1 Top 10 Noise Control Techniques Top 10 Noise Control Techniques innovative "magic bullets" that may make you think... Low cost, DIY engineering best practice for common problems 1 fan installation details 2 simple ductwork silencing 3 fan speed 4 pneumatic exhausts 5 pneumatic nozzles 6 damping - chutes, hoppers, guards... 7 vibration isolation pads - motors, pumps... 8 upgrade existing guards 9 chains and toothed belts 10 quiet motors - buy quiet retro-fit fan modifications yoghurt-based combustion control bolt-on quiet free collateral quiet Industrial Noise and Vibration Centre: Slough The You must control Noise at Work Regulations Placebo Silencers these regulations are concerned with controlling, not measuring it..." Hearing protection can no longer be used for long term risk management unless it can be proved that control is impractical Companies should not repeat risk assessments that do not include useful and practical information on control Companies should carry out a Noise Control Audit assess the control options using the best of current technology generate cost v reduction trade-offs for each item of noisy plant plan the most practical and cost effective control programme Copyright 2009 INVC
2 k14 Noise Control is... Self-Financing Noise Control Improved efficiency / productivity due to control modifications. Noise control is not a safety issue Noise control is an engineering problem that should be solved by engineering means, in particular through control at source. Effective control must be based on an accurate diagnosis and not on assumptions All the options must be considered, not just the conventional high cost palliatives of enclosures and silencers. These techniques should only be used where it can be proved that there is no engineering alternative. One company had spent 1,600,000 on acoustic enclosures. The Noise Control Audit and subsequent testing proved that using BPM would have saved over 1,000,000 and levels would have been substantially lower and operating costs would be significantly reduced (down-time). Noise source category vibrators burners fans weighing Pay-back Period 4 weeks 1 year 3 years 1 minute... doubled through-put higher efficiency, no cleaning cleaning down-time reduced avoided being shut-down... presses 2 years no enclosures, reduced down-time Noise control costs - 000's conventional best practice Fan Designs axial fan - quiet impellor Fans centrifugal fan Industrial Noise and Vibration Centre: Slough Copyright 2009 INVC
3 m15 Centrifugal Fan Installation m16 Axial Fan Installations NOISY QUIETER NOISY high pressure low pressure >2-3 duct diameters QUIET m35 Fan: Outlet dampers m20 Stalag Chicken-Run Henhouse Up to 19dB tonal reduction from axial fans via modifications to existing fan ductwork to improve flow conditions. As the main neighbourhood complaints were about the 62.5Hz tone, this was a very cost effective solution at 25/fan compared with very large conventional silencers. Copyright 2009 INVC
4 88 Simple Ventilation Silencing m85 Fan Outlet Silencer Cowl 600 mm steel / plywood ventilation silencer for rooms of up to 150m^3 150 mm 1000 mm acoustic absorbent perforated sheet steel 25% open area c3mm holes acoustic absorbent 250 mm 18swg steel sheet duct A simple, cheap absorbent lined cowl can give a 10-20dB(A) reduction in fan inlet /outlet Scrap Can Extract and Chopper Fans Fan Speed v Noise Problem Occupational and environmental tonal Conventional silencers, lagging and enclosures capital cost > c maintenance costs BPM Engineering internal fan modification reduced tones by 23dB and overall by 22dB(A) Cost c no maintenance costs (lasts the lifetime of the fans despite passage of cans) sound modified fan speed reduction reduction db 10% 2 20% 5 30% 8 40% 11 50% 15 Copyright 2009 INVC
5 s85 Cooling Tower Silencer Boiler Burner 16dB tonal reduction w20 Sand Burner Pneumatics Industrial Noise and Vibration Centre: Slough Copyright 2009 INVC
6 Pneumatic Silencers Pneumatic Nozzles Silencer Solutions zero back-pressure silencers - or a larger coupling standardise on 3 sizes fix piped silencers to machine and manifold multiple exhausts Entraining Nozzles c10db quieter for the same thrust use c 20% less air pay for themselves very quickly intrinsically "safe" reduce air pressure... entrained ambient air annulus compressed air directing cone m2 Quiet Nozzle Design Scrap Product Air-Lances db tool clearance (mm) flatjet commercial nozzle Cu pipe Copyright 2009 INVC
7 Filler Cooling Pipes Problem 94dB(A) from cooling pipes for sealed tube ends - rapid cooling a necessity Conventional Solution enclosure - high cost with hygiene and productivity issues BPM Solution Coanda effect linear nozzles 12dB(A) reduction (82dB(A)) improved performance (less turbulence disturbing tubes) 20% less air consumption - pay for themselves very quickly no effect on access or operation Vibration Damping Industrial Noise and Vibration Centre: Slough p10 Damping Thin Plates s90 Vibratory Bottle Unscrambler unconstrained layer of damping material damping material in sandwich construction Problem Vibratory feed hopper for unscrambler generating 90dB(A) damping material damping material deforms only near bends sheet metal damping material made to shear over whole area BPM poor design: vibrators at high level to vibrate whole hopper - feed still inefficient laminated plate inside existing hopper (grommet isolation), connected to vibrators through holes in hopper: cost c 400 reduced vibrator level, improved feed, reduced from 90dB(A) down to 82dB(A) Copyright 2009 INVC
8 m49 Damped Dry Chiller p1 115T Bliss Press Dynamic vibration absorbers designed and fitted to flywheel inside existing guards. Total 8dB(A) reduction under chiller (damping + absorbent) 10dB(A) reduction 20 materials; 1 day fitter time Panel Vib n13 Verso Press Problem High speed strip fed press at 101dB(A) in a quiet area Conventional Manufacturer supplied "acoustic guards" gave only 3dB(A) reduction. Full enclosure suggested. Vibration Isolation Industrial Noise and Vibration Centre: Slough isolation pads BPM Noise Control Audit showed dominant source to be fabricated press legs. Tico isolation fitted between frame and legs tuned to give natural frequency of 65Hz for both legs (different loads) 9dB(A) reduction at closest operator position. 45 materials, 1 man day to fit Copyright 2009 INVC
9 k58 Hydraulic Power Pack n10 Machine Foot Isolation Looking at the diagnostic procedure for this power pack:- m/c foot Tico pad load-spreading steel washer PPack bolt NO ISOLATION Tico pad bolt EFFECTIVE ISOLATION Modify Existing Machine Guards Minimise gaps halving the open area of gaps in a set of guards will reduce the from this source by 3dB reduce the openings by 90% - 10dB reduction Existing Guards Acoustic Absorbent Line a significant proportion of the inside of guards with acoustic absorbent (foam, rockwool) Guard vibration radiated as - use damping... Test mock-ups Industrial Noise and Vibration Centre: Slough Copyright 2009 INVC
10 Modify Existing Guards "Blue Peter" Cardboard Engineering gaps open outfeed no acoustic absorbent ringing box section Belt Drives replace noisy chains with belts use quiet tooth profiles on toothed belts chevron tooth pattern - ultra-quiet Chains and Toothed Belt Drives replace wide belts with a pair of narrower belts toothed belt is very sensitive to belt tension 5-20dB reductions possible Industrial Noise and Vibration Centre: Slough Copyright 2009 INVC
11 Buy Quiet Motors Do not allow your suppliers to spend your money on control without close scrutiny and evidence that they have followed diagnostic best practice Buy Quiet Motors Industrial Noise and Vibration Centre: Slough Remote Control of Noise video sound photos Remote Control Specialised analysis or CD Industrial Noise and Vibration Centre: Slough Free evaluation of control costs and options database Copyright 2009 INVC
12 Top 10 Noise Control Techniques innovative "magic bullets" that may make you think... Low cost, DIY engineering best practice for common problems 1 fan installation details 2 simple ductwork silencing 3 fan speed 4 pneumatic exhausts 5 pneumatic nozzles 6 damping - chutes, hoppers, guards... 7 vibration isolation pads - motors, pumps... 8 upgrade existing guards 9 chains and toothed belts 10 quiet motors - buy quiet retro-fit fan modifications yoghurt-based combustion control bolt-on quiet free collateral quiet Top 10 Noise Control Techniques Further information and case studies: Industrial Noise and Vibration Centre: Slough Copyright 2009 INVC
TOP 10 NOISE CONTROL TECHNIQUES
TOP 10 NOISE CONTROL TECHNIQUES The following are 10 simple noise control techniques that have wide application across the whole of industry. In many cases, they will produce substantial noise reductions
More informationVersatility. Features. By installing the SILENT MV, you will never experience the disturbance of noisy ventilation again. Benefits
Ultra quiet and low profile helicocentrifugal in-line fans suitable for a wide range of domestic and commercial applications. Fitted with sound absorbent insulation and manufactured with an adjustable
More informationSILENT MV Ultra Quiet In-line Fans
Ultra Quiet In-line Fans 5 IP44 2 YEAR GUARANTEE Ultra quiet and low profile helicocentrifugal in-line fans suitable for a wide range of domestic and commercial applications. Fitted with sound absorbent
More informationACTIVENT System. Specifications. Product code example ACTA
Activent is a ventilation system for supplying and distributing air. The system has been proven to function effectively in both small and large areas and is used in all types of premises ranging from offices
More informationREVIEW ON NOISE AND VIBRATION IN AUTOMOBILES
REVIEW ON NOISE AND VIBRATION IN AUTOMOBILES AZAR R. INAMDAR 1, PRANITA A. DESHPANDE 2, SWAPNALI R. GADEKAR 3 1,2,3 Department of Mechanical Engineering, Sandip Foundation s, Sandip Institute of Technology
More informationCAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1
X X testregistrierung CAV controllers Type For the precise control of normal and high constant volume flows Rectangular self-powered volume flow controllers for the control of supply air or extract air
More informationCompressor Noise Control
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1972 Compressor Noise Control G. M. Diehl Ingersoll-Rand Research Follow this and additional
More informationROL NOZZLE DUCT ROL-S ADJUSTMENT AND SILENCER UNIT
6. ROL NOZZLE DUCT ROL-S ADJUSTMENT AND SILENCER UNIT The stylish and silent nozzle duct ROL is designed for rooms requiring large air volumes distributed evenly and without draught. The functional entity
More informationCAV controllers. Type VFL. Volume flow limiter for insertion into ducting K
.1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical
More informationCAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)
X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered
More informationSound attenuators. Sound attenuators, Sound attenuating louvres. Sound attenuators. Rectangular sound attenuators DZ-2, DZ-3
, Sound attenuating louvres Rectangular sound attenuators DZ-2, DZ-3 Application are designed to attenuate noises of fans and air-conditioning devices in ventilation and air-conditioning installations.
More informationVAV terminal units. Type TVM. For dual duct systems PD TVM 1
X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings
More informationSILENCER SELECTION INSTRUCTIONS
For general information in HVAC Acoustics, consult the following publications: 2013 ASHRAE Fundamentals Handbook, Chapter 8 Sound and Vibration 2011 ASHRAE Applications Handbook, Chapter 48 Noise and Vibration
More informationV1000, A1000, E7, F7, G7,
White Paper High Slip Braking Software Applicable, and P7 (V/f Motor Control Method) Mike Rucinski, Manager, Applications Engineering, Yaskawa Electric America, Inc. Paul Avery, Sr. Product Training Engineer,
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationCAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1
X X testregistrierung CAV controllers Type For the precise control of constant volume flow rates Circular self-powered volume flow controllers for the control of supply air or extract air in constant air
More informationVane Axial Fans Models VAB and VAD. Belt and Direct Drive
Vane Axial Fans Models VAB and VAD Belt and Direct Drive July 2008 XX High Performance Vane Axial Fans Greenheck vane axial fans are designed for commercial and industrial applications where large volumes
More informationCAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1
X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered
More informationSCREW COMPRESSORS OIL-FREE
SCREW COMPRESSORS OIL-FREE Over 100,000 compressed air users expect more when it comes to their compressed air supply. BOGE air provides them with the air to work. BOGE oil-free screw compressors have
More informationThere are predominantly two reasons for excessive fuelling: increased fuel pressure and extended injector duration. Figure 1.0
In this tutorial we look at the actuators and components that affect the vehicles exhaust emissions when the electronically controlled fuel injection system is found to be over fuelling. There are predominantly
More informationNCF fans 50 Hz. Protection class IP 55
The Nederman NCF Fans have direct drive motors which means a safe and cost effective operation. Installing an energy efficient NCF fan with our other Nederman products saves time and reduces energy costs.
More informationCircular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/
6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn
More informationTRITON Underdrain Systems
TRITON Underdrain Systems TRITON UNDERDRAINS: The solution Triton Underdrains exceptional performance as a filter underdrain system utilizes Johnson s world renowned Vee-Wire screen technology and our
More informationSound Application Guide: Description and Ratings
Sound Application Guide: Description and Ratings AHRI SOUND STANDARD: DESCRIPTION AND RATINGS Table of Contents Overview..........................................................................4 AHRI
More informationNCF fans 60Hz. Protection class IP 55
The Nederman NCF Fans have direct drive motors which means a safe and cost effective operation. Installing an energy efficient NCF fan with our other Nederman products saves time and reduces energy costs.
More informationSPRAYBOOTH OVEN AUXILIARY AIR MOVEMENT DESIGN, OPERATION AND BENEFITS
SPRAYBOOTH OVEN AUXILIARY AIR MOVEMENT DESIGN, OPERATION AND BENEFITS 16 th May 2011 - Ref: QADs Review Junair Spraybooths ANZ Pty Ltd Phone: 1300 881 411 Post: Suite 302 Locked Bag 1, Robina Town Centre
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type RFD-Sirius, cross bar Horizontal swirling air discharge Circular diffuser face, integral measuring tubes is an air terminal device combined with a VAV
More informationSTANDARD DRYFILTER BOOTHS WITH CANOPY 1 METRE DEEP
STANDARD DRYFILTER BOOTHS WITH CANOPY 1 METRE DEEP Size Motor Extra 1000B 1 3500 24 1197.60 334.80 130.80 1500B 1.5 5000 24 1438.80 334.80 165.60 2000B 2 7000 24 1546.80 356.40 200.40 2500B 2.5 8000 24
More informationBenefits of EC Motor Technology for Automotive Air Handling
Benefits of EC Motor Technology for Automotive Air Handling Zeke Carlyon 10.30.12 Benefits of EC Motor Technology for Automotive Air Handling Lower Initial Cost With the simple open design fans units with
More informationTUBULAR CENTRIFUGAL INLINE FANS
Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS TUBULAR CENTRIFUGAL INLINE FANS MODEL TSL CATALOG 1001 APRIL 2014 CENTRIFUGAL INLINE FANS Model TSL The TSL is an inline centrifugal
More informationNoise Emissions At the Chicago Fuller Car Wash
Specialists in Hearing and Acoustics 12172 Route 47 - #218, Huntley, Illinois 60142 Tom Thunder, AuD, FAAA, INCE Principal Office: 847-359-1068 Fax: 847-359-1207 Greg Andorka, BSEE - Senior Field Engineer
More informationGUNOOK BOOTH CONTROLSYSTEM Saves energy, money and CO 2 emissions
RDM ENGINEERING Established 1951 COMPANY: ADDRESS: CONTACT NAME(S) RDM USE ONLY: QTY AVAILABLE /ISSUED QTY ORDERED /REQUIRED PHONE NO. PRICE LIST & DATA EXTRACTION UNITS SPRAYBOOTHS WATERWASH AND DRY FILTER
More informationOptimization of Total Operating Costs Using Electric Linear Drives
Optimization of Total Operating Costs Using Electric Linear Drives TCO analysis demonstrates high potential for savings, even for simple applications, by replacing pneumatic drives Electric linear drives
More informationCENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven
Model CBD Belt Driven Model CDD Direct Drive CENTAXIAL TUBULAR CENTRIFUGAL FANS BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) CATALOG 337 February 2004 Centaxial
More informationNoise Resist. - you need to improve the noise reduction of your existing sound enclosure
Noise Resist Is this your situation? - you need to reduce the noise emission of your machinery - you need to improve the noise reduction of your existing sound enclosure - you do not want delicate foam
More informationFINE-SEPARATION FOR AGGREGATES
FINE-SEPARATION FOR AGGREGATES LETTER FROM THE FAMILY Founded by H. William Derrick Jr. in 1951, Derrick Corporation was created to solve some of the most challenging mechanical separation needs of the
More information1/11 29/06/2016 CONTENTS 1. GENERAL DUCTS, AIR VENTS, VALVES MONOBLOCK UNITS FILTRATION CONTROL...
1/11 29/06/2016 VENTILATION AND Buildings & Technical Services Section AIR-CONDITIONING STANDARD CONTENTS 1. GENERAL... 2 2. DUCTS, AIR VENTS, VALVES... 2 3. MONOBLOCK UNITS... 3 4. FILTRATION... 5 5.
More informationBuilding Integrated Duct System
Mounting instruction Building Integrated Duct System Description We are facing one of the toughest challenges in decades. New buildings and existing homes must minimize their use of energy. In less than
More informationProduct Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm
Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA
More informationHere is the gap seal I used for the flaps, genuine hardware store quality. Note cross sectional shape visible on the right end.
HOMEBUILT AIRCRAFT DRAG REDUCTION - Case Study with a Lancair IV Part 3 Copyright - Fred Moreno - January 2009 Rev. 1 Portions may be reproduced for private, individual use 3- REDUCED AIRFRAME DRAG FOR
More informationRECTANGULAR EXTRACT FANS
RECTANGULAR EXTRACT FANS Wide duty range 0.05m 3 /sec to 3.2m 3 /sec Horizontal or vertical mounting Quick and easy to install VES EXTRACT FANS part of a complete range of innovative, flexible products
More informationNovenco Tunnel Fans. Novax October 2007
Novenco Tunnel Fans Novax October 2007 Product facts Product Novenco tunnel fans are produced with either round or rectangular outer dimensions. Both types are made in unidirectional (AUC and AUR) and
More informationFitting Instructions DucoGrille Close /03/2018
Fitting Instructions DucoGrille Close 105 27/03/2018 CONTENT 1. General 1.1 Dimensions 1.2 Orientation 1.3 Actuator side 1.4 Wiring diagram Belimo NM24A 1.5 Wiring diagram Belimo NM230A 1.6 Wiring diagram
More informationPent-A-Boost Compact Domestic Booster Sets
Pent-A-Boost Compact Domestic Booster Sets Model BTAF With Integral Automatic Bypass Valve - Overview Datasheet Page 1 of 8 Overview Compact booster pump set designed to boost pressure for tall buildings
More informationTWINFLOW STDR Product Brochure
TWINFLOW STDR Brochure Available for next day delivery with ELTA SELECT Direct Drive Twin Centrifugal Fan For full detailed information on the following: Sound Data, Accessories & Wiring Data and Optimum
More informationModular Acoustic Enclosures
Modular Acoustic Enclosures 225 375 kva Range www.fgwilson.com The innovative and functional design of the 225 375 kva range enclosures ensures performance in the harshest of environments. Extremely durable
More information2.6. Air Flow Control Valve Type PRD
2.6. Air Flow Control Valve Type PRD Page 1/10 Air Flow Control Valve, Type PRD Page 2/10 Air Flow Control Valve Type PRD Description and Design The PRD remains the air valve of choice for critical heating,
More informationSilencers. Transmission and Insertion Loss
Silencers Practical silencers are complex devices, which operate reducing pressure oscillations before they reach the atmosphere, producing the minimum possible loss of engine performance. However they
More informationInnovation in. Mechanical Motion & Vibration Controls
Innovation in Mechanical Motion & Vibration Controls ACE Controls Inc. located in Farmington Hills, Michigan, is a leading innovator in deceleration, vibration and motion control technology. For over a
More informationNCF 60 Hz. Protection class IP 55
The Nederman NCF Fans have direct drive motors which means a safe and cost effective operation. Installing an energy efficient NCF fan with our other Nederman products saves time and reduces energy costs.
More informationNEW. Iris Control Damper (ICD) For adjustment and measuring of airflow. Features. Quick and simple installation and maintenance
March 29 Iris Control Damper (ICD) NEW Iris Control Damper (ICD) For adjustment and measuring of airflow Features Quick and simple installation and maintenance Extended spigot connections 1% opening capacity
More informationIrisControlDamper. For Adjustment and Measuring of Airflow.
IrisControlDamper For Adjustment and Measuring of Airflow www.actionair.co.uk sales@actionair.co.uk Iris Control Damper (ICD) Quick, silent and efficient is the simple summary of the features of the Actionair
More informationTURBO PRESSURE BLOWERS
Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS TURBO PRESSURE BLOWERS TBA TBR CATALOG 10 APRIL 13 TURBO PRESSURE BLOWERS Models TBA TBR TBR Arrangement 8 Model TBA and TBR fans from
More informationHIGH PRESSURE SOLUTIONS. Oil-Free Compressors for PET Bottle Blowing
HIGH SOLUTIONS Oil-Free Compressors for PET Bottle Blowing GARDNER DENVER HIGH SOLUTIONS Gardner Denver High Pressure Compressors With the GD Compressors brands, we have grown into one of the world s most
More informationCAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1
X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical
More informationCP3650 Series CP AB & CP AB Angle Sanders
32 CP3650-20AB CP3650-075AB rpm CP3650-20AB 2000 CP3650-075AB 7500 Index No. Parts No. Description Qty Index No. Parts No. Description Qty 653967390 Adaptater 6 654300330 Inlet 7 656452290 Disc Spring
More informationSITRANS AS 100. Instruction Manual September 2001 ITRANS AS 100
SITRANS AS 100 Instruction Manual September 2001 ITRANS AS 100 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the
More informationPlanning Manual Beauty Angel CVT 32. Beauty Angel CVT 32. Contents
Planning Manual offers an innovative light treatment for photo-bio stimulation of the skin. The application of red light promotes the formation of collagen and elastin. The short-term effect shows itself
More informationVANEAXIAL FANS. DUCT FANS Capacities to 60,000 CFM Static pressures to 2 WG. TUBEAXIAL FANS Capacities to 86,000 CFM Static pressures to 3 WG
BULLETIN 671 AUGUST, 2016 VANEAXIAL FANS DUCT FANS Capacities to 60,000 Static pressures to 2 WG TUBEAXIAL FANS Capacities to 86,000 Static pressures to 3 WG Capacities to 0,000 Static pressures to 5 WG
More informationMinimizing Noise. Marybeth G. Nored Dr. Klaus Brun Eugene Buddy Broerman Augusto Garcia Hernandez Dennis Tweten. Southwest Research Institute
Minimizing Noise Marybeth G. Nored Dr. Klaus Brun Eugene Buddy Broerman Augusto Garcia Hernandez Dennis Tweten Southwest Research Institute Gas Electric Partnership Workshop September 9, 2010 Photo courtesy
More informationPROMO CODE PRODUCT DESCRIPTION PRODUCT CODE QTY TRADE VALUE
February 2017 Affinity All Purpose Stopper Pack 8.99 The universal all-purpose polyester stopper is very easy to spread, easy to sand and has excellent adhesion to all substrates. The Bodyline mixing board
More informationJM Aerofoil Multi-Stage 50 Hz
JM Aerofoil Multi-Stage 5 Hz JM AEROFOIL - MULTI-STAGE CONTENTS Page: JM Aerofoil Multi-Stage - Introduction -5 Multi-Staging Motor Frame Size Schedules - Three Phase 7-8 Performance Curves SK1- SK135
More informationWhy 24v? Case Handling. Pallet Handling. Accessories. Motor Driven Roller. Flat Motor Driven Roller Conveyor. Conveyor
Why 24v? Power savings: Since it is run on demand (meaning when a package or part is not present in a zone the zone shuts down) a 24V system uses very little power. Some studies suggest a 40-80% power
More informationCONSTANTFLOW Volume Flow Controllers
5/9.1/EN/8 CONSTANTFLOW Volume Flow Controllers for constant volume systems Type EN The art of handling air Contents Description Description 2 Application 3 Construction Dimensions Accessories 4 Dimensions
More informationPlanning Manual Ergoline Esprit 770-S. Ergoline Esprit 770-S. Dynamic Power Dynamic Power Climatronic. Contents
Planning Manual EN 60335-2-27:2003+A1:2009 Ultra Performance Plus-Technology combines face tanning units with UV-B optimized Spaghetti lamps. This ensures maximum, standardized tanning intensity as well
More informationVARYCONTROL VAV Dual Duct Terminal Boxes
5/2/B/3 VARYCONTROL VAV Dual Duct Terminal Boxes for variable volume systems Type TVM Trox (U.K.) Ltd Caxton Way GB-Thetford Norfolk IP24 3SQ Telephone +44 (0)1842 754545 Telefax +44 (0)1842 7051 www.troxuk.co.uk
More informationAFA TS GmbH - Werner von Siemens Str.3 - D Grafenberg Copyright 2009 Tel.: +49(0) Fax: +49(0)
AFA TS GmbH - Werner von Siemens Str.3 - D-72661 Grafenberg Copyright 2009 Tel.: +49(0)7123-97382-0 - Fax: +49(0)7123-97382-90 - E-Mail: mail@afa-ts.de Page 1-15 www.afa-ts.com Exhaust Extraction Systems
More informationHigh Performance Axial Fans
High Performance Axial Fans Model RA Standard and High Temperature High Efficiencies Low Sound January 2014 High Performance Axial Fans Greenheck s model RA, high performance, direct-driven axial fans,
More informationSF-Plus Blower and vacuum systems
Silent Flow Plus SF-Plus Blower and vacuum systems Silent Flow Plus range : The Silent Flow Plus range is made up of a group of rotary lobe blowers designed to circulate air or neutral gases in a non-hazardous
More informationPowerful Design For Tough Applications
Powerful Design For Tough Applications Conair's Viper Granulator 17-Series granulators are versatile, rugged and designed for central or machine-side recycling of tough, injection molded parts; bulky blow-molded
More informationUltra-quiet circular duct fans TD-SILENT ECOWATT Series
TD-SILENT ECOWATT - MODELS 5 to TD-SILENT ECOWATT - MODELS AND At 5% of full speed fan power consumption is reduced by 7% Low profile Mixed-flow fans with sound-absorbent insulation, extremely quiet, fan
More informationVent-Axia Roof Units Range Energy Recovery Ventilation (ERV) Range
CI/SfB (57.7) 1st Edition from Vent-Axia Vent-Axia Roof Units Range Energy Recovery Ventilation (ERV) Range Energy Recovery Ventilation (ERV) Range Building on the success of the Sentinel Totus 2 range
More informationSwegon PACIFIC. Integrated climate beam
Swegon Integrated climate beam www.eurovent-certification.com www.certiflash.com climate beam The is a high performance climate beam for installation in false ceilings. With high built-in flexibility,
More informationC O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CE SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR SLOT DIFFUSERS CE SERIES CE SERIES LINEAR SLOT DIFFUSERS CE SERIES QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application Colman
More information02. Purpose : Heating / Drying / Calcination etc. 04. Feeder System : 0.5 H.P. Motorized Screw Feeder with VFD.
I EQUIPMENT : GAS/OIL FIRED INDIRECTLY HEATED ROTARY REACTOR. Technical Data : 01. Type : Indirectly heated. 02. Purpose : Heating / Drying / Calcination etc. 03. Feed Size : 0 25mm. 04. Feeder System
More informationPassenger Vehicle Interior Noise Reduction by Laminated Side Glass. Abstract
The 22 International Congress and Exposition on Noise Control Engineering Dearborn, MI, USA. August 19-21, 22 Passenger Vehicle Interior Noise Reduction by Laminated Side Glass Jun Lu Solutia Inc. 73 Worcester
More informationSound attenuators, Sound attenuating louvres
, Sound attenuating louvres 09 Sound attenuating louvres 334 , Sound attenuating louvres SLOT DIFFUSERS, ROUND DUCT DIFFUSERS SWIRL DIFFUSERS, VARIABLE SWIRL DIFFUSERS CIRCULAR DIFFUSERS, SQUARE DIFFUSERS
More informationHigh Capacity Ventilation
High Capacity Ventilation DECEMBER 2012 Broan high capacity fans are an exceptionally quiet solution to continuous ventilation. With their heavy-duty motors, high capacity fans are an ideal solution for
More informationReciprocating Compressors AIRBOX / AIRBOX CENTER
www.kaeser.com Reciprocating Compressors AIRBOX / delivery. to.9 m³/min, Pressure. bar What do users expect from a reciprocating compressor? Answer: They expect maximum efficiency and reliability. This
More informationAcoustic Door Closer Instructions
Acoustic Door Closer Instructions 1 Contents Contents... 2 Introduction... 3 Contents of Box... 4 Contents of Door Closer Arm Box... 4 Contents of Accessories Box... 5 Tools Required... 5 Fitting the Door
More informationPneumatic Conveying Systems. Division of
Pneumatic Conveying Systems Division of You can expect from FOX TrimAway: lower first cost, lower operative cost and less noise. Typical Applications Paper, film and foil trim/waste Textiles and non-wovens
More informationS ACON SEACON SEACO QUIPMEN EQUIPMENTS SEACON EQUIPMENTS
S ACON EQ NTS ACON E NTS A S EQ A TS TS TS TS TS E AC AC AC AC AC AC S S UIP IPME IPME QU P QUI QUI EQ EQUI Q EQ EQ EQ EQ EN EN SE SE SEAC AC AC AC AC AC AC ACO EQUIP E MEN SEACO EQUIPMEN A EQU EQU AC
More informationSound science: Understanding AND
TECHNICAL article Sound science: Understanding AND IMPLEMENTING Generator set noise control The principles of generator set noise control are well understood, leaving economics as the primary limiting
More informationSINGLE DUCT TERMINAL UNITS 30X/HQX SERIES
30X/HQX SERIES 30X SERIES EXHUST 30HQX SERIES EXHUST HOSPITL GRDE QUIET TYPE WITH DISSIPTIVE SILENCER PRODUCT OVERVIEW Nailor Single Duct Exhaust Terminal Units are used to modulate exhaust flow from an
More informationWhen Time Matters! listed Fire Damper
listed Fire Damper The FAST fire damper is offered as an option for containing fire and smoke under the hood in the event of a fire from a cooking appliance. Construction : The fire damper is assembled
More informationRoof Units. Specification. Construction. Performance. Impellers. Size range. Ancillary Equipment
Roof Extract Units Roof Units Specification The Flaktwoods Colchester range of roof extract units are designed to satisfy the consultants functional requirement for a direct drive fan unit of guaranteed
More informationSynJet MR16 LED Cooler with Heat Sink
PRODUCT SynJet MR16 LED Cooler with Heat Sink Design Guide Version 1.1 June 2009 Version History Document Name: SynJet MR16 LED Cooler with Heat Sink Design Guide Document Number: MKTG-DOC-00029 Version
More informationThe Industrial Choice. Model VB Direct Drive. Model VBBD Belt Driven VANEAXIAL FANS. Direct Drive & Belt Driven Model VB / VBBD
The Industrial Choice. Model VB Direct Drive Model VBBD Belt Driven VANEAXIAL FANS Direct Drive & Belt Driven Model VB / VBBD BULLETIN 466 November 2000 Contents Construction Features Belt Driven... 3
More informationSEASONAL MAINTENANCE CHECKLISTS Johnson Controls
SPRING CHECK LIST ABSORPTION CHILLERS Check starter and control panel. Leak test. Check hand valve diaphragms and replace as required. Check operation of purge unit. Change oil in the purge pump. Lubricate
More informationProf. João Melo de Sousa Instituto Superior Técnico Aerospace & Applied Mechanics. Part B Acoustic Emissions 4 Airplane Noise Sources
Prof. João Melo de Sousa Instituto Superior Técnico Aerospace & Applied Mechanics Part B Acoustic Emissions 4 Airplane Noise Sources The primary source of noise from an airplane is its propulsion system.
More informationVAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1
X X testregistrierung VAV terminal units Type Easy controller Compact controller Rectangular connection on the room end Circular connection on the fan end For supply air systems with demanding acoustic
More informationSlot diffusers, Round duct diffusers. IMP Klima
, Round duct diffusers 04 Round duct diffusers 176 , Round duct diffusers SLOT DIFFUSERS, ROUND DUCT DIFFUSERS SWIRL DIFFUSERS, VARIABLE SWIRL DIFFUSERS CIRCULAR DIFFUSERS, SQUARE DIFFUSERS VENTILATING
More informationIJESRT. (I2OR), Publication Impact Factor: 3.785
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW ON A NOISE REDUCTION SYSTEM IN IC ENGINE Rajendra Kumar Kaushik*, Prakash Kumar Sen, Gopal Sahu *Student, Mechanical
More informationAIR VENT T E C H N O L O G Y. infinity. energy efficient - environmentally friendly - economical EC MOTORS - direct drive - CuSTOM built ErP Compliant
infinity AIR VENT T E C H N O L O G Y energy efficient - environmentally friendly - economical EC MOTORS - direct drive - CuSTOM built ErP Compliant INDEX Selection Chart Page 3 Internal & External Acoustic
More informationCentrifugal Cabinet Fans Model BCF Belt Drive Low-Profile
Centrifugal Cabinet s BCF Belt Drive Low-Profile May 2007 BCF Belt Drive Cabinet s Greenheck belt drive low-profile cabinet fans, BCF, are designed for efficiency and reliability in supply, exhaust or
More informationACOUSTIC CABINET FANS CVB / CVT Series
Cabinet fans manufactured from heavy gauge galvanised steel sheet and internally lined with melamine foam flame retardant acoustic insulation (M1). All models incorporate double inlet single phase direct-drive
More information50H Z VERSION. WindJet Air Knife Packages. Deliver superior blowing and drying performance in a complete, customizable package.
5H Z VERSION Experts in Spray Technology Spray Nozzles Spray Control Spray Analysis Spray Fabrication WindJet Air Knife Packages Deliver superior blowing and drying performance in a complete, customizable
More informationAXUS HIGH TEMPERATURE AXIAL FANS
WIDE RANGE OF SMOKE EXTRACT FANS FOR HIGH TEMPERATURE APPLICATIONS. 342 029 2085 8 BENEFITS TRIED & TESTED Nuaire s high temperature fans have been tested in accordance with the latest legislation and
More informationMounting hardware and accessories
Mounting hardware and accessories Mounting considerations Surface Wilcoxon s rugged sensors are designed to operate continuously in harsh industrial environments. Consideration of mounting surface and
More informationC O L M A N. Air Distribution LINEAR BAR GRILLES T SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR BAR GRILLES T SERIES T SERIES C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR BAR GRILLES T SERIES
More information