SafeRing / SafePlus Retrofit Motor Operation on 3PAE Mechanism F and SGT Modules

Size: px
Start display at page:

Download "SafeRing / SafePlus Retrofit Motor Operation on 3PAE Mechanism F and SGT Modules"

Transcription

1 SafeRing / SafePlus Retrofit Motor Operation on 3PAE Mechanism F and SGT Modules Installation Instructions Document status Responsible RELEASED NODIS Location Date Name Prepared NODIS 8/11/07 MUHU Checked NODIS 8/11/07 MARE Approved NODIS 8/11/07 OLGR Title SAFERING/SAFEPLUS RETROFIT MOTOR OPERATION ON 3PAE MECHANISM, F AND SGT MODULES Language EN/NO 1/31

2 General Safety Instructions! - Check that the installation, putting into service and maintenance of this apparatus is carried out by qualified personnel with knowledge of the apparatus and all the procedures as laid out in this installation and service instruction manual. - To perform the following installation requires a vocational training (electrician, electrical engineer) and some years of experience. - Make sure the standard and legal prescriptions are adhered to during the installation, putting into service and maintenance, so that all procedures are carried out in strict compliance to the rules of good working practice and safety at the work site. - Please read this instruction manual and plan your work before starting the installation. - Strictly follow the information given in this instruction manual. - Pay special attention to the danger notes as indicated in this manual by the following symbol: - Check and ensure that the personnel operating the apparatus have the instruction manual at hand, as well as the necessary information for correct installation. - Before starting the retrofit upgrade, please de-energize the switchgear by operating the switch-fuse-disconnector to open position. - Check that all mechanism springs are discharged. If you have doubts, close and open the switch. 2/31

3 Sikkerhetsinstruks! - Sørg for at installasjon, idriftsettelse og vedlikehold er utført av kvalifisert personell som har kjennskap til utstyret som blir installert. Vedkommende må også kjenne til prosedyrer som er beskrevet i dette installasjonsheftet. - For å utføre følgende installasjon kreves yrkesfaglig erfaring som elektriker, elektroingeniør eller liknende. - Sørg for at sikkerheten rundt installasjonsarbeidet er ivaretatt i henhold til nasjonale normer og forskrifter. Arbeidet utføres av en fagperson. - Les manualen nøye før du starter arbeidet som er beskrevet i dette dokumentet. - Utfør installeringen nøyaktig slik som beskrevet i denne manualen. - Vær spesielt nøye med å lese og følge anvisninger når det er indikert med fare symbolet: - Sørg for at betjeningspersonell har dette installasjonsheftet og har fått nødvendig informasjon når de betjener det installerte utstyret. - Før du starter med installasjonen, vennligst sørg for at avgangen som det skal jobbes på er strømløs og at bryteren er utkoblet. - Sørg for at alle fjærer på mekanismene er avspent. Hvis du er i tvil, kan du lukke og åpne bryteren. 3/31

4 Installation procedure 1. Operate the switch-fuse-disconnector to open position Betjen lastbryteren til utkoblet stilling 2. Please observe that the operating springs are not charged Observer at koblingsfjærene ikke er forspente 3. Unscrew the locking screw and remove the upper front cover Løsne låseskruen og fjern det øvre frontdekselet 4/31

5 5 6 4 * *Depending on SafeRing / SafePlus production year, the position indicator may be different compared to the drawing above. Please refer to Appendix A, if your position indicator is different. *Avhengig av når SafeRing / SafePlus anlegget er produsert, kan stillingsindikeringen være forskjellig fra tegningen over. Hvis dette er tilfelle, vennligst se Appendix A for eldre stillingsindikatorer. 4. Unscrew the fixing bracket for capacitive voltage indication Skru av festebraketten for kapasitiv spenningsindikering 5. Unscrew and remove the interlocking bracket Skru av forriglingsbraketten 6. Unscrew the push button bracket and remove it Skru av braketten med trykknapper og fjern denne 5/31

6 S8 S8 Deactivated * Activated 7. Fix the auxiliary switch marked S8 to the mechanism with 2 pieces of M4x6 screws Signalvenderen merket S8 festes til mekanismen med 2 stk M4x6 skruer *Please charge the springs with an operating handle and rotate the shaft back and forth in this position. Observe that the auxiliary switch marked S8 is both activated and deactivated. When the shaft is rotated clockwise until none back-lash is left, the auxiliary switch shall be activated. PLEASE WATCH YOUR FINGERS, SPRINGS ARE CHARGED! *Vennligst spenn koblingsfjærene med en betjeningsspak. Roter betjeningsspaken i denne posisjonen mot og med klokka. Observer at signalvenderen merket S8 aktiveres/deaktiveres vha. dødgangen på akselen. Når akselen dreies medurs inntil all dødgang er tatt opp, skal signalvender være aktivert. OBS! PASS FINGRENE, FJÆRER ER OPPSPENT! 6/31

7 Push direction Trykkretning 8 Push direction Trykkretning 9 8. Please discharge the closing spring of the mechanism by pressing the operating lever as shown PLEASE WATCH YOUR FINGERS! Avspenn innkoblingsfjæren ved å trykke på utløserstaget for mekanismen som vist OBS! PASS FINGRENE! 9. Please discharge the opening spring of the mechanism by pressing the operating lever as shown PLEASE WATCH YOUR FINGERS! Avspenn utkoblingsfjæren ved å trykke på utløserstaget for mekanismen som vist OBS! PASS FINGRENE! 7/31

8 Contactor Kontaktelement 10 S01 S02 X1 M6 x 10 MRT-TT S6 M4 x 10 MRT-TT 10. Fix the contactors to the new push button bracket NOTICE! Make sure that the numbers on the bracket, S01 and S02, correspond with the numbers written on the wires attached to the contactors Fest kontaktelementene til ny brakett med trykknapper OBS! Numrene S01 og S02 på braketten skal samsvare med numrene som står på ledningene til kontaktelementene 11. Fix control unit marked X1 to the mechanism with 2 pieces of M6x10 screws Fest rekkeklemme merket X1 til mekanismen med 2 stk M6x10 skruer 12. Fix the auxiliary switch marked S6 behind the front bracket of the mechanism with 2 pieces of M4x10 screws Monter signalvenderen merket S6 på baksiden av frontbraketten til mekanismen med 2 stk M4x10 skruer 8/31

9 M5 x 10 MRT-TT Y 1 Y 2 M5 x 10 MRT-TT X1 S6 Trip coil linkage Utløserarm Fix the trip coil Y1 and the closing coil Y2 to the mechanism with M5x10 screws Monter utløserspolen Y1 og innkoblingsspolen Y2 på mekanismen med M5x10 skruer 14. Fix the trip coil linkages for coils Y1 and Y2 to the operating lever with locking washers, as shown for the Y1 coil Fest utløserarmene for spolene Y1 og Y2 til utløserstaget med låseskiver, som vist for spole Y1 9/31

10 15. Snap on protection on the edges of the mechanism to avoid damage of wires Monter kantbeskyttelse på mekanismen for å unngå skade på ledninger X1 Y 1 Y 2 S10 S7 16. Pull the position indicator maximum 2 mm out and fit the auxiliary switch marked S7 and S10 behind the camshaft, as shown in the picture Fix the auxiliary switch with 2 pieces of M4x10 screws Dra ut stillingsindikeringen maksimalt 2 mm og vipp signalvenderen merket S7 og S10 bak kamakselen, som vist på bildet Monter signalvenderen med 2 stk M4x10 skruer 10/31

11 Insert with this side towards you Sett inn med denne siden mot deg 18 Trip lever Utløserarm 17. Remove transport safety screw and nut Fjern skrue og mutter for transport sikkerhet 18. Remove shaft extension piece Fjern akselforlengeren 19. Insert the motor drive on the operating shaft Før motoren inn på betjeningsakselen 20. Insert the brass bearing on the operating shaft Før messinglageret inn på betjeningsakselen 21. Insert bracket with push buttons on the operating shaft Fix it with 3 pieces of M6x30 screws Make sure that both trip levers of the mechanism are inserted into the push buttons Sett braketten med trykknapper inn på betjeningsakselen Fest den med 3 stk M6x30 skruer Sørg for at begge utløserarmene er plassert inne i hver sin trykknapp 11/31

12 23 Loctite 24 If the module is not equipped with interlocked cable cover, please continue to step number 28 Dersom feltet ikke har kabelromsforrigling, vennligst gå til punkt Remove standard nut from the rear side of the interlocking bracket Fjern mutteren fra pressbolten på baksiden av forriglingsbraketten 23. Apply Loctite glue on the surface of the special nut and mount it where the standard nut was removed Bruk Loctite lim på spesialmutteren og skru den fast på pressbolten 24. Mount the interlocking lever on the special nut Før forriglingsarmen inn på spesialmutteren 12/31

13 26 Locking washer Sikringskive 25 Slot Spor M4x16 screw Fit the interlocking lever in the slot as indicated by arrow Før forriglingsarmen inn i sporet som vist med pil 26. Fix the interlocking lever with a washer Fest forriglingsarmen med en sikringskive 27. Fix the interlocking bracket to the mechanism with 2 pieces of M4x10 screws Replace the screw, as indicated by the arrow, with 1 piece of M4x16 screw Fest forriglingsbraketten tilbake på mekanismen med 2 stk M4x10 skruer Erstatt skruen, som vist med pil, med 1 stk M4x16 skrue 13/31

14 28. Operate the earthing switch to closed position Betjen jordslutter til innkoblet posisjon 29. Open the lower front cover Åpne det nedre frontdekselet 14/31

15 Fuse trip indicator Flaggaksel Fix the auxiliary switch marked S13 with 2 pieces of M4x10 screws Skru på signalvenderen merket S13 med 2 stk M4x10 skruer 31. Fix the auxiliary switch marked S9 with 2 pieces of ST4.8x9.5 pan head tapping screws Skru på signalvenderen merket S9 med 2 stk ST4.8x9.5 plateskruer Please observe that the auxiliary switch marked S9 is both activated and deactivated, when fuse trip indicator is moved up and down, as shown in the picture Vennligst observer at signalvenderen merket S9 aktiveres og deaktiveres når flaggakselen beveges opp og ned, som vist i bildet over 15/31

16 32. Fix the new interlocking bracket to the mechanism with 2 pieces of M4x10 screws (See picture of the bracket) Omit this step if you have interlocked cable cover Monter på ny forriglingsbrakett med 2 stk M4x10 skruer (Se bildet av braketten) Hopp over dette punktet hvis modulen har kabelromsforrigling 33. Fix the auxiliary switch marked S15 below the interlocking bracket with 2 pieces of M4 lock nuts Monter signalkontakten merket S15 på undersiden av forriglingsbraketten med 2 stk M4 låsemuttere 16/31

17 Mount the fixing bracket for capacitive voltage indication which was removed during step 4 Monter tilbake festebraketten for kapasitiv spenningsindikering som ble fjernet under punkt 4 IMPORTANT! Connect the wires from motor operation, coils and auxiliary switches to control unit X1 Fix the wires to avoid any damages from moving parts VIKTIG! Kontroller at motor, spoler og signalkontakter er tilkoblet rekkeklemmelist X1 Kontroller at alle ledningene er festet slik at skader fra bevegelige deler unngås 35. Lock both the upper and the lower front cover Lukk både det øvre og det nedre frontdekselet 17/31

18 6 APPENDIX A Unscrew the fixing bracket for capacitive voltage indication Skru av festebraketten for kapasitiv spenningsindikering 5. Unscrew and remove the position indicator Skru av stillingsindikeringen 6. Unscrew and remove the interlocking bracket Skru av forriglingsbraketten 7. Unscrew the push button bracket and remove it Skru av braketten med trykknapper og fjern denne 18/31

19 S8 S8 Deactivated * Activated 8. Fix the auxiliary switch marked S8 to the mechanism with 2 pieces of M4x6 screws Signalvenderen merket S8 festes til mekanismen med 2 stk M4x6 skruer *Please charge the springs with an operating handle and rotate the shaft back and forth in this position. Observe that the auxiliary switch marked S8 is both activated and deactivated. When the shaft is rotated clockwise until none back-lash is left, the auxiliary switch shall be activated. PLEASE WATCH YOUR FINGERS, SPRINGS ARE CHARGED! *Vennligst spenn koblingsfjærene med en betjeningsspak. Roter betjeningsspaken i denne posisjonen mot og med klokka. Observer at signalvenderen merket S8 aktiveres/deaktiveres vha. dødgangen på akselen. Når akselen dreies medurs inntil all dødgang er tatt opp, skal signalvenderen være aktivert. OBS! PASS FINGRENE, FJÆRER ER OPPSPENT! 19/31

20 Push direction Trykkretning 9 Push direction Trykkretning Please discharge the closing spring of the mechanism by pressing the operating lever as shown PLEASE WATCH YOUR FINGERS! Avspenn innkoblingsfjæren ved å trykke på utløserstaget for mekanismen som vist OBS! PASS FINGRENE! 10. Please discharge the opening spring of the mechanism by pressing the operating lever as shown PLEASE WATCH YOUR FINGERS! Avspenn utkoblingsfjæren ved å trykke på utløserstaget for mekanismen som vist OBS! PASS FINGRENE! 20/31

21 Contactor Kontaktelement 11 S01 S02 X1 M6 x 10 MRT-TT S6 M4 x 10 MRT-TT 11. Fix the contactors to the new push button bracket NOTICE! Make sure that the numbers on the bracket, S01 and S02, correspond with the numbers written on the wires attached to the contactors Fest kontaktelementene til ny brakett med trykknapper OBS! Numrene S01 og S02 på braketten skal samsvare med numrene som står på ledningene til kontaktelementene 12. Fix control unit marked X1 to the mechanism with 2 pieces of M6x10 screws Fest rekkeklemme merket X1 til mekanismen med 2 stk M6x10 skruer 13. Fix the auxiliary switch marked S6 behind the front bracket of the mechanism with 2 pieces of M4x10 screws Monter signalvenderen merket S6 på baksiden av frontbraketten til mekanismen med 2 stk M4x10 skruer 21/31

22 M5 x 10 MRT-TT Y 1 Y 2 M5 x 10 MRT-TT X1 S6 Trip coil linkage Utløserarm Fix the trip coil Y1 and the closing coil Y2 to the mechanism with M5x10 screws Monter utløserspolen Y1 og innkoblingsspolen Y2 på mekanismen med M5x10 skruer. 15. Fix the trip coil linkages for coils Y1 and Y2 to the operating lever with locking washers, as shown for the Y1 coil Fest utløserarmene for spolene Y1 og Y2 til utløserstaget med låseskiver, som vist for spole Y1 22/31

23 16. Snap on protection on the edges of the mechanism to avoid damage of wires Monter kantbeskyttelse på mekanismen for å unngå skade på ledninger X1 Y 1 Y 2 17 S10 S7 17. Fix the auxiliary switch marked S7 and S10 with 2 pieces of M4x10 screws Monter signalvenderen merket S7 og S10 med 2 stk M4x10 skruer 23/31

24 Insert with this side towards you Sett inn med denne siden mot deg 19 Trip lever Utløserarm 18. Remove transport safety screw and nut Fjern skrue og mutter for transport sikkerhet 19. Remove shaft extension piece Fjern akselforlengeren 20. Insert the motor drive on the operating shaft Før motoren inn på betjeningsakselen 21. Insert the brass bearing on the operating shaft Før messinglageret inn på betjeningsakselen 22. Insert bracket with push buttons on the operating shaft Fix it with 3 pieces of M6x30 screws Make sure that both trip levers of the mechanism are inserted into the push buttons Sett braketten med trykknapper inn på betjeningsakselen Fest den med 3 stk M6x30 skruer Sørg for at begge utløserarmene er plassert inne i hver sin trykknapp 24/31

25 24 Loctite 25 If the module is not equipped with interlocked cable cover, please continue to step number 29 Dersom feltet ikke har kabelromsforrigling, vennligst gå til punkt Remove standard nut from the rear side of the interlocking bracket Fjern mutter fra pressbolten på baksiden av forriglingsbraketten 24. Apply Loctite glue on the surface of the special nut and mount it where the standard nut was removed Bruk Loctite lim på spesialmutteren og skru den fast på pressbolten 25. Mount the interlocking lever on the special nut Før forriglingsarmen inn på spesialmutteren 25/31

26 27 Locking washer Sikringskive 26 Slot Spor M4x16 screw Fit the interlocking lever in the slot as indicated by arrow Før forriglingsarmen inn i sporet som vist med pil 27. Fix the interlocking lever with a washer. Fest forriglingsarmen med en sikringskive. 28. Fix the interlocking bracket to the mechanism with 2 pieces of M4x10 screws Replace the screw, as indicated by the arrow, with 1 piece of M4x16 screw Fest forriglingsbraketten tilbake på mekanismen med 2 stk M4x10 skruer Erstatt skruen, som vist med pil, med 1 stk M4x16 skrue 26/31

27 29. Operate the earthing switch to closed position Betjen jordslutter til innkoblet posisjon 30. Open lower front cover Åpne nedre frontdeksel 27/31

28 Fuse trip indicator Flaggaksel Fix the auxiliary switch marked S13 with 2 pieces of M4x10 screws Skru på signalvenderen merket S13 med 2 stk M4x10 skruer 32. Fix the auxiliary switch marked S9 with 2 pieces of ST4.8x9.5 pan head tapping screws Skru på signalvenderen merket S9 med 2 stk ST4.8x9.5 plateskruer Please observe that the auxiliary switch marked S9 is both activated and deactivated, when fuse trip indicator is moved up and down, as shown in the picture Vennligst observer at signalvenderen merket S9 aktiveres og deaktiveres når flaggakselen beveges opp og ned, som vist i bildet over 28/31

29 33. Fix the new interlocking bracket to the mechanism with 2 pieces of M4x10 screws (See picture of the bracket) Omit this step if you have interlocked cable cover Monter på ny forriglingsbrakett med 2 stk M4x10 skruer (Se bildet av braketten) Hopp over dette punktet hvis modulen har kabelromsforrigling 34. Fix the auxiliary switch marked S15 below the interlocking bracket with 2 pieces of M4 lock nuts Monter signalkontakten merket S15 på undersiden av forriglingsbraketten med 2 stk M4 låsemuttere 29/31

30 S01 S02 X1 Y 1 Y 2 S15 S S S Cog wheel arrow shall point to the straight line Pilen i tannhjulet skal peke mot den rette linjen 35. Mount the fixing bracket for capacitive voltage indication, which was removed during step 4 Monter tilbake festebraketten for kapasitiv spenningsindikering, som ble fjernet under punkt Mount the position indicator which was removed during step 5 Monter tilbake stillingsindikeringen som ble fjernet under punkt 5 IMPORTANT! Connect the wires from motor operation, coils and auxiliary switches to control unit X1. Fix the wires to avoid any damages from moving parts VIKTIG! Kontroller at motor, spoler og signalkontakter er tilkoblet rekkeklemmelist X1. Kontroller at alle ledningene er festet slik at skader fra bevegelige deler unngås 30/31

31 Make sure that the position indicator for the switch-fusedisconnector show the correct position Påse at stillingsindikeringen viser korrekt stillingen for bryteren 31/31

RAY. Product Manual Produkthåndbok

RAY. Product Manual Produkthåndbok Product Manual Produkthåndbok ENG/NO Technical Specifications/ Tekniske Spesifikasjoner Type/Type 1 Type/Type 2 Description/ Beskrivelse Product number/ 100310 Produktnummer Vehicle interface/ 1P 16A T1

More information

Parameters. Overview. Functions. HDL Buspro Definition for Cable. Important. Do you need help? Contact

Parameters. Overview. Functions. HDL Buspro Definition for Cable. Important.  Do you need help? Contact BUS Enabled Motorized curtain Parameters Electrical Parameters: Type Bus voltage Rated voltage Voltage range Working voltage Bus power Consumption Slave interface Rated power Rated torque Rated speed Rail

More information

Date of occurrence Location name Alnabru terminal Local time 03:40 Latitude Railway vehicle movement events Trains collision Trains collision

Date of occurrence Location name Alnabru terminal Local time 03:40 Latitude Railway vehicle movement events Trains collision Trains collision Occurrence Summary What Location Date of occurrence 29-04-16 Location name Alnabru terminal Local time 03:40 Latitude Event type Railway vehicle movement events Longitude Description On Friday 29 April

More information

BenchTop Extraction Arm FX2

BenchTop Extraction Arm FX2 The best and most cost-efficient solution for extraction of hazardous airborne contaminants, in applications where small, flexible and easy-to-use arms are required. Nederman FX2 arms are made of lightweight

More information

Installation and user manual SIDE-POWER. SE 40/125 S IP Ignition Protected thruster assembly. Thruster Systems. manual onboard!

Installation and user manual SIDE-POWER. SE 40/125 S IP Ignition Protected thruster assembly. Thruster Systems. manual onboard! SIDE-POWER Thruster Systems SE 0/5 S IP Ignition Protected thruster assembly Keep this manual onboard! Installation and user manual SLEIPNER MOTOR AS P.O. Box 59 N-6 Fredrikstad Norway Tel: +7 69 0 00

More information

Goltens. instruction manual and sparepart list. goltens high. pressure pump type g1400 hp-rr

Goltens. instruction manual and sparepart list. goltens high. pressure pump type g1400 hp-rr Goltens Oslo AS instruction manual and sparepart list goltens high pressure pump type g1400 hp-rr Technical Information 72-1176 RR Weight: 15 Kg Dimension: 420 x 280 x 220 Max oil pressure rating (2 minutes):

More information

Installation and user manual SIDE-POWER. SE 60/185S IP Ignition Protected thruster assembly. Thruster Systems. manual onboard!

Installation and user manual SIDE-POWER. SE 60/185S IP Ignition Protected thruster assembly. Thruster Systems. manual onboard! SIDE-POWER Thruster Systems SE 60/85S IP Ignition Protected thruster assembly Keep this manual onboard! Installation and user manual SLEIPNER MOTOR AS P.O. Box 59 N-62 Fredrikstad Norway Tel: +7 69 30

More information

Verktøybasert utsugssett

Verktøybasert utsugssett Støvavsug ved kilden er den mest effektive metoden for å fange opp støv ved sliping, pussing og saging. Nederman festesett for håndverktøy fjerner støv svært effektivt under sliping, pussing og saging.

More information

Kiropraktikk- benker. ErgoStyle FX ES2000 ErgoStyle Hylo

Kiropraktikk- benker. ErgoStyle FX ES2000 ErgoStyle Hylo 2018 Kiropraktikk- benker ErgoStyle FX ES2000 ErgoStyle Hylo Ergostyle FX Flexion Distrac on Tables Variant ES5821 ES58490 Ergostyle FX Manual Flexion Standard ES58360 Tilt, Adjustable Face C4052 Single

More information

Intelligent Packaging Solutions

Intelligent Packaging Solutions Intelligent Packaging Solutions Hofstätter & Ebbesen A/S Højvangen 19 3060 Espergærde Denmark Tel +45 4912 2122 Fax +45 4912 2199 info@ultraplast.dk www.ultraplast.dk UltraPlast is a hi-tech company specializing

More information

Bybanen a success in Bergen

Bybanen a success in Bergen Bybanen a success in Bergen 90 5 904 905 221-222 Light Rail Days, Bergen 14-15 November 2016 Ivar Gubberud, Dirctor of Safety and Quality, Bybanen as The rolling stock at Bybanen 901 904 10 Variobahn 42m

More information

MORE BITE FOR YOUR MONEY PRODUCT CATALOGUE

MORE BITE FOR YOUR MONEY PRODUCT CATALOGUE Digital versjon 07/2018 MORE BITE FOR YOUR MONEY PRODUCT CATALOGUE n System for Excavators n System for Wheel Loaders n System for Front Shovel n System for Underground n Teeth & Bolts n Wear Protection

More information

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying

More information

Ivar Aasen Field Development Project

Ivar Aasen Field Development Project Ivar Aasen Field Development Project As-Built 03M 24.01.2017 Approved 02M 06.10.2016 Approved 02M 06.09.2016 Approved 01E 17.08.2016 IFR Rev. Date Reason for Issue Prepared by Reviewed by Approved by Ivar

More information

Førebuing/ Forberedelse

Førebuing/ Forberedelse Førebuing/ Forberedelse 29.11.2018 AUT4030 Automatiseringsfaget Nynorsk/Bokmål Nynorsk Informasjon til førebuingsdelen Førebuingstid Hjelpemiddel Bruk av kjelder Vedlegg Andre opplysningar Informasjon

More information

Installation and user manual SIDE-POWER. SEP 30/125S2 IP SEP 40/125S2 IP Ignition Protected thruster assembly. Thruster Systems. manual onboard!

Installation and user manual SIDE-POWER. SEP 30/125S2 IP SEP 40/125S2 IP Ignition Protected thruster assembly. Thruster Systems. manual onboard! SIDE-POWER Thruster Systems SEP 30/125S2 IP SEP 40/125S2 IP Ignition Protected thruster assembly Keep this manual onboard! Installation and user manual SLEIPNER MOTOR AS P.O. Box 519 N-1612 Fredrikstad

More information

User s Instruction Manual Flex-Lift, Collapsible & Portable Person Lift with Electrical Hoisting

User s Instruction Manual Flex-Lift, Collapsible & Portable Person Lift with Electrical Hoisting User s Instruction Manual Flex-Lift, Collapsible & Portable Person Lift with Electrical Hoisting 12A98, English Rev. 2014.10 USER S INSTRUCTION MANUAL Flex-Lift - Collapsible, Portable Person Lift with

More information

Sjøsikkerhetskonferansen 2018

Sjøsikkerhetskonferansen 2018 Sjøsikkerhetskonferansen 2018 Sjøsikkerhetskonferansen 2018 Nå IMOs klimastrategi Sveinung Oftedal Fagdirektør, Klima- og miljødepartementet Norwegian Ministry of Climate and Environment IMOs klimastrategi

More information

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers Instruction Leaflet IL2A12995H02 effective March 2012 Trip Indicator with Remote Reset for Magnum WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS

More information

ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes

ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes AIP NORGE / NORWAY ENR 3.4-1 ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes 1 Flygehøyder 1 Cruising altitudes Sivile helikoptre i trafikk til og fra oljeinstallasjoner i de områder av Nordsjøen hvor

More information

EP Ground Filter Products. I n s t a l l a t i o n a n d M a i n t e n a n c e M a n u a l. Power Quality For The Digital Age

EP Ground Filter Products. I n s t a l l a t i o n a n d M a i n t e n a n c e M a n u a l. Power Quality For The Digital Age Power Quality For The Digital Age EP Ground Filter Products I n s t a l l a t i o n a n d M a i n t e n a n c e M a n u a l www.ep2000.com 800.500.7436 EP Ground Filter Products Installation and Maintenance

More information

UniSec Operation and maintenance manual

UniSec Operation and maintenance manual Medium voltage products UniSec Operation and maintenance manual Safety 3 For your safety! 3 Skilled personnel 3 Critical messages 3 Contact us! 3 1. Introduction 4 1.1 General aspects 4 1.2 Operation and

More information

Ampgard medium voltage motor control renewal parts

Ampgard medium voltage motor control renewal parts Technical Data TD020001EN Contents Description Page General information.... 2 3 400A starter design.... 4 9 800A starter design.... 10 15 Control and potential transformers.... 16 Current transformers....

More information

TEMPER simulations of MCX-6100 filled 155 mm shell experimental properties, sympathetic

TEMPER simulations of MCX-6100 filled 155 mm shell experimental properties, sympathetic FFI-rapport 2015/01916 TEMPER simulations of MCX-6100 filled 155 mm shell experimental properties, sympathetic reaction and fragmentation studies Gunnar Ove Nevstad Forsvarets FFI forskningsinstitutt Norwegian

More information

6 x 10 Belt Disc Sander

6 x 10 Belt Disc Sander 6 x 10 Belt Disc Sander FOR HELP OR ADVISE ON THIS PRODUCT PLEASE CALL OUR CUSTOMER SERVICE HELP LINE : 01509 500400 THE MANUFACTURER RESERVES THE RIGHT TO ALTER THE DESIGN OR SPECIFICATION TO THIS PRODUCT

More information

Wilo-Control SC-Fire Jockey

Wilo-Control SC-Fire Jockey Pioneering for You Wilo-Control SC-Fire Jockey de en fr Einbau- und Betriebsanleitung Installation and operating instructions Notice de montage et de mise en service nl Inbouw- en bedieningsvoorschriften

More information

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A Medium voltage compact switchgears rated voltage 12 and 25 kv rated current 400 and 630 A 1 General The new air-insulated DRIESCHER medium voltage compact switchgears are ideal for application in secondary

More information

ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes

ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes AIP NORGE / NORWAY ENR 3.4-1 ENR 3.4 Helikopterruter ENR 3.4 Helicopter Routes 1 Flygehøyder 1 Cruising altitudes Sivile helikoptre i trafikk til og fra oljeinstallasjoner i de områder av Nordsjøen hvor

More information

Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers

Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers GE Industrial Solutions Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers This position switch actuator, mounted on the cassette using simple hardware, is an actuator or

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Technical Manual. DLM Module. This manual should remain with the unit.

Technical Manual. DLM Module. This manual should remain with the unit. Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism Effective October 2010 Supersedes June 2010 IL01301018EH03 Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD

More information

Liteline OFF. (mm) (mm) LED IP44 DALI * ** Accessories. Installation V >80

Liteline OFF. (mm) (mm) LED IP44 DALI * ** Accessories. Installation V >80 iteline (mm) 50 680 30 600 (mm) 50 00 50 50 E-nr Snro El.nr GTI ame ED color Color Unit effect 7 35 7 4 030 07 3 69 79 7399730439 iteline 600 White 35,5W 7 35 73 4 030 08 3 69 80 7399730446 iteline 600

More information

22b a. Se næste side for underdelen af Multi-tip / Go to next page for the lower part of the stool.

22b a. Se næste side for underdelen af Multi-tip / Go to next page for the lower part of the stool. 19 9 1 20 21 22b 24 19 3 9 21 22a 4 20 19 23 1 2 2 29 2 30 26 6 9 11 12 13 1 16 1 2 3 Se næste side for underdelen af Multi-tip / Go to next page for the lower part of the stool. 1 3 3 33 34 3 36 32 33

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

MCset 4-24 kv Withdrawable SF6 circuit breaker

MCset 4-24 kv Withdrawable SF6 circuit breaker Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal

More information

SD, SE, SDE, SCO series Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches,

SD, SE, SDE, SCO series Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches, 4 Electrics for Rolling Stock Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches, Change-Over-Switches 600 V to 3 kv Catalogue F84.en

More information

UTSTYR FOR LYSARMATUR EQUIPMENT FOR LIGHT FITTINGS

UTSTYR FOR LYSARMATUR EQUIPMENT FOR LIGHT FITTINGS UTSTYR FOR LYSARMATUR EQUIPMENT FOR LIGHT FITTINGS Being first is good, being smart is better, being both is Simply the Best! 1 Firmapresentasjon Company presentation PRODUKT- INFORMASJON Øglænd System

More information

Operating instructions Actuator and Emergency exit AZ/AZM 200-B30 AZ/AZM 201-B About this document. Content

Operating instructions Actuator and Emergency exit AZ/AZM 200-B30 AZ/AZM 201-B About this document. Content 1. About this document Operating instructions............pages 1 to 10 Original 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual 1ZSE 5492-155 en, Rev. 4 On-load tap-changers, type UC User s manual Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

CoolWave 2 Phase Control Board and Cable Replacement Kit

CoolWave 2 Phase Control Board and Cable Replacement Kit Instruction Sheet P/N 1102452-02 CoolWave 2 Phase Control Board and Cable Replacement Kit Use the Phase Control Board and Cable Kit to upgrade your CoolWave 2 power supply to the new configuration. NOTE:

More information

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages

More information

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use GAM cubicle (1250A) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

Product catalogue. ABB AS, Power Products Division SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus 36

Product catalogue. ABB AS, Power Products Division SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus 36 Product catalogue ABB AS, Power Products Division SF 6 -insulated Ring Main Unit, SafeRing 36 and SF 6 -insulated Compact Switchgear SafePlus 36 Content Applications SafeRing 36... 3 Applications SafePlus

More information

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. 1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM _ M MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM User's MANUAL Code: MVM Version: 01-BF Date: OCT 2005 Page 1/10 _ 1. INTRODUCTION Before starting to use your Energic plus MVM battery charger, please take

More information

VD4 Installation and service instructions kv A ka

VD4 Installation and service instructions kv A ka Medium voltage products VD4 Installation and service instructions 12... 36 kv - 630... 3150 A - 16... 50 ka Index For your safety! 1 I. Introduction 2 II. Programme for environmental protection 2 1. Packing

More information

INSTALLATION & MAINTENANCE

INSTALLATION & MAINTENANCE GB41316 INSTALLATION & MAINTENANCE Postadress/Postal address Säte/Registred office Telefon/Telephone Telefax/Facsimile F-skatt/Org no SCANDFILTER AB 556321-5572 S-512 85 SVENLJUNGA SVENLJUNGA Nat. 0325-66

More information

Product manual. SafeRing/SafePlus 36 kv SF 6. insulated Ring Main Unit and Compact Switchgear

Product manual. SafeRing/SafePlus 36 kv SF 6. insulated Ring Main Unit and Compact Switchgear Product manual SafeRing/SafePlus 3 kv SF insulated Ring Main Unit and Compact Switchgear 2 SAFERING/SAFEPLUS 3 KV PRODUCT MANUAL Contents 003 005 00 007 009 0 01 015 020 021 022 022 023 1. General description

More information

FFI-RAPPORT. Determination of detonation pressure and velocity for RDX/GAP propellant. Gunnar Ove Nevstad 17/00345

FFI-RAPPORT. Determination of detonation pressure and velocity for RDX/GAP propellant. Gunnar Ove Nevstad 17/00345 FFI-RAPPORT 17/00345 Determination of detonation pressure and velocity for RDX/GAP propellant Gunnar Ove Nevstad Determination of detonation pressure and velocity for RDX/GAP propellant Gunnar Ove Nevstad

More information

Programmer Disconnect Accessory Manual for Retrofil CB

Programmer Disconnect Accessory Manual for Retrofil CB GE Energy Programmer Disconnect Accessory Manual for Retrofil CB Programmer secondary disconnects are not provided on AKD5 legacy LVS breakers. If the customer has chosen to utilize the advanced features

More information

KEWTECH. KT56 digital multi function tester. Instruction manual

KEWTECH. KT56 digital multi function tester. Instruction manual KEWTECH KT56 digital multi function tester Instruction manual Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating

More information

Two-way cable interlock kit for Magnum fixed circuit breakers

Two-way cable interlock kit for Magnum fixed circuit breakers warning (1) Only qualified electrical personnel should be permitted to work on the equipment. (2) Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work

More information

USE AND INSTALLATION HANDBOOK

USE AND INSTALLATION HANDBOOK Date : 10/02/14 Rev. 01 PR.T : FG006172 USE AND INSTALLATION HANDBOOK DUPLEX-UP CONTROL PANEL FOR 2 ELECTRIC PUMPS WITH CURRENT CONTROL. DUPLEX-UP Via Enrico Fermi 8-35020 Polverara PD Tel.049/9772407

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #271 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 OPERATING INSTRUCTION Visit us at www.testequipmentdepot.com MODEL 3132 ANALOG INSULATION-CONTINUITY TESTER

More information

Operating Instructions

Operating Instructions FUSE 028028 Operating Instructions Monarch 9876 and 9878 Mobile Work Station (MWS ) TC987xOI Rev. AC 12/15 2007 Avery Dennison Corp. All rights reserved. Each product and program carries a respective

More information

BMW i. Freude am Fahren. Wallbox PURE. Installation instruction

BMW i. Freude am Fahren. Wallbox PURE. Installation instruction BMW i Freude am Fahren Wallbox PURE Installation instruction Imprint Bestellnummer 61 90 2 347 662 Wallbox Pure Type T2 (32 A, 7.4 kw) Publisher Bayerische Motorenwerke Aktiengesellschaft Munich, Germany

More information

Medium-Voltage Switchgear OPERATING INSTRUCTIONS

Medium-Voltage Switchgear OPERATING INSTRUCTIONS Medium-Voltage Switchgear Circuit-Breaker Switchgear Type NXAIR: Factory-Assembled, Type-Tested and Metal- Enclosed Switchgear for Indoor Installation, Air-Insulated Loss of Service Continuity Category:

More information

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

Open Chassis Star-Delta Starter User Guide

Open Chassis Star-Delta Starter User Guide Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...

More information

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK

More information

The above explanation leaves out a few details, which may frustrate a user. Here are some instructions with pictures to help you be successful.

The above explanation leaves out a few details, which may frustrate a user. Here are some instructions with pictures to help you be successful. When the user exceeds the current capacity of the MY64 multimeter, an internal fuse opens to protect the precision current shunt. Typically this occurs when the user leaves the multimeter in current measuring

More information

IAN COMPRESSOR PKO 500 A1. COMPRESSOR PKO 500 A1 Operation and Safety Notes Translation of original operation manual IE NI

IAN COMPRESSOR PKO 500 A1. COMPRESSOR PKO 500 A1 Operation and Safety Notes Translation of original operation manual IE NI COMPRESSOR PKO 500 A1 GB IE NI COMPRESSOR PKO 500 A1 Operation and Safety Notes Translation of original operation manual DK KOMPRESSOR PKO 500 A1 Drifts- og sikkerhedsinstruktioner Oversættelse af den

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com 8/05 Form #270 OPERATING INSTRUCTION MODEL 3005 DIGITAL INSULATION-CONTINUITY TESTER

More information

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers Supersedes IL 33-GS8-2 Dated 10/00 (Manually Operated Only) Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:...............................

More information

HD4-LMT. MV SF6 Circuit Breaker Installation and Service Instructions kv 1,250 A 31.5 ka

HD4-LMT. MV SF6 Circuit Breaker Installation and Service Instructions kv 1,250 A 31.5 ka HD4-LMT MV SF6 Circuit Breaker Installation and Service Instructions 17.5 kv 1,250 A 31.5 ka For your safety Make sure that the installation room ( i.e. spaces, divisions and the atmosphere ) are suitable

More information

AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500B MOTOR CONTACTOR WITH THERMAL PROTECTION 115VAC COIL

AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500B MOTOR CONTACTOR WITH THERMAL PROTECTION 115VAC COIL AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500B MOTOR CONTACTOR WITH THERMAL PROTECTION 115VAC COIL Thank you for choosing our Automatic Dust Collection System. We at Grngate have developed

More information

Tariffer og anleggsbidrag i Norden. Hvordan ser kartet ut? Trond Svartsund, Energi Norge

Tariffer og anleggsbidrag i Norden. Hvordan ser kartet ut? Trond Svartsund, Energi Norge Tariffer og anleggsbidrag i Norden. Hvordan ser kartet ut? Trond Svartsund, Energi Norge Innhold EU lovgivning Regulering i Norden Transmisjons- og distribusjonsnettariffer i Norden Anleggsbidrag i Norden

More information

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMB cubicle without earthing switch foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

INSTRUCTION MANUAL FOR

INSTRUCTION MANUAL FOR Page 1 of 8 INSTRUCTION MANUAL FOR for Vacuum Valve type HS ISO VAC Functional Description, Marking and Installation Instruction Manual no.: 1199-235 Revision 0 October, 2012 CUSTOMER INFORMATION OWNER:

More information

Cougar B Series Electric Vibrators 3 Frame

Cougar B Series Electric Vibrators 3 Frame Cougar B Series Electric Vibrators 3 Frame Go to Cougar B Series Electric Vibrators web page Operator s Manual M3929 Important MARTIN ENGINEERING HEREBY DISCLAIMS ANY LIABILITY FOR: DAMAGE DUE TO CONTAMINATION

More information

PSA MA gearbox. INA GearBOX

PSA MA gearbox. INA GearBOX LuK Repair Tractor Manual Clutches PSA MA gearbox INA GearBOX Repair Manual for the PSA MA gearbox Drain the transmission fluid (arrow). Remove the gearbox from the vehicle in accordance with the vehicle

More information

NEW EFD fuse disconnector

NEW EFD fuse disconnector NEW EFD fuse disconnector More space for finger to open fuse carrier Advantages of cylindrical fuse disconnector EFD ompliance with IE 60947-1, IE 60947-3, UL 4248-1, UL 4248-4, UL 4248-8, UL 486E and

More information

Motor-drive mechanism, type BUL. Technical guide

Motor-drive mechanism, type BUL. Technical guide Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Service Parts. John Deere 3029DF 3029TF 3029TF270. Engine. Engine Models: Generator Models: 20ROZJB REOZJB 20DSJB DSEJB.

Service Parts. John Deere 3029DF 3029TF 3029TF270. Engine. Engine Models: Generator Models: 20ROZJB REOZJB 20DSJB DSEJB. Service Parts Engine Engine Models: John Deere 3029DF 3029TF 3029TF270 Generator Models: 20ROZJB 20--40REOZJB 20DSJB 20--40DSEJB TP- 12/03b Table of Contents Description Page Description Page Introduction...

More information

Model TC-20. Tube Cut-Off Machine. Operator s Manual REV H

Model TC-20. Tube Cut-Off Machine. Operator s Manual REV H Model TC-20 Tube Cut-Off Machine Operator s Manual 90-2333 REV H Scientific Systems, Inc. 349 N. Science Park Road State College, PA 16803 www.ssihplc.com Phone: 800-441-4752 Fax: 814-238-7532 Email: sales@ssihplc.com

More information

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples. Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear

More information

5 Series Active Hybrid 5 F10

5 Series Active Hybrid 5 F10 5 Series Active Hybrid 5 F10 (since 12/2011) Legend Airbag Body reinforcement Airbag control unit High-voltage emergency separation point Gas generator Gas-filled shock absorber 12 V battery Active pedestrian

More information

Building winning teams with Total Specific Maintenance of Martin Linge, Rotating Equipment

Building winning teams with Total Specific Maintenance of Martin Linge, Rotating Equipment Building winning teams with Total Specific Maintenance of Martin Linge, Rotating Equipment Presenter: Øystein Solberg Eureka Pumps Director Operation Support Services (OSS) 1 Total Technical Safety A global

More information

Jernbaner Faste installationer Elektrisk sikkerhed, jording og returledning

Jernbaner Faste installationer Elektrisk sikkerhed, jording og returledning Dansk standard DS/IEC 62128-1:2013 1. udgave 2015-12-03 Jernbaner Faste installationer Elektrisk sikkerhed, jording og returledning Del 1: Beskyttelsesforanstaltninger mod elektrisk stød Railway applications

More information

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMVL cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

Electrically Held to Mechanically Latched Contactor

Electrically Held to Mechanically Latched Contactor Electrically Held to Mechanically Latched Contactor Bulletin 1502 Series E or later Retrofit Instructions Important User Information Read this document and the documents listed in the Additional Resources

More information

Electromagnetic Industries LLP

Electromagnetic Industries LLP GROUND FAULT CURRENT DETECTION GFM Relay (Model 252 & 262) The GFM system is designed for electrical protection, not for personnel protection Application: These Class 1 (Model GFM) Ground Fault protection

More information

INSTRUCTION MANUAL IM245. RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL

INSTRUCTION MANUAL IM245. RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM245 RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL SAFETY INSTRUCTIONS TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY

More information

HIB Enclosed Inverter User Guide

HIB Enclosed Inverter User Guide HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit

More information

Instruction/Installation Manual

Instruction/Installation Manual Instruction/Installation Manual Retrofit:LED Tube Lamp 4ft. Fluorescent T8/T10 Replacement 1 SECTION 1 - General Information Kit components:1-led Tube, 1-Label and 1-Set of Instructions Models were only

More information

AMP ASSEMBLY INSTRUCTIONS

AMP ASSEMBLY INSTRUCTIONS AMP ASSEMBLY INSTRUCTIONS ENGLISH IMPORTANT! Always shut off power to the circuit before starting installation work. In some coun-tries electrical installation work may only be carried out by a authorised

More information

IMPORTANT. Engineering Bulletin #101 Controller & System Upgrades

IMPORTANT. Engineering Bulletin #101 Controller & System Upgrades IMPORTANT Engineering Bulletin #101 Controller & System Upgrades O. Thompson Co. 84-00 73rd Ave. Unit F Glendale NY 11385 (718) 417-3131 (718) 417-9075 fax Copyright 1999 O. Thompson Co. MA Contactor Mounting

More information

Service Manual. Vegetable Preparation Machine RG V Single Phase. Date: Approved: Henrik Artursson

Service Manual. Vegetable Preparation Machine RG V Single Phase. Date: Approved: Henrik Artursson Service Manual Vegetable Preparation Machine RG-200 100 230 V Single Phase Date: 2015-08-27 Approved: Henrik Artursson Table of contents GENERAL 3 Installation, operation and cleaning 3 Tools 3 Lubrication

More information

Instruction Bulletin. Jockey Pump Controller

Instruction Bulletin. Jockey Pump Controller Instruction Bulletin Jockey Pump Controller Installation Start Up Service This instruction bulletin is a guide for personnel involved with maintenance, engineering and approval of Fire Pump equipment and

More information

Installation Instructions 500 A Current Sensor Kit for D2h/D4h/D7h/D8h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302

Installation Instructions 500 A Current Sensor Kit for D2h/D4h/D7h/D8h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302 Description The 500 A current sensor kit is designed for D2h/D4h/D7h/D8h enclosure sizes in the power ranges shown in Table 1.1. To identify the power rating, see Illustration 1.1. Product group and drive

More information

750 Paso Wiring Upgrade

750 Paso Wiring Upgrade 750 Paso Wiring Upgrade Supplies required: 2 Bosch 30A/12V Relays # #0 332 209 150 (with mounting tab) 1 30 Amp fuse holder 1 10 Amp fuse holder 12 inches of brown 12 gauge wire 60 inches of red 14 gauge

More information

In general this document presents specific safety procedures for systems with potentially lethal voltages on bare or exposed conductors.

In general this document presents specific safety procedures for systems with potentially lethal voltages on bare or exposed conductors. 1. Introduction All safety rules presented in this document are intended to ensure safe working conditions while working with potentially dangerous voltages. It is assumed that all personnel working with

More information

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information