Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

Size: px
Start display at page:

Download "Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No."

Transcription

1 Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB

2 General Description The PCM is part of Paragon Compressor control packages 6BSB and 6BSB Besides this Application Guide, the following manuals, I/O Zone Installation Guide and I/O Zone Integration Guide are necessary for proper installation and Network Protocol configuration. PCM Configuration 2

3 Compressor Protection See Table A & B for Tm control points. See Table A & B for Td control points. Run Recognition Signal The Slide Valve and Compressor Protection functionality are not active until the PCM receives the Run Recognition signal from the System Controller. LED Fault Indication Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Table C 3

4 Slide Valve Control: LED Indicators are provided in the PCM Controller Kit. Install labels next to each LED light identifying the indication. The end user will have to configure the PCM in the following way: PressureTemperature Physical InputNetwork Input See Table/Chart D & E Logic 1.) UpperDB-1 UpperDB-2. Upper DB-2Lower DB-3 3.) LowerDB-4 Slide Valve Coil #1, Coil #2 Slide Valve Coil #1, Coil #2 Logic 2.) UpperDB-2 Upper DB-2Lower DB-3 4.) LowerDB-3 lower and upper dead-bands are adjustable inputs Note: Place adhesive label in a location next to the PCM Controller so it is visible for Field Service and Refrigeration Technicians. 33

5 32 5

6 PCM Module Inputs Input #1: Slide-Valve Capacity Control See Chart E See Table F Input #2: Motor Temperature Control Note: The motor thermistor connection points are located in the compressors electrical box at terminals S1 and C. In the event of a thermistor failure, a spare thermistor is available between S2 and C terminal points. Table D Table A & B. Input #3: Discharge Temperature Control Table D Table A & B 6 31

7 General Installation Pictorials (for example only) Input #4: Dry Contact for Compressor Oil Protection Input #5: Compressor recognition signal (received from Master Controller) Tells the PCM Controller that the compressor is actually on/running. Slide Valve Control and Compressor Protection are activated when the PCM receives the recognition signal that the compressor is on. PCM controller initiates a 15 second delay regarding monitoring input#1 (suction pressure or thermistor temperature). PCM controller allows for a 3 second delay prior to beginning to monitoring inputs and taking action for inputs #2, #3, and #4 (eliminate nuisance trips on startup). When the compressor is off, there will be no oil flow. Therefore the oil flow switch will be open, causing output #5 to open, therefore not allowing the compressor to start. Therefore the controller must ignore the oil flow switch until the compressor is started and actual compressor oil flow is established, resulting in a closed oil flow switch. Input #6: Dry Contact for Manual Reset Compressor Operational PCM Module Outputs 30 7

8 Web Control Software Output #1 & #2: Slide Valve Control Output #3: Open/Close Motor Cooling Valve Output #4: LED Status indication for a Compressor Trip Table C.. Output #5: Enables the Compressor to Run When output is closed (energized), the compressor is enabled to run and therefore there are no fault conditions. Output must be part of Refrigeration System s pilot duty Start/Stop Compressor circuit. An alternative to output #5 is the end user receiving this compressor start/stop signal (run enable) via the PCM s communication port to the System Controller. Output will open (de-energize), tripping the compressor off line if the following fault conditions arise o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Controller Default Setting: PCM Default Setting Slide Valve Control: Enabled Upper Deadband-B: 2 F Compressor Protection: Enabled Upper Deadband-A: 1 F Upper Deadband-B: 2 psig Lower Deadband-A: 1 F Upper Deadband-A: 1 psig Lower Deadband-B: 2 F Lower Deadband-A: 1 psig Suction Pressure set-point: 30 psig Lower Deadband-B: 2 psig Temperature set-point: 35F 8 29

9 PCM Control Points Motor and Discharge Temperature Control Points ALC Controller Injection On ( F ) Injection Off( F) Shutdown Compressor ( F) Manually Reset Compressor( F) Time Delay required before manual reset (sec) Table A Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 28 9

10 Sensor Profile K NTC, Part# HH79NZ065 Deg F vs VDC VDC Deg F VDC Table D Sig Gnd 10 27

11 ZS PRO Display For permanent installation with the PCM Controller. See the I/O Zone Installation Guide for specifications and installation instruction for the ZS Pro. Large, easy-to-read LCD on the ZS Pro can be configured to display virtually any analog or digital value in your equipment. Here are some examples: zone temperature, outside air temperature, energy-saving mode icon, heating set-point, cooling set-point, relative humidity, CO2, VOCs, override time remaining, fan status, compressor status, alarms, and much more. Occupancy override is simple using the "Manual On" momentary push button on the ZS Pro. A single push switches the zone to an Occupied mode for a preset period of time. The user can increase or decrease the override time with the up or down arrows, and the LCD displays precisely how long the zone will stay occupied. The occupied time increment and maximum override time are fully adjustable. Zone set-points can be changed on the ZS Pro by pressing the up or down arrow buttons. Setpoint adjust increment amount and the maximum total adjustment are fully adjustable. Chart E NTC Thermistor, Part# A1004MS24P1 VDC vs Deg F Deg F Chart F PCM Layout and Interface: Note: The I/O Zone Installation Guide is for controller specifications, mounting requirements, and electrical requirements and installation. The I/O Zone Integration guide is for instruction regarding using the PCM with Network Protocols

12 BACview6 Virtual Display BACview User Guide 24 VAC Supply Power Input required. End User interface for pilot duty compressor on/off control circuit. 24VAC Supply Power Input required for BUS Outputs. 24 VAC input Supply Power required to the BUS

13 Hardwire connection location for permanent installations. How to Wire the Inputs for Pressure Transducer, Thermistor, or Dry Contact Connection port for portable or temporary installation. White Wire Red Wire 5vdc Power Supply 24 13

14 PCM Input #1 (Process Control Set-point): PCM Controller Display Features (3 WIRE) Carlyle kit 6BSB BLACK WHITE RED BACview6 Handheld BACview6 Software ZS PRO Web Control BACview6 Handheld Display BACview User Guide Set the configuration jumper for input #1 depending on if the control set-point will be measured via Pressure or Temperature. The jumper comes installed on the PCM and may already be in the correct position. Place the configuration jumper to this position if the Process Control Variable is a thermistor sensor for Input #1. OR Place the configuration jumper to this position if the Process Control Variable is a 0-5 vdc Pressure Transducer sensor for Input #

15 Slide Valve Wiring Diagram with System Controller I/OZ 560 Module Supply Power 24/120/240 Vac System Controller Slide Valve Override Output #1 Output #2 22 SV Coil #1 (Capacity Control) SV Coil #2 (Capacity Control) PCM Input #2: 15 S1 C S2 Must set the configuration jumper to this position for Input #2. This sets the type of signal the input will receive as a Thermistor. Failure to do so will result in input #2 not working correctly.

16 PCM output #5: PCM Input #3: Table A & B. must Output will open (de-energize), tripping the compressor off line, for the following fault conditions: o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short) Slide Valve Override Table B. See wiring diagram below. Slide Valve Override Control Points ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously ( F) Fully Load Compressor and restrict unloading below 100% Energize SV Coil #1 and Coil #2 continuously ( F) Table B 16 21

17 PCM output #3: PCM output #4: PCM Input #4: Fault Description LED Indication (Output #4) Output #5 Compressor Manual Reset Required Flow Switch Ratings VA Volts AMPS AC AMPS DC 20 17

18 PCM Input #5: PCM outputs #1 & #2: Note: All PCM outputs are rated for 1 amp. User must set the configuration jumper to this position for Input #5. This configures Input #5 as a Dry Contact. Failure to do so will result in input #5 not working correctly. PCM Input #6 Loads Comp Unloads Comp Freezes Unloading 18 19

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Vission 20/20 micro-controller. Operation and service manual

Vission 20/20 micro-controller. Operation and service manual Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1

More information

Control Panel. Operation and Service Manual

Control Panel. Operation and Service Manual Control Panel Operation and Service Manual 1 2 Important Note Before applying power to the control panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Vission 20/20 micro-controller. Operation and service manual Version 2.6 Vission 20/20 micro-controller Operation and service manual Version 2.6 Important Message READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation

More information

PCT-3001 plus. Display LCD

PCT-3001 plus. Display LCD PCT3 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS DESCRIPTION Pressure controller for refrigeration systems capable to control suction (compressors) and discharge (fans) pressures. It is possible

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

RSMD Technical Guide

RSMD Technical Guide RSMD Technical Guide TABLE OF CONTENTS OVERVIEW... 4 Features and Applications... 4 Module Dimensions... 5 INSTALLATION & WIRING... 6 Input Wiring... 6 Suction Pressure Sensor... 6 Head Pressure Sensor...

More information

CONTROL PANEL OPERATING MANUAL

CONTROL PANEL OPERATING MANUAL CONTROL PANEL OPERATING MANUAL CENTRIFUGAL CHILLERS Software version WCFU3UU03S D-EOMWC00804-14EN Table of Contents Introduction... 3 Features of the Control Panel... 4 General Description... 5 Component

More information

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide Factory Packaged Controls OE377-26-00058 (AAON Part No. V12090) MODGAS-X Controller Table of Contents GENERAL INFORMATION... 3 Overview...3 Features...3 INSTALLATION & WIRING... 4 Supply Air Temperature

More information

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data Fan Coil Thermostat Feature: Selectable analog & digital output Selectable fan speed contact Selectable Fahrenheit or Celsius scale Manual Night Set Back override (programmable) Multi level lockable access

More information

Application Engineering Europe

Application Engineering Europe Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for

More information

With Starter Information

With Starter Information Operating Manual OM CentrifMicro II-5 Group: Chiller Part Number: 331374901 Effective: November 2010 Supersedes: October 2010 MicroTech ΙΙ Controller With Starter Information For Centrifugal Chillers and

More information

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTOSYNC MODEL ASPSS DUAL COMPRESSOR SEQUENCER CONSOLE S/N 1638 AND ABOVE

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTOSYNC MODEL ASPSS DUAL COMPRESSOR SEQUENCER CONSOLE S/N 1638 AND ABOVE COMPRESSOR 1 EMERGENCY SHUTDOWN OFF POWER ON COMP LOADED COM PRESSOR OPERATING HOURS SYSTEM PRESSURE COMPRESSOR 2 EMERGENCY SHUTDOWN OFF POWER ON COMP LOADED COM PRESSOR OPERATING HOURS LEAD/LAG CONTROL

More information

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION $5.00 Installation, Operation, and Maintenance Manual CEMLINE CORPORATION CEM-TROL II Solid State Control Module and Electronic Control Valves P. O. Box 55, Cheswick, PA, 15024 Phone: (724) 274-5430 FAX

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TTX6048-SF-1K. ComfortLink II System Cooling 4TTX6048C1000A.

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TTX6048-SF-1K. ComfortLink II System Cooling 4TTX6048C1000A. Service Facts ComfortLink II System Cooling 4TTX6048C1000A 4TTX6048C1000A 230/1/60 28 45 CLIMATUFF - SCROLL 1-2 230/1/60 21.2-96 PROPELLER 27.6-1 DIRECT - 1 4600/4600 1-1/5 820 200/230/1/60 1.10 SPINE

More information

Centrifugal Operating Manual With Starter Information

Centrifugal Operating Manual With Starter Information Operating Manual OM 1153-1 Group: Chiller Part Number: 331374901 Effective: August 2012 Supersedes: May 2012 Centrifugal Operating Manual With Starter Information For Centrifugal Chillers and Templifiers

More information

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TWX6024-SF-1K. ComfortLink II System Heat Pump 4TWX6024C1000A.

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TWX6024-SF-1K. ComfortLink II System Heat Pump 4TWX6024C1000A. Service Facts ComfortLink II System Heat Pump 4TWX6024C1000A 4TWX6024C1000A 230/1/60 13 20 CLIMATUFF - SCROLL 1-2 230/1/60 10.3-52 PROPELLER 23-1 DIRECT - 1 2300/2300 1-1/8 825 200/230/1/60 0.70 SPINE

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS 50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS Date of last update: Apr-15 Ref: D7.8.4/0112-0415/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors...

More information

OUTDOOR UNIT CONTROLLER (OUC)

OUTDOOR UNIT CONTROLLER (OUC) AUCKLAND temperzone Ltd 38 Tidal Road, Mangere, Auckland. Private Bag 93303, Otahuhu, N.Z. Phone 0-9-279 5250 Fax 0-9-275 5637 Email sales@temperzone.co.nz WELLINGTON Phone 0-4-569 3262 Fax 0-4-566 6249

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners YD360/480/600, YJ-30/-40/-50 and J30/40/50 YD Models 642546-UAI-A-080 GENERAL Standard operation

More information

Vibralert Mechanical Switch Model 5550

Vibralert Mechanical Switch Model 5550 Vibralert Mechanical Switch Model 5550 APPLICATION TIPS -Lowest cost vibration protection; -Baseplates available to accomodate most previous Metrix or competitor s switch models for easy retrofit. -Watertight

More information

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTZ0036B-SF-1B. ComfortLink II System Cooling 4TTZ0036B1000A CAUTION

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTZ0036B-SF-1B. ComfortLink II System Cooling 4TTZ0036B1000A CAUTION Service Facts ComfortLink II System Cooling 4TTZ0036B1000A 4TTZ0036B1000A 208/230/1/60 19 30 CLIMATUFF 2-2 208/230/1/60 13.2-60.0 YES YES YES PROPELLER 27.6-1 DIRECT - 2 4450/3190 1-1/3 707/493 200/230/1/60

More information

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014 HS Refrigeration Screw Compressor Troubleshooting Guidelines SG-0003-01 March 2014 Refrigeration Screw Compressor Troubleshooting Guidelines SG-0003-01 March 2014 BITZER Screw Compressors CS High Temp

More information

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN February 2004 CNT-SVN02B-EN Tracer AH541

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Made in the U.S.A. NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Nema Enclosed DC Control Specifications Catalog Number BC140 or Features BC138 BC139 BC140-FBR BC154 BC160 BCWD140

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS TEC20 TEC20H ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-306D Supersedes: 2100-306C File: Volume

More information

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14 Zone Sensors Submittal Data English Language/IP Units SD1582EW 10/14 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and

More information

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units Universal and Multi Split Units If there is fault on any LG universal or multi unit a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the

More information

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18 Zone Sensors Submittal Data English Language/IP Units SD1582EW 06/18 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and

More information

RVS-DX Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTODUAL MODEL ADSE-2 DUAL COMPRESSOR SEQUENCER (firmware ver 1.02

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTODUAL MODEL ADSE-2 DUAL COMPRESSOR SEQUENCER (firmware ver 1.02 COMP RES SOR OPE RATING H OURS COMPR ESS OR OPE RATING H OURS COMPRESSOR 1 E ME RGENCY S HUTDOW N OFF P OW ER ON COMP LOADED LEAD/LAG CONTROL AUTO ON S YSTEM PRE SSU RE COMPRESSOR 2 E MERGE NCY S HUTDOW

More information

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL 1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This

More information

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series) Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant

More information

Designed for ease of integration with automation systems

Designed for ease of integration with automation systems BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from

More information

Service Facts. WARNING: HAZARdOuS VOLTAGE - disconnect POWER and discharge 4TWZ0024-SF-1F. ComfortLink II System Heat Pump 4TWZ0024A1000A.

Service Facts. WARNING: HAZARdOuS VOLTAGE - disconnect POWER and discharge 4TWZ0024-SF-1F. ComfortLink II System Heat Pump 4TWZ0024A1000A. Service Facts ComfortLink II System Heat Pump 4TWZ0024A1000A 4TWZ0024A1000A 200/230/1/60 14 20 CLIMATUFF 2-2 200/230/1/60 8.7-58 YES YES YES PROPELLER 27.6-1 DIRECT - 2 3390/2270 1-1/3 759/493 200/230/1/60

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

BAPI-Stat 3 Room Sensor

BAPI-Stat 3 Room Sensor Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read

More information

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved. MANUAL ECM Motor ECM / ECM-DX Series v100 Issue Date: 08/15/17 2017 Price Industries Limited. All rights reserved. ECM MOTOR TABLE OF CONTENTS ECM Motor Background...1 ECM Motor Power and Control Connectors...2

More information

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE MODEL KBRG-255 (5HP) KB Part No FULL WAVE 4 QUADRANT FWD ACCEL REV ACCEL FWD CL

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE MODEL KBRG-255 (5HP) KB Part No FULL WAVE 4 QUADRANT FWD ACCEL REV ACCEL FWD CL INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE MODEL KBRG-255 (5HP) KB Part No. 8821 FULL WAVE 4 QUADRANT FWD EN FWD ACCEL REV ACCEL DB MAX IR REV SPD RESP COMP CL FWD CL S/LT NLT OFFSET J8

More information

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System POWER TROLLEY 8 Model: SINE 1548 Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System Version 07 CONTENTS Page 1. INTRODUCTION... 1 2. USING THE POWER TROLLEY.... 2 3. BATTERY BACKUP

More information

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING TROUBLESHOOTING for the 5 BUTTON 3109228.001 COMFORT CONTROL CENTER SYSTEM INTRODUCTION The Comfort Control Center control system can be used to operate the following Duo-Therm Units: Roof Top Air Conditioners

More information

Description. functions including single duct pressure dependent or pressure independent systems.

Description. functions including single duct pressure dependent or pressure independent systems. Description The Meridian Basic control system converts a single zone HVAC unit into a variable air volume/variable air temperature multiple zone system. The microprocessor based Zone Manager calculates

More information

Digital Room Thermostats with Touch Screen LCD

Digital Room Thermostats with Touch Screen LCD TC40 Touch Series Digital Room Thermostats with Touch Screen LCD Revision Date February 22, 2013 Features Wall-mount Display Control to match any decor Extra large easy-to-read Liquid Crystal Display (LCD),

More information

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS TECHNICAL BROCHURE BSPDDRIVE C U L US Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS Aquavar SPD variable speed, constant pressure pump controller

More information

COMMUNICATIONS SETUP DBS STARTER PANEL

COMMUNICATIONS SETUP DBS STARTER PANEL S90-450 CS/APR 2001 File: SERVICE MANUAL - SECTION 90 Replaces: NOTHING (New Manual) Dist: 3, 3a, 3b, 3c DBS STARTER PANEL Version 1.0x S90-450 CS DBS STARTER PANEL Page 2 Table of Contents Communications

More information

Product Catalog. NQ Series. Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons

Product Catalog. NQ Series. Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons Product Catalog NQ Series Portable and Remote Air-Cooled Condenser Chillers 4 to 43 Tons Page Intentionally Blank Contents Standard Features...1 Available Options...3 Oversized Pumps... 3 High Flow Unit

More information

Power Distribution System User s Manual. Model: PDS-100

Power Distribution System User s Manual. Model: PDS-100 Power Distribution System User s Manual Model: PDS-0 Section Page Product Overview... 1 I) General Information... 2 II) Important Safety Information... 2 III) Installation... 3 A) Materials Provided...

More information

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3.

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3. MANUAL INSTALLATION Tracking Controller TC Series v100 Issue Date: 02/25/16 2016 Price Industries Limited. All rights reserved. Firmware: 1.3.0 TABLE OF CONTENTS Product Overview General...1 Tracking Controller

More information

Installation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

Installation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G) Part A, Section 3 Model This section covers the following unit configurations. Voltage 4 300V 3400V 3500V Pump Piston (E, F, G) Manifold Control 4-Port (A) 6-Port (B or C) -Port (S or T) Vista Pattern

More information

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN

More information

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE FULL WAVE 4 QUADRANT REV S/LT NLT R33 AC LINE FUSE ARMATURE F2 FUSE TB2

INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE FULL WAVE 4 QUADRANT REV S/LT NLT R33 AC LINE FUSE ARMATURE F2 FUSE TB2 INSTALLATION AND OPERATING INSTRUCTIONS REGENERATIVE DRIVE MODEL KBRG-225D (P/N 8800) MODEL KBRG-240D (P/N 8802) FULL WAVE 4 QUADRANT FWD EN FWD REV ACCEL ACCEL DB MAX IR REV FWD SPD RESP COMP CL CL S/LT

More information

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additional options include pushbutton override, fan

More information

TCM D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company

TCM D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company TCM-03-024D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company D-M-E Company TCM-03-024D Page 1 SAFETY D-M-E Company products have been designed to be safe and simple to operate.

More information

SE7200 Series Installation Guide

SE7200 Series Installation Guide SE7200 Series Installation Guide 24 VAC Low Voltage Zoning Terminal Equipment Controller For Commercial HVAC Applications CONTENTS Installation 2 Preparation 2 Location 2 Installation 2 Configurable BI/UI

More information

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With

More information

OnCommand Troubleshooting Guide Hayward Industries

OnCommand Troubleshooting Guide Hayward Industries OnCommand Troubleshooting Guide 2010 Hayward Industries Table of Contents Safety Precautions Page 1 Overview Pages 2-5 Software Troubleshooting Page 6 Local Display Pages 7-8 Relays Pages 9-10 Heaters

More information

Installation. Part A, Section 3. This section covers the following unit configurations. Voltage 1, 2, 3. Vista Standard (V) A3EN-04-[3V-A-AAXV]-11

Installation. Part A, Section 3. This section covers the following unit configurations. Voltage 1, 2, 3. Vista Standard (V) A3EN-04-[3V-A-AAXV]-11 Part A, Section 3 This section covers the following unit configurations. Model All Voltage 1, 2, 3 Pump All Manifold All Control Vista Standard (V) A 3-0 A 3-1 Section A 3 WARNING: Allow only qualified

More information

Model 550 Series Vibration Switches

Model 550 Series Vibration Switches OPERATION MANUAL Vibration Switches Includes: 550 550M 550-X 550M-X Page 2 SECTION TITLE PAGE 1. INTRODUCTION... 2 2. FEATURES... 3 3. WIRING... 4 4. ANALOG METER... 4 5. TESTING... 4 6. INSTALLATION...

More information

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18) AF Series Spring Return Direct Coupled Actuator Minimum 133 in-lb torque For damper areas up to 35 sq-ft* (For lower torque, see NF, LF, or TF series) Applications Remove for 3/4 to 1.05 shafts ZG106 or

More information

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION $5.00 Installation, Operation, and Maintenance Manual CEMLINE CORPORATION CEM-TROL Solid State Control Module and Electronic Control Valves P. O. Box 55, Cheswick, PA, 15024 Phone: (724) 274-5430 FAX (724)

More information

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH TGDFC-6 DFC Direct Fired Gas Heating System Technical Guide for: Outdoor Mounted Units To 0,000 CFM And 14M BTUH Applied Air Keeps You Warm Featuring the Patented AdaptAire controlled Circulation System

More information

SOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet

SOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet SOLAR SMART 12/24V 20Amp MPPT Solar Charge controller with Ethernet Embedded web pages, SNMP support, output port for external Relay board and GSM SMS unit port USER MANUAL PLEASE READ THIS MANUAL CAREFULLY

More information

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 MODEL NUMBER: AL-84111 Specifications OUTPUT Output Volt Amp Capacity (VA) 2200 Output kva Capacity

More information

QUICK START GUIDE FOR DEMONSTRATION CIRCUIT DC1259A BATTERY BACKUP MANAGER BOARD

QUICK START GUIDE FOR DEMONSTRATION CIRCUIT DC1259A BATTERY BACKUP MANAGER BOARD DESCRIPTION Demonstration circuit DC1259A is a single-battery battery-backup controller featuring the LTC4110. The LTC4110 controller provides all the features and functions to offer a complete standalone

More information

This Datasheet for the IC670MDL930. Relay 2A 8 Pt. 6 form A/2 form C Isolated.

This Datasheet for the IC670MDL930. Relay 2A 8 Pt. 6 form A/2 form C Isolated. This Datasheet for the IC670MDL90 2A 8 Pt. 6 form A/2 form C Isolated http://www.qualitrol.com/shop/p-142-ic670mdl90.aspx Provides the wiring diagrams and installation guidelines for this GE Field Control

More information

User Manual 1KVA-5KVA INVERTER / CHARGER

User Manual 1KVA-5KVA INVERTER / CHARGER User Manual 1KVA-5KVA INVERTER / CHARGER Version: 1.7 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

Uninterruptible Power System

Uninterruptible Power System USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency UPS 1 st Edition Uninterruptible

More information

Tattletale Annunciators and Magnetic Switches

Tattletale Annunciators and Magnetic Switches Tattletale Annunciators and Magnetic Switches Tattletale annunciators and magnetic switches are the nerve centers that translate Swichgage contact operations into decisions and operate the alarm or shutdown

More information

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to

More information

EZ-TRAC Digital Tension Readout and Control

EZ-TRAC Digital Tension Readout and Control Magnetic Power Systems, Inc. 1626 Manufacturers Drive. Fenton, MO 63026 Tel: 636.343.5550 Fax: 636.326.0608 magpowr@magpowr.com INSTRUCTION MANUAL EZ-TRAC Digital Tension Readout and Control Table of Contents

More information

Uninterruptible Power System

Uninterruptible Power System USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency UPS AVR Protection

More information

FIRE DOOR OPERATOR WARNING INSTALLATION LOGIC BOARD REPLACEMENT KIT K , K A-400 & K B-400 APPLICATION REMOVE AC AND DC POWER

FIRE DOOR OPERATOR WARNING INSTALLATION LOGIC BOARD REPLACEMENT KIT K , K A-400 & K B-400 APPLICATION REMOVE AC AND DC POWER APPLICATION Replacement of logic board for Models FDO and FDC operators with Rev. 400 wiring. FIRE DOOR OPERATOR LOGIC BOARD REPLACEMENT KIT K79-3493-400, K79-3493A-400 & K79-3493B-400 WARNING To prevent

More information

GE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline

GE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline GE Energy The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline DNGP with Modbus Communication protocol features ZERO Bleed * technology and control logic designed for natural gas control valves

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

MCC Automatic Start-Stop Microcomputer Charger Control

MCC Automatic Start-Stop Microcomputer Charger Control MCC Automatic Start-Stop Microcomputer Charger Control Installation & Operation Instructions Warning: Read ALL the instructions before starting. If anything is not clear, call your dealer or contact Arrgh!!

More information

Uninterruptible Power System

Uninterruptible Power System USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency AVR Protection Compact

More information

Installation Instructions

Installation Instructions Installation Instructions ECONOMIZER X, FACTORY INSTALLED OPTION LOW LEAK ECONOMIZER FOR 2 SPEED INDOOR FAN CONTROL UNITS This document is a supplemental installation instruction for the factory-installed

More information

Modbus Integration Integration for Modbus Functionality for VT8600 Series

Modbus Integration Integration for Modbus Functionality for VT8600 Series Modbus Integration Integration for Modbus Functionality for VT8600 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS

More information

KBVF Adjustable Frequency Drive

KBVF Adjustable Frequency Drive INSTALLATION AND OPERATING INSTRUCTIONS KBVF Adjustable Frequency Drive Variable Speed /Soft-Start AC Motor Control with I 2 t Electronic Overload Protection for 3-Phase Induction Motors through 1 HP!

More information

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication

More information

PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls. Instruction Sheet PA October 2007

PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls. Instruction Sheet PA October 2007 Instruction Sheet PA-00281 October 2007 PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls THE FLEXIBLE

More information

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO: YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT

More information

CONTROLLED CHILLED BEAM PUMP MODULE OWNER S MANUAL

CONTROLLED CHILLED BEAM PUMP MODULE OWNER S MANUAL ENERGY SAVINGS 1 ST COST SAVINGS PROACTIVE CONTROL CONTROLLED CHILLED BEAM PUMP MODULE 2 NEUTON PUMP MODULE TABLE OF CONTENTS Introduction.... 3 Configurations.... 3 Principle of Operation.... 4 Sequence

More information

Appendix A: Inputs, Outputs, and Parameters

Appendix A: Inputs, Outputs, and Parameters Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Appendix A: Inputs, Outputs, and Parameters Introduction This appendix describes the inputs, outputs, and parameters used with the Metasys Zoning

More information

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents. 1 10/2014 REV 7 !!Attention!! Before performing diagnostics: Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents. Check for Fault Codes using the

More information

TOTALINE PROTECTION CONTROLS

TOTALINE PROTECTION CONTROLS TOTALINE PROTECTION CONTROLS SOLID STATE HEAD PRESSURE CONTROL WITH OPTIONAL HEAT PUMP OVERRIDE Head Pressure Controls Temperature sensitive fan motor control which regulates head pressure at low ambients

More information

CDI series Model TW. Residential Water to Water Heat Pump. Engineering Submittal Sheet. Standard Features. Overview and Certifications

CDI series Model TW. Residential Water to Water Heat Pump. Engineering Submittal Sheet. Standard Features. Overview and Certifications CDI series Model TW Residential to Pump Engineering Submittal Sheet Overview and Certifications Standard Features, Factory Installed Options and Control Options Standard Features White Pre-Painted Sheet

More information

PoolPak ECCIII User s Guide Supplement to Form NM-1(1198)

PoolPak ECCIII User s Guide Supplement to Form NM-1(1198) ECCIII User s Guide SUPERSEDES: Nothing FORM NO: M51SV-EC3UG0310 PoolPak ECCIII User s Guide Supplement to Form NM-1(1198) TABLE OF CONTENTS INTRODUCTION 2 FEATURES 2 INSTALLATION 2 FIELD WIRING DIAGRAM

More information

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL Model No. DFC-X Support 877-351-4702 DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This manual covers the following products: DFC-X TS-01 DFTD RDU DAT-12 PWM-10V

More information