Fundamentals of the Ultrasonic Flowmeter

Size: px
Start display at page:

Download "Fundamentals of the Ultrasonic Flowmeter"

Transcription

1 Exercise 1 Fundamentals of the Ultrasonic Flowmeter EXERCISE OBJECTIVE Learn the working principle of ultrasonic flowmeters, familiarize yourself with the ultrasonic flow transmitter of the Instrumentation and Process Control Training System, and learn how to commission it. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Introduction How an ultrasonic flowmeter works Transit-time flowmeters. Frequency-difference measurement. Reynoldsnumber correction. Construction and installation. One, two, and four traverses. Characteristics of ultrasonic flowmeters Advantages and limitations. Industrial applications. Description of the supplied ultrasonic flowmeter Summary of technical specifications. Installing the ultrasonic flowmeter Installation procedure. Calibration DISCUSSION Introduction The invention of the ultrasonic flowmeter can be traced back to 1963 when Tokyo Keiki, a Japanese company, first commercialized this type of flowmeter. Almost a decade later, Controlotron (now part of Siemens) was the first American company to manufacture ultrasonic flowmeters. It was not until recently that manufacturers were able to overcome the main challenges of ultrasonic flow measurement and make affordable and reliable ultrasonic flowmeters. Ultrasonic flowmeters are available in two types: transit-time measurement and Doppler effect. Transit-time flowmeters measure the fluid velocity by comparing the downstream and upstream traveling times; the time difference between the two is proportional to the average fluid velocity. Doppler effect flowmeters measure the fluid velocity from the ultrasonic waves reflected back from bubbles or particles in suspension in the liquid. The disadvantage of this method is that the ultrasonic waves need something to reflect upon; hence, this flow measurement method is not suitable for clean water. In the following section, we will concentrate on the transit-time flow measurement method, which is ideal for acoustically transparent liquids. How an ultrasonic flowmeter works Below is a description of the time-transit method, which is one of the two measurement methods behind ultrasonic flowmeters. The different setups for the Festo Didactic

2 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion sensors and the electronic corrections available for most ultrasonic flow transmitters are also discussed. Transit-time flowmeters The basic principle behind transit-time flowmeters is simple: two ultrasonic energy pulses traverse diagonally through a pipe in opposite directions, with one pulse transmitted downstream (with the flow) and one pulse transmitted upstream (against the flow), as shown in Figure 1. The flowmeter measures the transit-time for both pulses, that is, the time it takes for the pulses to get from one sensor to the other. The flowmeter then computes the average velocity of the fluid from the difference between the two transit-times. Upstream signal Transducer B Flow Transducer A Downstream signal Figure 1. Transit-time flowmeter principle. To operate correctly, transit-time ultrasonic flowmeters require that the process fluid is transparent to ultrasonic waves and devoid of air bubbles or particles that can reflect or attenuate ultrasonic waves. A sound wave traveling in a moving fluid tends to be carried along with the flow. Therefore, an ultrasonic pulse traveling downstream travels faster than a pulse traveling upstream. Figure 2 shows that the flow direction of the fluid (moving at an average velocity ) is at an angle with the ultrasonic signal path. Depending on whether the ultrasonic signal is travelling upstream (Figure 2a) or downstream (Figure 2b), the portion of the fluid velocity parallel to the ultrasonic signal path is added or subtracted from the sound velocity. (a) (b) Figure 2. Transit time for the a) upstream signal and b) downstream signal. 2 Festo Didactic

3 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Figure 3 shows how the velocity of the fluid influences the velocity of the ultrasonic pulse. For the ultrasonic pulse traveling downstream (Figure 3a), the velocity of the fluid contributes positively to the overall speed of the pulse. Since the two transducers are at an angle, the contribution of fluid velocity to the ultrasonic pulse velocity is. For the ultrasonic pulse travelling upstream (Figure 3b), the velocity of the fluid reduces the overall speed of the pulse by. Note that the vectors are not to scale. The length of is greatly exaggerated so that the principle can be illustrated clearly. In general, the fluid velocity is much smaller than the speed of sound. (a) (b) Figure 3. Contribution of fluid velocity to the speed of ultrasound pulse. Knowing this, it is easy to calculate the time it takes for an ultrasonic pulse to travel downstream for the distance between transducer A and transducer B. The pulse transit-time from A to B is simply the distance divided by the pulse velocity. It is expressed as follows: (1) where is the transit time for the ultrasonic pulse to travel the distance is the distance between the two transducers is the speed of sound is the average fluid velocity is the angle between the ultrasonic pulse path and the pipe axis An ultrasonic pulse travelling upstream is slowed by the fluid flow. The transit time from transducer B to transducer A can be calculated using an equation similar to the one used for a downstream pulse, except that the contribution of the fluid flow must be subtracted from the sound velocity instead of added. Equation (2) gives the transit time for an ultrasonic pulse traveling upstream. (2) Festo Didactic

4 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Combining Equation (1) and Equation (2) allows the time difference between the two transit times to be expressed as follows: (3) This relation can be simplified further as detailed below: Since, we have ; therefore can be neglected compared to and the time difference can be approximated as: (4) Using Equation (4) we find that the average velocity of the fluid is: (5) Following steps similar to those presented above, it can be shown that the average transit-time is: (6) Thus, Equation (5) can be simplified as: (7) An important corollary of Equation (7) is that the measure of the fluid velocity using an ultrasonic flowmeter is independent of the speed of sound. This means that measurements made with an ultrasonic flowmeter are independent of the fluid temperature and pressure, which is an important advantage for several applications. Frequency-difference measurement Another way to analyze what is going on in an ultrasonic flowmeter is to look at the frequency difference between the upstream and downstream pulses. The 4 Festo Didactic

5 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion frequency for each of the two pulses is the reciprocal of their respective transit time. That is: and (8) The frequency difference is expressed in Equation (9). (9) Thus, the average velocity of the process fluid is: (10) Both Equation (7) and Equation (10) are independent of temperature, pressure, density, and viscosity. Once the average velocity of the process fluid is known, the flow rate can be easily calculated using the cross-sectional area of the pipe: (11) where is the flow rate is the average fluid velocity is the cross-sectional area of the pipe Reynolds-number correction The distribution of the local velocities varies according to the average velocity of the fluid in a pipe. The form that the distribution of the velocities takes is called the flow profile. Figure 4 shows a laminar profile and a turbulent flow profile, which are the two main types of flow profiles for a fluid in a pipe. A turbulent flow (Figure 4a) has an almost flat velocity profile while a laminar flow (Figure 4b) has a velocity profile with a bump since the distribution of the velocities is not uniform. Therefore, with a laminar profile, the ultrasonic pulse velocity varies along its path between the two transducers, depending on the local fluid velocity. Laminar flow occurs at a low flow rate. To determine if a flow is turbulent or laminar, the Reynolds number must be calculated. If the Reynolds number is greater than 4000, the flow is turbulent. A Reynolds number below 4000 means the flow is either transitional (a mix between laminar and turbulent) or laminar (below 2000). Festo Didactic

6 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion (a) Figure 4. Shape of the different velocity profiles. To tackle the problem caused by the variation of the flow profile, many ultrasonic flowmeters include a Reynolds-number correction mechanism. This usually involves multiple ultrasonic measurement beams coupled with an algorithm that matches the measurements with a flow profile to make the required corrections for determining the average flow rate of the fluid. c (b) For details on the calculation of the Reynolds number or on the different types of flows, refer to the Measurement manual. Construction and installation The transducers of an ultrasonic flowmeter are either housed in a pipe section with flanged ends or installed on a clamp-on system, allowing them to fit on a wide range of pipe diameters. The ultrasonic pulses are generated and detected by the transducers using piezoelectric crystals. Piezoelectric material, mainly crystals and some ceramics, has the peculiar ability to generate an electric signal when subjected to a mechanical stress such as vibration. The beauty of piezoelectricity is that it also works the other way around! That is, if an electric signal is applied to a piezoelectric material, it responds by vibrating at its resonant frequency. For small pipe diameters, the transit time is short since the traveled distance between the two transducers is small. Too small a travel distance produces inaccurate and sometimes unusable signals. Using one of the multiple traverses installations described below can correct this problem. One, two, and four traverses For small pipelines, it is possible to amplify the time difference between the two transit times by increasing the distance the ultrasonic pulse has to cross. This is done by making the pulse bounce one or more times on the pipe walls. Figure 5a shows a one traverse installation where the signal goes directly from one transducer to the other, Figure 5b shows a two traverses installation where the signal bounces once on the pipe walls before being detected, and finally, Figure 5c shows a four traverses installation where the signal bounce three times and the crossed distance is multiplied by four compared to a one traverse installation. 6 Festo Didactic

7 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion 45 (a) (b) (c) Figure 5. One, two, and four traverses. Characteristics of ultrasonic flowmeters Ultrasonic flowmeters are useful for clean water applications. They are particularly useful for applications where the flowmeter cannot come into contact with the process fluid, either because it is installed on an existing installation or because it can contaminate or disturb the process fluid. Advantages and limitations Below is a list of some of the advantages and limitations of time-transit flowmeters. Some of these advantages and limitations, but not all, also apply to Doppler flowmeters which also use ultrasound to measure flow rate. Can be used on large diameter pipes Cause no obstruction or pressure drop Not affected by changes in the liquid temperature, viscosity, density, or pressure Easy to install using clamp-on sensors Can be installed on an existing installation Can measure null, laminar, transitional, and turbulent flows Festo Didactic

8 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Can measure nonconductive fluids No moving parts Long operating life No risk of process contamination Work well for nonconductive fluids or ultra-pure water Notwithstanding these numerous advantages, ultrasonic flowmeters using the time-transit method have the following limitations and disadvantages: Subject to interference from the pipe wall Cannot be used for dirty or particulate-laden fluids Bubbles in the fluid or air between the fluid and the pipe wall affect accuracy and repeatability The fluid must be acoustically transparent The signal can be attenuated by concrete, fiberglass, or plastic-lined pipes Accuracy depends on the flow profile Expensive Can be used only in limited applications Build-up in pipes can cause reading errors Industrial applications The limitations of ultrasonic flowmeters restrict their use to a small range of applications. Nonetheless, they are extremely useful in this well-defined niche. Some of the applications where ultrasonic flowmeters are likely to be used are listed below: Clean fluid measurement (water, natural gas, liquefied gases) Clean water in water treatment plants Hot and cold water supply in commercial or public buildings Pure and ultra-pure water in semiconductor, pharmaceutical, and food industries Acid flow measurement in the chemical industry Acoustically transparent crude oil Cryogenic liquids Description of the supplied ultrasonic flowmeter The ultrasonic flow transmitter (Model 46927) is shown in Figure 6. It consists of a transmitter with two sensors that can be mounted on a transparent pipe using the preinstalled sensor holders affixed with tensioning bands. The transparent pipe is installed on a bracket for mounting on the process workstation, while the bracket of the transmitter allows it to be secured on the instrumentation mounting pipe. Table 1 describes the main components of the ultrasonic flow transmitter. 8 Festo Didactic

9 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Figure 6. Ultrasonic flow transmitter (Model 46927). Table 1. Components of the ultrasonic flow transmitter. Component Digital display Transmitter bracket Inlet Pipe Sensor holders Sensors Outlet Pipe bracket Description Displays the measured flow rate and other information related to the operation of the flowmeter. The protective cover can be removed to gain access to the control keys and manually control the device. Used to secure the transmitter to the instrumentation mounting pipe of the process workstation. Fluid must enter the flowmeter from this port. A DN 40 (NPS 1½) pipe on which the sensor holders are installed. Two sensor holders are installed on the pipe. The sensor holders are identified A and B. Two sensors identified A and B that must be secured in the corresponding holders. Fluid must exit the flowmeter from this port. Used to install the pipe/sensor assembly on the process workstation. Festo Didactic

10 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Fault panel Component 24 V dc input / Analog output Description Contains one switch used to simulate a fault with the apparatus. Power input for the flowmeter. Used to energize the ultrasonic flowmeter with a 24 V dc signal. The analog output provides a 4-20 ma signal proportional to the measured flow rate. A HART communication signal can be sent from the output. The display can be used to configure several parameters and to read the flow rate directly. The function of each button is described below: go backward in a menu or modify a value go forward in a menu or modify a value select an item from a menu or store an entry ESC press the + and buttons simultaneously to return to the previous menu or display Summary of technical specifications Some technical specifications are summarized in this section. For further details, please refer to the documentation provided with the system. Device name Prosonic 91 Measured variables Power supply Communication protocols Pipe diameter Measuring range Flow accuracy Flow velocity 24 V dc HART 3.8 cm (1.5 in) 0 m/s to 15 m/s (0 ft/s to 50 ft/s) ±2% of reading or ±7.5 mm/s (0.3 in/s) of maximum full scale value Temperature of the process -20 C to 80 C (-4 F to 176 F) Installing the ultrasonic flowmeter The ultrasonic flowmeter is heavy and bulky. Use proper techniques to lift it and request help whenever necessary. Always wear safety shoes when working with this equipment and make sure it is properly secured to the workstation. 10 Festo Didactic

11 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion The following equipment and tools are required to install the ultrasonic flowmeter on the instrumentation workstation: Ultrasonic flowmeter Spring nuts and bolts for fixation to the support strut Ratchet with a ½ in. socket or an equivalent wrench Mounting rail Adjustable wrench Screw driver Coupling fluid Installation procedure The ultrasonic flowmeter has two main components, the transmitter and the pipe/sensors assembly. The transmitter is designed to be installed on the instrumentation mounting pipe of the process workstation, while the pipe with the sensors must be installed horizontally on one of the struts of the process workstation. The ultrasonic flowmeter is a delicate instrument and it must be carefully installed as described in the procedure below. Even if the sensor holders are preinstalled, you may have to remove them for maintenance or pedagogical reasons. This procedure describes how to install the ultrasonic transmitter, including how to correctly install the sensor holders. 1. Secure the pipe bracket on the process workstation and the transmitter bracket on the instrumentation mounting pipe. 2. If the tensioning bands are not installed on the pipe, install them as shown in Figure 7 without tightening them. Figure 7. Install the tensioning bands. 3. Using a screw driver, tighten the tensioning band A, which is the closest to the inlet (Figure 8). Festo Didactic

12 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Figure 8. Tighten the tensioning band A. 4. Using the mounting rail, adjust the distance between the two tensioning bands so that one of the threaded studs is at position I and the other at position 27, as shown in Figure 9. Figure 9. Use position I27 on the mounting rail to adjust the distance. 5. Once the studs are correctly spaced, use a screw driver to tighten the second tensioning band. To ensure both studs are correctly spaced, do not remove the mounting rail before both tensioning bands are tightened. 6. Install the sensor holders on the pipe using the threaded studs. Tighten the nuts using an adjustable wrench as shown in Figure 10. Figure 10. Tighten the nuts. 12 Festo Didactic

13 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion 7. Once both sensor holders are installed, your setup should look as shown in Figure 11. Figure 11. Both sensor holders correctly installed. 8. Coat the surface of each of the sensor housings with approximately 0.5 mm (0.02 in) of coupling fluid as shown in Figure 12. Coat with coupling fluid Figure 12. Coat the surface of the sensor housings with coupling fluid. 9. Press each of the sensor housings into position until they are locked in their respective holders. You will hear a click (Figure 13). Figure 13. Press the sensor housings into position. 10. Once both sensor housings are installed, your setup should look as shown in Figure 14. Festo Didactic

14 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Discussion Figure 14. Installed sensor housings. 11. Insert each sensor cable into its housing. Make sure to insert the A cable into the housing installed on the holder labeled A on the pipe (Figure 15) and the B cable into the housing on the holder labeled B (Figure 16). Figure 15. Insert sensor cables. Figure 16. Insert the cables in the housings. 12. Once the sensor holders, the sensor housings, and the sensor cables are properly installed, the pipe with the installed components should look as shown in Figure Festo Didactic

15 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure Outline Figure 17. Sensors installed on the pipe. 13. The ultrasonic flow transmitter is now ready to be configured as described in the Procedure section below. Calibration The ultrasonic flowmeter is calibrated by the manufacturer at the factory and should not require further calibration. Nevertheless, some calibration parameters are available, but it is not recommended to modify any of them. Please refer to the manufacturer documentation for details. PROCEDURE OUTLINE The Procedure is divided into the following sections: Set up and connections Commissioning the ultrasonic flow transmitter Enabling programming mode (access code). Changing the transmitter units. Commissioning. Using the ultrasonic flow transmitter PROCEDURE Set up and connections 1. Connect the equipment according to the piping and instrumentation diagram (P&ID) shown in Figure 18 and use Figure 19 to position the equipment correctly on the frame of the training system. To set up your system for this exercise, start with the basic setup presented in the Familiarization with the Instrumentation and Process Control Training System manual and add the equipment listed in Table 2. Be sure to move the control valve to the left, just above the rotameter, to make space for the ultrasonic flow transmitter tube. Table 2. Material to add to the basic setup for this exercise. Name Model Identification Ultrasonic flow transmitter FIT 1 Accessories Festo Didactic

16 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure Calibrator (4-20 ma) Figure 18. P&ID. Figure 19. Setup. 16 Festo Didactic

17 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure 2. Connect the control valve to the pneumatic unit. Details about the installation and operation of the control valve are available in the Familiarization with the Instrumentation and Process Control Training System manual. 3. Connect the pneumatic unit to a dry-air source with an output pressure of at least 700 kpa (100 psi). 4. Wire the emergency push-button so that you can cut power in case of emergency. The Familiarization with the Instrumentation and Process Control Training System manual covers the security issues related to the use of electricity with the system as well as the wiring of the emergency push-button. 5. Do not power up the instrumentation workstation yet. You should not turn the electrical panel on before your instructor has validated your setup that is not before step Be sure to install the transmitter as shown in Figure 19 and connect it to a 24 V dc power outlet on the electrical unit. Use one of the direct outputs to keep the transmitter from shutting off in case the emergency push-button or the OFF button (S2) is used. 7. Before proceeding further, complete the following checklist to make sure you have set up the system properly. The points on this checklist are crucial elements for the proper completion of this exercise. This checklist is not exhaustive, so be sure to follow the instructions in the Familiarization with the Instrumentation and Process Control Training System manual as well. f The hand valves are in the positions shown in the P&ID. The valve at the suction of the pump (HV1) is set so that the flow is directed toward the pump inlet. The control valve is fully open. The pneumatic connections are correct. 8. Ask your instructor to check and approve your setup. 9. Make sure it is safe to energize the system for you and for the team working on the other side of the system, if any. When ready, turn on the main power by placing the safety switch in the ON position. Do not press the S1 button yet. The transmitter initializes and the remote display turns on after a few seconds. Festo Didactic

18 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure Commissioning the ultrasonic flow transmitter a Note: The following procedure assumes you are using the display to program the transmitter. If you want to configure your transmitter from a computer, you can do so by accessing the same menus and inputting the same values in the appropriate fields of the FieldCare software. Please refer to either the HART Device Configuration manual (P/N 86050) or the Foundation Fieldbus Device Configuration manual (P/N 86002) for more information on how to connect your transmitter to a computer. Enabling programming mode (access code) In many plant applications, it is crucial to the process that the settings of transmitters remain unchanged unless authorized. To avoid inadvertent changes to their settings, most devices provide the option of protecting their settings using a numerical code. The ultrasonic flow transmitter has such a protection system and requires that the user enter a numerical code to enable the programming mode. The programming mode is disabled automatically at boot or if no key has been pressed within 60 seconds. If the programming mode is disabled and you try to change a protected setting, the transmitter prompts you to enter the ACCESS CODE. ACCESS CODE *** 10. The default access code is 91. Use the + and buttons to select the digits, and the E button to confirm. This allows you to enter the code to enable the programming mode. You must input the symbol to conclude this step. ACCESS CODE 91 * 11. Once the correct access code is entered, the transmitter displays a message that indicates that the programming mode is enabled. PROGRAMMING ENABLED Changing the transmitter units 12. You may wish to change the default units used by the transmitter. To do so, press the E button to access the GROUP SELECT menu and use the + and buttons to select the SYSTEM UNITS function group. Press the E button once to access the group. 13. From the SYSTEM UNITS group, use the + and buttons to navigate through the available settings of each parameter. Press the E button to confirm each selection and go to the next parameter. Each time a parameter is set, the transmitter confirms the modification by displaying: ENTRY STORED. 18 Festo Didactic

19 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure 14. Once the units are configured, the transmitter displays SETUP COMPLETE. Press ESC to return to the main display. Commissioning 15. Before you can use the ultrasonic flow transmitter, several parameters must be configured correctly. The easiest way to configure the transmitter is via the SETUP function, which allows configuring most of the parameters that are mandatory for a successful setup. Press the E button to access the GROUP SELECT menu and use the + and buttons to select the SENSOR SETUP function group. Press the E button once to access the group. 16. From the SENSOR SETUP group, use the + and buttons to select the SETUP function. Press the E button once to access the function parameters. 17. The SETUP function consists of a series of parameters which must be set for the transmitter to work correctly. Use the + and buttons to navigate through the available settings of each parameter and set the parameter values as indicated in Table 3. Press the E button to confirm each selection and go to the next parameter. Each time a parameter is set, the transmitter confirms this by displaying: ENTRY STORED. Table 3. etup commissioning. Function Parameter value Description LIQUID WATER Sets the type of liquid in the pipe. TEMPERATURE SOUND VEL. LIQ. PIPE MATERIAL SOUND VELOCITY CIRCUMFERENCE PIPE DIAMETER C m/s PVC m/s mm mm Sets the process temperature of the liquid at normal operating conditions. Displays the speed of sound in the process liquid. The value of this parameter depends on the LIQUID and TEMPERATURE parameters. Sets the pipe material. The pipe provided with the ultrasonic flow transmitter, Model 46927, is made of PVC. Displays the speed of sound in the pipe wall. The value of this parameter depends on the PIPE MATERIAL parameter. Sets the pipe outer circumference. Either the pipe circumference or the pipe diameter must be specified. Changing the CIRCUMFERENCE parameter automatically modifies the PIPE DIAMETER parameter. Sets the pipe outer diameter. Either the pipe circumference or the pipe diameter must be specified. Changing the PIPE DIAMETER parameter automatically modifies the CIRCUMFERENCE parameter. WALL THICKNESS mm Sets the wall thickness of the pipe. Festo Didactic

20 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure Function Parameter value Description LINER MATERIAL SENSOR TYPE SENSOR CONFIG. CABLE LENGTH LINER NONE W-CL-2F-L-B 4 TRAVERSES LEN. 5m/15 feet Sets the liner material of the pipe. The pipe provided with the ultrasonic flow transmitter, Model 46927, has no liner. Sets the sensor type. The sensors of the ultrasonic flow transmitter, Model 46927, are W-CL-2F-L-B sensors. Sets the configuration of the sensors (i.e., the number of traverses). For small pipe diameters, such as the pipe provided with the ultrasonic flow transmitter, this parameter must be set to 4 traverses. Sets the length of the sensor cables. The sensor cables of the ultrasonic flow transmitter, Model 46927, are 5 m long (15 ft). POS. SENSOR I 27 Displays the position on the mounting rail that must be used to install the sensor on the pipe. SENSOR DISTANCE mm Displays the distance between the two sensors. 18. Once the setup commissioning is completed, the transmitter displays SETUP COMPLETE. Press ESC to return to the main display. 19. There is one last parameter that must be configured to make the transmitter operational, it is the FLOW DAMPING parameter. This parameter filters the noise in the process variable and prevents the transmitter output from varying erratically due to local perturbations in the flow rate. Essentially, the transmitter damping function acts as a low-pass filter allowing only the relevant information to go through while discarding noise. To access the FLOW DAMPING parameter, press the E button to access the GROUP SELECT menu and use the + and buttons to select the SYSTEM PARAMETER function group. Press the E button once to access the group. 20. Set the parameters of the SYSTEM PARAMETER group to the value given in Table 4. Table 4. System parameters. Function Parameter value Description INSTL. DIR. SENSOR MEASURING MODE POS. ZERO RETURN FORWARD STANDARD OFF Sets the positive flow direction. FORWARD is when the fluid flows from transducer A to transducer B and REVERSE is when the fluid flows from transducer B to transducer A. Sets the measuring mode for all outputs of the transmitter. When ON, this function set all functions and outputs to zero. 20 Festo Didactic

21 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Procedure Function Parameter value Description FLOW DAMPING 2.00 s Sets the damping value of the digital filter. 21. Once the parameters are set, the transmitter displays SETUP COMPLETE. Press ESC to return to the main display. Using the ultrasonic flow transmitter 22. Close HV Press the S2 button to power up the drive. Set the drive to 60 Hz. 24. Open HV2 and make sure the pipe of the ultrasonic flow transmitter is completely filled with water. 25. Using HV2, reduce the flow rate until the reading is 4 L/min (1 gal/min) on the rotameter. Wait until the transmitter displays the flow rate. If the transmitter displays an error code, refer to Appendix B to troubleshoot your transmitter. 26. Record in Table 5 the measurements of the ultrasonic flow transmitter. Table 5. Ultrasonic flowmeter and rotameter flow rate readings. Flow rate (Rotameter) L/min (gal/min) 4 (1) 8 (2) 12 (3) 16 (4) 20 (5) 24 (6) 28 (7) 32 (8) 36 (9) 40 (10) Flow rate (Ultrasonic TX) L/min (gal/min) 27. Use the ball valve HV2 to increase the flow rate (as read on the rotameter) in steps of 4 L/min (or 1 gal/min) until you reach 30 L/min (8 gal/min). For each flow rate, record in Table 5 the flow rate measured by the ultrasonic flow transmitter. Stop the drive once the table is filled. Festo Didactic

22 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Conclusion 28. Compare the flow rate values obtained with the ultrasonic flow transmitter to the flow rate readings on the rotameter. How good is the agreement between the two? Which one would you say is the most precise? 29. Turn off the electrical unit on the instrumentation station and store the equipment appropriately. Make sure the station is clean and in a proper state for its next use. CONCLUSION In this exercise, you have learned how to commission an ultrasonic flow transmitter for use on the Instrumentation and Process Control system. You learned the basic principles of ultrasonic flow measurement and how they are used to infer the flow rate. REVIEW QUESTIONS 1. Name the two measurement methods commonly used to measure flow rate using ultrasound. 2. For an ultrasonic flow transmitter, why are the upstream and downstream traveling times of the ultrasonic pulse not the same? 3. What is a Reynolds-number correction mechanism used for in an ultrasonic flow transmitter? 4. Why is increasing the number of traverses useful in some circumstances? 22 Festo Didactic

23 Exercise 1 Fundamentals of the Ultrasonic Flowmeter Review Questions 5. Name three advantages and three limitations of ultrasonic flow transmitters. Festo Didactic

Familiarize yourself with the pressure loss phenomenon. The Discussion of this exercise covers the following point:

Familiarize yourself with the pressure loss phenomenon. The Discussion of this exercise covers the following point: Exercise 3-2 Pressure Loss EXERCISE OBJECTIVE Familiarize yourself with the pressure loss phenomenon. DISCUSSION OUTLINE The Discussion of this exercise covers the following point: Pressure loss Major

More information

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work?

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work? Exercise 4-1 Flowmeters EXERCISE OBJECTIVE Learn the basics of differential pressure flowmeters via the use of a Venturi tube and learn how to safely connect (and disconnect) a differential pressure flowmeter

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 2 Float Switch EXERCISE OBJECTIVE Learn the working principle of float switches and how to use the float switch, Model 46935. DISCUSSION OUTLINE The Discussion of this exercise covers the following

More information

Basic Thermal Energy Transfer with a Heat Exchanger

Basic Thermal Energy Transfer with a Heat Exchanger Exercise 4-1 Basic Thermal Energy Transfer with a Heat Exchanger EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the basic principles of operation of a typical heat

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-3 Venturi Tubes EXERCISE OBJECTIVE In this exercise, you will study the relationship between the flow rate and the pressure drop produced by a venturi tube. You will describe the behavior of

More information

ULTRAFLO 2000 ULTRASONIC LIQUID FLOW AND HEAT/ENERGY METERS FOR PERMANENT INSTALLATION HIGH TEMPERATURE SENSORS AS STANDARD

ULTRAFLO 2000 ULTRASONIC LIQUID FLOW AND HEAT/ENERGY METERS FOR PERMANENT INSTALLATION HIGH TEMPERATURE SENSORS AS STANDARD ULTRASONIC LIQUID FLOW AND HEAT/ENERGY METERS HIGH TEMPERATURE SENSORS AS STANDARD FOR PERMANENT INSTALLATION ULTRASONIC LIQUID FLOW AND HEAT/ENERGY METERS The Ultraflo 2000 is a Transit Time ultrasonic

More information

The Discussion of this exercise covers the following points: Centrifugal pumps in series Centrifugal pumps in parallel. Centrifugal pumps in series

The Discussion of this exercise covers the following points: Centrifugal pumps in series Centrifugal pumps in parallel. Centrifugal pumps in series Exercise 2-4 Centrifugal Pumps in Series and in Parallel (Optional Exercise) EXERCISE OBJECTIVE In this exercise, you will observe the effects that connecting two centrifugal pumps in series or parallel

More information

Portable Transit Time Flow Meter for Accurate Flow Measurement from Outside a Pipe

Portable Transit Time Flow Meter for Accurate Flow Measurement from Outside a Pipe Portable Transit Time Flow Meter for Accurate Flow Measurement from Outside a Pipe Portable Ultrasonic Flowmeters Models PT400 & PT500 Measure Flow of Clean Fluids in Full Pipes with Non-contacting Ultrasonic

More information

FUNDAMENTALS OF INSERTION TURBINE METERS Les Bottoms Thermo Electron Corporation, Flow Systems

FUNDAMENTALS OF INSERTION TURBINE METERS Les Bottoms Thermo Electron Corporation, Flow Systems FUNDAMENTALS OF INSERTION TURBINE METERS Les Bottoms Thermo Electron Corporation, Flow Systems 9303 W. Sam Houston Parkway, Houston, TX 77099 INTRODUCTION The insertion turbine meter is well suited for

More information

Proline Prosonic Flow 93T Portable

Proline Prosonic Flow 93T Portable Brief Operating Instructions Portable ultrasonic flow measuring system These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply. Detailed

More information

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit Exercise 3-1 Basic Hydraulic Circuit EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the hydraulic schematic and components of the nacelle trainer. You will identify

More information

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit Exercise 3-1 Basic Hydraulic Circuit EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the hydraulic schematic and components of the nacelle trainer. You will identify

More information

EASZ-10P Operating Instructions

EASZ-10P Operating Instructions 219 East Main Street Mechanicsburg, PA, USA 17055 Toll Free: 866-EESIFLO Fax: (717) 697-2122 EASZ-10P Operating Instructions Introduction... 2 Sensor Mounting... 2 Keypad.. 4 Battery... 4 Menu System.

More information

Exercise 2-1. Hub and Low-Speed Shaft EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Blade pitch in the nacelle system

Exercise 2-1. Hub and Low-Speed Shaft EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Blade pitch in the nacelle system Exercise 2-1 Hub and Low-Speed Shaft EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the portion of the nacelle that extracts mechanical power from the wind and transfers

More information

Fundamental Training. Flow Con t

Fundamental Training. Flow Con t Fundamental Training Flow Con t 1 Contents Topics: Slide No: Velocity flow meters 3-11 Mass flow meters 12-17 Displacement meters 18 Exercise 19-20 2 Velocity Meter Magnetic Flowmeter Faraday s Law of

More information

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 2900 MIXER TO BE USED BY CNRL FOR BITUMEN VISCOSITY CONTROL Report R0. By Kimbal A.

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 2900 MIXER TO BE USED BY CNRL FOR BITUMEN VISCOSITY CONTROL Report R0. By Kimbal A. COMPUTATIONAL FLOW MODEL OF WESTFALL'S 2900 MIXER TO BE USED BY CNRL FOR BITUMEN VISCOSITY CONTROL Report 412509-1R0 By Kimbal A. Hall, PE Submitted to: WESTFALL MANUFACTURING COMPANY May 2012 ALDEN RESEARCH

More information

Portable Ultrasonic Flow Measuring System prosonic flow 92

Portable Ultrasonic Flow Measuring System prosonic flow 92 Technical Information TI 060D/24/ae Portable Ultrasonic Flow Measuring System prosonic flow 92 Temporary volume flow measurement of liquids with Clamp On sensors Features and benefits Portable transmitter,

More information

INDEX. Introduction. Introduction. Sensor Mounting. Keypad System. Battery. Menu System. Error/Warning Messages. Troubleshooting guide

INDEX. Introduction. Introduction. Sensor Mounting. Keypad System. Battery. Menu System. Error/Warning Messages. Troubleshooting guide Measuring Flow Worldwide INDEX Introduction Sensor Mounting Keypad System Battery Menu System Error/Warning Messages Troubleshooting guide Questions and Answers Introduction The EASZ-10P Flow Meter measures

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 1 Battery Fundamentals EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with various types of lead-acid batteries and their features. DISCUSSION OUTLINE The Discussion

More information

Permanent Multipath Clamp-On Transit Time Flow Meter

Permanent Multipath Clamp-On Transit Time Flow Meter Permanent Multipath Clamp-On Transit Time Flow Meter By: Dr. J. Skripalle HydroVision GmbH, Germany Introduction For many years now, ultrasonic flow measurements with wetted sensors have been a well established

More information

Vantage 6000 Portable Ultrasonic Flow Meter

Vantage 6000 Portable Ultrasonic Flow Meter Vantage 6000 Portable Ultrasonic Flow Meter Instruction Manual Eastech Badger Flow Technology Group 4250 S. 76 th East Ave. Tulsa OK 74145 800-226-3569 Description The Vantage 6000 portable transit time

More information

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring.

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring. Test 1 1. Which statement is True? A. Pneumatic systems are more suitable than hydraulic systems to drive powerful machines. B. Mechanical systems transfer energy for longer distances than hydraulic systems.

More information

Fluid Flow Conditioning

Fluid Flow Conditioning Fluid Flow Conditioning March 2014 Flow Conditioning There is no flow meter on the market that needs flow conditioning. All flow meters are effective without any type of flow conditioning. 1 Flow Conditioning

More information

Lower maintenance costs: with no moving parts, there is nothing on the DFX to wear down. Wide measuring range: 0.15 to 30 FPS (0.05 to 9 MPS).

Lower maintenance costs: with no moving parts, there is nothing on the DFX to wear down. Wide measuring range: 0.15 to 30 FPS (0.05 to 9 MPS). PRODUCT APPLICATIONS / APPLICATION QUALIFICATION DIMENSIONAL SPECIFICATIONS MECHANICAL DIMENSIONS: INCHES (mm) DOPPLER ULTRASONIC FLOW METER Carbonated liquids Mining slurry Drilling mud Coal-seam water

More information

Model DFX Doppler ultrasonic flow meter

Model DFX Doppler ultrasonic flow meter Badger Meter Europa GmbH Nürtinger Str. 76 72639 Neuffen (Germany) Tel. +49-7025-9208-0 Fax +49-7025-9208-15 www.badgermeter.de badger@badgermeter.de Model DFX Doppler ultrasonic flow meter Features Badger

More information

Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters

Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters 8000A/8300/9300A/9100A/9200A SERIES S Perfect for municipal water & wastewater applications 1.6 to 900 mm (1/16 to 36

More information

DYNAMETERS SERIES DMTF ULTRASONIC FLOW METER

DYNAMETERS SERIES DMTF ULTRASONIC FLOW METER DYNAMETERS SERIES DMTF ULTRASONIC FLOW METER Advanced Clamp-on Transit-time Ultrasonic Flow meter for Accurate Flow Measurement Features: Cost effective and versatile High accuracy, better than ±1.0% read

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-2 Hydraulic Brakes EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the hydraulic circuits of the yaw and the rotor brakes. You will control brakes by changing

More information

Vortex Eggs Delta Flowmeter

Vortex Eggs Delta Flowmeter Product Data Sheet PDS-FLM Vortex Eggs Delta Flowmeter Technical Specifications (Liquid, Gas & Air) Easy to read Free positioning EEPROM DESCRIPTION The unique sensor body and transmitter design makes

More information

Model TUR-200D Turbine Flowmeter

Model TUR-200D Turbine Flowmeter General Specifications Model TUR-200D Turbine Flowmeter Liquid flows through the turbine housing causing an internal rotor to spin. As the rotor spins, an electrical signal is generated in the pickup coil.

More information

TABLE OF CONTENTS Service Information 2 Quick Start Instructions 4-5 Introduction 6 Specifications 6 Controls and Terminology

TABLE OF CONTENTS Service Information 2 Quick Start Instructions 4-5 Introduction 6 Specifications 6 Controls and Terminology 1 2 TABLE OF CONTENTS Service Information... 2 Quick Start Instructions... 4-5 Introduction... 6 Specifications... 6 Controls and Terminology... 7 Transducer Mounting Locations... 8 Mounting the Transducer...

More information

Inline Ultrasonic Flowmeter

Inline Ultrasonic Flowmeter M-1500 Series Installation and Operating Manual The M-1500 series is an inline primary flow sensor and externally mounted controller unit. The flow sensor is a straight through flow tube that uses Transit

More information

Range of Ultrasonic Flowmeters.

Range of Ultrasonic Flowmeters. Range of Ultrasonic Flowmeters www.adeptfluidyne.com Ultrasonic Flowmeter Series 6700 Working Principle The Transit Time Flowmeter utilises two transducers that function as both, ultrasonic transmitters

More information

PRODUCT REQUIREMENTS

PRODUCT REQUIREMENTS Model 622 Technical Specifications Page 1 of 6 GAS TURBINE AND JET ENGINE COMPONENT TESTING Mass Airflow Test Stand Model 622 Automatic Airflow Test Stand Dimensions: 67" H x 57" W x 42" D 1702mm H x 1448mm

More information

Flow Measurement SITRANS F S Clamp-on

Flow Measurement SITRANS F S Clamp-on Function Operating Principle The SITRANS F S system is a transit-time ultrasonic meter that provides exceptional performance using a non-intrusive clampon approach. Ultrasonic sensors transmit and receive

More information

Sentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter

Sentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter GE Measurement & Control Sentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter Applications The Sentinel flowmeter is a complete ultrasonic flowmeter system for the measurement of natural gas

More information

tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement

tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement Sensing the pulse of industry tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement tekflo sensors are proud to present their tekson TS Series ultrasonic water energy meter, which uniquely

More information

Exercise 7. Thyristor Three-Phase Rectifier/Inverter EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Thyristor three-phase rectifier/inverter

Exercise 7. Thyristor Three-Phase Rectifier/Inverter EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Thyristor three-phase rectifier/inverter Exercise 7 Thyristor Three-Phase Rectifier/Inverter EXERCISE OBJECTIVE When you have completed this exercise, you will know what a thyristor threephase rectifier/limiter (thyristor three-phase bridge)

More information

UL6300 SONICMAX. Ultrasonic Clamp-on Flowmeter OUTLINE FEATURES STANDARD SPECIFICATION. Common specification

UL6300 SONICMAX. Ultrasonic Clamp-on Flowmeter OUTLINE FEATURES STANDARD SPECIFICATION. Common specification SONICMAX UL63 Ultrasonic Clamp-on Flowmeter OUTLINE SONICMAX UL63 is the ultrasonic flowmeter of the time flight system which combined the highly efficient converter (UFC3) with the clamp-on sensor (UFS6).

More information

PORTAGAUGE 4 USER MANUAL

PORTAGAUGE 4 USER MANUAL PORTAGAUGE 4 USER MANUAL Contents 1. Introduction and Key Features 1.1 What does the Portagauge do? 1.2 The Portagauge 4 1.21 The Portagauge 4 Unit and Measuring Screen 1.22 The Portagauge 4 Definition

More information

Sentinel. Panametrics Custody Transfer Gas Ultrasonic Flowmeter. GE Sensing. Applications. Features

Sentinel. Panametrics Custody Transfer Gas Ultrasonic Flowmeter. GE Sensing. Applications. Features Applications The Sentinel flowmeter is a complete ultrasonic flowmeter system for the measurement of natural gas flow applications such as: Custody transfer Transmission and distribution Underground storage

More information

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF VERSION UF-5xx d INSTALLATION MANUAL ISO 9001:2008 CONTENTS Page INTRODUCTION... 3 1. SAFETY INSTRUCTIONS... 4 2. MOUNTING PREPARATION... 4 3. MOUNTING REQUIREMENTS...

More information

Instruction Manual. DMF-1-Series Coriolis Mass Flow Meter

Instruction Manual. DMF-1-Series Coriolis Mass Flow Meter 1 京制 01050054 号 Instruction Manual DMF-1-Series Coriolis Mass Flow Meter Beijing Sincerity Automatic Equipment Co., LTD Tel: +86(010)52073959/ 52073956 18600270515 2 NOTICE We thank you very much for your

More information

Exercise 2. Discharge Characteristics EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Cutoff voltage versus discharge rate

Exercise 2. Discharge Characteristics EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Cutoff voltage versus discharge rate Exercise 2 Discharge Characteristics EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the discharge characteristics of lead-acid batteries. DISCUSSION OUTLINE The Discussion

More information

Exercise 2-1. The Separately-Excited DC Motor N S EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Simplified equivalent circuit of a dc motor

Exercise 2-1. The Separately-Excited DC Motor N S EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Simplified equivalent circuit of a dc motor Exercise 2-1 The Separately-Excited DC Motor EXERCISE OBJECTIVE When you have completed this exercise, you will be able to demonstrate the main operating characteristics of a separately-excited dc motor

More information

Proline Prosonic Flow 91W

Proline Prosonic Flow 91W Brief Operating Instructions Proline Prosonic Flow 91W Ultrasonic flow measuring system 6 These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope

More information

Proving Liquid Ultrasonic Flowmeters Summary of Testing Conducted January 2011

Proving Liquid Ultrasonic Flowmeters Summary of Testing Conducted January 2011 M E A S U R E M E N T S Y S T E M S Technical Paper No. 162 Rev. 0 Proving Liquid Ultrasonic Flowmeters Summary of Testing Conducted January 2011 LEFM 280CiRN Measurement Systems Introduction Proving Liquid

More information

SITRANS F flowmeters SITRANS F US. SITRANS FUT1010 Ultrasonic flowmeter. Overview. Application

SITRANS F flowmeters SITRANS F US. SITRANS FUT1010 Ultrasonic flowmeter. Overview. Application Overview SITRANS F flowmeters Application Liquid applications Gas applications Pipelines Custody transfer, allocation, Upstream Production wells, line balance, gathering, separation interface/densitometer

More information

Permanent Magnet DC Motor Operating as a Generator

Permanent Magnet DC Motor Operating as a Generator Exercise 2 Permanent Magnet DC Motor Operating as a Generator EXERCIE OBJECTIVE When you have completed this exercise, you will be familiar with the construction of permanent magnet dc motors as well as

More information

Basic voltmeter use. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Basic voltmeter use. Resources and methods for learning about these subjects (list a few here, in preparation for your research): Basic voltmeter use This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

FH8500. Metering Solution for Custody Transfer Applications. One Step Ahead in Ultrasonic Flowmetering. Main Applications

FH8500. Metering Solution for Custody Transfer Applications. One Step Ahead in Ultrasonic Flowmetering. Main Applications FH85 Metering Solution for Custody Transfer Applications One Step Ahead in Ultrasonic Flowmetering Main Applications Oil Production & Allocation FSO, FPSO Metering Tanker Off-loading Storage Management

More information

TEK-F LUX 1400A. Electromagnetic Flowmeter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys FLOW

TEK-F LUX 1400A. Electromagnetic Flowmeter.  Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys FLOW Technology Solutions TEK-F LUX 1400A Electromagnetic Flowmeter FLOW www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Electromagnetic flowmeters are also

More information

Coriolis Density Error Compensating for Ambient Temperature Effects

Coriolis Density Error Compensating for Ambient Temperature Effects Coriolis Density Error Compensating for Ambient Temperature Effects Presented by Gordon Lindsay Oil & Gas Focus Group December 2018 Contents Project aims and objectives Experiment Setup Phase 1 Exploratory

More information

Exercise 3. Battery Charging Fundamentals EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Charging fundamentals

Exercise 3. Battery Charging Fundamentals EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Charging fundamentals Exercise 3 Battery Charging Fundamentals EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the effects of charge input, charge rate, and ambient temperature on the voltage

More information

Ultrasonic Flowmeter. M-1500 Plus Non-invasive Inline DSP Ultrasonic Flowmeter. Operating Principle. Features

Ultrasonic Flowmeter. M-1500 Plus Non-invasive Inline DSP Ultrasonic Flowmeter. Operating Principle. Features M1500 Plus Noninvasive Inline DSP Ultrasonic Flowmeter Accuracy ± 2% of Reading All wetted parts made of PFA Contamination free from ions or particles Minute flow measurements down to 4 ml/min* Easy configuration

More information

White paper: Originally published in ISA InTech Magazine Page 1

White paper: Originally published in ISA InTech Magazine Page 1 Page 1 Improving Differential Pressure Diaphragm Seal System Performance and Installed Cost Tuned-Systems ; Deliver the Best Practice Diaphragm Seal Installation To Compensate Errors Caused by Temperature

More information

Flowmeter Ultrasonic Flow Metering / Dosing Device. Operating Manual

Flowmeter Ultrasonic Flow Metering / Dosing Device. Operating Manual Flowmeter Ultrasonic Flow Metering / Dosing Device Operating Manual Read the user's manual carefully before starting to use the unit or software. Producer reserves the right to implement changes without

More information

Electromagnetic flowmeter EMKO E

Electromagnetic flowmeter EMKO E Electromagnetic flowmeter EMKO E - Quality design - High corrosion resistance - Reliable measurement principle Doc. no.: 70, en_cat_emkoe, 8/2015 Description Electromagnetic Flowmeter EMKO E consists of

More information

Experiment (4): Flow measurement

Experiment (4): Flow measurement Introduction: The flow measuring apparatus is used to familiarize the students with typical methods of flow measurement of an incompressible fluid and, at the same time demonstrate applications of the

More information

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter Warranty Agreement J-TEC Associates warrants this product to be in good working order for a period of

More information

USER'S GUIDE and Spare Parts Drawings GENERIC APPLICATIONS

USER'S GUIDE and Spare Parts Drawings GENERIC APPLICATIONS Super ELF-X2 USER'S GUIDE and Spare Parts Drawings GENERIC APPLICATIONS SUPER ELF X2 WARNING! - Condensation could form on the Weft Feeder when it is moved from the cold environment of the warehouse to

More information

Paddle-wheel flow controller with optical principle for On/Off control

Paddle-wheel flow controller with optical principle for On/Off control Paddle-wheel flow controller with optical principle for On/Off control Type 8039 can be combined with... Indication, monitoring, transmitting and On/Off control in one device. Programmable s (transistor

More information

Measurement Products Measurement made easy. Swirl flowmeters FS4000 Simply fitting your purpose Application guide

Measurement Products Measurement made easy. Swirl flowmeters FS4000 Simply fitting your purpose Application guide Measurement Products Measurement made easy Swirl flowmeters FS4000 Simply fitting your purpose Application guide Swirl flowmeters Serving your application Exceeding your expectations about modern field

More information

Minimizing Noise. Marybeth G. Nored Dr. Klaus Brun Eugene Buddy Broerman Augusto Garcia Hernandez Dennis Tweten. Southwest Research Institute

Minimizing Noise. Marybeth G. Nored Dr. Klaus Brun Eugene Buddy Broerman Augusto Garcia Hernandez Dennis Tweten. Southwest Research Institute Minimizing Noise Marybeth G. Nored Dr. Klaus Brun Eugene Buddy Broerman Augusto Garcia Hernandez Dennis Tweten Southwest Research Institute Gas Electric Partnership Workshop September 9, 2010 Photo courtesy

More information

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control. Benefits.

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control. Benefits. GE Measurement & Control Sentinel LCT Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement Benefits Extremely reliable and highly accurate flowmeter, designed specifically for custody

More information

The EPSILON is based on the principle of measuring velocity in the pipe line, therefore the flow measurement is volumetric.

The EPSILON is based on the principle of measuring velocity in the pipe line, therefore the flow measurement is volumetric. Typical Applications EPSILON Flowmeter The EPSILON flow meters measure the flow of most liquids and gases within the process industries, including chemical, petro-chemical, pharmaceutical and the power

More information

Paddle-wheel flow controller for On/Off control

Paddle-wheel flow controller for On/Off control Paddle-wheel flow controller for On/Off control Type 803 can be combined with... Indication, monitoring, transmitting and On/Off control in one device Programmable s (transistor or relay) Automatic-calibration:

More information

PRODUCT REQUIREMENTS

PRODUCT REQUIREMENTS Model 644 Technical Specifications Page 1 of 9 GAS TURBINE AND JET ENGINE COMPONENT TESTING Mass Airflow Test Stand PRODUCT REQUIREMENTS Multiple manufacturers in the Aerospace industry required Airflow

More information

Application Note Original Instructions Development of Gas Fuel Control Systems for Dry Low NOx (DLN) Aero-Derivative Gas Turbines

Application Note Original Instructions Development of Gas Fuel Control Systems for Dry Low NOx (DLN) Aero-Derivative Gas Turbines Application Note 83404 Original Instructions Development of Gas Fuel Control Systems for Dry Low NOx (DLN) Aero-Derivative Gas Turbines Woodward reserves the right to update any portion of this publication

More information

NCM-603 Hand Held Clamp-on Ultrasonic Transit Time Flowmeter

NCM-603 Hand Held Clamp-on Ultrasonic Transit Time Flowmeter NCM-603 Hand Held Clamp-on Ultrasonic Transit Time Flowmeter Quick Start - Operation Manual Rev 10.01.08 This Quick Start is provided solely to help you get the flowmeter up and running as quickly as possible.

More information

Time Delta S Fixed Transit-Time Flow Meter System

Time Delta S Fixed Transit-Time Flow Meter System Fixed Transit-Time Flow Meter System Key Features Dynamic flow correction Simple configuration Digital outputs Enhanced anti-bubble measurement technology (ABM) Rugged and reliable Maintenance free The

More information

Ultrasonic Flowmeters

Ultrasonic Flowmeters Ultrasonic Flowmeters For Liquids and for Air From Air to Oil Reliable Flow Measurement 21A1-E-0006a Innovative Solutions for Various Applications Spool Piece Ultrasonic Flowmeter for Liquids High accuracy:

More information

Ultrasonic Flow Meter Series Smart-IN US. Features. Description

Ultrasonic Flow Meter Series Smart-IN US. Features. Description Features Series 7200 is single-board, self-contained and state-of -the-art ultrasonic flow meter. It has the notable characteristics of high precision, high reliability, high performance, low price etc..

More information

Electromagnetic flowmeters Series FLOMID Electromagnetic flowmeter for conductive liquids

Electromagnetic flowmeters Series FLOMID Electromagnetic flowmeter for conductive liquids Electromagnetic flowmeters Series FLOMID Electromagnetic flowmeter for conductive liquids Flow rate measurement is independent of density, temperature, viscosity and pressure Pulsed coil excitation to

More information

Liquid Turbine Flow Meter OwnerÊs Manual

Liquid Turbine Flow Meter OwnerÊs Manual Liquid Turbine Flow Meter OwnerÊs Manual Manual LWGY-G Rev.1.0 Content 1.0 GENERAL INFORMATION... 1 2.0 SPECIFICATIONS... 2 3.0 OPERATION CONDITIONS... 3 4.0 CAUTIONS FOR INSTALLATION... 4 5.0 DIMENSION...

More information

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control Exercise 6 Three-Phase AC Power Control EXERCISE OBJECTIVE When you have completed this exercise, you will know how to perform ac power control in three-phase ac circuits, using thyristors. You will know

More information

Special edition paper

Special edition paper Countermeasures of Noise Reduction for Shinkansen Electric-Current Collecting System and Lower Parts of Cars Kaoru Murata*, Toshikazu Sato* and Koichi Sasaki* Shinkansen noise can be broadly classified

More information

STEEMCO-MAS Flowmeter for Steam

STEEMCO-MAS Flowmeter for Steam STEEMCO-MAS Flowmeter for Steam Typical Applications The STEEMCO-MAS flow meters measure the mass flow of superheated steam within the process industries, including chemical, petro-chemical, pharmaceutical

More information

PORTAFLOW SE ULTRASONIC FLOWMETER MANUAL

PORTAFLOW SE ULTRASONIC FLOWMETER MANUAL PORTAFLOW SE ULTRASONIC FLOWMETER MANUAL Micronics Ltd, Knaves Beech Business Centre, Davies Way, Loudwater, High Wycombe, Bucks HP10 9QR. Tel: 01628 810456 Fax: 01628 531540 e-mail: sales@micronicsltd.co.uk

More information

VersaFlow Vortex 100 Vortex Flow Meter Specifications

VersaFlow Vortex 100 Vortex Flow Meter Specifications VersaFlow Vortex 100 Vortex Flow Meter Specifications 34-VF-03-05 May 2011 The All-In-One Solution The VERSAFLOW is the only vortex flowmeter with integrated and temperature compensation in 2- wire technology.

More information

USER S GUIDE. Installation & Operation Instructions. PORTAFLOW SE Ultrasonic Transit Time Flow Meter

USER S GUIDE. Installation & Operation Instructions. PORTAFLOW SE Ultrasonic Transit Time Flow Meter USER S GUIDE Installation & Operation Instructions PORTAFLOW SE Ultrasonic Transit Time Flow Meter 1 CONTENTS PAGE No. PAGE No. Introduction 3 Status, Error and Warning Messages 19 Fast Track Set up Procedure

More information

Constant Known Conductivity Fuel Systems. & how they assist fuel conductivity management

Constant Known Conductivity Fuel Systems. & how they assist fuel conductivity management Constant Known Conductivity Fuel Systems & how they assist fuel conductivity management Background JF-1A in-line conductivity sensor is designed to provide high-accuracy, continuous measurement of conductivity

More information

better measurement Simply a question of

better measurement Simply a question of Simply a question of better measurement SCHMIDT Flow Sensor SS 2.415 and SS 2.515 The tried and tested measurement experts for the monitoring of laminar flows extremely precise and quickly installed Industrial

More information

Ex. 1-1 Nacelle Familiarization and Safety Discussion

Ex. 1-1 Nacelle Familiarization and Safety Discussion Exercise 1-1 Nacelle Familiarization and Safety EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with key components and safety aspects of the nacelle trainer. You will be

More information

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T KROHNE 10/2001 7.02313.23.00 GR/OP Vortex Flowmeters F-T W-T Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters Level measuring

More information

Automated Seat Belt Switch Defect Detector

Automated Seat Belt Switch Defect Detector pp. 10-16 Krishi Sanskriti Publications http://www.krishisanskriti.org/publication.html Automated Seat Belt Switch Defect Detector Department of Electrical and Computer Engineering, Sri Lanka Institute

More information

KL-8070D. Fully Digital Stepping Driver. Table of Contents 1. Introduction, Features and Applications...1 Introduction...1 Features...

KL-8070D. Fully Digital Stepping Driver. Table of Contents 1. Introduction, Features and Applications...1 Introduction...1 Features... Contents KL-8070D Fully Digital Stepping Driver Attention: Please read this manual carefully before using the driver! I Table of Contents 1. Introduction, Features and Applications...1 Introduction......1

More information

Paddle-wheel flow controller for On/Off control

Paddle-wheel flow controller for On/Off control Paddle-wheel flow controller for On/Off control Type 8032 can be combined with... Indication, monitoring, transmitting and On/Off control in one device Programmable outputs (transistor or relay) Automatic-calibration:

More information

Spray Height Controller

Spray Height Controller Spray Height Controller UC5 SERVICE MANUAL AGCO North America Printed in Canada Copyright 2013 by NORAC Systems International Inc. Reorder P/N: UC5 SERVICE MANUAL AGCO NA Rev A NOTICE: NORAC Systems International

More information

M-2800 Series. Inline Ultrasonic Flow Meter. Description. Measurement Principle. Key Features. Applications

M-2800 Series. Inline Ultrasonic Flow Meter. Description. Measurement Principle. Key Features. Applications M2800 Series Inline Ultrasonic Flow Meter Description The M2800 consists of an inline flow sensor and electronics in one package. The flow sensor is a straightthrough PFA tube with a pair of assemblies

More information

9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER

9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER Design Specifications DS-9900 Revision 04 9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER 2-Wire loop powered flowmeter/transmitter 316 Stainless steel measuring unit Automatic temperature

More information

LCMass Series Mass Flow Sensor

LCMass Series Mass Flow Sensor LCMass 100-140 Series Mass Flow Sensor Technical Data Sheet HIGH ACCURACY The LCMass 100 achieves a ±0.15% accuracy on liquids. COMPACT ECONOMIC DESIGN Straight twin-tube design allows for an overall smaller

More information

(Refer Slide Time: 1:13)

(Refer Slide Time: 1:13) Fluid Dynamics And Turbo Machines. Professor Dr Dhiman Chatterjee. Department Of Mechanical Engineering. Indian Institute Of Technology Madras. Part A. Module-2. Lecture-2. Turbomachines: Definition and

More information

Chapter 13: Application of Proportional Flow Control

Chapter 13: Application of Proportional Flow Control Chapter 13: Application of Proportional Flow Control Objectives The objectives for this chapter are as follows: Review the benefits of compensation. Learn about the cost to add compensation to a hydraulic

More information

Condensed Version of Operator s Manual For The VL600 Series Flowmeters

Condensed Version of Operator s Manual For The VL600 Series Flowmeters Condensed Version of Operator s Manual For The VL600 Series Flowmeters Warranty Agreement JTEC Associates warrants this product to be in good working order for a period of twelve (12) months from installation.

More information

Module 13 Rate-controller functions and settings Getting the best out of the functions available

Module 13 Rate-controller functions and settings Getting the best out of the functions available SPRAY APPLICATION MANUAL FOR GRAIN GROWERS Module 13 Rate-controller functions and settings Getting the best out of the functions available Graham Betts and Bill Gordon PAGE 2 Key points A rate controller

More information

INSERTION flowmeter with paddle wheel, ELEMENT design

INSERTION flowmeter with paddle wheel, ELEMENT design INSERTION flowmeter with paddle wheel, design Up to PN, size of measurement pipes: DN to DN400 Configurable outputs: one or two transistor output(s) and single or dual 4... ma analog output(s) Removable

More information

INSERTION flow sensor for continuous flow measurement

INSERTION flow sensor for continuous flow measurement INSERTION flow sensor for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN)

More information

Hydraulic Proportional and Closed Loop System Design

Hydraulic Proportional and Closed Loop System Design Hydraulic Proportional and Closed Loop System Design Neal Hanson Product Manager Industrial Valves and Electrohydraulics 1 Electrohydraulics Contents 1. Electrohydraulic Principles 2. Proportional Valve

More information

Radiant High Voltage. Displacement Measurement Fixture. Construction. Introduction. Figure 1

Radiant High Voltage. Displacement Measurement Fixture. Construction. Introduction. Figure 1 Radiant High Voltage Displacement Measurement Fixture Introduction Radiant Technologies, Inc. offers four types of high voltage test fixtures. One, the High Voltage Test Fixture (HVTF), has been very popular

More information