ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102

Size: px
Start display at page:

Download "ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102"

Transcription

1 INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL-15 CONTENTS GENERAL...2 NOTES, CAUTIONS AND WARNINGS REFERENCE...2 INSTALLATION...3 ELECTRICALCOMPONENTS... 5 START-UP...5 MAINTENANCE FIGURES HEATERINSTALLATION...2 FIELDWIRING...6 CONTROL BOX AND HARNESS SUPPORT HEATERDIMENSIONS...7 TRANSFORMERWIRING...8 TABLES HEATERCAPACITY...3 TERMINALCONNECTIONS...5 AUTOMATICRESETS...5 HEATERDIMENSIONS...8 2HFHEATERPARTS...9 2HGHEATERPARTS...9 CAUTION: SAVE THIS MANUAL READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE A-0102

2 GENERAL This instruction covers the installation and operation of these electric heat accessories. Every electric heat accessory is shipped in two parts, (1) 2HF Model Heater and (1) 2HG Model Heater. The heaters are shipped completely assembled and pre-wired with all of the power and control wiring that will be required to interconnect them with the basic unit. However, the basic LB180/LL-15 unit control transformer is not sized to handle the amp draw of the electric heat accessory controls. Therefore, the 2HF Model Heater contains a 150 VA transformer in addition to fuse holders, fuses and all connection wiring. Refer to Table 1 for accessory model numbers and for capacity ratings based on the voltage of the power supply and the mode of operation. Theseelectricheaterscanbeinstalledoneitherverticalor horizontal units supplied with ductwork. Note: The Electric Heat Accessory is not ETL approved on freestanding units equipped with a Supply Air Plenum Accessory. Split-system units equipped with an electric heat accessory will require only one power supply for both the heater elements and the supply air blower motor. Refer to Figures 1 and 4 for the locations of both the power and the control wire access openings and to the following instructions for routing and connecting the wires. When an indoor unit is equipped with electric heat, provide at least 1 Inch clearance to combustible material around heater cabinet, supply air plenum and supply air ducts up to 3 feet from unit. NOTES, CAUTIONS AND WARNINGS Installer should pay particular attention to the words: NOTE, CAUTION, andwarning. Notesare intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not followed correctly. REFERENCE Refer to the indoor section instructions for additional information on the installation of the basic unit, for the application limitations of the total system and for the minimum clearance requirements of the indoor unit. FIGURE 1 : HEATER INSTALLATION Unitary Products Group 2

3 TABLE 1: HEATER CAPACITY HEATER MODEL HEATING CAPACITY 1 HEATER RATING CONTROL BOXSIDE 1ST. STAGE OPPOSITE CONTROL BOX SIDE 2ND. STAGE POWER SUPPLY 1ST. STAGE KW 2ND. STAGE KW 20 kw 2HF HG HF HG kw 2HF HG HF HG kw 2HF HG HF HG Capacity ratings do not include heat generated by the supply air blower. INSTALLATION WARNING If the unit is connected to power sources, make sure that all electrical power to the unit has been disconnected prior to installation Install these electric heat accessories per the following step-by-step procedures and the illustrations shown in Figures 1 and Remove the electrical heat accessories from their shipping containers. 2. Remove the control box access panels from the heater cabinets. 3. Remove both end access panels of the indoor unit blower section. 4. Remove the cover from the indoor unit electrical control box. 5. Remove the two 1 knockouts from the top of the indoor unit. See Figure 1 for their location. These knockouts are located in the top panel on both sides of the unit. 6. Remove the 3/4 knockout from the bottom of the 2HF heater cabinet. 7. Remove the four #10 x ½ screws from the top of the indoor unit. Two each located adjacent to the outside edge of both Air Supply Duct Flanges. See Figure 1 for their location.. 8. Set the 2HF heater cabinet on top of the unit as shown in Figure1. 9. Position the heater so that: The duct flanges around the unit s supply air opening fit into the heater opening. The 3/4 knockout hole in the bottom of the heater control box aligns with the 1 knockout removed per step 5. The two slotted screw holes in the bottom of the heater control box align with the two holes on the top of the indoor unit, where screws were removed per step Secure the heater to the unit at the holes aligned per step 9 using the two #10 x ½ screws previously removed from the top panel per step 7. See Figure Drill three 5/32 holes through the top of the unit using, as a template, the holes in the ¾ mounting flange located on the opposite end of the electric heater. See Figure Secure the heater to the unit at these locations using the three remaining #10 x ½ screws provided with the accessory. 13. Insert snap bushing into the 3/4 knockout hole, removed per step 6, and through the 1 knockout removed from the top of unit per step Route the heater wiring harness through the snap bushing. 15. Repeat steps 7 14 for the mounting of the 2HG heater cabinet. This heater is mounted opposite the control box of the indoor unit. See Figure 1. 3 UnitaryProductsGroup

4 16. Insert the 3/4 snap bushing, provided with the accessory, in the side panel of the indoor unit electrical control box.seefigure Route line voltage wires 724/R, 725/R and 726/R of the 2HF heater wiring harness through the bushing installed per step 16. Connect 724/R to Terminal L1 on Contactor (M1). Contactor (M1) is located in the indoor unit control box. Connect 725/R to Terminal L2 on Contactor (M1). Connect 726/R to Terminal L3 on Contactor (M1). Secure this harness to the support angles with wire ty-raps (provided). 18. Route control voltage wires 801/R, 804/BK, 806/BL and 811/BK of the 2HF heater wiring harness through the bushing installed per step 16. Connect 801/R to Terminal W1 on Terminal Block (TB1). Connect 804/BK to Terminal HC on Terminal Block (TB1). Connect 806/BL to Terminal C on Terminal Block (TB1) Connect 811/BK to Terminal HR on Terminal Block (TB1) Secure this harness to the support angles with wire ty-raps (provided). 19. Route line voltage wires 735/R, 736/R and 737/R of the 2HG heater wiring harness through the snap bushing on the bottom of the 2HF heater control box. Connect 735/R to Terminal L1 on Terminal Block (TB10). Connect 736/R to Terminal L2 on Terminal Block (TB10). Connect 737/R to Terminal L3 on Terminal Block (TB10). Secure this harness to the support angles with wire ty-raps (provided). 20. Route control voltage wires 830/W, 833/BK, 835/BL and 836/BK of the 2HG heater wiring harness through the bushing installed per step 16. Connect 830/W to Terminal W2 on Terminal Block (TB1). Connect 833/BK to Terminal HC on Terminal Block (TB1). Connect 835/BL to Terminal C on Terminal Block (TB1) Connect 836/BK to Terminal HR on Terminal Block (TB1) Secure this harness to the support angles with wire ty-raps (provided). 21. Place new terminal label (provided in kit) over old terminal label in the indoor unit control box. 22. Remove existing 75 VA Transformer (T1) from the indoor unit control box. 23. Install new 150 VA Transformer (T1) (provided) in the indoor unit control box, with screws removed from step 21. Mounting holes are pre-punched in the control panel at the position marked Transformer (T1) as shown on the unit connection diagram. 24. Install Transformer (T1) Fuse Holders and Fuses (FU1/ FU2/FU3) in the indoor unit control box (with screws provided). Mounting holes are pre-punched in the control panel at the position marked Optional Fuses (FU1/FU2/ FU3) as shown on the unit connection diagram. 25. Wire new Transformer (T1) and Fuse Holders (FU1/FU2/ FU3) to Figure 5 as follows: Connect wire 105/BL to the Common Primary Terminal on Transformer (T1). Connect wire 104/BK to the appropriate Primary Terminal on Transformer (T1) for the Supply Voltage of the unit. Connect wire 204/BR to one of the 24 Volt Secondary Terminals of Transformer (T1). Connect wire 206/RD to the other 24 Volt Secondary Terminal of Transformer (T1). Remove end of existing wire 104/BK from Terminal L1 on Contactor (M1) and connect it to Fuse (FU1). Connect wire 750/BK from Terminal L1 on Contactor (M1) to Fuse (FU1). Remove end of existing wire 105/BL from Terminal L2 on Contactor (M1) and connect it to Fuse (FU2). Connect wire 751/BL from Terminal L2 on Contactor (M1) to Fuse (FU2). Remove end of existing wire 206/RD from 3 amp. Circuit Breaker (CB1) and connect it to Fuse (FU3). Remove end of existing wire 205/RD from 3 amp. Circuit Breaker (CB1) and connect it to Fuse (FU3). Remove end of existing wire 205/RD from Terminal 7 on Blower Relay (BR1) and connect it to Terminal HR on Terminal Block (TB1). Remove end of existing wire 204/BR from Contactor (M1) Holding Coil and connect it to Terminal HC on Terminal Block (TB1). Connect wire 850/BR from Contactor (M1) Holding Coil to Terminal HC on Terminal Block (TB1). Unitary Products Group 4

5 Connect wire 851/RD from Terminal 7 on Blower Relay (BR1) to Terminal HR on Terminal Block (TB1). Note: All field wiring must follow all city, local and / or national codes in effect at time of installation of this heater. 26. Use knockout (provided) on the back of 2HF heater for field supplied main power conduit. See Figure 4. Route power wiring into 2HF heater control box, and connect the power and ground wires to the Terminal Block (TB10) and ground lug as shown on the 2HF heater wiring diagram. 27. Use 7/8 knockout (provided) on top of unit for field supplied control-wiring conduit. See Figure 1 for its location. Connect control wiring as shown in Figure Make sure all electrical connections are tight. 29. Replace all panels and control box covers. The indoor unit electrical control box cover. Both end access panels of the indoor blower section. Both heater control box access panels. TABLE 2: TERMINAL CONNECTIONS 2HF Heater kw Terminal Designation on TB1 2HG Heater Terminal Designation on TB1 C W1 HR HC kw C W2 HR HC /BL 801/R 811/BK 804/BK /BL 830/W 836/BK 833/BK /BL 801/R 811/BK 804/BK /BL 830/W 836/BK 833/BK ELECTRICAL COMPONENTS These electric heat accessories include staging relays, contactors and two high limit controls (1 LC and 2 LC). On a call for heat the staging relay is energized through the system thermostat. The staging relay contacts close, energizing the heater contactor. The heater contactor contacts close energizing the heater element. The high limit controls are in series with the staging relay contacts to prevent the electric heat accessory from operating at an excessive temperature. They will open and reset automatically at the temperatures listed below. Open the main disconnect switch before servicing the heating accessory. TABLE 3: AUTOMATIC RESETS HIGH LIMIT CONTROL WARNING LOCATION 2HF & 2HG OPENS CLOSES 1LC Entering F 80 0 F 2LC Leaving F 80 0 F START-UP Make sure that all electrical connections are tight before closing the disconnect switch to the indoor unit. Close the disconnect switch and check the operation of each heating stage. Check the total unit CFM in accordance with the basic unit instruction as referenced on page 2. De-energize the electric heat accessory after it has been operating for several hours, and recheck all of the electrical connections for tightness. MAINTENANCE CAUTION Failure to properly adjust the supply air CFM could cause nuisance tripping of the high limit controls. Although these electric heat accessories do not require any specified maintenance, the factory recommends a semiannual inspection of all components to see if they are functioning properly. Check all unit filters for dirt accumulation. Dirty filters will restrict air flow and could cause nuisance tripping of the high limit controls. Filters must be changed as often as necessary to assure good air flow and filtering action. 5 UnitaryProductsGroup

6 FIGURE 2 : FIELD WIRING Unitary Products Group 6

7 FIGURE 3 : CONTROL BOX AND HARNESS SUPPORT FIGURE 4 : HEATER DIMENSIONS 7 UnitaryProductsGroup

8 TABLE 4: HEATER DIMENSIONS HEATER MODEL 1 NOM. KW HEATER DIMENSIONS (INCHES) A B C D E F G H K L M 2HF , HF , HG , /4 25-1/ /2 5 1/2 1 1/2 1 1/2 22-1/4 19-1/4 2HG , The 2HF heaters are installed on the drive side of the Indoor unit. The 2HG heaters are installed on the opposite end. FIGURE 5 : 150 VA TRANSFORMER WIRING Unitary Products Group 8

9 TABLE 5: 2HF HEATER PARTS ITEM QTY. PART NO. DESCRIPTION 1* 1ea ea (T1) Transformer, 150 VA 208/230 Volt. (T1) Transformer, 150 VA 460 Volt. 2 2ea Transformer Pri. Fuse Holder 3 2ea Transformer Pri. Fuse 4 1ea Transformer Sec. Fuse Holder 5 1ea Transformer Sec. Fuse 6 4ea Screw, PNH #6-32 X.5 7 2ea Screw, PNH #8-32 X.5 8 6ea Screw, Hex #10 X.5 9 2ea Bushing, Snap 10 1ea Terminal Label 11 6ea Cable Strap 12 1ea 750/BK Wire 13 1ea 751/BL Wire 14 1ea 850/BR Wire 15 1ea 851/R Wire From Terminal L1 on (M1) Contactor to Fuse (FU1) From Terminal L2 on (M1) Contactor to Fuse (FU2) From (M1) Contactor Holding Coil to Terminal (HC) on Terminal Block (TB1) From Terminal (7) on Blower Relay (BR1) to Terminal (HR) on Terminal Block (TB1) *Depends on Primary Voltage of heater ordered. TABLE 6: 2HG HEATER PARTS ITEM QTY. PART NO. DESCRIPTION 1 3ea Screw, Hex #10 X.5 2 1ea Bushing, Snap 3 6ea Cable Strap 9 UnitaryProductsGroup

10 Unitary Products Group 10

11 11 UnitaryProductsGroup

12 Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group All rights reserved. Supersedes: Nothing A-0102 Unitary 5005 Interstate Norman Product Drive OK Group North 73069

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS ELECTRIC HEAT ACCESSORY MODELS THROUGH 55 AND HH5 & 55 NOTE: These heater accessories may be installed before or after the unit has been set on a curb or slab. Table

More information

INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY MODELS 2NH THRU 2NH045025, 2NP THRU 2NP045025, 2ND , AND 2NX GENERAL

INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY MODELS 2NH THRU 2NH045025, 2NP THRU 2NP045025, 2ND , AND 2NX GENERAL INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY S NH0005 THRU NH005, NP000 THRU NP005, ND006, AND NX006 Supersedes: 0-65-003-D-05 0-65-003-E-0705 GENERAL This instruction covers the installation of

More information

INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY MODELS 2NH THRU 2NH045025, 2NP THRU 2NP045025, 2ND , AND 2NX GENERAL

INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY MODELS 2NH THRU 2NH045025, 2NP THRU 2NP045025, 2ND , AND 2NX GENERAL INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY S NH0005 THRU NH005, NP000 THRU NP005, ND006, AND NX006 Supersedes: 0-65-003-A-0704 0-65-003-B-005 GENERAL This instruction covers the installation of

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS 5-799- REV. A (/) ACCESSORY KIT INSTALLATION INSTRUCTIONS ELECTRIC HEAT ACCESSORY MODELS HE595 THRU 55 AND HH55 & 55 NOTE: Note: These heater accessories may be installed before or after the unit has been

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS BLOWER OVERLOAD KIT MODELS 2MP04702100, 2MP04702200 692486-UAI-B-0112 For 20 Ton Generation 1 And 2 Split System Indoor Units WITH 7.5 HP Motor TABLE 1: BLOWER OVERLOAD

More information

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil

More information

INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS

INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS NOTE TO INSTALLER The words SHALL and MUST indicate a requirement which is essential to satisfactory and safe product

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only GENERAL These split-system condensing units are designed to

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: 036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 00, HB 60 / 80 / 600, HF-25, HL-0 / -0 / -50 Models GENERAL These split-system condensing units

More information

NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B)

NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B) www.source1parts.com HVAC SERVICE PARTS NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B) Supersedes:Nothing 035-23123-001 Rev. A (1011) 1 of 8 CONDENSER ROOF (SEE FIGURE 2) EVAPORATOR

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS GENERAL Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 00, HB 60 / 80 / 600, HF-25, HL-0 / -0 / -50 Models These split-system condensing units

More information

AUXILIARY ELECTRIC HEATER KITS FOR 7.5, 10, 15 AND 20 TON COMMERCIAL AIR HANDLERS RXHE-CE, DE

AUXILIARY ELECTRIC HEATER KITS FOR 7.5, 10, 15 AND 20 TON COMMERCIAL AIR HANDLERS RXHE-CE, DE AUXILIARY ELECTRIC HEATER KITS FOR 7., 10, 1 AND 20 TON COMMERCIAL AIR HANDLERS RXHE-CE, DE WARNING: THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UN - SATISFACTORY

More information

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ) 550.39-TG1YI (994) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H5CE090 & H3CE120 7.5 AND 10 NOMINAL TONS (World 50HZ) HCE090 SUNLINE 2000 DESCRIPTION These Sunline 2000 units are completely assembled, piped

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS ELECTRIC HEAT ACCESSORY MODELS 2TP04510325 THROUGH 2358 FOR USE IN 3-5 TON PACKAGE PRODUCT (60Hz) 565402-UAI-A-0310 INSTALLATION Improper installation, adjustment,

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS ELECTRIC HEAT ACCESSORY MODELS 2TP04540925 THROUGH 543658 INSTALLATION Improper installation, adjustment, service or maintenance can cause injury or property damage.

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 300, HB 360 / 480 / 600, HF-25, HL-30 / -40 / -50 Models GENERAL These split-system condensing

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA300, HB360/480/600, HF-25, HL-30/-40/-50 and J25HA, J30/40/50 HB Models GENERAL These split-system

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners YD360/480/600, YJ-30/-40/-50 and J30/40/50 YD Models 642546-UAI-A-080 GENERAL Standard operation

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS GAS HEAT KIT FOR -60 F OPERATION KIT MODELS 2BC04700106, 2BC04700151 and 2BC04700154 FOR SINGLE PACKAGE AIR CONDITIONERS 6.5 THRU 12.5 TONS MODELS DM, DL, J**DM,

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS SUPPLY AIR PLENUM ACCESSORY MODELS 1SP0412, 1SP0413, 1SP0414 For 7.5 Thru 20 Ton Generation 2 Split-System Indoor Units and 7.5 Thru 20 Ton Generation 2 Split-System

More information

DESCRIPTION FEATURES

DESCRIPTION FEATURES SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H5CE150, H5CE180 AND H5CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at

More information

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15, 20 & 25 TONS MODELS: J07 thru 25NC, 2-PIPE J10 thru 20ND, 4-PIPE

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15, 20 & 25 TONS MODELS: J07 thru 25NC, 2-PIPE J10 thru 20ND, 4-PIPE SUBMITTAL DATA SHEET SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15, 20 & 25 TONS MODELS: J07 thru 25NC, 2-PIPE J10 thru 20ND, 4-PIPE JOB NAME: LOCATION: PURCHASER: ORDER NO: ENGINEER: SUBMITTED TO: FOR:

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners (H5CE180/240, HEHB180/240 and J15/20H5CE odels Only) 350160-UAI-B-0709 GENERAL Standard split-system

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS 550.13-TG11Y (0500) SPLIT-SYSTEM EVAPORATOR BLOWER K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS EER 8.5 DESCRIPTION This completely assembled dual circuit evaporator blower includes a well-insulated

More information

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT Service Literature Corp. 9711 L7 CB29M CB30M ELITE 10 CB29M and ELITE 12 CB30M SERIES UNITS INCLUDING ECB29 The Elite 10 CB29M and Elite 12 CB30M are high efficiency blower coils. Several models are available

More information

Air Handlers. ACBX32CM 3 Phase Multi-Position FEATURES AND BENEFITS. Application. Components. Cabinet. Accessories. Warranty ACBX32CM-100 (07/2011)

Air Handlers. ACBX32CM 3 Phase Multi-Position FEATURES AND BENEFITS. Application. Components. Cabinet. Accessories. Warranty ACBX32CM-100 (07/2011) Air Handlers ACBX32CM 3 Phase Multi-Position ACBX32CM-100 (07/2011) FEATURES AND BENEFITS Application Environmentally friendly R410A refrigerant 3, 4, and 5 ton nominal capacities Multi-position applications

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION 0 F LOW AMBIENT ACCESSORY MODELS 2LA04703425, 3546 & 3658 (208, 230, 460 & 575 VOLT APPLICATIONS) Supersedes: 530.18-N5.6V (1091) 530.18-N5.6V (1193) FOR 15, 20 & 25 TON COOLING

More information

MF Product Specifications

MF Product Specifications Product Specifications MODULAR ELECTRIC FURNACE 2, 3, 4, and 5 TONS FEATURES Modular Blower Cabinet, Air Conditioning or Heat Pump ready Upflow, horizontal right or left applications Downflow requires

More information

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S P R O D U C T S P E C I F I C AT I O N S A I R H A N D L E R S CB6UH-R MERIT Series R- - Upflow / Horizontal Bulletin No. 1067 April 01 Supersedes January 01 Nominal Capacity - 1.5 to 5 Tons Optional Electric

More information

BCE3V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY

BCE3V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER FORM NO. -100 (03/2017) APPLICATION 1.5-5 ton systems Upflow and horizontal Sequenced for demand management External access to heater circuit breakers INSTALLATION

More information

ELITE SERIES R-410A Ready - Multi-Position

ELITE SERIES R-410A Ready - Multi-Position PRODUCT SPECIFICATIONS AIR HANDLERS CBXM ELITE SERIES R-0A Ready - Multi-Position Bulletin No. 0 October 07 Supersedes June 0 Nominal Capacity -. to Tons Optional Electric Heat -. to 0 kw MODEL NUMBER

More information

Installation Instructions

Installation Instructions 08A0, 09A0, 08A00, 08A00 For Use With Horizontal EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY HORIZONTAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS

More information

Installation Instructions

Installation Instructions CRPWREXH08A0, CRPWREXH09A0, CRPWREXH08A00, CRPWREXH08A00 For Use With Horizontal EconoMi$er IV, EconoMi$er, or EconoMi$er X (W70) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... PACKAGE

More information

PAB SERIES 3thru6-1/3Ton. Belt Drive 10 SEER CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT /01

PAB SERIES 3thru6-1/3Ton. Belt Drive 10 SEER CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT /01 PAB SERIES 3thru6-1/3Ton Belt Drive CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT 10 SEER SINGLE PACKAGE Electric cooling, self contained for year-round comfort. Systems can be installed on roof top

More information

Installation Instructions

Installation Instructions 00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON

More information

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS 550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece

More information

DESCRIPTION FEATURES

DESCRIPTION FEATURES TECHNICAL GUIDE MODELS: N*AH Modular Air Handlers For use w / Split System Cooling & Heat Pump 600-2000 CFM Blowers 2-5 Ton Coils Optional 1 & 3 Electric Heaters DESCRIPTION This unique modular system

More information

SUNLINE 2000 TM TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS

SUNLINE 2000 TM TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS TECHNICAL GUIDE SUNLINE 2000 TM SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS MODELS B2CH 180 & B1CH 240 15 & 20 NOMINAL TONS 9.9-8.8 EER DESCRIPTION York Sunline 2000 Heat Pumps are convertible single package

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls UNIT OBJECTIVES After studying this unit, the reader should be able to Describe and identify power- and non-power-consuming Describe

More information

Predator Model Number Nomenclature

Predator Model Number Nomenclature DM, DH 6.5, 7.5, 8.5, 10.0, 12.5 Ton Single Package Air Conditioner HVAC SERVICE PARTS Supersedes: 035-17288-000 Rev A (800) 035-17288-001-A-0804 Predator Model Number Nomenclature 1 of 16 D H 120 N 20

More information

Installation Instructions

Installation Instructions 30RAP010-150, 38APS05-065, 38APD05-130 Ground-Fault Interrupter Convenience Outlet Accessory Installation Instructions Part No. 30RA-900---058, 30RA-900---059 SAFETY CONSIDERATIONS Installation of this

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

MV Product Specifications

MV Product Specifications Product Specifications MODULAR VARIABLE SPEED BLOWER CABINET 2, 3, 4, and 5 TONS FEATURES Variable Speed modular blower Supports two stage outdoor units Dehumidification Speed: 80% Airflow Efficient low

More information

Installation Instructions

Installation Instructions H3HK Series Installation Instructions Large Package Electric Heater Kits Description Installation of 208/240V H3HK Heater Kits in Packaged Air Conditioners and Packaged Heat Pumps. These instructions are

More information

B2HZ SERIES - 13 SEER SINGLE PACKAGED HEAT PUMPS (R-410A, STYLE A,B)

B2HZ SERIES - 13 SEER SINGLE PACKAGED HEAT PUMPS (R-410A, STYLE A,B) www.source1parts.com HVAC SERVICE PARTS B2HZ SERIES - 13 SEER SINGLE PACKAGED HEAT PUMPS (R-410A, STYLE A,B) Supersedes:Nothing 035-23152-001 Rev. A (0212) 1 of 10 74 73 70 72 71 80 76 66 77 68 69 67 78

More information

WPS-104 Heater Installation Instructions For 500EFI, 700 XP, & Crew Applications

WPS-104 Heater Installation Instructions For 500EFI, 700 XP, & Crew Applications WPS-104 Heater Installation Instructions For 500EFI, 700 XP, & Crew Applications ORDER OF INSTALLATION FOR A COMPLETE ENCLOSURE OF A RANGERWARE WPS (Weather Protection System) IS AS FOLLOWS: 1. Heater

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2005 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CB29M & CB30M Elite Series Units MULTI POSITION BLOWER COILS 504,79M 09/05 Supersedes 04/05 Litho U.S.A. RETAIN THESE INSTRUCTIONS

More information

Typical Applications. Horizontal Installation

Typical Applications. Horizontal Installation ENGINEERING DATA COILS COIL UNITS CB19 AND CBH19 SERIES UP-FLOW, DOWN-FLOW AND HORIZONTAL COIL UNITS *12,600 to 65,500 Btuh (3.7 to 19.2 kw) Cooling Capacity 11,500 to 60,000 Btuh (3.4 to 17.6 kw) Heat

More information

TECHNICAL GUIDE. Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

TECHNICAL GUIDE. Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES TECHNICAL GUIDE Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE NATURAL GAS 40-130 MBH INPUT EFFICIENCY RATING CERTIFIED DESCRIPTION These high efficiency, dedicated

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE NATURAL GAS 40-130 MBH INPUT EFFICIENCY RATING CERTIFIED DESCRIPTION These high efficiency, dedicated

More information

G23 Bulletin # September 1998 Supersedes June 1995

G23 Bulletin # September 1998 Supersedes June 1995 ENGINEERING DATA ELITE 80Z UP-FLOW GAS FURNACES *80.0% to 80.8% A.F.U.E. 50,000 to 150,000 Btuh (14.7 to 44.0 kw) Gas Heating Input 1 thru 6 Tons (3.5 thru 21.1 kw) Nominal Add-On Cooling *Isolated Combustion

More information

SINGLE PACKAGE AIR CONDITIONING WATER COOLED

SINGLE PACKAGE AIR CONDITIONING WATER COOLED MODELS: CU060-300 5-25 TONS VERTICAL SINGLE PACKAGE AIR CONDITIONING WATER COOLED MODELS: CH060-5-10 TONS HORIZONTAL FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TABLE OF CONTENTS

More information

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS (500) SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DBHB/DBUC 180 & 40 15 AND 0 NOMINAL TONS 8.5-8.7 EER DESCRIPTION These units are convertible single package units. All models

More information

TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE DESCRIPTION

TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE DESCRIPTION Heating TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE NATURAL GAS 58-188 MBH OUTPUT Air Conditioning R DESCRIPTION This

More information

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS TECHNICAL GUIDE HIGH-EFFICIENCY WATER SOURCE H PUMPS AND WATER COOLED AIR CONDITIONERS HORIZONTAL & VERTICAL MODELS 1/2-5 TONS GENERAL All Models 1/2-5 tons ship as factory-charged packages. Horizontal

More information

TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE DESCRIPTION

TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE DESCRIPTION Heating TECHNICAL GUIDE MODELS: P*HM, P*DH, P*LB OIL-FIRED WARM AIR UPFLOW / HORIZONTAL, DOWNFLOW / HORIZONTAL AND LOWBOY FURNACES 80 AFUE NATURAL GAS 58-188 MBH OUTPUT Air Conditioning R DESCRIPTION This

More information

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS (1100) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H3CE180 & 240 15 AND 20 NOMINAL TONS DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at the factory to provide one-piece

More information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone. INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is

More information

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited. SERVICE MANUAL ELECTRIC BRAISING PANS (30 & 40 GALLON) VE30 VE40 ML-126849 ML-126850 VE40 SHOWN - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used

More information

F2FP (G), F3FP (TG) SERIES FAN COIL UNIT

F2FP (G), F3FP (TG) SERIES FAN COIL UNIT www.source1parts.com F2FP (G), F3FP (TG) SERIES FAN COIL UNIT HVAC SERVICE PARTS Supersedes:035-20107-001 Rev. A (0704) 035-20107-001 Rev. B (0806) 1 of 8 7 17 16 14 3 4 5 2 6 23, 24, 25 29, 30, 31 15

More information

Installation Instructions

Installation Instructions CR101A00-CR112A00, CR103B00,CR104B00, CR113B00 - CR116B00 CR117A00-CR119A00 CR264A00-CR269A00, CR288A00-CR299A00 CR301A00,CR308A00 CR316A00-CR322A00 CRSINGLE037A00-CRSINGLE054A00 Installation Instructions

More information

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60 TECHNICAL GUIDE GUARDIAN SERIES DRY SHIP AIR CONDITIONER CONDENSING UNITS SHIPPED WITH NITROGEN CHARGE ONLY 13 SEER R-22 1 PHASE 1.5 THRU 5 NOMINAL TONS MODELS: GCGD18 THRU 60 UARDIAN Due to continuous

More information

AHKD SERIES ELECTRIC RESISTANCE HEAT KITS INSTALLATION & OPERATING INSTRUCTIONS

AHKD SERIES ELECTRIC RESISTANCE HEAT KITS INSTALLATION & OPERATING INSTRUCTIONS AHKD SERIES ELECTRIC RESISTANCE HEAT KITS INSTALLATION & OPERATING INSTRUCTIONS Made in the USA by: Goodman Manufacturing Company, L.P. 2550 North Loop West, Suite 400 IO-608 Houston, TN 77092 AHKD SERIES

More information

Accessory 44 Strip Heater. Automatic Transfer Switches. Wiring. Mounting H

Accessory 44 Strip Heater. Automatic Transfer Switches. Wiring. Mounting H Accessory 44 Strip Heater for Automatic Transfer Switches Accessory 44 Strip Heater is designed to keep humidity and/or temperature within the ATS enclosure at acceptable levels. This accessory consists

More information

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS 550.23-TG1Y (595) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H4CE090 & H2CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 8.9-9.5 EER SUNLINE 2000 HCE090 208/230/460 VOLT ONLY 208/230/575 VOLT ONLY DESCRIPTION

More information

BCE5V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS ACCESSORIES WARRANTY

BCE5V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS ACCESSORIES WARRANTY PRODUCT SPECIFICATIONS APPLICATION 1 1/2-5 ton systems Sequenced for demand management External access to heater circuit breakers FORM NO. -100 (12/2018) INSTALLATION 1 piece design Smaller profile for

More information

E1RA, E2RA SERIES - 10 SEER, 1PH & 3PH HEAT PUMP- OUTDOOR UNIT

E1RA, E2RA SERIES - 10 SEER, 1PH & 3PH HEAT PUMP- OUTDOOR UNIT L2 L1 LOW SIDE PRESSURE PORT www.source1parts.com E1RA, E2RA SERIES - 10 SEER, 1PH & 3PH HEAT PUMP- OUTDOOR UNIT HVAC SERVICE PARTS Supersedes:035-13604-001 Rev. E (0603) 035-13604-001 Rev. F (0104) 1

More information

SUNLINE 2000 (WORLD 50 HZ)

SUNLINE 2000 (WORLD 50 HZ) 530.26-TG1YI (298) SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS D3CE 036, 048, 060 & 076 D5CG 036, 048, 060 & 076 3, 4, 5 AND 6 NOMINAL TONS SHOWN SUNLINE 2000 (WORLD 50 HZ) DESCRIPTION YORK Sunline 2000

More information

Eclipse 2000 Service Parts

Eclipse 2000 Service Parts This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior

More information

WATER SOURCE HEAT PUMPS REPLACEMENT PARTS MANUAL MODELS: General Notes. Contents. Important

WATER SOURCE HEAT PUMPS REPLACEMENT PARTS MANUAL MODELS: General Notes. Contents. Important REPLACEMENT PARTS MANUAL WATER SOURCE HEAT PUMPS MODELS: GTB-A GTA300UDAA GTA0UDAA GTC3S2-ADC GTCS2-ADC GTC0S2-ADC GTC3S2-ADN GTCS2-ADN GTC0S2-ADN Blower Section Coil Section Coil Section General Notes

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS MiniCOREVentilator ENERGY RECOVERY CORE INSTALLATION INSTRUCTIONS MC500-1ERV JANUARY 10, 2018 SUPERSEDES: NONE INSTALLATION INSTRUCTIONS FOR MINICORE VENTILATOR (MCV) WITH FACTORY INSTALLED OPTIONS USED

More information

ETP-5E & ETP-10E ECO-TECH PLUS ELECTRIC CONVECTION STEAMER PARTS AND SERVICE MANUAL

ETP-5E & ETP-10E ECO-TECH PLUS ELECTRIC CONVECTION STEAMER PARTS AND SERVICE MANUAL ETP-5E & ETP-10E ECO-TECH PLUS ELECTRIC CONVECTION STEAMER PARTS AND SERVICE MANUAL EFFECTIVE JANUARY 10, 2018 Superseding All Previous Parts Lists. The Company reserves the right to make substitution

More information

LIGHT COMMERCIAL - 3 HP ECM MOTOR / CONTROLLER HIGH STATIC DRIVE KITS

LIGHT COMMERCIAL - 3 HP ECM MOTOR / CONTROLLER HIGH STATIC DRIVE KITS LIGHT COMMERCIAL - 3 HP ECM MOTOR / CONTROLLER HIGH STATIC DRIVE KITS INSTALLATION INSTRUCTIONS For R7TQ/P7TQ/Q7TQ -090 (T) and -120 (T) Series Single Package Rooftop Units IMPORTANT ATTENTION INSTALLERS:

More information

Q3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS

Q3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS TECHNICAL SPECIFICATIONS Q3RD Series Single Packaged Heat Pump, Single Phase Q3RD-13 SEER 2 thru 4 Ton Units Cooling: 24,000 to 48,000 Btuh Heating: 23,200 to 48,000 Btuh The Q3 Series single packaged

More information

P3RC-12 SEER 2 Ton thru 4 Ton Units Cooling: 23,800 to 48,000 Btuh

P3RC-12 SEER 2 Ton thru 4 Ton Units Cooling: 23,800 to 48,000 Btuh TECHNICAL SPECIFICATIONS P3R(A,C) Series Single Packaged Air Conditioner, Single Phase P3RA-10 SEER 2 thru 5 Ton Units Cooling: 24,000 to 59,000 Btuh P3RC-12 SEER 2 Ton thru 4 Ton Units Cooling: 23,800

More information

30A SMART ENERGY MANAGEMENT SYSTEM TM

30A SMART ENERGY MANAGEMENT SYSTEM TM 30 Amp EMS Display Panel P/N 00-00903-030 (Black) 30 Amp EMS Distribution Panel P/N 00-0091-000 CAUTION The 30A SMART EMS is a centralized power switching, fusing, and distribution center. Power from the

More information

SUNLINE 2000 SINGLE PACKAGE AIR - TO - AIR HEAT PUMPS DESCRIPTION. B1CH 180 & and 20 NOMINAL TONS ( EER)

SUNLINE 2000 SINGLE PACKAGE AIR - TO - AIR HEAT PUMPS DESCRIPTION. B1CH 180 & and 20 NOMINAL TONS ( EER) 511.06-TG3Y (0600) SINGLE PACKAGE AIR - TO - AIR HEAT PUMPS B1CH 1 & 40 15 and 0 NOMINAL TONS (8.5-8.8 EER) SUNLINE 000 DESCRIPTION York Sunline 000 Heat Pumps are convertible single package units. All

More information

Electric Furnace KF/KFS Series

Electric Furnace KF/KFS Series Electric Furnace KF/KFS Series KF/KFS 20 20 1 A B C D A: Series B: 20-208V 24-240V 48-480V C: Kilowatts D: 1 or 3-phase Heavy duty open-coil element Direct drive motor Up to 3-speed motor Standard 24 Volt

More information

IMPORTANT ATTENTION INSTALLERS:

IMPORTANT ATTENTION INSTALLERS: Power Exhaust Kit for P7TQ, Q7TQ & R7TQ Series INSTALLATION INSTRUCTIONS IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

BCE3 PRODUCT SPECIFICATIONS STANDARD AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY

BCE3 PRODUCT SPECIFICATIONS STANDARD AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY PRODUCT SPECIFICATIONS STANDARD AIR HANDLER FORM NO. -100 (05/2014) APPLICATION 1 1/2-5 ton systems Upflow and horizontal (counterflow capable with kits) Sequenced for demand management External access

More information

MERIT Series R-410A - Upflow / Horizontal - Variable Speed

MERIT Series R-410A - Upflow / Horizontal - Variable Speed PRODUCT SPECIFICATIONS AIR HANDLERS CBX5UHV (-01) MERIT Series R-10A - Upflow / Horizontal - Variable Bulletin No. 10611 March 015 Supersedes November 01 MODEL NUMBER IDENTIFICATION CB X 5 UH V - 00-0

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICL GUIDE SPLIT-SYSTEM EVPORTOR LOWERS K*ES120 10 NOMINL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling coil

More information

S6BQ Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Split System 2-Stage Air Conditioner. 7 1/2 and 10 Ton rated at 11.2 EER and 12.

S6BQ Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Split System 2-Stage Air Conditioner. 7 1/2 and 10 Ton rated at 11.2 EER and 12. TECHNICAL SPECIFICATIONS S6BQ Series Split System 2-Stage Air Conditioner 7 1/2 and 10 Ton rated at 11.2 EER and 12.9 IEER The S6BQ Series of air conditioners offers exceptional performance. The unit,

More information

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS.     DESCRIPTION TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: AHE18 THRU 60* DESCRIPTION The Air Handler line offers the ultimate in comfort, sound and application

More information

Water to Water Geothermal Heat Pump 3-Phase Models Both 208 & 480

Water to Water Geothermal Heat Pump 3-Phase Models Both 208 & 480 Installer Water to Water Geothermal Heat Pump 3-Phase s Both 208 & 480 Installation Instructions : THA-***-2 (208, 3-Phase) THT-***-2 (208, 3-Phase) THA-***-3 (480, 3-Phase) THT-***-3 (480, 3-Phase) This

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4, & 5 Ton Wall Mount Heat Pumps Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H3CE150, H4CE180 AND H3CE A-0402

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H3CE150, H4CE180 AND H3CE A-0402 TECHNICAL GUIDE SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H3CE150, H4CE180 AND H3CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) DESCRIPTION These outdoor condensing units are completely assembled, piped

More information

FEATURES. a coil in horizontal position) Three speed PSC blower motor. Accessory Heater. Designed for 208/240 Volt. Single & Three phase models

FEATURES. a coil in horizontal position) Three speed PSC blower motor. Accessory Heater. Designed for 208/240 Volt. Single & Three phase models ELECTRIC FURNACE 2 THRU 5 TONS SPLIT SYSTEM EF Series FEATURES Electric Furnace, Air Conditioning or Heat Pump ready Upflow or horizontal left or right airflow as shipped. (Horizontal Drain Pan Accessory

More information

FORM NO. HSC-543 AIR HANDLERS

FORM NO. HSC-543 AIR HANDLERS FORM NO. HSC- AIR HANDLERS AH10X1 High Efficiency featuring New Industry Standard R-10A Refrigerant Features AH10X1 features the new X-1 (ECM) motor which provides enhanced SEER performance with most Sure

More information

GQ3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS

GQ3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS GQ3RD Series Single Packaged Heat Pump, Single Phase GQ3RD-13 SEER 2 thru 4 Ton Units Cooling: 24,000 to 48,000 Btuh Heating: 23,200 to 48,000 Btuh The GQ3 Series single packaged

More information

SUNLINE PLUS SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS DESCRIPTION. D1EG/D1EE 180 & and 20 NOMINAL TONS 9.5 EER

SUNLINE PLUS SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS DESCRIPTION. D1EG/D1EE 180 & and 20 NOMINAL TONS 9.5 EER SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS D1EG/D1EE 180 & 40 15 and 0 NOMINAL TONS 9.5 EER SUNLINE PLUS DESCRIPTION YORK Sunline PLUS II units are convertible single package high efficiency rooftops.

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS SUSPENSION MOUNTING ACCESSORY MODELS 1HH0403, 1HH0404 & 1HH0405 For 25, 30, 40 and 50 Ton R-410A Split-System Evaporator Units 651459-UAI-A-1010 TABLE 1: SUSPENSION

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 3 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT General The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment. Economizer Model

More information

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910) LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS IMPORTANT!

More information

TECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES DESCRIPTION WARRANTY FEATURES Rev.

TECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES DESCRIPTION WARRANTY FEATURES Rev. TECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES 40-130 MBH INPUT HIGH-EFFICIENCY INDUCED COMBUSTION EFFICIENCY RATING CERTIFIED This product was manufactured in a plant whose

More information