1 Transformer Bushings Type STARIP / STARIP -Si Mounting Operating and Maintenance Instructions Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 1 of 17

2 SAFETY INSTRUCTIONS These instructions are valid for mounting, operation and maintenance of transformer bushings type STARIP and STARIP -Si. Mounting, operation and maintenance works involve followings safety risks: - Perilous, electrical voltages - High voltage - Moving machines - Large weight - Handling of moving masses - Injuries caused by slipping, stumbling or falling Especially rules and instructions for these topics have to be obeyed when handling such equipment. Disregarding of these instructions can include severe injuries to persons, death, damages of products and materials or following industrial injury and/or consequential damages. In addition to these rules national and international safety rules have to be obeyed. In these instructions we have marked risks of injuries or persons and material with following signs near the texts and mounting steps: Personal injuries or fatal damages Industrial injury and/or consequential damages These operating and maintenance instructions are valid for the type range STARIP / STARIP -Si. This regulation is valid only for the respective execution of the bushing in connection with the respective execution specification which includes all technical data and the dimensional drawing. It is an integral part of the operation and maintenance instruction. Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 2 of 17

3 CONTENT 1 Description Design Design Head Type STARIP Design Head Type STARiP -Si Design Head Type STARIP -Si Design General Operating Conditions Mechanical Stress Montage Status of Dispatch Handling Lifting and Erection Preparation for Mounting STARIP Disassembly Draw Lead Bolt, detachable Conductor Bolt STARIP -Si Disassembly Draw Lead Bolt Mounting Draw Lead Bolt Installation Bushing on the Transformer Grounding of the Bushing Flange Putting into operation Air Release at the Bushing Flange Head Evacuation of the Transformer Recommended Checks before putting into Operation Electrical Measurements Test Tap Maintenance Recommended Maintenance and Checks STARIP -Si Cleaning of the Insulator Surface Electrical Measurements Measuring Procedures Equipment Limits Thermo-Control by Means of Thermovision Possibilities of repair Storage Disposal after end of operation Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 3 of 17

4 1 Description 1.1 Design Connecting Terminal Clamping Armature Head Porcelain Housing Silicone Composite Housing Flange with test tap transformer ventilation threaded hole for lifting eyes Fig.1 RIP-Insulting body 1.2 Design Head Type STARIP Design for draw lead bolt or detachable conductor bolt Fig Design Head Type STARiP -Si Design for draw lead bolt or detachable conductor bolt Fig Design Head Type STARIP -Si Design for undetachable conductor bolt Fig.4 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 4 of 17

5 1.5 Design A = STARIP Condenser bushing transformer/outdoor porcelain insulator draw lead design B = STARIP -Si like A, but silicone composite insulator C = STARIP -Si or STARIP design with undetachable current conductor bolt D = like C, transformer side end Main insulation of the RIP transformer bushing STARIP /-Si is an insulating body (20). It is made of a special paper impregnated with epoxy resin under vacuum and wound onto a central tube (19) made of aluminium and coaxially placed grading layers (24) made of aluminium foil to provide uniform voltage distribution. On the transformer side end the inner diameter is increased to accommodate the draw lead insulation, it is screened by an integrated shield electrode (32). This insulating body is installed in a housing, which for type STARIP (A) is a porcelain housing (16) cemented into the bushing flange (29) by Portland cement (25) and sealed by O-rings (26). The head armature is pressed on by plate springs (12). For type STARIP -Si (B) the housing is made of fibre glass re-inforced epoxy resin tube (23) with sheds made of silicone elastomere vulcanized onto it. The bushing flange and the head are glued to the housing tube in a special process and the sheds are vulcanized onto the tube. This type does not have a spring bracing, because the head armature bears itself. The gap between the insulating housing and the insulating body is filled with a dry filler (15), a flexible PU-elastomere, which provides an adhesive joint between surfaces. Therefore these types cannot be disassembled. The flange made of weather-resistant aluminium alloy (29) is equipped with test tap (27), lifting eyes (28) and grounding screws (30). The threaded bores can be used for air release screws in case of glued sealing bearer. C B D A Fig.5 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 5 of 17

6 The head of the bushing type STARIP (A) consists of a cover (11) to close the porcelain housing and plate springs (12), which transmit their compressive force to the porcelain housing via the thrust ring (10) and the bracing nut (9) screwed to the end of the central tube. Cover and thrust ring are made of aluminium alloy, the bracing nut is made of brass. In the top the bracing nut has a slit and a clamp screw (3). This fixes the draw lead bolt (2). In this area the draw lead bolt has two shafts (5), into one of which the locking screw (4,13)) locks depending upon the position of the bolt. On the front side of the bolt there is a screw M12 (1) to pull through the bolt with soldered transformer lead. On the outer side of the locking nut there is an air release screw (8) for air release of the central tube. The head of type STARIP -Si (B) has the same construction in the area of the bolt clamping. The cover (18) is glued to the composite housing, therefore no spring bracing is required and the clamping element (14) for the draw lead bolt is screwed directly to the cover. To avoid corrosion a non-corrosive steel washer (17) is placed between cover and clamping element. As in the STARIP design the central air release screw is located on the outer side. C B A In addition to the draw lead design (A and B) there is a design with solid conductor bolt, which is fixed in the bushing head in the same way as the draw lead bolt. Another design is the undetachable conductor bolt (C and D) which is impregnated directly into the core instead of the central tube. In this case no bolt clamping in the head is required. A thrust washer (6) serves as corrosion protection and also presses the upper bolt sealed tight. On the transformer side end the bolt has a fixed, undetachable O-ring sealing (31). D All sealings are made of oil-resistant Perbunan, the bolt sealings (21) are designed as double radial sealings Fig.5 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 6 of 17

7 1.6 General Operating Conditions Application: Classification: Ambient temperature: Installation height: Rain level and humidity: Bushing for installation in transformers Epoxy resin impregnated paper, capacitive grading, Outdoor-transformer bushing Outdoor side: - 30 bis + 40 C ** corresponding to temperature class 2 acc.to IEC Transformer side: daily mean value + 90 C, max. value 100 C ** < 1000 m above sea level. 1-2 mm rain/min. vertical and horizontal acc. to IEC I Pollution class : Corresponding to the specific creepage distance *** acc. to IEC Immersion medium: Oil level below bushing flange: max. oil pressure: Possibility to evacuate: Corrosion protection: Transformer oil of all common types acc. to standards max. 15 mm 200 kpa excess pressure No restrictions regarding level and time Armatures and fixing material made of corrosion-resistant materials Marking: Acc. to IEC Packing: Wooden case, ventilated, bushing protected by styro-foam cushions below the head and the flange, welded in plastic foil with inlaid dehydrating bags. ** Standard values, Deviations for special cases see corresponding bushing specification *** Standard min. 25 mm/kv for heavily polluted environment. Deviations see bushing specification 1.7 Mechanical Stress Test bending load: Standard acc. to IEC table 1, class II * Operating load: 50% of the values for test bending load * Standard values. Deviations for special cases see corresponding bushing specification Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 7 of 17

8 2 Montage 2.1 Status of Dispatch The bushing is dispatched in a ventilated wooden crate. It is supported by styro foam cushions, which are located in the porcelain area and at the bushing flange for the porcelain type and for the silicone type at the bushing head and at the flange. In case of bigger bushings the flange is supported by wooden cross beams. The whole bushing is sealed in plastic foil with desiccant bags added. (Fig.6) In this packaging the bushing can be stored in dry rooms covered by a roof for 12 months. When the bushing is packed in aluminium coated foil instead of plastic foil it can be stored for 24 months under the same conditions. Longterm storage, e.g. for spare parts, can only be made when the transformer side end of the bushing is covered by a metal protection tank with oil filling. The oil filling does not require any special maintenance measures apart from visual checks for leakages. (also see item 7.0) Fig Handling To remove the bushing from its crate the type STARIP can be lifted and put down at the flange and at the porcelain housing with plastic ropes or loops. The type STARIP -Si can be lifted and put down at the head and at the flange only, because lifting at the silicone insulator can lead to damages of the sheds, putting the bushing down at the insulator leads to a deformation of the sheds. Surface influenced by moisture The bushing must not be put down on the transformer side end. Even in case of a suitable upholstering there is the danger that in case of bumps cracks develop in the insulating material, which may be not visible, but jeopardize later operation of the bushing. When the transformer side end of the bushing is not protected, it can by handled outside for a short period of time during dry weather. Longer storage, e.g. during rain, is not permitted. The material RIP is hygroscope and absorbs moisture on the surface, which has a negative influence on the operating behavior on the transformer. Dry surface When bushings with clear traces of the influence of humidity are detected, contact the manufacturer. See comparative picture on the left hand side. (Fig.7) Fig. 7 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 8 of 17

9 2.3 Lifting and Erection Use the lifting eyes on the flange to lift the bushing. On the front side of the connecting bolt there is a screw M12. Into the thread of this screw a lifting eye can be fixed. This lifting eye serves as second lifting point. The bushing is lifted with the help of two lifting devices. This way any required inclined position can be achieved for the installation on the transformer (Fig. 8). Smaller bushings with a weight below 50 kgs can be lifted at the ring screw. The transformer side end of the bushing can be guided manually. Bigger bushings can also be lifted with only one lifting device. For this purpose the ropes or loops are led from the crane shackle to the bushing flange. Another lifting device, e.g. a pulley, is fixed in the same shackle and its ropes or loops are led to the bushing head. By pulling the pulley the lengths of both ropes or loops are adjusted in such a way that the crane shackle is located above the center of gravity of the bushing. The inclination is achieved by further pulling of the pulley. Caution: The lengths of both parts, i.e. rope and pulley have to be chosen in such a way, that the permitted diagonal pull at the eyes does not exceed the permitted angle! (60 from axis direction of the lifting eye) Fig.8 In no case the bushing must be put down with its lower insulating end for erection purposes. This may cause invisible cracks which jeopardize the operating behavior. 2.4 Preparation for Mounting After the bushing was removed from the packaging it has to be put down on bearing blocks at the flange and at the head. The plastic foil is removed do not use a knife for bushings of type STARIP -Si, because the silicone sheds may be damaged. The transformer side end of the bushing has to be thoroughly cleaned if necessary. Do not use heavily vaporizing solvents. Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 9 of 17

10 2.4.1 STARIP Disassembly Draw Lead Bolt, detachable Conductor Bolt Fig.9 At the head of the bushing type STARIP there are following parts: (Fig.12) 1 Thrust washer (Fig.5/10) 2 Air release screw central tube (Fig.5/8) 3 Locking screw (Fig.5/4,13) 4 Sealing draw lead bolt radial O-rings (Fig.5/5) 5 Clamping screw(fig.5/3) 6 Bracing nut with slit for bolt clamping (Fig.5/9) To disassemble the draw lead or conductor bolt first the clamping screw (5) and the locking screw (3) have to be loosened (Fig.9). After that the bolt is pushed into the bushing by slight beats with a mallet (Fig.10). This is necessary because the friction in the sealing of the draw lead bolt (4) has to be overcome. The draw lead bolt is pushed through the bottom end of the bushing (Fig.11) with the help of a rod (wood or similar) STARIP -Si Disassembly Draw Lead Bolt The head of the bushing type STARIP-Si consists of following parts: (Fig.14) 7 Clamping element (Fig.5/14) 8 O-ring sealing side clamping element (Fig.5/17) 9 Draw lead bolt (Fig.5/2) 10 Disc (Fig.5/17) 11 O-ring sealing side cover (Fig.5/17) 12 Cover (Fig.5/18) 13 Fixing screws for (7) First the four screws (11) for the clamping element (7) are loosened. Then the whole clamping element including draw lead bolt or conductor bolt can pulled out of the bushing (Fig.15). As clamping and sealing of the bolt have the same design as for the bushing type STARIP, after that - as described above - the locking screw (3) and the clamping screw (5) have to be loosened and the bolt has to be pushed out. Note: In case of a detachable conductor bolt this bolt has to be removed only, if it is required by the arrangement in the transformer. The connection to the transformer lead can now be made. The bore to solder the transformer lead has to be made according to the requirements, max. Ø30 and max. 70mm deep Fig.10 Fig.12 Fig.11 Fig.13 Fig.14 Fig.15 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 10 of 17

11 2.5 Mounting Draw Lead Bolt When the bushing is mounted on the transformer the draw lead bolt with soldered transformer lead is pulled upwards through the bushing with the help of a pulling wire or rod while the bushing is led down onto the transformer until the draw lead bolt comes out of the bushing head. (Example pulling wire see Fig.16). Make sure that the diameter of the pulling accessories including their fastening material does not exceed Ø30 mm to avoid a damage of the O-ring while pulling them through. Fig.16 The bold has a conical beginning. When the end of the cone with its big Ø is located flush with the clamping armature, the upper of the two shafts is at the same position as the locking screw (Fig.12/3) and this screw can be slightly fastened. After that the clamping screw is fastened (Fig.12/5) with a torque of 18 Nm. At an interval of 8 mm there is the second shaft. If for tolerance reasons the main lead has to be more tense, the second position can be chosen for the draw lead bolt. Finally the threaded bore at the front side of the bolt has to be shut with screw and sealing. 1 Fig.17 In case a solid, detachable conductor bolt has to be pulled through, we recommend to use a pulling rod (no through-going threaded rod, because the O-rings to seal the bolt may be damaged). screw torque(nm) torque(kpm) 3 Installation Bushing on the Transformer The bushing is mounted on the transformer following the handling instructions for the draw lead or detachable conductor bolt described in 2.3 in reverse sequence. When introducing to the transformer has to be paid attention that the core of the bushing not crash into the edge of the opening If available follow the instructions of the transformer manual. This also applies for sealing and fastening of the fastening screw. If no specifications are existing, the fastening screws have to be tighten for the bushing flange according to table (Fig.18) The given values are reference values and refer to bolted joints with stainless steel screws. Applicable only for flange joints with O-ring seal and metallic contact of the parts. If used with flat gaskets, adequate external brace support is required. Fig.18 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 11 of 17

12 3.1 Grounding of the Bushing Flange The bushing flange has grounding screws. The flange has to be connected to the transformer tank by grounding bands or cables. Apart from the observation of several national rules this guarantees faultless galvanic connection. It is possible to achieve grounding by a screw with tip. This screw (M12) has to be closed with a cap nut to protect it against torsion and corrosion. 4 Putting into operation 4.1 Air Release at the Bushing Flange Head Before putting the bushing into operation air has to be released from the central tube at the screw (1, Fig. 17) and air bubbles in the flange area with the screw (2, Fig.19). The screw (3, Fig.19) must not be opened, it is used to fill the bushing with dry filler Evacuation of the Transformer If the transformer has to be evacuated there are no restrictions regarding level and duration up to the operating temperature of the bushing. The material RIP is suitable for such treatment. Fig Recommended Checks before putting into Operation Visual check of all visible parts of the bushing with respect to external damages, all screws being fixed and tight acc. to instructions, cover of the test tap being tightly closed A leakage check is possible only to a limited extend on the mounted bushing, because the transformer oil reaches up to the flange, but in case of vertically installed bushing not up to the head. The double sealings at the bolt guarantee reliable sealing. Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 12 of 17

13 4.4 Electrical Measurements The bushings are certified suitable for operation by the routine tests carried out before delivery. It is useful and therefore recommended to carry out a reference measurement on site. This guarantees that is case of later control measurements the measuring conditions are the same and comparable results are achieved. For some transformers these measurements are carried out before the transformer is delivered. In this case comparative data is available already. Measurements include the bushing capacitance as main capacitance C1 and the dielectric loss factor tan delta. Measurement of the capacitance between the last grading layer C2 and the flange is possible, but it does not provide any information about the main insulation. It only shows the condition in the area of the test tap. Description of the procedure see item Test Tap The last layer of the capacitive grading is led out insulated at the bushing flange via a small auxiliary bushing Fig. 20 (2). The contact pin (1) is suitable for the connection of test plugs with a Ø of 4mm. The cover (3) has a contact socket (5) into which the contact pin locks when the cap is closed and provides a reliable grounding of the grading. The cover is protected against penetration of moisture by an O-ring sealing (4). Circuit diagram of the test tap arrangement see Fig. 21 Fig.20 The test taps are not self-grounding! Therefore during operation the cap has to be closed always! 5 Maintenance 5.1 Recommended Maintenance and Checks The bushing is free of maintenance. Check and maintenance refer specifically to the insulator and its condition and the armatures and their condition regarding corrosion. This type of check should be carried out once per year or together with transformer revision. We recommend to carry out electrical measurements of the bushing after the first 5 years of operation, after that depending upon the measurement results every 3 years or in shorter intervals. (see item 5.3.3) Fig.21 C1 main capacitane C2 flange capacitane 1 capacitive grading 2 flange 3 test tap Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 13 of 17

14 5.2 STARIP -Si Cleaning of the Insulator Surface The silicone compound insulator should not be cleaned regularly. It s good features regarding pollution are heavily influenced temporarily by cleaning, because on the surface there is a water-repellent coating which is removed by cleaning. Cleaning is performed with cloths free of fluffs and soaked with cleaning liquid. As the sheds are flexible do not apply heavy force, but rub more frequently with less force. Cleaning liquid: Wacker E10 from Wacker Chemie, lot size 25 ltr. container, consumption 1 ltr. for approx. 3 5 m 2 of surface. After cleaning the features return to their original condition after approx. 1-2 days. An approximate statement about the condition of this socalled hydrophobicity is made by the HC-classification shown on the left hand side.(fig.22) For testing purposes during wind-still, dry weather sufficiently spray an area of the size of a hand with water from a spray bottle from a distance of approx. 30 cm and compare the image of the drops with the HC-table.(Fig.22) Up to class HC 3 it can be assumed that the features are still sufficient for the operation behavior. It is only a roughly comparing procedure the result of which is no guarantee for the operation behavior. In addition the insulator should be checked for possible discharge traces. Such traces must not occur, because they damage the surface of the insulator in this area regarding its hydrophobicity. In such a case the cause for the discharges has to be investigated. Damages of the sheds or on the body, i.e. shearings, cannot be repaired on site. In case of smaller faults repair in the factory may be possible and have to be agreed upon with the manufacturer. Possible larger remainders of paint can be pulled off after they have hardened do not use solvents! Fig.22 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 14 of 17

15 5.3 Electrical Measurements Measurements on bushings require experience with measuring. equipment, test set up and the interpretation of the measurement results. This is for some part due to the relatively small capacitance values, which are corrupted by ambient influence of the environment alone. This measurement of the dielectric dissipation factor can be influenced by humidity, weather etc Measuring Procedures Mainly the measuring procedures differ by the coupling of the measuring signal. In case of so-called not grounded measurements the test voltage is applied to the conductor of the bushing and the measuring signal is taken at the test tap of the bushing. The grounded measuring procedure is applied, if the bushing which has to be measured does not have a test tap. This is not applicable for the bushings of the type range STARIP and STARIP -Si. The devices required for the measurement are usually equipped specifically for the measurement of bushings. The measurement methods are described in comprehensive manuals. Example of a mobile measuring equipment Equipment Measuring equipment is available from several manufacturers. Data can be found in the internet or enquired at HSP. (Fig.23) Fig Limits For the measurement the influence of the ambient temperature has to be taken into consideration. In the diagram shown on the left side for C and tan delta the variations through temperature are shown. (Fig. 24) For the material RIP, resin impregnated paper, there are limit values for the deviation of the capacitance and the dielectric dissipation factor with relation the new value. This value is reliably deducted from the reference measurement described under 4.4. In case the deviances are larger than mentioned in the table below, HSP has to be contacted in any case. When there are very large deviations the bushing may have to be taken out of operation. Voltage Level C Deviation < 123 kv 10 % 123 kv 5 % Guide value tan delta Fig.24 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 15 of 17

16 5.4 Thermo-Control by Means of Thermovision If as a routine thermovision controls are carried out in the installations following items have to be taken into account for the bushings: An increase of temperature by up to 40 K can as a rule be detected at the external contact point, i.e. the lead clamp and is not unusual. Higher temperatures or excess temperatures during low load should lead to a check of the contacts. Irregularities in the temperatures along the outdoor insulator length, though may be caused by hotspots and have to be investigated more closely, if necessary contact the manufacturer. (Fig.25) Fig.25 6 Possibilities of repair Repair is restricted to the parts accessible from outside, because due to the construction disassembly of the composite housing is not possible. These operating and maintenance instructions are valid for the type STARIP /STARIP -Si, therefore in case of a repair sectional drawings and parts lists for explanation are necessary. If the case occurs the documents can be ordered from HSP by quoting the serial number and the specification number and will be transmitted immediately. (Example of a sectional drawing and a parts list (Fig. 26). Above that depending upon repair requirements corresponding short instructions can be given. In case of internal failure the composite insulator has to be destroyed to allow access to the inner construction parts. We recommend to return the bushing to the manufacturer, who has suitable means and measures and professional investigation methods. Fig.26 Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 16 of 17

17 7 Storage In its original packaging the bushing can be stored in dry rooms up to 12 months. If the bushing is packed in aluminium coated foil with inlaid dehydrating bags, storage time is 24 months. Longterm storage, e.g. of spare bushings, is possible only with protection tank on the transformer side. The material RIP is hygroscope and can absorb humidity, especially in case of long periods of storage. The protection tank is made of spray-galvanized steel and is screwed with sealings to the bushing flange. The tank has a screw through which it is filled with insulating oil, 7% less than the total volume as compensation volume in case of temperature variations. This type of longterm storage has the advantage that checks are limited to visual checks for leakages.(fig.27) Protection tanks 8 Disposal after end of operation The bushing does not contain any liquids, the parts are neither toxic, self-inflamable nor physically burdening. All parts can be disposed of as industrial waste. Fig.27 Following components: - Porcelain (STARIP ), - Silicone elastomere (STARIP -Si) - Fibre-glass re-inforced epoxy resin (STARIP-Si) - Polyurethane Elastomere (dry filling) - Epoxy resin impregnated special paper with aluminium foils as layers - Central tube and armatures made of aluminium alloys - Draw lead or conductor bolt made of E-Cu - Fastening elements, test tap, screws etc. made of stainless steel, aluminium alloy or brass As the insulating body is undetachably fixed to the composite housing by the dry filler it is recommended to cut the bushing above and underneath the flange and the head several time for easy disposal. For type STARIP the porcelain housing has to be destroyed(caution: Danger of chipping!) Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 17 of 17

Transformer Bushing Type EKTG

Transformer Bushing Type EKTG Transformer Bushing Type EKTG Mounting Operating and Maintenance Instructions Operation Instructions BAL EKTG/05e Visum 01/14 T/gue Page 1 of 18 SAFETY INSTRUCTIONS These instructions are valid for mounting,

More information

HVDC Transformer Bushings Type GSETF / GSETFt

HVDC Transformer Bushings Type GSETF / GSETFt HVDC Transformer Bushings Type GSETF / GSETFt Mounting Operating and Maintenance Instructions Service Instruction BAL GSETF/GSETFt_07e Visum 08/15 T/lid page 1 of 19 SAFETY INSTRUCTIONS These instructions

More information

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide 1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide HVDC bushing without oil side porcelain Type GOF, for outdoor mounting Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

A of 14. Edition : Date : Page : Document No. Amendments :

A of 14. Edition : Date : Page : Document No. Amendments : &RQWHQWV,QVWUXFWLRQVIRU(UHFWLRQ 2SHUDWLRQ 2XWGRRU7UDQVIRUPHU%XVKLQJ 57.)N9.6,7 6HULHV&25,3 +/$%( Document No. Edition : Date : Page : Amendments : A 29.11.02 1 of 14 *(1(5$/'(6,*1 3$&.,1* %XVKLQJ6XSSO\&RQGLWLRQV

More information

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical

More information

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY

Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY PAO Condenser Bushings - kv BUSHINGS OI-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C.9.0-000 AND IEEE C.9.0-99 AN ASTOM COMPANY PAO bushings are capacitance-graded bushings with an oil-impregnated

More information

Transformer bushings, type GSA-OA Technical guide

Transformer bushings, type GSA-OA Technical guide Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to

More information

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide 1ZSE 2750-111 en, Rev. 9 Transformer bushings, type GSA-OA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

OIL TO AIR BUSHINGS SERIES PNO. VOLTAGE FROM 52 kv TO 245 kv

OIL TO AIR BUSHINGS SERIES PNO. VOLTAGE FROM 52 kv TO 245 kv Nuova Strada di Piano PPR 20099 Sesto San Giovanni (MI), Italy Tel. +39 02 24 10 50 01 www.alstom.com Page 1 of 17 OIL TO AIR BUSHINGS SERIES PNO VOLTAGE FROM 52 kv TO 245 kv INSTRUCTION FOR STORAGE, TRANSPORTATION,

More information

1ZSC ABE en, Rev. 1. HVDC bushing, type GSD Installation and maintenance guide

1ZSC ABE en, Rev. 1. HVDC bushing, type GSD Installation and maintenance guide 1ZSC000563-ABE en, Rev. 1 HVDC bushing, type GSD Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for

More information

Installation Manual Bushings, IEEE/ANSI Standard

Installation Manual Bushings, IEEE/ANSI Standard Installation Manual Bushings, IEEE/ANSI Standard Type COTA 150.2050 for Transformers Type COBA for OCB Bushing Replacement E 8322.72 2007 Contents Page 1. Introduction 3 2. Scope 3 3. Construction 3-5

More information

Karussell- und Spezialmaschinenbau. Update on wear limits Zierer Wave Swinger Ride. To whom it may concern

Karussell- und Spezialmaschinenbau. Update on wear limits Zierer Wave Swinger Ride. To whom it may concern ZIERER Karussell- und Spezialmaschinenbau GmbH Josef-Wallner-Str. 10, D -94469 Deggendorf Karussell- und Spezialmaschinenbau GmbH Ihre Nachricht vom: Ihre Zeichen: Unser Zeichen: Tel.-Durchwahl: Datum:

More information

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to

More information

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137 Transformer Bushings Type COT 5... COT 050 4 kv to 45 kv up to A IEC 37 Features If you need any transformer bushing proven in operation conditions around the world, Trench has it! experience in bushing

More information

Guide units. For toolmaking, fixture manufacturing and machine engineering

Guide units. For toolmaking, fixture manufacturing and machine engineering Guide units For toolmaking, fixture manufacturing and machine engineering Guide units in compliance with DIN, ISO and STEINEL standards or according to your specifications Guide pillars Guide and pillar

More information

Keystone Figure V11 Butterfly Valve Installation, Operation and Maintenance Manual

Keystone Figure V11 Butterfly Valve Installation, Operation and Maintenance Manual Please read these instructions carefully - indicates that it may lead to injuries or damages on the properties. Warning - indicates that it may lead human body to serious injuries. Danger - indicates that

More information

1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide

1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide 1ZSC000563-ABJ EN, REV. 1 Gas insulated wall bushings type GGFL Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Installation and Operational Instructions for EAS -Compact overload clutch, Type 49_. 4._ Sizes 4 and 5

Installation and Operational Instructions for EAS -Compact overload clutch, Type 49_. 4._ Sizes 4 and 5 Please read these Operational Instructions carefully and follow them accordingly! Ignoring these Instructions may lead to malfunctions or to clutch failure, resulting in damage to other parts. Contents:

More information

produces and delivers products worldwide can provide the optimal solution for your requirements. are dedicated to supplying you with

produces and delivers products worldwide can provide the optimal solution for your requirements. are dedicated to supplying you with www.ppcinsulators.com The very Best. The very Best. That s what we deliver. Only a company that develops, produces and delivers products worldwide can provide the optimal solution for your requirements.

More information

Manual for installation and operation HB 602/05 en. ZX2 Gas-insulated medium voltage switchgear

Manual for installation and operation HB 602/05 en. ZX2 Gas-insulated medium voltage switchgear Manual for installation and operation HB 602/05 en ZX2 Gas-insulated medium voltage switchgear Your safety first always! That s why our instruction manual begins with these recommendations: Operate the

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

KEYSTONE Figure 990/991 Butterfly valves Installation, operation and maintenance instructions

KEYSTONE Figure 990/991 Butterfly valves Installation, operation and maintenance instructions Before installation these instructions must be fully read and understood Potentially dangerous practices: disregarding instructions improper use of product use of insufficiently qualified personnel Application

More information

Butterfly Valve Type 57P

Butterfly Valve Type 57P Butterfly Valve Type 57P Contents Lever Type: 50-200 mm (2-8 ) Body Material: CPVC Gear Type: 50-200mm (2-8 ) Body Material: CPVC (1) Be sure to read the following warranty clauses of our product 1 (2)

More information

Instructions for Fitting, Operating and Maintenance

Instructions for Fitting, Operating and Maintenance EN Instructions for Fitting, Operating and Maintenance Retractable Door 1 818 024 RE / 10.2011 ENGLISH Contents 1 Safety Instructions... 3 1.1 Qualified persons... 3 1.2 Symbols and signal words used...

More information

Instructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: )

Instructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: ) EN Instructions for Fitting, Operating and Maintenance Canopy Door 1 818 012 RE / (St.: 12.2010) 12.2010 ENGLISH Contents 1 Safety Instructions... 3 1.1 Qualified persons... 3 1.2 Symbols and signal words

More information

SKiM 63/93 IGBT Modules. Content. Mounting Instruction

SKiM 63/93 IGBT Modules. Content. Mounting Instruction Mounting Instruction SKiM 63/93 IGBT Modules Revision: 1.7 Issue date: 2016-02-26 Prepared by: Anastasia Schiller Approved by: Peter Beckedahl Keyword: SKiM63/93, Mounting Instruction Content 1. Preparation,

More information

Assembly and Maintenance Instructions. Pad Thrust Bearings

Assembly and Maintenance Instructions. Pad Thrust Bearings Assembly and Maintenance Instructions for Pad Thrust Bearings 1. General Assembly Regulations The bearings are delivered as fully assembled units. Roller bearings are pre-lubricated at the factory with

More information

High Voltage and Extra High Voltage Cables

High Voltage and Extra High Voltage Cables High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high

More information

PhiCap Capacitors for Power Factor Correction

PhiCap Capacitors for Power Factor Correction PhiCap Capacitors for Power Factor Correction Product Profile 2000 http://www.epcos.com PhiCap AC Capacitors for Power Factor Correction General The PhiCap series, is a well approved and reliable EPCOS

More information

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.

More information

KEVA 24 Cxx(c) Indoor voltage sensors for NEXANS Instructions for installation, use and maintenance

KEVA 24 Cxx(c) Indoor voltage sensors for NEXANS Instructions for installation, use and maintenance Medium Voltage Products KEVA 24 Cxx(c) Indoor voltage sensors for NEXANS Instructions for installation, use and maintenance 1. Operating conditions 2 2. Technical details 2 3. Instructions for installation

More information

CABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv.

CABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv. MV-CONNEX, HV-CONNEX, IXOSIL Terminations, IXOSIL MSA Slip-on Joint Boxes CABLE SYSTEMS Accessories and Systems for Medium and High-Voltage Cables up to 300 kv. Welcome to the CABLE SYSTEMS Centre of Competence.

More information

Operating and Maintenance Instructions. Abteilung TB, Schell Seite 1 8 SERIES 56

Operating and Maintenance Instructions. Abteilung TB, Schell Seite 1 8 SERIES 56 Abteilung TB, Schell Seite 1 8 These instructions supersede all earlier instructions, in particular BWS 109-0 till BWS 109-3. For applications in areas with explosion hazard it is obligatory to observe

More information

Installation Instructions

Installation Instructions Description Instructions given in this bulletin apply to either a standard, unshielded or high-performance, shielded antenna. The antenna consists of a two-piece reflector, braced by a back structure;

More information

Inductive voltage transformers

Inductive voltage transformers Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They

More information

WATERFLUX 3070 Quick Start

WATERFLUX 3070 Quick Start WATERFLUX 3070 Quick Start Battery powered electromagnetic water meter Electronic Revision ER 4.3.0_ up to ER 4.3.4_ (SW.REV 4.2.2_ up to 4.2.5_) KROHNE CONTENTS WATERFLUX 3070 1 Safety instructions 4

More information

HL (AZH) Limit Switches

HL (AZH) Limit Switches COMPACT SIZE LIMIT SWITCHES HL (AZH) Limit Switches Compact, high-performance limit switch with superior environmental resistance. Broad lineup covers from die casting cases to economical plastic cases.

More information

BEARINGS The lower bearing assemble is constructed to allow continuous operation when fully submerged in wastewater.

BEARINGS The lower bearing assemble is constructed to allow continuous operation when fully submerged in wastewater. GENERAL SPECIFICATION INTENT The equipment to be supplied by manufacturer includes the screw pumps, support for the drive unit, profile plates, motors, gearboxes, couplings, guards, upper and lower bearing

More information

Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES

Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES REVISION 1.1 03/15/2002 LIST OF EFFECTIVE PAGES On a revised page, the portion of text or illustrations affected by the change is indicated by a vertical

More information

SERIES TAP-CHANGER

SERIES TAP-CHANGER SERIES 090 - TAP-CHANGER Main characteristics This is an off-circuit tap changer. It means DO NOT OPERATE WHILE THE TRANSFORMER IS ENERGISED. Main characteristics of this tap-changer series are: dimensional

More information

Rotary Heat Exchangers

Rotary Heat Exchangers Rotary Heat Exchangers INSTALLATION AND OPERATING INSTRUCTIONS XPXR 12/2009 Contents General Information... 2 Use... 3 Operating Conditions... 3 Design... 3 Handling and Transport... 3 Installation Site...

More information

Energy Supply Systems

Energy Supply Systems Energy Supply Systems SINGLE POLE INSULATED CONDUCTOR RAIL 815 100 amps KAT0815-0001b-E Conductor rail system in a high bay storage Slip ring with conductor rail system in a stretch-foil packing machine

More information

PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors

PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors MARCH 2017 PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors Be sure to read and completely understand this procedure before applying product. Be sure to select the proper PREFORMED

More information

17 KV 45MA Solid State Jacobs Ladder Kit Instructions

17 KV 45MA Solid State Jacobs Ladder Kit Instructions 17 KV 45MA Solid State Jacobs Ladder Kit Instructions by Physics Playground www.physicsplayground.com WARNING: Jacobs Ladders are high voltage devices that may be lethal if touched and produce very high

More information

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does

More information

TEKNISK RIKTLINJE TR05-10E

TEKNISK RIKTLINJE TR05-10E Notes Change notes Date 1 (A) Revision of standards and new template 09 / 07 2010 2 Template changed.clause. 10.5.1.4 support clamp inserted. Clause 10.5.4.2 creepage text revised. Clause 10.6.7 Dry inserted

More information

TOOLFLEX Operating-/Assembly Instructions

TOOLFLEX Operating-/Assembly Instructions D-807 Rheine heet: 5810 EN 1 of 19 Backlash-free, torsionally stiff and maintenance-free coupling is a backlash-free, torsionally stiff and maintenance-free metal bellow-type coupling designed to be used

More information

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM. QAD#IM6055.REVA

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM.  QAD#IM6055.REVA LSSN Butterfly Valve Installation Operation Maintenance Licence Number: 5326 www.challengervalves.com.au 1 Index 1. INTRODUCTION 1.1 Design Features 3 1.2 Flange and Pipe Compatibility 4 1.3 Operating

More information

AIR CORE REACTORS. Phoenix Electric Corporation

AIR CORE REACTORS. Phoenix Electric Corporation AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed

More information

Nor-Mex G. Assembly and operating instructions TSCHAN Elastic coupling BAWN 002-GBR-1 10/2008

Nor-Mex G. Assembly and operating instructions TSCHAN Elastic coupling BAWN 002-GBR-1 10/2008 BAWN 002-GBR-1 10/2008 Assembly and operating instructions TSCHAN Elastic coupling Nor-Mex G TSCHAN GmbH Zweibrücker Straße 104 D-66538 Neunkirchen-Saar Telefon: +49(0) 6821 866 0 Telefax: +49(0) 6821

More information

Installation and Operation Instructions RINGFEDER Type 2050 AM RINGFEDER Type 2050 AP

Installation and Operation Instructions RINGFEDER Type 2050 AM RINGFEDER Type 2050 AP Installation and Operation Instructions RINGFEDER Type 2050 AM RINGFEDER Type 2050 AP 22.10.2003 10069125 Type 2050 AM General RINGFEDER Type 2050 AM, part no.: 14994532 RINGFEDER Type 2050 AP, part no.:

More information

Installation manual portable distributors

Installation manual portable distributors EN Installation manual portable distributors EN 60003206 Issue 11.2016 15/11/2016 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal words used 4 2 Intended

More information

Repair Manual 11/99 PS-34. Page 1

Repair Manual 11/99 PS-34. Page 1 Repair Manual /99 PS-4 Page Table of contents Index Technical Data page Special tools 4 Repair instructions, general 0 Chain brake 6 0 Centrifugal clutch 8 0 Oil pump 9-04 Ignition system - 0 Starting

More information

ROBATIC ROBA -quick ROBA -takt. Reliable coupling and braking.

ROBATIC ROBA -quick ROBA -takt. Reliable coupling and braking. Reliable coupling and braking Equipment Technology Packaging Machinery Conveyors and Materials Handling Equipment Door drives Indexing tables ROBATIC ROBA -quick ROBA -takt www.mayr.de Electromagnetic

More information

PRECISION BELLOWS COUPLINGS

PRECISION BELLOWS COUPLINGS PRECISION BELLOWS COUPLINGS Bellows couplings are used where precise rotation, high speeds, and dynamic motion must be transmitted. They exhibit zero backlash and a high level of torsional stiffness, offering

More information

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA

More information

TECHNICAL INFORMATION. Dipl.-Ing. (FH) Christian Niklis. Stationary Lance Earthing Device

TECHNICAL INFORMATION. Dipl.-Ing. (FH) Christian Niklis. Stationary Lance Earthing Device TECHNICAL INFORMATION Dipl.-Ing. (FH) Christian Niklis Stationary Lance Earthing Device GENERAL Lance earthing devices - What s s the use of them? Short-circuit-proof earthing in high voltage substations

More information

Gear Pumps - AP05. Reference: 200-P EN-05 1/26. Issue:

Gear Pumps - AP05. Reference: 200-P EN-05 1/26. Issue: Gear Pumps - Reference: 200-P-991218-EN-05 Issue: 09.2015 1/26 Contents Page 1 General information... 3 1.1 Introduction to the product... 3 1.2 Non-standard symbols used in the text... 4 2 Technical information...

More information

1.8L & 2.2L 4-CYL Article Text 1998 Subaru Impreza

1.8L & 2.2L 4-CYL Article Text 1998 Subaru Impreza 1.8L & 2.2L 4-CYL Article Text 1998 Subaru Impreza ARTICLE BEGINNING 1995-98 ENGINES Subaru - 1.8L & 2.2L 4-Cylinder 1995-97: Impreza (1.8L) 1995-98: Impreza (2.2L), Legacy (2.2L) * PLEASE READ THIS FIRST

More information

Hand Pallet Truck NC. Operation Manual

Hand Pallet Truck NC. Operation Manual Hand Pallet Truck -------NC Operation Manual Operation Manual 1 Application Range This product is suitable for using in rated load of up to 5500lbs. This PL5500HD is the perfect jack for handling palletized

More information

CAST RESIN TRANSFORMERS

CAST RESIN TRANSFORMERS MODEL TAM CAST RESIN - TAM TYPE Epoxy cast resin dry-type transformers are recommended to operate in places that require security, the materials used in its construction are hard to combust and are self-extinguishable

More information

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1

More information

SIT-LOCK self locking elements

SIT-LOCK self locking elements self locking elements Advantages of on the shaft-hub connection compared with traditional systems Easy assembly and disassembly Both actions take place by locking and unlocking the clamping screws with

More information

A Issue F. Instruction Manual. EMF3, EMF10 and EMF20 EMF20 Oil Mist Filter

A Issue F. Instruction Manual. EMF3, EMF10 and EMF20 EMF20 Oil Mist Filter Instruction Manual A462-26-880 Issue F EMF3, EMF10 and EMF20 Oil Mist Filters Description EMF3 Oil Mist Filter EMF10 Oil Mist Filter EMF20 Oil Mist Filter Item Number A462-20-000 A462-26-000 A462-29-000

More information

SERIES A & AA ROLLER DOORS INSTALLATION GUIDE

SERIES A & AA ROLLER DOORS INSTALLATION GUIDE SERIES A & AA ROLLER DOORS INSTALLATION GUIDE THESE INSTRUCTIONS ARE PROVIDED FOR USE BY EXPERIENCED INSTALLERS OF GARAGE DOORS BY UNDER-TAKING THE INSTALLATION OF THIS DOOR, THE INSTALLER UNDERSTANDS

More information

Manual for installation and operation HB 601/03 en. ZX1.2 Gas-insulated medium voltage switchgear

Manual for installation and operation HB 601/03 en. ZX1.2 Gas-insulated medium voltage switchgear Manual for installation and operation HB 601/03 en ZX1.2 Gas-insulated medium voltage switchgear Your safety first - always! That s why our instruction manual begins with these recommendations: Operate

More information

Standard Parts for Mould Making

Standard Parts for Mould Making Standard Parts for Mould Making Index Your Production Partner 4-5 Guide Elements Locating units, round 8 Locating units, flat 8 Compensation Discs 9 Adjusting washers 9 Ejector rods 10 Centering sleeves

More information

Transformer components. De-energized tap changer, type DTW Technical information guide

Transformer components. De-energized tap changer, type DTW Technical information guide Transformer components De-energized tap changer, type DTW Technical information guide Scope This guide contains general information for ordering and installing the type DTW de-energized tap changer. This

More information

Technical Description Edition 2007 Mounting, maintenance and repair of propshafts with flanged universal joints

Technical Description Edition 2007 Mounting, maintenance and repair of propshafts with flanged universal joints Technical Description Edition 2007 Mounting, maintenance and repair of propshafts with flanged universal joints 1. Recommendations Assembly, disassembly, maintenance and repair of propshafts should be

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual

Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual Table of Contents Definition of Terms 1 Introduction 1 Installation 1 Maintenance 2 Stem Seal Replacement 4 Seat Replacement

More information

PRECAUTIONS FOR HANDLING VALVE REGULATED (SEALED) LEAD-ACID BATTERIES INDEX

PRECAUTIONS FOR HANDLING VALVE REGULATED (SEALED) LEAD-ACID BATTERIES INDEX PRES FOR HANDLING VALVE REGULATED (SEALED) LEAD-ACID BATTERIES Precautions for handling Valve Regulated (Sealed) Lead-Acid Batteries This document should be read in its entirety and its contents fully

More information

E a s y B - S e r i e s M o d u l e s M o u n t i n g I n s t r u c t i o n s f o r E a s y P I M a n d E a s y P A C K M o d u l e s

E a s y B - S e r i e s M o d u l e s M o u n t i n g I n s t r u c t i o n s f o r E a s y P I M a n d E a s y P A C K M o d u l e s E a s y B - S e r i e s M o d u l e s M o u n t i n g I n s t r u c t i o n s f o r E a s y P I M a n d E a s y P A C K M o d u l e s IFAG IPC Edition 2011-02-02 Published by Technologies AG 59568 Warstein,

More information

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other

More information

Installation, Operation, and Maintenance Manual Full Port Y-Pattern, Bolted Bonnet, Globe and Check Valves

Installation, Operation, and Maintenance Manual Full Port Y-Pattern, Bolted Bonnet, Globe and Check Valves SMITH VALVES Installation, Operation, and Maintenance Manual Full Port Y-Pattern, Bolted Bonnet, Globe and Check Valves Globe Valve Series: YG80/YG15 Welded Bonnet Globe Valve Series: YG87/YG17 Piston

More information

Installation and Operational Instructions for ROBA-stop Holding Brake Type _._

Installation and Operational Instructions for ROBA-stop Holding Brake Type _._ Please read these Installation Instructions carefully and follow them accordingly! Ignoring these Instructions may lead to malfunctions or to brake failure, resulting in damage to other parts. Contents:

More information

BUSBAR SOLUTIONS TECHNOLOGY FOR ELECTRICAL ENERGY

BUSBAR SOLUTIONS TECHNOLOGY FOR ELECTRICAL ENERGY BUSBAR SOLUTIONS TECHNOLOGY FOR ELECTRICAL ENERGY A Phoenix Mecano Partner Company CONTENTS: General information about the solid cast resin insulated bus bars 3 Field of application 3 Range of Electrical

More information

ISP-500B. Oil-free Scroll Vacuum Pump. Instruction Manual. View our inventory. Record of Pump Information. Serial Number: Purchase date:

ISP-500B. Oil-free Scroll Vacuum Pump. Instruction Manual. View our inventory. Record of Pump Information. Serial Number: Purchase date: ISP-500B Oil-free Scroll Vacuum Pump Instruction Manual View our inventory Serial Number: Record of Pump Information Purchase date: In Service date: Dealer information: IM-500B 1/3/07 Page 1 of 26 Important

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Spring hangers, spring supports

Spring hangers, spring supports Spring hangers, spring supports 2 spring Spring hangers, supports PRODUCT 2 GROUP Spring hangers, spring supports Contents Page Field of application...2.1 Overview of spring hangers and spring supports...2.3

More information

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 13 Engine-Crankshaft, Cylinder block (Page GR-13)

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 13 Engine-Crankshaft, Cylinder block (Page GR-13) 13 Engine-Crankshaft, Cylinder block (Page GR-13) Engine, disassembly and assembly 10-222 A/21 guide from 10-222 A support tool, modifying Ribbed belt, removing and installing Semi-automatic toothed belt

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

BRUSHLESS EXCITERS FOR TURBINE GENERATORS

BRUSHLESS EXCITERS FOR TURBINE GENERATORS BRUSHLESS EXCITERS FOR TURBINE GENERATORS Economical, Manpower Saving Exciters Based on State-of-the-Art Technology. Mitsubishi Electrical manufactures brushless exciters for all types of turbine generator,

More information

2-20 (50mm-500mm) SERIES 30/31 Wafer/Lug RESILIENT SEATED BUTTERFLY VALVES. The High Performance Company

2-20 (50mm-500mm) SERIES 30/31 Wafer/Lug RESILIENT SEATED BUTTERFLY VALVES. The High Performance Company BUTTERFLY VALVES RESILIENT SEATED SERIES 30/31 Wafer/Lug 2-20 (50mm-500mm) The High Performance Company SERIES 30/31 2-20 (50mm-500mm) Bray Controls is proud to offer a high quality line of butterfly valves

More information

Belt Conveyor Pull Rope Switch Types HEN, HEK and SEM OPERATING INSTRUCTIONS

Belt Conveyor Pull Rope Switch Types HEN, HEK and SEM OPERATING INSTRUCTIONS Belt Conveyor Pull Rope Switch Types HEN, HEK and SEM OPERATING INSTRUCTIONS 2 CE-Sign and Conformity The device meets the requirements of the valid European and national regulations. Conformity has been

More information

NARVIK-YARWAY. High Pressure Level Gauges, Model: 17

NARVIK-YARWAY. High Pressure Level Gauges, Model: 17 NARVIK-YARWAY Narvik-Yarway covers requirements for level gauges and electronic water level systems with a wide range of models, sizes and materials to satisfy all the specifications of the power and process

More information

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield sa B-CABLES nv ENERGY

sa B-CABLES nv PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield sa B-CABLES nv ENERGY PROTOLON(ST) NTSCGEWOEU.../3E Medium Voltage Flexible Cables for Use in Water with Copper Core Shield ENERGY Technical Data Electrical Thermal Type Type designation PROTOLON (ST) NTSCGECEWÖU.../3E Approvals/

More information

CAUTION CONTENTS 5.0 WARRANTY

CAUTION CONTENTS 5.0 WARRANTY 5.0 WARRANTY ELECTROMATIC Equipment Co., Inc. (ELECTROMATIC) warrants to the original purchaser that this product is of merchantable quality and confirms in kind and quality with the descriptions and specifications

More information

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability 3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability Power Transmission and Distribution 1 A perfect Combination of Cost-Savings, Safety and Reliability 3EQ Surge Arresters:

More information

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

Z1 Free Ride (110) GENERAL

Z1 Free Ride (110) GENERAL GENERAL (110) 175 80 Ø 30 +0.05 0 L.MAX=493 L.L.=483 ±2 L.MIN=373 426 ±2 57 CORSA 110 TRAVEL 110 18 Ø 30 15 20 0-0.1 +1 0 248.5 Special ride and Downhill fork whose legs are damped by a spiral springs

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

Electromagnetic clutch-brake combinations INTORQ

Electromagnetic clutch-brake combinations INTORQ Electromagnetic clutch-brake combinations INTORQ 14.800 14.867 7.5 120 Nm setting the standard 2 CBC en 5/2005 Contents Clutch-brake combinations Product information 4 Type code 6 Design selection 8 Overview

More information