1 PURCHASE ENQUIRY Inquiry No : MDG/PUR/PKS/ENQ/Panels, Dated: Jan 30, 2015 Description Qty Specifications : Purchase Inquiry for Supply, installation and commissioning of Panels for PFP Expansion project. : As per Annexure -I. : As per Annexure-II Due Date : 10 th Feb, 2015 Dear Sir, You are requested to give your most competitive rates for supply & installation and commissioning of Electrical Panels at Packaging Film Plant at Gandhinagar with all the accessories required, as per the annexure attached herewith: The offer should reach, Mother Dairy (A Unit Of Gujarat Co - Operative Milk Marketing Federation Limited.) Plot No. - 35, Near Indira Bridge, Ahmedabad - Gandhinagar Highway, Village: Bhat, Dist.: Gandhinagar. Pin No The offer should be sent in sealed cover super scribing on the top left hand corner offer for inquiry No. MDG/PUR/PKS/ENQ/panels dtd. 30/01/2015. Offer received after due date for whatsoever reason may be rejected. Your offer should be sent through Post/Courier/mail & not by Fax or personally. Offer should be valid for acceptance, for 45 days from due date of submission of offer. The price should be quoted on F.O.R basis inclusive of packing and forwarding, taxes, excise duties, freight etc. However if it is separate, it should be clearly mentioned in the quotation as per the attached annexure. It should cover a warranty of at least one-year against manufacturing defect from commissioning of the plant. Realistic earliest delivery period should be indicated. It is not binding on us to accept lowest offer. Right to reject any or all the offers without assigning any reason is reserved by us. Offer which are incomplete or not meeting the conditions or only for part items, are liable for rejections. No queries regarding the status of the offer will be entertained at any time. The final supplier will be the combined decision of our technical team and management and no reason of final selection will be conveyed to any bidder. Payment terms with 30 days credit shall be preferred. We are an ISO certified unit. We follow Eco- friendly processes in our factory & also expect same to be followed in your company. GA drawing detailed fabrication drawing and Design calculation is to be submitted along with the offer. Approval from PFP-Mother dairy, Gandhinagar is to be taken before starting the Work. Site Address: Mother Dairy Packaging Film Plant, K road, GIDC, Opp. Madhur Dairy, Gandhinagar- Dist: Gandhinagar Contact detail: Mr. Palak Shah, Mail: palak.shah@amul.coop, Mob:
2 Annexure-I Sr. No. Description UOM Qty 1 Bus Bar Panel 800 A No MCC 400 A for Cooling Tower + Silo No MCC 1250 A for CAP making m/c No Slitter Distribution Panel No Cooling Tower Starter Panel No. 03 Note: The Incomer MCCB feeder shall have metering facility with LCD display. Supervision on installation, testing & commissioning should be included in quoted price.
3 Annexure-II Technical Specifications Of Supply of MCC and Busbar Termination Panel For PFP Expansion Project
4 1. Introduction INDEX 2. Design Basis 3. Technical Specifications 4. Schedule of Requirement 5. Drawings.
5 1. Introduction MOTHER DAIRY Supplier requested to study all details and requirement related to project and quote for all the material/equipment listed under Schedule of requirement SITE ADDRESS: Packaging Film Plant, (A unit of Mother Dairy) Sector 25, GIDC, Opp: Madhur Dairy, Gandhinagar Phone: Fax: Contact Person: Mr. Urmil Sorathiya (Manager) Mobile No: Design Basis The design basis for proposed electrical system shall be as follows; Bus Bar Panel: Two Nos. of Copper Bus bar panels are also in the scope of supply, which shall be installed near Blown Film 7 & 8 Plant, in which the incoming Aluminum Cables are connected at one end and on other side of Bus Bar suitable rating flexible Copper cables are connected. The same shall be finally connected to the BFP-7 & BFP-8 panel incomer. A detailed scope of Supply along with required rating is enclosed with the enquiry. Suppliers are requested to quote for the same. Detailed Technical specification is given in the Technical Specification: section. All Aluminum Bus bars shall be designed based on current density of 0.8 A/mm 2 And Copper Bus bars shall be designed based on current density of 1.2 A/mm 2
6 3. TECHNICAL SPECIFICATION 1. Bus Bar Panel BFP Plant Bus Bar Panel BFP Plant Silo + CT MCC 4. Cap Making M/C MCC 5. Slitter Distribution Panel 6. Starter Panel Bus bar type: Copper Bus Bar Size of the Bus Bar: Mention in respected Annexure. Size of the Panel: Refer attached drawing Cooling: by 230 V Panel Cooling Fan.
7 The Panel shall be designed with Following Features; Sr. No. Location Cable Entry Rating GA Drawing Annexure Bus Bar Termination Panel 1 with 800 A MCCB 4P EF Bus Bar Termination Panel 2 with 800 A MCCB 4P EF Silo+ CT MCC Panel with 400 A MCCB 4P EF Cap Making MCC panel with 1250 A ACB 4P EF BF Plant 7 BF Plant 8 Silo + CT Cap Making Machine Slitter SR 8 Distribution Panel with 125 A MCCB 4P EF Starter Panel Starter Panel 03 Nos. Incomer Cable: 3.5C, 400 Sq. mm., Al, XLPE, Armoured cable 02 Nos. Outgoing Cable: 4C, 240 Sq. mm., Cu, XLPE, Flexible 02 Nos. MCCB: 800 A 01 No. Incomer Cable: 3.5C, 400 Sq. mm., Al, XLPE, Armoured cable 02 Nos. Outgoing Cable: 4C, 240 Sq. mm., Cu, XLPE, Flexible 02 Nos. MCCB: 800 A 01 No. Incomer Cable: 3.5C, 240 Sq. mm., Al, XLPE, Armoured cable 01 Nos. MCCB: 400 A 01 No. Incomer Cable: 3.5C, 400 Sq. mm., Al, XLPE, Armoured cable 02 Nos. Outgoing Cable: 4C, 240 Sq. mm., Cu, XLPE, Flexible 01 Nos. ACB: 1250 A 01 No. Incomer Cable: 3.5C, 95 Sq. mm., Al, XLPE, Armoured cable 01 Nos. MCCB:125 A 01 No. Incomer Cable: 4C, 16 Sq. mm., Cu, XLPE, Armoured cable 01 Nos. 800 A Annexure A Annexure A Annexure A Annexure A Annexure A Annexure 5
8 1. Bus Bar Termination Panel Duty: To connect the incoming Aluminum Armored cable at one end of bus bar and copper flexible cable at other end for the following machine; (These panels shall be installed near the machines) DESIGN DETAILS 1.0 SYSTEM PARAMETERS 1.1 Ambient temperature.1 Maximum ambient air temperature Deg. C 45.2 Reference ambient temperature for Design 1.2 Rated voltage Deg. C 50.1 Rated operational voltage V 415V AC (+/- 10%), 3 Phase 4 wire System.2 Highest system voltage V 457 V AC 1.4 Rated frequency Hz 50 Hz (+/-3%) 1.5 Earthing Solidly Earthed 2.0 CONSTRUCTION: 2.1 Type of switchboard Incomer MCCB: Fixed type Other MCCB: Fixed type, Single Front, Compartmentalized 2.2 Overall Dimension (W X H X D) Mm As per Drawing Annexure Constructional features.1 Structure 2 mm CRCA.2 Mounting Plate 2 mm CRCA.3 Door 2 mm CRCA.4 Partitions / Covers 1.6 mm CRCA.5 Gland Plate 3 mm
9 2.4 Installation MOTHER DAIRY.1 Mounting on Floor (Free standing), Indoor.2 Additional channel frame for foundation Base frame of 75 mm height..3 Lifting Arrangement Lifting hook provided (4 Nos.).4 Front access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.5 Rear access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley 2.5 Degree of Protection IP Paint.1 Material Epoxy Powder Coated min. 250 micron.2 Inside shade Siemens Grey.3 Outside shade Siemens Grey.4 Mounting Plate Orange.5 Base Frame Black 6. Surface Preparation 7 tank Process 2.7 Name plates Aluminum Anodized with letters engraved 3.0 TERMINATION & WIRING/BUSBAR ARRANGEMENTS: 3.1 BUSBAR FEEDER CONNECTIONS.1 System 3Phase, 4 Wire System.2 Rated Current Amp 800A.3 Qty. X Cross section (HBB) mm 2 1 X 80 X 10 For Phase 1 X 80 X 10 For Neutral Note: Bidder to confirm the above size with calculation considering 1.2 A / sq.mm.4 Bus bar clearances Mm To be designed as per relevant IS code.5 Insulation (except at joints & tap-offs) Heat shrink PVC sleeves Red for R Phase, Yellow For Y Phase, Blue for B Phase, Black For Neutral.6 Insulation at joints & tap-offs Air.7 Color coding Strip of Colored heat shrinks PVC sleeves as a Marking at any 2 Feet Interval.
10 4.2 Earth Bus bar MOTHER DAIRY.1 Material / Grade Electrolytic grade Aluminum(E91E Grade) as per relevant IS.2 Qty. X Cross section (in mm) 1 X 50 X 6 mm 4.3 Incomer.1 Power cable entry from Bottom 4.4 Out-going.1 Power cable out from Bottom.2 Control cable entry from Bottom 4.5 Glands.1 Supply at site.2 Drilling of gland plate at site (Removable Gland Plate) 4.6 Wiring.1 Type of wire Single Core Cu. Flexible wire.2 Insulation 1100 V PVC.3 Power wiring size 2*3.5 C*400 Sq. mm. Al Armoured.4 Control Wiring size 1.5 Sq.mm.5 C.T Wiring 2.5 Sq.mm.6 Colour coding for identification Colour sleeves at termination.7 Power Termination Crimped Tinned Copper Lugs Provided.8 Control Termination Crimped End Insulated Tinned Copper Lugs Provided 4.7 Control terminal.1 Size of terminal Suitable to 2.5 Sq.mm wire size PANEL COOLING SYSTEM 1 no. of 4 Rexnord make Cooling Fan NOTES: 1. Earthing of doors will be through 2.5-mm2 yellow-green wires. 2. All the indication lamp shall be LED type.
11 2. Cooling Tower + Silo Distribution Panel The distribution panel shall be designed with Following Feeders; Sr. No./ TAG Description Type Rating GA Drawing Annexure 01 IC-1 Incomer MCCB with MP based OC & SC protection released (Four Pole) 400 A Annexure 2 02 Supply to Silo MCCB with MP based OC & SC 100 A protection released (Four Pole) 03 Supply to CT - 3 MCCB with MP based OC & SC 100A protection released (Four Pole) 04 Supply to CT 4 MCCB with MP based OC & SC 100 A protection released (Four Pole) 05 Supply to CT 5 MCCB with MP based OC & SC 100 A protection released (Four Pole) 06 Supply to CT 6 MCCB with MP based OC & SC 100 A protection released (Four Pole) 07 Supply to Exhaust Fan SFU 63 A
12 The Distribution Panel shall be designed with the following specifications; DESIGN DETAILS 1.0 SYSTEM PARAMETERS 1.1 Ambient temperature.1 Maximum ambient air temperature Deg. C 45.2 Reference ambient temperature for Design 1.2 Rated voltage Deg. C 50.1 Rated operational voltage V 415V AC (+/- 10%), 3 Phase 4 wire System.2 Highest system voltage V 457 V AC 1.4 Rated frequency Hz 50 Hz (+/-3%) 1.5 Earthing Solidly Earthed 2.0 CONSTRUCTION: 2.1 Type of switchboard Incomer MCCB: Fixed type Other MCCB: Fixed type, Single Front, Compartmentalized 2.2 Overall Dimension (W X H X D) Mm As per Drawing Annexure Constructional features.1 Structure 2 mm CRCA.2 Mounting Plate 2 mm CRCA.3 Door 2 mm CRCA.4 Partitions / Covers 1.6 mm CRCA.5 Gland Plate 3 mm 2.4 Installation.1 Mounting on Angle Stand, Outdoor.2 Additional channel frame for foundation Base frame of 75 mm height.
13 .3 Lifting Arrangement Lifting hook provided (4 Nos.).4 Front access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.5 Rear access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.6 Future Extension Extensible on both side 2.5 Degree of Protection IP Paint.1 Material Epoxy Powder Coated min. 250 micron.2 Inside shade Siemens Grey.3 Outside shade Siemens Grey.4 Mounting Plate Orange.5 Base Frame Black 6. Surface Preparation 7 tank Process 2.7 Name plates Aluminum Anodized with letters engraved 3.0 CONTROL/AUXILLARY SUPPLY: 3.1 Circuit Rated Bus bar/wire Source Operational Voltage (V).1 Indication 240 V AC Wire Internal.2 Metering 240 V AC Wire Internal 4.0 TERMINATION & WIRING/BUSBAR ARRANGEMENTS: 4.1 BUSBAR FEEDER CONNECTIONS.1 System 3Phase, 4 Wire System.2 Rated Current Amp 400A.3 Material/ Grade (HBB) Electrolytic grade Aluminum(E91E Grade).4 Qty. X Cross section (HBB) mm 2 1 X 50 X 10 For Phase 1 X 50 X 10 For Neutral Note: Bidder to confirm the above size with calculation considering 0.8 A / sq.mm.5 Material/ Grade (VBB) Electrolytic grade Aluminum(E91E Grade)
14 .6 Qty. X Cross section (VBB) Mm As Per feeder rating of vertical section.7 Bus bar clearances Mm To be designed as per relevant IS code.8 Insulation (except at joints & tap-offs) Heat shrink PVC sleeves Red for R Phase, Yellow For Y Phase, Blue for B Phase, Black For Neutral.9 Insulation at joints & tap-offs Air.10 Color coding Strip of Colored heat shrinks PVC sleeves as a Marking at any 2 Feet Interval. 4.2 Earth Bus bar.1 Material / Grade Electrolytic grade Aluminum(E91E Grade) as per relevant IS.2 Qty. X Cross section (in mm) 1 X 50 X 6 mm 4.3 Incomer.1 Power & Control cable entry from Bottom 4.4 Out-going feeder.1 Power cable entry from Bottom.2 Control cable entry from Bottom 4.5 Glands.1 Supply at site.2 Drilling of gland plate at site (Removable Gland Plate) 4.6 Wiring.1 Type of wire Single Core Cu. Flexible wire.2 Insulation 1100 V PVC.3 Power wiring size.4 Control Wiring size 1.5 Sq.mm.5 C.T Wiring 2.5 Sq.mm.6 Colour coding for identification Colour sleeves at termination.7 Power Termination Crimped Tinned Copper Lugs Provided
15 .8 Control Termination Crimped End Insulated Tinned Copper Lugs Provided 4.7 Control terminal.1 Size of terminal Suitable to 2.5 Sq.mm wire size PANEL COOLING SYSTEM To be designed & submit the calculation for heat dissipation & Cooling system NOTES: 1. Earthing of doors will be through 2.5-mm2 yellow-green wires. 2. All the indication lamp shall be LED type. 3. Cap making MCC Panel The distribution panel shall be designed with Following Feeders; Sr. No./ TAG Description Type Rating GA Drawing Annexure 01 IC-1 Incomer Draw out type, Four Pole ACB 1250 A Annexure 3 02 Supply to CAP 1 MCCB with MP based OC & SC 630 A protection released (Four Pole) 03 Supply to CAP 1 MCCB with MP based OC & SC 125A Chiller protection released (Four Pole) 04 Supply to CAP -1 SFU 63 A Compressor 05 Supply to CAP 1 CT SFU 63 A Starter Panel 06 Supply to Exhaust Fan SFU 63 A 07 Supply to CAP 2 MCCB with MP based OC & SC 630 A protection released (Four Pole) 08 Supply to CAP 2 MCCB with MP based OC & SC 125A Chiller protection released (Four Pole) 09 Supply to CAP - 2 SFU 100 A Compressor 10 Supply to CAP 2 CT SFU 100 A Starter Panel 11 Supply to Exhaust Fan SFU 100 A
16 The Distribution Panel shall be designed with the following specifications; DESIGN DETAILS 1.0 SYSTEM PARAMETERS 1.1 Ambient temperature.1 Maximum ambient air temperature Deg. C 45.2 Reference ambient temperature for Design 1.2 Rated voltage Deg. C 50.1 Rated operational voltage V 415V AC (+/- 10%), 3 Phase 4 wire System.2 Highest system voltage V 457 V AC 1.4 Rated frequency Hz 50 Hz (+/-3%) 1.5 Earthing Solidly Earthed 2.0 CONSTRUCTION: 2.1 Type of switchboard Incomer ACB: Draw out type Other MCCB: Fixed type, Single Front, Compartmentalized 2.2 Overall Dimension (W X H X D) Mm As per Drawing Annexure Constructional features.1 Structure 2 mm CRCA.2 Mounting Plate 2 mm CRCA.3 Door 2 mm CRCA.4 Partitions / Covers 1.6 mm CRCA.5 Gland Plate 3 mm 2.4 Installation.1 Mounting on Floor (Free standing), Indoor.2 Additional channel frame for foundation Base frame of 75 mm height.
17 .3 Lifting Arrangement Lifting hook provided (4 Nos.).4 Front access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.5 Rear access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.6 Future Extension Extensible on both side 2.5 Degree of Protection IP Paint.1 Material Epoxy Powder Coated min. 250 micron.2 Inside shade Siemens Grey.3 Outside shade Siemens Grey.4 Mounting Plate Orange.5 Base Frame Black 6. Surface Preparation 7 tank Process 2.7 Name plates Aluminum Anodized with letters engraved 3.0 CONTROL/AUXILLARY SUPPLY: 3.1 Circuit Rated Bus bar/wire Source Operational Voltage (V).1 Indication 240 V AC Wire Internal.2 Metering 240 V AC Wire Internal 4.0 TERMINATION & WIRING/BUSBAR ARRANGEMENTS: 4.1 BUSBAR FEEDER CONNECTIONS.1 System 3Phase, 4 Wire System.2 Rated Current Amp 400A.3 Material/ Grade (HBB) Electrolytic grade Aluminum(E91E Grade).4 Qty. X Cross section (HBB) mm 2 1 X 160 X 10 For Phase 1 X 160 X 10 For Neutral Note: Bidder to confirm the above size with calculation considering 0.8 A / sq.mm.5 Material/ Grade (VBB) Electrolytic grade Aluminum(E91E Grade)
18 .6 Qty. X Cross section (VBB) Mm As Per feeder rating of vertical section.7 Bus bar clearances Mm To be designed as per relevant IS code.8 Insulation (except at joints & tap-offs) Heat shrink PVC sleeves Red for R Phase, Yellow For Y Phase, Blue for B Phase, Black For Neutral.9 Insulation at joints & tap-offs Air.10 Color coding Strip of Colored heat shrinks PVC sleeves as a Marking at any 2 Feet Interval. 4.2 Earth Bus bar.1 Material / Grade Electrolytic grade Aluminum(E91E Grade) as per relevant IS.2 Qty. X Cross section (in mm) 1 X 50 X 6 mm 4.3 Incomer.1 Power & Control cable entry from Bottom 4.4 Out-going feeder.1 Power cable entry from Bottom.2 Control cable entry from Bottom 4.5 Glands.1 Supply at site.2 Drilling of gland plate at site (Removable Gland Plate) 4.6 Wiring.1 Type of wire Single Core Cu. Flexible wire.2 Insulation 1100 V PVC.3 Power wiring size.4 Control Wiring size 1.5 Sq.mm.5 C.T Wiring 2.5 Sq.mm.6 Colour coding for identification Colour sleeves at termination.7 Power Termination Crimped Tinned Copper Lugs Provided
19 .8 Control Termination Crimped End Insulated Tinned Copper Lugs Provided 4.7 Control terminal.1 Size of terminal Suitable to 2.5 Sq.mm wire size PANEL COOLING SYSTEM To be designed & submit the calculation for heat dissipation & Cooling system NOTES: 1. Earthing of doors will be through 2.5-mm2 yellow-green wires. 2. All the indication lamp shall be LED type. Sr. No./ TAG 4. Slitter Distribution Panel The distribution panel shall be designed with Following Feeders; Description Type Rating GA Drawing Annexure Incomer MCCB with MP based OC & SC 125 A Annexure protection released (Four Pole) 4 01 IC-1 02 Supply to SR8-1 SFU 63 A 03 Supply to SR8-2 SFU 63 A 04 Supply to SR8-3 SFU 63 A 05 Supply to SR8-4 SFU 63 A 06 Supply to Spare SFU 63 A
20 The Distribution Panel shall be designed with the following specifications; DESIGN DETAILS 1.0 SYSTEM PARAMETERS 1.1 Ambient temperature.1 Maximum ambient air temperature Deg. C 45.2 Reference ambient temperature for Design 1.2 Rated voltage Deg. C 50.1 Rated operational voltage V 415V AC (+/- 10%), 3 Phase 4 wire System.2 Highest system voltage V 457 V AC 1.4 Rated frequency Hz 50 Hz (+/-3%) 1.5 Earthing Solidly Earthed 2.0 CONSTRUCTION: 2.1 Type of switchboard Incomer MCCB: Fixed type Other MCCB: Fixed type, Single Front, Compartmentalized 2.2 Overall Dimension (W X H X D) Mm As per Drawing Annexure Constructional features.1 Structure 2 mm CRCA.2 Mounting Plate 2 mm CRCA.3 Door 2 mm CRCA.4 Partitions / Covers 1.6 mm CRCA.5 Gland Plate 3 mm 2.4 Installation.1 Mounting on Floor (Free standing), Indoor.2 Additional channel frame for foundation Base frame of 75 mm height.
21 .3 Lifting Arrangement Lifting hook provided (4 Nos.).4 Front access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.5 Rear access Hinged doors For Feeders & Cable Alley Bolted Covers For Busbar Alley.6 Future Extension Extensible on both side 2.5 Degree of Protection IP Paint.1 Material Epoxy Powder Coated min. 250 micron.2 Inside shade Siemens Grey.3 Outside shade Siemens Grey.4 Mounting Plate Orange.5 Base Frame Black 6. Surface Preparation 7 tank Process 2.7 Name plates Aluminum Anodized with letters engraved 3.0 CONTROL/AUXILLARY SUPPLY: 3.1 Circuit Rated Bus bar/wire Source Operational Voltage (V).1 Indication 240 V AC Wire Internal.2 Metering 240 V AC Wire Internal 4.0 TERMINATION & WIRING/BUSBAR ARRANGEMENTS: 4.1 BUSBAR FEEDER CONNECTIONS.1 System 3Phase, 4 Wire System.2 Rated Current Amp 125A.3 Material/ Grade (HBB) Electrolytic grade Aluminum(E91E Grade).4 Qty. X Cross section (HBB) mm 2 1 X 20 X 10 For Phase 1 X 20 X 10 For Neutral Note: Bidder to confirm the above size with calculation considering 0.8 A / sq.mm.5 Material/ Grade (VBB) Electrolytic grade Aluminum(E91E Grade)
22 .6 Qty. X Cross section (VBB) Mm As Per feeder rating of vertical section.7 Bus bar clearances Mm To be designed as per relevant IS code.8 Insulation (except at joints & tap-offs) Heat shrink PVC sleeves Red for R Phase, Yellow For Y Phase, Blue for B Phase, Black For Neutral.9 Insulation at joints & tap-offs Air.10 Color coding Strip of Colored heat shrinks PVC sleeves as a Marking at any 2 Feet Interval. 4.2 Earth Bus bar.1 Material / Grade Electrolytic grade Aluminum(E91E Grade) as per relevant IS.2 Qty. X Cross section (in mm) 1 X 25 X 6 mm 4.3 Incomer.1 Power & Control cable entry from Bottom 4.4 Out-going feeder.1 Power cable entry from Bottom.2 Control cable entry from Bottom 4.5 Glands.1 Supply at site.2 Drilling of gland plate at site (Removable Gland Plate) 4.6 Wiring.1 Type of wire Single Core Cu. Flexible wire.2 Insulation 1100 V PVC.3 Power wiring size.4 Control Wiring size 1.5 Sq.mm.5 C.T Wiring 2.5 Sq.mm.6 Colour coding for identification Colour sleeves at termination.7 Power Termination Crimped Tinned Copper Lugs Provided
23 .8 Control Termination Crimped End Insulated Tinned Copper Lugs Provided 4.7 Control terminal.1 Size of terminal Suitable to 2.5 Sq.mm wire size PANEL COOLING SYSTEM To be designed & submit the calculation for heat dissipation & Cooling system NOTES: 1. Earthing of doors will be through 2.5-mm2 yellow-green wires. 2. All the indication lamp shall be LED type. AIR CIRCUIT BREAKERS These will be motor operated draw-out/non Draw out type suitable for 415 V, 50Hz supply. The ACB will have suitable built in solid state/ microprocessor based protective device with all accessories. Current rating, short circuit current, protection relays etc. will be provided. Mechanical interlock will be provided such that the ACB feeder cubical door can not be open when ACB is ON. All accessories such as 6 NO/6 NC auxiliary contact, safety shutter, door interlocking, locking in isolated position, racking interlock will be provided. The ACB shall be designed for fault level of 70 KA. MOULDED CASE CIRCUIT BREAKERS MCCBs will be manual type provided with operating handle mechanism and door interlocking. The MCCBs will be with four pole construction arranged for simultaneous three pole manual closing or opening & automatic instantaneous tripping on short circuit. Closing mechanism will be quick make & quick break & trip free type & will give a clear indication ON, OFF & TRIP indication. Control voltage for MCCB will be 240 volts. Fault rating of MCCB will be minimum 35kA. SWITCH FUSE UNIT The load break switches shall be suitable for continuos maximum rating, air break type & shall have manual quick make/ break mechanism. Switch handle shall be provided with door interlocking mechanism. Also the defeat arrangement shall be provided to open the door in switch close position for testing purpose. Live terminals of switch shall be shrouded. Fuses shall be HRC link type One set of fuse puller also shall be provided.
24 5. Starter Panel for Cooling Tower Starter panel contains with the following accessories: 5.1 Income MCCB 100Amp, 4 Pole with SC and EF protection 5.2 Star-Delta & DOL starters as per GA drawing (Annexure-V) 4. Schedule of Requirement Sr. No. Description UOM Qty 1 Bus Bar Panel 800 A No MCC 400 A for Cooling Tower + Silo No MCC 1250 A for CAP making m/c No Slitter Distribution Panel No Cooling Tower Starter Panel No. 03 Note: The Incomer MCCB feeder shall have metering facility with LCD display. Supervision on installation, testing & commissioning should be included in quoted price. 5. DRAWINGS Panel layout of Busbar panel Annexure 1 Panel of Cooling Tower + Silo Distribution MCC panel Annexure -2 Panel of Cap Making MCC Annexure -3 Slitter Distribution Panel Annexure 4 Starter Panel Annexure - 5
25 Special note to bidders: 1) Drawings to be submitted by the bidder for approval a) GA of all panels (MCC and Busbar Terminal Box) b) Wiring diagram of panels 2) Detailed Technical Specification should be submitted by the bidder. 3) MDG reserves the right of approving the make of all switchgears, Electricals, wires, cables and components. It will be binding on the successful bidder to supply panels using approved make items only. APPLICABLE STANDARDS Sr. No. IS No. Description 1) IS: : Specification for AC circuit breakers. NOTE : 2) IS:2705 : CT for measuring and protection. 3) IS:3155 : Voltage (Potential) Transformers. 4) IS:3236 Part II : Voltage Transformer. 5) IS:373 : Busbar arrangement and marking. 6) IS:2099 : Bushing 7) IS:2629 & 2633 : Hot Dip Galvanizing 8) IS:3842 : Relays. 9) IS: : Meters (measuring). 10) IS: : Installation of Switch gears. 11) IS:3043 : Code of practice for earthing. 12) IS: : HD Air breaker, Switch gears and fuses for Voltage not exceeding 1000 Volts. 13) IS:2208 : HRC cartridge fuse and links up to 660 volts. 14) IS:9224 : HRC fuses having rupturing capacity of 90 KA. All codes and standards means the latest where not specified otherwise the installation shall generally follow the Indian Standard codes of practice or relevant British Standard Codes of Practice in the absence of corresponding Indian Standards.
26 MAKES OF MAJOR SWITCHGEARS 1) Switch Fuse Unit : L&T, Siemens, Schneider - AC 23 duty 2) HRC Fuses : L&T, Siemens, Schneider 3) Glands : Compression type, Heavy duty and deep threading with rubber ring and double washers. (Sample to be approved) HMI 4) Cable Lugs : Dowells 5) Connectors : Elemax 6) MCCB : L&T, Siemens, Schneider (Non Draw out) 7) Relay : Siemens, L&T, Schneider 8) Meter : L & T or Equivalent 9) Load Manager : Conzerv 6436 (Suitable for PC Connectivity) 10) Flexible cables for internal : Finolex, Polycab, havells equivalent Control wiring 11) Push Button/ LED Type indication Lamp : L&T Recommended Makes for Cables and Wires: 1) Polycab 2) Havells 3) Avocab 4) KEI
27
28
29
30
31
MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY
PURCHASE ENQUIRY Inquiry No : MDG/PUR/PKS/ENQ/Panels, Dated: Nov 3, 2014 Description Qty Specifications : Purchase Inquiry for Supply, installation and commissioning of Panels for PFP Expansion project.
More informationAMULFED DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY
PURCHASE ENQUIRY Inquiry No : AFD/PUR/PKS/ENQ/FB, Dated: May 18, 2018 Description Qty : Purchase Inquiry for Supply of Forklifts, Battery Operated Hand Pallet trucks & Hand Pallet trucks for AFD & PFP
More informationMOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE INQUIRY
PURCHASE INQUIRY Inquiry No : MDG/PUR/PKS/ENQ/PET/2, Dated: Nov 14, 2014 Description : Purchase Inquiry for Supply Installation and Commissioning of Pre-processing system for New PET Line. Qty : 1 set
More informationMOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY
PURCHASE ENQUIRY Enquiry No : MDG/PUR/PKS/ENQ/High Speed/1, Aug 11, 2015 Sub : Purchase Inquiry for supply and installation of two High speed Milk Qty : 2 Nos Due Date : 22/8/2015. Terms and Conditions
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:
More informationTECHNICAL SPECIFICATIONS OF PCC PANEL
S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More informationSTANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011
Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV
More informationMAIN INCOMER -1 (500 KVA TRF.)
Sr.No. DESCRIPTION MAKE QTY 1 MAIN L.T.PANEL Design, fabrication assembling, supply, installation, testing and commissioning of cubicale type LT panels floor mounted free standing suitable for 415 V 3
More informationNLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX
NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.
More informationBHARAT HEAVY ELECTRICALS LIMITED, JHANSI
BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause
More informationTender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount
Tender Schedule for Electrical Works at Varagani Branch Sl. No. 1 Particulars Quantity Unit Rate Amount SITC of following rated Indoor operated wall/floor mounted, cubicle type MV cum APFC Panel suitable
More information: Material Description Quantity UOM
Page : 1 / 2 OIL INDIA LIMITED (A Govt. Of India Enterprise) Tel :033 2230 1657, 1658 4, India Exchange Place, Fax :91 33 2230 2596 Kolkata-700001 E-mail :oilcalmn@cal2.vsnl.net.in ANNEXURE-I Item No./
More informationTechnical Specifications
LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for
More informationTECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077
spec- 200 Amp. & 400 Amp. LT Dist. Kiosk.doc - 1 - SCHEDULE-III TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077
More informationWest Bengal State Electricity Distribution Co. Ltd.
West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,
More informationTENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID
TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES
More informationDATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT
44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More informationTECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)
TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA TENDER FOR
GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA - 390 007 TENDER FOR Design,Engineering, manufacturing, supply, erection, testing & commissioning of 66
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender Notice No. 40/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Electrical work for the Clean Room at NCFlexE IIT Kanpur. Name of the Contractor S. No Description
More informationD.C. DISTRIBUTION BOARD
PRAMBL: The TC is maintaining 50-volt battery backup system for the PLCC communication. The 50-volt D.C. supply from the Float cum Boost charger is brought to D.C. Distribution Board from where supply
More informationNPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations
Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification
More information37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS
SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS
More informationAN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR
AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/696/411 FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL
More informationSection VI: List of Requirements (REVISED)
As per Technical Specifications attached in Section VII Date: 18/06/2018 of Electrical Items With reference to the above tender, the following Corrigendum may kindly be noted against the Section VI, Section
More informationWEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A
Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum
More informationPURCHASE ENQUIRY MDG/PUR/PKS/ENQ/APS Oct 16, 2012
PURCHASE ENQUIRY MDG/PUR/PKS/ENQ/APS Oct 16, 2012 Sub : Purchase Inquiry for Supply, Installation, testing and commissioning of MCC Panel for APS simplicity and PET Bottle Filling line at MDG. Dear Sir,
More informationto UPS outgoing DB. c With 2 nos. 6 Sq.mm + 1 no. 2.5 Sq.mm. PVC insulated copper wire from UPS outgoing DB to CDB / Main panel to LDB /
Bill of Quantity for Electrical & Computer wiring works for Shifting of RACPC Jamshedpur to new location of Jamshedpur Branch Premises S.No. Item Description Qty. Rate Amount 1 UPS DB / COMPUTER DB Supply
More informationKENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO
BILL 1 MAINS POWER DISTRIBUTION 2-1 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test, commission and set to work the following:- 1.01 Free-standing purpose made front access sub main switchboard
More information33KV INDOOR SWITCHGEAR
33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More information(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:
10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1
More informationKey features. DESIGNS: - Conservator type - Hermetically sealed
Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the
More informationTENDER DOCUMENT. (TENDER No: NRO/CON/696/660) FOR
TENDER DOCUMENT (TENDER No: ) FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1 & 2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION
More informationBill of Quantity for Electrical & Computer wiring works for Shifting of SMECC Jamshedpur to Jamshedpur Branch Premises
Bill of Quantity for Electrical & Computer wiring works for Shifting of SMECC Jamshedpur to Jamshedpur Branch Premises S.No. Item Description Qty. Rate Amount 1 Removing and Reinstallation of Main Incoming
More informationINVITATION FOR QUOTATION. TEQIP-III/2018/gcej/Shopping/50
INVITATION FOR QUOTATION TEQIP-III/2018/gcej/Shopping/50 15-Sep-2018 To, Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for the
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender tice. 21/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Construction of second floor above central block at ACES building (SH: Electrical works). Name of the
More informationBILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH
BILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH SL NO. DESCRIPTION OF ITEM / WORK UNIT QTY PART - A : ELECTRICAL WORKS 1 1 Energy Meter Cubicle : a Fabrication, Supply, Installation, testing
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More informationMetal Clad VCBs ~ Mk1
Metal Clad VCBs ~ Mk1 DUVI 150/40 ROLL ON FLOOR VCBs Range: 6kV, 00A, 1.5kA, 12kV, 150A, 40kA ( 4A000A Bus-Bars ) ` Widest range for MV (up to 6kV) Distribution Networks Megawin make metal clad VCB Panels
More informationS H A D E S ELECTRICAL DB MANUFATURING
CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give
More informationSCHEDULE OF QUANTITY
SCHEDULE OF QUANTITY ELECTRICAL WORKS PM PALEM BRANCH, VISAKHAPATNAM SL NO. DESCRIPTION OF ITEM / WORK UNIT Qty RATE AMOUNT PART - A : ELECTRICAL WORKS 1 Energy Meter Cubicle : 2 Emergency Off Box (Red
More informationINDIAN MARITIME UNIVERSITY KOLKATA CAMPUS
INDIAN MARITIME UNIVERSITY KOLKATA CAMPUS No. IMU-KC/Laboratory Equipment/16-17 Date: 17.02.2017 Sub: Quotation for procurement of Instruments for Electrical Machine Laboratory at IMU-Kolkata Campus Sealed
More information16.13 Unit Substation to 15kV Construction Standards Page 1 of 7
Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected
More informationGAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura
Modular-C\Standardized Motor Control Centres\ M600204.15 PT Guna Era Manufaktura Catalogue 2015 GAE MCC Modular-C Standardized Motor Control Centres General Definition Type-tested low-voltage switchgear
More informationMEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV
CE - B36 - C - en - REV.00 2011.9 EDIU VOLTAGE EDIU VOLTAGE APPLICATION CE-B etal Clad switchboards are designed for use in public and industrial distribution system up to 36kV for the operation and protection
More informationAmendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).
Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Sr. No. Clause No Existing Proposed 1 8.0 Dischar ge device 2 15.0
More informationTender Schedule. Sl. No. Particulars Quantity Unit Rate `
Tender Schedule Estimate for Electrical Works at Savalyapuram Branch(18901) Guntur(District). Sl. No. Particulars Quantity Unit Rate ` 1 Wiring for light point/ fan point/ exhaust fan point/ call bell
More informationype UP T Busplugs Low Voltage Switchboard Equipment
Busplugs Type UP Low Voltage Switchboard Equipment Publication UP 2013 Since product improvement is a continuing policy, we reserve the right to change specifications without notice. Contents Descriptive
More informationTECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY.
TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. 1.0 SCOPE: This specification covers the design, manufacturing and testing of LT Distribution
More information31-SDMS-01 REV. 03 SPECIFICATIONS FOR
31-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PANEL This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1.0 SCOPE
More informationMEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV
MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE-B Metal Clad switchboards are designed for use in public and industrial distribution system up to 24kV for the operation and protection of lines, generators,
More informationPART A: FINANCIAL BID
TENDER DOCUMENT FOR INTERIOR FURNISHING WORKS (excluding ELECTRICAL & DATA CABELING WORK) IN BANK OF INDIA BRANCH AT FARIDABAD,(SME BRANCH), HARYANA BANK OF INDIA, ZONAL OFFICE, STAR HOUSE, S.C.O. NO.
More informationType SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear
Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated
More informationشركة كهرباء محافظة القدس المساهمة المحدودة
Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationSAVE ENERGY FOR BENEFIT OF SELF AND NATION
Taluka: Thasra Dist : Kheda Pin: 388 239 Telephone No. 02699-235 522 Fax No. 02699-235 607 CHIEF ENGINEER (C&O), GSECL,, INVITES TENDERS FROM INTERESTED BIDDERS, FOR SUPPLY OF ABOVE MATERIAL. THE DETAILS
More informationINVITATION FOR QUOTATION. TEQIP-II/2015/GJ1G02/Shopping/M-EE-09
INVITATION FOR QUOTATION TEQIP-II/2015/GJ1G02/Shopping/M-EE-09 02-Dec-2015 Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for
More informationSPECIFICATIONS OF SINGLE GIRDER UNDER SLUNG E.O.T. CRANE CAPACITY: 5 MT
1 SPECIFICATIONS OF SINGLE GIRDER UNDER SLUNG E.O.T. CRANE CAPACITY: 5 MT QUALIFICATION CRITERIA Vendor has to compulsorily meet the following requirements to get qualified for consideration of the technical
More informationSupply of 63 kva DIESEL GENERATOR SET WITH AMF
No. NIQ/INKEL/2015-16/162 24 TH Nov 2015 NOTICE INVITING QUOTATION Sealed Quotations are invited for and on behalf of INKEL Limited, having its registered office at INKEL Centre, Off Vallathol junction,
More informationMEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV
CE--C-en-REV.04 2016.1 MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE- Metal Clad switchboards family are designed for use in public and industrial distribution system up to 40,5kV for the operation and
More informationName of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal.
Name of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal. TENDER SCHEDULE -1-1 2 3 4 5 6 7 1 208 Point Wiring for light point/ fan point/ exhaust fan point/ call bell
More information32-SDMS-02 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV METERED RING MAIN UNIT UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES 3
More informationCENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies
Selection Checklist CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies Use this checklist to help you configure your CENTERLINE 2500 Motor Control Center. You can type in the fields
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationIntelligent Choice for Prestigious Buildings
Intelligent Choice for Prestigious Buildings Table of Contents I-LINE Moulded Case Circuit Breakers General Characteristics 16A to 160A 125A to 250A 250A to 600A 300A to 800A 630A to 1250A 2/3 4 5 6 6
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More information1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".
SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationNS Feeder pillar up to 3200A
NS Feeder pillar up to 3200A Advanced technology for low voltage, outdoor distribution Merlin Gerin Modicon Telemecanique Outdoor electrical distribution with advanced technology Merlin Gerin low voltage,
More information31-SDMS-02 REV. 01 SPECIFICATIONS FOR
31-SDMS-02 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PILLAR This specification is property of SEC and subject to change or modification without any notice C O N T E N T S S. NO. D E S C R I P
More informationSPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /
SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / 2005-06 SR.NO ITEM PAGE 1. SCOPE 2 2. WEATHER CONDITIONS 2 3. RATED VOLTAGE & FREQUENCY 2 4. GENERAL REQUIREMENT
More informationItem Code Description Unit Qty Total
UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationTENDER DOCUMENT TENDER No.: NRO / CON / 592 / 537 FOR SUPPLY & INSTALLATION. DG Sets & Sychronising Panel
TENDER DOCUMENT TENDER No.: NRO / CON / 592 / 537 FOR SUPPLY & INSTALLATION OF DG Sets & Sychronising Panel FOR for multistoreyed Boy s Hostel SARDAR VALLABHBHAI NATIONAL INSTITUTE OF TECHNOLOGY, SURAT,
More informationSwitchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.
www.siemens.com/medium-voltage-switchgear Switchgear Type 8BT1, up to 24 kv, air-insulated Medium Voltage Switchgear Catalog HA 26.31 2012 Answers for infrastructure and cities. R-HA26-013. eps Contents
More informationINDEX Bustrunking System Standard & Specifications Technical Parameters Copper Aluminum Components
INDEX Bustrunking System.. (1) Standard & Specifications.. (2) Technical Parameters Copper.. (3-4) Aluminum.. (5-6) Components Straight Length (Feeder & Plug in type).. (7) Uniblock Joint, Edge Elbow &
More informationRate (Rs.) in figure. Rate (Rs.) in words. VAT (%) Amount (Rs.) & all other taxes.
PRICE FORMAT FOR SUPPLY OF ELECTRICAL ITEMS PART B PRICE BID TITLE: PROCUREMENT OF ELECTRICAL ITEMS IN BHEL TOWNSHIP, SECTOR 17, NOIDA NIT NO: 08:AA:NOI:ADMN:Electrical Items :112:2013 14 Dated 02/08/2013
More informationATLV MaxSG. Low Voltage Metal Enclosed Switchgear
ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,
More informationCircuit Breaker Prepared By :
Circuit Breaker Prepared By : Eng : Ayman Soliman Selmy Circuit Breaker Specification of circuit Breaker:- [1] Operating voltage of C.B [2] Rated current of C.B (Ir or In) Amp. [3] Instantaneous short
More informationTotal Cost Abstract. Project Name : - RDPL, Jaipur. Grand Total
Project Name : - RDPL, Jaipur Total Cost Abstract S. No. Description Amount 1 Metering & Distribution Boxes 2 Earthing 3 Point Wiring & Fixtures 4 Data & Voice Grand Total Project Name : - RDPL, Jaipur
More information32-SDMS-03 SPECIFICATIONS FOR
SPECIFICATIONS FOR EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES
More informationMEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES
MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications
More informationDistribution Blocks & Bus-bar Solutions
Distribution Blocks & Bus-bar Solutions Insulated Multi Laminate Flexible Copper Bus-bars Threaded Copper Bus-bars Solid Copper Bus-bars Bus-bar Insulators & Supports Insulated Flexible Copper Braided
More informationEuroload Changeover Switch
Euroload Features: Quick make & quick break mechanism. High electrical & mechanical endurance. Advance neutral. Enclosed housing to avoid dust ingress. Staggered terminals upto 800A. Load and Line reversibility.
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationTENDER DOCUMENT PART-II
1 NATIONAL BANK FOR AGRICULTURE AND RURAL DEVELOPMENT TAMILNADU REGIONAL OFFICE TENDER DOCUMENT PART-II (PRICE BID) Supply, Installation, Testing and Commissioning of 25 kva DG Sets with Acoustic Enclosure
More informationAIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE
AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly
More information२१७१ २-१ ४४ २०१८ २-१ २१०९-४ २०१८ २९ ०६ २०१८ २ २ १२४९ २-१ ४४ २०१८ २१ ०७ २०१८ ३ २ १७०५ २ / -१ ४४ २०१८ १० १० २०१८ १ २ ३ २ ३ १३ २०१८-१९
२१७१ २-१ ४४ २०१८ २ :- (०७१७२)२२७३८२-४४२४०३ - (०७१७२)२२७३८२ - mlidn2@rediffmail.com ३१ / १२ २०१८ - - १ २१०९-४ २०१८ २९ ०६ २०१८ २ २ १२४९ २-१ ४४ २०१८ २१ ०७ २०१८ ३ २ १७०५ २ / -१ ४४ २०१८ १० १० २०१८ ------000-----
More informationEstimate For Electrical Works PROPOSED RUDSET INSTITUTE AT BERHAMPUR
Estimate For Electrical Works PROPOSED RUDSET INSTITUTE AT BERHAMPUR Sl No Brief description of work item Unit Qty Rate Amount Total Rs A INTERNAL WIRING Supply, laying of 2mm thick approved make PVC conduit
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More information/ १७८६ य २-२ / ४४ / ब ऑफर २०१७
-https://wrd.maharashtra.gov.in / १७८६ य २-२ / ४४ / ब ऑफर २०१७ :- (०७१७२)२२७३८२ फ - (०७१७२)२२७३८२ म :- mlidn2@rediffmail.com ०४ ०८ २०१७-442403 - म य य ब म य य य म य य य भ म र भ र य र म ब र ऑफर. ८ / २०१७-१८
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationLow Voltage Main Distribution Board
s M series... Low Voltage Main Distribution Board Safe and intelligent power distribution Whether in industrial plants, in infrastructure or in buildings, all technical plant depends on the reliable supply
More informationLIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016
No Description/ Specification Amendment 1 EDD 1 :2008 11/0.415 kv Distribution Transformer, Oil Filled - 2 ED 2 :1987 The Galvanization of Iron and Steel, Articles Other Than Steel Wire - 3 ED 3 :1979
More information