INSTALLATION/OPERATING INSTRUCTIONS MCP

Size: px
Start display at page:

Download "INSTALLATION/OPERATING INSTRUCTIONS MCP"

Transcription

1 INSTALLATION/OPERATING INSTRUCTIONS MCP Modulating Digital Set Point Control with Boiler Output and External Activation Temperature Range -30 to 250 F (-35 to 120 C) Pressure Ranges 0-30, 0-100, 0-200PSI Digital display reads sensor value constantly Black Red White Output wires Output light indicates status relay Push this button to display the Set Point, Differential, or Offset settings. Offset is only available on MCP-Pressure SYS =System SP =Set Point dif =Differential GAn =Gain PUr =Purge OFS =Offset R HEAT TIMER CORP SENSOR T-STAT OUTPUT 24VAC UP PRESS TO READ DOWN Blue wires to power with 120VAC Blue Blue Yellow wires to activate heating or cooling source Yellow Yellow Push these buttons to adjust the settings To use 24VAC power connect to these two terminals Wire sensor provided with the unit to these terminals Observe polarity when using Pressure Sensor - + Connect to T-STAT terminals to Enable the System. If not used, DO NOT remove Jumper To use 24VAC connect to these two terminals observing the polarity WARNING This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control. LIMITED ONE YEAR WARRANTY This Heat-Timer device was thoroughly tested for defects and workmanship before leaving our factory. We do warrant the equipment to be free of defects under normal use for a period of one year from the date of installation. Transportation charges for factory repairs must be prepaid. Damage to the Heat-Timer device or any of its components due to misuse, abuse, improper installation, or caused by power failures, fire, flood, or lightning are not covered by this warranty. The company assumes no liability for indirect or consequential damages of any nature. This Heat-Timer warranty applies only to the original purchaser/user, is not assignable or transferable, and does not cover damage to the device occurring in shipment. Any service, repairs, modifications or alterations to the unit not expressly authorized by the company will invalidate the warranty. This warranty is in lieu of all other warranties expressed or implied. 1

2 INSTALLATION Mounting the Controller The MCP is designed to mount on a 1900 (4 x4 ) electrical box. If the MCP is to be panel mounted, or if additional room is needed for wiring, an extension skirt is available. Locate the MCP in a convenient location near the unit to be controlled. Mount the MCP away from excessive heat or cold. Ambient operating temperature is from 20 to 120 F. After completing all the wiring connections (see below) use the two screws provided to mount the MCP to the 1900 box. Installing the Temperature Sensor (Included with MCP-Temperature) The temperature sensor wires can be extended up to 500' by splicing with 18 gauge shielded wire. Do not run wires in conduit with line voltage. If measuring liquid temperature, the sensor should be inserted into a 3/8" ID well (HT# or equivalent). The MCP will operate based on the temperature it reads at the sensor location. Therefore, select a sensor location which is representative of the entire system. The wires can also be connected to the rear of the MCP using the Rear Wire connector*. Connect the sensor wires to the orange and yellow Rear Wires. Polarity is not important. Either wire from the sensor can be connected to either MCP sensor input. Installing a Pressure Sensor (Included with MCP-Pressure) Attach a 1/4 brass isolation tube (pigtail) to the steam header. Screw the pressure sensor to the pigtail. The sensor has 1/4 NPT tapered threads. The BLACK and RED pressure sensor wires can be extended up to 500 by splicing with 18 gauge shielded wire. Any other pressure sensor wires (green, white, or shield) and the tube are not used and do not need to be extended. Do not run wires in conduit with line voltage. The MCP will operate based on the pressure sensor reading. Therefore, select a sensor location which is representative of the entire system. The pressure sensor BLACK wire should be connected to the terminal marked SENSOR (-). The RED wire from the pressure sensor should be connected to the terminal marked SENSOR (+). The transducer wires can also be connected to the back of the MCP using the Rear Wire connector*. Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire. Connecting the T-STAT terminals The thermostat input can be used to enable or disable the system by connecting it either to a thermostat or external control. The thermostat input should be dry contact only. Polarity is not important. Either wire from the thermostat can be connected to either MCP T-STAT terminal. If no thermostat or control is connected to the T-STAT terminals, leave the jumper supplied as a contact between the T- STAT terminals. No outputs will be active unless the T-STAT terminals are closed. Connect to T-STAT terminals to Enable the System. If not used, DO NOT remove Jumper WARNING T-STAT contacts must be closed (shorted) for the control to be active. - + SENSOR T-STAT 24VAC Black Red Wire to 0-30, 0-100, or PSI pressure transducer observing the polarity. Temperature Sensor does not The Optional Mounting Kit includes the extension skirt, the Rear Wire connector, and an input terminal cover. Order separately as HT #

3 Wiring the Power - MCP can use either 120VAC or 24VAC 120VAC Attach line voltage to the two blue wires extending from the back of the MCP. Use wire nuts, or wrap the connections with electrical tape. Class 1 voltages must enter the enclosure through a different opening from any Class 2 wiring. 24VAC Use a dedicated transformer with at least a 5VA output. Bring 24VAC to the two screws on the front of the MCP marked 24VAC. 24VAC can also be connected to the rear of the MCP using the Rear Wire connector*. Connect the 24VAC to the violet and gray Rear Wires. WARNING The MCP can accept only one source of power: 120VAC, or 24VAC. If more than one power source is applied, the unit may be damaged. Wiring the Valve/Boiler Output The MCP output is suitable for 135Ω actuators (see diagram). The Red MCP wire is Common and should be connected to the R terminal of the actuator. Connect the Black (Close) and White (Open) MCP wires to the B and W terminals of the actuator consecutively. Wiring the Heating Source Output The MCP has a set of N.O. contacts to activate a heating source (Yellow wires from back). The N.O. contacts DO NOT source power. They are simply a dry contact. The MCP can switch 10A, 1/8 HP at 120V. If more power is required, an external relay must be used. Connect the 2 Yellow wires to the boiler TYPICAL WIRING DIAGRAM Sensor White (Open) Red (Common) Black (Close) Yellow Yellow 135 Ohm Motorized Valve Boiler 24VAC or wire 120VAC to rear transformer (blue wires) T-STAT Dry Contact Only 3 MCP Manual

4 Startup Settings Whenever the MCP is powered up, it will display the software version number and then the current operating mode. Each display will remain on the screen approximately 5 seconds. If the mode is correct, there is no need to make any adjustments. Once the mode has been set for a particular application, it will be retained in memory and will not need to be reset. Note that if you do change an operating mode, you will need to reset all the settings. An operating mode can only be changed when it is being displayed in the start-up sequence. To restart the sequence it is necessary to remove power to the MCP and then power it again. Set the operating modes as described in sequence below: Temperature Operation F Fahrenheit or C Celsius (Temperature Models Only) If the display shows F then the Digi-Span will operate in Fahrenheit degrees. If the display shows C then the Digi-Span will operate in Celsius degrees. To change the mode, hold down the center button while pushing either the UP or DOWN button to toggle between the displays of F and C. When the correct temperature mode is selected, release the buttons and wait approximately 5 seconds. Pressure Range P03 (0-30), P10 (0-100), or P20 (0-200) (Pressure Models Only) If the display show P03 then the range will be from 0 to 30 psi and be displayed in 0.5psi increments. If the display shows P10 or P20, the range will be 0 to 100psi or 0 to 200psi and display in 1psi increments. To change the range, hold down the center button while pushing either the UP or DOWN button to toggle between pressure ranges. When the range is selected, release the buttons and wait approximately 5 seconds.operation Operating Mode nor or blr When the MCP is set to nor for valve operation in which the control will modulate the actuator of the motorized valve based on how far the system temperature/pressure SYS is from the Set Point SP settings. When the MCP is set to blr for boiler operation in which the control will modulate the burner based on how far the system temperature/pressure SYS is from the Set Point SP settings. Also, it allows you adjust the Boiler Purge Time PUr and the Differential around the Set Point SP setting to prevent short cycling. Failed Output Mode FOn (Output ON) or FOF (Output OFF) The MCP allows you to choose how outputs should behave when sensor fails. By selecting FOn (Output ON) the 135Ω output and the heating source output will be active when sensor fails. Using FOF (Output OFF) the 135Ω output and the heating source output will be inactive when sensor fails. STARTUP SETTINGS Software Version Temp standard F (Fahrenheit) C (Celsius) Operating mode nor (Valve) blr (Boiler) Pressure standard P03 (30PSI) P10 (100PSI) P20 (200PSI) 4 Output Fail mode FOn (Enable) FOF (Disable) 4

5 Operation Settings The following are the settings in which can be read or changed while the control is in operation. By pressing the Press to Read button multiple times the MCP will rotate its display between the available settings. After a setting symbol is displayed, tits value will diplay after 3 seconds. A setting can be adjusted during the display of its value by pressing the Up and Down buttons. The diplay will revert to display System temperature/pressure SYS after approximately 10 seconds. When system temperature/perssure SYS is above the Set Point SP, the display will show OFF. You can read the System temperature/ pressure by pressing the Press to Read button till SYS is displayed. Push Press to Read button Set Point SP Differential dif Gain gan Purge PUr Offset OFS System SYS Display The Set Point is the temperature or pressure which the MCP will modulate its output to hold. The temperature Set Point is adjustable between 0 F to 200 F. Default is 70 F. Pressure Set Point is depends on the startup setting. P03 (0-30 PSI) with a default of 10PSI, P10 (0-100 PSI) with a default of 30PSI, P20 (0-200 PSI) with a default of 60PSI. The Differential is the number of degrees or psi above and below the Set Point where MCP will make small or no changes to the actuator. Only available in Boiler Mode blr. The Temperature Differential is adjustable between 1 F to 40 F. Default is 2 F. Pressure Differential depends on the startup setting. P03 (0.5-5 PSI) with a default of 2PSI, P10 (1-20 PSI) with a default of 7PSI, P20 (1-20 PSI) with a default of 7PSI. The Gain controls how aggressively the MCP will change the level of output to the actuator when the system is away from the Set Point ± the Differential. The Gain is adjustable between -10 to +10. Default is 0. The Purge should be set to the boiler manufacturer recommendation. It is adjustable between 0.0 to 9.9 minutes with a default of 2.0 minutes. Available in Boiler Mode blr only. The Offset calibrates the pressure sensor reading by the number of pounds selected. Pressure Differential depends on the startup setting. For P03 ( PSI) with a default of 0PSI, P10 ( PSI) with a default of 0PSI, P20 ( PSI) with a default of 0PSI. System temperature or pressure. Will read OFF when above Set Point. Will read OPn or SHt when sensor fails. Value is Read only and can not be changed. Only available when Boiler Mode blr is selected during startup. Only available in MCP Pressure control. Output Light The output light will flash whenever the MCP is adjusting the valve position. The time between flashes can vary from 5 seconds to 30 seconds or even longer if the set point is satisfied. The MCP makes small changes to the actuator position, and then evaluates the effect of that change on the system. The output light will be ON during the Purge cycle. 5 MCP Manual

6 Troubleshooting No Display Check the power to the MCP. The MCP can run on any of the power sources described on page 2. Turn the power off and back on. OPn Display The MCP does not see a sensor connected. Check the wires are continuous from the sensor to the MCP controller. Then follow the procedure for Incorrect Temperature or Pressure Display. SHt Display The MCP sees a short across the input terminals. If you remove the sensor wires from the MCP terminals, the display should change to read OPn. If the display does not change to OPn, the MCP may be damaged. Incorrect Temperature Display Remove the wires from the SENSOR screws. The display should change to read OPn. If it doesn t, the MCP may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the chart on the opposite page. If the ohm reading is significantly different, the sensor may be damaged. Incorrect Pressure Display Remove the wires from the SENSOR screws. The display should change to read OPn. If it doesn t, the MCP may be damaged. Use a voltmeter to measure across the SENSOR screws. There should be at least 24VAC across the two terminals. If there isn t, the MCP may be damaged. Finally, reconnect the sensor with a ma meter in series with one sensor wire. The ma reading should correspond to the Pressure Sensor Chart on the opposite page. You can use the Offset (see pg. 5) to make small adjustments to the pressure reading. Output Red Light does not stay on The red light will flash only when the MCP is adjusting the actuator. The red light should be on constantly only during purge cycle PUr. MCP does not move the motor Check the Set Point SP and Differential dif settings. If the Sensor reading SYS is within the Differential band, the MCP may not adjust the motor position. If this is not the case, the MCP output can be tested with an ohm meter. Remove any wires connected to the MCP Red, White, and Black output wires. If the System reading SYS has been below the Set Point SP for at least 10 minutes, then an ohm reading from the Red to Black wires should be less then 25Ω; the reading from Red to White should be more than 135Ω. If the system temperature has been above the set point for at least 10 minutes, then an ohm reading from the Red to Black wires should be more than 135Ω; the reading from Red to White should be less than 25Ω. MCP does not control system to hold the set point temperature The set point is the average value the system will hold. If the system temperature/pressure is overshooting and undershooting the Set Point SP by a small amount, increase the Differential value dif. If the system temperature/pressure significantly overshoots and undershoots the Set Point SP, decrease the Gain gan setting by one or two. If the system temperature/ pressure is almost always below the Set Point SP, increase the Gain gan setting by one or two. Wait approximately 15 minutes to see how the system responds. 6

7 Temperature Sensor Chart TEMPERATURE (in Degrees F) Value (in Ohms) Pressure Sensor Chart Pressure Input (in ma) 0-30 PSI Range PSI Range PSI Range MCP Manual

8 Heat-Timer Controls for the HVAC/R & Plumbing Industry Steam heating controls Hydronic heating controls Sequencing controls Radiant heat controls Digital set point controls Precision tempering valves VARIVALVE air vents 2, 3, and 4 way motorized valves Snow melt controls C O R P O R A T I O N R 20 New Dutch Lane, Fairfield, NJ Fax P/N Rev. C

INSTALLATION/OPERATING INSTRUCTIONS TSC

INSTALLATION/OPERATING INSTRUCTIONS TSC INSTALLATION/OPERATING INSTRUCTIONS TSC Two-Stage Set Point Control with External Activation Two-Stage Heating (Rotation Included) Two-Stage Cooling (Rotation Included) Change-Over Control (Heat/Cool)

More information

INSTALLATION/OPERATING INSTRUCTIONS VSP. A Variable Speed Pump Control

INSTALLATION/OPERATING INSTRUCTIONS VSP. A Variable Speed Pump Control INSTALLATION/OPERATING INSTRUCTIONS VSP A Variable Speed Pump Control The VSP is a hydronic heating control. The temperature of the heating water is controlled by regulating the speed of a pump which injects

More information

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE SRC STEAM RESET CONTROL An Outdoor Reset Control for Sub-Atmosphere Steam Systems Heat-Timer s theory of steam reset heating is as follows: Pulse the valve open to a limited valve position, very slowly

More information

Motorized Tempering Valves with Transformers for

Motorized Tempering Valves with Transformers for Motorized Tempering Valves with Transformers for Bronze and Stainless-Steel Valves Installation and Operation Manual M800 WARNING This Heat-Timer Motorized Tempering Valve is strictly an operating valve.

More information

Motorized Stainless 2-Way Valves

Motorized Stainless 2-Way Valves Installation and Operation Manual Motorized Stainless 2-Way Valves Safety Valve ETV Applications WARNING This Heat-Timer valve is strictly an operating valve; it should never be used as a primary limit

More information

2-Way Motorized Valves

2-Way Motorized Valves Installation and Operation Manual 2-Way Motorized Valves with Feedback for Vacuum and Subatmospheric Steam Heating Systems Warning All Heat-Timer controls and valves are strictly operating controls and

More information

ESV. Electronic Steam Valve Control Modulates One or Two Actuators. Installation and Operation Manual ESV. Control Module

ESV. Electronic Steam Valve Control Modulates One or Two Actuators. Installation and Operation Manual ESV. Control Module Installation and Operation Manual Electronic Steam Valve Control Modulates One or Two Actuators ESV ACTUATOR SIGNAL 8psi 9psi BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 48 VA ESV Control Module Warning

More information

TC62D Installation Instructions

TC62D Installation Instructions TC62D Installation Instructions January 2007 This TC62D has a return water low temperature limit option. Using the low limit precludes using a room sensor because both sensors plug into the same port.

More information

DCC-3000 Climate Control for Vintage Air GEN-IV systems

DCC-3000 Climate Control for Vintage Air GEN-IV systems INSTALLATION AND OPERATOR S MANUAL FOR DCC-3000 Climate Control for Vintage Air GEN-IV systems PARTS INCLUDED WITH THIS SYSTEM Vent sensor housings: 2 1 / 2 housings (x2) 2 housings (x2) Installation/operator

More information

INSTALLATION AND OPERATION INSTRUCTIONS. Variable Speed Pump Control

INSTALLATION AND OPERATION INSTRUCTIONS. Variable Speed Pump Control INSTALLATION AND OPERATION INSTRUCTIONS VSP DIGI-El i t e Variable Speed Pump Control Injection Pump Control for Hydronic Heating in Outdoor Reset or Set Point Applications DECREASE Boiler SYSTEM = 147F

More information

ODYR-25-1 & SLX-25-1 rev. A VACUUM/BOOST PRESSURE, TEMP, and EGT GAUGE

ODYR-25-1 & SLX-25-1 rev. A VACUUM/BOOST PRESSURE, TEMP, and EGT GAUGE ODYR-25-1 & SLX-25-1 rev. A VACUUM/BOOST PRESSURE, TEMP, and EGT GAUGE SENSOR CONNECTION: The vac./boost sensor has 1/8 NPT on the end which can be treaded into the intake track, or into a pipe adapter

More information

Manual Installation & Operation

Manual Installation & Operation Manual Installation & Operation Model: NCxxLxx 12A or 30A Solid State Solar Charging Regulator and 12A Load Controller. 231 Patent #: 5,642,030 Applies Page 1 Warnings When Installing, connect grounds,

More information

Solar Differential Temperature Controller Model DTC-D

Solar Differential Temperature Controller Model DTC-D OVERVIEW The DTC-D is specifically designed for solar heating applications where the collector circulation pump is powered from a solar (PV) panel, or optionally, battery power or any 12VDC source. Its

More information

DCC-2500 Digital Climate Control for Vintage Air GEN-IV systems

DCC-2500 Digital Climate Control for Vintage Air GEN-IV systems INSTALLATION AND OPERATOR S MANUAL FOR DCC-2500 Digital Climate Control for Vintage Air GEN-IV systems PARTS INCLUDED WITH THIS SYSTEM Vent sensor housings: 2 1 / 2 housings (x2) 2 housings (x2) Installation/operator

More information

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls P-269-89-0408 Installation Installation & Operating Instructions Contents Introduction........................... 2 Specifications.........................

More information

GARNET. SEE Tester II TM INSTRUMENTS LTD. Model 900M Manual PRINTED IN CANADA

GARNET. SEE Tester II TM INSTRUMENTS LTD. Model 900M Manual PRINTED IN CANADA GARNET INSTRUMENTS LTD. SEE EELEVE EVEL II Tester II TM Model 900M Manual PRINTED IN CANADA GARNET INSTRUMENTS LTD. L II TM SEE EELEVE EVEL II Tester Model 900M Manual TABLE OF CONTENTS 1) OVERVIEW and

More information

INSTALLATION/OPERATING INSTRUCTIONS TEMPERING VALVE HOT C GASKET STANDARD PIPE TAP MIXED HOT COLD HOT INLET INLET 3/4" 1" 1 1/4" 3/4" 1 1/4"

INSTALLATION/OPERATING INSTRUCTIONS TEMPERING VALVE HOT C GASKET STANDARD PIPE TAP MIXED HOT COLD HOT INLET INLET 3/4 1 1 1/4 3/4 1 1/4 INSTALLATION/OPERATING INSTRUCTIONS NIPPLE A MIXED OUTLET INSERT "O" RING MIXER VALVE BODY COLD OUTLET B SPRING COLD INLET C O L D FAIRFIELD, N.J. R H O T INLET GUIDE PISTON C GASKET BONNET ADJUSTING SCREW

More information

Modulating Furnace Information. Warning on Meter Setting - Read First!

Modulating Furnace Information. Warning on Meter Setting - Read First! Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56

More information

EasyStart. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual

EasyStart. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual EasyStart 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter Installation Manual Micro-Air Corporation www.microair.net 124 Route 526 Phone (609) 259-2636 Allentown NJ 08501 Fax (609) 259-6601 Retrofit

More information

Installation Instructions for the Lingenfelter TBRC-001 Temperature Based Relay Controller

Installation Instructions for the Lingenfelter TBRC-001 Temperature Based Relay Controller Installation Instructions for the Lingenfelter PN: L460220000 Lingenfelter Performance Engineering 1557 Winchester Road Decatur, IN 46733 (260) 724-2552 (260) 724-8761 fax www.lingenfelter.com Revision

More information

ODY-19-1 AIR PRESSURE GAUGE

ODY-19-1 AIR PRESSURE GAUGE ODY-19-1 AIR PRESSURE GAUGE Introduction: The Odyssey gauge series from Dakota Digital, Inc. incorporates the reliability and quality of our standard gauges, along with several unique features and easy

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

Exterior Digital Load Scale 201-EDG-01(B) Installation and Operation Manual Please read carefully before installation

Exterior Digital Load Scale 201-EDG-01(B) Installation and Operation Manual Please read carefully before installation Exterior Digital Load Scale 201-EDG-01(B) Installation and Operation Manual Please read carefully before installation 2 Exterior Digital Load Scale 201-EDG-01(B) Table of Contents Specifications & Overview

More information

Models DTT-84, DTT-94

Models DTT-84, DTT-94 Models DTT-84, DTT-94 Symbol of Reliability DTT Solar Controls Installation Instructions, Operational Tests and Troubleshooting Guide Power Wiring This controller works with 120 VAC power. See the controller

More information

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation GRUNDFOS INSTRUCTIONS Grundfos Variable Speed Installation and Operation Pumps Incorporating the (VS) Variable Speed Control with Date Code 0838 or higher 1. 2. 3. 4. Shipment Inspection General Features

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

SETRA Operating Instructions Series DPT 230 Pressure Transducers

SETRA Operating Instructions Series DPT 230 Pressure Transducers SETRA Operating Instructions Series DPT 230 Pressure Transducers GENERAL INFORMATION Your Setra Pressure Transducer has been carefully tested and calibrated before shipment. Specific performance information

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

ICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide

ICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide ICM325HN Head Pressure Control with Optional Heat Pump Override Temperature sensitive control regulates head pressure Installation, Operation & Application Guide For more information on our complete range

More information

CBC-300 & CBC Series Dual Channel Adjust Clutch/Brake Controls

CBC-300 & CBC Series Dual Channel Adjust Clutch/Brake Controls CBC-300 & CBC-300- Series Dual Channel Adjust Clutch/Brake Controls P-205-WE 89-0549 Installation & Operating Instructions An Altra Industrial Motion Company Contents Introduction... 2 Specifications...

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

6. Electrical. 7. Settings. 8. Quick

6. Electrical. 7. Settings. 8. Quick Grundfos Variable Speed Circulator Pump Pumps Incorporating the VS, Variable Speed Control 1. Shipment Inspection Page 2 2. General Page 2 3. Operational Limits Page 3 4. Pump Installation Page 4 5. Installation

More information

Operation and Installation Manual

Operation and Installation Manual BOMBA PRESURIZADORA AUTOMÁTICA CONTROLADOR SOLAR AQUA SOLAR SERIE MINI SMART GL-235 MINI25-10/1115-110V Electronic Solar Control Operation and Installation Manual GL-235 Description The GL-235 is a differential

More information

SOLAR AQUA. Operation and Installation Manual LDLINE AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP. Electronic Solar Control Center. for models CONTROLS INC.

SOLAR AQUA. Operation and Installation Manual LDLINE AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP. Electronic Solar Control Center. for models CONTROLS INC. AQUA SOLAR TM Electronic Solar Control Center Operation and Installation Manual for models AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP G LDLINE CONTROLS INC. www.goldlinecontrols.com 888-921-7665 IMPORTANT SAFETY

More information

- Data Brochure D 156. Difference Setpoint Control 156. Item 06/10

- Data Brochure D 156. Difference Setpoint Control 156. Item 06/10 - Data Brochure Difference Setpoint Control 156 D 156 06/10 The Difference Setpoint Control 156 is designed to operate an on/off pump to transfer heat from a heat source to a storage tank. The control

More information

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION EMP-5 Installation Manual - P/N 80103 - Ed. 01/09 EMP-5 Current or Voltage Input Drive Modulating Actuator Installation Instructions 1 7 SPECIFICATIONS The EMP-5 series actuators provide damper control

More information

Series 2100 Operating Instructions

Series 2100 Operating Instructions Series 2100 Operating Instructions Installation Instructions Visit the link below or scan the QR code to watch a detailed installation video: http://triteqlock.com/fresh After the lock, temperature probe,

More information

Easy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual

Easy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual Easy Start 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter Installation Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526. www.microair.net Allentown NJ 08501 Fax (609) 259-6601 Retrofit

More information

Wiring Installation Instructions for : Pressure. Wiring Installation Instructions for : Temperature. 2 1/16 Spek Pro Professional Racing Gauge

Wiring Installation Instructions for : Pressure. Wiring Installation Instructions for : Temperature. 2 1/16 Spek Pro Professional Racing Gauge Wiring Installation Instructions for : Pressure DIAGRAM 1 Pressure Sensor 1/8 NPT 3 AMP Wiring Installation Instructions for : Temperature GAUGE 12-Pin Wiring Harness & Plug Firewall Grommet DIAGRAM 2

More information

Inlet Controller SB3500 USER'S MANUAL

Inlet Controller SB3500 USER'S MANUAL Inlet Controller USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice

More information

Tracer VMA with AutoReg

Tracer VMA with AutoReg Tracer with AutoReg Flowmeter with Automatic Flow Regulation Operating Instructions RoHS Compliant General The Tracer Flowmeter with AutoReg provides: Analog Flow Output (Selectable 0 to 3.5V, 0 to 5V

More information

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction A186-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED Introduction The MAXIGARD A1500

More information

UTV-1000 Multi Gauge for Yamaha Rhino

UTV-1000 Multi Gauge for Yamaha Rhino IMPORTANT NOTE! This gauge has an hour meter and odometer preset option available only for the first 1.0 engine hour and 10 miles (16km). See ODO/HR PRESET for instructions. UTV-1000 Multi Gauge for 2004-2006

More information

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0330 Rev 0 0416 TABLE OF CONTENTS SAFETY SUMMARY... 3 SPECIFICATIONS... 4 1.0 INTRODUCTION/DESCRIPTION.... 5 2.0 LOCATION AND MOUNTING... 5 3.0 CONNECTIONS

More information

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated DC-4 SEQUENCE OVERFIRE DRAFT CONTROL SYSTEM OPERATING AND MAINTENANCE MANUAL THE POWER TO MANAGE ENERGY 2001 South 21 st Street, Parsons, Kansas 67357 Telephone 620-421-0480, Fax

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Generator Start Control Module

Generator Start Control Module Generator Start Control Module Part# GSCM Rev C. Code Version: 5.13 ATKINSON ELECTRONICS, INC. 14 West Vine Street Murray, Utah 84107 Table of Contents Operations... 3 Specifications... 3 GSCM Wiring Diagram...

More information

This document describes:

This document describes: Thank you for purchasing this product from ERM. We appreciate your interest in our unique product line as we try to offer our customers an alternative to today s traditional products. This programmable

More information

ODY-05-2 VOLTMETER FOR REMOTE MONITORING

ODY-05-2 VOLTMETER FOR REMOTE MONITORING ODY-05-2 VOLTMETER FOR REMOTE MONITORING Introduction: The Odyssey gauge series from Dakota Digital, Inc. incorporates the reliability and quality of our standard gauges, along with several unique features

More information

HLY-1111 HEAD TEMPERATURE GAUGE

HLY-1111 HEAD TEMPERATURE GAUGE HLY-1111 HEAD TEMPERATURE GAUGE Introduction: The Odyssey gauge series from Dakota Digital, Inc. incorporates the reliability and quality of our standard gauges, along with several unique features and

More information

CM3000 SIGNAL TRANSMITTER. Introduction. The MAXIGARD CM3000 is designed to convert shaft speed into a 4/20 ma or 0-10 VDC analog output signal.

CM3000 SIGNAL TRANSMITTER. Introduction. The MAXIGARD CM3000 is designed to convert shaft speed into a 4/20 ma or 0-10 VDC analog output signal. CM228-03, Page 1 952-935-4201, INC. (Fax) 952-935-9628 3947 MEADOWBROOK ROAD, MINNEAPOLIS, MN 55426 800-328-0738 CM3000 SIGNAL TRANSMITTER Introduction The MAXIGARD CM3000 is designed to convert shaft

More information

BCP-8S BCP-8X 35F 13PSI AND BCP-8S <AB> DE GH JK HI LO -- OFF. Part Number /0408 STEAM SEQUENCING CONTROL SYS AUX OUT

BCP-8S BCP-8X 35F 13PSI AND BCP-8S <AB> DE GH JK HI LO -- OFF. Part Number /0408 STEAM SEQUENCING CONTROL SYS AUX OUT BCP-8S AND BCP-8X BCP-8S STEAM SEQUENCING CONTROL Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H C SYS AUX OUT COMB. AIR US 13PSI 35F DE GH JK HI LO -- OFF STAGE MENU OUTPUT RATING:

More information

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additional options include pushbutton override, fan

More information

UTV-1200 Multi Gauge for 2008 Yamaha Rhino

UTV-1200 Multi Gauge for 2008 Yamaha Rhino IMPORTANT NOTE! This gauge has an hour meter and odometer preset option available only for the first 1.0 engine hour and 10 miles (16km). See ODO/HR PRESET for instructions. UTV-1200 Multi Gauge for 2008

More information

ODYR-19-5 & SLX-19-5 DUAL, TRIPLE, or QUAD AIR PRESSURE GAUGE

ODYR-19-5 & SLX-19-5 DUAL, TRIPLE, or QUAD AIR PRESSURE GAUGE ODYR-19-5 & SLX-19-5 DUAL, TRIPLE, or QUAD AIR PRESSURE GAUGE Features: All bag pressure readings displayed at once on a 2-line display. Optional storage tank pressure readout. A warning feature that flashes

More information

Model Combustible Gas Sample Draw Detector Head Operator s Manual

Model Combustible Gas Sample Draw Detector Head Operator s Manual Model 1017-07 Combustible Gas Sample Draw Detector Head Operator s Manual Part Number: 71-0480 Revision: P1 Released: 1/4/19 www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

MAXIGARD A2000 SPEED SWITCH. Introduction

MAXIGARD A2000 SPEED SWITCH. Introduction A107-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 MAXIGARD A2000 SPEED SWITCH Introduction The Maxigard A2000 Speed Switch is designed to monitor

More information

COMMANDO REMOTE CONTROL ENGINE STARTER. Limited Warranty Statement MADE IN THE U.S.A. IMPORTANT KEEP YOUR INVOICE WITH THIS WARRANTY STATEMENT!

COMMANDO REMOTE CONTROL ENGINE STARTER. Limited Warranty Statement MADE IN THE U.S.A. IMPORTANT KEEP YOUR INVOICE WITH THIS WARRANTY STATEMENT! Limited Warranty Statement GNU COMMANDO LINE WARRANTY STATEMENT GNU warrants this product to be free from defects in material and workmanship for a period of one (1) year from the date of sale to the original

More information

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION $5.00 Installation, Operation, and Maintenance Manual CEMLINE CORPORATION CEM-TROL Solid State Control Module and Electronic Control Valves P. O. Box 55, Cheswick, PA, 15024 Phone: (724) 274-5430 FAX (724)

More information

Two Channel Remote Shutdown Device

Two Channel Remote Shutdown Device Installation & Operation Standard Features: Two Channel Remote Shutdown Device I. Introduction Latched shutdown for increased safety Powerful transmitter with 300 feet range Waterproof sealed transmitter

More information

PHOTO VOLTAIC CHARGE MODULE MULTI POINT TRACKING

PHOTO VOLTAIC CHARGE MODULE MULTI POINT TRACKING FEATURES Multi Point Tracking (MPT)/ Pulse Width Modulation (PWM) is a six stage solar charge controller. Drop-in PWM replacement for the PVCM-25D two stage solar charge controller. Works with the PVDM4-LC,

More information

ICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide

ICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide ICM 326HN/327HN Line Voltage Head Pressure Control With built-in transformer Optional heat pump override ICM326HN ICM327HN Installation, Operation & Application Guide For more information on our complete

More information

This document describes:

This document describes: Thank you for purchasing this product from ERM Products. We appreciate your interest in our unique product line as we try to offer our customers an alternative to today s traditional products. This universal

More information

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series) Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant

More information

C3000 SIGNAL TRANSMITTER. Introduction

C3000 SIGNAL TRANSMITTER. Introduction C131-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 C3000 SIGNAL TRANSMITTER Introduction The MAXIGARD C3000 series is designed to convert shaft

More information

Water Valve Shutoff. WVS Water Valve Shutoff

Water Valve Shutoff. WVS Water Valve Shutoff Water Valve Shutoff Monitors flooding from leaking or broken water line Automatic control of main water supply line Form C Relay output for external monitoring devices Visual and audible status indicators

More information

RP-4000 Reserve Power Control

RP-4000 Reserve Power Control Instruction Manual IM-0580 RP-4000 Reserve Power Control Table of Contents General Information... 2-3 Introduction... 2 Cautions... 2 Receiving/Inspection... 2 Storage... 2 Equipment Return... 2 Identification

More information

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures A419 Issue Date February 10, 2003 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures The A419 series controls are single-stage, electronic temperature

More information

ODY-04-1 or ODY-04-2 rev. B WATER TEMPERATURE GAUGE

ODY-04-1 or ODY-04-2 rev. B WATER TEMPERATURE GAUGE ODY-04-1 or ODY-04-2 rev. B WATER TEMPERATURE GAUGE Introduction: The Odyssey gauge series from Dakota Digital, Inc. incorporates the reliability and quality of our standard gauges, along with several

More information

Model Combustible Gas Sample Draw Detector Head Operator s Manual

Model Combustible Gas Sample Draw Detector Head Operator s Manual Model 1017-06 Combustible Gas Sample Draw Detector Head Operator s Manual Part Number: 71-0356 Revision: P1 Released: 2/4/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

Owner s Guide CARS & CA4B5

Owner s Guide CARS & CA4B5 PROFESSIONAL SERIES Owner s Guide For Model: CARS & CA4B5 Deluxe Vehicle Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described in this

More information

Installation and Operation Manual

Installation and Operation Manual Wireless Technology Enabled Exterior Digital Load Scale 201-EBT-02(B) Installation and Operation Manual Please read carefully before installation The Bluetooth word mark and logos are registered trademarks

More information

A/C PRESSURE MONITOR INSTALLATION INSTRUCTIONS SYSTEM OPERATION GREEN INDICATOR LIGHT

A/C PRESSURE MONITOR INSTALLATION INSTRUCTIONS SYSTEM OPERATION GREEN INDICATOR LIGHT A/C PRESSURE MONITOR INSTALLATION INSTRUCTIONS Do not attempt to clean or inspect anything while the engine is running. Cleaning and inspection must be done by a certified mechanic. All A/C service must

More information

SCHNITZ MOTORSPORTS PNC-202, 2-STAGE PROGRESSIVE NITROUS CONTROLLER USER MANUAL AND INSTALLATION GUIDE NOS PULSE FREQUENCY

SCHNITZ MOTORSPORTS PNC-202, 2-STAGE PROGRESSIVE NITROUS CONTROLLER USER MANUAL AND INSTALLATION GUIDE NOS PULSE FREQUENCY SCHNITZ MOTORSPORTS PNC-202, 2-STAGE PROGRESSIVE NITROUS CONTROLLER USER MANUAL AND INSTALLATION GUIDE NOS #2, FUEL SOLENOID(GROUND) 1GA PURPLE, PAGE 14 NOS #2 NITROUS SOLENOID(GROUND) 1GA PURPLE, PAGE

More information

Digital Mobile Charge Advanced Electronic In-Transit 4-Stage Battery to Battery Charger

Digital Mobile Charge Advanced Electronic In-Transit 4-Stage Battery to Battery Charger Digital Mobile Charge Advanced Electronic In-Transit 4-Stage Battery to Battery Charger Owner s Manual and Installation Guide Model Part Number Description Digital Mobile Charge 05502 Advanced In-Transit

More information

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL Model No. DFC-X Support 877-351-4702 DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This manual covers the following products: DFC-X TS-01 DFTD RDU DAT-12 PWM-10V

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Features: Enhanced throttle response, excellent acceleration, strong brakes and throttle linearity. Using LED program card to make adjustments.

Features: Enhanced throttle response, excellent acceleration, strong brakes and throttle linearity. Using LED program card to make adjustments. Thank you for purchasing the ZTW Brushless Electronic Speed Controller (ESC). The ZTW 1:10 Scale BEAST Series ESC is specifically designed for operating 4 Pole Sensorless brushless motors. This is a high

More information

GL-235 Solar Pool Controller

GL-235 Solar Pool Controller GL-235 Solar Pool Controller Installation & Operation Manual G LDLINE CON TROLS www.goldlinecontrols.com Description The GL-235 is a differential temperature control for solar heating of pools, spas, and

More information

CA 5054 Owner s Guide

CA 5054 Owner s Guide PROFESSIONAL SERIES CA 5054 Owner s Guide Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described in this manual is applicable to most vehicles.

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

MCL-3000 SERIES AIR PRESSURE PART# MCL-3K-A

MCL-3000 SERIES AIR PRESSURE PART# MCL-3K-A MCL-3000 SERIES AIR PRESSURE PART# MCL-3K-A Thank you for purchasing the Dakota Digital MCL-3K-A gauge for your Harley Davidson Touring bike. This gauge is designed to be a direct, plug in replacement

More information

Generator Start Control Module

Generator Start Control Module Generator Start Control Module Part# GSCM-mini-i ATKINSON ELECTRONICS, INC. 14 West Vine Street Murray, Utah 84107 Contact cbdsales@atkinsonel.com for the proper hookup diagram. Please include the generator

More information

ValveMate 7000 Controller Operating Manual

ValveMate 7000 Controller Operating Manual A NORDSON COMPANY ValveMate 7000 Controller Operating Manual Steady Test Clear Time Set Fast Slow POWER RUN SETUP CYCLE A NORDSON COMPANY VALVEMATE 7000 Run Setup Purge Program Fast Slow Time Set Pressure

More information

Owner s Guide. ca5354

Owner s Guide. ca5354 PROFESSIONAL SERIES Owner s Guide for models: ca5354 Deluxe Vehicle Remote Start System with 900Mhz 2 Way Confirming LED Remote Control IMPORTANT NOTE: The operation of the Security and Convenience System

More information

SCHNITZ MOTORSPORTS USER MANUAL AND INSTALLATION GUIDE PRO-MOD BATTERY VOLTS DIAGNOSTICS NOS PULSE FREQUENCY NOS DELAY TIME IN SECONDS

SCHNITZ MOTORSPORTS USER MANUAL AND INSTALLATION GUIDE PRO-MOD BATTERY VOLTS DIAGNOSTICS NOS PULSE FREQUENCY NOS DELAY TIME IN SECONDS SCHNITZ MOTORSPORTS DSC-CS "PRO-MOD" IGNITION CONTROLLER USER MANUAL AND INSTALLATION GUIDE COIL, (OPTIONAL) GA YELLOW, COIL, NEGATIVE GA WHITE, GA BLACK, SHIFT LIGHT +V OUTPUT PAGE 0 NOS ACTIVATION INPUT

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR 24 Volt AC input Built in 15 second low fire start timer 0-24 Volt DC modulating output Remote temperature selection Calibration trim pot Rated for -40 F (-40 C) DFC-1 STANDARD TEMPERATURE CONTROL DFC-2

More information

NEXUS. Introduction SENSOR MODULE &

NEXUS. Introduction SENSOR MODULE & 2650-1056 INSTALLA AT TION INSTRUCTIONS NEXUS SENSOR MODULE & REMOTE ASSEMBLY IMPORTANT WEAR SAFETY GLASSES 60 80 40 100 FUEL 20 PSI 0 AUTO METER PRODUCTS INC. c 2004-6463 0 10 20 10 20 BOOST VAC In.Hg

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual 25500181 Rev. A0 415 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification Systems

More information

CMD-4000 SERIES REV. A 4+ FUNCTION REMOTE CONTROL DOOR LATCH OPENER SYSTEM INTRODUCTION

CMD-4000 SERIES REV. A 4+ FUNCTION REMOTE CONTROL DOOR LATCH OPENER SYSTEM INTRODUCTION CMD-4000 SERIES REV. A 4+ FUNCTION REMOTE CONTROL DOOR LATCH OPENER SYSTEM INTRODUCTION Thank you for purchasing the CMD-4000 series Remote Control Door Latch Opener System from Dakota Digital, Inc. This,

More information

ECLIPSE Laundry Dispenser Controller

ECLIPSE Laundry Dispenser Controller ECLIPSE Laundry Dispenser Controller Reference Manual Programming and Operation Online and downloadable Product Manuals and Quick Start Guides are available at www.hydrosystemsco.com Please check online

More information

Auto-Trol Limited 1660 SW 196th Avenue * Aloha, OR 97003

Auto-Trol Limited 1660 SW 196th Avenue * Aloha, OR 97003 Auto-Trol Limited 1660 SW 196th Avenue * Aloha, OR 97003 Model AT-1000 Installation Instructions The model AT-1000 Auto-Trol Battery Charger Control extends battery life reduces maintenance power by replacing

More information

Subject Underhood G System Error Codes and Symptoms System or Parts affected

Subject Underhood G System Error Codes and Symptoms System or Parts affected System or Parts affected Index Underhood70G (V90Gxxx) System or Parts affected... 1 Overview... 1 Identifying your System... 1 Retrieving Logged Error Messages... 1 Error Messages... 3 Error Message Table...

More information

Part Number Analog EGT Gauge

Part Number Analog EGT Gauge Part Number 30-5131 Analog EGT Gauge Figure 1. Wiring Schematic AEM EGT Gauge Parts 1 x 35-5131(B/W) EGT Gauge Assembly 1 x 30-2065 EGT Sensor Thermocouple w/mount 1 x 35-4302 Install Kit (6 Butt Connectors)

More information

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL AUTOMATIC FILTERS, INC. 67 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 30 839 88 800 336 94 FAX 30 839 6878 www.tekleen.com info@tekleen.com Tekleen GB6 & GB7 USERS MANUAL GB6 & GB7 USERS MANUAL AUTOMATIC

More information

Owner s Guide CA 5055

Owner s Guide CA 5055 PROFESSIONAL SERIES Owner s Guide For Model: CA 5055 Vehicle Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described in this manual is applicable

More information