Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated

Size: px
Start display at page:

Download "Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated"

Transcription

1 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA Answers f infrastructure and cities.

2 R-HA eps Application Public power supply system R-HA35-56 eps Application Offshe wind park R-HA eps Application Steel wks 2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

3 Contents Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA Invalid: Catalog HA / medium-voltage-switchgear Application Page Types, typical uses, ratings 4 and 5 Requirements Features, safety, technology 6 and 7 Technical Data Electrical data 8 and 9 Room planning 0 Shipping data, classification Dimensions Front views, sections, flo openings, fixing points 2 to 2 Product Range Single-busbar panels 22 and 23 Double-busbar panels to 27 Design Single-busbar panel design 28 Double-busbar panel design 29 Components Vacuum circuit-breaker 30 and 3 Three-position disconnect 32 and 33 Busbar, module coupling 34 Current transfmers 35 Voltage transfmers to 38 Panel connection with outside cone 39 and 4 Installation possibilities with outside cone 42 and 43 Panel connection with inside cone 44 and 45 Installation possibilities with inside cone 46 and 47 Indicating and measuring equipment 48 to 5 Protection, control, measuring and moniting equipment 52 Standards Standards, specifications, guidelines 56 and 57 The products and systems described in this catalog are manufactured and sold accding to a certified management system (acc. to ISO 900, ISO 400 and BS OHSAS 800). Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

4 Application Types R-HA tif R-HA tif Panel f single busbar Panel f double busbar 4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

5 Application Typical uses, ratings Fixed-mounted circuit-breaker switchgear NXPLUS is a facty-assembled, type-tested, metal-enclosed, metal-clad, SF 6 -insulated switchgear f single-busbar and double-busbar applications f indo installation. It is used in transfmer and switching substations, e. g., in: Power supply companies Power stations Cement industry Automobile industry Iron and steel wks Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshe installations Electrochemical plants Petrochemical plants Shipbuilding industry Diesel power plants Emergency power supply installations Lignite open-cast mines Traction power supply systems. Electrical data (maximum values) and dimensions Single-busbar panels Rated voltage max. kv Rated frequency Hz 50 / 60 Rated sht-duration kv power-frequency withstand voltage Rated lightning kv impulse withstand voltage Rated sht-circuit max. ka 3.5 breaking current Rated sht-time max. ka 3.5 withstand current, 3 s Rated sht-circuit max. ka 80 making current Rated peak max. ka 80 withstand current Rated nmal current max. A 2000 ) 2000 ) 2000 ) 2000 of the busbar Rated nmal current max. A 2000 ) 2000 ) 2000 ) 2000 of the feeders Double-busbar panels Rated voltage max. kv 2 Rated frequency Hz 50 / 60 Rated sht-duration kv power-frequency withstand voltage Rated lightning kv impulse withstand voltage Rated sht-circuit max. ka 3.5 breaking current Rated sht-time max. ka 3.5 withstand current, 3 s Rated sht-circuit max. ka 80 making current Rated peak max. ka 80 withstand current Rated nmal current max. A of the busbar Rated nmal current max. A of the feeders ) 2500 A on request Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

6 Requirements Features Safety Environmental independence Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts of the primary circuit under high voltage of NXPLUS switchgear Insensitive to certain aggressive ambient conditions, such as: Air humidity Dust Condensation Tight to ingress of feign objects, such as: Dust Pollution Small animals Humidity Independent of the site altitude. Compact design Thanks to the use of SF 6 insulation, compact dimensions are possible up to 40.5 kv. Thus: Existing switchgear rooms and substation rooms can be used effectively New constructions cost little Costly city-area space is saved. Maintenance-free design Switchgear vessels designed as sealed pressure systems, maintenance-free switching devices and enclosed cable plugs ensure: Maximum supply reliability Personnel safety Sealed-f-life design accding to (sealed pressure system) Installation, operation, extension and replacement without SF 6 gas wk Reduced operating costs Cost-efficient investment No maintenance cycles. Innovation The use of digital secondary systems and combined protection and control devices ensures: Clear integration in process control systems Flexible and highly simplified adaptation to new system conditions and thus to cost-efficient operation. Service life Under nmal operating conditions, the expected service life of gas-insulated switchgear NXPLUS is at least 35 years, probably 40 to 50 years, taking the tightness of the hermetically welded switchgear vessel into account. The service life is limited by the maximum number of operating cycles of the switchgear devices installed: F circuit-breakers, accding to the endurance class defined in F three-position disconnects and earthing switches, accding to the endurance class defined in Personal safety Safe-to-touch and hermetically sealed primary enclosure Cable terminations, busbars and voltage transfmers are surrounded by earthed layers All high-voltage parts including the cable terminations, busbars and voltage transfmers are metal-enclosed. Capacitive voltage detecting system to verify safe isolation from supply Operating mechanisms and auxiliary switches safely accessible outside the primary enclosure (switchgear vessel) Due to the system design, operation is only possible with closed switchgear enclosure Standard degree of protection IP 65 f all high-voltage parts of the primary circuit, IP 3XD f the switchgear enclosure accding to and VDE High resistance to internal arcs by logical mechanical interlocks and tested switchgear enclosure Panels tested f resistance to internal faults up to 3.5 ka Logical mechanical interlocks prevent maloperation Make-proof earthing by means of the vacuum circuit-breaker. Security of operation Hermetically sealed primary enclosure independent of environmental effects (pollution, humidity and small animals) Maintenance-free in an indo environment ( and VDE 067-) Operating mechanisms of switching devices accessible outside the primary enclosure (modules) Metal-coated metal-enclosed, plug-in inductive voltage transfmers mounted outside the SF 6 switchgear vessel Current transfmers as ring-ce current transfmers mounted outside the SF 6 switchgear vessel Complete switchgear interlocking system with logical mechanical interlocks Welded switchgear vessels, sealed f life Minimum fire load Type and routine-tested Standardized and manufactured using numerically controlled machines Quality assurance in accdance with DIN EN ISO 900 Me than 500,000 switchgear panels of Siemens in operation wldwide f many years Option: Resistance against earthquakes (single busbar only). Reliability Type and routine-tested Standardized and manufactured using numerically controlled machines Quality assurance in accdance with DIN EN ISO 900 Me than 500,000 switchgear panels of Siemens in operation wldwide f many years. 6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

7 Requirements Technology General 3-pole enclosure of the primary part via modules made of stainless steel Insulating gas SF 6 Three-position switch as busbar disconnect and feeder earthing switch Make-proof earthing by means of the vacuum circuit-breaker Panel spacing of incoming and outgoing feeder panels: mm (200 mm as of 2300 A feeder current) Hermetically tight, welded switchgear vessel made of stainless steel -pole solid-insulated, screened module coupling in bolted technology Cable connection with inside-cone outside-cone plug-in system, f connection of solid-insulated bars Wall-standing free-standing arrangement Cable connection access from front rear Low-voltage do hinges on the left on the right Installation and extension of existing switchgear at both ends without gas wk and without modification of existing panels Panel-internal control cables in metallic wiring ducts. Interlocks Accding to and VDE Logical mechanical interlocks prevent maloperation Three-position disconnect can only be operated with circuit-breaker in OPEN position Circuit-breaker can only be operated with three-position switch in end position and operating lever removed Three-position disconnect interlocked against the circuit-breaker in circuit-breaker panels and in bus sectionalizers with one panel spacing Feeder earthed locking device Locking device f three-position switch The following interlocks can be fulfilled by placing the padlock accdingly: Padlock on the left: Three-position switch DISCONNECTING function cannot be operated, three-position switch READY-TO-EARTH function can be operated Padlock in the center: Control gate blocked, no switching operations possible Padlock on the right: Three-position switch DISCONNECTING function can be operated, three-position switch READY-TO-EARTH function cannot be operated Option: Cable compartment cover interlocked against the three-position switch (circuit-breaker panel, disconnect panel) Option: Electromagnetic interlocks Option: Actuating openings of the circuit-breaker can be padlocked Option: Feeder locking device. Modular design Replacement of the circuit-breaker module without gas wk Low-voltage compartment removable, plug-in bus wires. Instrument transfmers Can be removed without altering the position of the busbar and circuit-breaker modules (outside the gas compartments) Current transfmers not subjected to dielectric stress Easy replacement of ring-ce current transfmers Metal-coated metal-enclosed, plug-in and disconnectable voltage transfmers. Vacuum circuit-breaker Maintenance-free under nmal ambient conditions accding to and VDE 067- No relubrication readjustment Up to 0,000 operating cycles Vacuum-tight f life. Secondary systems Customary protection, measuring and control equipment Option: Numerical multifunction protection relay with integrated protection, control, communication, operating and moniting functions Can be integrated in process control systems. Standards (see page 56) Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

8 Technical Data Electrical data, filling pressure, temperature f single-busbar switchgear Common electrical data, filling pressure and temperature Rated insulation level Rated voltage U r kv Rated sht-duration power-frequency withstand voltage U d : phase-to-phase, phase-to-earth, open contact gap kv across the isolating distance kv Rated lightning impulse withstand voltage U p : phase-to-phase, phase-to-earth, open contact gap kv 75 across the isolating distance kv 85 Rated frequency f r Hz 50 / 60 Rated nmal current I 2) r f the busbar up to A 2000 ) 2000 ) 2000 ) 2000 Rated filling level p 3) re Minimum functional level p 3) me Ambient air temperature 50 kpa (absolute) at 20 C 30 kpa (absolute) at 20 C 5 C to + 55 C Data of the switchgear panels Circuitbreaker Rated nmal current I 2) r A panel Rated sht-time f switchgear with t k = 3 s Outside cone withstand current I k up to ka A Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 / Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 / Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations Circuitbreaker panel and bus sectionalizer Inside cone 250 A A 2000 A Circuitbreaker panel Separate inside cone 250 A A 2000 A Rated nmal current I r 2) Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 80/82 Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 80/82 Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations Rated nmal current I r 2) Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 80/82 Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 80/82 Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations A A A A A A Disconnect panel Outside cone 250 A Disconnect panel Inside cone 250 A A 2000 A Rated nmal current I 2) r A Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 / Rated nmal current I r 2) Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 80/82 A A A ) 2500 A on request 2) The rated nmal currents apply to ambient air temperatures of max. 40 C. The -hour mean value is max. 35 C (accding to / VDE 067-) 3) Pressure values f gas-insulated switchgear vessels 8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

9 Technical Data Electrical data, filling pressure, temperature f double-busbar switchgear Common electrical data, filling pressure and temperature Rated insulation level Rated voltage U r kv 2 Rated sht-duration power-frequency withstand voltage U d : phase-to-phase, phase-to-earth, open contact gap kv across the isolating distance kv Rated lightning impulse withstand voltage U p : phase-to-phase, phase-to-earth, open contact gap kv 75 across the isolating distance kv 85 Rated frequency f r Hz 50 / 60 Rated nmal current I ) r f the busbar up to A Rated filling level p 2) re Minimum functional level p 2) me Ambient air temperature 50 kpa (absolute) at 20 C 30 kpa (absolute) at 20 C 5 C to +55 C Data of the switchgear panels Circuit-breaker Rated nmal current I ) r A panel Rated sht-time f switchgear with t k = 3 s Outside cone withstand current I k up to ka A Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations Circuit-breaker panel, bus coupler, bus sectionalizer Inside cone 250 A A 2000 A 2300 A 2500 A Circuit-breaker panel Separate inside cone 250 A A 2000 A 2300 A 2500 A Rated nmal current I r 2) Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations Rated nmal current I r 2) Rated sht-time f switchgear with t k = 3 s withstand current I k up to ka Rated peak withstand current I p 50 / 60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit making current I ma 50/60 Hz up to ka 80/82 80/82 80/82 Rated sht-circuit breaking current I sc up to ka Electrical endurance of vacuum circuit-breakers at rated nmal current at rated sht-circuit breaking current 0,000 operating cycles 50 breaking operations A A A A A A A A A A ) The rated nmal currents apply to ambient air temperatures of max. 40 C. The -hour mean value is max. 35 C (accding to / VDE 067-) 2) Pressure values f gas-insulated switchgear vessels Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

10 Technical Data Room planning Switchgear installation F single-busbar doublebusbar applications: Wall-standing arrangement Free-standing arrangement Face-to-face arrangement accdingly. Room dimensions See opposite dimension drawings. Room height SBB 2950 mm DBB 300 mm. Do dimensions The do dimensions depend on the dimensions of the individual panels (see pages 2 to 2). Switchgear fixing Flo openings and fixing points of the switchgear (see pages 2 to 2) Foundations: Steel girder construction Steel-reinfced concrete with foundation rails, welded bolted on. HA35-07d eps HA eps Room planning f single-busbar switchgear B 80 ³50*** Wall-standing arrangement (top view) B 80 ³50*** B 80 ³500** B 80 ³500** ³* ³50 ³* ³500 Panel dimensions See pages 2 to 2. Weights Single-busbar panels 200 kg. Double-busbar panels 800 kg. Free-standing arrangement (top view) Room planning f double-busbar switchgear Panel width B (spacing) Circuit-breaker panel Disconnect panel Bus sectionalizer panel Panel width B2 (spacing) Circuit-breaker panel ) Bus coupler panel ) Bus sectionalizer panel, system system 2 2) Metering panel ) 200 mm at 2300 / 2500 A 2) 900 mm 200 mm at 2300 / 2500 A mm mm 900 mm mm mm mm 300 mm mm HA35-09c eps B2 80 ³50*** B2 80 ³500** Wall-standing arrangement / free-standing arrangement (top view) * Aisle width ** Free space next to the last panel installed, either on the left on the right of the switchgear row *** Recommendation 500 mm 0 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA ³* 840 ³500

11 Technical Data Shipping data, classification Transpt NXPLUS switchgear is delivered in fm of individual panels. Please observe the following: Transpt facilities on site Transpt dimensions and transpt weights Size of do openings in building. Packing Means of transpt: Rail and truck Panels on pallets Open packing with PE protective foil. Means of transpt: Ship Panels on pallets In closed crates with sealed upper and lower PE protective foil With desiccant bags With sealed wooden base Max. stage time: 6 months. Transpt dimensions, transpt weights ) Panel widths Transpt dimensions Transpt weight Width x Height x Depth with packing without packing mm mm mm mm approx. kg approx. kg Single-busbar switchgear transpt by rail truck (2850) 2) (2850) 2) Single-busbar switchgear transpt by ship Double-busbar switchgear transpt by rail truck (2850) 2) (2850) 2) (2850) 2) Double-busbar switchgear transpt by ship Classification of NXPLUS switchgear accding to Design and construction Partition class PM (partition of metal) 3) Loss of service continuity categy LSC 2 Accessibility to compartments (enclosure) Busbar compartment Switching-device compartment Low-voltage compartment Cable compartment Internal arc classification Designation of the internal arc classification IAC IAC class f: Wall-standing arrangement Free-standing arrangement Type of accessibility A F L R Arc test current Test duration Tool-based Tool-based Tool-based Tool-based IAC A FL 3.5 ka, s IAC A FLR 3.5 ka, s Switchgear in closed electrical service location, access f authized personnel only (accding to )) Front Lateral Rear (f free-standing arrangement) 3.5 ka s ) Average values depending on the degree to which panels are equipped 2) Panels with 00 mm high low-voltage compartment 3) Cresponds to metal-clad accding to fmer standard Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

12 Dimensions Front views, sections, flo openings, fixing points f single-busbar switchgear Circuit-breaker panels Outside cone ) 28 HA35-255c eps A Legend and footnotes Fixing point 2 Flo opening f high-voltage cables 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment Inside cone Separate inside cone ) ) 28 HA b eps 935 HA a eps A A 2000 A A A 2000 A Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

13 Dimensions Front views, sections, flo openings, fixing points f single-busbar switchgear Disconnect panels Outside cone Bus sectionalizer ) ) 28 HA b eps HA b eps 250 A A A 2000 A Inside cone ) 28 HA a eps A A 2000 A Legend and footnotes Fixing point 2 Flo opening f high-voltage cables 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

14 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Circuit-breaker panels Outside cone Inside cone ) ) HA c eps HA b eps A A A 2000 A Inside cone ) HA c eps A 2500 A Legend and footnotes Fixing point 2 Flo opening f high-voltage cables 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment 4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

15 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Circuit-breaker panels Separate inside cone 2 ) HA b eps ) HA35-256b eps 250 A A 2000 A Separate inside cone Legend and footnotes Fixing point 2 Flo opening f high-voltage cables 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment 2300 A 2500 A Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

16 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Bus sectionalizers Busbar system 2 ) HA b eps 935 HA b eps ) 250 A A 2000 A A 2500 A Legend and footnotes Fixing point 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

17 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Bus sectionalizers Busbar system 2 2 ) HA b eps ) HA c eps A A 2000 A A 2500 A Legend and footnotes Fixing point 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

18 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Bus sectionalizer consisting of circuit-breaker panel + disconnect panel ) HA35-286a eps ) HA35-288b eps ) HA35-285a eps 250 A A 2000 A A A 2000 A ) HA35-287b eps A 2500 A A 2500 A Fixing point 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment 8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

19 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Bus sectionalizer consiting of circuit-breaker panel + disconnect panel: HA35-289b eps HA35-282d eps 250 A A 2000 A 2300 A 2500 A Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

20 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Bus couplers 2 ) HA d eps A A 2000 A ) HA c eps A 2500 A Legend and footnotes Fixing point 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment 20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

21 Dimensions Front views, sections, flo openings, fixing points f double-busbar switchgear Metering panels HA b eps 2 ) ) HA b eps Legend and footnotes Fixing point 3 Flo opening f control cables ) 265 mm f higher low-voltage compartment Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

22 Product Range Single-busbar panels Circuit-breaker panel (cable connection as outside cone) Busbar current transfmer Solid-insulated bar Voltage transfmer, plug-in type Voltage transfmer, disconnectable Current transfmer HA f eps and ) Capacitive voltage detecting system Circuit-breaker panel (cable connection as inside cone) Surge arrester, plug-in type HA35-254b eps 2) Plug-in cable, -to 4-fold, inside-cone interface type 2 3 (not included in the scope of supply) Cable connection with outside-cone plug (not included in the scope of supply) HA e eps and ) ) Not possible with busbar voltage transfmer 2) Requires cable connection with vessel f separate inside cone Capacitive voltage detecting system 22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

23 Product Range Single-busbar panels Disconnect panel (cable connection as outside cone) Bus sectionalizer Busbar current transfmer Solid-insulated bar HA c eps Voltage transfmer, plug-in type Voltage transfmer, disconnectable Current transfmer HA e eps HA a eps and ) Disconnect panel (cable connection as inside cone) and ) Capacitive voltage detecting system Surge arrester, plug-in type Plug-in cable, -to 4-fold, inside-cone interface type 2 3 (not included in the scope of supply) Cable connection with outside-cone plug (not included in the scope of supply) Capacitive voltage detecting system HA35-254b eps ) Not possible with busbar voltage transfmer Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

24 Product Range Double-busbar panels Circuit-breaker panel (cable connection as outside cone) SS SS2 Busbar current transfmer Solid-insulated bar HA h eps 2) 2) Voltage transfmer, plug-in type Voltage transfmer, disconnectable Current transfmer Circuit-breaker panel (cable connection as inside cone) SS SS2 Capacitive voltage detecting system Surge arrester, plug-in type HA35-254b eps HA35-239g eps ) 2) Plug-in cable, -to 4-fold, inside-cone interface type 2 3 (not included in the scope of supply) Cable connection with outside-cone plug (not included in the scope of supply) ) Requires cable connection with vessel f separate inside cone 2) Ring-ce current transfmer, oval design, suitable f use as of 000 A Abbreviations SS = Busbar SS2 = Busbar 2 Capacitive voltage detecting system Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

25 Product Range Double-busbar panels Bus sectionalizer Busbar current transfmer SS SS2 Solid-insulated bar HA e eps Voltage transfmer, plug-in type Voltage transfmer, disconnectable Bus sectionalizer circuit-breaker panel (cable connection as inside cone) SS SS2 Bus sectionalizer disconnect panel (cable connection as inside cone) SS SS2 Current transfmer Capacitive voltage detecting system Surge arrester, plug-in type HA35-254b eps Plug-in cable, -to 4-fold, inside-cone interface type 2 3 (not included in the scope of supply) HA f eps Cable connection with outside-cone plug (not included in the scope of supply) Capacitive voltage detecting system Abbreviations SS = Busbar SS2 = Busbar 2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

26 Product range Double-busbar panels Bus coupler SS SS2 Current transfmer Capacitive voltage detecting system HA35-254b eps HA c eps Voltage transfmer, plug-in type SS SS2 HA d eps Metering panel Abbreviations SS = Busbar SS2 = Busbar 2 26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

27 Product Range Single-busbar panels, double-busbar panels Single-busbar panels Circuit-breaker panel With cable connection as outside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2000 A (2500 A on request), and of feeders up to 250 A With cable connection as inside cone f Rated voltage up to 40.5 kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2000 A (2500 A on request) With cable connection as separate inside cone f Rated voltage up to 40.5 kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2000 A (2500 A on request). Disconnect panel With cable connection as outside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2000 A (2500 A on request), and of feeders up to 250 A With cable connection as inside cone f Rated voltage up to 40.5 kv Rated sht-time withstand current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2000 A (2500 A on request). Bus sectionalizer f Rated voltage up to 40.5 kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2000 A (2500 A on request). Double-busbar panels Circuit-breaker panel With cable connection as outside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2500 A, and of feeders up to 250 A With cable connection as inside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2500 A With cable connection as separate inside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2500 A. Bus sectionalizer f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2500 A. Bus sectionalizer (circuit-breaker panel and disconnect panel) With cable connection as inside cone f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars and feeders up to 2500 A. Bus coupler f Rated voltage up to kv Rated sht-circuit breaking current up to 3.5 ka Rated nmal currents of busbars up to 2500 A. Metering panel with a panel spacing of 300 mm mm f Rated voltage up to kv Rated nmal currents of busbars up to 2500 A. Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

28 Design Single-busbar panel design Insulating system Switchgear vessel filled with SF 6 gas Featurs of SF 6 gas: Non-toxic Odless and colless Non-inflammable Chemically neutral Heavier than air Electronegative (high-quality insulat) Pressure of SF 6 gas in the switchgear vessel (absolute values at 20 C): Rated filling level: 50 kpa Design pressure: 80 kpa Design temperature of the SF 6 gas: 80 C Pickup pressure of the bursting disc: 300 kpa Bursting pressure: 550 kpa Gas leakage rate: < 0, % p.a. Panel design Facty-assembled, type-tested Metal-enclosed, metal-clad Hermetically tight, welded switchgear vessel made of stainless steel Electrical connections via cast-resin insulated, screened and bolted module couplings Maintenance-free Degree of protection IP 65 f all high-voltage parts of the primary circuit IP 3XD f the switchgear enclosure Vacuum circuit-breaker Three-position disconnect f disconnecting and earthing by means of the circuit-breaker Make-proof earthing by means of the vacuum circuit-breaker Cable connection with outside-cone plug-in system inside-cone plug-in system accding to DIN EN 508 Wall-standing free-standing arrangement Installation and possible later extension of existing panels without gas wk Replacement of the circuit-breaker module without gas wk Instrument transfmers can be removed without altering the position of the busbar and circuit-breaker modules Replacement of instrument transfmers without gas wk, as they are located outside the gas compartments Enclosure made of sendzimir-galvanized sheet steel, front and rear side of switchgear as well as end walls powdercoated in col light basic (SN 700) Low-voltage compartment removable, plug-in bus wires Lateral metallic wiring duct f control cables. 2 Z HA g eps Modular design (example) Front view Detail Z: Panel with integrated inside cone (up to kv) Panel with integraded inside cone (up to 40,5 kv) Panel with outside cone (up to kv) HA c eps Panel with separated inside cone (up to 40,5 kv) 28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

29 Design Double-busbar panel design 2 Z HA35-0h eps Modular design (example) Front view Detail Z: Panel with integrated inside cone Panel with outside cone Panel with separate inside cone HA35-263b eps Low-voltage compartment 2 Multifunction protection relay SIPROTEC 4 (example) 3 Actuating opening f charging the circuitbreaker springs 4 Position indicat f circuit-breaker 5 Spring charged indicat 6 Operations counter f circuit-breaker 7 Capacitive voltage detecting system 8 Interrogation lever 9 Control gate and locking device f disconnecting / earthing functions of three-position switch 0 Actuating opening f disconnecting function of three-position switch Actuating opening f ready-to-earth function of three-position switch 2 Position indicat f disconnecting function of three-position switch 3 Position indicat f ready-to-earth function of three-position switch 4 Busbar cover 5 Busbar module, welded, SF 6 -insulated 6 Pressure relief (bursting disc) 7 Three-phase busbar system 8 Three-position disconnect 9 Module coupling between busbar module and circuit-breaker module 20 Circuit-breaker module, welded, SF 6 -insulated 2 Select gate f selecting the three-position disconnect in double-busbar switchgear 22 ON pushbutton f circuit-breaker 23 OFF pushbutton f circuit-breaker Vacuum interrupter of circuit-breaker 25 Feeder locking device (suitable f padlocking) 26 Pressure relief duct 27 Integrated cable connection as inside cone 28 Cover of cable compartment 29 Cable connection with inside-cone plugs 30 Feeder current transfmer 3 Operating mechanism f three-position switch 32 Mechanical control board 33 Operating mechanism f circuit-breaker 34 Voltage transfmer connection socket as outside cone 35 Cable compartment Feeder voltage transfmer 37 Earthing busbar 38 Disconnecting facility f feeder voltage transfmer 39 Bushing f feeder voltage transfmer 40 Cable connection with outside-cone T-plugs 4 Module coupling between circuit-breaker module and separate inside-cone module 42 Separate inside-cone module 43 Integrated cable connection as inside cone 44 Voltage transfmer connection socket as outside cone Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

30 Components Vacuum circuit-breaker Features Accding to and VDE (f standards, see page 56) Application in hermetically welded switchgear vessel in confmity with the system Climate-independent vacuum interrupter poles in the SF 6 -filled switchgear vessel Maintenance-free f indo installation accding to and VDE 067- Individual secondary equipment A metal bellows is used f gasketless separation of the SF 6 insulation and the operating mechanism (already used with success f over 2 million vacuum interrupters). Trip-free mechanism The vacuum circuit-breaker is fitted with a trip-free mechanism accding to 6227 and VDE 067. Switching duties and operating mechanisms The switching duties of the vacuum circuit-breaker are dependent, among other facts, on its type of operating mechanism. Mot operating mechanism Mot operating sted-energy mechanism F auto-reclosing (K) F synchronization and rapid load transfer (U). Further operating mechanism features Located outside the switchgear vessel in the operating mechanism box and behind the control board Sted-energy spring mechanism f 0,000 operating cycles. Operating mechanism functions Mot operating mechanism ) (M *) In the case of mot operating mechanism, the closing spring is charged by means of a mot and latched in the charged position ( spring charged indication is visible). Closing is effected either by means of an ON pushbutton a closing solenoid. The closing spring is recharged automatically (f auto-reclosing). Endurance class of circuit-breaker Function Class Standard Property of NXPLUS BREAKING M ,000 times mechanically without maintenance E ,000 times rated nmal current without maintenance 50 times sht-circuit breaking current without maintenance C Very low probability of restrikes Operating times Closing time Closing solenoid < 75 ms Opening time st release 2 nd release < 65 ms < 50 ms Arcing time at 50 Hz < 5 ms Break time Dead time Total charging time st release 2 nd release < 80 ms < 65 ms 300 ms < 5 s HA eps Inside view of the vacuum circuit-breaker Gear with mot (M *) 2 Position switch (S4 *) 3 Closing spring 4 Closing spring charged indication 5 Closing solenoid (Y9 *) 6 Operations counter 7 Auxiliary switch 6 NO + 6 NC (S *), option: 2 NO + 2 NC 8 CLOSED/OPEN position indicat f circuit-breaker 9 Option: 2 nd release (Y2 *), 3 rd release (Y7 *) 0 st release (Y *) Feeder locking device Section through the vacuum circuit-breaker 2 Fixed terminal 3 Pole suppt 4 Vacuum interrupter 5 Moving terminal R-HA35-26a eps 6 Metal bellows 7 Switchgear vessel, SF 6 -insulated, with vacuum interrupter 8 Operating mechanism box (see figure above) 9 Operating kinematics Abbreviations f switching duties: U = Synchronization and rapid load transfer (closing time 90 ms) K = Auto-reclosing ) Mot rating at 60 V to 220 V DC: 700 W 00 V up to 230 V DC: 00 VA * Item designation 30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

31 Components Vacuum circuit-breaker Secondary equipment The scope of the secondary equipment of the vacuum circuitbreaker depends on the type of application and offers a wide range of possible variations, allowing almost every requirement to be satisfied: Switching rate of the vacuum interrupter Closing solenoid Type 3AY5 0 (Y9 *) F electrical closing. Shunt release Types: Standard: 3AY5 0 (Y *) Option: 3AX 0 (Y2 *), with energy ste Tripping by protection relay electrical actuation. Undervoltage release Type 3AX 03 (Y7 *) Consisting of: Energy ste and unlatching mechanism Electromagnetic system, which is permanently connected to voltage while the vacuum circuit-breaker is closed; tripping is initiated when this voltage drops Connection to voltage transfmers possible. Anti-pumping (mechanical and electrical) Function: If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= pumping) is avoided. Circuit-breaker tripping signal F electrical signaling (as pulse > 0 ms), e. g. to remote control systems, in the case of automatic tripping (e. g. protection) Via limit switch (S6 *) and cutout switch (S7 *). Varist module To limit overvoltages to approx. 500 V f protection devices (when inductive components are mounted in the vacuum circuit-breaker) F auxiliary voltages 60 V DC. Auxiliary switch Type 3SV9 (S *) Standard: 6 NO + 6 NC, free contacts thereof ) 2 NO + 2 NC Option: 2 NO + 2 NC, free contacts thereof ) 8 NO + 8 NC. Position switch Type 3AX4 (S4, S42, S6 *) F signaling closing spring charged F circuit-breaker blocked indication. Mechanical interlocking Mechanical interlocking to the three-position disconnect During operation of the three-position switch, the vacuum circuit-breaker cannot be operated. Possible release combinations Release Release combination st shunt release type 3AY50 2nd shunt release type 3AX0 Undervoltage release type 3AX03 ) F utilization by the customer * Item designation Abbreviations: NO = nmally open contact NC = nmally closed contact Electrical data Curve ➀ Curve ➁ Curve ➂ Curve ➃ Rated voltage 2 kv kv kv / 40.5 kv Rated sht-circuitbreaking current 3.5 ka 25 ka 25 ka 3.5 ka Rated nmal current 250 A 250 A 2000 A 2500 A Rated operating sequences Rapid transfer (U): O-t-CO-t -CO (t 0.3 s, t 3 min) Auto-reclosing (K): O-t-CO-t -CO (t 0.3 s, t 3 min) Auto-reclosing (K): O-t-CO-t -CO (t 0.3 s, t 5 s) O = OPEN operation C = CLOSE operation CO = CLOSE operation with subsequent OPEN operation at the shtest internal close-open time of the vacuum circuit-breaker Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

32 Components Three-position disconnect Features of the three-position disconnect Accding to and VDE (f standards, see page 56) Application in hermetically welded switchgear vessel in confmity with the system Climate-independent contacts in the SF 6 -filled switchgear vessel Maintenance-free f indo installation accding to and VDE 067- A metal bellows is used f gasketless separation of the SF 6 insulation and the operating mechanism as already used with success in millions of vacuum interrupters Compact design due to sht contact gaps in SF 6 gas Operating shaft and contact blades with common center of rotation and reliable switch position up to the operating front of the panel 2000 mechanical operating cycles f CLOSED / OPEN 000 mechanical operating cycles f OPEN / READY-TO-EARTH Position indication via mechanical coupled indicats Separate operating shafts f the disconnecting and ready-to-earth functions Maintenance-free. 3 Switch positions of the three-position disconnect Three-position disconnect (in OPEN position) (view into the laterally open switchgear vessel) R-HA35-073b eps Fixed contact at the busbar 2 Swivel-mounted contact blade 3 Fixed contact f feeder EARTHED 4 Push rod Switch positions of the three-position disconnect 2 4 HA35-258a eps CLOSED OPEN Feeder EARTHED Switch positions CLOSED Closed current path between busbar and vacuum circuit-breaker Contact blades connected with fixed contacts at the busbar bushings OPEN Open current path between busbar and vacuum circuit-breaker Isolating distances withstand prescribed test voltages READY-TO-EARTH Contact blades connected with earth contact of switchgear vessel Earthing and shtcircuiting the cable connection possible by closing the vacuum circuitbreaker Endurance class of three-position disconnect Function Class Standard Property of NXPLUS DISCONNECTING M times mechanically without maintenance READY- TO-EARTH M0 E times mechanically without maintenance no making capacity EARTHING E2 ) times rated sht-circuit making current I ma without maintenance ) The EARTHING function with endurance class E2 is achieved by closing the circuit-breaker in combination with the three-position disconnect (endurance class E0) 32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

33 Components Three-position disconnect Interlocks Selection of permissible switching operations by means of a control gate with mechanically interlocked vacuum circuit-breaker Cresponding operating shafts are not released at the operating front until they have been pre-selected with the control gate Operating lever cannot be removed until switching operation has been completed Circuit-breaker cannot be closed until control gate is in neutral position again Switchgear interlocking system also possible with electromechanical interlocks if switchgear is equipped with mot operating mechanisms (mechanical interlocking f manual operation remains). Switch positions CLOSED, OPEN, EARTHED READY-TO-EARTH In circuit-breaker panels, earthing and sht-circuiting the cable connection is completed by closing the vacuum circuit-breaker. HA35-283a eps Transmission principle f operating mechanisms Three-position disconnect 2 Gas-filled switchgear vessel 2 Gas-tight welded-in metal bellows Operating mechanism Slow motion mechanism, used in: Circuit-breaker panel Disconnect panel Bus sectionalizer Bus coupler Slow motion mechanism actuated via operating lever at the operating front of the panel Separate operating shafts f the DISCONNECTING and EARTHING READY-TO-EARTH functions Option: Mot operating mechanism f the DISCONNECTING and EARTHING READY-TO-EARTH functions Maintenance-free due to non-rusting design of parts subjected to mechanical stress Bearings which require no lubrication. Transmission principle f operating mechanisms (see illustration) Transmission of operating power from outside into the gas-filled switchgear vessel by means of a metal bellows Gas-tight Maintenance-free. Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

34 Components Busbar, module coupling Busbar Designed as module coupling Solid-insulated Interconnects the panels as well as the vessels within a panel. Panel interconnections in circuit-breaker panel (example) 5 Module coupling Single-pole, bolted type Consisting of round-bar copper, cast-resin insulated Bolted busbar joint, siliconerubber insulated Field control by means of electrically conductive layers on the insulation (inside and outside) Screened by earthing the external layers with the switchgear vessel Switchgear installation, extension panel replacement without SF 6 gas wk HA m eps HA35-e eps Module couplings f single-busbar panels Module couplings f double-busbar panels Module coupling R-HA35-5 eps Module coupling 2 Busbar module 3 Circuit-breaker module 4 End wall 5 Bushing in adjacent panel 6 Busbar conduct 7 Silicone sleeve 8 Earthing clamps 9 High-quality joint 0 Cast-resin bushing Vessel wall 2 Cast-resin insulation 3 Conductive layer 4 Bolted busbar joint 5 Pressure ring 6 5 Busbar module SF 6 -insulated Module coupling (solid-insulated) 9 0 HA f eps Busbar module SF 6 -insulated 34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

35 Components Current transfmers Features Accding to and VDE Designed as ring-ce current transfmers, single-pole Flexibility f selecting the mounting location Free of dielectrically stressed cast-resin parts (due to design) Insulation class E Inductive type Certifiable Climate-independent Secondary connection by means of a terminal strip in the low-voltage compartment of the panel. HA35-266a eps Current transfmer installation (basic scheme) HA35-267a eps HA35-268a eps Installation Arranged outside the primary enclosure (switchgear vessel) Mounting locations At the busbar () Between busbar module and circuit-breaker module (2) At the panel connection (3) Between circuit-breaker module and cable connection module (4) Zero-sequence current transfmer. Current transfmer types Busbar current transfmer (): Inside diameter of transfmer 20 mm Max. usable height 70 mm Current transfmer between busbar module and circuitbreaker module (2): Inside diameter of transfmer 20 mm Max. usable height 70 mm Current transfmer at the panel connection (3): Inside diameter of transfmer 20 mm Max. usable height 205 mm Current transfmer between circuit-breaker module and cable connection module (4): Inside diameter of transfmer 20 mm Max. usable height 70 mm Zero-sequence current transfmer underneath the panels (included in the scope of supply); on-site installation. HA eps 2 Current transfmer at the busbar 2 Current transfmer between busbar module and circuit-breaker module 3 Current transfmer at the panel connection 4 Current transfmer between circuit-breaker module and cable connection module Electrical data Designation Operating voltage Rated sht-duration power-frequency withstand voltage (winding test) Rated frequency Rated continuous thermal current Rated sht-time thermal current, max. 3 s Rated current dynamic primary secondary Type 4MC max. 0.8 kv 3 kv 50 / 60 Hz max..2 x rated current (primary) max. 3.5 ka unlimited, 40 A to 2500 A A and 5 A 3 4 Designation Type 4MC Multiratio (secondary) 200 A 00 A to 2500 A 250 A Ce data depending on the max. 3 ces rated primary current: Measuring Rating ce Class Overcurrent fact 2.5 VA to 30 VA 0.2 to Protection Rating FS 5, FS 0 ce Class Overcurrent fact 2.5 VA to 30 VA 5 P 0 P 0 to 30 Permissible ambient air max. 60 C temperature Insulation class E HA eps HA eps Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

36 Components Voltage transfmers Features Accding to and VDE Single-pole, plug-in design Connection system with plug-in contact Inductive type Safe-to-touch due to metal enclosure Certifiable Climate-independent Secondary connection by means of plugs inside the panel Cast-resin insulated Arranged outside the primary enclosure (switchgear vessel) Mounting locations: At the busbar on the busbar module () (single busbar), in a separate metering panel (8) (double busbar) At the panel connection (2)(3)(5). Voltage transfmers Feeder voltage transfmer (metal-coated) 4MT3 Voltage transfmer installation (basic scheme) R-HA35-20 eps Busbar voltage transfmer (metal-enclosed) 4MT6 Z R-HA eps Voltage transfmer types Busbar voltage transfmer 4MT6 () on the busbar module (single busbar) Pluggable into an inside-cone socket size 2 No separate metering panel required Suitable f 80% of the rated sht-duration power-frequency withstand voltage at rated frequency Busbar voltage transfmer 4MT9 (8) in a separate, 300 mm mm wide metering panel (double busbar) Connected with the busbar through a flexible cable with inside-cone plug, f connection to the busbar and to the voltage transfmer Suitable f 80 % of the rated sht-duration power-frequency withstand voltage at rated frequency. HA35-269a eps 2 Voltage transfmer at the busbar 2 Voltage transfmer at the panel connection (inside-cone connection) 3 Voltage transfmer at the panel connection (outside-cone connection) 4 Operating lever f disconnecting facility 5 Voltage transfmer at the panel connection (separate inside-cone connection) 6 Panel connection 7 Switchgear vessel wall (earthed) CLOSED HA a eps 6 OPEN and EARTHED HA a eps HA eps Disconnecting facility f feeder voltage transfmer (detail Z) Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

37 Components Voltage transfmers Voltage transfmers 4MU 4MT3 (3) at the panel connection of the panels with outside-cone connection Pluggable into an outsidecone bushing at the panel connection Application of type 4MU at kv kv and 3.5 ka Application of type 4MT3 up to kv Disconnectable via a disconnecting facility at the cable connection Switchable through an SF 6 -insulated disconnecting facility in the switchgear vessel Positions: CLOSED and Transfmer bushing EARTHED Operation of the disconnecting facility from outside through a metal bellows welded in the switchgear vessel Voltage transfmers 4MU2 4MT5 at the panel connection of the panels with inside-cone connection Connection via an outsidecone bushing at the panel connection f type 4MU2 (2) Connection via a flexible cable between an inside-cone socket at the panel connection and an inside-cone socket at the voltage transfmer type 4MU2 (5) Application of type 4MU2 up to kv Application of type 4MT5 up to 40.5 kv. HA a eps Voltage transfmer installation (basic scheme) Voltage transfmer at the panel connection (inside-cone connection) 3 Voltage transfmer at the panel connection (outside-cone connection) 4 Operating lever f disconnecting facility 5 Voltage transfmer at the panel connection (separate inside-cone connection) 8 Voltage transfmer at the busbar (double-busbar metering panel) HA35-262b eps Z HA35-280a eps HA35-28 eps Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

38 Components Voltage transfmers Electrical data Primary data F types 4MT3, 4MT5, 4MT6, 4MT9, 4MU and 4MU2 F operating voltages from 6.0 kv to 38 kv, rated voltage fact U n / 8h =.9; U n / continuous =.2 Rated voltage Rated sht-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Standard Operating voltage kv kv kv kv / 3; 6. / 3; 6.3 / 3; 6.6 / 3; 6.9 / / 3; 7.6 / 3; 8.0 / 3; 8.3 / 3; 8.4 / 3; 8.9 / 3; 0 / 3; 0.5 / 3; / 3;.4 / 3;.5 / 3;.6 / / 3; 2.4 / 3; 2.47 / 3; 2.5 / 3; 2.8 / 3; 3.2 / 3; 3.4 / 3; 3.8 / 3; 4.4 / 3; 5 / 3; 5.8 / 3; 6/ 3; 7/ 3; / 3; 8 / 3; 9 / 3; 20 / 3; 22 / 3; 23 / 3; / 3; 25.0 / 3; 25.8 / 3; 27.6 / 3; 30.0 / 3; 33.0 / 3; 34.5 / 3; 35.0 / 3; / 3; Secondary data F type Operating voltage V 4MT3 00 / 3 0 / 3 20 / 3 4MT5 00 / 3 0 / 3 20 / 3 4MT6 4MT9 4MU 4MU2 00 / 3 0 / 3 20 / 3 00 / 3; 0 / 3; 20 / 3 Auxiliary winding V 00 / 3 0 / 3 20 / 3 00 / 3 0 / 3 20 / 3 00 / 3 0 / 3 20 / 3 00 / 3; 0 / 3; 20 / 3 Thermal limit current (measuring winding) A Rated longtime current 8 h A Rating at accuracy class VA 6 4 0, 5, 20, 25, , 0, 5, 20, , 0, 5, 20, , 0.5, 20, 25 VA 0, 5, 20, 25, 30, 45, 50, 60, 75, 90 0, 5, 20, 25, 30, 45, 50, 60, 75 0, 5, 20, 25, 30, 45, 50, 60, 75 0, 5, 20, 25, 30, 45 VA 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50, 80 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50 0, 5, 20, 25, 30, 45, 50, 60, 75 3 VA 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50, 80 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50 0, 5, 20, 25, 30, 45, 50, 60, 75, 90, 00, 20, 50 0, 5, 20, 25, 30, 45, 50, 60, Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

39 Components Panel connection with outside cone Features F circuit-breaker panel 250 A, f disconnect panel 250 A Bushings with outside cone With bolted contact (M6) as interface type C accding to EN 5080 / EN 508 Cable connection height 59 mm Max. connection depth: 960 mm with standard cable compartment cover With cable bracket, type C40 accding to DIN EN 500 Option: Acess to cable compartment only if the feeder is isolated and earthed F thermoplastic-insulated cables F shielded cable T-plugs cable elbow plugs with bolted contact F connection cross-sections up to 800 mm 2 Larger cross-sections on request Cable routing downwards, cable connection from the front F rated nmal currents up to 250 A Cable T-plugs are not included in the scope of supply. Surge arresters Pluggable on cable T-plug Surge arresters recommended if, at the same time, the cable system is directly connected to the overhead line, the protection zone of the surge arrester at the end tower of the overhead line does not cover the switchgear. Surge limiters Pluggable on cable T-plug Surge limiters recommended when mots with starting currents < A are connected. Cable compartment HA eps HA a eps HA35-260a eps 05 L L2 L Panel width mm Connectable cables Cable T-plug with coupling insert Connection with cable per phase HA eps 4 HA35-2a eps Cable T-plug with coupling T-plug Connection with 2 cables per phase Solid-insulated bar HA a eps Connection with 2 cables per phase 3 2 Connection with 3 cables per phase HA a eps 3 3 Connection with 3 cables per phase Cable T-plug 2 Coupling T-plug 3 Screw-type coupling insert 4 End adapter Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

40 Components Panel connection with outside cone (commercially available cable plugs and bar connections) Cable type Cable sealing end Comment Make Type Cross-section mm 2 Thermoplastic-insulated cables 2 kv accding to and VDE ce cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) 3-ce cable, PE and XLPE-insulated, N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) Euromold 400TB / G 430TB / G 440TB / G 484TB / G 489TB / G nkt cables CB CB CB -630(250) CB Südkabel SET 2 SEHDT 3 Tyco Electronics Raychem RSTI-58xx RSTI-395x 400 to to to to to to to to to 800 EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer ABB Kabeldon CSE-A 2630-xx 25 to 630 EPDM with semi-conductive layer Euromold 400TB / G 430TB / G nkt cables CB CB Südkabel SET 2 Tyco Electronics Raychem SEHDT 3 25 to to to 500 Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) EPDM with semi-conductive layer, in combination with distribution kit EPDM with semi-conductive layer, in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer, in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit RSTI-58xx Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x ABB Kabeldon CSE-A 2630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit Thermoplastic-insulated cables kv accding to and VDE ce cable, PE and XLPE-insulated, N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) 3-ce cable, PE and XLPE-insulated, N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) Euromold K400TB / G K430TB / G K440TB / G K484TB / G K489TB / G nkt cables CB -630 CB -630(250) CB Südkabel SET SEHDT 23 Tyco Electronics Raychem RSTI-58xx RSTI-595x 400 to to to to to to to to 800 EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer ABB Kabeldon CSE-A 630-xx 25 to 630 EPDM with semi-conductive layer Euromold K400TB / G K430TB / G Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point EPDM with semi-conductive layer, in combination with distribution kit EPDM with semi-conductive layer, in combination with distribution kit nkt cables CB -630 Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Südkabel SET SEHDT 23 Tyco Electronics Raychem 50 to to 500 Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit RSTI-58xx Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x ABB Kabeldon CSE-A 630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit Thermoplastic-insulated cables kv accding to and VDE ce cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) Euromold M400TB / G M430TB / G M440TB / G M484TB / G M489TB / G nkt cables CB -630 CB -630(250) CB Südkabel SET SEHDT 33 Tyco Electronics Raychem RSTI-68xx RSTI-695x 400 to to to to to to to to 800 EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) ABB Kabeldon CSE-A 630-xx 50 to 630 EPDM with semi-conductive layer Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point 40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

41 Components Panel connection with outside cone (commercially available cable plugs and bar connections) Cable type Cable sealing end Comment Make Type Cross-section mm 2 Thermoplastic-insulated cables kv accding to and VDE ce cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) Paper-insulated belted cables (non-draining cables) 2 kv accding to 55 and VDE ce cable, paper insulated NKBA (Cu), NKBY (Cu), NKRA (Cu) and NKFA (Cu) NAKBA (Al), NAKBY (Al), NAKRA (Al) and NAKFA (Al) Euromold 400TB / G 430TB-630A EPDM with semi-conductive layer in combination with distribution kit MIND EPDM with semi-conductive layer in combination with distribution kit MIND nkt cables CB to 0 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SÜEV 0 Paper-insulated belted cables (non-draining cables) 2 kv accding to GOST ce cable, paper insulated ASB and ASBL Euromold 400TB / G 430TB-630A EPDM with semi-conductive layer in combination with distribution kit MIND EPDM with semi-conductive layer in combination with distribution kit MIND nkt cables CB to 0 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SÜEV 0 Paper-insulated belted cables (mass-impregnated cables) 2 kv accding to GOST ce cable, paper insulated NKBA (Cu), NKBY (Cu), NKRA (Cu) and NKFA (Cu) NAKBA (Al), NAKBY (Al), NAKRA (Al) und NAKFA (Al) nkt cables CB to 0 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SÜEV 0 Paper-insulated belted cables (mass-impregnated cables) 2 kv accding to GOST ce cable, paper insulated ASB and ASBL Euromold M400TB / G M430TB / G EPDM with semi-conductive layer, in combination with distribution kit EPDM with semi-conductive layer, in combination with distribution kit nkt cables CB -630 Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Südkabel SET SEHDT 33 Tyco Electronics Raychem RSTI-66xx RSTI-68xx 50 to to 500 Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x ABB Kabeldon CSE-A 630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit nkt cables CB to 0 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SÜEV 0 Commercially available bar systems Bar type Bar connection Comment Solid-insulated bar Make Type Conduct material MGC Moser Glaser Max. rated current Duresca DE Aluminum 250 A Outer sheath made of polyamide Duresca DE Copper 250 A (polyamide tube) Duresca DG Aluminum 250 A Outer sheath made of CrNi steel aluminum Duresca DG Copper 250 A (metal sheath) Preissinger ISOBUS MR Aluminum 250 A Outer sheath made of heat shrinkable tube; ISOBUS MR Copper 250 A insulated with cast-resin impregnated paper bandage Surge-proof caps Outside-cone plug-in system accding to EN 508 Make Type Size Rated voltage Comment 3M SP 33 SP 33 SP 33 Nexans Euromold 400DR-B K400DR-B M400DR-B nkt cables CBC CBC CBC Südkabel SP 33 SP 33 SP 33 Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C Outside cone type C 2 kv kv kv 2 kv kv kv 2 kv kv kv 2 kv kv kv Silicone with semi-conductive layer EPDM with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

42 Components Installation possibilities with outside cone f cable connections and surge arresters Number of cables per panel and phase Make Rated voltage Conduct crosssection ) Insulation Cable T-plugs Coupling inserts / coupling plugs Surge arresters with coupling inserts Coupling Arresters inserts kv mm 2 bolted bolted additionally Circuit-breaker panel 250 A Disconnect panel 250 A Nexans EPDM Euromold Südkabel 2 2 nkt cables 2 Tyco Electronics Raychem ABB Kabeldon 2 Nexans Euromold Südkabel to 0 50 to to to to to to to to to to to to 0 70 to to to to to to to to to to to to to to to to to 0 50 to to to to to to to to to to to to 0 50 to to to to to 500 EPDM EPDM EPDM EPDM x 400TB/G x K400TB/G x M400TB/G x 430TB/G x K430TB/G x M430TB/G x 440TB/G x K440TB/G x M440TB/G x 484TB/G x K484TB/G x M484TB/G x 489TB/G x K489TB/G x M489TB/G Silicone x SET 2 x SET x SET Silicone x SEHDT 3 x SEHDT 23 x SEHDT 33 Silicone x CB x CB -630 x CB -630 Silicone x CB -630(250) x CB -630(250) x CB -630(250) Silicone x CB x CB x CB Silicone Silicone EPDM EPDM EPDM EPDM EPDM EPDM x RSTI-58xx x RSTI-58xx x RSTI-68xx x RSTI-395x x RSTI-595x x RSTI-695x x CSE-A 2630-xx x CSE-A 630-xx x CSE-A 630-xx 2x 400TB/G 2x K400TB/G 2x M400TB/G x 430TB/G x K430TB/G x M430TB/G 2x 440TB/G 2x K440TB/G 2x M440TB/G x 484TB/G x K484TB/G x M484TB/G x 489TB/G x K489TB/G x M489TB/G Silicone x SET 2 x SET Silicone 2x SET 2 2x SET Silicone 2x SEHDT 3 2x SEHDT 23 2x SEHDT 33 x 400CP x K400CP x M400CP x 300PB/G x K300PB/G x K300PB/G x 400CP x K400CP x M400CP x 804TB/G x K804TB/G x M804TB/G x 809PB/G x K809PB/G x M809PB/G x SEHDK 3. x SEHDK 23. x KU 23.2 x KU 23.2 x KU 33 x KU 33 x KU PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 300SA-5(0)SA 300SA-5(0)SA 300SA-5(0)SA 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx MUT 23 MUT 23 MUT 33 MUT 23 MUT 23 MUT 33 CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx oder RSTI-CC-68SAxxxx 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 300SA-5(0)SA 300SA-5(0)SA 300SA-5(0)SA 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 400PB-5(0)-SA-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx 800SA-0-xxx MUT 23 MUT 23 MUT 23 MUT 23 MUT 23 MUT 23 MUT 33 KU 33 KU 33 KU 33 Accding to standard GOST f Russia & CIS GB / DL f China ) Observe the actual current and sht-current carrying capacity of the cables and the sealing ends. 42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

43 Components Installation possibilities with outside cone f cable connections and surge arresters Number of cables per panel and phase Make Rated voltage Conduct crosssection ) Insulation Cable T-plugs Coupling inserts / coupling plugs Surge arresters with coupling inserts Coupling Arresters inserts kv mm 2 bolted bolted additionally Circuit-breaker panel 250 A Disconnect panel 250 A 2 nkt cables 2 Tyco Electronics Raychem ABB Kabeldon 3 Nexans Euromold nkt cables 2 Tyco Electronics Raychem to to to to to to to to to to to to to to to to 0 50 to to to to to to to to to to to to to to to to to to to to to to 800 Silicone x CB x CB -630 x CB -630 Silicone 2x CB x CB x CB -630 Silicone x CB -630(250) x CB -630(250) x CB -630(250) Silicone 2x CB -630(250) 2x CB -630(250) 2x CB -630(250) Silicone x CB x CB x CB Silicone Silicone EPDM EPDM EPDM EPDM EPDM EPDM x RSTI-58xx x RSTI-58xx x RSTI-68xx x RSTI-395x x RSTI-595x x RSTI-695x 2x CSE-A 2630-xx 2x CSE-A 630-xx 2x CSE-A-630-xx 3x 400TB/G 3x K400TB/G 3x M400TB/G x 430TB/G x K430TB/G x M430TB/G 3x 440TB/G 3x K440TB/G 3x M440TB/G x 484TB/G x K484TB/G x M484TB/G x 489TB/G x K489TB/G x M489TB/G Silicone x CB x CB -630 x CB -630 Silicone 3x CB x CB x CB -630 Silicone x CB -630(250) x CB -630(250) x CB -630(250) Silicone 3x CB -630(250) 3x CB -630(250) 3x CB -630(250) Silicone x CB x CB x CB Silicone Silicone x RSTI-58xx x RSTI-58xx x RSTI-68xx x RSTI-395x x RSTI-595x x RSTI-695x x CC x CC -630 x CC -630 x CP 630-C x CP 630-C x CP 630-C x CC -630(250) x CC -630(250) x CC -630(250) x CP 630-M6 x CP 630-M6 x CP 630-M6 x CC x CC x CC x RSTI-CC-58xx x RSTI-CC-58xx x RSTI-CC-68xx x RSTI-CC-395x x RSTI-CC-595x x RSTI-CC-695x PC PC PC L 2x400CP 2xK400CP 2xM400CP x 300PB/G 2x K300PB/G 2x K300PB/G 2x400CP 2xK400CP 2xM400CP 2x 804TB/G 2x K804TB/G 2x M804TB/G 2x 809PB/G 2x K809PB/G 2x M809PB/G 2x CC x CC x CC x CP 630-C 2x CP 630-C 2x CP 630-C 2x CC -630(250) 2x CC -630(250) 2x CC -630(250) 2x CP 630-M6 2x CP 630-M6 2x CP 630-M6 2x CC x CC x CC x RSTI-CC-58xx 2x RSTI-CC-58xx 2x RSTI-CC-68xx 2x RSTI-CC-395x 2x RSTI-CC-595x 2x RSTI-CC-695x CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x CSA 2-x CSA -x CSA -x RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx oder RSTI-CC-68SAxxxx Accding to standard GOST f Russia & CIS GB / DL f China ) Observe the actual current and sht-current carrying capacity of the cables and the sealing ends. Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

44 Components Panel connection with inside cone Panel connection with inside-cone plug-in system solid-insulated bar Connection options Features F circuit-breaker and disconnect panels Inside-cone plug-in system accding to DIN EN 508 F connection cross-sections up to 630 mm 2 Up to 4 cables with inside-cone plug size 2 Up to 3 cables with inside-cone plug size 3 With cable bracket, type C40 accding to DIN EN 500 Option: Access to the cable compartment only if the feeder has been isolated and earthed F thermoplastic-insulated cables Cable routing downwards, cable connection from the front Inside-cone plugs are not part of the scope of supply Additionally one outside-cone termination (up to kv) one inside-cone socket (40.5 kv) f connection of a voltage transfmer Instead of an inside-cone plug, the cable connection can also be designed f a solid-insulated bar. Surge arresters Inside-cone sockets can be equipped with a surge arrester instead of an inside-cone cable plug Surge arresters are available f plug-in sockets size 2 3 Surge arresters are available with discharge currents of 5 ka and 0 ka. 4 HA35-2f eps cables per phase (option: surge arrester) Interface type 2 HA35-3f eps 3 cables per phase (option: surge arrester) Interface type 2 3 HA35-4f eps 4 2 cables per phase (option: surge arrester) Interface type 2 3 HA35-5f eps 4 cable per phase (option: surge arrester) Interface type 2 3 HA35-6g eps 5 6 solid-insulated bar per phase Cable plug-in sockets 2 Voltage transfmer connection socket 3 Cable plug, interface type 2 4 Cable plug, interface type Silicone sleeve 6 Solid-insulated bar 44 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

45 Components Panel connection with inside cone (commercially available cable plugs and bar connections) Panel connection (commercially available plugs) Cable type Cable sealing end Comment Make Type Size Cross-section mm 2 Thermoplastic-insulated cables 2 kv accding to and VDE ce cable 3-ce cable, PE and XPLE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) nkt cables CPI 2 2 Insulation material silicone rubber, with without CPI to 630 metal housing, installation without special tool Pfisterer CONNEX 2 50 to 300 Insulation material silicone rubber, CONNEX 3 0 to 630 with metal housing Südkabel SEIK 4 2 Insulation material silicone rubber, SEIK to 630 with metal housing Thermoplastic-insulated cables kv accding to and VDE ce cable 3-ce cable, PE and XPLE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) nkt cables CPI 2 2 Insulation material silicone rubber, with without CPI to 630 metal housing, installation without special tool Pfisterer CONNEX 2 50 to 300 Insulation material silicone rubber, CONNEX 3 50 to 630 with metal housing Südkabel SEIK 2 Insulation material silicone rubber, SEIK to 630 with metal housing Thermoplastic-insulated cables kv accding to and VDE ce cable 3-ce cable, PE and XPLE-insulated N2YSY (Cu) and N2XSY (Cu) NA2YSY (Al) and NA2XSY (Al) nkt cables CPI 2 2 Insulation material silicone rubber, with without CPI to 630 metal housing, installation without special tool Pfisterer CONNEX 2 Insulation material silicone rubber, CONNEX 3 95 to 630 with metal housing Südkabel SEIK 34 2 Insulation material silicone rubber, SEIK to 630 with metal housing Commercially available bar systems Bar type Bar connection Comment Make Type Conduct material Max. rated current Solid-insulated bar MGC Duresca DE Aluminum 2500 A Outer sheath made of polyamide Moser Glaser Duresca DE Copper 2500 A (polyamide tube) Duresca DG Aluminum 2500 A Outer sheath made of CrNi steel aluminum Duresca DG Copper 2500 A (metal sheath) Preissinger ISOBUS MR Aluminum 2500 A Outer sheath made of heat shrinkable tube; ISOBUS MR Copper 2500 A insulated with cast-resin impregnated paper bandage Surge-proof caps Inside-cone plug-in system accding to EN 508 Make Type Size Rated voltage Comment nkt cables FPI 2 Inside cone size kv Silicone with metal cover FPI 3 Inside cone size kv Silicone with metal cover Pfisterer CONNEX Inside cone size kv Silicone with metal cover CONNEX Inside cone size kv Silicone with metal cover Südkabel ISIK 4 ISIK ISIK 34 ISIK 5 ISIK 25 ISIK 35 Inside cone size 2 Inside cone size 2 Inside cone size 2 Inside cone size 3 Inside cone size 3 Inside cone size 3 2 kv kv 40.5 kv 2 kv kv 40.5 kv Silicone with metal cover Silicone with metal cover Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

46 Components Installation possibilities with inside cone f cable connections and surge arresters Number of cables per panel and phase Size of inside-cone plug-in system Make Rated voltage Conduct crosssection ) Insulation Cable plugs Surge arresters Accding to standard kv mm 2 bolted additional inside-cone plug-in connection required Circuit-breaker panel 250 A Circuit-breaker panel A Circuit-breaker panel 2000 A Circuit-breaker panel 2300 A Circuit-breaker panel 2500 A Disconnect panel 250 A Disconnect panel A Disconnect panel 2000 A Size 2 nkt cables Pfisterer Südkabel Size 3 nkt cables Pfisterer Südkabel Size 2 nkt cables Pfisterer Südkabel Size 3 nkt cables Pfisterer Südkabel to to to to to to to to to to to to to to to to to to to to to to to to to to to to 400 Silicone x CPI 2 x CPI 2 x CPI 2 x CPI 2 Silicone x MV-CONNEX x MV-CONNEX x MV-CONNEX x MV-CONNEX Silicone x SEIK 4 x SEIK x SEIK 34 Silicone x CPI 3 x CPI 3 x CPI 3 x CPI 3 Silicone x MV-CONNEX x MV-CONNEX x MV-CONNEX x MV-CONNEX Silicone x SEIK 5 x SEIK 25 x SEIK 35 x SEIK 55 Silicone 2x CPI 2 2x CPI 2 2x CPI 2 2x CPI 2 Silicone 2x MV-CONNEX 2x MV-CONNEX 2x MV-CONNEX 2x MV-CONNEX Silicone 2x SEIK 4 2x SEIK 2x SEIK 34 Silicone 2x CPI 3 2x CPI 3 2x CPI 3 2x CPI 3 Silicone 2x MV-CONNEX 2x MV-CONNEX 2x MV-CONNEX 2x MV-CONNEX Silicone 2x SEIK 5 2x SEIK 25 2x SEIK 35 2x SEIK 55 SPI 2 MV-CONNEX GOST f Russia & CIS GB / DL f China SPI 3 MV-CONNEX SPI 2 MV-CONNEX SPI 3 MV-CONNEX 46 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

47 Components Installation possibilities with inside cone f cable connections and surge arresters Number of cables per panel and phase Size of inside-cone plug-in system Make Rated voltage Conduct crosssection ) Insulation Cable plugs Surge arresters Accding to standard kv mm 2 bolted additional inside-cone plug-in connection required Circuit-breaker panel 250 A Circuit-breaker panel A Circuit-breaker panel 2000 A Circuit-breaker panel 2300 A Circuit-breaker panel 2500 A Disconnect panel 250 A Disconnect panel A Disconnect panel 2000 A 3 Size 2 nkt cables Pfisterer Südkabel Size 3 nkt cables Pfisterer Südkabel Size 2 nkt cables Pfisterer Südkabel to to to to to to to to to to to to to to to to 300 Silicone 3x CPI 2 3x CPI 2 3x CPI 2 3x CPI 2 Silicone 3x MV-CONNEX 3x MV-CONNEX 3x MV-CONNEX 3x MV-CONNEX Silicone 3x SEIK 4 3x SEIK 3x SEIK 34 Silicone 3x CPI 3 3x CPI 3 3x CPI 3 3x CPI 3 Silicone 3x MV-CONNEX 3x MV-CONNEX 3x MV-CONNEX 3x MV-CONNEX Silicone 3x SEIK 5 3x SEIK 25 3x SEIK 35 3x SEIK 55 Silicone 4x CPI 2 4x CPI 2 4x CPI 2 4x CPI 2 Silicone 4x MV-CONNEX 4x MV-CONNEX 4x MV-CONNEX 4x MV-CONNEX Silicone 4x SEIK 4 4x SEIK 4x SEIK 34 SPI 2 MV-CONNEX GOST f Russia & CIS GB / DL f China SPI 3 MV-CONNEX SPI 2 MV-CONNEX Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

48 Components Indicating and measuring equipment Voltage detecting systems accding to 63-5 VDE VDE (WEGA ZERO) To verify safe isolation from supply LRM detecting systems with integrated indicat with integrated indicat, type VOIS+, VOIS R+; WEGA ZERO with integrated indicat, with integrated repeat test of the interface, with integrated function test, type CAPDIS-S+, WEGA.2, WEGA.2 Vario, with integrated signaling relay, type CAPDIS-S2+, WEGA 2.2. Plug-in voltage indicat Verification of safe isolation from supply phase by phase Indicat suitable f continuous operation Measuring system and voltage indicat can be tested Voltage indicat flashes if high voltage is present. VOIS+, VOIS R+ Integrated display, without auxiliary power With indication A to A3 (see legend) Maintenance-free, repeat test required With integrated 3-phase LRM test socket f phase comparison With integrated signaling relay (only VOIS R+) Degree of protection IP54. CAPDIS-Sx+: Common features Maintenance-free Integrated display, without auxiliary power Integrated repeat test of the interfaces (self-moniting) With integrated function test (without auxiliary power) by pressing the Display Test pushbutton Adjustable f different operating voltages (adjustable capacity C2) With integrated 3-phase LRM test socket f phase comparison With connectabel signal-lead test With overvoltage moniting and signaling (.2 times operating voltage) Degree of protection IP54. CAPDIS-S+ Without auxiliary power With indication A to A7 (see legend) Without ready-f-service moniting Without signaling relay (without auxiliary contacts). CAPDIS-S2+ With indication A0 to A8 (see legend) Only by pressing the Display Test pushbutton: ERROR indication (A8), e. g. in case of missing auxiliary voltage With ready-f-service moniting (auxiliary power required) With integrated signaling relay f signals (auxiliary power required). R-HA40-03 eps R-HA40-04 eps R-HA35-54 eps R-HA35-55 eps HA a eps Indicats and detecting systems C Plug-in voltage indicat per phase at the panel front Integrated voltage indicat VOIS+, VOIS R+ Integrated voltage detecting system CAPDIS-S+, -S2+ U LE C2 U 2 LRM system plugged in Voltage indication via capacitive voltage divider (principle) Symbols shown A0 A A2 A3 A4 A5 A6 A7 A8 VOIS+, VOIS R+ CAPDIS-S+ CAPDIS-S2+ A0 CAPDIS-S2+: Operating voltage not present A Operating voltage present A2 Operating voltage not present, f CAPDIS-S2+: auxiliary power not present A3 Failure in phase L, operating voltage at L2 and L3 (f CAPDIS-Sx+ also earth-fault indication) A4 Voltage (not operating voltage) present A5 Indication Test passed A6 Indication: Test not passed (lights up briefly) A7 Overvoltage present (lights up permanently) A8 Indication ERROR, e.g. in case of missing auxiliary voltage L L2 L3 CAPDIS / VOIS installed C Capacitance integrated into bushing C2 Capacitance of the connection leads and the voltage indicat to earth U LE = U N / 3 during rated operation in the three-phase system U 2 = U A = Voltage at the capacitive interface of the switchgear at the voltage indicat 48 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

49 Components Indicating and measuring equipment WEGA ZERO Voltage detecting system accding to VDE With indication A to A4 (see legend) Maintenance-free With integrated 3-phase test socket f phase comparison Degree of protection IP54. WEGA.2, WEGA.2 Vario Voltage detecting system accding to 63-5 VDE With indication A to A5 (see legend) Maintenance-free Integrated repeat test of the interface (self-moniting) With integrated function test (without auxiliary power) by pressing the Display Test pushbutton With integrated 3-phase LRM test socket f phase comparison Without integrated signaling relay Without auxiliary power Degree of protection IP54 Adjustable f different operating voltages (adjustable capacitance C2 only f WEGA.2 Vario). WEGA 2.2 Voltage detecting system accding to 63-5 VDE With indication A0 to A6 (see legend) Maintenance-free Integrated repeat test of the interface (self-moniting) With integrated function test (without auxiliary power) by pressing the Display Test pushbutton With integrated 3-phase LRM test socket f phase comparison With integrated signaling relay (auxiliary power required) Degree of protection IP54. Integrated voltage indicat WEGA ZERO HA a eps C U LE C2 U 2 LRM system plugged in Voltage indication via capacitive voltage divider (principle) L L2 L3 WEGA installed C Capacitance integrated into bushing C2 Capacitance of the connection leads and the voltage indicat to earth U LE = U N / 3 during rated operation in the three-phase system U 2 = U A = Voltage at the capacitive interface of the switchgear at the voltage indicat R-HA35-4a tif R-HA tif Integrated voltage detecting system WEGA.2, WEGA.2 Vario R-HA tif Integrated voltage detecting system WEGA 2.2 Symbols shown A0 A A2 A3 A4 A5 A6 WEGA ZERO WEGA.2 WEGA 2.2 WEGA.2 Vario L L2 L3 L L2 L3 L L2 L3 LC display gray: not illuminated LC display white: illuminated A0 F WEGA 2.2: Operating voltage not present, auxiliary power present, LCD illuminated A Operating voltage present F WEGA 2.2: Auxiliary power present, LCD illuminated A2 Operating voltage not present F WEGA 2.2: Auxiliary power not present, LCD not illuminated A3 Failure in phase L, operating voltage at L2 and L3 F WEGA 2.2: Auxiliary power present, LCD illuminated A4 Voltage present, current moniting of coupling section below limit value F WEGA 2.2: Auxiliary power present, LCD illuminated A5 Indication Dispaly Test passed F WEGA 2.2: Auxiliary power present, LCD illuminated A6 F WEGA 2.2: LCD f missing auxiliary voltage is not illuminated HA eps Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

50 Components Indicating and measuring equipment Verification of crect terminal-phase connections Verification of crect terminalphase connections possible by means of a phase comparison test unit (can be dered separately) Safe-to-touch handling of the phase comparison test unit by inserting it into the capacitive taps (socket pairs) of the switchgear. Phase comparison test units accding to 63-5 VDE R-HA eps R-HA tif Phase comparison test unit make Pfisterer, type EPV as combined test unit (HR and LRM) f Voltage detection Phase comparison Interface test Integrated self-test Indication via LED R-HA35- eps Phase comparison test unit make Hstmann, type ORION 3. as combined test unit (HR and LRM) f Phase comparison Interface testing at the switchgear Voltage detection Integrated self-test Indication via LED and acoustic alarm Phase sequence indicat R-HA35-75 eps Phase comparison test unit make Kries, type CAP-Phase as combined test unit (HR and LRM) f Voltage detection Repeat test Phase comparison Phase sequence test Self-test The unit does not require a battery. Phase comparison test unit make Hachmann, type VisualPhase LCD as combined test unit (HR and LRM) f Voltage detection with measured-value indication Interface test Undervoltage detection Documentable repeat test Phase comparison with LED signal and measured-value indication Phase angle from 80 to +80 Phase sequence evaluation Frequency quality Complete self-test 50 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

51 Components Indicating and measuring equipment Ready-f-service indicat Self-moniting; easy to read Independent of temperature and pressure variations Independent of the site altitude Only responds to changes in gas density Contactless detection of the measurand by means of a proximity switch. Mode of operation F the ready-f-service indicat, a gas-tight measurement box is installed inside the switchgear vessel. A coupling magnet, which is fitted to the bottom end of the measurement box, transmits its position to an outside armature through the non-magnetizable switchgear vessel. Then, the armature activates the proximity switch. While changes in the gas density during the loss of gas, which are decisive f the dielectric strength, are displayed, temperaturedependent changes in the gas pressure are not. The gas in the measurement box has the same temperature as that in the switchgear. The temperature effect is compensated via the same pressure change in both gas volumes. HA b eps Ready-f-service indicat 2 Stainless-steel vessel filled with SF 6 gas, relative pressure 50 kpa at 20 C Principle of operation of gas moniting with ready-f-service indicat Measurement box 2 Magnetic coupling 3 Proximity switch 3 Ready-fservice indicat R-HA tif Low-voltage compartment Low-voltage compartment with SIPROTEC 5 7SJ86 (example) F description of the SIPROTEC 5 protection devices, see page 53 and 54. Low-voltage compartment F accommodation of protection, control, measuring and metering equipment Partitioned safe-to-touch from the high-voltage part of the panel Low-voltage compartment can be removed, bus wires and control cables are plugged in Option: Higher low-voltage compartment (00 mm instead of von 935 mm) possible. Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

52 Components Protection, control, measuring and moniting equipment Protecting, controlling and moniting are the basic requirements placed on a complete bay controller across all technology generations. The properties the user expects from modern bay controllers are: multifunctionality, reliability, safety and communication capability. The increasing integration of many functions in one multifunctional device leads to an optimally suppted engineering process, IT security, service and testability, simple and safe operability of the devices and tools. On the following pages you will find functional descriptions f some selected devices. The low-voltage compartment can accommodate all customary protection, control, measuring and moniting equipment available on the market: Overview of the device types of the SIPROTEC device series: SIPROTEC 5, SIPROTEC Compact and SIPROTEC 4 SIPROTEC 5 SIPROTEC Compact SIPROTEC 4 Overcurrent protection with PMU, control and power quality Distance protection with PMU and control Line differential protection with PMU and control Combined line differential and distance protection with PMU and control Circuit-breaker management device with PMU and control Overcurrent protection f lines Transfmer protection with PMU, control, moniting Mot protection with PMU Central busbar protection Bay controllers f control/interlocking tasks with PMU and moniting, optionally with protection funktions Digital fault recder Overcurrent protection Mot protection Voltage and frequency protection Line differential protection Distribution system controller Overcurrent protection Distance protection 7SJ82, 7SJ85 7SA84, 7SA86, 7SA87 7SD84, 7SD86, 7SD87 7SL86, 7SL87 7VK87 7SJ86 7UT85 7UT86 7UT87 7SK82, 7SK85 7SS85 6MD85, 6MD86 7KE85 7SJ80, 7SJ8 7SK80, 7SK8 7RW80 7SD80 7SC80 EASY 7SJ45/7SJ46 7SJ, 7SJ60, 7SJ602 7SJ6, 62, 63, 64 7SA522 7SA6 Line differential protection 7SD, 7SD60 7SD52, 53 Transfmer differential protection 7UT62, 63, 63 Busbar protection Generat and mot protection Accessies f generat and mot protection Rapid changeover device Bay controllers U/f relay Transient earth-fault relay Breaker failure protection Automatic reclosing, synchrocheck High-impedance protection 7SS60, 7SS522 7SS52 7UM6, 7UM62, 7VE6 7UM58 7UW50; 7XR, 3PP, 7KG6, 7XT, 4NC 7VU683 6MD6, 6MD63 6MD662, 663, 664 6MB525 7RW 7SN 7SV 7VK6 7VH60 52 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

53 Components Protection, control, measuring and moniting equipment SIPROTEC 5 device series Powerful automation with graphical CFC (Continuous Function Chart) Secure serial protection data communication, also over large distances and all available physical media (fiber-optic cable, 2-wire connections and communication netwks) Recognition of static and transient earth faults (passing contact function in resonant-earthed and isolated systems) Measurement of operational values Phas Measurement Unit (PMU) f synchrophas measured values and IEEE C37.8 protocol Powerful fault recding Control of switching devices. Overcurrent protection device SIROTEC 7SJ82 Directional and non-directional time-overcurrent protection with additional functions Time optimization of the tripping times by directional comparison and protection data communication Frequency protection and rate-of-frequency-change protection f load shedding applications Overvoltage and undervoltage protection in all required variations Power protection, configurable as active reactive power protection Control, synchrocheck and system interlocking Firmly integrated electrical Ethernet pt J f DIGSI Complete 6850 (repting and GOOSE) via integrated pt J Two optional, pluggable communication modules usable f different and redundant protocols ( 6850, , DNP3 (serial+tcp), Modbus RTU Slave, protection data communication). Distance protection SIPROTEC 7SA86 Line protection f all voltage levels with 3-pole tripping Very sht tripping time Selective protection of overhead lines and cables with singleand multi-ended infeeds Time-graded backup protection to differential protection relays Suitable f radial, ring-shaped, any type of meshed systems of any voltage level with earthed, resonant-earthed isolated neutral point Main protection function: 6-system distance protection Detection of current transfmer saturation f fast tripping with high accuracy at the same time. R-HA35-77.tif R-HA35-79.tif SIPROTEC 7SJ82 SIPROTEC 7SA86 R-HA35-78.tif R-HA35-80.tif Differential protection SIPROTEC 7SD86 Line protection f all voltage levels with 3-pole tripping Phase-selective protection of overhead lines and cables with single- and multi-ended infeeds of all lengths with up to 6 line ends Transfmers and shunt reacts within the protection zone are possible Suitable f radial, ring-shaped, any type of meshed systems of any voltage level with earthed, resonant-earthed isolated neutral point Protection of lines with capacitive series compensation Directional backup protection and various additional functions. R-HA35-79.tif SIPROTEC 7SD86 Modularly expandable 2 Pluggable and retrofittable communication pts 3 Pluggable current and voltage terminal blocks R-HA35-80.tif 2 3 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

54 Components Protection, control, measuring and moniting equipment Transfmer differential protection SIPROTEC 7UT85 Transfmer differential protection f two-winding transfmers with versatile additional protection functions Universal utilization of the permissible measuring points Flexible adjustment to the transfmer vect group, controlling of making and overexcitation processes, secure perfmance in case of current transfmer saturation with different saturation degrees. Protection of standard power transfmers and autotransfmers Increased sensitivity in case of earth sht-circuits close to the neutral point by means of a separate earth-fault differential protection Additional current and voltage inputs can be provided f standard protection functions such as overcurrent, voltage, frequency, etc. In the standard version, two communication modules can be plugged in, and different protocols can be used ( 6850, , DNP3 (serial, TCP), Modbus RTU Slave). Mot protection SIPROTEC 7SK82 Mot protection functions: start-time supervision, thermal overload protection f stat and rot, restart inhibit, unbalanced load protection, load-jump protection Stat and bearing temperature moniting via a temperature sens with an external RTD box Directional and non-directional time-overcurrent protection (sht-circuit protection) with additional functions Overvoltage and undervoltage protection in all required variations Power protection, configurable as active reactive power protection Control, synchrocheck and switchgear-interlocking system Firmly integrated electrical Ethernet pt J f DIGSI Complete 6850 (repting and GOOSE) via integrated pt J Two optional, pluggable communication modules usable f different and redundant protocols ( 6850, , DNP3 (serial+tcp), Modbus RTU Slave, protection data communication). R-HA35-82.tif R-HA35-8.tif SIPROTEC 7UT85 Digital fault recder SIPROTEC 7KE85 Fast-scan recder Up to 2 slow scan recders Up to 5 continuous recders Usable as Phas Measurement Unit (PMU) accding to IEEE C37.8 Standard Transfer of recdings and triggering via 6850 Variable sampling rates programmable between khz 6 khz No-loss data compression Time synchronization via IRIG-B, DCF77 and SNTP Free mapping of measured values to the individual recders Free combination of measuring groups f power calculation Quality bits f displaying the momentary channel quality The trigger functions of a function block are the fundamental value, r.m.s. value, zero-sequence, positive-sequence, negativesequence system, Σ active, Σ reactive and Σ apparent power Level trigger and gradient trigger f each trigger function Flexible cross and netwk trigger Creation of trigger functions with the graphical automation edit CFC (Continuous Function Chart) Trigger functions by combination of single signals, double signals, analog values, binary signals, Bool signals and GOOSE messages. R-HA35-83.tif Modularly expandable SIPROTEC 7SK82 SIPROTEC 7KE85 54 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

55 Components Protection, control, measuring and moniting equipment SIPROTEC Compact series Overcurrent protection SIPROTEC 7SJ80 Pluggable current and voltage terminals Binary input thresholds settable using DIGSI (3 stages) Secondary current transfmer values (A/5A) settable using DIGSI 9 programmable function keys 6-line display Buffer battery exchangeable from the front USB front pt 2 additional communication pts 6850 with integrated redundancy (electrical optical) Relay-to-relay communication through Ethernet with 6850 GOOSE Millisecond-accurate time synchronization through Ethernet with SNTP. SIPROTEC 4 series Overcurrent and mot protection SIPROTEC 7SJ6 / 7SJ62 F stand-alone master operation Communications and bus capability Functions: Protection, control, signaling, communication and measuring LC text display (4 lines) f process and equipment data, as text, e.g. f Measuring and metering values Infmation on status of switchgear and switching device Protection data General indications Alarms Four freely programmable function keys f frequently perfmed functions Seven freely programmable LEDs f displaying any desired data Keys f navigation in menus and f entering values Fault recder. Overcurrent and mot protection SIPROTEC 7SJ63 F stand-alone master operation Communications and bus capability Functions: Protection, control, signaling, communication and measuring LC display f process and equipment data in the fm of a feeder control diagram and as text, e.g. f Measuring and metering values Infmation on status of switchgear and switching device Protection data General indications Alarms Four freely programmable function keys f frequently perfmed functions Fourteen freely programmable LEDs f displaying any desired data Two key-operated switches to switch between local and remote control and interlocked and non-interlocked operation Keys f navigation in menus and f entering values Integrated mot control by special relays with enhanced perfmance Fault recder. R-HA35-03 eps R-HA35-76.eps R-HA35-02 eps SIPROTEC 7SJ80 SIPROTEC 7SJ6 / 7SJ62 SIPROTEC 7SJ63 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Siemens HA

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated www.siemens.com/medium-voltage-switchgear Fixed-Mounted Circuit-Breaker Switchgear Type 8D and 8DB up to 0.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog H 35.11 201 nswers for infrastructure and

More information

Types. Fixed-mounted circuitbreaker. NXPLUS C is a factoryassembled,

Types. Fixed-mounted circuitbreaker. NXPLUS C is a factoryassembled, R-HA5-05a eps Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C, up to kv, Gas-Insulated Contents Application Page Types Application Types, typical uses, ratings to Requirements Features, safety,

More information

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35. Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to kv, SF 6 -Insulated Medium-Voltage Switchgear Catalog HA 5. 00 Invalid: Catalog HA 5. 00 R-HA5-05 eps Fixed-Mounted Circuit-Breaker Switchgear

More information

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated Fixed-Mounted Circuit-Breaker Switchgear Type 8D and 8DB up to 0.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog H 35. 00 nswers for energy. R-H35-30.eps pplication Public power supply system R-H35-3.eps

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec Catalog HA 41.43 Edition 2018 Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear siemens.com/simosec Application Typical uses R-HA41-135.tif R-HA40-112.tif R-HA41-115.tif

More information

medium voltage switchgear manufacturer VACUUM CIRCUIT-BREAKER SWITCHGEAR TYPE SIMOPRIME, UP TO 17.5kV, AIR INSULATED MEDIUM-VOLTAGE SWITCHGEAR. UNDER LICENSE BY SIEMENS. www.simosynergy.com/simoprime VACUUM

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable www.siemens.com/medium-voltage-switchgear Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.43 2012 Answers for infrastructure and cities. Neue Bilder

More information

Switchgear Type 8DJH 36 for Secondary

Switchgear Type 8DJH 36 for Secondary Catalog HA 40.3 Edition 2017 Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kv, Gas-Insulated Medium-Voltage Switchgear siemens.com/8djh36 Application Typical uses R-HA40-135.tif R_HA40-150a

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Totally Integrated Power SIMOSEC Catalog HA 41.43 Edition Sept. 2014 Answers for infrastructure and cities. Neue

More information

Power Transmission and Distribution. NXPLUS C double busbar. The economical solution when replacing old systems

Power Transmission and Distribution. NXPLUS C double busbar. The economical solution when replacing old systems Power Transmission and Distribution NXPLUS C double busbar The economical solution when replacing old systems The compact switchgear system NXPLUS C double busbar up to kv, up to 5 ka and up to 500A the

More information

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Catalog HA 40.2 Edition 2017 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear siemens.com/8djh Application Typical uses R-HA40-111.tif R-HA40-112.tif

More information

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear Catalog HA 26.11 2008 Answers f energy. R-HA26-010c.eps Contents Application Benefits, typical uses Application

More information

Fixed-Mounted Circuit-Breaker Switchgear up to 36 kv, SF 6 -Insulated

Fixed-Mounted Circuit-Breaker Switchgear up to 36 kv, SF 6 -Insulated Medium- Switchgear Catalog HA 35.51 2000 Supersedes: Catalog HA 35.51 1998 Contents General Infmation Page Application, features, requirements General Infmation Application, features, 2 requirements Technical

More information

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 2009 Answers for energy. -HA40-111.eps -HA40-110.eps -HA40-109.eps -HA40-112.eps

More information

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 2010 Answers for energy. -HA40-110.eps -HA40-109.eps -HA40-112.eps -HA40-111.eps

More information

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Switchgear Type 8BT1, up to 24 kv, air-insulated.   Medium Voltage Switchgear Catalog HA 26. www.siemens.com/medium-voltage-switchgear Switchgear Type 8BT1, up to 24 kv, air-insulated Medium Voltage Switchgear Catalog HA 26.31 2012 Answers for infrastructure and cities. R-HA26-013. eps Contents

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

NXAirS Withdrawable Medium-Voltage Switchgear up to 24kV Air-Insulated

NXAirS Withdrawable Medium-Voltage Switchgear up to 24kV Air-Insulated NXAirS Withdrawable Medium- Switchgear up to 24kV Air-Insulated Contents Application Types Application Types Typical uses Classification Requirements Customer benefits and features Circuit-breaker switchgear

More information

Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv

Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv Catalog HA 25.71 Edition 2016 Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv Medium-Voltage Switchgear siemens.com/nxair Application Typical applications R-HA25-366.tif R-HA25-362.tif NXAIR

More information

8DJ. Maintenance-free for lifetime

8DJ. Maintenance-free for lifetime 8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and

More information

Benefits, typical uses

Benefits, typical uses R-HA26-013. eps Switchgear Type 8BT1, up to 24kV,Air-Insulated Contents Application Page Application Benefits 2 Typical uses 2 and 3 Technical Data Ratings 4 Classification, dimensions, 5 room planning

More information

Catalog HA Edition Medium-Voltage Switchgear. siemens.com/nxair

Catalog HA Edition Medium-Voltage Switchgear. siemens.com/nxair Catalog HA 25.71 Edition 2017 Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv Medium-Voltage Switchgear siemens.com/nxair Application Typical applications NXAIR circuit-breaker switchgear is

More information

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear. Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear www.siemens.com/energy Technology s Contents Application Page Benefits 2 Typical uses 2 and 3 Technical

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.02 2011 Contents SION Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

Vacuum Circuit Breaker

Vacuum Circuit Breaker Vacuum Circuit Breaker 12/24kV VECTOR series Vacuum Circuit Breaker VMS series Metal-clad Switchgear Medium Voltage Systems 003 FM 73638 12/24kV VECTOR VCB Features of the VECTOR Vacuum Circuit Breaker:

More information

HB1 and VB1 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. siemens.com/generatorswitchgear. Catalog HB1 and VB1 Edition 2017

HB1 and VB1 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. siemens.com/generatorswitchgear. Catalog HB1 and VB1 Edition 2017 Catalog HB1 and VB1 Edition 2017 HB1 and VB1 Generat Circuit-Breaker Switchgear edium-voltage Switchgear siemens.com/generatswitchgear Application Typical uses R-HB1-001.tif R-HB1VB1-003.tif R-HB1VB1-002.tif

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities.

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities. www.siemens.com.cn/medium-voltage-switchgear Air Insulated Switchgear NXAirS, Answers for infrastructure and cities. Applications Page Application Type 2 Typical uses 3 Classification 3 Type NXAirS withdrawable

More information

Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable

Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable Switchgear Type DH0 up to kv, Gas-Insulated, Extendable Medium-Voltage Switchgear Catalog HA. 00 Answers for energy. Contents Application, Requirements Features Application, Requirements Page Features,

More information

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv] BasisBlock MC 1 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC1-12 MC1-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage

More information

HB3-80 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. Totally Integrated Power HB3-80. Catalog HB3-80.

HB3-80 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. Totally Integrated Power HB3-80. Catalog HB3-80. HB3-80 Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear Totally Integrated Power HB3-80 Catalog HB3-80 Edition 2014 www.siemens.com/generatorswitchgear R-HB1-001.tif R-HB3-001.tif R-HB3-003.tif

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

HB3 Generator Circuit-Breaker Switchgear

HB3 Generator Circuit-Breaker Switchgear Catalog HB3 Edition 2017 HB3 Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear R-HB1-001.tif R-HB3 001.tif R-HB3 003.tif R-HB3 002.jpg 2 HB3 Generator Circuit-Breaker

More information

VB1-D Generator Circuit-Breaker Switchgear

VB1-D Generator Circuit-Breaker Switchgear Catalog VB1-D Edition 2016 VB1-D Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear 05_VB1_D_ECI tif 11_VB1_D_ECI tif R-HB1-001 tif R-HB3-001 tif Application:

More information

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment General The switchgear must be suitable for 36 kv rated voltage and specifically conceived for the secondary distribution substations in M.V. with either ring or radial type networks. The switchgear must

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

Siemens AG Catalog HG11.07 Edition 10/ AE6 Medium-Voltage Equipment. siemens.com/sion

Siemens AG Catalog HG11.07 Edition 10/ AE6 Medium-Voltage Equipment. siemens.com/sion Siemens AG 2018 Catalog HG11.07 Edition 10/ 2018 SION Lateral Vacuum Circuit-B Breaker with Laterrall Operating Mechaniism m 3AE6 Medium-Voltage Equipment siemens.com/sion 2 Catalog HG11.07 10 / 2018 SION

More information

Vacuum Circuit-Breaker Modules

Vacuum Circuit-Breaker Modules Vacuum s Medium-Voltage Equipment Catalog HG.5 998 Vacuum s Medium-Voltage Equipment Description Catalog HG.5 998 Siemens AG 998 NXACT Vacuum vacuum circuit-breaker module, kv Features DIN EN ISO 900

More information

HIGS Highly Integrated Generator Circuit-Breaker Switchgear

HIGS Highly Integrated Generator Circuit-Breaker Switchgear Catalog HIGS Edition 2018 HIGS Highly Integrated Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear HIGS_2 tif HIGS_1 jpg HIGS_3 tif Application: Gas-fired steam

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

Medium-Voltage Switchgear

Medium-Voltage Switchgear Medium-Voltage Switchgear Type SIMOSEC 12 up to 12 kv, Extendable, up to 1250 A Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCTIONS Order No.: 834-6001.9 Revision: 01 Issue: 21-09-2009 About

More information

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314

More information

Features. 2 Siemens HA Page. 8DJ10 switchgear is a factoryassembled,

Features. 2 Siemens HA Page. 8DJ10 switchgear is a factoryassembled, Switchgear Type 8DJ0 up to 4 kv, Gas-Insulated Contents Application, Requirements Application, Requirements Features Designs, typical application Technical Data, Shipping Electrical data, temperature,

More information

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application

More information

with Vacuum Circuit Breaker HAF

with Vacuum Circuit Breaker HAF M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better

More information

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1. DISTRIBUTION SOLUTIONS ZX1.5-R Gas-insulated medium voltage for railway application Safety and reliability 20% footprint saving Easy operation Complete solution ZX1.5-R Gas-insulated medium voltage for

More information

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kv, ANSI, Air-Insulated, Extendable

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kv, ANSI, Air-Insulated, Extendable Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 7.6 kv, ANSI, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 4.3 008 Answers for energy. R-HA4-086 eps Contents Application Application,

More information

Distributing Power Economically. Totally Integrated Power. Gas-insulated medium-voltage switchgear: safe, compact, and reliable

Distributing Power Economically. Totally Integrated Power. Gas-insulated medium-voltage switchgear: safe, compact, and reliable Totally Integrated Power Distributing Power Economically Gas-insulated medium-voltage switchgear: safe, compact, and reliable www.siemens.com/mediumvoltage Totally Integrated Power (TIP) we bring power

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

ZX2.2 Gas-insulated medium voltage switchgear

ZX2.2 Gas-insulated medium voltage switchgear ZX2.2 Gas-insulated medium voltage switchgear 2 Brochure ZX2.2 Power engineering from ABB Solutions for the future As a technology group with global operations, ABB supplies the solutions of the future

More information

Medium-Voltage Switchgear OPERATING INSTRUCTIONS

Medium-Voltage Switchgear OPERATING INSTRUCTIONS Medium-Voltage Switchgear Circuit-Breaker Switchgear Type NXAIR: Factory-Assembled, Type-Tested and Metal- Enclosed Switchgear for Indoor Installation, Air-Insulated Loss of Service Continuity Category:

More information

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel We engineer, we assure. EMC 24 SERIES METAL CLAD SWITCHGEAR Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel Saudi Cable Company REF: EMC24-EN-16-04 2 www.elimsan.com

More information

>> WI. up to 52 kv. Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase. System configuration AREVA T&D

>> WI. up to 52 kv. Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase. System configuration AREVA T&D GAS-INSULATED SWITCHGEAR UNITS >> WI up to 52 Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase System configuration AREVA T&D Conditions of Delivery The General Conditions of Delivery

More information

Cost-Efficient Solution for Power Distribution. Gas-Insulated Medium-Voltage Switchgear: Safe, Compact and Reliable

Cost-Efficient Solution for Power Distribution.  Gas-Insulated Medium-Voltage Switchgear: Safe, Compact and Reliable www.siemens.com/mediumvoltage Cost-Efficient Solution for Power Distribution Gas-Insulated Medium-Voltage Switchgear: Safe, Compact and Reliable Answers for infrastructure and cities. Contents Gas-insulated

More information

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy. Gas-insulated medium-voltage switchgear For the mining industry Answers for energy. Full power even under extreme conditions Reliable All over the world, the demand for mineral resources is increasing.

More information

Reliable medium-voltage switchgear for fail-safe operation, up to 24 kv siemens.com/simoprime-partner

Reliable medium-voltage switchgear for fail-safe operation, up to 24 kv siemens.com/simoprime-partner SIMOPRIME partnering Reliable medium-voltage switchgear for fail-safe operation, up to 24 kv siemens.com/simoprime-partner SIMOPRIME partnering Typical applications SIMOPRIME technology partner: air insulated

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

Metal Clad Air Insulated Switchgear

Metal Clad Air Insulated Switchgear Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system

More information

ZX2 Gas-insulated medium voltage switchgear

ZX2 Gas-insulated medium voltage switchgear Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters

More information

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES 1 TABLE OF CONTENTS 1. SCOPE 2. GENERAL 2.1 STANDARDS AND REGULATIONS 2.2 OPERATING CONDITIONS 2.3 DOCUMENTATION

More information

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV CE--C-en-REV.04 2016.1 MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE- Metal Clad switchboards family are designed for use in public and industrial distribution system up to 40,5kV for the operation and

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy. Gas-insulated medium-voltage switchgear For the metal industry Answers for energy. Full power even under extreme conditions All over the world, the demand for raw materials and energy is increasing dramatically.

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Air-insulated medium voltage switchgear metal-enclosed type-tested factory-assembled withdrawable-unit design 12 kv / 24 kv

Air-insulated medium voltage switchgear metal-enclosed type-tested factory-assembled withdrawable-unit design 12 kv / 24 kv Air-insulated medium voltage switchgear metal-enclosed type-tested factory-assembled withdrawable-unit design 12 kv / 24 kv Leukhardt...switch to safety! Version 2.07.EN of 28.11.2011 page 1 of 9 Standards

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

DIRECT CONTACT. Switchgear Sales Team TEL : ~9 CHANGWON PLANT Switchgear Design Team TEL : ~9

DIRECT CONTACT. Switchgear Sales Team TEL : ~9 CHANGWON PLANT Switchgear Design Team TEL : ~9 HEAD OFFICE 450, Gongdeok-Dong, Mapo-Gu, Seoul, Korea 121-720 TEL : 82-2-707-7000 R&D CENTER 183, Hogye-Dong, Dongan-Gu, Anyang-Shi, Gyeonggi-Do, Korea 431-080 TEL : 82-31-428-1000 CHANGWON PLANT 454-2,

More information

Medium voltage vacuum circuit breaker. E-VAC series

Medium voltage vacuum circuit breaker. E-VAC series Medium voltage vacuum circuit breaker E-VAC series Product description E-VAC vacuum circuit breaker Contents Description Product description... Technical data... Dimensions... Wiring diagram... E-VAC series

More information

ZX-Family Gas-insulated medium voltage switchgear

ZX-Family Gas-insulated medium voltage switchgear ZX-Family Gas-insulated medium voltage switchgear Minimum overall costs ZX offers maximum economy The compact design of the panels reduces the space required and therefore the size of the station. Freedom

More information

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV CE - B36 - C - en - REV.00 2011.9 EDIU VOLTAGE EDIU VOLTAGE APPLICATION CE-B etal Clad switchboards are designed for use in public and industrial distribution system up to 36kV for the operation and protection

More information

TECHNICAL CATALOGUE TK 502/20 EN. ZX2 Gas-insulated medium voltage switchgear

TECHNICAL CATALOGUE TK 502/20 EN. ZX2 Gas-insulated medium voltage switchgear TECHNICAL CATALOGUE TK 502/20 EN ZX2 Gas-insulated medium voltage switchgear Contents Page 1 Introduction 5 2 Applications 6 3 Characteristics 7 4 Your benefit 8 5 Technical data 9 5.1 Technical data of

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear MEDIUM VOLTAGE PRODUCTS Powerbloc Pre-assembled modules for building medium voltage switchgear Powerbloc are the ideal solution for replacing fixed circuit breakers with withdrawable circuit breakers,

More information

Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCTIONS

Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCTIONS Medium-Voltage Switchgear Type 8DA11 / 8DA12 Fixed-Mounted Circuit-Breaker Switchgear up to 27.5 kv, extendable 1/2-Pole Switchgear for AC Traction Power Supply Medium-Voltage Switchgear INSTALLATION AND

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

TECHNICAL SPECIFICATION. UP TO 36 kv METAL-CLAD. With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

TECHNICAL SPECIFICATION. UP TO 36 kv METAL-CLAD. With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES TECHNICAL SPECIFICATION UP TO 36 kv METAL-CLAD With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES 1 TABLE OF CONTENTS 1. SCOPE 2. GENERAL 2.1 STANDARDS AND REGULATIONS 2.2 OPERATING CONDITIONS

More information

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications Medium voltage products UniSec Y800 New 24 kv air-insulated medium voltage switchgear to e-istribuzione specifications UniSec Y800 ubicles available Unit e-istribuzione specifications (Ed. 4) UniSec IS/1

More information

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE-B Metal Clad switchboards are designed for use in public and industrial distribution system up to 24kV for the operation and protection of lines, generators,

More information

36kV Gas Insulated Medium Voltage Switchgear

36kV Gas Insulated Medium Voltage Switchgear GE Industrial Solutions 36kV Gas Insulated Medium Voltage Switchgear User Manual Safety first! Important recommendations: Switchgear should be installed in a clean, dry, ventilated room suitable for electrical

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCTIONS

Medium-Voltage Switchgear INSTALLATION AND OPERATING INSTRUCTIONS Medium-Voltage Switchgear Type 8DB Extendable Fixed-Mounted Circuit-Breaker Switchgear up to 40.5 kv Double Busbar, Single-Pole Metal-Enclosed, Gas-Insulated Medium-Voltage Switchgear INSTALLATION AND

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV PT Guna Era Manufaktura Catalogue 2015 GAE TPS Medium Voltage Switchgear 12kV - 24kV General Description Introduction Safety GAE TPS is a complete unit range which can be equipped with SF6 disconnector

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

DATA SHEET 3VT3 MCCB ACCESSORIES

DATA SHEET 3VT3 MCCB ACCESSORIES Issued June 7 DATA SHEET VT MCCB ACCESSORIES Based on Siemens Catalog LV 8 VT Molded Case Circuit Breakers up to A 7 Accessies and Components es Overview Type designation accding to contact arrangement

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The

More information

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy.

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy. Gas-insulated medium-voltage switchgear For marine and offshore applications Answers for energy. Full power on the high seas This much is certain: whatever happens on the surface and on the floors of the

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

GMA. Medium-voltage switchgear

GMA. Medium-voltage switchgear Medium-voltage switchgear Gas-insulated switchgear up to 24 kv - 2500 A - 31.5 ka Earthing without automatically CLOSE / OPEN of the Circuit Breaker Operation - Maintenance Technical Manual No. AGS 531

More information