SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control
|
|
- Benjamin Wheeler
- 6 years ago
- Views:
Transcription
1 SP-32, SP-32D SP-33, SP-33D SP-34, SP-34D Single Stage Temperature Control Description The SP-3x and SP-3xD series of controls are single stage, general purpose, temperature controls with wide application in HVAC, refrigeration, and industrial applications. The setpoint temperature ranges are: SP-32 & SP-32D -26 F to +90 F SP-33 & SP-33D 40 F to 104 F SP-34 & SP-34D 90 F to 200 F The SP-3xD controls are identical to the SP-3x, except for one additional relay. The SP-3x controls provide one isolated SPDT relay output while the SP-3xD provides two (effectively DPDT). The SP-3xD also provides R-W interrupt spade terminals for Class II interlocks on the Output 2 relay. The relays on both the SP-3x and SP-3xD are controlled by comparing the thermistor temperature sensor to a setpoint temperature. The installer to can select either heat mode (relay operates on temperature Specifications Power: Approx. 2VA required from any power source: 21-27VAC, 50/60Hz 21-27VDC VAC, 50/60Hz VAC, 50/60Hz Outputs:SPDT isolated (dry)contacts, 1HP@115VAC, 2HP@240VAC 240VAC: 20A on NO contacts 10A on NC contacts Sensors: Thermistor, 25 C/77 F Type SW supplied with control Interchangeable with any IE fall) or cool mode (relay operates on temperature rise). The control setpoint can be set using the internal setpoint dial (factory setting) or you can wire a remote setpoint (see Goldline RSP series of remote setpoints) or you can wire a fixed setpoint (see Goldline ESP series of fixed setpoints) which provides high accuracy and prevents unauthorized tampering with the setting. The SP-3xD series controls also feature a plug in connector for a TD-SP Digital Display Monitor which displays sensor and setpoint temperatures. Power can be provided from a 24VAC, 24VDC, 115VAC or 240VAC power source. Relay contacts are completely isolated so the outputs can switch any voltage, regardless of the power source. On SP-3xD models, one relay output can switch high voltage, the other switch low voltage. A movable divider is provided to separate high and low voltage wiring compartments. temperature sensor 1000 ft. maximum wire run Setpoint: SP-32, SP-32D to +90 F SP-33, SP-33D 40 to 104 F SP- 34, SP-34D 90 to 200 F Differential: SP-32, SP-32D 1-25 F SP-33, SP-33D 1-15 F SP- 34, SP-34D 1-25 F Accuracy: +/- 1 F Environment: -30 to +130 F 0-95% rh, non-condensing
2 Installation Page 2 1. Mounting The SP-3x and SP-3xD series controls are designed for mounting indoors, protected from the weather and with non-condensing humidity. For outdoor use or in moist environments use a Goldine RE-1 raintight enclosure. Use the mounting screws supplied or optional mounting bracket (consult IE factory). 2. Sensor Mounting and Wiring To maximize temperature measurement accuracy securely mount the sensor and then insulate it to protect it from the effects of ambient temperature. 18 AWG twisted pair wire should be used for normal indoor runs. Sensor wiring run outdoors must be rated for outdoor use and ensure that wire connections are protected from the weather. For long runs or runs near other electrical wiring use shielded cable (Belden 8760 for indoor use or Belden 8428 for outdoor use). Ground the shields to one of the control's cover screws. If the SW sensor supplied with the control does not meet your needs, contact your distributor for information on the wide range of interchangeable Goldline temperature sensors. 3. Power input The SP-3x and SP-3xD controls require power to operate. You may connect either 24VAC to the R and C terminals; 24VDC to the R (+) and C (-); 115VAC to the terminals marked 115VAC or 208/240VAC to the terminals marked 240VAC. Connect grounds
3 Installation (Continued) to the green screw provided or use grounding clips (eg Steel City Gee clips or Raco #975). Refer to wiring diagram on page Output wiring SP-3x: The SP-3x provides one set of isolated SPDT relay outputs. If you are directly controlling a load (eg pump, blower, valve, etc), you must connect a source of power through this output relay. NO are normally open contacts which close when the control output is on. NC are normally closed contacts which open when the control output is on. Refer to the sample diagrams shown below. SP-3xD: The SP-3xD provides two sets of isolated SPDT relay outputs. If you are directly controlling a load (eg pump, blower, valve, etc), you must connect a source of power through these output relays. NO are normally open contacts which close when the control output is on. NC are normally closed contacts which open when the control output is on. Refer to the sample diagrams shown on the following page. Page 3 The output 2 relay on the SP-3xD control will be disabled when the insulated wire jumper (located next to the "R" and "W" spade terminals) is cut. Shorting across "R" and "W" will again enable the output 2 relay. This feature allows for a switch (manual, temperature, etc.) to be wired across "R" and "W" to provide additional control of the output 2 relay (see diagram on page 6). A common application of this feature is a high or low limit override for the second relay. For normal operation, when this type of control is not needed, the wire jumper should remain untouched. 5. Setpoint Controls are shipped from the factory set up to use the internal setpoint adjustment knob. If you would like to use a remote setpoint or a fixed setpoint, the internal setpoint adjustment can be disabled. To accomplish this, remove the jumper from terminals "1" and "2" and connect an RSP (potentiometer) or an ESP (fixed resistor) to terminals "2" and "3". RSP's and ESP's are available through your Goldline dealer. Setback can also be accomplished with the use of any SPDT timer. Refer to diagram on page Adjustments Set the mode jumper into the heat or cool position. Adjust the setpoint and differential to the desired settings.
4 Operation The test switch should normally be left in the AUTO position in which case operation is completely automatic with no operator intervention required. The Power indicator should always be on. The Output indicator will show the status of the control output relays. When the switch is in the ON position, the output is forced on (both relays energized) and when in Page 4 the OFF position, the output is forced off (both relays de-energized). The only exception to this is if the "R" and "W" feature is enabled. If so, the output 2 relay will be de-energized whenever continuity is broken across "R" and "W". In cool mode the control output will turn on when the sensor temperature rises to the setpoint SP-3xD SP-3xD SP-3xD
5 Operation (continued) temperature plus the differential. In heat mode the control output will turn on when the temperature falls to the setpoint temperature Page 5 minus the differential. The control output always turns off at the setpoint.
6 Page 6
7 Technical Assistance For help in installing, operating, or troubleshooting this control, you may call for technical assistance at Independent Energy s technicians are available from 8:00AM to 5:00PM Eastern Time, Monday through Friday. You may call at other times and leave a message, and a technician will call you back as soon as possible. Temperature vs. Resistance Chart All Goldline controls use 10K thermistor sensors. When disconnected from the control, the sensor will read 10 K ohms at 25 C/77 F. Refer to the chart below for the resistance at other temperatures. For a given temperature, the resistance is accurate to +/- 1%. For a given resistance the temperature is accurate to +/- 0.5 F. F OHM F OHM F OHM F OHM F OHM F OHM F OHM , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , INDEPENDENT ENERGY INC. 42 Ladd Street, East Greenwich, RI (401) (800) (401) fax P/N (G)
SOLAR AQUA. Operation and Installation Manual LDLINE AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP. Electronic Solar Control Center. for models CONTROLS INC.
AQUA SOLAR TM Electronic Solar Control Center Operation and Installation Manual for models AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP G LDLINE CONTROLS INC. www.goldlinecontrols.com 888-921-7665 IMPORTANT SAFETY
More informationSystem 350 P352AB Electronic Pressure Control Series
System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure
More informationIMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS
DIFFERENTIAL TEMPERATURE CONTROLLERS MAIN FEATURES - Microprocessor programed specifically for optimal performance of WARM AIR systems - Large easy-to-read 40 character (x0) backlit LCD display showing
More informationA419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
A419 Issue Date February 10, 2003 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures The A419 series controls are single-stage, electronic temperature
More informationA419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures
Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature
More informationIMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS
DIFFERENTIAL TEMPERATURE CONTROLLERS MAIN FEATURES - PV POWERED from 0 V to VDC with smart power management at very low PV power levels, A must, for soft FAN start & smooth controller operation - Microprocessor
More informationGL-235 Solar Pool Controller
GL-235 Solar Pool Controller Installation & Operation Manual G LDLINE CON TROLS www.goldlinecontrols.com Description The GL-235 is a differential temperature control for solar heating of pools, spas, and
More informationSetPoint 150 Controller Installation Manual
SetPoint 150 Controller Installation Manual SetPoint 150 Controller Installation Manual is published by Uponor Wirsbo, Inc. 5925 148th Street West Apple Valley, MN 55124 Phone: (952) 891-2000 Fax: (952)
More informationModel No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Model No. DFC-X Support 877-351-4702 DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This manual covers the following products: DFC-X TS-01 DFTD RDU DAT-12 PWM-10V
More informationA419ABG-3C Electronic Temperature Control
Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where
More informationLF Series At A Glance
LF Series Spring Return Direct Coupled Actuator Minimum 35 in-lb Torque For damper areas up to 8 sq-ft* Applications Cost effective quality and performance for a range of applications including: Classroom
More informationBAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)
Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant
More informationSE8300 Series Installation Guide 24 Vac Low Voltage
Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS TEC20 TEC20H ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-306D Supersedes: 2100-306C File: Volume
More informationAQUA SOLAR. Operation and Installation Manual AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP. Electronic Solar Control Center. for models CON TROLS
AQUA SOLAR TM Electronic Solar Control Center Operation and Installation Manual for models AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP G LDLINE CON TROLS www.goldlinecontrols.com IMPORTANT SAFETY INSTRUCTIONS
More informationSetPoint 501 and 501s Controllers Installation and Operation Manual
SetPoint 501 and 501s Controllers and Operation Manual SetPoint 501s SetPoint 501 Setpoint 501 and 501s Controllers and Operation Manual is published by Uponor Wirsbo, Inc. 5925 148th Street West Apple
More informationCDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems
CDBR-B Dynamic Braking Unit Instruction Manual April 2009 Part Number: 146-10001-R1 Copyright 2009 Electromotive Systems 2009 MAGNETEK All rights reserved. This notice applies to all copyrighted materials
More informationECONOMIZERS. 1/2012 Supersedes
ECONOMIZERS Litho U.S.A. 2012 506948 01 1/2012 Supersedes 506394 01 K1ECON20C 1 ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZER AND OUTDOOR AIR (604592 03; 54W77) USED WITH KG/KC/KH 180 300S UNITS
More informationSurface mounting, flush mounting, and DIN track mounting
Solid-state Timer H3JA Economical, Compact, Plug-in Timer Time limit, ON-delay, operation with automatic resetting. DIN size (36 x 36 mm), fits standard 8-pin sockets. Wide choice of supply voltages: 24,
More informationMAXIGARD A2000 SPEED SWITCH. Introduction
A107-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 MAXIGARD A2000 SPEED SWITCH Introduction The Maxigard A2000 Speed Switch is designed to monitor
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationBAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint
Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication
More informationBAPI-Stat 3 Room Sensor
Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read
More informationInstallation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas
Installation Manual IOM-MBC-00 08-30-04 Mixing Box Control Systems Installation,, and Maintenance Manual Contents Page Introduction...1 General...1 Safety...1 Inspection...1 Mixing Box Control Systems...2
More informationOperation and Installation Manual
BOMBA PRESURIZADORA AUTOMÁTICA CONTROLADOR SOLAR AQUA SOLAR SERIE MINI SMART GL-235 MINI25-10/1115-110V Electronic Solar Control Operation and Installation Manual GL-235 Description The GL-235 is a differential
More informationScrew. (Note 4) Spacer for 1" filter ILL. 3. Screw
ICP INSTALLATION INSTRUCTIONS for (NPECOMZR006A00) ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully
More information4 x 0-10Vdc Channels Fused 24V o/p terminals for actuator power Direct or buffered output signals
IO Input/Output Modules IO-ABM4 Analogue Override Module Description IO-ABM4 Analogue Override Module Intended for applications which require independent manual override of analogue output channels from
More informationApplication Engineering
Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor
More informationScrew. (Note 4) Spacer for 1" filter ILL. 3. Screw
MicroMetl INSTALLATION INSTRUCTIONS for 0637-0311 (CPECOMZR006A00) MicroMetl's 0637 economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions
More informationDFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR
24 Volt AC input Built in 15 second low fire start timer 0-24 Volt DC modulating output Remote temperature selection Calibration trim pot Rated for -40 F (-40 C) DFC-1 STANDARD TEMPERATURE CONTROL DFC-2
More informationCP (Vdc) CP (Milliamp) CP (Slidewire)
CP-91-456 (Vdc) CP-91-716 (Milliamp) CP-91-717 (Slidewire) Electronic General Instructions Application Electronic actuator drive is used to provide proportional control of an electric gear train actuator
More informationBlank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw
ICP INSTALLATION INSTRUCTIONS for NPECOMZR00A00 ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully
More informationApplication Engineering
Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the
More informationPRO REMOTE Series CAPACITANCE PROBE
Price $5.00 PRO REMOTE Series CAPACITANCE PROBE OPERATING INSTRUCTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT TABLE OF CONTENTS GENERAL SPECIFICATIONS...3 1.0 INTRODUCTION...4 2.0 APPLICATIONS...4
More informationSAV Electronic Valve Actuator
Document No. 155-548 Non-spring Return, 24 Vac/dc, 3-Position Control Description The SAV Non-spring Return (NSR), Electronic Valve Actuator requires a 24 Vac/dc supply to provide three-position (floating)
More informationCDBR-B. Instruction Manual. Dynamic Braking Unit. March 2013 Part Number: R4 Copyright 2013 Magnetek
B Dynamic Braking Unit Instruction Manual March 2013 Part Number: 146-10001 R4 Copyright 2013 Magnetek 2013 Magnetek All rights reserved. This notice applies to all copyrighted materials included with
More informationLF Series Spring Return Direct Coupled Actuator
LF Series Spring Return Direct Coupled Actuator Minimum in-lb torque LF actuator For damper areas up to 8 sq-ft* Applications Cost effective quality and performance for a range of applications including:
More informationTHC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None
THC-2, THC-3, THCR-4, THCR-5 Enthalpy Control General Instructions APPLICATION For ON-OFF (two position) low voltage control of the amount of air brought into the cooling system with respect to the total
More informationSAX Electronic Valve Actuator
SAX Electronic Valve Actuator Non-spring Return, 24 Vac, Proportional Control Technical Instructions Document No. 155-506 Description The SAX Non-spring Return (NSR), Electronic Valve Actuator requires
More informationBAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions
Product Identification Fig 1. BAPI-Com Communication Output Module Fig 2. BAPI-Com Room Sensor, BA/BS4SCOM Operations Overview The BAPI-Com sensor is designed to be used in retrofit applications on just
More informationWARNING IMPORTANT
75-540.0 5H0847510000 September, 2015 INSTALLATION/SETUP INSTRUCTIONS Electronic Mild Temperature Thermostat gas-fired duct furnace/make-up air units Model Series: D, H, I, & O Application The Electronic
More informationSeries 20 Installation Instructions
Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property
More informationBAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control
Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additional options include pushbutton override, fan
More informationLC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE
LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101194 Document revision: D DCN number: 105128 Date: 3/23/2006 1840 Industrial Circle Longmont, CO 80501 Fax: 303-678-7504 Tel: 303-678-7500
More informationR & D SPECIALTIES ROTROL I USER'S MANUAL
R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL
More informationINSTALLATION/OPERATING INSTRUCTIONS TSC
INSTALLATION/OPERATING INSTRUCTIONS TSC Two-Stage Set Point Control with External Activation Two-Stage Heating (Rotation Included) Two-Stage Cooling (Rotation Included) Change-Over Control (Heat/Cool)
More informationGE Measurement & Control
GE Measurement & Control Telaire Ventostat 8000 Series CO 2 Sensor User Instructions Installing the Sensor!WARNING! Before performing service or maintenance operations on the systems, turn OFF main power
More informationOpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary
Document No. 155-785 OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary Description The OpenAir direct coupled enhanced non-spring return rotary electric actuators are designed
More informationPOWER EXHAUST START UP PRE START UP ONCE THE POWER EXHAUST ECONOMIZER IS INSTALLED, REMOVE THE ACCESS DOORS ON THE EXHAUST CABINET. ROUTE LINE VOLTAGE CABLE FROM THE VFD TO THE DISCONNECT OR UNIT POWER
More informationRemote Temperature Controllers. Quick Selection Guide
Remote Temperature Controllers Quick Selection Guide A Complete Selection For A Wide Range Of Applications Electronic Standalone Controllers T775 Provide on/off, modulating, or reset control in applications
More informationSystem 350 S350C Temperature Slave Stage Module
FANs 930, 930.5, 125, 121 Product/Technical Bulletin Issue Date April 8, 2014 System 350 Temperature Slave Stage Module The Temperature Slave Stage Module is used in conjunction with the A350 Temperature
More information2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / /
Non-Regen Drives Non-regenerative drives are typically used on applications which primarily motor in one direction and stopping is achieved through friction or infrequent use of a dynamic braking resistor.
More informationCombined Ventilation Controller RVWS-T-224HA
Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage
More informationICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide
ICM325HN Head Pressure Control with Optional Heat Pump Override Temperature sensitive control regulates head pressure Installation, Operation & Application Guide For more information on our complete range
More informationElectric Actuator Instructions
BAC IOM Electric Actuator Instructions E024, E025, E026, E029 & E030 TABLE OF CONTENTS Electric Actuator Specifications...2 Overview...3 Actuator Wiring Diagrams...4 VMS-35 Specifications and Wiring Diagram...5
More informationPhone: Fax: Web: -
Timer - Delay-on-Make The TAC1 Series was designed to delay the operation of a compressor relay. It eliminates the possibility of relay chatter due to half-wave failure of the output. It connects in series
More informationSystem 350 S350P Proportional Plus Integral Temperature Stage Module
FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350
More informationBAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor
Product Identification and Overview Power and Communication on Just Two Wires Available with Temperature Sensing, Temperature Setpoint, Optional Occupant Override, Optional Display and Optional %RH Sensing
More informationSAVE THESE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be
More information24HR 30A SPST TM SW. Features. Long Description
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-794 Fax: 936-560-4685 ET05C 24HR 30A SPST TM SW Intermatic Inc. Catalog Number Manufacturer Description Weight per unit Product Category ET05C
More informationRevision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide
Revision 8 THERMO TECHNOLOGIES USDT 2001 Differential Controller Installation and User s Guide USDT 2001 DIFFERENTIAL CONTROLLER Installation and User s Guide Table of Contents Introduction General Information
More informationSALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN
Form 1254 BRAKETRON Electronic Motor Brake Instructions SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN TABLE OF CONTENTS SECTION TITLE PAGE I. Introduction 1 II. Specifications 1 III. Principles
More informationSLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS
SLC-811X Series TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com Single Loop Proportional Temperature Controller General Instructions APPLICATION Electronic temperature controller
More informationCT325 TEMPERATURE CONTROLLER INSTALLATION AND OPERATING INSTRUCTIONS
CT325 TEMPERATURE CONTROLLER INSTALLATION AND OPERATING INSTRUCTIONS Heat items with up to 240 watts DC only Up to 60 VDC Signals to display, on your voltmeter, the set point and actual temperatures in
More informationFlowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control
Document No. 155-507 Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control Description The Flowrite 599 Series SAX Non-spring Return (NSR), Electronic Valve Actuator
More informationLMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V
LMB- (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, V Torque min. 5 in-lb for control of damper surfaces up to sq ft. Technical Data LMB- on/off-floating Power Supply VAC ±
More informationMODEL MSD MOTION CONTROL INSTALLATION AND OPERATION
CONVEYOR COMPONENTS COMPANY 130 Seltzer Road, PO Box 167 Croswell, MI 48422 USA PHONE: (810) 679-4211 TOLL FREE (800) 233-3233 FAX: (810) 679-4510 Email: info@conveyorcomponents.com http://www.conveyorcomponents.com
More informationAMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V
AMB-(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, V Torque min. 80 in-lb for control of damper surfaces up to 5 sq ft. Application For on/off and floating point control of dampers
More informationFigure 1: WPR2 Dimensions and Hardware
Installation and Operation Instructions WPR2 Series (Max. Line Pressure < 300 PSI) Wet to Wet Differential Pressure Ø0.200" 2.60" 4.47" 5.47" 5.28" 3.00" Precautions Figure 1: WPR2 Dimensions and Hardware
More informationAccuPower AQU126B Installation Instructions
Tel 1.800.MAGLOCK info@securitron.com 1.800.624.5625 www.securitron.com AccuPower AQU126B Installation Instructions Recommended Tools & Additional Materials #2 Phillips Screw Driver Wire connectors Lead
More information- Application A Mixing Setpoint Control 153. Mechanical. Electrical 12/08
Mixing Setpoint ontrol - Application A -1 12/08 Mechanical 24 V (ac) SW2 SW1 V1 Additional zones Electrical M1 = Actuating Motor 741-24V (ac) Floating Action = Heating Load Pump = System Pump = Mix Supply
More information24-hour/Weekly Time Switch H2F
24-hour/Weekly Time Switch H2F Up to 96 ON/OFF Cycles from DIN-sized (72 x 72 mm) Timer Easy setting with color-coded programming tabs. Choose from 24-hour or 1-week models with either SPST-NO or SPDT
More informationDescription. functions including single duct pressure dependent or pressure independent systems.
Description The Meridian Basic control system converts a single zone HVAC unit into a variable air volume/variable air temperature multiple zone system. The microprocessor based Zone Manager calculates
More informationFilm-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.
Film-Tech The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment. These manuals are designed to facilitate the exchange of information related to cinema
More informationICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide
ICM 326HN/327HN Line Voltage Head Pressure Control With built-in transformer Optional heat pump override ICM326HN ICM327HN Installation, Operation & Application Guide For more information on our complete
More informationFincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible
DC Drives Flexible & Powerful single-phase DC drives provide a complete family solution from the compact Series 2120 chassis drive to the powerful Series 2230 and it s feature rich application specific
More informationGraham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual
Graham TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual Vari Speed S1000 Instruction Manual TABLE OF CONTENTS Introduction 4 Unit Features 5 Operating Conditions 6 Specifications 7 Ratings
More informationCarbon Monoxide Transmitter
Introduction The CO Transmitter uses an electrochemical sensor to monitor the CO level and outputs a 4-20 ma signal. The standard product features a 2- wire loop-powered output. Optionally, the device
More informationR81EAA-2 Economizer Circuit Board
FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration
More informationDWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/
Series 43000 Capsu-Photohelic Pressure Switch/Gage Specifications - Installation and Operating Instructions Bulletin B-34 Ø4-3/4 [120.65] 3-7/8 SQ [98.43] 3/4 CONDUIT 4-3/8 [111.13] HOUSING REMOVAL 3-1/16
More informationBOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD)
LAKEWOOD INSTRUMENTS MODEL 260 SERIES BOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD) INSTALLATION & OPERATION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI
More informationSystem 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0614 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
More informationTemperature Control Panel Wiring Diagram Model: ISPA-120-1P-15A
Temperature Control Panel Wiring Diagram Model: ISPA-0-P-5A Shift Controls, Inc. Installed Options: TC Jack Panel Connector Interlock Relay, RLY- 5A Power Cord www.shift-controls.com support@shift-controls.com
More informationAccuPower AQU128B Installation Instructions
Tel 1.800.MAGLOCK info@securitron.com 1.800.624.5625 www.securitron.com AccuPower AQU128B Installation Instructions Recommended Tools & Additional Materials #2 Phillips Screw Driver Wire connectors Lead
More informationCO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure
Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to
More informationModel 550 Series Vibration Switches
OPERATION MANUAL Vibration Switches Includes: 550 550M 550-X 550M-X Page 2 SECTION TITLE PAGE 1. INTRODUCTION... 2 2. FEATURES... 3 3. WIRING... 4 4. ANALOG METER... 4 5. TESTING... 4 6. INSTALLATION...
More informationHow to Select the RE Industrial Actuator Part Number
How to Select the RE Industrial Actuator Part Number RE 10 T F 2 Torque (in-lb) 1.5 150 3 300 6 600 8.5 850 10 1000 15 1500 20 2000 25 2500 30 3000 Reversing Electronic Torque Maximizer (optional) Increases
More informationRESISTIVITY MONITOR/CONTROLLERS
RESISTIVITY MONITOR/CONTROLLERS Installation Operation Maintenance User Manual for Models: 750, 752, 753, 762 2450 Impala Drive Carlsbad, CA 92010-7226 USA Tel: 1-760-438-2021 Fax: 1-800-869-7668 / 1-760-931-9189
More informationAA4006 Speed Sensitive Trip Unit. User Manual
AA4006 Speed Sensitive Trip Unit User Manual Software Version 2.00 Issued 01/2005 Don Controls Limited Westfield Industrial Estate Kirk Lane, Yeadon Leeds, LS19 7LX Telephone: +44 (0)845 1304946 Fax: +44
More informationMicroTech II Applied Rooftop Unit Controller
Installation and Maintenance IM-696-2 Group: Applied Systems Part Number: IM696 Date: March 2004 MicroTech II Applied Rooftop Unit Controller Used with McQuay models: RPS, RFS, RCS, RDT, RPR, RFR, RPE,
More informationControl Solutions Biofloor
MCF234 Distributor for Wired Control System COMAP proposes a new control system for heating and cooling underfloor. Consisting of a 6 or 10- channels controller (MCF234), analogic (TAF234) or electronic
More informationLPT30 TROUBLESHOOTING AND REPAIR MANUAL ALL REPAIRS SHOULD BE PERFORMED BY A QUALIFIED ELECTRICIAN
LPT30 TROUBLESHOOTING AND REPAIR MANUAL ALL REPAIRS SHOULD BE PERFORMED BY A QUALIFIED ELECTRICIAN The LPT30 is a field repairable switch. Warranty covers defective parts only. Do not return the complete
More informationOpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary
EA GDE/GLB-2 OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary Description OpenAir non-spring return, 24 Vac, floating control, direct-coupled, actuators
More informationML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators
ML640, ML740 Non-Spring Return Electric Linear Valve Actuators EATURES Quick and easy installation. No separate linkage required. Conduit connector is standard. No adjustments required. Low power consumption.
More informationO.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA
AA...A2 Differential Air Pressure Switch Installation Instructions USA CDN Table of Contents Table of Contents...Page 1 Approvals...Page 1 Attention...Page 1 Specification...Page 2 Model Description &
More informationFincor Series 2230 MKII/2240
Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new
More informationECONOMIZERS. 5/2012 Supersedes
Litho U.S.A. 2012 ECONOMIZERS 507031 01 5/2012 Supersedes 506747 01 K1ECON ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS AND OUTDOOR AIR HOODS USED WITH KG/KC/KH 024, 030, 036, 048, 060, 072, 090
More informationMODEL 422 Submersible Pump Controller
MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
Technical data sheet DRK24A-5 SuperCap rotary actuator with emergeny control function and extended functionalities for butterfly valves Nominal torque 9 Nominal voltage AC/DC 24 V Control Open-close Design
More informationSEN and SEN Outdoor Air Temperature Sensors
FANs 216, 1628.3 Product/Technical Bulletin SEN-500-2, SEN-500-3 Issue Date 0996 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors The SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors offer
More information