EN 60332-1-2

More information

GEMSCAB has been associated with marketing and manufacturing of Electric Cables

GEMSCAB has been associated with marketing and manufacturing of Electric Cables I NTRODUCTION GEMSCAB has been associated with marketing and manufacturing Electric Cables for over a period 4 decades now. Customer satisfaction has been the prime focus GEMSCAB and today it has established

More information

CONDUCTOR Plain bright annealed copper! alluminium, solid! stranded conductor confirming to IS: 8130: INSULATION INNER SHEATH

CONDUCTOR Plain bright annealed copper! alluminium, solid! stranded conductor confirming to IS: 8130: INSULATION INNER SHEATH c A B L E 5 [B) Techno Flex manufacture high quality heavy duty power cable confirming to IS: 1554 (Part -1) L.T. 1100 volts grade CONSTRUCTION DETAILS:- Power Cable CONDUCTOR Plain bright annealed copper!

More information

XLPE Insulated 1100V. Grade. Aluminium & Copper, Power & Control, Armoured & Unamoured Cables. As per IS : 7098

XLPE Insulated 1100V. Grade. Aluminium & Copper, Power & Control, Armoured & Unamoured Cables. As per IS : 7098 XLPE Insulated 1100V. Grade. Aluminium & Copper, Power & Control, Armoured & Unamoured. As per IS : 7098 SINGLE CORE Armoured Aluminium (A2XWaY/A2XFaY) & Copper (2XWaY/2XFaY) 1100 V. Grade. No. Cores &

More information

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK 1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

Power Electronics and Drives (PED)

Power Electronics and Drives (PED) Power Electronics and Drives (PED) Introduction Spurred on by technological progress and a steadily increasing concern about the efficient use of depleting energy resources, static power electronic converters

More information

Submarine Power Cables

Submarine Power Cables Submarine Power Cables Submarine Power Cables Since decades Nexans plant in Hannover is specialised in the design, production and installation of low and medium voltage submarine power cables required

More information

Ensuring the Safety Of Medical Electronics

Ensuring the Safety Of Medical Electronics Chroma Systems Solutions, Inc. Ensuring the Safety Of Medical Electronics James Richards, Marketing Engineer Keywords: 19032 Safety Analyzer, Medical Products, Ground Bond/Continuity Testing, Hipot Testing,

More information

I N T R O D U C T I O N

I N T R O D U C T I O N I N T R O D U C T I O N GEMSCAB are being manufactured by the people who have been associated with the industry for over years and understand the requirements their valued customers. The company took up

More information

The Introduction of Euro 5 and Euro 6 Emissions Regulations for Light Passenger and Commercial Vehicles

The Introduction of Euro 5 and Euro 6 Emissions Regulations for Light Passenger and Commercial Vehicles The Introduction of Euro 5 and Euro 6 Emissions Regulations for Light Passenger and Commercial Vehicles Introduction As a member of the European Union, Ireland is obliged to introduce Regulation (EC) No.

More information

CORDAFLEX(SMK) (N)SHTÖU Tough Rubber-Sheathed Reeling Cables

CORDAFLEX(SMK) (N)SHTÖU Tough Rubber-Sheathed Reeling Cables CORDAFLEX(SMK) (N)SHTÖU Tough Rubber-Sheathed Reeling Cables 3 SK1_1-001.tif 4 SK1_1-003.tif SK1_1-00.tif Selection and dimensioning criteria Refer to Section 4 for further details Ü Type CORDAFLEX(SMK)

More information

Circumstances affecting the protection against electrode potential rise (EPR)

Circumstances affecting the protection against electrode potential rise (EPR) Ŕ periodica polytechnica Electrical Engineering 53/1-2 (2009) 79 83 doi: 10.3311/pp.ee.2009-1-2.10 web: http:// www.pp.bme.hu/ ee c Periodica Polytechnica 2009 Circumstances affecting the protection against

More information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide 1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules. Fuseology Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression Optima Fuse Holders & Overcurrent Protection Modules Compact, full-featured modules that deliver Type 2 coordinated protection,

More information

National Seminar on New Generation High Performance Conductors. 4 th Dec 14

National Seminar on New Generation High Performance Conductors. 4 th Dec 14 National Seminar on New Generation High Performance Conductors 4 th Dec 14 Compulsion for alternative why? Limitation of power flow New line ROW Constraint Increasing urbanization left no inlet for critical

More information

CiMEC Technologies Pvt. Ltd., 23/H, Meldi Estate, Gota, Ahmedabad, Gujarat. Discipline Electrical Testing Issue Date

CiMEC Technologies Pvt. Ltd., 23/H, Meldi Estate, Gota, Ahmedabad, Gujarat. Discipline Electrical Testing Issue Date Last Amended on - Page 1 of 6 I. CABLES AND ACCESSORIES 1. PVC Insulated Cables Tests on Conductor: Annealing Test (copper) IS 10810 (Part 1):1984 (RA 2011) 0 to 50 % Tensile Test (Aluminium) IS 10810

More information

XLPE Cable Systems. User s guide. rev. 2

XLPE Cable Systems. User s guide. rev. 2 XLPE Cable Systems User s guide rev. 2 C O N T E N T XLPE Cable Systems Page Page Introduction... 3 XLPE cable systems - design, installation and testing... 4 XLPE cables... Cable accessories... Installation

More information

This chapter gives details of the design, development, and characterization of the

This chapter gives details of the design, development, and characterization of the CHAPTER 5 Electromagnet and its Power Supply This chapter gives details of the design, development, and characterization of the electromagnets used to produce desired magnetic field to confine the plasma,

More information

Grid Stability Analysis for High Penetration Solar Photovoltaics

Grid Stability Analysis for High Penetration Solar Photovoltaics Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department

More information

LR9 F OVERLOAD RELAYS

LR9 F OVERLOAD RELAYS Issued November 2009 DATA SHEET LR9 F OVERLOAD RELAYS Based on Schneider MKTED2050EN Catalogue General 6 Motor protection Operating conditions There are many possible causes of electric motor failure.

More information

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU Medium Voltage Flexible Cables for Use In Water sa B-CABLES nv ENERGY

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU Medium Voltage Flexible Cables for Use In Water sa B-CABLES nv ENERGY PROTOLON(ST) NTSCGEWOEU Medium Voltage Flexible Cables for Use In Water ENERGY Technical Data Electrical Thermal Type Type designation PROTOLON(ST) NTSCGEWÖU Approvals/ standards DIN VDE 0250 part 813

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 ER42 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 Int QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Details make the Difference

Details make the Difference 9001:2008 14001:2004 OHSAS 18001:2007 IS 7098 (Part I) Details make the Difference XLPE INSULATED HEAVY DUTY CABLES 650/1100V. Product Range L.V. PVC & XLPE POWER CABLES WITH COPPER AND ALUMINIUM CONDUCTOR

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 Candidate Code No. Result Date Int For Board Use Only ER38 Version of AS/NZS 3000 used (tick ONE Box) 2000 2007 & Amend 1 ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 QUESTION AND ANSWER BOOKLET

More information

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield sa B-CABLES nv ENERGY

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield sa B-CABLES nv ENERGY PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield ENERGY Technical Data Electrical Thermal Type Type designation PROTOLON (ST) NTSCGECEWÖU.../3E Approvals/

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

Introduction. for over a period 4 decades now. Customer satisfaction has been the prime focus of

Introduction. for over a period 4 decades now. Customer satisfaction has been the prime focus of Introduction GEMSCAB has been associated with marketing and manufacturing Electric s for over a period 4 decades now. Customer satisfaction has been the prime focus GEMSCAB and today it has established

More information

Analyzing the Thermal Operating Conditions of a Solenoid

Analyzing the Thermal Operating Conditions of a Solenoid A CASE STUDY FROM SOLENOID SYSTEMS Analyzing the Thermal Operating Conditions of a Solenoid BACKGROUND When designing a Solenoid the operating temperature of the Coil must be taken into account when assessing

More information

High Voltage and Extra High Voltage Cables

High Voltage and Extra High Voltage Cables High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high

More information

Chemical resistance Accidental

Chemical resistance Accidental Industrial flexible cable, insulation and outer sheath in elastomer. Oil resistant, flame retardant according to IEC/EN 60332-1-2 standard. Description Application flexible cable is intended for installations

More information

SUBSTATION DESIGN TRAINING

SUBSTATION DESIGN TRAINING 2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show.

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show. 1 PAPER 7 Sample Questions - C&G 2382 17th Edition paper C 1 o/c 1 - BS 7671 relates to permanent and temporary installations for equipment on: a marinas. b ships. c equipment on aircraft. d railway traction

More information

Restructuring of an Air Classifier Rotor by Finite Element Analysis

Restructuring of an Air Classifier Rotor by Finite Element Analysis Restructuring of an Air Classifier Rotor by Finite Element Analysis Anuj Bajaj 1, Gaurav V.Patel 2, Mukesh N. Makwana 2 1 Graduate Research Assistant, mechanical Engineering Department, Arizona State University,

More information

LOW VOLTAGE XLPE INSULATED POWER CABLES

LOW VOLTAGE XLPE INSULATED POWER CABLES Advanced Solutions Through Technology and Innovation LOW VOLTAGE XLPE INSULATED POWER CABLES CONTENTS Page Introduction... 1 Customer Service... 23 Product Range... 4 Specification and Construction...

More information

SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv

SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv AEIC CS8-13 SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv (4 th Edition) Association of Edison Illuminating Companies AEIC CS8-13 SPECIFICATION FOR EXTRUDED DIELECTRIC,

More information

ElectroFlo. Rapid Virtual Prototyping for Thermal Analysis of Electronics

ElectroFlo. Rapid Virtual Prototyping for Thermal Analysis of Electronics ElectroFlo Rapid Virtual Prototyping for Thermal Analysis of Electronics TES International Company Overview Established in 1994, TES is an engineering company committed to providing innovative and cost-effective

More information

BS 5467 Copper Conductor Multi Core SWA PVC BASEC 0.6/1kV Cable

BS 5467 Copper Conductor Multi Core SWA PVC BASEC 0.6/1kV Cable BS 5467 Copper Conductor Multi Core SWA PVC BASEC 0.6/1kV Cable Eland Product Group: A9S APPLICATION Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary control cables for use in power

More information

CONTENTS. Introduction Customer Service Product Range Specification and Construction...4-6

CONTENTS. Introduction Customer Service Product Range Specification and Construction...4-6 CONTENTS PAGE Introduction... 1 Customer Service...2-3 Product Range... 4 Specification and Construction...4-6 Salient Features of Ducab s Design... 7 Installation and Electrical Data...7-19 XLPE Insulated

More information

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2 BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002

More information

Gasket Simulations process considering design parameters

Gasket Simulations process considering design parameters Gasket Simulations process considering design parameters Sonu Paroche Deputy Manager VE Commercial Vehicles Ltd. 102, Industrial Area No. 1 Pithampur, District Dhar MP - 454775, India sparoche@vecv.in

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

TEK Brief July Is there a difference in installation requirements between communications cables with and without the LP designation?

TEK Brief July Is there a difference in installation requirements between communications cables with and without the LP designation? BECAUSE YOUR BUSINESS RUNS THROUGH US TEK Brief July 2016 LP Cabling: Frequently Asked Questions Table of Contents Introduction Prior to the beginning of the review cycle of the 2017 National Electrical

More information

Pure Lead-Tin Technology

Pure Lead-Tin Technology Pure Lead-Tin Technology Pure Lead-Tin technology offers many advantages which include: High overall efficiency High energy density Excellent high rate performance Excellent low temperature performance

More information

SECTORFLEX CABLE CATALOGUE

SECTORFLEX CABLE CATALOGUE SECTORFLEX CABLE CATALOGUE SAVING SPACE AND TIME R & D + i SERVING OUR CUSTOMERS PRESENTATION One of the largest companies in the sector worldwide. General Cable is a leading company in the manufacture

More information

SUSPENSION 04 CLAMPS

SUSPENSION 04 CLAMPS SUSPENSION CLAMPS 04 4 SUSPENSION CLAMPS 57 Contents General... 58 Suspension clamp trunnion type, forged,... 63 Suspension clamp trunnion type, forged, with bigger angle of deflection, for aluminium based

More information

EFFECT OF SURFACE ROUGHNESS ON PERFORMANCE OF WIND TURBINE

EFFECT OF SURFACE ROUGHNESS ON PERFORMANCE OF WIND TURBINE Chapter-5 EFFECT OF SURFACE ROUGHNESS ON PERFORMANCE OF WIND TURBINE 5.1 Introduction The development of modern airfoil, for their use in wind turbines was initiated in the year 1980. The requirements

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

Corflex. Continuous Corrugated Aluminum Sheathed PL, MC and MV Industrial Cables. Introduction Applications... 3

Corflex. Continuous Corrugated Aluminum Sheathed PL, MC and MV Industrial Cables. Introduction Applications... 3 Corflex Continuous Corrugated Aluminum Sheathed PL, MC and MV Industrial Cables Introduction................................. 2 Applications................................. 3 Corflex PL 300V Instrumentation

More information

Power Arc Testing on Insulator Sets

Power Arc Testing on Insulator Sets Power Arc Testing on Insulator Sets Abstract:Insulator sets are among the most common components in transmission networks and their quality and performance play a vital role in ensuring a reliable electricity

More information

The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw

The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw Powerful, efficient, independent The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw Outstanding testing expertise and always up to date Benefit from decades

More information

Power & Control Cables. U o. /U 0.6/1 kv - IEC

Power & Control Cables. U o. /U 0.6/1 kv - IEC Power & Control Cables U o /U 0.6/1 kv - IEC 60502-1 2 KERPEN GmbH & Co. KG 07.2005 Printing errors excepted. Subject to alteration List of Contents Introduction Page B1 Construction Page B3 Use Page B4

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

REMEZ REMEZ GATE OPERATORS SWING GATE MOTORS REMEZ STANDARD / FAST / HEAVY DUTY SWING GATE MOTORS 220 VOLT A/C AND 12 VOLT D/C

REMEZ REMEZ GATE OPERATORS SWING GATE MOTORS REMEZ STANDARD / FAST / HEAVY DUTY SWING GATE MOTORS 220 VOLT A/C AND 12 VOLT D/C REMEZ GATE OPERATORS SWING GATE MOTORS REMEZ STANDARD / FAST / HEAVY DUTY SWING GATE MOTORS 220 VOLT A/C AND 12 VOLT D/C REMEZ DOMESTIC LIGHT DUTY SWING MOTORS 12 VOLT D/C Remez Gate Operators - 1 - Installation

More information

THE PROTEAN AND POC-MAST DESIGN

THE PROTEAN AND POC-MAST DESIGN THE PROTEAN AND POC-MAST DESIGN Contents 1. The changing landscape of generation for power transmission and distribution. 2. The Holford rules and recommendations for OHL routing and design. 3. The current

More information

Features IN THIS CHAPTER

Features IN THIS CHAPTER CHAPTER THREE 3Special Features IN THIS CHAPTER Motor Braking Regeneration Solutions Sharing the Power Bus: V Bus+ and V Bus- Current Foldback (I T Limit) Front Panel Test Points Resolver Alignment ➂ Special

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate

CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate Sandeep M, U Sathishkumar Abstract In this paper, a study of different cross section bundle arrangements

More information

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A) A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where

More information

DC in the LV network: cable challenges. Antonios Tzimas Dimitris Antoniou Simon Rowland

DC in the LV network: cable challenges. Antonios Tzimas Dimitris Antoniou Simon Rowland DC in the LV network: cable challenges Antonios Tzimas Dimitris Antoniou Simon Rowland UK Government s 2050 reduction in CO2 emissions target. Top of the network describes the HV transmission where transcontinental

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 MOTIVATION OF THE RESEARCH Electrical Machinery is more than 100 years old. While new types of machines have emerged recently (for example stepper motor, switched reluctance

More information

Generators for the age of variable power generation

Generators for the age of variable power generation 6 ABB REVIEW SERVICE AND RELIABILITY SERVICE AND RELIABILITY Generators for the age of variable power generation Grid-support plants are subject to frequent starts and stops, and rapid load cycling. Improving

More information

lectronic starter for single phase duction motor

lectronic starter for single phase duction motor lectronic starter for single phase duction motor PROJECT NO: 104 SUPERVISOR: DR. WEKESA EXAMINER: PROF MANG OLI Prepared by: GITONGA HILDA WANJIKU- F17/39921/2011 PROJECT OUTLINE 1. Project Objective 2.

More information

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes Instructions for the BASIC BCVA Rotary heat exchanger, Sizes 080 120 1. General The BCVA heat recovery unit is a rotary heat exchanger that offers high temperature efficiency. The heat exchanger operates

More information

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS Farhad Shahnia Saeed Tizghadam Seyed Hossein Hosseini farhadshahnia@yahoo.com s_tizghadam@yahoo.com hosseini@tabrizu.ac.ir Electrical and

More information

COLD PLATE SOFTWARE PROGRAM ANALYZES AIRCRAFT

COLD PLATE SOFTWARE PROGRAM ANALYZES AIRCRAFT COLD PLATE SOFTWARE PROGRAM ANALYZES AIRCRAFT DISPLAY T. Renaud Sanders, a Lockheed Martin Co. Nov, 2000 Introduction Finned heat exchangers, called cold plates, have been used for many years to cool military

More information

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives Electrical and Computer Engineering E E 452. Electric Machines and Power Electronic Drives Laboratory #12 Induction Machine Parameter Identification Summary The squirrel-cage induction machine equivalent

More information

DURAREEL TRAILING REELING CABLE

DURAREEL TRAILING REELING CABLE Supplementary Technical Information Reeling and trailing material characteristics: A. Power core conductor Flexible strands tinned annealed copper complies with AS/NZS 1802, AS/NZS 2802, AS/NZS 1125, and

More information

USP s. 30 mm BEND RADIUS

USP s. 30 mm BEND RADIUS Side Deco - White F UV GLOW WIRE 850 C CLEANING AGENTS RoHS FROST IP40/IP68 SEA WATER IK08 SWIMMING POOL R 30 mm BEND RADIUS USP s Made in Europe Unique co-extrusion technology with built in reflection

More information

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

Protection and Connection Motorized and automatic transfer switches IEC Technical guide Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety

More information

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw

More information

Volume-III : Section-I 370 Technical Specifications

Volume-III : Section-I 370 Technical Specifications Volume-III : Section-I 370 TECHNICAL SPECIFICATION-PIERCING INSULATOR 5.1 Insulation Piercing Connectors (IPC) 5.1.1 Insulation Piercing Connectors (IPC) are used for making Tee/Tap-off/Service connectors

More information

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

DATA SHEET FUSIBLE ALLOY THERMAL SENSITIVE PELLET TYPE, 2 AMPERES RATED CURRENT

DATA SHEET FUSIBLE ALLOY THERMAL SENSITIVE PELLET TYPE, 2 AMPERES RATED CURRENT DATA SHEET Thermal Cutoff SEFUSE TM SM/A SERIES FUSIBLE ALLOY THERMAL SENSITIVE PELLET TYPE, 2 AMPERES RATED CURRENT NEC's SEFUSE (SM/A series) is a small, solid and reliable product which can be used

More information

Code Calculations. for an Off-Grid PV System

Code Calculations. for an Off-Grid PV System Code Calculations for an Off-Grid PV System John Wiles Sponsored by the Photovoltaic Systems Assistance Center, Sandia National Laboratories Judy LaPointe s home is on its way to becoming a finished, off-grid

More information