SIEMENS. Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide E87010-A0151-T003-A1-49EC. August, 2012

Size: px
Start display at page:

Download "SIEMENS. Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide E87010-A0151-T003-A1-49EC. August, 2012"

Transcription

1 SIEMENS August, 12 Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide

2 Hazardous voltage. Will cause death, serious injury, or property damage. Always de-energize and ground the equipment before maintenance. Read and understand this manual before installing, operating or maintaining the equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel may result in dangerous conditions which may cause death or serious personal injury or equipment or property damage. Follow all safety instructions contained herein. SIGNAL WORDS The signal words DANGER, WARNING and CAUTION used in this manual indicate the degree of hazard that may be encountered by user. These words are defined as below: Danger Indicates death, severe personal injury or property damage will result if proper precautions are not taken. Warning - Indicates death, severe personal injury or property damage can result if proper precautions are not taken. Caution Indicates personal injury or property damage may result if proper precautions are not taken. KEEP OUT QUALIFIED PERSON ONLY Disconnect power before working on this equipment. For the purpose of this manual and product labels a qualified person is one who is familiar with the installation, construction, oper ation, or maintenance of the equipment and the hazards involved. In addition this person has the following qualifications: (a) Is trained and authorized to energize, deenergize, clear, ground, and tag circuits and equipment in accordance with established safety practices. (b) Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. (c) Is trained in rendering first aid. WARNING Short-Circuit Explosion Hazard. Can cause death, serious personal injury, or property damage. Fully engage all door latches and spread ends of door hinge pins approximately 45 degrees before energizing equipment. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 2 of 18

3 Table of Contents Application... 4 Components Layout... 5 Starter Installation... 8 Reset Assembly... 9 Circuit Breaker Installation Fuse Clip Installation Pilot Device Installation Torque Requirements Label Installation Test Procedure Packaging Instructions IMPORTANT These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purpose, the matter should be referred to the local Siemens sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statement contained herein does not create new warranties or modify the existing warranty. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 3 of 18

4 Application Combination starter enclosure kits are used to assemble combination starters as listed below. 49EC17BB241108R 49EC17CB2408R 49EC17FN362412R 49EC18DB241108R 17CP92B*81 17GP92B*81 17IP92N*81 18CP92B**81 17CU*92B* 17GU*92B* 17IU*92N* 18CU*92B* 17DP92B*81 17HP92B*81 17JP92N*81 18DP92B**81 17DU*92B* 17HU*92B* 17JU*M92N* 18DU*92B* 17EP92B*81 17GP92B* IP92N* EP*92B**81 17EU*92B* 17GP92B* IP92N* EU*92B* 17FP92B*81 17HP92B* JP92N* FU*92B* 17FU*92B* 17HP92B* JP92N* CP92B* GU*92B*14 17IU*92N*16 49EC18DN241108R 17CP92B* GU*92B*15 17IU*92N*17 17DP92B* HU*92B*14 17JU*92N*16 18CP92N**81 17DP92B* HU*92B*15 17JU*92N*17 18CU*92N* 17DP92B* DP92N**81 17EP92B* EC17CN2408R 49EC17FB362412R 18DU*92N* 17EP92B* EP*92N**81 17FP92B* GP92N*81 17IP92B*81 18EU*92N* 17FP92B* GU*92N* 17IU*L92B* 18FU*92N* 17CU*92B*10 17HP92N*81 17JP92B*81 17CU*92B*11 17HU*92N* 17JU*92B* 49EC18DB2408R 17DU*92B*10 17GP92N* IP92B* DU*92B*11 17GP92N* IP92B* GP92B**81 17DU*92B*12 17HP92N* JP92B* GU*92B* 17EU*92B*12 17HP92N* JP92B* HP92B**81 17EU*92B*13 17GU*92N*14 17IU*92B*16 18HU*92B* 17FU*92B*12 17GU*92N*15 17IU*92B*17 18HU*92N* 17FU*92B*13 17HU*92N*14 17JU*92B*16 17HU*92N*15 17JU*92B*17 49EC18DN2408R 49EC17BN241108R 18GP92N**81 17CP92N*81 18GU*92N* 17CU*92N* 18HP92N**81 17DP92N*81 17DU*92N* 17EP92N*81 49EC18DB362412R 17EU*92N* 17FP92N*81 18IP92BP*81 17FU*92N* 18IU*L92B* 17CP92N* CP92N* EC18DN362412R 17DP92N* DP92N* IP92NP*81 17DP92N* IU*L92N* 17EP92N* EP92N* FP92N* EC18EB362412R 17FP92N* CU*92N*10 18JP92BR*81 17CU*92N*11 18JU*92B* 17DU*92N*10 17DU*92N*11 49EC18EN362412R 17DU*92N*12 17EU*92N*12 18JP92NR*81 17EU*92N*13 18JU*92N* 17FU*92N*12 17FU*92N*13 Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 4 of 18

5 Components Layout The follow steps are for the installation of components in the enclosure kits. Once the components needed have been identified from the component selection guide, it s important to place them in the proper location. 1. Locate the components to be installed from the appropriate tables and layouts below. a. To locate the mounting holes for a component, use the column marked Hole I.D. No. b. Match the hole number from the table to the hole number on the panel layout. c. Place the component in the location identified and making sure all mounting holes have been located. 2. Using the hardware specified in table Hole ID Information, secure the component in its location and torque accordingly. 3. After all the components have been installed, wire according to the composite diagram. Enclosure Kits 49EC17**112408R and 49EC18**112408R Hole No. ID 6 B 7 B 8 B 9 B B 21 B 22 B 23 B 24 B 25 B 26 B 27 B 28 B 29 B 40 B 41 B 46 B 47 B 48 B 58 B 78 B 81 B 82 B 83 B 130 B Hole Description 30 / 60A Disc Sw 30 / 60A Disc Sw 30 / 60A Disc Sw 30 / 60A Disc Sw 60A 250V Fuse Spacing 60A 250V Fuse Spacing 30A 250V Fuse Spacing 30A 250V Fuse Spacing 30 / 60A Fuse Spacing Class J 30 / 60A Fuse Spacing Class J 30A 600V Fuse Spacing 30A 600V Fuse Spacing 60A 600V Fuse Spacing 60A 600V Fuse Spacing Class 14 SZ 2 Starter ESP / BIM Class 14 SZ 2 Starter ESP / BIM Class 14 SZ 0 1 3/4 Starter ESP, BIM Class 14 SZ 0 1 3/4 Starter ESP, BIM Class 14 SZ 0 1 3/4 Starter ESP, BIM Class 14 SZ 2 Starter ESP / BIM VA Control Transformer 100VA Control Transformer 45, 50VA Control Transformer 150VA Control Transformer 150VA Control Transformer Hole ID Information I.D. Description Torque B Screw #10-32 X 1/2 25 in-lbs Note: All screws are to be thread forming. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 5 of 18

6 Hole No. ID 15 B 16 B 17 B 18 B 19 B 15 B 16 B 17 B 18 B 19 B 32 B 33 B 34 B B 41 B 42 B 43 B 44 B 45 B 46 B 47 B 48 B 49 B 50 B 51 B 52 B 53 B 54 B 55 B 56 B 57 B 58 B 59 B 60 B 63 B 64 B 78 C 79 C 80 C 87 C 88 C 89 C 114 B 115 B 116 B 123 B 124 B 212 B 213 B 214 B Hole Description 50VA Control Transformer VA Control Transformer 100VA Control Transformer 45, 150VA Control Transformer 0VA Control Transformer 50VA Control Transformer VA Control Transformer 100VA Control Transformer 45, 150VA Control Transformer 0VA Control Transformer 100A Disc. Sw. 100A Disc. Sw. 100A Disc. Sw. 100A Disc. Sw. 0A Fuse Spacing 0A Fuse Spacing 0A 250V Fuse Spacing 0A 250V Fuse Spacing 0A 600V Fuse Spacing Class J 0A 600V Fuse Spacing Class J 0A 600V Fuse Spacing 0A 600V Fuse Spacing 100A 600V Fuse Spacing Class J 100A 600V Fuse Spacing Class J 100A 250V Fuse Spacing 100A 250V Fuse Spacing 100A 600V Fuse Spacing 100A 600V Fuse Spacing 100A 600V Fuse Spacing Class J 100A 600V Fuse Spacing Class J 100A 250V Fuse Spacing 100A 250V Fuse Spacing 100A 600V Fuse Spacing 100A 600V Fuse Spacing 300VA Control Transformer 45VA Control Transformer Class 14 SZ 3 Starter ESP Class 14 SZ 3 Starter ESP Class 14 SZ 3 Starter ESP Class 14 SZ 3 Starter BIM Class 14 SZ 3 Starter BIM Class 14 SZ 3 Starter BIM Class 14 SZ 2 ½ Starter ESP Class 14 SZ 2 ½ Starter ESP Class 14 SZ 2 ½ Starter ESP Class 14 SZ 2 ½ Starter BIM Class 14 SZ 2 ½ Starter BIM 0, 300VA Control Transformer 0VA Control Transformer 300VA Control Transformer Hole ID Information I.D. Description Torque B C Screw #10-32 X ½ Screw #1/4- X ½ 25 in-lbs in-lbs Note: All screws are to be thread forming. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 6 of 18

7 Enclosure Kits 49EC17**362412R and 49EC18**362412R Hole No. ID 48 B 49 B 51 B 52 B 54 B 55 B 56 B 72 B 73 B 74 B 75 B 76 B 77 B 78 B 79 B 80 B 82 B 83 B 84 B 85 B 86 B 87 B 88 B 96 B 97 B 99 B 100 B 102 B 103 B 104 B 117 C 118 C 119 C 1 C 121 C 122 C 123 C 132 C 145 B 152 B 5 B 6 B Hole Description 300VA Control Transformer 0, 300VA Control Transformer 100, 150VA Control Transformer 0, 300VA Control Transformer 0VA Control Transformer 150VA Control Transformer 300VA Control Transformer 100A Fuse Spacing 100A Fuse Spacing 0A Fuse Spacing 0A 600V Fuse Spacing 0A 600V Fuse Spacing 100A 600V Fuse Spacing 0A 250V Fuse Spacing 100A 600V Fuse Spacing 0A 250V Fuse Spacing 100A 250V Fuse Spacing 100A Fuse Spacing Class J 0A Fuse Spacing Class J 100A 250V Fuse Spacing 100A Fuse Spacing Class J 0A Fuse Spacing 0A Fuse Spacing 0, 300VA Control Transformer 100, 150VA Control Transformer 300VA Control Transformer 300VA Control Transformer 150VA Control Transformer 0VA Control Transformer 300VA Control Transformer Class 14 SZ 3, 3 ½ Starter ESP Class 14 SZ 3-4 Starter ESP Class 14 SZ 3-4 Starter ESP Class 14 SZ 4 Starter ESP Class 14 SZ 3, 3 ½ Starter BIM Class 14 SZ 3-4 Starter BIM Class 14 SZ 3-4 Starter BIM Class 14 SZ 4 Starter BIM 100VA Control Transformer 100VA Control Transformer 0VA Control Transformer 0VA Control Transformer Hole ID Information I.D. Description Torque B C Screw #10-32 X ½ Screw #1/4- X ½ 25 in-lbs in-lbs Note: All screws are to be thread forming. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 7 of 18

8 Starter Installation After selecting the appropriate starter from the Component Selection Guide, place the starter in location detailed in the Component Placement section of this manual. Mount and secure. Torque as specified in Torque Requirements section of this manual. Using the power wire supplied, wire from the load side of the disconnect to the line side of the starter for non-fused combination starter (See Figure 1)or from the load side of the fuse block to the line side of the starter for fusible combination starters. (See Figure 2) The power should not be cut. Loop wire has shown in figure 1 & 2. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 8 of 18

9 Reset Assembly Follow these steps to install the reset. 1. With the cover on the enclosure closed, reset button removed, quarter turns latched and the starter installed measure the X dimension. (From the top of the enclosure cover to the top of the overload reset button. Make sure the reset on the overload has been pushed in before measuring.) 2. For the 49EC****241108R and 49EC****2408R enclosures, cut the reset rod to the calculated length, (L) = measured length (X) plus (inches) per Figure 1. Use calculations per Figure 2 for 49EC****362412R enclosure. 3. Reinstall the push button through the hole in the cover and thread the plastic nut on the push button from the inside of the cover. Use assembly tool 3SX1707 to secure. 4. Press the reset rod firmly into the push button from the inside of the cover. When installing a reset button in a Nema 12 enclosure, follow the previous steps with the following exceptions. 1. Install the gasket and push button cover provided. 2. The button cover is placed over the push button and the gasket is placed between the cover and plastic nut. Make sure the button cover has fully engaged the underside of the push button before installing in the cover. 3. As before, tighten the plastic nut using tool 3SX1707. DO NOT over tighten. Reset assembly needs only be snug. If the gasket has extruded from between the cover and the plastic nut, it is too tight. Loosen the assembly and repeat. If the assembly is too tight or too loose, leakage may occur. (Figure 1) (Figure2) Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 9 of 18

10 Circuit Breaker Installation Hazardous voltage. Will cause death, serious injury, or property damage. Always de-energize and ground the equipment before maintenance. Read and understand this manual before installing, operating or maintaining the equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel may result in dangerous conditions which may cause death or serious personal injury or equipment or property damage. Follow all safety instructions contained herein. 1. Locate the barrier under pivot assembly. Align the mounting holes with holes in the barrier. The barrier can be temporarily held in place using a small piece of adhesive tape. (See Figure 1) 2. Locate the breaker over the barrier making sure the toggle on the circuit breaker is in the notch on the pivot assembly and secure using (4) #8 32 x 4.06 screws and (4) 3/8 x 13/16 flat washers (Supplied). Torque screws to in-lbs. Remove adhesive tape from barrier. (See Figure 1) 3. No adjustment to the handle assembly required. 4. Verify that the handle mechanism turns ON and OFF the circuit breaker. 5. Manually trip the circuit breaker and verify that the handle assembly resets the circuit breaker. If the circuit breaker does not reset, contact tech support for assistance. 6. Verify that the door cannot be opened with the handle in the ON position. 7. Install power wires on the load side of the breaker and torque screws. See torque values on circuit breaker. Install wire tie (provided) as shown in Figure 2. Note: Power wire shall not be tin plated. Make sure there are no loose strains of wire. When installing a 5 or 10 amp breaker be sure to use wire Part number D (provided). This wire is used to maintain the short circuit rating on lower amp circuit breaker style combination starters. Discard unused set of wire. Wire Tie Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 10 of 18

11 Fuse Clip Installation Hazardous voltage. Will cause death, serious injury, or property damage. Always de-energize and ground the equipment before maintenance. Read and understand this manual before installing, operating or maintaining the equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel may result in dangerous conditions which may cause death or serious personal injury or equipment or property damage. Follow all safety instructions contained herein. The class 49EC17 enclosure kits have the appropriate disconnect and power wire already installed for non-fused combination starter. Follow the steps below to install fuse clips for a fusible combination starter. 1. Remove the power wire and lugs from the load side of disconnect. Save the power wire to be installed later. 2. Locate the fuse clip trailer block assembly below disconnect. Make sure you have located the appropriate mounting holes for the proper fuse spacing. (See Component Placement) A sample fuse of the right Amp and Voltage can be used to verify fuse spacing. 3. Secure the trailer block using (2) #10 32 x ½ screws provided in the fuse clip kit and torque in-lbs. 4. Install fuse clips on the load side of disconnect using hardware provided and torque in-lbs. Refer to the fuse clip kit instructions for fuse clip orientation and installation of rejection pins for 100 amp and larger. 5. Reinstall power wire to the load side of the trailer block lugs and torque. (Refer to Torque Requirements) 6. Install wire tie (provided) locating it in the center of the power wire securing all 3 wires. (See Figure 1) 7. When installing fuse clips in the 49EC17**362412R enclosure, (2) fuse clip kits will be needed. Install one assembly above the other and turn 180 degree to create a line and load side fuse block making sure you have the proper fuse spacing between the two fuse clip assemblies. Cut a small length from all three power wires included and connect between disconnect switch and line side fuse block. Use remaining power wire to connect load side fuse block to starter. Follow steps 5 & 6 and torque as specified. (See Figure 2) Wire Jumpers Tie Wrap (Figure 1) (Figure 2) Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 11 of 18

12 Pilot Device Installation Hazardous voltage. Will cause death, serious injury, or property damage. Always de-energize and ground the equipment before maintenance. Read and understand this manual before installing, operating or maintaining the equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel may result in dangerous conditions which may cause death or serious personal injury or equipment or property damage. Follow all safety instructions contained herein. 1. When installing pilot devices, the primary control (off) shall be installed in the lower right side of the enclosure with subsequent devices installed as shown in Figure 1 for combination starters. 2. For installation for pilot devices, refer to instruction sheet included with each device for proper assembly and installation. OFF Light if installing Start stop Push Button and ON / RUN light 4 th Position 3 rd Position 2 nd Position 1 st Position ON / RUN / OFF Light If installing start stop Push Buttons OR OFF / ON / RUN Light If installing an HOA Start Push Button Or ON / RUN / OFF Light if installing an HOA Hand Off Auto Selector switch Or Stop Push Button NOTE: This drawing does not cover all possible combinations. Figure (1) Nema 1 & 12 Flange Mounted Devices Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 12 of 18

13 Torque Requirements To insure that a screw or bolt is tight and remains tight, a certain amount of tension must be developed in the joint. An indirect measure of this tension is the amount of torque or force applied to a wrench in tightening a joint. To achieve a specific torque, one can use a torque wrench or other tool such as air wrench which has been calibrated. It can be calibrated to stop by itself or it may have a clutch which slips when the specific torque has been reached. A torque wrench is a tool which indicates the torque being applied at any instance. All screws intended for mechanical connection (such as mounting of components) shall use the torque values that are recommended per the instruction sheet. If no instruction sheet is supplied, or the torque value is not stated, then follow tables below. MECHANICAL CONNECTIONS TIGHTING TORQUES TIGHTING TORQUE TIGHTING TORQUES (IN METAL) IN PLASTIC THREAD FORMING SCREWS SCREW SIZE MIN. TORQUE SCREW SIZE MIN. TORQUE SCREW SIZE MIN. TORQUE (IN-LBS) TYPE 25 (IN-LBS) IN-LBS) # # # # ¼- # # # # / 4 75 ¼ / / / LUG AND CLAMP TORQUE Screw Size Description Minimum Torque #8 or Smaller #10 or Larger 5/16 3/8 7/16 1/8 3/16 1/4 5/16 3/8 7/16 1/2 9/16 5/8 11/16 3/4 Pressure or Saddle Clamp Slotted Lug- Slotted Lug- Slotted Lug- Slotted Lug- Allen Head Lug- Allen Head Lug- Allen Head Lug- Allen Head Lug- Allen Head Lug- Allen Head Lug- Allen Head 12 in-lbs in-lbs in-lbs in-lbs in-lbs in-lbs 50 in-lbs 75 in-lbs 100 in-lbs 125 in-lbs 150 in-lbs 0 in-lbs Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 13 of 18

14 ELECTRICAL CONNECTIONS CONTROL / POWER WIRE WIRE GAUGE MIN. TORQUE INCH LBS RANGE STARTER / CONTACTOR SIZE 00 & ¾ 1 ¾ 1 ¾ 2, 2 ½ 2, 2 ½ 2, 2 ½ 3, 3 ½ 3, 3 ½ 3, 3 ½ 3, 3 ½ ALL < 10 8 < < < > 3 < > 3 STRANDED WIRE STAKE-ON CIRCUIT BREAKER AMPS Refer to torque level on device FUSIABLE DISCONNECTS PRESSURE PLATE 30 60A BOX LUGS A Refer to torque level on device TERMINAL BLOCKS GA GA. 6 4 GA. Refer to torque level on device 11 COIL TERMINALS OVERLOAD TERMINALS 7-10 (bimetal OLR) (solid-state OLR) Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 14 of 18

15 Label Installation 1. When installing labels, locate labels as outlined in figure 1 for 49EC****241108R, figure 2 for 49EC****2408R and figure 3 for 49EC****362412R enclosures. 2. Fill out the modified to label by writing in the new catalog number with black ink in the space labeled Modified To making sure that the catalog number does not run off the label. Enter the Company name and initials of the person making the modification in the area labeled By and the date the modification was made in the area labeled Date. 3. When installing a thermal overload, apply the heater table label furnished with the starter. 4. For enclosure kits 49EC****2408R and 49EC****362412R, apply composite label furnished loose with enclosure kit. 5. Check off the appropriate box (s) for modifications made to the unit on the exterior carton label using a black permanent marker. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 15 of 18

16 OUTSIDE OF DOOR INSIDE OF DOOR Heater Table (Bi-Metal Overload Only) 49EC Product I.D. / Modified To: (To be filled in when unit has been modified) Composite Label D (Wiring Diagram) Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 16 of 18

17 Test Procedure The following test applies to Class 17 & 18 Combination starters which have had control devices added, i.e., START- STOP pushbuttons, PILOT LIGHTS etc., This test procedure is for the purpose of testing control wiring and do not require the running of a motor. DANGER A potentially hazardous situation which, if not avoided, will result in death or serious injury. Disconnect power before proceeding with any work on this equipment. This product contains hazardous voltage. Severe personnel injury, death or property damage can result if safety practices are not followed. Only qualified personnel should test this equipment after becoming thoroughly familiar with its electrical schematic and operation. Turn off all power supplying this equipment before any adjustments, wiring, parts replacement, or before any act requiring physical contact with working components of this equipment is performed. Starters Under Test 1. Check that mechanical assembly matches assembly drawings (when applicable) and / or wiring diagrams. 2. If installed, check that the CPT primary voltage is correct and connected per the wiring diagram. 3. Combination Starter Disconnect / Motor Circuit Interrupter test: Circuit breaker manual trip test: - Manually trip circuit breaker - Check that circuit breaker resets 4. Door safety interlock test: - Check that door will not open when disconnect or circuit breaker handle is in the ON position. - Check that the disconnect / circuit breaker handle will not turn ON with the door open. 5. Check that the catalog number is correct and the components match the wiring diagram. Electrical Test 1. Ensure input tester power supply is OFF before proceeding. CAUTION: Ensure the start pilot device is in the OFF position. 2. Connect the correct input power per wiring diagram. 3. Apply input power to starter. 4. Apply the ON signal and observe the proper operating sequence of the contactor(s) and components. 5. Check the proper operation of all inputs and outputs (including simulating customer supplied and / or remote pilot devices) of the starter. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 17 of 18

18 6. Test that the overload relay will trip the control circuit and will de-energize starter. 7. Reset overload relay and check that starter will re-energize. 8. Shut down starter. 9. Turn OFF test supply power. 10. Disconnect all input power, pilot devices and jumpers. If any part of this test fails, check the connections and retest. If the test still fails, contact Siemens Tech Support. Packaging Instructions 1. For modified products, repackage the item in the container in which the unit was originally shipped. Be sure to apply the correct catalog number to the shipping label. Fill in any other applicable information on the shipping label. 2. If it is not possible to reuse the original container, find a suitable box and package the items securely. A suitable box is one in which all items can be placed without deforming the box flaps. This can be accomplished by completely filling the box with packaging material after items have been placed in it. The box should be firm and not subject to crushing during normal handling. Affix an appropriate size, blank label to the box. Complete the label by printing the correct catalog number. Fill in any other applicable information on the shipping label. 3. Securely tape the box closed. Be sure that the tape does not prevent the ability to read any part of the shipping label. 4. When filling out the carton label, the catalog number should not run off the label. Carton label is located on the end of the original shipping carton. 5. When printing catalog number on labels, legibly print catalog number in black. 6. DO NOT COVER enclosure labels (inside door) with the blank label. Siemens Industry, Inc Triangle Parkway, Norcross, GA A5E A-001 Page 18 of 18

SIEMENS. Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide E87010-A0151-T003-A1-49EC. September, 2017

SIEMENS. Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide E87010-A0151-T003-A1-49EC. September, 2017 SIEMENS September, 17 Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide Hazardous voltage. Will cause death, serious injury, or property damage. Always de-energize and ground

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the

More information

Instruction sheet WARNING. October, 2014

Instruction sheet WARNING. October, 2014 E8700-A064-T003-A6-LCN0 Page of 6 October, 04 WARNING Hazardous voltage Can cause death or serious injury. Disconnect main power and control voltages before installation or maintenance on the equipment.

More information

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3 SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious

More information

Instruction and Installation Guide

Instruction and Installation Guide Instruction and Installation Guide Type 2A Arc Resistant tiastar Motor Control Center www.usa.siemens.com/mcc DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualified personnel

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only s SFIS-70090-0808 August, 2008 TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only Siemens Energy & Automation, Inc. Hazardous voltage. Will cause death or serious injury.

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968 Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988 Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

RGZESDI Inverter Duty AC Induction Motors

RGZESDI Inverter Duty AC Induction Motors November 1999 RGZESDI Inverter Duty AC Induction Motors Installation Operation Maintenance Instructions Frames: 143T through S449SS/LS SIGNAL WORDS The signal words Danger, Warning and Caution used in

More information

Cradle Mounted Key Interlock Guide Frame Accessory

Cradle Mounted Key Interlock Guide Frame Accessory s Cradle Mounted Key Interlock Guide Frame Accessory Cat. No.: WLDLKRK, WLDLSUP, WLDLDKRK, WLDLDSUP, WLDLPR, WLDLDPR For Use With: Circuit Breaker Adapters WLG _ 3 Installation Instructions Instruction

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN Reclosers MN280022EN Effective October 2015 Supersedes S280-40-10 April 2014 COOPER POWER SERIES Mercury switch to microswitch retrofit kit KA349WE installation instructions DISCLAIMER OF WARRANTIES AND

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type AMR For Allis Chalmers 5kV Instructions Installation Operation Maintenance E50001-U229-A289-X-US00 Hazardous voltages and high-speed moving parts. Will cause death,

More information

Quik-Spec Coordination Panelboard

Quik-Spec Coordination Panelboard Read and retain for future reference Quik-Spec Coordination Panelboard Instruction Leaflet 3A1071 RevD Section TABLE OF CONTENTS Page Danger and warnings for installation of the equipment.............3-4

More information

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry See NEW information on Class 82 size 1 in an extra wide enclosure and size 2 standard enclosures. usa.siemens.com/controls

More information

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

Controls Express. A wide selection of enclosed NEMA controls now available with faster shipping as a standard. Fast. Easy. Reliable.

Controls Express. A wide selection of enclosed NEMA controls now available with faster shipping as a standard. Fast. Easy. Reliable. Controls Express A wide selection of enclosed NEMA controls now available with faster shipping as a standard. Fast. Easy. Reliable. usa.siemens.com/controls-express Table of contents Starters at the speed

More information

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN Reclosers MN280014EN Effective September 2015 Supersedes S280-10-6 April 2003 COOPER POWER SERIES Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits DISCLAIMER OF WARRANTIES AND

More information

Product guide. Enclosed NEMA starters. usa.siemens.com/controls

Product guide. Enclosed NEMA starters. usa.siemens.com/controls Product guide Enclosed NEMA starters usa.siemens.com/controls The right choice for applications that demand the best Siemens NEMA combination and non-combination starters for industrial and construction

More information

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers Contents Description Page Introduction.............................. 2 Step 1: General Breaker Preparation......... 3 Step 2: Removing the Original Components.. 3 Step 3: Installing the Sensors..............

More information

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G) Part B, Section 1 This section covers the following unit configurations. Model 3100 3400 3500 Voltage 1, 2 Pump Piston (E, F, or G) Manifold 4-Port (A) 6-Port (B or C) Control UniScan (1) B 1-0 B 1-1 Section

More information

Installation and Operation

Installation and Operation S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters

More information

ibusway for Data Center

ibusway for Data Center ibusway for Data Center PBPQOD Plug-In Units with 15 60 A Circuit Breakers for Use On Busway Straight Sections Class 5600 Installation S1B99523 06/2012 Hazard Categories and Special Symbols Read these

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND

More information

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640 Instruction Bulletin 4-722-2 /29 Peru, IN, USA Replaces 4-722-1 1/28 Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 164 Retain for future use. Introduction

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type GER 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9978D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry See NEW preliminary information on Class 82 size 1 in an extra wide enclosure and size 2 standard enclosures. www.usa.siemens.com/controls

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

49 E B 14 E B R. NEMA Type B NEMA 1 0 NEMA 12 W NEMA 4 S.S.

49 E B 14 E B R. NEMA Type B NEMA 1 0 NEMA 12 W NEMA 4 S.S. Non-Combination Kits, Class 49 49 E B 14 E B 11 07 05 R Class 49 Field Kit Type E Only Model B Model C 2002 Product Class 14 Class 14, 40 22 Class 22, 43 30 Class 30 Starter Size E 00, 0, 1, 1 3 4 G 2,

More information

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER

More information

Effective November 2016 Supersedes September 1998 (S )

Effective November 2016 Supersedes September 1998 (S ) Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

O & M Manual for the EATON Generator Ready Loadcenter

O & M Manual for the EATON Generator Ready Loadcenter O & M Manual for the EATON Instructional Booklet New Information Description Page 1. Introduction............................... 2 2. Receiving, Handling, and Storage................ 4 3. Equipment Description........................

More information

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

CM52 Network Protector with Arc Flash Reduction Module

CM52 Network Protector with Arc Flash Reduction Module Contents Description Page 1: General.............................. 2 2: Maintenance Mode Settings.............. 2 3: Arming Maintenance Mode.............. 2 4: Remote Indicator....................... 2

More information

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

MOTORTRONICS Solid State AC Motor Control

MOTORTRONICS Solid State AC Motor Control Solid State AC Motor Control MWH Series Solid State Motor Winding Heater 10 to 80 Amps INSTALLATION & START-UP MANUAL REV 4 6091101MN Table of Contents Chapter 1: General Information... 1 1.1 Introduction

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2 SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

Installation Guide Current Ford F-250 & Ford F-350 Super Duty. Product Code: 109 & 119

Installation Guide Current Ford F-250 & Ford F-350 Super Duty. Product Code: 109 & 119 Installation Guide 2008 - Current Ford F-250 & Ford F-350 Super Duty Product Code: 109 & 119 September 1, 2012 Tools Needed Components Included 3/8" Drill P2 Tip #2 Philips Screwdriver 1/2" Drill Bit Hinged

More information

NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry Answers for industry.

NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry Answers for industry. www.usa.siemens.com/controls NEA Pump Controls Class 82 slim line NEA pump controller for the agricultural industry Answers for industry. Class 82 Slim Line NEA Pump Controller Typical applications include:

More information

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions Reclosers MN280034EN Effective December 2015 Supersedes S280-10-13 May 2003 COOPER POWER SERIES KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

Product guide. Enclosed NEMA starters. Answers for industry.

Product guide. Enclosed NEMA starters. Answers for industry. Product guide Enclosed NEMA starters Answers for industry. The right choice for applications that demand the best Siemens NEMA combination and non-combination starters for industrial and construction applications

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Effective March 2015 Supersedes S August 2012

Effective March 2015 Supersedes S August 2012 Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions

More information

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES

More information

WARRANTY INFORMATION...

WARRANTY INFORMATION... Table of contents 1 General Information... 3 1.1 Description... 3 1.2 Features... 3 1.3 Specifications... 4 1.4 Receiving and Unpacking... 4 1.5 Dimensions... 4 2 Installation... 5 2.1 Wiring... 5 3 Operation...

More information

SAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS! When using electrical equipment, basic safety precautions should always be

More information

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

Figure 1. Kearney Type HX cutout.

Figure 1. Kearney Type HX cutout. Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2

More information

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640 Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640 80043-731-02 10/2009 Peru, IN, USA Retain for future use. Introduction This bulletin contains

More information

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches An Investment in Plant Floor Safety 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches Notes 2 802C Cable Pull Safety Switches Safety and Application Safety

More information

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by

More information

Technical Manual. DLM Module. This manual should remain with the unit.

Technical Manual. DLM Module. This manual should remain with the unit. Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S ) Pad-mounted Switchgear MN285019EN Effective March 2017 Supersedes February 2007 (S285-10-6) COOPER POWER Type VFI fault interrupter with tri-phase control single-phase trip to three-phase trip conversion

More information

INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES

INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES SYSTEM CONCEPT When not transferring fuel, the pressure in the underground closed piping system of a gasoline station may fall due

More information

CCP2-FLR1-21_ flange-rod operating mechanism

CCP2-FLR1-21_ flange-rod operating mechanism Installation manual 3A3747 Rev A Contents Description Page General information 1 Required tools 2 Hardware contents 2 Installation and adjustment 2-6 Flange drilling pattern 7 HAZARD OF ELECTRIC SHOCK,

More information

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps Operator s Manual 7000 Series ATS Automatic Switches 600 through 1200 amps 600---1000 amp. size An experienced licensed electrician must install the ATS. DANGER is used in this manual to warn of high voltages

More information

IMPORTANT WARRANTY & INSTALLATION INSTRUCTIONS ATTACHED TO ACTIVATE YOUR WARRANTY GO TO: CORSAPERFORMANCE.COM/WARRANTY STOP

IMPORTANT WARRANTY & INSTALLATION INSTRUCTIONS ATTACHED TO ACTIVATE YOUR WARRANTY GO TO: CORSAPERFORMANCE.COM/WARRANTY STOP IMPORTANT WARRANTY & INSTALLATION INSTRUCTIONS ATTACHED Please Forward All Attached Information to Consumer Warranty Not Valid Unless Returned to CORSA Performance We ask that you take a few moments to

More information

Installation Instructions

Installation Instructions Installation Instructions Bulletin 1494V Variable Depth, Flange Operated Circuit Breaker Operating Mechanisms For use with Circuit Breakers 140G-G, 140MG-G, 140G-H, 140MG-H, 140G-I, 140MG-I, 140G-J, 140MG-J,

More information

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS

More information

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION To reduce the risk of death, personal injury or property damage from

More information

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 Installation Instructions Series I Encapsulated Current Limiting Fuse GWI 701-4 Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage. Voltage Regulators QD8 Movable Contact Board Replacement Procedure Kit 5742895B01 Service Information S225-50-38 Contents General..................................... 1 Parts Supplied...............................

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter Operation, and Maintenance of the Instruction Bulletin Read and understand these instructions before attempting any installation, operation, or maintenance of the. This equipment shall be installed and

More information

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers Supersedes IL 33-GS8-2 Dated 10/00 (Manually Operated Only) Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:...............................

More information

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640 Instruction Bulletin H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640 80043-725-02 02/2009 Peru, IN, USA Replaces 80043-725-02 01/2008 Retain for future

More information

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy NorthStar TM brand Instruction Manual SLIM Tach SL56 1.125 Thru-Shaft Diameter Magnetoresistive Encoder Designed for GE Wind Energy Patent Pending *791-1061-00* Rev. B Page 2 Table of Contents Chapter/Paragraph/Illustration

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

Effective November 2016 Supersedes February 2012 (S )

Effective November 2016 Supersedes February 2012 (S ) Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling

More information

Installation Instructions

Installation Instructions 265V Subbase Receptacle Accessory Kit For Use With Packaged Terminal Air Conditioner Installation Instructions INTRODUCTION These instructions cover the installation of the 265V Subbase Receptacle Accessory

More information