A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

Size: px
Start display at page:

Download "A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures"

Transcription

1 A419 Issue Date February 10, 2003 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures The A419 series controls are single-stage, electronic temperature controls with a Single-Pole, Double-Throw (SPDT) output relay. They feature a lockable front-panel touchpad for setup and adjustment, and a Liquid Crystal Display (LCD) for viewing the temperature and status of other functions. A Light-Emitting Diode (LED) indicates the controls output relay On/Off status. The A419 controls are available in 24 VAC or 120/240 VAC powered models. The A419 controls have heating and cooling modes, adjustable setpoint and differential, an adjustable anti-short cycle delay, and a temperature offset function. The setpoint range is -30 to 212 F (-34 to 100 C). The controls feature remote sensing capability and interchangeable sensors. The A419 controls are available in either NEMA 1, high-impact plastic enclosure suitable for surface or DIN rail mounting or NEMA 4X watertight, corrosion-resistant surface-mount enclosures. Figure 1: A419 Temperature Control with NEMA 1 Enclosure and A99 Temperature Sensor Easy-to-Read Front-Panel Liquid Crystal Display Features and Benefits Displays the sensed temperature and control-function status clearly; custom icons on the display indicate the control and system status at a glance Wide Temperature Differential Adjustment Range (1 to 30F or C ) Adjustable Anti-Short Cycle Delay (0 to 12 Minutes in 1-Minute Increments) Switch-Activated Temperature Offset Function High-Impact, Thermoplastic NEMA 1 or NEMA 4X Watertight, Corrosion-Resistant Enclosures Lockable Front Panel Touchpad Low- and Line-Voltage Models Allows the user to set a precise (1F or C ) temperature differential from 1 to 30F or C ; providing a much tighter differential than electromechanical controls Ensures that the output relay remains off for a user-set time delay, which helps avoid hard starts, nuisance overload outages, and unnecessary equipment wear Allows the user to shift the cut-in and cutout setpoints by an adjustable offset based on the status of a user-installed, external switch, such as a time clock Increase application options, allowing surface and snap-fit DIN rail mount, or Watertight surface mount Allows easy set up and adjustment of the A419 control setpoint, differential, and other functions; a concealed jumper locks the touchpad, and deters unauthorized adjustment of the control settings Provide options for most refrigeration and HVAC control-voltage applications 2003 Johnson Controls, Inc. 1 Code No. LIT

2 Application IMPORTANT: The A419 Series Temperature Controls are intended to control equipment under normal operating conditions. Where failure or malfunction of an A419 Series Control could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of or protect against failure or malfunction of the A419 Series Control must be incorporated into and maintained as part of the control system. The A419 Electronic Temperature Control can be used to control a wide variety of single-stage refrigeration or Heating Ventilating, and Air Conditioning (HVAC) equipment. Typical applications include: retail store display freezers and reach-in coolers supermarket display cases for produce/meats retail store walk-in coolers and freezers boiler operating control (used as a thermostat) condenser fan cycling or staging cooling tower pump and fan control space and return air temperature control FCC Compliance This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his or her own expense. Dimensions 1/2 (13) 2-15/16 (75) 9/64 (3.7) 1-9/16 (40) 1/4 (6) DIN Rail 7/16 (11) Sensor 2 (50) 2-3/8 (61) 7/8 (22) MENU 2-3/8 (61) 5 (127) 4 (102) 2-3/8 (61) 7/8 (1/2 in. Trade Size) (22) Conduit Hole Figure 2: A419 Temperature Control with NEMA 1 Enclosure, Dimensions, in./(mm) 2-1/4 (56) A419 MENU 2-13/16 (71) 6-5/8 (168) 6-1/8 (155) 1-3/4 (44) 1-1/16 (27) Position the A99 sensor in the bracket at the bottom of the A419 NEMA 4X enclosure. 2-13/16 (71) Figure 3: A419 Temperature Control with NEMA 4X Watertight, Corrosion-resistant, Enclosure, Dimensions, in./(mm) Canadian Compliance Statement This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. 2 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

3 Liquid Crystal Display During normal operation, the LCD displays the temperature at the sensor, the units of temperature ( F or C), and an icon indicating if the control is set for Heating ( ) or Cooling ( ) mode. The LCD also displays BIN if the Temperature Offset function is activated. See Figure 5. During control set up or adjustment, the LCD displays the control functions and their values (settings). After 30 seconds of inactivity, the display returns to the sensed-temperature display. See the Adjustments section to adjust the control setting. Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the SPDT output relay is energized and the Normally Open (N.O.) contacts are closed. See Figure 5. Figure 4: A419 Temperature Control with NEMA 4X Enclosure and A99 Temperature Sensor Operation Overview The A419 control s front-panel, LCD, LED, and the A419 control functions are described below. See the Adjustments section for instructions on setting up and adjusting the A419 control. A419 Control Front-Panel The front panel of the A419 control has a three-button touchpad and LCD for adjusting control function values, and an LED indicator that displays the On/Off status of the SPDT output relay. See Figure 5. MENU BIN F Temperature Offset Indicator Temperature Units Indicator Operating Mode Indicator Liquid Crystal Display MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Figure 5: A419 Control Front-Panel with Display A419 Control Definitions Cut-in is the temperature at which the N.O. contacts on the SPDT output relay close. Cutout is the temperature at which the N.O contacts on the SPDT output relay open. A419 Functions Set at the Front-Panel (SP) establishes the temperature value that energizes or de-energizes the output relay, depending on the user selected mode of operation. The control may be set either to cut in or to cut out at. See the Cooling/Heating and Modes. The range is -30 to 212 F (-34 to 100 C). If mode is Cut-in, is the temperature value that closes the N.O. contacts. If mode is Cutout, is the temperature value that opens the N.O. contacts. See Figure 7 and Figure 8. Differential (dif) establishes the difference in temperature (in F or C ) between the cut-in and cutout values. The differential is set relative to and may be set from 1 to 30F or C. See Figure 7 and Figure 8. Anti-Short Cycle Delay (ASd) establishes the minimum time that the N.O. contacts remains open (after reaching cutout) before closing again. The delay overrides any Load Demand and does not allow the N.O. contacts to close until the set time-delay value has elapsed. See Figure 6. When the delay is activated, the LCD alternately flashes the sensor temperature and ASd. The delay may be set for 0 to 12 minutes in 1-minute increments. A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 3

4 For example, if the anti-short cycle delay is set for 7 minutes, the A419 control will not restart the equipment for 7 minutes after the equipment has cut out, even if the cut-in temperature value is reached during the delay. If the temperature reaches the cut-in value during the delay period, the display flashes between the sensed temperature and ASd, indicating that the next On-cycle is being delayed. After the set delay time has elapsed, the A419 control returns to normal operation, restarts the equipment (if cut-in has been reached), ASd stops flashing, and the LCD reverts to the normal operating display. Note: Any interruption in supply power to the A419 control activates the anti-short cycle delay. Time Off Off On On Anti-short Cycle Delay Load Demand Overridden Load Demand Output Status Figure 6: Anti-short Cycle Delay Sensor Failure Operation (SF) establishes how the A419 control operates the equipment in the event of a sensor or sensor-wiring failure. The A419 control may be set to run the equipment continuously or to shut it down if the sensor or sensor wire fails. When a failure is detected the LCD flashes SF alternately with OP if the sensor circuit is open, or SF and SH if the sensor circuit is shorted. The control implements a 1-minute delay before initiating a failure response to allow for verification of the failure condition and to avoid nuisance failure indications. Temperature Units establishes the units of temperature (F or C ) displayed on the LCD. Temperature Offset (OFS) establishes the value of setpoint-shift (in F or C ) applied to (and Differential) when a (user-installed) circuit is closed between the binary input (BIN) and common (COM) terminals. The offset value may be set from 0 to 50F or C. The Temperature Offset function is used to reset the Heating to a lower temperature (secondary) setpoint or reset the Cooling to a higher temperature (secondary) setpoint by the temperature value set in Temperature Offset. The BIN and COM terminals may be connected to a (user-supplied) external switching device, such as a time clock, that has a set of Single-Pole, Single-Throw (SPST) contacts. Closing a circuit between the BIN and COM terminals activates the Temperature Offset. See Wiring. This function enables the control to alternate between two temperature setpoints based on the position of the binary input switch. The difference between the primary and secondary setpoints (in F or C ) is set in the Temperature Offset function (OFS) using the touchpad. See Setting Other Functions. Table 1 shows an example of Temperature Offset. Table 1: Temperature Offset Example Mode of Operation Temperature Offset Value Cooling Heating Secondary * * when circuit between binary input terminals (BIN and COM) is closed When the circuit is closed between the binary input (BIN) common (COM) terminals, the offset function is enabled and the A419 control cycles on the secondary setpoints. BIN is displayed on the LCD above the F or C symbol when the offset is enabled. See Figure 5. A419 Control Functions Set by Jumper Position For instructions on positioning jumpers, see Positioning the Jumpers in the Adjustments section. Refer to Figure 12 and Figure 13. Touchpad Lock: The jumper at P5 establishes whether the touchpad is locked or unlocked. Locking the touchpad deters accidental or unauthorized changes to all of the function parameters. Heating/Cooling Mode is established by positioning the jumper on the top two pins of the P4 jumper. See Figure 13. Mode: Removing or installing the lower jumper at P4 establishes whether is the cut-in temperature or cutout temperature. See Figure 13. Cooling/Heating and Modes The A419 control may be in four operating modes: Cooling/Cut-in, Cooling/Cutout, Heating/Cut-in, and Heating/Cutout. Position the jumpers located on the circuit board under the A419 control cover to set the desired mode of operation. See Positioning the Jumpers. In Cooling/Cut-in mode the differential is below. The output relay energizes and the LED illuminates when the temperature rises to. When the temperature drops to minus the differential value, the relay and LED de-energize. 4 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

5 In Cooling/Cutout mode the differential is above. The output relay energizes and LED illuminates when the temperature rises to plus the differential value. When the temperature drops to, the relay and LED de-energize. Temperature (+) Cooling/Cut-out (-) Cut-in (On) Differential Cut-out (Off) Cooling/Cut-in Cut-in (On) Differential Cut-out (Off) Figure 7: Cooling Modes When the Heating/Cut-in mode is selected, the differential is above. The output relay energizes and LED indicator illuminates when the temperature drops to. When the temperature rises to plus the differential value, the output relay and LED de-energize. When Heating/Cutout mode is selected, the differential is below. The output relay energizes and LED indicator illuminates when the temperature drops to minus the differential value. When the temperature rises to, the output relay and LED indicator de-energize. Temperature (+) Heating/Cut-in Cut-out (Off) Mounting An A419 control has either a standard high-impact plastic NEMA 1 or a NEMA 4X corrosion-resistant, watertight enclosure. The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment. Note: When mounting the control to rigid conduit, attach the hub to the conduit before securing the hub to the control enclosure. The mounting hole pattern of the NEMA 1 enclosure is identical to that of the System 350 controls, and most models of the A19 control. The NEMA 1 enclosure may also be mounted on 35 mm DIN rail. See Figure 1 and Figure 2. The NEMA 4X models may be mounted to flat vertical surfaces using the four screw holes at the enclosure corners. See Figure 3 and Figure 4. To maintain the watertight and corrosion resistant integrity of the NEMA 4X enclosure, use a conduit fitting rated for the environment in which the control is installed. An additional (low-voltage) two-wire cable is required to operate the temperature offset function. On NEMA 4X enclosures you must install a suitable liquid-tight fitting in an available knockout to pass the two-wire cable through the enclosure wall. IMPORTANT: The short-lead A99 sensor, included with A419 NEMA 4X model controls, must be mounted on the bottom of the control in the bracket molded on the NEMA 4X housing. Mounting the sensor on top of the control may reduce the accuracy of the displayed temperature. See Figure 3 and Figure 4 for proper sensor position. Heating/Cut-out Differential Cut-in (On) Cut-out (Off) Differential (-) Cut-in (On) Figure 8: Heating Modes A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 5

6 Wiring! WARNING: Risk of Electrical Shock. To avoid the risk of electrical shock, disconnect all power sources to the control before wiring any connections. More than one disconnect may be required to completely de-energize the control and equipment. IMPORTANT: All wiring must conform to local, national, and regional regulations. Use copper conductors only for all wire connections. Do not exceed the electrical ratings for the A419 control or the equipment it is wired to. Refer to Figure 9, Figure 10, and Figure 11 for typical examples of wiring an A419 control to the controlled equipment. Use wire no larger than 12 AWG when connecting to the two lower terminal blocks (TB1 and TB2). Use wire no larger than 16 AWG when connecting to the upper sensor terminal block (TB3). Wire insulation rating must be 90 C, minimum. A99 temperature sensors are not polarity sensitive. Wire the leads to (+) SEN and (-) COM on the sensor terminal block (TB3). See Figure 9, Figure 10, and Figure 11. Keep the leads between the control and sensor as short as possible/practical in your application. The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature. Refer to Table 1 when extending sensor leads. Temperature sensor signals may be affected by electrical interference. When extending sensor cable beyond 50 ft (15.2 m) use a twisted-pair, shielded cable to reduce electrical interference. If the Temperature Offset function is used, wire a switch (such as a switching time clock) between the binary input terminal (BIN) and the common terminal (COM). See Figure 9, Figure 10, and Figure 11 for terminal strip location. (Optional) Binary Input Switch Cable Shield (if used) A99 Sensor 24 VAC Class 2 Transformer TB3 TB1 A419GBF-1 A419GEF-1 (+) BIN ( ) COM (+) SEN T1 T2 TB2 NC C NO Load Figure 9: Wiring the 24 VAC A419 Control (Optional) Binary Input Switch Cable Shield (if used) A99 Sensor 120 VAC Neutral TB3 TB1 240 AC COM 120 A419ABC-1 A419AEC-1 (+) BIN ( ) COM (+) SEN TB2 NC C NO Load Figure 10: Wiring the 120 VAC A419 Control (Optional) Binary Input Switch Cable Shield (if used) A99 Sensor TB3 TB1 A419ABC-1 A419AEC-1 (+) BIN ( ) COM (+) SEN TB2 240 L1 VAC L2 240 AC COM 120 NC C NO Load Figure 11: Wiring the 240 VAC A419 Control 6 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

7 Adjustments This section provides instructions for setting up and adjusting the A419 controls using the jumpers and touchpad. Positioning the Jumpers The P5 Jumper Pin Block has a single set of jumper pins and is used to lock or unlock the touchpad. The P4 Jumper Pin Block has two sets of jumper pins. The top set of pins at P4, labeled JUMP1, is used to set the control for Heating or Cooling mode. The bottom set of pins, labeled JUMP2, is used to establish at cut-in or at cutout. See Figure 12. To position a jumper in the Installed position, place the jumper on both pins. To position a jumper in the Removed position, place the jumper on only one pin. (Save the jumper in case it is required in the future.) See Figure 12. Position the jumpers as follows. Refer to Figure 12, Figure 13, and Table Verify that all power sources to the A419 control have been disconnected. 2. Remove the control s cover by loosening the four captive cover screws. 3. Position the jumpers to set Cooling/Heating,, and Touchpad Lock functions. 4. Replace the cover and fasten in place with the four screws. 5. Restore power to the control. Jumper Pins = Installed (Jumper Positioned on Both Pins) = Removed (Jumper Positioned on One Pin) Figure 12: Positioning the Jumpers Touchpad Locked P5 JUMP2 P4 Heating Mode Cut-in at Cooling Mode Cut-in at Heating Mode Cutout at Cooling Mode Cutout at Figure 13: Jumper Positions and Control Settings IMPORTANT: Verify that the Cooling/Heating jumper is positioned properly before powering the A419 control, to ensure that the relay operates as intended. See Figure 13 and Table 2. Table 2: Jumper Designations, Jumper Positions and Control Settings Function Operating Mode Cooling/Heating Jumper Pins Designation on Control Setting Jumper Position* JUMP1 Cooling Removed (Top Pair of Pins on Block P4) Heating Installed Factory Default Setting (and Jumper Position) Cooling (Removed position) JUMP2 At Cut-in Removed (Bottom Pair of Pins on Block P4) At Cut-out Installed Cut-in (Removed Position) Touchpad Lock P5-Touchpad Unlock Locked Unlocked Removed Installed Unlocked (Installed Position) Note: The touchpad cannot be unlocked without a jumper. Do not discard any jumpers in case they are required in the future. A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 7

8 Changing Temperature Units The A419 control is set at the factory to display in Fahrenheit temperature units. To convert to Celsius units, press the Up and Down buttons simultaneously. Press them again to return to Fahrenheit units. Notes: Make sure the Touchpad Lock jumper is in the unlocked (installed) position before adjusting the control. See Figure 13. Verify that the A419 control is displaying the desired temperature units (F or C ) before establishing the setpoint value. Setting the To view and adjust the temperature setpoint, follow these steps and refer to Table 3: 1. Press and hold the MENU button until the display changes to flashing SP. This will take about 2 seconds. 2. Press the MENU button again. The current setpoint is displayed. 3. Press the Up or Down button to adjust the setpoint temperature. 4. Press the MENU button to save. The display then returns to the sensor temperature. Notes: If no entries are made for 30 seconds while programming is in progress, the control reverts to the normal temperature display. If the MENU button is not pressed after changing the setpoint value, the new value is not saved and the A419 control reverts to the previously saved setpoint value. Table 3: Function Ranges and Settings Function SP: Range -30 to 212 F (-34 to 100 C) dif: Differential 1 to 30 (F or C) 5 ASd: Anti-short Cycle Delay OFS: Temperature Offset SF:Sensor Failure Operation Factory Setting 30 0 to 12 minutes 1 0 to 50 (F or C) 0 0 = output de-energized 1 = output energized Operation at Extremes: If the combination of setpoint plus or minus the differential falls outside the temperature range (-30 to 212 F [-34 to 100 C]), the A419 control operates as follows: Cooling/Cut-in: If the control is operating in Cooling/Cut-in mode and setpoint minus differential is less than -30 F, the control switches on at setpoint and off when the temperature drops below -30 F (-34 C). Heating/Cut-in: If the control is operating in Heating/Cut-in mode and setpoint plus differential is greater than 212 F (100 C), the control switches on at setpoint and off when the temperature exceeds 212 F (100 C). Cooling/Cutout: If the control is operating in Cooling/Cutout mode and setpoint plus differential is greater than 212 F (100 C), the control switches on when the temperature exceeds 212 F (100 C) and off at setpoint. Heating/Cutout: If the control is operating in Heating/Cutout mode and setpoint minus differential is less than -30 F (-34 C), the control switches on when the temperature drops below -30 F (-34 C) and off at setpoint. 1 Any saved A419 control setting values are non-volatile and remain in the control s memory during power interruptions. 8 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

9 Setting Other Functions To set the Differential (dif), Anti-short Cycle Delay (ASd), Temperature Offset (OFS), or Sensor Failure (SF) operation, use the method illustrated and outlined below. Figure 14 illustrates the order of functions shown using the Up or Down button. The Up button accesses functions in the clockwise direction; the Down button accesses functions in the counterclockwise direction. Refer to Table 3 for function ranges and factory settings. Up Button S P S F d I F Down Button O F S A S d Figure 14: Order of the Functions 1. Press and hold the MENU button until the display changes to flashing SP. This will take about 2 seconds. 2. Press the Up or Down button repeatedly until the desired function is displayed. See Table Press the MENU button to display the function s current value. 4. Press the Up or Down button until the desired value is displayed. 5. Press the MENU button to save the new value. The display then returns to the sensor temperature. Checkout Before applying power, make sure installation and wiring connections are according to job specifications. After necessary adjustments and electrical connections have been made, put the system in operation and observe the control for at least three complete operating cycles before leaving the installation. Troubleshooting If the control system does not function properly, verify that the unit is wired, configured, and set properly. If the problem persists, use the following procedures to determine the cause of the problem: 1. Check for proper supply voltage to the A419 control. a. Remove the cover by loosening the four captive cover screws.! WARNING: Risk of Electrical Shock. High voltages may be present at electrical terminals and other exposed internal metal surfaces. Avoid contact with all metal surfaces on control when cover is removed. b. Use a reliable AC voltmeter to check the voltage between the COM and 120V or 240V terminals on line voltage models and the two 24V terminals on low-voltage models. Refer to Figure 9, Figure 10, and Figure 11. c. The voltage must be between: 20 and 30 VAC for 24 volt applications, 102 and 132 VAC for 120 volt applications, 177 and 264 VAC for 208/240 volt applications Notes: If the voltage reading is within the required range, proceed to Step 2. If the voltage reading is not within the required range, check the power source and input power wires for problems. Notes: If no entries are made for 30 seconds while programming is in progress, the control reverts to the normal temperature display. If the MENU button is not pressed after setting a new value, the new value is not saved and the A419 control reverts to the previously saved value for that function. Any saved A419 control setting values are non-volatile and remain in the control s memory during power interruptions. A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 9

10 2. Check for proper sensor operation. Disconnect all power sources to control. a. Take a temperature reading at the sensor location, using an accurate thermometer. b. Disconnect the sensor from the control. c. Use a reliable ohmmeter, to measure the resistance across the two sensor leads while the sensor is at the temperature taken in Step b. d. Refer to Figure 15 to verify that the measured temperature and resistance conform to established temperature and resistance values. e. If the measured values conform to the values in Figure 15, proceed to Step 3. f. If the sensor s measured resistance value is substantially different from the expected value for that temperature, check the sensor wiring. If sensor wiring is okay, replace the sensor. Temperature ( F) Resistance in Ohms Temperature ( C) g. Press and hold the MENU button until appears (occurs in about 2 seconds). h. Use the Up and Down buttons to change the temperature above and below the current sensor temperature until the output relay energizes and de-energizes as shown in Table 4. If the anti-short cycle delay has a time greater than 0 minutes, the relay will not energize until the timed delay has elapsed. i. If the output relay does not perform as indicated in Table 4, replace the A419 control. j. If proper operation of the A419 control is verified, reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment. Table 4: A419 Output Relay Operation Mode Cutout Cut-in Operating Mode Cooling Heating Cooling Output Relay Energized at plus differential minus differential Output Relay De-energized at minus differential plus Heating differential Note: When the relay is energized, the N.O. contacts are closed and the LED is illuminated. Figure 15: Nominal Temperature vs. Sensor Resistance 3. Check the A419 for proper operation. a. Perform Troubleshooting Steps 1 and 2 before performing this step. b. Disconnect the load from the output relay terminals. c. Ensure that the Touchpad Lock jumper is installed, so that the touchpad is unlocked. d. Reconnect the sensor leads and supply power to the control. e. Replace the cover. f. Check the control settings for proper values. 10 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

11 Fault Codes A419 controls are programmed to display certain fault codes on the LCD as described in Table 5. Table 5: Fault Codes Defined Fault Code Definition System Status Solution SF flashing alternately with OP SF flashing alternately with SH Open temperature sensor or sensor wiring Shorted temperature sensor or sensor wiring EE Program failure Output is off Output functions according to the selected sensor failure mode (SF setting) Output functions according to the selected sensor failure mode (SF setting) See Troubleshooting section. Cycle power to reset the control. See Troubleshooting section. Cycle power to reset the control. Reset the control by pressing the Menu button. If problems persist, replace the control. Repairs and Replacement Do not attempt to repair or recalibrate the A419 Control. In case of a defective or improperly functioning control, contact your nearest Authorized Johnson Controls/PENN Distributor or Sales Representative. When contacting your Johnson Controls/PENN distributor, have the model number of the control available. This number can be found on the label inside the cover of the control. Ordering Information Refer to Table 6 to order controls and accessories. Table 6: Ordering Information Product Code Item Number A419ABC-1C A419AEC-1C A419GBF-1C A419GEF-1C A99BB-200C A99BA-200C A99BB-25C BKT287-1R BKT287-2R PLT344-1R Line Voltage, NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included Line Voltage, NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included 24 VAC, NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included 24 VAC, NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included Replacement Temperature Sensors Accessory Mounting Hardware Description Supply Voltage: 120 or 240 VAC Range: -30 to 212 F (-34 to 100 C) Differential: 1 to 30F (1 to 30C ) Sensor Lead Length: NEMA 1 Models 6-1/2 ft (2 m), NEMA 4X Models 9 in (0.25 m) Supply Voltage: 24 VAC, Class 2 Range: -30 to 212 F (-34 to 100 C) Differential: 1 to 30F (1 to 30C ) Sensor Lead Length: NEMA 1 Models 6-1/2 ft (2 m), NEMA 4X Models 9 in (0.25 m) PTC Sensor with 6-1/2 ft (2 m) Leads PTC Sensor with 6-1/2 ft (2 m) Shielded Leads PTC Sensor with 9 in (0.25 m) 12 in. (305 mm) long DIN Rail 36 in. (914 mm) long DIN Rail Two End Clamps for DIN Rail Mounting CLK350-2C Digital Clock 7-Day Programmable Digital Clock for controlling Temperature Offset Function WEL11A-601R Immersion Well Immersion Well for applying sensor in fluid applications A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures 11

12 Technical Specifications Product Range Differential Range A419 Series Electronic Temperature Controls with NEMA 1 General Purpose or NEMA 4X Watertight, Corrosion-Resistant Enclosures -30 to 212 F (-34 to 100 C) 1 to 30F (1 to 30C ) Supply Voltage 24 VAC, 60 Hz, Class 2: A419GBF-1 (NEMA 1 Enclosure Model) A419GEF-1 (NEMA 4X Watertight Enclosure Model) 120 or 240 VAC, 60 Hz: A419ABC-1 (NEMA 1 Enclosure Model) A419AEC-1 (NEMA 4X Watertight Enclosure Model) Power Consumption 1.8 VA Maximum Output Relay Contacts Electrical Ratings 24 VAC Models: A419GBF-1 (NEMA 1 Enclosure) A419GEF-1 (NEMA 4X Watertight Enclosure) 100 VA, 30 VAC maximum, Class 2 120/240 VAC Models: A419ABC-1 (NEMA 1 Enclosure) A419AEC-1 (NEMA 4X Watertight Enclosure) Applied Voltage: 120 VAC 208 VAC 240 VAC Horsepower N.O. (N.C.): 1 (0.25) hp 1 (0.33) hp 1 (0.5) hp Full Load Amperes N.O. (N.C.): 16 (5.8) A 9.2 (4.0) A 8.0 (4.9) A Locked Rotor Amperes N.O. (N.C.): 96 (34.8) A 55.2 (24) A 48 (29.4) A Non-inductive Amperes N.O. (N.C.): 15 (10) A 10 (10) A 10 (10) A Pilot Duty: 125 VA (N.O. 24 to 240 VAC 125 VA (N.C. 120 to 240 VAC 50 VA (N.C. 24 VAC Sensor Type A99BB Type PTC Sensor (See Table 6) Control Ambient Temperature Ambient Humidity Operating: Shipping: -26 to 140 F (-32 to 60 C) -40 to 185 F (-40 to 85 C) 0 to 95% RH Non-condensing; Maximum Dew Point: 85 F (29 C) Control Material Case and Cover: NEMA 1 High-Impact Thermoplastic NEMA 4X Watertight, Corrosion-Resistant, High-Impact Noryl Thermoplastic Agency Listings UL: File E27734; CCN s XAPX (US), XAPX7 (Canada) FCC: CFR 47, Part 15, Class A. DOC, Class A The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, contact Application Engineering at Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

System 350 P352AB Electronic Pressure Control Series

System 350 P352AB Electronic Pressure Control Series System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

System 350 S350C Temperature Slave Stage Module

System 350 S350C Temperature Slave Stage Module FANs 930, 930.5, 125, 121 Product/Technical Bulletin Issue Date April 8, 2014 System 350 Temperature Slave Stage Module The Temperature Slave Stage Module is used in conjunction with the A350 Temperature

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation Instructions M9206-Bxx-2S Issue Date May 14, 2003 M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation IMPORTANT: Use this M9206-Bxx-2S Series actuator to control equipment

More information

System 350 A350E Electronic Cooling Control

System 350 A350E Electronic Cooling Control FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0614 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw

More information

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control

More information

M9216 Series Electric Spring Return Actuators

M9216 Series Electric Spring Return Actuators *34636461G* 34-636-461, Rev. J Installation Instructions M9216 Issue Date October 217 M9216 Series Electric Spring Return Actuators Installation IMPORTANT: The M9216 Series actuator is intended to control

More information

A25 Series Warm Air Control with Manual Reset

A25 Series Warm Air Control with Manual Reset FANs 125, 121 Product/Technical Bulletin A25 Issue Date 0316 A25 Series Warm Air Control with Manual Reset The A25 Series Warm Air Control with Manual Reset is designed to shut down fans, burners, dampers,

More information

F261 Series Fluid Flow Switches

F261 Series Fluid Flow Switches F261 Series Fluid Switches Product Bulletin Code No. LIT-12011987 Issued March 9, 2015 The F261 Series Switches respond to fluid flow in lines carrying water, ethylene glycol, or other nonhazardous fluids.

More information

P70, P72, and P170 Controls for Low Pressure Applications

P70, P72, and P170 Controls for Low Pressure Applications Master Catalog 125 Pressure Controls Section P Product/Technical Bulletin Issue Date 0900 P70, P72, and P170 Controls for Low Pressure Applications The P70, P72, and P170 controls for low pressure applications

More information

VA-7450 Series. Electric Valve Actuators

VA-7450 Series. Electric Valve Actuators 34-636- 771, Rev. D Installation Instructions VA-7450 Series Issue Date 0216 VA-7450 Series Electric Valve Actuators Applications VA-7450 Series Electric Valve Actuators provide on/off, floating, or proportional

More information

P70, P72 and P170 Series Controls for High Pressure Applications

P70, P72 and P170 Series Controls for High Pressure Applications Installation Instructions P70 Issue Date October 16, 2002 P70, P72 and P170 Series Controls for High Pressure Applications Application P70, P72 and P170 Series Controls for High Pressure Applications provide

More information

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators Installation D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators IMPORTANT: The D- Series actuators are intended to control equipment under normal operating conditions. Where failure

More information

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m) Installation Instructions D24-53 Issue Date November 4, 23 D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m) Installation IMPORTANT: The D24-53 Series actuator is intended to control

More information

G72x Series Direct Spark Ignition Controls

G72x Series Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G72x Issue Date 1299 G72x Series Direct Spark Ignition Controls Figure 1: G72x Direct Spark Ignition

More information

P66 Series Electronic Fan Speed Controls

P66 Series Electronic Fan Speed Controls FANs 125, 121 Pressure Controls Section P Product/Technical Bulletin P66 Issue Date 0498 P66 Series Electronic Fan Speed Controls The P66 is a pressure actuated electronic motor speed controller. This

More information

F61 Series Standard Flow Switches

F61 Series Standard Flow Switches Installation Instructions F61 Issue Date July 30, 2002 F61 Series Standard Switches Installation IMPORTNT: ll F61 Series Switches are intended to control equipment under normal operating conditions. Where

More information

VA-4233-GGx Series Electric Valve Actuators

VA-4233-GGx Series Electric Valve Actuators Installation Instructions Issue Date August 11, 2003 VA-4233-GGx Series Electric Valve Actuators Installation Refer to Figures 2 through 4 for proper actuator orientation before attempting to make the

More information

Applications. A421 Series Standard Electronic Temperature Controls Installation Guide

Applications. A421 Series Standard Electronic Temperature Controls Installation Guide A421 Series Standard Electronic Temperature Controls Installation Guide Applications Important: Use this A421 Series Electronic Temperature Control only as an operating control. Where failure or malfunction

More information

YCCS TE-6800 Series Temperature Sensors

YCCS TE-6800 Series Temperature Sensors YCCS TE-6800 Series Temperature Sensors TE-68xx-xNN0S Installation Instructions 85-YIM-B-070 Applications The York Commercial Comfort System (YCCS) TE-68xx-xNN0S Series Temperature Sensors provide temperature

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date April 8, 2014 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is

More information

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators Product Bulletin M91xxx Issue Date September 2017 M9116, M9124, and M9132 Series Electric Non-spring Return Actuators The M91xx Series includes M9116, M9124, and M9132 models. All of these direct-mount

More information

G76x Direct Spark Ignition Controls

G76x Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G76x Issue Date 0400 G76x Direct Spark Ignition Controls Figure 1: G76x Direct Spark Ignition

More information

Series Y63, Y64, Y65, Y66, and Y69 Transformers

Series Y63, Y64, Y65, Y66, and Y69 Transformers Product/Technical Bulletin Issue Date December 17, 2002 Series Y63, Y, Y65, Y66, and Y69 Transformers The series Y63, Y, Y65, Y66, and Y69 transformers handle 24 power requirements from 40 VA through 300

More information

VA-715x Electric Valve Actuator

VA-715x Electric Valve Actuator Product/Technical Bulletin VA-7150 Issue Date 0513 VA-715x Electric Valve Actuator The VA-715x Series synchronous motor-driven actuator provides incremental (three wire), incremental with feedback, or

More information

VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators

VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators FIG:mntpos_H2O_app VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions VA9208-BAA-3, VA9208-BAC-3, VA9208-BDA-3 VA9208-BDC-3, VA9208-BGA-3, VA9208-BGC-3 Applications

More information

M9210-xxx-3 Electric Spring Return Actuators

M9210-xxx-3 Electric Spring Return Actuators M9210-xxx-3 Electric Spring Return Actuators Product Bulletin Code No. LIT-12011056 Issued June 1, 2009 Supersedes February 4, 2009 The M9210-xxx-3 Series Actuators are direct mount, spring return electric

More information

SetPoint 150 Controller Installation Manual

SetPoint 150 Controller Installation Manual SetPoint 150 Controller Installation Manual SetPoint 150 Controller Installation Manual is published by Uponor Wirsbo, Inc. 5925 148th Street West Apple Valley, MN 55124 Phone: (952) 891-2000 Fax: (952)

More information

P70, P72, and P170 Series Controls for High Pressure Applications

P70, P72, and P170 Series Controls for High Pressure Applications Installation Instructions P70 Issue Date 0918 P70, P72, and P170 Series Controls for High Pressure Applications Application P70, P72, and P170 Series Controls for High Pressure Applications provide high-side

More information

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators M9208-Bxx-3 Series On/Off Electric Spring Return Actuators Installation Instructions M9208-BAA-3, M9208-BAC-3, M9208-BDA-3, M9208-BDC-3, M9208-BGA-3, M9208-BGC-3 Part No. 34-636-2103, Rev. B Issued May

More information

General Description. Product Specification. Document Digital Temperature Interlock

General Description. Product Specification. Document Digital Temperature Interlock Document 474751 Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the

More information

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320 Inlet Controller SB 2000 USER'S MANUAL AUTO OPEN MANUAL PUSH TO SEARCH NEXT STAG E CLOSE Aerotech, Inc. FORM: QM 1320 4215 Legion Dr. Mason, MI 48854-1036 USA Rev. 3, Sept. 1997 Ph. (517) 676-7070 Fax

More information

G600 Series Replacement Intermittent Pilot Ignition Controls

G600 Series Replacement Intermittent Pilot Ignition Controls Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators FIG:mntpos_H2O_app VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions Part No. 14-1336-15, Rev. C Issued July 6, 2011 Supersedes December 28, 2007 Applications The

More information

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions M9208-AGA-3, M9208-AGC-3, M9208-AGA-2 Applications The M9208-AGx-x Series On/Off and Floating Point

More information

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies Installation Instructions Part No. 24-4034-42, Rev. D Issued December 9, 2011 Supersedes August 1, 1997 Applications TE-6100

More information

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Product Overview. Product Identification. Amps One CT Two CTs Three CTs AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

INSTALLATION/OPERATING INSTRUCTIONS TSC

INSTALLATION/OPERATING INSTRUCTIONS TSC INSTALLATION/OPERATING INSTRUCTIONS TSC Two-Stage Set Point Control with External Activation Two-Stage Heating (Rotation Included) Two-Stage Cooling (Rotation Included) Change-Over Control (Heat/Cool)

More information

VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators

VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators FIG:mntpos_H2O_app VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation VA9203-AGA-2Z, VA9203-AGB-2Z Applications The VA9203-AGx-2Z Series On/Off and Floating

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

VA2202-xxx-2 Series Electric Spring Return Valve Actuators VA222-xxx-2 Series Electric Spring Return Valve Actuators Product Bulletin Code No. LIT-26 Issued March 25, 28 Supersedes March, 26 VA222 Series Spring Return Electric Valve Actuators are available in

More information

Digital Room Thermostats with Touch Screen LCD

Digital Room Thermostats with Touch Screen LCD TC40 Touch Series Digital Room Thermostats with Touch Screen LCD Revision Date February 22, 2013 Features Wall-mount Display Control to match any decor Extra large easy-to-read Liquid Crystal Display (LCD),

More information

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series) Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant

More information

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

M9206-GGx-2S Series Proportional Electric Spring Return Actuators Installation Instructions M9206-GGx-2S Issue Date November 17, 2004 M9206-GGx-2S Series Proportional Electric Spring Return ctuators pplications The M9206-GGx-2S Series Proportional ctuators are direct-mount,

More information

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control SP-32, SP-32D SP-33, SP-33D SP-34, SP-34D Single Stage Temperature Control Description The SP-3x and SP-3xD series of controls are single stage, general purpose, temperature controls with wide application

More information

SEN and SEN Outdoor Air Temperature Sensors

SEN and SEN Outdoor Air Temperature Sensors FANs 216, 1628.3 Product/Technical Bulletin SEN-500-2, SEN-500-3 Issue Date 0996 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors The SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors offer

More information

G861 Series Integrated Function. Direct Spark Ignition Control

G861 Series Integrated Function. Direct Spark Ignition Control Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G861 Issue Date 0699 G861 Series Integrated Function Direct Spark Ignition Control Figure 1:

More information

VA-8020 Floating Valve Actuator

VA-8020 Floating Valve Actuator FANs 977, 1628.3 Product/Technical Bulletin VA-8020 Issue Date 0300 VA-8020 Floating Valve Actuator The VA-8020 synchronous motor-driven actuator provides floating (three wire) control of valves with up

More information

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

G821L/G822L Series Integrated Function Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G821L/G822L Issue Date 1199 G821L/G822L Series Integrated Function Direct Spark Ignition Controls

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

M9220-xxx-3 Electric Spring Return Actuators

M9220-xxx-3 Electric Spring Return Actuators M9220-xxx-3 Electric Spring Return Actuators Product Bulletin Code No. LIT-12011057 Issued September 2017 The M9220-xxx-3 Actuators are direct mount, spring return electric actuators that operate on these

More information

AV-8020 Series Floating Control Actuated Valve

AV-8020 Series Floating Control Actuated Valve FANs 977, 1628.3 Product/Technical Bulletin AV-8020 Issue Date 0300 AV-8020 Series Floating Control Actuated Valve The AV-8020 is an electric actuator/brass valve combination that furnishes floating control

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

TM-9100 Series Room Command Module

TM-9100 Series Room Command Module FANs 216, 1628.3 Product/Technical Bulletin TM-9100 Issue Date 0400 TM-9100 Series Room Command Module The TM-9100 Series Room Command Modules are designed for use with the TC-9100 series of DDC (Direct

More information

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators VA9104-xGA-1S ii01.cdr VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators Installation Instructions Part No. 14-1336-7, Rev. B Issued December 28, 2007 Supersedes April 12, 2006 Applications

More information

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data Fan Coil Thermostat Feature: Selectable analog & digital output Selectable fan speed contact Selectable Fahrenheit or Celsius scale Manual Night Set Back override (programmable) Multi level lockable access

More information

KE2 FanControl Installation Instructions

KE2 FanControl Installation Instructions Installation N.2.1 November 2011 Installation Instructions KE2 Therm Solutions Providing Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems Page 2 For condensed installation

More information

BAPI-Stat 3 Room Sensor

BAPI-Stat 3 Room Sensor Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read

More information

M9208-xxx-x Series Electric Spring Return Actuators

M9208-xxx-x Series Electric Spring Return Actuators M9208-xxx-x Series Electric Spring Return Actuators Product Bulletin M9208-GGx-x, M9208-AGx-x, M9208-Bxx-3 The M9208-xxx-x Series Electric Spring Return Actuators provide control of dampers in Heating,

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

CSD Series Current Devices Split Core

CSD Series Current Devices Split Core CSD Series Current Devices Split Core Installation Instructions CSD-CF0A0-1 CSD-CF0J0-1 CSD-CA1G0-1 Part. 24-10345-34, Rev. D Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch

More information

WF-5110R True Sine Wave Inverter

WF-5110R True Sine Wave Inverter Operator s Manual WF-5110R True Sine Wave Inverter WF-9900 Series WF-5110R ( The Inverter model number is located on the label on top of the enclosure) Distributed in the U.S.A. and Canada by ARTERRA DISTRIBUTION

More information

R1000 Series Relays. Features and Benefits. Enclosed Relay Contacts Delivers maximum durability and extends life; inhibits corrosion and dust build-up

R1000 Series Relays. Features and Benefits. Enclosed Relay Contacts Delivers maximum durability and extends life; inhibits corrosion and dust build-up Master atalog 125 s and ontactors Section R Product Bulletin R1000 Issue Date 0493 R1000 Series s The R1000 Series s switch line voltage devices from low voltage controllers. Plug-in DPDT relays and snap-in

More information

VA-4233-AGx Series Electric Valve Actuators

VA-4233-AGx Series Electric Valve Actuators Installation Instructions VA-4233 No. 1 Issue Date June 30, 2014 VA-4233-AGx Series Electric Valve Actuators Installation Refer to Figures 2 through 4 for proper actuator orientation before attempting

More information

M9109 Series Electric Non-spring Return Actuators

M9109 Series Electric Non-spring Return Actuators 34-636- 1190, Rev. D Installation Instructions M9109 Issue Date 03/1/16 M9109 Series Electric Non-spring Return Actuators Installation IMPORTANT: Use this M9109 Series actuator only to control equipment

More information

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger Document: PRODSPEC-140 Revision: G DCN No. 106512 Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger 1. GENERAL DESCRIPTION 1.1 General Description Fully regulated, constant voltage,

More information

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1484, Rev. B Installation Instructions M9109-GGx-4 Issue Date March 2016 M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators Installation IMPORTANT: The M9109-GGx-4 Series Electric

More information

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1468, Rev. B Installation Instructions M9106-GGx-4 Issue Date March 2016 Installation IMPORTANT: The M9106-GGx-4 Electric Actuator

More information

PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls. Instruction Sheet PA October 2007

PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls. Instruction Sheet PA October 2007 Instruction Sheet PA-00281 October 2007 PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls PS1 Single High and Low Pressure & PS2 Dual Pressure Refrigeration Controls THE FLEXIBLE

More information

M9203-xxx-2(Z) Series Electric Spring Return Actuators

M9203-xxx-2(Z) Series Electric Spring Return Actuators M9203-AGx-2(Z), M9203-GGx-2(Z), M9203-Bxx-2(Z) M9203-xxx-2(Z) Series Electric Spring Return Actuators Code No. LIT-1900682 Issued February 16, 2011 Description The M9203-xxx-2(Z) Series Electric Spring

More information

TC62D Installation Instructions

TC62D Installation Instructions TC62D Installation Instructions January 2007 This TC62D has a return water low temperature limit option. Using the low limit precludes using a room sensor because both sensors plug into the same port.

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service Installation Instructions VA-908x Code No. LIT-12011566 Issued August 24, 2009 Applications The VA-908x Series Electric

More information

- Wiring Brochure Zone Manager 335

- Wiring Brochure Zone Manager 335 - Wiring Brochure W 335 12/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications Rough-in Wiring Rough-in wiring instructions 3 4 Wiring

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output TCAF Series Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output Issue Date March 1, 2018 Features Ultra slim wall-mount unit to match any décor Large easy-to-read Liquid Crystal Display (LCD), with

More information

- Wiring Brochure Zone Manager 336

- Wiring Brochure Zone Manager 336 - Wiring Brochure W 336 12/08 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in 4 Wiring Brochure Wiring

More information

WF-5110R True Sine Wave Inverter

WF-5110R True Sine Wave Inverter Operator s Manual WF-5110R True Sine Wave Inverter WF-9900 Series WF-5110R ( The Inverter model number is located on the label on top of the enclosure) Distributed in the U.S.A. and Canada by ARTERRA DISTRIBUTION

More information

Instruction Manual. Blink HQ Charger. Charge on. a CarCharging Company

Instruction Manual. Blink HQ Charger. Charge on. a CarCharging Company Instruction Manual Blink HQ Charger a CarCharging Company 2014 by Blink Network, LLC No part of the contents of this document may be reproduced or transmitted in any form or by any means without the express

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners YD360/480/600, YJ-30/-40/-50 and J30/40/50 YD Models 642546-UAI-A-080 GENERAL Standard operation

More information

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

User Manual. T6 Tachometer. Online:   Telephone: P.O. Box St. Petersburg, Florida 33736 User Manual T6 Tachometer Online: www.phareselectronics.com Telephone: 727-623-0894 P.O. Box 67251 St. Petersburg, Florida 33736 Table of Contents Overview... 1 Description... 1 Wiring... 1 T6 Tachometer

More information

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION! INSTALLATION INSTRUCTIONS FOR SYMCOM S MOTORSAVER MODEL 460 BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

More information

VA-715x Electric Valve Actuator

VA-715x Electric Valve Actuator Product/Technical Bulletin VA-7150 Issue Date March 31, 2014 VA-715x Electric Valve Actuator The VA-715x Series synchronous motor-driven actuator provides incremental (three wire), incremental with feedback,

More information

WARNING IMPORTANT

WARNING IMPORTANT 75-540.0 5H0847510000 September, 2015 INSTALLATION/SETUP INSTRUCTIONS Electronic Mild Temperature Thermostat gas-fired duct furnace/make-up air units Model Series: D, H, I, & O Application The Electronic

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

R81EAA-2 Economizer Circuit Board

R81EAA-2 Economizer Circuit Board FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration

More information

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller LC-ZEC200-xxxx Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller Description The CCS Variable Air Volume (VAV) Zone Pressure Independent Damper Controllers

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

E Series CE Approved Intermittent Pilot Ignition Control

E Series CE Approved Intermittent Pilot Ignition Control Installation Instructions Issue Date January 11, 2013 E Series CE Approved Intermittent Pilot Ignition Control Application The E Series CE Approved Intermittent Pilot Ignition Control is a safety control

More information

Powerware Vdc Extended Battery Cabinet User s Guide.

Powerware Vdc Extended Battery Cabinet User s Guide. Powerware 9125 48 Vdc Extended Battery Cabinet User s Guide www.powerware.com FCC Part 15 Class A EMC Statements NOTE This equipment has been tested and found to comply with the limits for a Class A digital

More information

MA40-704X Series MA41-707X Series MA41-715X Series

MA40-704X Series MA41-707X Series MA41-715X Series MA4-74X Series MA4-77X Series MA4-75X Series SmartX Actuators Spring Return Two-Position General Instructions Application SmartX Direct Coupled Actuators are designed to be used in both damper and valve

More information

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication

More information

M100F Incremental Motor Actuator R81F Interface Board

M100F Incremental Motor Actuator R81F Interface Board Installation Sheets Manual 121 Motor Actuators Section M Technical Bulletin M100F Issue Date 0493 M100F Incremental Motor Actuator R81F Interface Board Application Details Figure 1: M100 Motor Actuator

More information

Temperature Controller OVATION 214 User's Guide

Temperature Controller OVATION 214 User's Guide Temperature Controller User's Guide Read this guide carefully before using the controller. 890-00045 rev.00 TABLE OF CONTENTS Page TABLE OF CONTENTS... 2 PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System Product Bulletin Code No. LIT-12011620 Issued July 2, 2014 RA-1250 Thermal Dispersion Fan Inlet Sensor Airflow Measuring System averages

More information